Fluke 1750

Three-Phase Power Recorder

Never miss capturing a disturbance—with the exclusive threshold-free measurement system, it’s automatic.

Capture every measurement, every event, on every cycle, all the time with the Fluke

1750 Power Recorder. Outstanding accuracy and resolution provide complete visibility into your installation or distribution system.

Power quality that meets the standard:

All measurements comply with IEC61000-4-30 standards for correct evaluation of all measured values including voltage, current, power, harmonics, fl icker etc.

Quick and reliable confi guration: PDA wireless “front panel interface” provides the ability to verify setup without a laptop along with a window into what the instrument is recording, even in awkward test locations.

Threshold-free setup: Apply thresholds after data is collected with Fluke Power Analyze

Software so there is no need to worry about missed information due to incorrect set-up.

Captures everything: Cross-channel and current triggering capture every measurement, on every channel, every time.

Intuitive PC software: Easily analyze data and generate reports. Automated EN50160 reporting and compliance.

Plug and play: Set up in minutes with selfidentifying current probes and single-lead voltage connections.

No need to reconnect wires: Swap channels internally with the wireless PDA or PC when connections are not correct.

Measure every parameter: voltage and current on three phases, neutral, and ground.

5 MHz, 8000 Vpk waveform capture: Get a detailed picture of even the shortest events.

Quickly retrieve data: With included SD memory card or via the 100BaseT high-speed Ethernet connection.

Applications

Long-term analysis: Uncover hard-to-fi nd or intermittent issues; monitor critical equipment, capturing power quality events to correlate with equipment malfunction

Power quality surveys: Quantify power quality throughout a facility, documenting results with professional reports

Quality of service compliance: Validate incoming power quality at the service entrance

Equipment Installation/Commissioning: Benchmark power system prior to install to insure quality of service

Easy to use

The recorder automatically detects, scales, and powers current probes without needing batteries.

Requiring only single-lead voltage connections enables safe and quick setups. Once power is applied the instrument automatically begins recording and LEDs give you assurance that the recorder is powered up and signals are within range – no more uncertainty that data is being recorded. The

Fluke 1750 has an exclusive capture algorithm which makes certain all events are captured without the tedious setups and blind spots associated with threshold driven equipment.

The PDA wirelessly interfaces with the recorder, allowing quick setup and verifi cation with waveform displays, meter screens, and phasor diagrams.

The built-in wireless technology allows you to control multiple instruments from a distance easily, without the need for a laptop computer (laptops can also be used when desired).

View measurements real-time with wireless PDA interface.

Configurations are simple with wiring diagrams to guide you.

2 Fluke Corporation Fluke 1750 Three-Phase Power Recorder

No need to reconnect wires—swap channels internally using the PDA interface.

Comprehensive power system data

Every cycle on every channel is simultaneously sampled providing complete analysis of power quality, harmonics, power and energy. Crosschannel current and voltage triggering captures event data on all input channels simultaneously, no matter which channel triggered the event. When periodic analysis of the waveform may be needed, the Snapshot mode captures waveforms at userdefi ned intervals. Even dc signals can be recorded!

Events can be displayed against a variety of tolerance curves.

Full FFT on each channel to the 50th harmonic.

Display multiple parameters simultaneously on one graph.

Full-featured power meter display for each channel and totals.

Thresholds for the EN50160 report are easily customized.

Powerful data management

Data is automatically stored on the internal fl ash memory that can store records for over a month without compression or overwriting. Data is retrieved via one of two quick and easy options: download the data onto the included SD memory

EN50160 report delivers an easy to read pass or fail chart along with drill down data.

card without using your laptop, or transfer directly to your computer via Ethernet, using TCP/IP protocol.

Voice, data, and picture annotations can be made via the PDA to fl ag important points in the data stream. Imagine being able to fl ag in your recorded data when a transfer switch was operated, or load changes were made.

3 Fluke Corporation Fluke 1750 Three-Phase Power Recorder

View data the way you want

The new Fluke Power Analyze software revolutionizes your ability to analyze data. No need to worry about thresholds—with Fluke Power Analyze, thresholds can be modifi ed after the data is recorded! And the easy-to-use user interface will display voltage as a phase-to-phase or phase-toneutral reading.

Apply thresholds to data after collection using a variety of standard or customized templates.

Simplified report writer feature included in Fluke Power

Analyze.

All the latest power quality standards are built-in

IEC 61000-4-30 compliant measurement systems provide the confi dence that all parameters are measured and calculated consistently with international standards.

Automated EN50160 compliance reporting for rapid Pass/

Fail testing.

600 V CAT IV and

1000 V CAT III safety rating

Designed to help protect you and your equipment, the Fluke 1750 Three-Phase Power Recorder and accessories are all certifi ed to meet the stringent safety standards for use in 600 V CAT IV and 1000 V CAT III environments. They are the fi rst tools of their kind to carry the

CAT IV rating and, therefore, can be used for most power connections and for all outlets in a low-voltage power distribution system.

4 Fluke Corporation Fluke 1750 Three-Phase Power Recorder

Optional Accessories

Fluke power quality current transformers and fl exible current probes are specially designed to work seamlessly with Fluke power monitors (1750 and 1650).

All clamp-on and fl exi-CT’s are matched to take full advantage of your instrument’s ability to set scale factors for accurate readings.

Cases

1750/CASE Transit Case

• Rugged water tight transit case with rollers

Miscellaneous

1750/MC

Additional SD Memory Card for Fluke 1750

1750/SEAT-L

Fluke Power Analyze –

Additional SEAT LICENSE

• One additional license for installation on one additional

PC

1750/SITE-L

Fluke Power Analyze -

Additional SITE LICENSE

• Site license for installation on unlimited PCs

4006 Security Cable

• 1.8 m (6 ft) looped lockable steel cable for securing monitor

Model No.

CT Type

3005-PR Clamp-On

3014-PR

3140R

Clamp-On

Clamp-On

Model No.

CT Type

3110-PR Flexi-CT

3210-PR

3310-PR

3312-PR

Flexi-CT

Flexi-CT

Flexi-CT

Current Range

0.01 A to 5 A

0.1 A to 40 A

2 A to 400 A

Accuracy

Frequency

Response

1 % RDG ± 0.5 % FS 5 kHz

Jaw Opening

2 cm (.78 in) dia.

1 % RDG ± 0.1 % FS 5 kHz

2 % RDG ± 0.04 A 20 kHz

2 cm (.78 in) dia.

3.2 cm (1.25 in) dia.

Current Range

2 A to 100 A

20 A to 1000 A

Accuracy

1 % rdg ± 0.5 % FS

1 % rdg ± 0.15 % FS

Frequency

Response

7 kHz

7 kHz

100 A to 5000 A 1 % rdg ± 0.15 % FS 7 kHz

Probe Length

60 cm (24 in)

60 cm (24 in)

60 cm (24 in)

100 A to 5000 A 1 % rdg ± 0.15 % FS 7 kHz 120 cm (48 in)

5 Fluke Corporation Fluke 1750 Three-Phase Power Recorder

Specifi cations for the System:

Recorder and Power Analyze Software

General

Power quality measurement standards

Conformance

Clock/calendar

Real-time clock accuracy

Internal memory capacity for data

Maximum recording period

Measurement time control

Maximum number of events

Power requirements

Operating time during interruptions

(internal UPS operation)

Dimensions

Mass (weight)

IEC 61999-1-4 Class 1, IEC 61000-4-30, IEEE519, IEEE1159, IEEE1459 and EN50160

Leap years, 24-hour clock

Not more than ± 1 s/day

At least 2 GB

At least 31 days

Automatic

Limited only by the size of the internal memory

100 to 240 V rms ± 10 %, 47-63 Hz, 40 W

5 minutes per interruption, 60 minutes total operating time without recharging

215 mm x 310 mm x 35 mm (8.5 in x 12.2 in x 3.5 in)

6.3 kg (14 lb)

Input

Measurement types

Input channels

Voltage channels

Current input characteristics

Measuring method

One Phase Plus Neutral, One Phase IT No Neutral, One Phase Split Phase, Three Phase Wye,

Three Phase Delta, Three Phase IT, Three Phase High Leg, Three Phase Open Leg, 2 Element Delta,

2 1 /

2

Element Wye

Voltage: 4 channels, ac/dc

Current: 5 channels

Input resistance: 2 MΩ

Input capacitance: < 20 pF

2 V rms = full scale, 1 MΩ Input Impedance for ferro CTs, low impedance for Flexi-CTs

Simultaneous digital sampling of voltage and current. Digital PLL synchronized sampling, internal frequency reference used during voltage drops.

Synchronization and sampling

PLL-synchronization source

PLL lock range

Sampling frequency

A/D resolution

The PLL synchronizes to the A-N voltage for wye power types, and to the A-B voltage for delta power types. All listed power types can be characterized as either wye or delta.

42.5 to 69 Hz

Voltage and current: 256 samples/cycle

Inter-harmonics per IEC 61000-4-7: 2560 points/10 cycles (50 Hz),

3072 points/12 cycles (60 Hz)

Transient Voltage: 5 MHz

Voltage and current: 24 bits

Transient voltage: 14 bits

Voltage and current measurements

Voltage measurement range

Voltage crest factor

Current measurement range

Current crest factor

AC voltage: 1000 V rms ± 10 % over range

DC voltage: ± 1000 V + 10 % over range

3 or less

Depends on current probe used

4 or less

Voltage and current measurement accuracy

RMS voltage

Measurement type

Measurement uncertainty

True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by IEC 61000-4-30.

AC: ± 0.2 % reading ± 0.1 % full scale, above 50 V rms

DC: ± 0.5 % reading ± 0.2 % full scale, above 50 V dc

RMS current

Measurement type

Measurement uncertainty

True rms calculated continuously: every cycle, every 1/2 cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards

Ferromagnetic Clamps: ± (0.1 % full scale + 0.2 % reading + current sensor accuracy), valid for 5 % to 100 % of current sensor range

Flexible Current Probes: ± (0.1 % full scale + 0.5 % reading + current sensor accuracy), valid for 5 % to 100 % of current sensor range

6 Fluke Corporation Fluke 1750 Three-Phase Power Recorder

Transient voltage (impulse)

Measurement type

Full scale

Sample resolution

Measurement uncertainty

Waveshape sampling

8000 V pk

200 nS

± 5 % reading ± 20 V (test parameters: 1000 V dc, 1000 V rms, 100 kHz)

Dip (Sag) and Swell Measurements

Voltage swell (rms swell)

Measurement type

Displayed data

Measurement uncertainty

Voltage dip (rms sag)

Measurement type

True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)

Amplitude and duration of swell

Same as rms voltage

Displayed data

Measurement uncertainty

Voltage dropout (interruption)

Measurement type

True rms (one cycle calculation by overlapping each half cycle - voltage between lines is measured for 3P3W lines and phase voltage is measured for 3P4W lines)

Amplitude and duration of dip or interruption

Same as rms voltage

Same as voltage dip

Power Measurements

Calculated per IEEE1459 for best performance when distortion is present

Measurement type

Measurement accuracy

True rms calculated continuously: every cycle, and every 10 or 12 cycles at 50 or 60 Hz respectively, as required by standards

+/- (voltage uncertainty + current uncertainty + current probe uncertainty)

Frequency

Measurement range

Measurement source

Measurement accuracy

Power factor

Measurement range

Measurement accuracy

Displacement power factor

42.5 to 69 Hz

Same as PLL synchronization source

± 10 mHz (10 to 110 % of range, with sine wave)

0.000 to 1.000

± 1 digit from the calculation of each measured value (±3 digits for total)

Measurement method

Measurement range

Measurement accuracy

Calculated from the phase difference between voltage fundamental and current fundamental

- 1.000 (leading) to + 1.000 (lagging)

± 0.5 % reading ± 2 % full scale ± 1 digit

Voltage unbalance and phase sequence

Measurement method Positive sequence voltage divided by negative sequence voltage, per IEC 61000-4-30

Harmonic voltage and current

Analysis window

Analysis order

Measurement accuracy rectangular

1st to 50th order

Measurement method

Voltage / Current: 1st to 20th orders: ± 0.5 % reading ± 0.2 % full scale, 21st to 50th orders: ± 1 % reading ± 0.3 % full scale (current sensor accuracy must be included for current and power)

IEC 61000-4-7

Inter-harmonic voltage and current (intermediate harmonics)

Analysis window

Analysis orders

Measurement method

Voltage fl icker

Measurement method rectangular

1.5 to 49.5th order

IEC 61000-4-7 as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)

7 Fluke Corporation Fluke 1750 Three-Phase Power Recorder

External Interface Specifi cations

LAN interface

Connector

Speed and type

Communications protocol

Wireless controller interface

Connection

Speed

Communications protocol

RJ-45

10/100 Base-T, auto MDIX

TCP/IP over Ethernet wireless (2.4 GHz radio) up to 700 kbit/second

Bluetooth SPP

Environmental and safety specifi cations

Operating environment

Storage temperature and humidity

Operating temperature and humidity

Maximum rated working voltage

Voltage terminals

Voltage durability

Indoors or in covered area outdoors, up to 2000 m altitude (for compliance to IEC61010 standard)

-20 °C to 50 °C, 80 % RH max, non-condensing

0 °C to 40 °C, 80 % RH max, non-condensing

1100 V rms

5550 V rms ac for 1 minute, between voltage input terminals, voltage input terminals and current probes, and voltage input terminals and case (50/60 Hz, 1 mA sense current)

IP30 (per EN 60529) Enclosure protection

Standards conformance

EMC

Safety

EN 61326-1:1997+A1:1998 Class A

EN 61000-3-2:1995+A1:1998+A2:1998

EN 61000-3-3:1995

EN 61010-1 2nd Edition; 2000

Voltage input unit: Contamination Level 2, Overvoltage Category 1000 V CAT III, 600 V CAT IV

(anticipated overvoltage: 8000 V)

Ordering information

Fluke 1750 Three-Phase Power

Recorder

Includes:

1750 acquisition unit

• PDA wireless “front panel interface” and charger power plug adapters

4 - 400 A current probes (3140R)

5 test leads and clips

SD memory card

Fluke Power View and Fluke Power

Analyze software

• Power cord with international plug set

Ethernet cable

Color localization set

• Printed Getting Started manual

• Product CD with software and users manual PDF

Soft carrying case

Fluke 1750/B Three-Phase Basic Power Recorder

Includes items above with the exception of the

4 - 400 A current probes (3140R)

8 Fluke Corporation Fluke 1750 Three-Phase Power Recorder

Fluke offers a full suite of power quality test tools to locate, predict, prevent and troubleshoot power problems.

Handheld troubleshooters for instant analysis

• Ready-to-use power loggers

• Comprehensive power quality recorders

Power calibrators and standards backed by Fluke metrology expertise

The Fluke power quality set of products offers the highest level of performance and maintains the Fluke promise of rugged and reliable test tools.

Fluke. Keeping your world up and running.

®

Fluke Corporation

PO Box 9090, Everett, WA 98206 U.S.A.

Fluke Europe B.V.

PO Box 1186, 5602 BD

Eindhoven, The Netherlands

For more information call:

In the U.S.A. (800) 443-5853 or

Fax (425) 446-5116

In Europe/M-East/Africa +31 (0) 40 2675 200 or

Fax +31 (0) 40 2675 222

In Canada (800)-36-FLUKE or

Fax (905) 890-6866

From other countries +1 (425) 446-5500 or

Fax +1 (425) 446-5116

Web access: http://www.fluke.com

©2006-2009 Fluke Corporation. Windows ® is a registered trademark of Microsoft Corporation.

Specifi cations subject to change without notice.

Printed in U.S.A. 10/2009 2428201F D-EN-N

Modification of this document is not permitted without written permission from Fluke Corporation.

Pub-ID 11578-eng

Mouser Electronics

Authorized Distributor

Click to View Pricing, Inventory, Delivery & Lifecycle Information:

Fluke

:

FLUKE-1750 FLUKE-1750/CASE FLUKE-1750/SITE-L FLUKE-1750/B FLUKE-1750/MC2GB

advertisement