- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Sharp
- AE-X 9PSR
- Service manual
- 73 Pages
SHARP AY-X 9PSR, 12PSR, AE-X 9PSR, 12PSR split-system air conditioner Service Manual
AY-X9PSR, AY-X12PSR, AE-X9PSR and AE-X12PSR are split-system air conditioners that offer a variety of features to keep your home cool and comfortable. It features a microcomputer control system for precise temperature control and a range of safety features for peace of mind. With a variety of operating modes and settings, you can customize your comfort to meet your needs.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
73
AY-X9PSR SERVICE MANUAL SC213AYX9PSR/C MODELS SPLIT TYPE ROOM AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT MODELS AY-X9PSR AE-X9PSR AE-X12PSR AY-X12PSR In the interests of user-safety (Required by safety regulations in some countries) the set should be restored to its original condition and only parts identical to those specified should be used. CONTENTS [5] CHAPTER 1. SPECIFICATION [1] SPECIFICATION ...........................................1-1 [2] EXTERNAL DIMENSION ..............................1-2 [3] WIRING DIAGRM..........................................1-3 [4] ELECTRICAL PARTS....................................1-4 CHAPTER 2. EXPLANATION OF CIRCUIT AND OPERATION [1] BLOCK DIAGRAMS ......................................2-1 [2] MICROCOMPUTER CONTROL SYSTEM ........2-3 [3] FUNCTION ..................................................2-18 CHAPTER 3. FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES [1] PROTECTION DEVICE FUNCTIONS AND OPERATIONS ...............................................3-1 [2] AIR CONDITIONER OPERATION IN THERMISTOR ERROR.................................3-2 [3] THERMISTOR TEMPERATURE CHARACTERISTICS...............................................3-3 [4] GENERAL TROUBLESHOOTING CHART....3-6 [6] [7] MALFUNCTION (PARTS) CHECK METHOD..................................................................3-8 CHART .........................................................3-10 TROUBLE SHOOTING GUIDE ................... 3-11 CHAPTER 4. REFRIGERATION CYCLE [1] SCHEMATIC DIAGRAM ................................ 4-1 [2] STANDARD CONDITION .............................. 4-1 [3] TEMPERATURE AT EACH PART AND PRESSURE IN 3-WAY VALVE....................... 4-2 [4] PERFORMANCE CURVES ........................... 4-2 CHAPTER 5. DISASSEMBLY PROCEDURE [1] INDOOR UNIT ............................................... 5-1 [2] OUTDOOR UNIT ........................................... 5-4 [3] CONTROL BOX............................................. 5-7 CHAPTER 6. OPERATION MANUAL CHAPTER 7. INSTALLATION MANUAL PARTS LIST Parts marked with " " are important for maintaining the safety of the set. Be sure to replace these parts with specified ones for maintaining the safety and performance of the set. This document has been published to be used for after sales service only. The contents are subject to change without notice. SHARP(CHINA)INVESTMENT CO.,LTD CHAPTER 1. PRODUCT SPECIFICATION [1] SPECIFICATION 1. AY-X9PSR/AY-X12PSR MODEL INDOOR UNIT OUTDOOR UNIT AY-X9PSR ITEMS AE-X9PSR INDOOR UNIT OUTDOOR UNIT AY-X12PSR AE-X12PSR Rated cooling capacity(Min-Max) kW 2.6(1.00-3.10) 3.5(1.1-3.7) Rated heating capacity(Min-Max) kW 2.6(1.0-3.80) 3.5(1.1-4.5) Moisture removal(at cooling) Liters/h 0.8 1.0 Single Single 50 50 Electrical date Phase Rated frequency Hz V 220-240 220-240 Cool A 3.5(1.32-5.0) 4.9(1.32-6.1) Heat A 3.1(1.32-6.4) 4.6(1.32-7.8) Cool W 760(290-1100) 1060(290-1330) Heat W 680(290-1400) 1010(290-1700) Cool % 94 94 Rated voltage Rated current(Min-Max) Rated input(Min-Max) Power factor Heat Maximum operating current Compressor % 95 95 A 6.4 7.8 Hermetically sealed ROTARY TYPE Hermetically sealed ROTARY TYPE Type Refrigerant system Model DA89M1C-81EZ8 DA108M1C-81EZ8 Oil charge 370ml˄ESTER OIL VG74˅ 370ml˄ESTER OIL VG74˅ Evaporator Louver fin and grooved tube type Louver fin and grooved tube type Condenser Louver fin and grooved tube type Louver fin and grooved tube type Control Microcomputer controlled reverse system Microcomputer controlled reverse system Refrigerant(R410A) 750 950 Microcomputer controlled reverse system Microcomputer controlled reverse system De-Ice system Noise Level(at cooling) High dB(A) 38 60 38 Low dB(A) 34 34 Soft dB(A) 26 26 62 Fan system Drive Direct drive Direct drive Air flow quantity(at cooling) High m3/min 11.0 Low m3/min 8.4 8.4 Soft m3/min 5.8 5.8 Fan 31.7 Cross flow fan Propeller fan 11.0 28.3 Cross flow fan Propeller fan Connections Refrigerant coupling Refrigenrant tube size Gas,Liquid Drain pipe Flare tpye Flare tpye inch 3/8",1/4" 1/2",1/4" mm O.D16 O.D16 Fan motor:thermal fuse Fan motor:thermal fuse Fuse,Micro compute control Fuse,Micro compute control Polypropylene net(washable) Polypropylene net(washable) Others Safety device Air filters Net dimensions Net/Gross weight Width mm 820 700 820 700 Height mm 280 256 280 256 Depth mm kg 183 551 183 551 10/12 24/28 10/12 26/30 1-1 [2] EXTERNAL DIMENSION INDOOR UNIT OUTDOOR UNIT 1-2 [3]WIREING DIAGRAM 1.AY-X9PSR/AY-X12PSR AE-X9PSR/AE-X12PSR © Indoor unit Outdoor unit 1-3 [4]ELECTRICAL PARTS 1.AY-X9PSR/AE-X9PSR Indoor unit DESCRIPTION Indoor fan motor Main PCB CODE REMARKS 1170030067 220V/50Hz 1090260049AA Display PCB 1090320292 Transformer 1170240024 220V/50/60Hzˈ12V Vane motor 1170020011 12V Indoor sensor 1170230001 5k CODE REMARKS Outdoor unit DESCRIPTION Power source board 210900163 Inverter module 210900026 Inductor 1171990046 5.0mHˈ10A outdoor fan motor 1170040126 220V/50Hz Discharge Temp. sensor 1170230006 2.1k Pipe Temp. sensor and outdoor Temp. sensor 1170230007 5k CODE REMARKS 1170030067 220V/50Hz 2.AY-X12PSR/AE-X12PSR Indoor unit DESCRIPTION Indoor fan motor Main PCB 1090260049AA Display PCB 1090320292 Transformer 1170240024 Vane motor 1170020011 12V Indoor sensor 1170230001 5k CODE REMARKS 220V/50/60Hzˈ12V Outdoor unit DESCRIPTION Power source board 210900168 Inverter module 210900026 Inductor 1171990046 5.0mHˈ10A outdoor fan motor 1170040126 220V/50Hz Discharge Temp. sensor 1170230006 2.1k Pipe Temp. sensor and outdoor Temp. sensor 1170230007 5k 1-4 SHARP(CHINA)INVESTMENT CO., LTD CHAPTER 2.EXPLAMATION OF CIRCUIT AND OPERATTION [1] BLOCK DIAGRAM 1. INDOOR UNIT Unit-unit wiring (AC power and serial signals)and serial Indoor/outdoor control signals) LED display board 3.15A fuse LED Display driver Overcurrent detection Zero-crossing detection Transformer Power Supply+15V DC+5V Reset circuit Anion driving circuit CPU Anion circuit Outdoor Power control Power on relay of outdoor unit of indoor Auxiliary driving circuit Auxiliary circuit control unit Fan speed detection Indoor fan drive circuit Indoor fan motor Buzzer drive circuit Buzzer LEV drive circuit LEV EEPROM Room Temp detection circuit Room temp thermistor IDU pipe temp detection circuit IDU pipe temp thermistor Model selection Model jumper 2-1 SHARP(CHINA)INVESTMENT CO., LTD 2. OUTDOOR UNIT LED Unit-unit wiring AC Zero-crossing Programmer port PFC CPU (AC power and PFC IGBT Driving Circuit serial signals)and serial signals) DC +5V2 Bus current detecting circuit 20A FUSE Filter PFC enable circuit Inrush current protection Crystal oscillator of LED Terminal of Compressor CPU Compressor over current detection circuit Compressor phase current detection circuit Of Module PFC Circuit IPM Module Bus capacitance Power supply +15V Power supply Board AC Voltage Detection Reset circuit DC +5V Programmer port Bus Voltage detection circuit COMM DC +5V LED Power on relay driving circuit Compressor selection AC detection circuit EERPOM Power Indoor/outdoor control signal CPU EEPROM circuit Of power Reset Circuit Crystal oscillator of board SPI Communication Exhaust Temp Detection ODU Ambient Function select (System Function select(self Temp Compressor shell Temp ODU pipe Temp 2-2 Fan driving circuit Fan circuit 4-way valve relay drive 4-way valve SHARP(CHINA)INVESTMENT CO., LTD [2] MICROCOMPUTER CONTROL SYSTEM 1. INDOOR UNIT 1.1. Electronic control circuit diagram AY-X9PSR/AY-X12PSR 2-3 SHARP(CHINA)INVESTMENT CO., LTD 2 AY-X9PSR/AY-X12PSR 2-4 SHARP(CHINA)INVESTMENT CO., LTD AY-X9PSR/AY-X12PSR 2-5 SHARP(CHINA)INVESTMENT CO., LTD AY-X9PSR/AY-X12PSR 2-6 SHARP(CHINA)INVESTMENT CO., LTD 1.2. Printed wiring board Indoor unit AY-X9PSR/AY-X12PSR 2-7 SHARP(CHINA)INVESTMENT CO., LTD 2. Outdoor unit 2.1. Electronic control circuit diagram inverter modul board 1 AE-X9PSR/AE-X12PSR 2-8 SHARP(CHINA)INVESTMENT CO., LTD AE-X9PSR/AE-X12PSR 2-9 SHARP(CHINA)INVESTMENT CO., LTD AE-X9PSR/AE-X12PSR 2-10 SHARP(CHINA)INVESTMENT CO., LTD AE-X9PSR/AE-X12PSR 2-11 SHARP(CHINA)INVESTMENT CO., LTD AE-X9PSR/AE-X12PSR 2-12 SHARP(CHINA)INVESTMENT CO., LTD POWER SUPPLY BOARD AE-X9PSR/EX-X12PSR 2-13 SHARP(CHINA)INVESTMENT CO., LTD AE-X9PSR/EX-X12PSR 2-14 SHARP(CHINA)INVESTMENT CO., LTD AE-X9PSR/EX-X12PSR 2-15 SHARP(CHINA)INVESTMENT CO., LTD 2.2 Printed wiring board Inverter module board AE-X9PSR/AE-X12PSR 2-16 SHARP(CHINA)INVESTMENT CO., LTD POWER SUPPLY BOARD AE-X9PSR/AE-X12PSR 2-17 SHARP(CHINA)INVESTMENT CO.,LTD [3] FUNCTION 1. Fuction 1.1. Compressor delay operate TheOnce the compressor stops operating, it will not restart for 3 minutes to protect the compressor . Therefore, if the operating compressor is shut down from the remote control and then turned back on immediately after, the compressor will restart after a preset delay time. z z z z Air flow direction Power ON/OFF Automatic operation mode setting Swing louvre 1.7.2. Setting not memorized z Timer setting 1.2. Four-way valve control in heating model When the unti operates in heating model, the comprassor start-up after the four-way valve start up for 5 seconds, the four-way valve shut down after the compressor stops for 2 minutes when the unit shut down 1.4.ON timer The ON timer can be activated by pressing the ON timer button.when the ON timer is activated, the operation start time is adjusted base on fuzzy logic calculations 1hour before the set time so that the room temperature reaches the set temperature at the set time. 1.7.3. Active auto restart and disabling auto restart function If the auto resart wasn’t actived,you can presse the ON/OFF switch and then supply the power and keep 10 seconds(the buzze sound 3 sounds) to actives it. Contrary, if the auto restart has actived, you can press the ON/OFF switch and then supply the power and keep until 4beeps sound to disable it. 1.8. FULL POWER Operation 1.5. OFF timer The OFF timer can be activated by pressing the OFF timer button. z When the OFF timer is set, the operation stops after the set time. z When the temperature is set during timer setting, the temperature will show in the display for 5 seconds and then return to the timer display. The airconditioner works at the maximum power to make the room cool or warm rapidly z The remote control will display ” “ button z The temperature display will go off. z The yellow FULL POWER lamp ” ” on. Timer duration can be set from a minimum half an hour to a maximum of12 hours. Up to 9.5 hours, you can set in half-hour increments, and from10 to 12 hours, in 1hour increments. TO CANCEL Press the FULL POWER button again. The yellow FULL POWER lamp ” ” on the unit will turn off NOTE z The airconditioner will operate at “Extra HIGH” fan speed for 5 minUtes, and then shift to “HIGH” fan speed. z You can not set the temperature or fan speed during the FULL POWER operation. 1.6. ON/OFF operation If the air conditioner is off, you can pressing the ON/OFF button to operates cooling or heating mode. Presses the ON/OFF button, when the buzzer sounds 1 short sound then enter cooling operation, 2 short sounds enter heating operation, 1 long sound shut down the unit. 1.9. compressor discharge overheat prevevtion control When the compressor discharge temperatureTP2(95ć), forbid the frequency raise until the discharge temperature is bellow than TP2 decrease 2ć. The unit operates in the set mode in the first 10 minutes of ON/OFF operation, in the first 10 minutes, the indoor fan speed operates on high speed, the vane swings, the compressor operates at maximum frequency F4. In cooling operation, the set temperature automatically 1ć lower than room temp., in heating mode the set temp. automatically 1ć higher than room temp., then the set temperature set at 23ć after 10 minutes, the maximum operating frequency is F7. When the discharge temperatureTP3(100ć), drop the operating frequency. If discharge temperature is over 105ć, then shut-down the compressor, outdoor fan motor stop after 15 seconds, when the discharge temperature˘TP2(95ć) and the compressor is stoped for 3 minutes, the unit operates again. 1.7.Auto restart 1.10. Voltage prevention Will automatically restart in the same setting whicth were active before the power failure. When the voltage AC 158V, the uint stops and displays the code P1 until the voltage AC162V , when the voltage AC265V and keeps 30 minutes, the unit stops and displays code P1 until the voltage AC 260V. 1.7.1. Operating mode at auto restart(Cool, Heat, Dry) z z z 1.11. Over current prevention Temperature adjustment (within 2°C range) automatic operation Temperature setting Fan setting ƽ when the outdoor currentIdrop frequency,the controller drops1Hz/second until the minimum operation frequency. 2-18 SHARP(CHINA)INVESTMENT CO.,LTD ƽwhen the unit enter drop frequency prevention opreates, if Idrop I outdoorInormal, the controller limit the operation frequency rise until Ioutdoor˘ Inormal. ƽ When the outdoor current Imax, the compressor stops and outdoor motor stops after 15 seconds about 33°C in order to prevent cold air from blowing into the room. Also, the indoor unit fan operates at low speed until the temperature ofthe indoor unit heat exchanger reaches about 37°C so that people inthe room will not feel chilly air flow. 37ć temperature temperature drop rise set fan speed 33ć low fan speed 1.12. Compressor drive prevention During the compressor start up or operation, if the signal of the compressor can’t be checked or check the load is exceptonal or driver fail then shut down the outdoor unit and displays the fail code. 25ć 34ć soft 28ć stop 22ć 1.13. Indoor unit evaporator freeze prevention 1.19. Auto restart When power failure occurs, after power is recovered, the unit will automatically restart in the same setting which auto restart function were active before the power failure, except for timer settings. When the indoor evaporator temperature IPT4ć and keeps 1 minutes, the uint enter the evaporator freeze prevention. If the indoor evaporate temperature IPT-1 ć and remains 5 minutes during cooling or dry operation, the compressor stops in order to prevent the freezer and displays code P5. When the indoor unit evaporator temperature IPT6ć, the compressor restarts and resumes normal operation. If a power failure ocurse while the timer is set, the timer setting will be cancelled and willl not be retrived even after the power is restored. 1.20. Defrosting 1.14. Outdoor unit overheat prevention Defrosting is controlled by the microprocessor. During cooling operation, if the temperature of the outdoor unit heat-exchanger OPTexceeds the limit frequency rise temperature TOP2, the contoller limit the operation frequency rise unti the OPT˘TOP2. 1.20.1. conditions of defrosting The defrost operation starts when the one of the following conditions is satisfied, the unit will come into defrosting. When the defrost operation starts, if the indoor excharge temperature less than 34ć, the indoor unit fan stops. If if the temperature of the outdoor unit hea-texchanger OPT reach or exceeds stops unit temperature TOP4, the compressor stop operating,until OPTTOP1(prevention cancel temperature), the unit restart and opreates at normal. 1.15. Indoor unit overheat prevention control a. utdoor heat exchanger Temperature (OPT) is continuously up to or less than 3ć while the unit runs for more than 40 minutes, and OPT is keep under -6ć for more than 3 minutes. b. Outdoor heat exchanger Temperature (OPT) is continuously uo to or less than 3ć meanwhile the unit runs for more than 80 minutes, and OPT is keep under -4ć for more than 3 minutes. c. Outdoor heat exchanger Temperature (OPT) is continuously up to or less than 3ć while the unit runs for more than 120 minutes, and OPT is keep below -2ć for more than 3 minutes. d. Once in the heating mode, if the outdoor heat excharge temperature(OPT) keep lower than 0ć and outdoor temperature higher than 3ć, also the compressor operates for more than 20 minutes and the outdoor heat exchanger Temperature (OPT) reaches -6ć or less and keeps 3 minutes, enter the first defrost. The defrost operation stops when the outdoor unit heat-exchanger temperature rises to about 15°C or higher or the defrosting time exceeds 10 minutes. During heating operation, if the temperature of the indoor unit heat-exchanger IPT exceeds the limit frequency rise temperature TIP2, the contoller limits the operation frequency rise unti the IPT˘TIP2. If the temperature of the outdoor unit heat-exchanger IPT reaches or exceeds stops unit temperature TIP4, the compressor stops operating and diplayes code P7,until IPTTIP1(prevention cancel temperature), the unit restart and opreates at normal. 1.16. IPM pretector If the IPM checked the temperature itself or current is higher than prevent temperature or current, the contrller shuts down the outdoor unit and displays code P0, when the IPM temperature or current drops to lower than prevention temperature, the outdoor unit restarts and operates at normal. 1.20.2. Compressor operation frequecy 1.17. Startup control Before the air conditioner come into defrosting, compressor running frequen- cy drop down to a lower frequency firstly, then the compressor shuts down. When the air conditioner starts in the cooling or heating mode, if the room temperature is 3.5°C higher than the set temperature, the unit operates with the operating frequency at maximum. Then, when the set temperature is reached, the unit operates at the operating frequency determined by fuzzy logic calculation, then enters the normal control mode after a while. In defrosting, the max. frequency of compressor is F9, in this period all protection functions are avaliable. 1.20.3 The part operation order. 1.18. Cold air prevention control When the air conditioner starts up in heating mode, the indoor unit fanwill not operate until the temperature of the indoor unit heat excharge reaches compressor ON OFF 4-way valve ON OFF ON outdoor fan motor OFF 50S 10S 2-19 İ10minutes 15S 15S SHARP(CHINA)INVESTMENT CO.,LTD z If the “AUTO” mode operates in DRY , the set temperature and the fan speed can’t changed. 1.22. Airflow control 1.21. Information about auto mode. In the AUTO mode, the temperature setting and mode are automatically selected according to the room temperature when the unit is turned on. Model z Initial Room Temerature Initial Set Temperature COOLING RT26ć 23ć DRY 26ć˚RT20ć RT-2 HEATING RT˘20ć 23ć FAN RT˘20ć - ƽ Press the SWING button, the vetical air flow louver will swing. ƽ Press the SWING button again to stop at the desired position. In the “AUTO”model, when the controller receives the up or down singnals of temperature from remote control, the set temperature can be adjusted by 1ćupper or lower. The maximum you can adjust by 2ć upper or lower. 1.23. Difference relating to set temperature Temperature setting method Auto mode Cooling Heating Drying Automatic temperature setting based on outside air temperature. Can be changed within ±2°C using remote con-trol. Cooling Can be changed between 18 and 32°C using remote control. Manual mode Heating Can be changed between 18 and 32°C using remote control. Drying Automatic setting. Can be changed within±2°C. 1.24. Drying operation control When the unit operates in drying mode, the set temperature is set and keep at room temperature decrease 2°C , and you can not adjusted it. 2. Outline of PWM (Pulse Width Modulation) circuit 2.1. Power Factor Correction(PFC) The PFC circuit varies the compressor drive voltage and controls the rotation speed of the compressor. The IGBT shown in the block diagram charges the energy (electromotive force) generated by the reactor to the electrolytic capacitor for the inverter by turning ON and OFF. 2-20 SHARP(CHINA)INVESTMENT CO.,LTD When the IGBT is ON, an electric current flows to the IGBT via the reactor. When the IGBT turns OFF, the energy stored while the IGBT was ON is charged to capacitor. As such, by varying the ON/OFF duty of the IGBT, the output voltage is varied. This circuit brings the operating current waves form closer to the waveform of commercial power supply voltage to maintain a high power factor. Because of the capacitor input, when the PFC circuit is OFF, the phase of the current waveform deviates from the voltage waveform. The IGBT turns ON after the time length determined by the zero-cross point to supply a current to the IGBT via the reactor. This brings the current waveform closer to the voltage wave form in phase. As described above, the ON/OFF operation of the IGBT controls maintain a high power factor by keeping the current phase closer to that of the supply voltage. 2.2 Detailed explanation of PFC drive circuit sequence t0~t1: IGBT Off, to detect the voltage Zero-crossing; t1~t2: IGBT PWM (20KHz), to improve current waveform closer to voltage waveform; t2~t3: IGBT Off; t3~t4: IGBT PWM (20KHz), to improve current waveform closer to voltage waveform; t4~t5: IGBT Off, to detect the voltage Zero-crossing; The detected clock waveform is used to judge the power source frequency (50Hz/60Hz). 3. Explanation of IPM drive circuit The IPM for compressor drive is made by Fairchild. The power supply for the IPM drive, the shunt resistance for over current detection, etc., are provided outside the IPM (control PCB). 3.1. IPM drive power supply circuit The power supply for the upper-phase IGBT (HU, HV, HW) drive employs a bootstrap system, and provides power to the upper-phase IC. The 15-V power supply for the lower-phase IC is provided by the control printed circuit board (PCB). 3.1.1 Brief explanation of bootstrap system (single power drive system) To supply power to the upper-phase IC, the microcomputer (IC1) turns ON the lower-phase IGBT (LU, LV, LW). This results in a charging current that flows to the electrolytic capacitor of each upper-phase IC input and charges the bootstrap capacitor with a 15V current The power supply for the subsequent stages is charged while the lower-phase IGBT is ON in ordinary compressor drive control. -Bootstrap Circuit Design Operation of Bootstrap Circuit The VBS voltage difference between VB(U,V,W) and VS(U,V,W), provides the supply to the HVIC within the Mini-DIP SPM package family in Motion-SPM products. This supply must be in the range of 13.0V~18.5V to ensure that the HVIC can fully drive the high-side IGBT. The Mini-DIP SPM package includes an under-voltage lockout protection for the VBS to ensure that the HVIC does not drive the high-side IGBT, if the VBS voltage drops below a specific voltage(refer to the datasheet).This function prevents the IGBT from operating in a high-dissipation mode. The VBS Floating supply can be generated a number of ways, including the bootstrap method described here (refer to Figure 34).This method has the 2-21 SHARP(CHINA)INVESTMENT CO.,LTD advantage of being simple and inexpensive; however, the duty cycle and on-time are limited by the need to refresh the charge in the bootstrap capacitor. The bootstrap supply is formed by a combination of and bootstrap diode, resistor, and capacitor as shown in Figure35 and Figure36. The current flow path of the bootstrap circuit is show in Figure 35. When Vs is pulled down to ground (either through the low-side or the load), the bootstrap capacitor CBS) is charged through the bootstrap diode (DBS) and the resistor (RBS) from the VCC supply. (Figure 34) (Figure 35) (Figure 36) 3.1.2 Compressor over current detection circuit When a current of about 25 A or higher flows through the shunt resistance (R638,R642,R644) on the control printed circuit board (PCB), the voltage at this resistance is input to IPM CSC pin (8). Then the gate voltage of the lower-phase IGBT (LU, LV, LW) inside the IPM turns OFF to cut off the over current. At the same time, an L output of about 2ms is generated from IPM VFO pin (6), and this results in an L input to overcurrent detection input VFO of the microcomputer and turns OFF the PWM signal output through to the IGBT gate. 2-22 SHARP(CHINA)INVESTMENT CO.,LTD 2-23 SHARP(CHINA)INVESTMENT CO.,LTD CHAPTER 3. FUNCTION AND OPERATION OF PROTECTIVE PROCEDURES [1] PRETECTION DEVICE FUNCTIONS AND OPERATIONS Self-daignosis result display Operation FUNTION Detection period Description 1 Compressor Discharge temperatureTP2 When discharge over heat (95ć), forbid the frequency compressor shut-down raise. in Reset condition Discharge is operation temperature P4 none yes none none none P1 none yes P1 none yes P2 none yes Operation offf of on P9 none yes P5 none yes none yes P7 yes none P0 none yes Operation OFF or ON E3 yes yes Operation OFF or ON E8 yes yes is below than TP2-2ć. Discharge temperature Discharge temperatureTP3 ˘ TP2(95ć). (100ć),drop Discharge the operating Indoor unit Indoor Outdoor unit error display unit temperature frequency. If discharge tem- ˘ TP1(90ć) and after perature over 105ć, shut- compressor stops for 3 down the compressor,outdoor minutes. fan motor stops after 15 seconds. 2 Compressor delaye operation 3 Lower voltage preventiion 4 5 The When the com- The compressor stops minutes to restart compressor delayes 3 pressor stopes for 3 minutes The When the unit in When unit stops if AC 158V Higher voltage The AC162V operation unit stops if When the mach- preventiong AC265V Over current When the outdoor current When Imax,the machine When AC260V ine in operation compressor stops and outdoor motor stops after the in When the outdoor current˘I normal operation 15 seconds 6 Compressor drive If the system can’t check the When the com- feed-back signal of compress- pressor drives or or or load is operates. exceptonal or driver fail then the 7 shut down outdoor unit Indoor unit evaporator Compressor stops if indoor When in cooling Automatic reset when frezze prevention pipe temperature IPT-1 ć or dehumidifying indoor pipe temperature and remains 5minutes operation IPT 6 ć and remains When the unit in When the outdoor pipe P6 outdoor operation temperature OPTTOP1 light 10 minutes 8 Outdoor unit overheat Compressor shtops if the prevention outdoor unit heatexchanger temperature OPTTOP4 9 flash 5cycle Indoor unit overheat Compressor stops if indoor When the unit is When the indoor pipe prevention exchaege in operation temperature IPTTIP1 IPM pretector The outdoor unit shutt down if When the unit is When the IPM chck the the in operation temperature of IPM itself temperature IPTTIP4 10 IPM checks temperature of IPM itself the or or the current fall to the current is too high 11 Outdoor unit normal heat Indoor and outdoor unit stops At exchanger thermistor if there is short-circuit or startup short-circuit compressor break in outdoor unit heat exchanger thermistor 12 Outdoor unit outside Indoor and outdoor unit stops At air temperature ther- if there is short-circuit or startup mistor error open-circuit compressor break in outdoor unit heat exchanger thermistor 3-1 SHARP(CHINA)INVESTMENT CO.,LTD Detection period Description 13 unit Indoor and outdoor unit stops At thermistor if there is short-circuit or startup Outdoor discharge Indoor unit Indoor Outdoor error display unit unit Reset condition compressor Operation OFF or ON E3 yes yes Operation OFF or ON E8 yes yes Operation OFF or ON E8 yes yes Operation OFF or ON E8 yes yes Reset after reception of E0 yes yes EF yes yes break in outdoor unit heat open-circuit error exchanger thermistor 14 15 Outdoor unit outside Indoor and outdoor unit stops At air if there is short-circuit or startup temperature ther-mistor break in outdoor unit heat short-circuit error exchanger thermistor Discharge compressor pipe Indoor and outdoor unit stops At temperature themister if there is short-circuit or startup short-circuit error compressor break in outdoor unit heat exchanger thermistor 16 Discharge pipe Indoor and outdoor unit stops At temperature themister if there is short-circuit or startup open-circuit error compressor break in outdoor unit heat exchanger thermistor 17 Serial signal error Indoor and outdoor unit stops When if outdoor unit cannot receive operation in serial signal serial signal from indoor unit for 2minutes. 18 Outdoor unit DC fan Operation stops if there is no When error input of rotation pulse signal unit from out-door unit fan motor operation outdoor fan is Operation OFF or ON in for 30 seconds [2] AIR CONDITIONER OPERATION IN THERMISTOR ERROR 1. Indoor unit Item Mode Control operation Room tempe- Auto Operation rature ther- mode judgment mistor (TH1) When resistance is low (tempera-ture judged higher than actual) Short-circuit When resistance is high (temperature judged lower than actual) Open-circuit Cooling The unit stops Heating The unit stops mode is activated even if room temperature is low. Cooling Frequency conRoom temperature is temperature is high. Room becomes too cold The unit stops trol Dehumidifying mode activated even if room Room does not The unit stops become cool. Normal operation. The unit stops Normal operation. The unit stops Room does not become The unit stops Room becomes too The unit stops memory frequency control Heating Frequency control warm Heat exchanger Cooling thermistor (TH2) Drying Heating Freeze prevention warm. Indoor unit evaporator The unit stops may freeze. Cold air prevention Cold air deactivates Compressor stops The unit stops prevention The unit stops occasionally. prevention too soon and cold air discharges. 2. Outdoor unit 3-2 The unit stops Cold air deactivates too slow. SHARP(CHINA)INVESTMENT CO.,LTD Item Compressor discharge pipe thermistor (TH1) Mode Control operation Cooling Expansion Dyring control Heating compressor valve and When resistance is low (tempera-ture judged higher than actual) Short-circuit When resistance is high (temperature judged lower than actual) Open-circuit Compressor Compressor Layer short-circuit or Compressor but room operates, does not become cool or warm protection discharge pipe open-circuit may discharge pipe temperature result in compres-sor temperature error indica- in normal oper-ation. error indica- Normal operation. Outdoor tion. tion. Heat exchanger Cooling Outdoor unit heat Compressor operates at Outdoor unit thermistor (TH2) Drying exchanger low speed or stops. thermistor short- thermistor circuit error open-circuit over heat prevention indication. Heating Expansion valve control Defrosting Defrosting operation is Outdoor not activated as needed, thermistor unit error indication. unit Defrosting operation Outdoor is activated unnece- thermistor short-circuit and frost accumulates short-circuit error ssarily, on outdoor unit indication. does and not room become unit error indication. warm Outside air Auto temper-ature Operation mode judgement Cooling mode is activated even if room thermistor (TH3) temperature is low. Cooling Operation Drying affected not Normal operation. Outdoor unit thermistor Heating activated mode is Outdoor even if thermistor short-circuit error room temperature is indication. high. error indication. Normal operation. Outdoor Outdoor unit thermistor short -circuit open-circuit unit thermistor open error -circuit indication. Heating unit error indication. Rating Defrosting operation is Outdoor Defrosting operation Outdoor controlDefrosting activated unnecessarily. ther-mistor short is not activated, and thermistor -circuit frost accumulates on open-circuit outdoor unit. error indication. indication. unit error unit [3] THERMISTOR TEMPERATURE CHARACTERISTICS 1. Indoor unit and outdoor exchange temperature and outside air temperature thermistor temperature characteristics Resistance Votalge of TEMP. (k Ohm) resisitance -30 63.513 -29 Resistance Votalge of (k Ohm) resisitance Resistance Votalge of TEMP. (k Ohm) resisitance TEMP. 4.628 15 7.447 2.968 60 1.464 1.115 60.135 4.609 16 7.148 2.918 61 1.418 1.088 -28 56.956 4.589 17 6.863 2.868 62 1.374 1.061 -27 53.963 4.568 18 6.591 2.819 63 1.331 1.035 -26 51.144 4.547 19 6.332 2.769 64 1.290 1.009 -25 48.488 4.524 20 6.084 2.720 65 1.250 0.984 -24 45.985 4.501 21 5.847 2.671 66 1.212 0.960 -23 43.627 4.477 22 5.621 2.621 67 1.175 0.936 -22 41.403 4.452 23 5.404 2.572 68 1.139 0.913 -21 39.305 4.426 24 5.198 2.524 69 1.105 0.890 -20 37.326 4.399 25 5.000 2.475 70 1.072 0.868 -19 35.458 4.371 26 4.811 2.427 71 1.040 0.847 -18 33.695 4.343 27 4.630 2.379 72 1.009 0.825 -17 32.030 4.313 28 4.457 2.332 73 0.979 0.805 -16 30.458 4.283 29 4.292 2.285 74 0.950 0.785 -15 28.972 4.252 30 4.133 2.238 75 0.922 0.765 -14 27.567 4.219 31 3.981 2.192 76 0.895 0.746 32 3.836 2.146 77 0.869 0.728 -13 26.239 4.186 3-3 SHARP(CHINA)INVESTMENT CO.,LTD Resistance Votalge of TEMP. (k Ohm) resisitance -12 24.984 -11 Resistance Votalge of TEMP. R(k Ohm) resisitance 2.101 78 0.843 0.710 2.057 79 0.819 0.692 Resistance Votalge of TEMP. (k Ohm) resisitance 4.152 33 3.697 23.795 4.117 34 3.563 -10 22.671 4.082 35 3.435 2.012 80 0.795 0.675 -9 21.606 4.045 36 3.313 1.969 81 0.773 0.658 -8 20.598 4.008 37 3.195 1.926 82 0.751 0.641 -7 19.644 3.969 38 3.082 1.883 83 0.729 0.625 -6 18.732 3.930 39 2.974 1.842 84 0.709 0.610 -5 17.881 3.890 40 2.870 1.800 85 0.689 0.595 -4 17.068 3.850 41 2.770 1.760 86 0.669 0.580 -3 16.297 3.808 42 2.674 1.720 87 0.651 0.566 -2 15.565 3.766 43 2.583 1.681 88 0.633 0.552 -1 14.871 3.723 44 2.494 1.642 89 0.615 0.538 0 14.212 3.680 45 2.410 1.604 90 0.598 0.525 1 13.586 3.635 46 2.328 1.567 91 0.582 0.512 2 12.991 3.590 47 2.250 1.530 92 0.566 0.499 3 12.426 3.545 48 2.174 1.495 93 0.550 0.487 4 11.889 3.499 49 2.102 1.459 94 0.535 0.475 5 11.378 3.452 50 2.032 1.425 95 0.521 0.463 6 10.893 3.406 51 1.965 1.391 96 0.507 0.452 7 10.431 3.358 52 1.901 1.357 97 0.493 0.441 8 9.991 3.310 53 1.839 1.325 98 0.480 0.430 9 9.573 3.262 54 1.779 1.293 99 0.467 0.419 10 9.174 3.214 55 1.721 1.262 100 0.455 0.409 11 8.795 3.165 56 1.666 1.231 12 8.433 3.116 57 1.613 1.201 13 8.089 3.067 58 1.561 1.172 14 7.760 3.017 59 1.512 1.143 Resistance at 2ć 5 k. TH1: indoor room temperature thermistor and outside air temperature thermistor TH2: indoor exchange temperature themistor and outside exchange temperature thermistor Before measuring resistance,disconnect connectors as shown above. 2. Outdoor unit thermistor temperature characteristics 3-4 SHARP(CHINA)INVESTMENT CO.,LTD Rmin R(t) Rmax Rmin R(t) Rmax Rmin R(t) Rmax TEMP. (k Ohm) (k Ohm) (k Ohm) TEMP. (k Ohm) (k Ohm) (k Ohm) TEMP. (k Ohm) (k Ohm) (k Ohm) -30 283.3 322.9 367.7 24 19.36 20.89 22.52 78 2.563 2.654 2.745 -29 267.4 304.4 346.3 25 18.55 20 21.54 79 2.481 2.567 2.654 -28 252.5 287.1 307.4 26 17.77 19.14 20.6 80 2.402 2.484 2.567 -27 238.5 270.9 307.4 27 17.03 18.32 19.7 81 2.327 2.404 2.483 -26 225.4 255.7 289.8 28 16.32 17.55 18.85 82 2.254 2.327 2.401 -25 213.1 241.4 273.3 29 15.65 16.81 18.04 83 2.183 2.253 2.323 -24 201.5 228 257.9 30 15 16.1 17.27 84 2.115 2.182 2.248 -23 190.6 215.5 243.4 31 14.39 15.43 16.54 85 2.05 2.113 2.176 -22 180.3 203.6 229.8 32 13.81 14.79 15.34 86 1.985 2.047 2.109 -21 170.7 192.5 217 33 13.25 14.18 15.17 87 1.922 1.983 2.045 -20 161.6 182.1 205 34 12.72 13.6 14.54 88 1.861 1.922 1.983 -19 153.1 172.3 193.7 35 12.21 13.05 13.93 89 1.802 1.862 1.923 -18 145 163.1 183.2 36 11.72 12.52 13.36 90 1.746 1.805 1.865 -17 137.5 154.4 173.2 37 11.26 12.01 12.81 91 1.692 1.75 1.809 -16 130.3 146.2 163.9 38 10.82 11.53 12.29 92 1.639 1.697 1.755 -15 123.6 138.5 155.1 39 10.29 11.07 11.78 93 1.589 1.646 1.703 -14 117.3 131.3 146.8 40 9.986 10.63 11.31 94 1.54 1.596 1.653 -13 111.3 124.4 139 41 9.6 10.21 10.85 95 1.493 1.549 1.604 -12 105.6 118 131.7 42 9.231 9.813 10.42 96 1.448 1.502 1.558 -11 100.3 111.9 124.7 43 8.878 9.43 10 97 1.404 1.458 1.512 -10 95.24 106.2 118.2 44 8.54 9.064 9.612 98 1.362 1.415 1.469 -9 90.49 100.8 112.1 45 8.217 8.714 9.233 99 1.321 1.373 1.426 -8 85.99 95.68 106.3 46 7.908 8.38 8.872 100 1.284 1.335 1.387 -7 81.75 90.86 100.8 47 7.612 8.06 8.526 101 1.245 1.296 1.348 -6 77.74 86.31 95.74 48 7.328 7.754 8.196 102 1.209 1.258 1.309 -5 73.94 82.01 90.88 49 7.057 7.461 7.88 103 1.173 1.222 1.272 -4 70.35 77.95 86.29 50 6.797 7.18 7.578 104 1.139 1.187 1.236 -3 66.96 74.11 81.96 51 6.548 6.912 7.289 105 1.105 1.153 1.202 -2 63.74 70.48 77.87 52 6.309 6.655 7.013 106 1.073 1.12 1.168 -1 60.69 67.05 74 53 6.08 6.409 6.748 107 1.042 1.089 1.136 0 57.81 63.8 70.34 54 5.861 6.173 6.495 108 1.013 1.058 1.104 1 55.08 60.72 66.88 55 5.651 5.947 6.253 109 0.9833 1.028 1.074 2 52.49 57.81 63.61 56 5.449 5.73 6.02 110 0.9553 0.9997 1.045 3 50.03 55.05 60.52 57 5.255 5.522 5.798 111 0.9283 0.9719 1.016 4 47.71 52.44 57.59 58 5.07 5.323 5.585 112 0.9021 0.9451 0.9892 5 45.5 49.97 54.82 59 4.891 5.132 5.381 113 0.8765 0.9191 0.9626 6 43.41 47.62 52.2 60 4.72 4.949 5.101 114 0.8524 0.894 0.9367 7 41.42 45.4 49.71 61 4.556 4.774 4.997 115 0.8087 0.8595 0.9117 8 39.53 43.2 42.33 62 4.398 4.605 4.817 116 0.8059 0.8461 0.8875 9 37.74 41.29 45.12 63 4.247 4.448 4.644 117 0.7837 0.8233 0.8641 10 36.04 39.39 43.01 64 4.101 4.288 4.479 118 0.7623 0.8012 0.8413 11 34.42 37.59 41 65 3.961 4.139 4.32 119 0.7415 0.7798 0.8193 12 32.89 35.87 39.1 66 3.827 3.995 4.167 120 67 3.698 3.858 4.021 121 0.702 0.7386 0.7773 13 31.43 34.25 37.29 3-5 SHARP(CHINA)INVESTMENT CO.,LTD Rmin R(t) Rmax Rmin R(t) Rmax TEMP. (k Ohm) (k Ohm) (k Ohm) 14 30.04 32.71 15 29.72 31.24 TEMP. (k Ohm) (k Ohm) (k Ohm) 35.58 68 33.95 69 70 3.339 16 Rmin R(t) Rmax TEMP. (k Ohm) (k Ohm) (k Ohm) 122 0.6631 0.7195 0.7572 123 0.6649 0.7007 0.7378 3.476 3.616 124 0.6472 0.6824 0.7189 17 71 3.229 3.359 3.491 125 0.6301 0.6647 0.7006 18 25.13 27.26 29.55 72 3.122 3.246 3.372 126 0.6135 0.6476 0.6829 19 24.05 26.07 28.23 73 3.02 3.138 3.257 127 0.5974 0.6309 0.6657 20 23.02 24.93 26.97 74 2.921 3.033 3.146 128 0.5818 0.6148 0.649 21 22.04 23.84 25.77 75 2.827 2.933 3.04 129 0.5667 0.5991 0.6328 22 21.1 22.81 24.63 76 2.735 2.836 2.938 130 0.5521 0.5839 0.6171 23 20.21 21.83 23.55 77 2.647 2.743 2.84 R—Resistance Rrsistance at 25ć20 k TH3: Outdoor unit discharge pipe thermistor Before measuring resistance,disconnect connectors as shown above. [4] GENERAL TROUBLESHOOTING CHART 1. Indoor unit does not turn on Main cause Cracked PCB. Inspection method Normal value/condition Check visually. There should be no cracking in (Cracked pattern) Open-circuit in FU1 (250 V, 3.15A). Remedy Replace PCB. PCB or pattern. Check melting of FU1. There should be no open-circuit. Replace PCB. 2. Indoor unit fan does not operate Main cause Inspection method Open-circuit in heat exchanger ther- Measure mistor (TH2) (dismount for check). thermistor Normal value/condition resistance Refer to themistor temperature Remedy Replace thermistor. characteristic There should be no open-circuit Replace thermistor. or faulty contact. Disconnected heat exchanger ther- Inspect connector on PCB.Check Thermistor mistor (TH2) thermistor installation con-dition. disconnected. 3. Indoor unit fan speed does not change 3-6 should not be Install correctly. SHARP(CHINA)INVESTMENT CO.,LTD Main cause Inspection method Remote control not designed to allow Normal value/condition Fan speed should change ex- Check operation mode. fan speed change. Remedy Explain to user. cept during dehumidifying operation, sleep operation,internally normal operation 4. Remote control signal is not received Main cause Inspection method Batteries at end of service life. Normal value/condition 2.5 V or higher (two batteries in Measure battery voltage. Remedy Install new batteries. series connection) Batteries installed incorrectly. As Check battery direction. Lighting fixture is too close, or Turn off light and check. fluorescent lamp is burning out. indicated on battery Install batteries in indicated compartment. direction. Signal should be received when Change light position or install light is turned off. new fluorescent lamp. Operate within range specified in Signal should be received within Explain appropriate handling inap-propriate. manual. range specified in manual. to user. Open-circuit or short-circuit in wiring Check if wires of light receiving Wires of light receiving section Replace of light receiving section. section are caught. should not have any damage receiving section. Defective light receiving unit. Check signal receiving circuit Operating position/angle is wires of light caused by pinching. Tester indicator should move Replace PCB. when signal is received. Dew condensation on light receiving Check for water and rust. unit. Signal should be received within Take moisture-proof measure range specified in manual. for lead wire outlet of light receiving section. 5. Vane do not move Main cause Caught in sliding section. Inspection method Normal value/condition Operate to see if vane are caught Vane should operate smoothly. in place. Disconnected connector (CN5 on Remove or correct catching section. Inspect connectors. Connectors or pins should not relay PCB, louver motor side) Contact of solder on PCB(connector Remedy Install correctly. be disconnected. Check visually. There should not be solder section on PCB) Correct contacting section. contact. 6. Compressor does not start Main cause Erroneous inter-unit connection. DamageD IPM Main cause Blown outdoor unit fuse. Inspection method Normal value/condition Check wiring between indoor and Terminal board 1-N: 230 VAC, outdoor units. 50 Hz Check IPM continuity Remedy Correct wiring. Replace IPM Inspection method Normal value/condition Check 20-A fuse.Check 15-A fuse. Fuse should not be blown. Remedy Replace fuse. Replace outdoor unit PWB assembly. Power supply voltage is too low. Measure power supply voltage 220± 10 VAC, 50 Hz during startup. Compressor lock. Make sure that power supply voltage is 198 V or higher. Supply current and touch com- Compressor should start nor- Apply pressor cover (sound absorbing mally. compressor.Replace material) to check if operation starts. 3-7 external compressor. impact to SHARP(CHINA) INVESTMENT CO., LTD [5] MALFUNCTION (PARTS) CHECK METHOD 1. Procedure for determining defective outdoor unit IPM/compressor The following flow chart shows a procedure for locating the cause of a malfunction when the compressor does not start up and a DC overcurrent indication error occurs. Use the remote operate the air conditioner No P9 Compressor starts up No conector right Yes Does low or high press valve conectes wire again Yes No Open open Does indoor unit LED Does the wire Does d compressor start up Yes Yes display error code No Replace the Operates again after 3 mins inverter PCB No Yes Normal Normal Replace compressor No P0 Does the wire No conectes wire Does compressor start conector right agrin Yes Clean indoor heat excharge or outdoor No Check indoor heat excharge and outdoor heat excharge Check the refrigerant the installation amount Check condition Installation again 3-8 Normal Replace the inverter PCB SHARP(CHINA) INVESTMENT CO., LTD 6. DC Over Current Error error memory isrecorded. Start Are valves(2-way and Yes 3-way) close? Fully open stop valves Does compressor rotate? No Yes Does compressor rotate more Yes than 30 seconds? No Is IPM PWB floating from the Yes heat sink? No Check IPM lead Fix IPM PWB with screws securely. Abnormal wire.(UVW) Check the AC power supply normal Modify the connection of compressor voltage when compressor lead wire on PWB. rotate.(rated voltage±10%) normal Check IPM short Abnormal circuit. Yes Replace P WB. Cooling mode? normal No Heating mode Check compressor Check outdoor exchanger termistor and discharge thermistor. Abnormal terminal. normal Modify compressor terminal marking. Check indoor exchanger thermistor and discharge thermistor. Abnormal Modify or replace termistor. Modify or replace termistor. Replace PWB normal Check outdoor heat Check indoor heat exchanger. Does Abnormal exchanger. compressor Clean indoor heat rotate? Clean indoor heat exchanger. normal No Check the refrigerant amount. Replace Compressor Check the discharge pressure. 3-9 Check the installation condition. exchanger. SHARP(CHINA)INVESTMENT CO.,LTD [6] CHART 1. The failure code display(indoor unit) Fault Type 2. Function Indicator lamp Digital LED display Indoor/out door c ommunication fault RUN&POWER: ON E0 (Flashing) Outdoo r commu nication fault RUN&POWER: ON EC (Flashing) Room temperature sensor (IRT) RUN&POWER: ON E1 (Flashing) Indoor pipe (coil) temperature sensor (IPT) RUN&POWER: ON E2 (Flashing) Outdoor pipe (coil) temperature sensor (OPT) RUN&POWER: ON E3 (Flashing) Model configuration wrong RUN&POWER: ON E5 (Flashing) Indoor fan motor fault RUN&POWER: ON E6 (Flashing) Outdoor air temperature sensor RUN&POWER: ON E7 (Flashing) Discharge temperature sensor RUN&POWER: ON E8 (Flashing) IPM of drive and module fault RUN&POWER: ON E9 (Flashing) Outdoor fan motor fault (DC Motor) RUN&POWER: ON EF (Flashing) Curre nt sensor f ault RUN&POWER: ON EA (Flashing) EEPROM fault RUN&POWER: ON EE (Flashing) Temperature switch fault (on top of the compressor) RUN&POWER: ON EP Voltage sensor f ault RUN&POWER: ON EU (Flashing) (Flashing) Intake temperature sensor RUN&POWER: ON EH (Flashing) The failure code display 2.1. Outdoor power supply PCB (The lamp on the outdoor PCB) Blink times(n) Fault Message Blink times(n) 1 IPM protection 17 2 Overvoltage / un dervoltage 18 Fault Message Defrost state Short-circuit / open-circuit fault of intake temperature sensor 3 Over current 19 Outdoor EEPROM fault 4 Exhaust overtemperature protection 20 Outdoor fan motor protection 5 Outdoor coil overtemperature protection 21 Indoor fan motor protection 6 Drive faulture protection 23 System in shortage of Freon 7 Communication fault with indoor unit 24 Model configuration wrong 8 Compressor overheat fault (compressor 25 Indoor sensor fault 26 Indoor coil sensor fault 27 Indoor EEPROM fault 28 Indoor fan motor fault top switch) 9 Short-circuit / open-circuit fault of outdoor temperature sensor 10 Short circuit / open-circuit fault of outdoor heat exchanger temperature sensor 11 Short-circuit / open-circuit fault of discharge temperature sensor 12 Voltage sensor fault 30 Outdoor drive fault 13 Current sensor fault 31 Outdoor environmental Overtemperature/ 14 IPM fault 32 Indoor coil defors t prevention 33 Indoor coil overheating protection undertemperature protection 15 communication fault between power source board and intelligent power module 16 No feedback from DC fan motor(outdoor unit) 3-10 SHARP(CHINA)INVESTMENT CO.,LTD 2.2. Outdoor IPM Flash times(n) Fault Message Blink times(n) Fault Message 1 IPM protection/fa ilture 13 The phase current of compressor failture 2 DC overhigh/lower voltage 15 communication fault between power source board and intelligent power module 3 Overcurrent of compressor Display on outdoor power source board: The indicator alerts the fault in a cycle as such that it is bright for 0.5 seconds, dark for 0.5 seconds, flases”n” times and then dark for 3 seconds. 2.3. Protection Code Protection Type Function Indicator (flash) Digital LED display Overvoltage / un dervoltage prot e c tion RUN: Flaring ; TIMER: 1 time /8 sec P1 Overcurrent protection RUN: Flaring; TIMER: 2 times /8 sec P2 Exhaust overtemperature protection RUN: Flaring; TIMER: 4 times /8 sec P4 Subcooling protection under cooling mode RUN: Bright; TIMER: 5 times /8 sec P5 Overheating protection under cooling mode RUN: Bright; TIMER: 6 times /8 sec P6 Overheating protection under heating mode RUN: Bright; TIMER: 7 times /8 sec P7 Outdoor over/ under temperature protection RUN: Bright; TIMER: 8 times /8 sec P8 Drive protection (software control ) RUN: Flaring; TIMER: 9 times /8 sec P9 Module protection (hardware control) RUN: Flaring; TIMER: 10 times /8 sec P0 [7] Trouble shooting Guide According to the fault code 1. Display E1 or E2 Problem symptom Display E1 o r E2 Cause Room temperature thermistor (IRT) and Indoor exchange temperature thermistor (IPT) fault Malfunction No. 1 Content of diagn osis Action Contact between indoor room and exchange Insert again if loose. temperature thermistor CN6 (RT, IPT) and slot 2 Measure the resistance on the two ends of indoor Replace the temperature sensor if the resistance is incurred to drift, temperature open or short circuiting. sensor: (25ć/ 5k). For other resistance, please refer to the temperature – Resistance Sheet 3 If the above testing is normal Replace the indoor control board 3-11 SHARP(CHINA)INVESTMENT CO.,LTD 2. Display E6 Problem symptom Display E6 Cause Indoor fan motor fault Malfunction No. Content of diagn osis Action 1 Check the indoor cross-flow fan blade If the fan does not run, readjust the fan position until it can run 2 If the motor insert (CN3, CN4) on indoor main PCB is in Insert again if loose. smoothly. good contact with the slot 3 Startup capacitance value Capacitance incorrect. Replace with a new capacitor. 4 The above inspe c tions are normal Replace the indo or main PCB 3. Display E3, E7, E8 Problem symptom Display E3, E7, E8 Cause Outdoor exchange temperature thermistor and outdoor air temperature thermistor and discgarge temperature sensor fault Malfunction No. 1 Content of diagn osis Action If the temperature sensor on outdoor power source Insert again if loose. board is in good contact with the slot (CN1, CN2) 2 Measure the resistance on the two ends of outdoor Replace the temperature sensor if the resistance is incurred to drift, open or short circuiting. temperature thermistor: Resistance of CN1 terminal thermistor (25ć / 5k). For other resistance, please refer to the temperature – Resistance Sheet. Resistance of CN2 terminal thermistor(25ć / 20k). For other resistance, please refer to the discharge temperature thermistor resistance sheet. 3 If the above testing is normal Outdoor power source board 4. Display EA Problem symptom Display EA Cause Malfunction No. 1 Current sensor fault Content of diagn osis Action Check for refrigerant leakage Find the leakage point and recharge the refrigerant Replace the outdoor power source board 3-12 SHARP(CHINA)INVESTMENT CO.,LTD 5. Display EC Problem symptom Display EC Cause Outdoor communication fault between power source board and intelligent power module Malfunction No. 1 Content of diagnosis Action Check the contact of communication wire (CN5) Insert again if loose. between power source board and intelligent power module 2 After the unit is complete The indicator on power energized, source board flare normal check the indicators (bright for 1 second and dark on for outdoor source power board and intelligent module power 1 second), but Replace the intelligent power If the fault remains unsolved, module replace the power source board again. the indicator on intelligent power module does not work normally The indicator on intelligent Replace the power source If the fault remains unsolved, power module flare normal board replace the intelligent power (bright for 1 second and dark for 1 second), but module again. the indicator on power source board does not work normally You can check each voltage of the electrical board communication pin, the normal data is as the following: Pin 1 2 3 4 5 6 Voltage(V) 5 1.0-4.8 1.8-4.1 2.6 earthing 15 Outdoor communication circuit 3-13 SHARP(CHINA)INVESTMENT CO.,LTD 6. Display EU Problem symptom Display EU Cause Malfunction No. 1 Voltage sensor fault Content of diagnosis Action The outdoor power source bord can’t check the voltage, check the votage lower or higher than the protector voltage . Insert again if loose. Replace the outdoor power source board 3-14 voltage sampling circuit 7. Display EP Problem symptom Display EP Cause Malfunction No. 1 Temperature switch fault ( on top of the compressor) Content of diagnosis Action Check the insert position CN3 of the compressor Insert again if loose. top temperature switch wires on outdoor power source board 2 No switch on compressor top Jumper short-circuiting (This function not provided for 1 – 1.5P unit) The correct sequence of U. V and W wiring shall be “red, white and Compressor Check the U, V and W wires of temperature. The the compressor. blue”. Connect again if incorrect. temperature Check the system pressure. The pressure is low. Add refrigerant to ensure the system pressure very is high, is normal. accompanied with bad smell. Check the outdoor ventilation Install to the position as required in the Installation Manual and and if there is any obstruction ensure the air inlet and outlet of the outdoor unit is smooth. that affects the normal radiating of the air conditioner. 3 Compressor temperature: The temperature is not high. Short circuit CN3. If the fault is solved after short circuiting, replace the shell temperature switch. If the fault remains unsolved after replacing the shell temperature switch, please replace the outdoor power source board. 8. Display P1 Problem symptom Display P1 Cause Malfunction No. 1 Overvoltage / undervoltage protection Content of diagnosis Action Test the supply voltage if it is between 160V ̚260V It is normal protection if exceeding this range. ˄AC˅. Test if the voltage between L and N terminal of 2 3 It is normal protection if exceeding this range. outdoor unit is within 160V̚260V˄AC˅. If the voltage is normal: Replace the outdoor power source board 3-14 SHARP(CHINA)INVESTMENT CO.,LTD 9. Display E9 (Firstly display P0 or P9, then change to E9) Problem symptom Display E9 (Firstly display P0 or P9, then change to E9) Cause Malfunction No. 1 Intelligent power module of drive and module fault Content of diagnosis Action Re-energize If this code is displayed when the compressor is and started for several seconds or even not started, check the check the compressor connection for correctness protection “P0” Check if the outdoor module is code appears tightly installed onto the radiating on display. when Firstly air evenly display P0 conditioner Check the system pressure. If no insert wrong, replace the intelligent power module Fix the screws again if loose. fins and if the silicone is applied the Recharge refrigerant if the pressure is low. Discharge is working some refrigerant if the pressure is too high. Check the outdoor ventilation and if Install to the position as required in the Insallation there is any obstruction that affects manual and ensure the air inlet and outlet of the outdoor the normal radiating of the air unit is smooth. conditioner. The above inspections are normal, Replace the intelligent power module but the fault remains unsolved 2 Re-energize If this code is displayed when the compressor is and started for several seconds or even not started, check the If no insert wrong, replace the intelligent power module check the compressor connection for correctness protection When the compressor is restarted immediately Try starting the air conditioner again after a longer period code after stop, this might also cause P9 protection of stop on display. because the cooling system is not stable. Firstly P9 appears Cooling / heating is normal display P9 after the during run air conditioner started is and If the cooling abnormal, has run for a compressor period of time correctness. / heating check wiring is Replace the intelligent power module Insert again if loose. the for 10. Display EE Problem symptom Display EE Cause Malfunction No. 1 EEPROM fault Content of diagnosis Action Shut off the power and suplyes again,if EE dispay again: Replace outdoor power source board 11. Display P1 Problem symptom Display P1 Cause Malfunction No. 1 2 Overvoltage / undervoltage protection Content of diagnosis Action Test the supply voltage if it is between 160V ̚260V˄AC˅. It is normal protection if exceeding this range. Test if the voltage between L and N terminal of outdoor unit is It is normal protection if exceeding this range. within 160V̚260V˄AC˅. 3 If the voltage is normal Replace the outdoor power source board 12. Display E0ǃE5 3-15 SHARP(CHINA)INVESTMENT CO.,LTD Problem symptom Display E0 Cause Malfunction No. 1 E5 Indoor / ou tdoor communication fault Content of diagn osis Energize Action 1. Check if the indoor and outdoor connections are and correct. The terminal L and N shall correspond to observe for each other on indoor and outdoor units. Measure approx. 10 the voltage on outdoor terminal L and N (before minutes. display of E0 fault). If the voltage is “0”: E0 is If still 2. If the L & N voltage is normal, measure the displayed or voltage between the outdoor terminal N and 1. If changed to the voltage change occurs between 0~24V E5 after a (change pulse voltage) period time: of 3. If the L & N voltage is normal, measure the Replace the indoor main PCB. Replace the indoor main PCB. Replace the outdoor power source board. voltage between the outdoor terminal N and 1. If the voltage change occurs between 0~12V change pulse voltage), but there is no 24V: 4. If the L & N voltage is normal, measure the Firstly replace the indoor main PCB. If the fault remains voltage between the outdoor terminal N and 1. If unsolved, replace the outdoor power source board. the voltage has no change: 5. 1) The indicator is dark: Check IPM Indicator board – Test the pins of rectifier on bridge, fast recovery diode (FRD) outdoor and power breakdown, source damage. board IGBT elements short for circuiting Replace the power source board. any or 2) If no damage, test the DC voltage Replace the power source board. between DC+ and DC-. If the voltage is approx. 310V: 3) If no damage, test the DC voltage Replace the power source board. between DC+ and DC-. If the voltage is zero: 6. If the problem cannot be solved by using the Firstly replace the intelligent power module . If the methods above: problem remains unsolved, replace the indoor main PCB. 7. If this fault appears at the initial installation and please check if the indoor control board and outdoor testing of the complete unit inverter module are of the same generation. Power source board . power factor correction. The schematic diagram of Indoor unit communication loop The schematic diagram of the partial outdoor unit communication loop 3-16 SHARP(CHINA)INVESTMENT CO.,LTD 13. Display P4 Problem symptom Display P4 Cause Malfunction No. 1 Discharge overtemperature protection Content of diagn osis Action Check if the air inlet and outlet of outdoor unit is blocked by any Install to the position as required in the Instruction obstructions. Manual and ensure the air inlet and outlet of the outdoor unit is smooth. 2 Check the system for shortage of refrigerant. Add refrigerant 3 Check if the exhaust temperature sensor is drifted, short circuited or Replace the exhaust temperature sensor open circuited. (25ć/20k). For other resistances, please refer to the Exhaust Temperature Sensor – Resistance Sheet) 4 Control board damaged Replace the outdoor power source board 14. Display P2 Problem symptom Display P2 Cause Malfunction No. 1 Overcurrent protection Content of diagn osis Action Check if the outdoor fan motor is stopped due to overheat Replace the fan capacitor,replace the outdoor power protection, or damaged, and if the fan capacitor is damaged. source board and the damaged outdoor fan motor. 15. Display P5 Problem symptom Display P5 Cause Subcooling prote c tion under cooling mode Malfunction No. Content of diagn osis Action 1 Check if the air inlet and outlet of indoor unit is blocked by any Install to the position as required in the Installation manual obstructions. and ensure the air inlet and outlet of the outdoor unit is smooth. 2 Check the system for shortage of refrigerant. Add refrigerant 3 Check if the exhaust temperature sensor is drifted, short Replace room temperature sensor (IRT) and Indoor pipe circuited or open circuited. (Measure the resistance of the (coil) temperature sensor (IPT) resistors on two ends of indoor temperature sensor: (25ć / 5k). For other resistances, please refer to the Temperature – Resistance Sheet. 4 Control board damaged Replace the indoor control board 16. Display P6 Problem symptom Display P6 Cause Overheating protection under cooling mode Malfunction No. Content of diagn osis Action 1 Check if the air inlet and outlet of outdoor unit is blocked by any Install to the position as required in the Installation manual obstructions. and ensure the air inlet and outlet of the outdoor unit is smooth. 2 Check the system for shortage of refrigerant. Add refrigerant 3 Check if the outdoor evaporator coil temperature sensor is Replace the outdoor coil temperature sensor drifted, short circuited or open circuited (25ć/5K). For other resistance, please refer to the Temperature – Resistance Sheet. 4 Control board damaged Replace the outdoor power source board 3-17 SHARP(CHINA)INVESTMENT CO.,LTD 17. Display P7 Problem symptom Display P7 Cause Overheating protection under heating mode Malfunction No. 1 Content of diagn osis Action Check if the air inlet and outlet of outdoor unit is blocked by any Install to the position as required in the Installation manual obstructions. and ensure the air inlet and outlet of the outdoor unit is smooth. 2 Check the system for shortage of refrigerant. Add refrigerant Check if the indoor exchange temperature thermistor is drifted, short circuited or open circuited. (Measure the resistance of the 3 resistors on two ends of indoor temperature thermistor: (25ć / Replace the Indoor exchange temperature thermistor(IPT) 5k). For other resistances, please refer to the Temperature – Resistance Sheet. 4 Control board damaged Replace the indoor control board 18. Display P8 Problem symptom Display P8 Cause Outdoor air temperature over/under protection Malfunction No. Content of diagn osis Action The compressor cannot run under cooling mode when the 1 outdoor temperature is lower than -1ć, or run under heating Normal protection function mode when the outdoor temperature is higher than 33ć, whilst the compressor alarms P8 protection. If the temperature is not within the protective range above, please refer to the Temperature – Resistance Sheet (See 2 Appendix). Use the multimeter to measure the resistors on the Replace the sensor if it is incurred to drift, open circuiting two ends of outdoor intake temperature sensor (CN1) or short circuiting. (25ć/5k). For other resistance, please refer to the Temperature – Resistance Sheet. 3 If the fault remains unsolved after replacement of the sensor Replace the outdoor power source board 19. Display P9 Problem symptom Display E9 (Firstly display P0 or P9, then change to E9) Cause Intelligent power module of drive and module fault Malfunction No. Content of diagn osis Re-energize If this code is displayed when the compressor is and check the started for several seconds or even not started, Replace the intelligent power module.(Be sure to apply protection check silicone when replacing the intelligent power module.). code 1 Action on the compressor connection for correctness. display. P9 appears Cooling/heating Firstly display after the during run P9 conditioner started air is normal Insert again if loose is and If the cooling / heating are has run for a abnormal, period of time compressor check wiring the for Insert again if loose correctness. When the compressor is restarted immediately Try starting the air conditioner again after a longer after stop, this might also cause P9 protection period of stop because the cooling system is not stable. 3-18 SHARP(CHINA)INVESTMENT CO.,LTD CHAPTER 4. REFRIGERATION CYCLE [1] SCHEMATIC DIAGRAM [2] STANDARD CONDITION Indoor side Outdoor side Dry-bulb Temp. (°C) Relative Humidity (%) Cooling 27 47 Heating 20 Dry-bulb Temp. (°C) Relative Humidity (%) 35 40 7 87 [3] TEMPERATURE AT EACH PART AND PRESSURE IN 3-WAY VALVE NOTE 1)Indoor fan speed: Hi 2)Vertical adjustment louver "front”, Horizontal adjustment louver "level" 3)Indoor air temp. : Cooling 27°C, Heating 20°C 4)Power source : 230V, 50Hz 5)Compressor speed : Rated frequency 4-1 SHARP(CHINA)INVESTMENT CO.,LTD AY-XP9PSR/AE-XP9PSR 1.1. At Cooling 1.2. At Heating 㪏㪌㪇㩷 㪎㪇㪇㩷 㪏㪇㪇㩷 㪠㫅㫇㫌㫋㩷㩿䌗㪀 㪠㫅㫇㫌㫋㩷㩿㪮㪀 㪍㪌㪇㩷 㪍㪇㪇㩷 㪎㪌㪇㩷 㪎㪇㪇㩷 㪌㪌㪇㩷 㪍㪌㪇㩷 㪍㪇㪇㩷 㪌㪇㪇㩷 㪉㪇 㪉㪌 㪊㪇 㪊㪌 㪋㪇 㪄㪈㪇 㪋㪌 㪄㪌 㪇 㪦㫌㫋㫊㫀㪻㪼㩷㪸㫀㫉㩷㫋㪼㫄㫇㪅㩷䋨㷄䋩 㪈㪇 㪈㪌 㪋㪅㪇㩷 㪊㪅㪌㩷 㪊㪅㪌㩷 㪟㪼㪸㫋㫀㫅㪾㩷㪺㪸㫇㪸㪺㫀㫋㫐㩷㩿㫂㪮㪀 㪚㫆㫆㫃㫀㫅㪾㩷㪺㪸㫇㪸㪺㫀㫋㫐㩷㩿㫂㪮㪀 㪌 㪦㫌㫋㫊㫀㪻㪼㩷㪸㫀㫉㩷㫋㪼㫄㫇㪅㩷㩿㷄㪀 㪊㪅㪇㩷 㪉㪅㪌㩷 㪉㪅㪇㩷 㪊㪅㪇㩷 㪉㪅㪌㩷 㪉㪅㪇㩷 㪈㪅㪌㩷 㪉㪇 㪉㪌 㪊㪇 㪊㪌 㪋㪇 㪦㫌㫋㫊㫀㪻㪼㩷㪸㫀㫉㩷㫋㪼㫄㫇㪅㩷䋨㷄䋩 㪄㪈㪇 㪋㪌 㪄㪌 㪇 㪌 㪈㪇 㪦㫌㫋㫊㫀㪻㪼㩷㪸㫀㫉㩷㫋㪼㫄㫇㪅㩷㩿㷄㪀 㪈㪌 AY-X12PSR/AE-X12PSR 1.1. At Cooling 1.2. At Heating 㪈㪈㪇㪇㩷 㪈㪉㪇㪇㩷 㪈㪇㪇㪇㩷 㪠㫅㫇㫌㫋㩷㩿䌗㪀 㪠㫅㫇㫌㫋㩷㩿㪮㪀 㪈㪈㪇㪇㩷 㪐㪇㪇㩷 㪈㪇㪇㪇㩷 㪏㪇㪇㩷 㪐㪇㪇㩷 㪎㪇㪇㩷 㪉㪇 㪉㪌 㪊㪇 㪊㪌 㪋㪇 㪏㪇㪇㩷 㪋㪌 㪄㪈㪇 㪦㫌㫋㫊㫀㪻㪼㩷㪸㫀㫉㩷㫋㪼㫄㫇㪅㩷䋨㷄䋩 㪄㪌 㪇 㪌 㪈㪇 㪈㪌 㪦㫌㫋㫊㫀㪻㪼㩷㪸㫀㫉㩷㫋㪼㫄㫇㪅㩷㩿㷄㪀 㪍㪅㪇㩷 㪋㪅㪇㩷 㪟㪼㪸㫋㫀㫅㪾㩷㪺㪸㫇㪸㪺㫀㫋㫐㩷㩿㫂㪮㪀 㪚㫆㫆㫃㫀㫅㪾㩷㪺㪸㫇㪸㪺㫀㫋㫐㩷㩿㫂㪮㪀 㪋㪅㪌㩷 㪊㪅㪌㩷 㪊㪅㪇㩷 㪉㪅㪌㩷 㪉㪇 㪉㪌 㪊㪇 㪊㪌 㪋㪇 㪦㫌㫋㫊㫀㪻㪼㩷㪸㫀㫉㩷㫋㪼㫄㫇㪅㩷䋨㷄䋩 㪌㪅㪇㩷 㪋㪅㪇㩷 㪊㪅㪇㩷 㪉㪅㪇㩷 㪋㪌 㪄㪈㪇 㪄㪌 㪇 㪌 㪈㪇 㪦㫌㫋㫊㫀㪻㪼㩷㪸㫀㫉㩷㫋㪼㫄㫇㪅㩷㩿㷄㪀 4-2 㪈㪌 SHARP(CHINA) INVESTMENT CO., LTD CHAPTER 5. DISASSEMBLY PROCEDURE If, in carrying out repairs and modifications, the work requires the use of arc- and flame-producing apparatus, such as welding, brazing and solderingequipment, this work shall only be started after the rooms have been thoroughly ventilated. While the work is being carried out, the mechanical venti-lation, if any, shall be kept in constant operation and all windows and doors kept open. In the case of repairs to parts of the refrigerant circuit, it maybe necessary that not only the workman but also a second person shall be present for observation and assistance.Necessary protective equipment shall be available and, in the case of open flames or arcs, fire extinguishing apparatus shall be ready to hand.Welding and brazing shall be carried out by qualified workmen. [1] INDOOR UNIT 1) Open the open panel and remove it. 4) Loosen the screws on the terminal board and remove the unit-tounit wiring connected with the board. 2) Remove a screw fixing the cord holder. 5) Slide out the 2 air filters. 3) Remove the cord holder. 6) Remove 5 screws fixing the front panel. 5-1 SHARP(CHINA) INVESTMENT CO., LTD 8) Remove the thermistor suppertor and the thermistor clip.Remove a screw fixing the earth wire. 7) Unfasten the front panel and pull forward it slightly. (4 circled spotsin the picture are hooked.) 9) Remove the screw fixing on the control box cover from the control Open the horizontal louver. box and pull it away. Back 10) Remove the 3 screw and the 5 connectors and remove the control Horizontal Louver Pull the front panel toward in the direction shown the picture. box. Another one is iner 5-2 SHARP(CHINA) INVESTMENT CO., LTD 11) Remove the horizontal louver fromcabinet while warping. 12) Remove the two screw and remove the vane motor. b) Remove the tube cover. •Insert the (–) screwdriver to A hole, D clip and then lean it to theright as lifting B part. c) Remove the evaporator from the cabinet. •Take off the catch of the tube cover from the plate and movethe evapo 13) Remove the water drainge assembly and take off . D 14) a) Remove the 4 screws fixing the side left and side right. 5-3 SHARP(CHINA) INVESTMENT CO., LTD 15) Loosen the screw of cross flow fan and separate the cross flow fan When assembling them, insert the motor shaft in the boss of thecross and the fan motor flow fan to the ring position. Ring [2] OUTDOOR UNIT 1)The fixed screw of control box cover is removed and control 3) The 2 screws on the left-hand side of top plate ass’y is removed. boxcover is removed. 4)The screw on the left-hand side of grille is removed 2)The 2 screws on the right-hand side of top plate ass’y is removed. 5-4 SHARP(CHINA) INVESTMENT CO., LTD 5)The screw on the right-hand side of front panel is removed 9) Unscrew the 4 screws on the back side of of right plate and removed the right plate. 6)The screw on the left-hand side of front panel is removed 10) Unscrew the 4 screws on the side left grille and removed the left grille. 7) The 3 screws of the front of a front panel is removed. 8)The 5 screws on the right-hand side of right plate is removed. 5-5 SHARP(CHINA) INVESTMENT CO., LTD 11) Remove the connectors and reactor in the control box. 14) Remove the compressor covers 1 and 2. 15) Remove the nut, and remove the terminal cover. 12)Remove the 2 screws fixed the control box. 16) Remove the lead wire and the cover gasket. 17) Remove the compressor cover. 13) Remove the 3 screws fixed the bulkhead plate. 5-6 SHARP(CHINA) INVESTMENT CO., LTD 18) Remove the 3 thermistors. [3] CONTROL BOX 1.Control unit box's Approach to decomposition. 1) Take off lead wires from terminal assembly. (Blue wire,Brown wire,Black wire) 19) Thermistor position. Discharge Temp. 2) Take off screw (earth). Take off earth lead wire(green/yellow) from electronic box. Outside air Temp. Outside pipe Temp. 20) Remove the outdoor fan. 3) Take off box cover. 19) Unscrew the 2 screws and remove the motor angle. Box cover 4) Take off screws 6 PCS) 5-7 SHARP(CHINA) INVESTMENT CO.,LTD CHAPTER7.INSTALLATION MANUL 795 190 40 280 40 150 95 7-1 SHARP(CHINA) INVESTMENT CO.,LTD 80 70 10 7-2 SHARP(CHINA) INVESTMENT CO.,LTD 7-3 SHARP(CHINA) INVESTMENT CO.,LTD 80 70 10 (1) 7-4 SHARP(CHINA) INVESTMENT CO.,LTD CHAPTER 6. OPERATION MANUAL 6-1 SHARP(CHINA) INVESTMENT CO., LTD 6-2 SHARP(CHINA)INVESTMEN T 50 13 CO., LTD 50 3 6- 3 SHARP(CHINA) INVESTMENT CO., L TD 6-4 SHARP(CHINA) INVESTMENT CO., LTD 21 27 6-5 46 18 24 7 AY-X9PSR/AY-12PSR PartsGuide PARTS GUIDE ROOM AIR CONDITIONER MODEL INDOOR UNIT AY-X9PSR AY-X12PSR OUTDOOR UNIT AE-X9PSR AE-X12PSR CONTENTS [1] INDOOR UNIT PARTS [4] OUTDOOR UNIT PARTS [2] ACCESSORY PARTS [5] OUTDOOR PACKING PARTS [3] INDOOR PACKING PARTS Parts marked with " " are important for maintaining the safety of the set. Be sure to replace these parts with specified ones for maintaining the safety and performance of the set. This document has been published to be used for after sales service only. The contents are subject to change without notice. SHARP(CHINA) INVESTMENT CO., LTD [1] INDOOR UNIT PARTS AY-X9PSR/AY-X12PSR 1 2 3 4 27 5 26 6 7 25 24 8 9 23 22 21 20 19 10 11 18 17 16 15 14 13 12 2 SHARP(CHINA) INVESTMENT CO., LTD AY-X9PSR No. Part No. Part Name Q’ty Remark 1 PPLTNA161JBWZ Installation Plate 1 2 LCHS-A674JBF A Base 1 3 NFANCA15 5JBKZ Cross Fan 1 4 NBRG-A075JBE Z Bearing Mount 1 5 DEVA-A582JBKZ Evaporator 1 6 CSRA-A896JBKZ Water Drainage Assembly 1 7 MLOV-A588JBFA Vertical Vane Assembly 2 8 GWAK-A420JBF A Face Fra m e 1 9 LHLD-B288JBFA Screw Cover 3 10 PFILMA289JBE A Air Filter 2 11 HPNL-B314JBR A Front Panel 1 12 QACC-A362JBZZ Power Supply Cord 1 13 MLOV-A58 9JBF A Vane 1 14 PHOS-A067JBEZ Drainage Hose 1 15 CDECQA084JBKZ Display PCB Cover 1 16 RLCDSA127JBZ Z Display PCB 1 17 HDECQA533JBFA Display PCB Box 1 18 LHLD-B289JBFA Cable Clamp 1 19 DSGY-F199JBKZ Main PCB 1 20 DBOX-A15 6JBKZ Electrical Box 1 21 CMOTLB546JBEZ Vane Motor 1 22 LHLD-B290JBFZ Sensor Holder 1 23 CMOTLB547JBEZ Indoor Motor 1 24 PCOV-C123JBFZ Indoor Motor Cover 1 25 RTRNWA070JBZZ Transformer 1 26 RH-HXA191JBZZ Indoor Sensor Assembly 1 27 PCOV-C124JBFZ In And Out Pipe Fixer 1 3 SHARP(CHINA) INVESTMENT CO., LTD AY-X12PSR No. Part No. Part Name Q’ty Remark 1 PPLTNA161JBWZ Installation Plate 1 2 LCHS-A674JBF A Base 1 3 NFANCA15 5JBKZ Cross Fan 1 4 NBRG-A075JBE Z Bearing Mount 1 5 DEVA-A583JBKZ Evaporator 1 6 CSRA-A896JBKZ Water Drainage Assembly 1 7 MLOV-A588JBFA Vertical Vane Assembly 2 8 GWAK-A420JBF A Face Fra m e 1 9 LHLD-B288JBFA Screw Cover 3 10 PFILMA289JBE A Air Filter 2 11 HPNL-B314JBR A Front Panel 1 12 QACC-A362JBZZ Power Supply Cord 1 13 MLOV-A58 9JBF A Vane 1 14 PHOS-A067JBEZ Drainage Hose 1 15 CDECQA084JBFA Display PCB Cover 1 16 RLCDSA127JBZZ Display PCB(Digital) 1 17 HDECQA533JBFA Display PCB Box 1 18 LHLD-B289JBFA Cable Clamp 1 19 DSGY-F199JBKZ Main PCB(Digital) 1 20 DBOX-A15 6JBKZ Electrical Box 1 21 CMOTLB546JBEZ Vane Motor 1 22 LHLD-B290JBFZ Sensor Holder 1 23 CMOTLB547JBEZ Indoor Motor 1 24 PCOV-C123JBFZ Indoor Motor Cover 1 25 RTRNWA070JBZZ Transformer 1 26 RH-HXA191JBZZ Indoor Sensor Assembly 1 27 PCOV-C124JBFZ In And Out Pipe Fixer 1 4 SHARP(CHINA) INVESTMENT CO., LTD [2] ACCESSORY PARTS 1 2 3 ACCESSORY PARTS No. Part No. Part Name Q’ty 1 CRMC-A891JBEZ REMOTE CONTROL 1 2 TINSJB281JBRZ INSTALLTION MANUAL 1 TINSJB280JBRZ OPERATION MANUAL 1 3 Remark [3] INDOOR UNIT PARTS 1 2 3 (4) t Foaming INDOOR PACKING PARTS No. Part No. Part Name Q’ty Remark 1 SPADBA703JBEZ Left Foaming 1 2 SPADBA703JBEZ Right Foaming 1 3 SPAKCE433JBEZ Indoor Carton 1 for AY-X9PSR 4 SPAKCE466JBEZ Indoor Carton 1 for AY-X12PSR SHARP(CHINA) INVESTMENT CO., LTD [4] OUTDOOR UNIT PARTS AE-X9PSR/AE-X12PSR 6 7 3 4 5 2 1 29 28 8 27 26 25 24 9 23 22 21 20 19 18 17 10 11 12 6 13 14 15 16 SHARP(CHINA) INVESTMENT CO., LTD AE-X9PSR No. Part No. Part Name Q’ty Remark 1 CCAB-A597JBKZ Top cover 1 2 DCoN-A784JBPZ Condenser 1 3 LANGKA345JBPZ Outdoor motor supporter 1 4 CMoTLB548JBEZ Outdoor motor 1 5 NFANPA154JBEZ Propeller fan 1 6 PPLT-A990JBTA Left grille supporter 1 7 GGADUA015JBEA Left grille 1 8 GCAB-A486JBTA Front plate 1 9 GGADPA028JBFA Fan guard 1 10 FCMPRA374JBKZ Compressor and accessories 1 11 FVLV-A301JBKZ 4-way valve 1 12 CVLV-B263JBKZ 4-way valve assembly 1 13 CCHS-B413JBYZ Base 1 14 PPLT-A991JBTA Right plate 1 15 DVLV-B426JBK Z Two-way valve 1 16 PPLT-A992JBPZ Valve supporter 1 17 DVLV-B425JBKZ Three-way valve 1 18 JHNDPA035JBF A Electrical box cover 1 19 LHLD-AA01SRFZ Cable clamp 1 20 PDAi-A304JBWZ Terminal 1 21 PBoX-A604JBPZ Electrical box 1 this is assembly 22 QTANZA097JBZZ Power source board 1 23 DSGY-F210JBKZ Inverter module 1 24 LANGKA344JBPZ Radiator 1 25 RCiLZA059JBZZ Inductor 1 26 RH-HXA194JBZZ Pipe Temp. sensor and outdoor 1 Temp. sensor 27 RH-HXA195JBZZ Discharge Temp. sensor 1 28 PSKR-A423JBPZ Partition plate 1 29 CCPY-A333JBKZ Capillary assemb ly 1 7 SHARP(CHINA) INVESTMENT CO., LTD AE-X12PSR No. Part No. Part Name Q’ty Remark 1 CCAB-A597JBKZ Top cover 1 2 DCON-A785JBPZ Condenser 1 3 LANGKA345JBPZ Outdoor motor supporter 1 4 CMOTLB548JBEZ Outdoor motor 1 5 NFANPA154JBEZ Propeller fan 1 6 PPLT-A990JBTA Left grille supporter 1 7 GGADUA015JBEA Left grille 1 8 GCAB-A486JBTA Front plate 1 9 GGADPA028JBFA Fan guard 1 10 FCMPRA375JBKZ Compressor and accessories 1 11 FVLV-A301JBKZ 4-way valve 1 12 CVLV-B264JBKZ 4-way valve assembly 1 13 CCHS-B413JBYZ Base 1 14 PPLT-A991JBTA Right plate 1 15 DVLV-B426JBK Z Two-way valve 1 16 PPLT-A992JBPZ Valve supporter 1 17 DVLV-B427JBKZ Three-way valve 1 18 JHNDPA035JBFA Electrical box cover 1 19 LHLD-AA01SRFZ Cable clamp 1 20 PDAI-A304JBWZ Terminal 1 21 PBOX-A604JBP Z Electrical box 1 this is assembly 22 QTANZA098JBZZ Power source board 1 23 DSGY-F210JBKZ I n v e r t e r m o d ul e 1 24 LANGKA344JBPZ Radiator 1 25 RCiLZA059JBZZ I nd u c t o r 1 26 RH-HXA194JBZZ Pipe Temp. sensor and outdoor 1 Temp. sensor 27 RH-HXA195JBZZ Discharge Temp. sensor 1 28 PSKR-A423JBPZ Partition plate 1 29 CCPY-A334JBKZ Capillary assembly 1 8 SHARP(CHINA) INVESTMENT CO., LTD [5] OUTDOOR PACKING PARTS 2 3 4 1(5) PACKING PARTS No. Part No. Part Name Q’ty 1 SPAKCE434JBEZ Cabinet carton 1 2 SPADBA706JBFZ Cover foaming 1 3 SPADBA705JBFZ Base foaming 1 4 SPAKCE435JBEZ Base carton 1 5 SPAKCE468JBEZ Cabinet carton 1 Remark for AE-X9PSR for AE-X12PSR 9
advertisement
Key Features
- Microcomputer control system
- Compressor delay operation
- Four-way valve control in heating mode
- ON/OFF operation
- Auto restart
- FULL POWER Operation
- Compressor discharge overheat prevention control
- Voltage prevention
- Over current prevention
- Compressor drive prevention
Frequently Answers and Questions
What is the purpose of the compressor delay operation?
The compressor delay operation prevents the compressor from restarting immediately after it has been turned off. This helps to protect the compressor from damage.
How does the four-way valve control work in heating mode?
When the unit operates in heating mode, the compressor starts up after the four-way valve has started up for 5 seconds. The four-way valve shuts down after the compressor stops for 2 minutes when the unit shuts down.
What is the purpose of the FULL POWER operation?
The FULL POWER operation allows the air conditioner to operate at maximum power to cool or warm the room rapidly.
What is the purpose of the auto restart function?
The auto restart function allows the air conditioner to automatically restart in the same setting which was active before a power failure.
What is the purpose of the defrosting function?
The defrosting function helps to prevent frost from accumulating on the outdoor unit. This ensures that the air conditioner can operate efficiently and effectively.