GB.GOLDLP.160901 Operation and Maintenance Instructions GOLD LP Applicable to program version 3.02 and newer versions The document was originally written in Swedish. We reserve the right to alter specifications without notice. www.swegon.com 1 GB.GOLDLP.160901 Content 1 GENERAL..................................... 3 9 FUNCTIONS............................... 17 11 READINGS............................... 40 1.1 Range of Application.................................3 1.2 Mechanical Design....................................3 1.3 Control System.........................................3 1.4 Environmental Documentation..................3 1.5 The Components of the Air Handling Unit.4 9.1 Temperature...........................................17 9.2 Temperature Regulation..........................17 9.2.1.1 ERS Regulation...............................18 9.2.1.2 Supply Air Regulation.....................19 9.2.1.3 Extract Air Regulation.....................19 9.2.2 Outdoor Temperature Compensation.20 9.2.3 Summer Night Cooling......................21 9.2.4 Intermittent Night-time Heating.........22 9.2.5 Morning BOOST................................23 9.2.6 Setpoint Temperature Displacement...23 9.2.7 External Temperature Sensors............24 9.3 Flow/Pressure..........................................25 9.3.1 Fan Regulation..................................25 9.3.1.1 Flow Regulation..............................25 9.3.1.2 Pressure Regulation........................25 9.3.1.3 Demand Control.............................25 9.3.1.4 Slave Control..................................25 9.3.1.5 Clean Air Control............................26 9.3.2 Outdoor Temperature Compensation............................................27 9.3.3 Downspeed Control of Fan Speed to Min. Set Point, Airflow/pressure..................28 9.3.4 To adjust the flow of the slave fan......28 9.4 To Activate the GOLD SD Filter Monitoring Function.............................28 9.5 Operation...............................................29 9.5.1 Switch clock......................................29 9.5.2 Extended Operation...........................29 9.5.3 Summer time/Winter time.................29 9.6 Heating...................................................30 9.6.1 Heat exchanger.................................30 8.6.1.1 Defrosting the rotary heat exchanger..........................................30 9.6.2 Pre-/Reheating...................................31 9.6.3 Heating BOOST.................................31 9.7 Cooling...................................................32 9.7.1 Operation..........................................32 9.7.2 Cooling Regulation (Control).............32 9.7.3 Periodic Operation.............................33 9.7.4 Regulation Speed..............................33 9.7.5 Outdoor Temperature Limit................33 9.7.6 Restart Time......................................33 9.7.7 Cooling Min Air Flow.........................33 9.7.8 Neutral Zone.....................................33 9.7.9 Cooling BOOST.................................33 9.8 Humidity.................................................34 9.9 Input/output connections........................35 9.10 IQnomic Plus.........................................36 9.11 All Year Comfort...................................37 9.12 OPTIMIZE..............................................38 12 MANUAL TEST........................ 40 2 SAFETY PRECAUTIONS............... 5 2.1 Safety Isolating Switch/Main Switch...........5 2.2 Risks ........................................................5 2.3 Safety Guards...........................................5 3 INSTALLATION............................ 6 4 COMMISSIONING....................... 6 4.1 General.....................................................6 4.2 Adjusting the Duct System ......................... and Air Devices.......................................7 4.2.1 Adjustment Sequence..........................7 4.2.2 Adjustment Procedure.........................7 4.3 To Adjust the Pressure Balance ..................8 4.3.1 General...............................................8 4.3.2 To Ensure the Correct Leakage Direction.........................................8 5 HAND-HELD MICRO TERMINAL AND HOW TO USE THE MENUS.... 9 5.1 HAND-HELD MICRO TERMINAL.................9 5.1.1 General...............................................9 5.1.2 Buttons...............................................9 5.1.3 Display Screen.....................................9 5.1.4 Abbreviations......................................9 5.2 Menu tree...............................................10 MAIN MENU................................ 10 6 MAIN MENU.............................. 11 6.1 General...................................................11 6.2 Selection of Language.............................11 6.3 Changing Operating Mode.....................11 6.4 Settings..................................................11 7 USER LEVEL............................... 12 7.1 Temperature...........................................12 7.1.1 Readings...........................................12 7.1.2 Settings.............................................12 7.2 Air flow/Pressure.....................................13 7.2.1 Readings...........................................13 7.2.2 Settings.............................................13 7.3 Switch clock............................................14 7.4 Filters......................................................14 7.4.1 Readings...........................................14 7.4.2 Calibration - Filters............................14 7.4.3 Calibration - Rotary Heat Exchanger...14 7.5 Air Adjustment........................................15 7.6 Alarms....................................................15 8 INSTALLATION LEVEL............... 16 8.1 Menu Survey...........................................16 2 www.swegon.com 10 AUTOMATIC FUNCTIONS....... 39 10.1 General.................................................39 10.1.1 Starting Sequence...........................39 10.1.2 Cooling Recovery.............................39 10.1.3 Zero Point Calibration......................39 10.1.4 Anti-frost Monitoring Function – Air Heater for Hot Water..................................39 10.1.5 Additional cooling – Electric Air Heater.......................................39 10.1.6 Additional running Heat Exchanger..........................................39 10.1.7 Density-corrected Airflow................39 10.1.8 Carry-over Control...........................39 10.1.9 Calculaton of the efficiency of the rotary heat exchanger.................................39 13 ALARM SETTINGS................... 41 13.1 Fire Alarms............................................41 13.2 External Alarms.....................................41 13.3 Alarm Limits..........................................41 13.4 Alarm Priority........................................41 14 HAND-HELD TERMINAL......... 42 14.1 Language..............................................42 14.2 Air flow unit..........................................42 14.3 Min/Max Adjustment............................42 14.4 Base Settings.........................................42 15 COMMUNICATION.................. 43 15.1 EIA-485................................................43 15.2 Ethernet................................................43 16 SERVICE LEVEL........................ 43 17 MAINTENANCE....................... 44 17.1 Filter Change........................................44 17.1.1 To Remove the Filters.......................44 17.1.2 To Install New Filters........................44 17.2 Cleaning and Inspection........................44 17.2.1 General...........................................44 17.2.2 Filter Spaces....................................44 17.2.3 Heat Exchanger...............................44 18.2.4 Fans and Fan Spaces........................44 17.3 Performance Checks.............................44 18 ALARMS AND FAULT TRACING........................... 45 18.1 General.................................................45 18.1.1 A and B Alarms................................45 18.1.2 Resetting of alarms..........................45 18.1.3 Changing Alarm Settings.................45 18.2 Alarm Descriptions with Factory Settings............................................46 19 INFORMATIVE MESSAGES ..... 52 20 TECHNICAL DATA................... 53 20.1 Dimensions, GOLD LP one-piece unit.....53 20.2 Electrical Equipment Cubicle.................54 20.2.1 Internal Connections.......................54 20.2.2 Connection to Terminal Blocks.........56 20.3 Electrical Data.......................................57 20.3.1 Air Handling Unit.............................57 20.3.2 Fans................................................57 20.3.3 Electrical equipment cubicle.............57 20.3.4 Heat Exchanger Motor.....................57 20.3.5 Control Inaccuracy...........................57 21 ANNEXES................................ 58 21.1 Compliancy Declaration........................58 21.2 Commissioning Record..........................59 21.3 Ecodesign data......................................70 We reserve the right to alter specifications without notice. GB.GOLDLP.160901 1 GENERAL 1.1 Range of Application The GOLD LP is a complete air handling unit with built-in control equipment. The air handling units are designed for comfort ventilation and can be utilised in buildings such as offices, schools, day nurseries, public buildings, shops and residential buildings. The GOLD LP units are one-piece air handling units. If supplementary function sections such as dampers and air coolers are required, they must be installed in the ductwork. In order to fully obtain all the benefits the GOLD LP has to offer, it is important keep in mind the air handling unit’s special characteristics in conjunction with designing the project, installing the unit, adjusting it and operating the system. The unit must be installed indoors. Important! Always read the safety precautions in Section 2 that explain the risks involved in running the unit and designate who shall be permitted to operate and service the unit, and carefully follow the installation instructions provided in each paragraph. The product identification plate is located on the electrical equipment cubicle. Refer to the particulars on the product identification plate when you contact Swegon. 1.2 Mechanical Design The GOLD LP is available in two sizes. The external sheet metal surfaces of the unit are painted white, NCS S 0502-G, except for the back side which consists of aluminium-zinc plated sheet steel.. The inner skin is predominantly made of aluminium-zinc plated sheet steel. The casing, including the inspection panels, has a 30 mm thick intervening slab of mineral wool insulation. The GOLD LP is equipped with Class F7 bag filters. DThe type RECOnomic rotary heat exchanger is variable speed controlled and has a peak temperature efficiency of 85%. The supply air and extract air fans are direct-driven plenum fans. The fans are equipped with EC motors that provide high efficiency across the entire operating range. 1.3 Control System The IQnomic control system is microprocessor-based and is integrated into the unit. It controls and regulates the fans, heat exchanger, temperatures, airflows, operating times and a large number of internal and external functions as well as alarms. 1.4 Environmental Documentation Environmental Documentation with the Dismantling Instructions for Recycling and the Environmental Product Declaration can be downloaded from our website: www. swegon.com. The air handling unit is designed in such a way that it can be dismantled into its natural parts for scrapping. When the unit has ended its useful product life, the services of an accredited recycling company should be utilised for disposal. The recyclable weight of the GOLD LP is about 94% of its initial weight. Swegon AB is associated with the REPA Register, No. 5560778465. Contact Swegon AB, Phone: +46 (0)512-322 00, if you have any questions regarding the dismantling instructions or the air handling unit’s impact on the environment. We reserve the right to alter specifications without notice. www.swegon.com 3 GB.GOLDLP.160901 1.5 The Components of the Air Handling Unit The individual components each specified below in a simplified and diagrammatical description. 5 3 2 6 4 7 8 9 1 11 2 1 Fig 1a 21 20 19 18 17 16 15 14 13 10 12 1 Outdoor air Supply air Extract air Exhaust air 2 Fig 1b The air handling units are supplied in the right-hand version as shown in Fig. 1a. Coversion to the left-hand version as shown in Fig. 1b can be carried out by making a simple adjustment in the control equipment. In the left-hand version (Fig. 1b), the components marked with an asterisk change function and designation (the components are named according to whether they are for supply air or extract air). The arrangement of the components and their designations 1 OUTDOOR AIR* (Left-hand version: Extract air) 2 3 4 5 6 7 8 4 EXHAUST AIR* (Left-hand version: Supply air) Extract air fan* with motor and motor controller Pressure sensor, extract air fan* (Position on function selector switch = 1) Electrical equipm. cubicle with control unit Hand-held Micro Terminal Main switch/Safety switch Extract air filter* www.swegon.com Left-hand version 9 EXTRACT AIR* (Left-hand version: Outdoor air) 10 SUPPLY AIR* (Left-hand version: Exhaust air) 11 Supply air temp. sensor (to be mounted in supply air duct) 12 Supply air fan* with motor and motor controller 13 Extract air temperature sensor* 14 Pressure sensor, supply air fan* (Position on function selector switch = 2) 15 Heat exchanger 16 Drive motor, heat exchanger 17 Sensor, rotation monitor 18 Outdoor air temperature sensor* 19 Mounting bracket for securing the unit in position, 4 brackets 20 Supply air filter* 21 Slide rails for the inspection panels We reserve the right to alter specifications without notice. GB.GOLDLP.160901 2 SAFETY PRECAUTIONS All staff concerned must acquaint themselves with these instructions before beginning any work on the unit. Any damages to the unit or parts of it due to improper handling or misuse by the purchaser or the fitter cannot be considered subject to guarantee if these instructions have not been followed correctly. Warning Only a qualified electrician or service personnel trained by Swegon shall be permitted to modify the air handling unit in conjunction with electrical installations or the wiring of external functions. 2.1 Safety Isolating Switch/Main Switch On the GOLD LP one-piece unit, the safety isolating switch is externally positioned on the electrical equipment cubicle. 2.3 Safety Guards The lockable inspection panels serve as a safety guard for the fans/heat exchanger. The cover over the power supply unit in the electric equipment cubicle serves as a safety guard for this unit. Only a qualified electrician or trained service technicians shall be allowed to remove the safety guards. Warning The power supply to the unit shall be isolated by switching off the safety isolating switch before removing the safety guard. All the inspection panels must be closed and the cover of the electrical equipment cubicle must be fastened while the air handling unit is operating. The air handling unit must normally be started and stopped from the hand-held micro terminal; not by switching the safety isolating switch on and off. Always switch off the safety isolating switch before servicing the unit if not otherwise specified in the pertinent instructions. 2.2 Risks Warning Before carrying out any work, make sure that the power supply to the air handling unit has been switched off. Risk areas with moving parts Typical moving parts are fan impellers and drive pulleys of the rotary heat exchanger. Inspection panels can only be opened using a special key, they therefore function as safety guards for fans and the heat exchanger. If the ducts are not connected to the fan outlets, the outlets must be fitted with a safety guard (wire mesh screen). Warning The inspection panels on the filter/fan sections must not be opened while the unit is in operation. Under normal operating conditions, use the stop button on the hand-held terminal to stop the air handling unit. Wait until the fans have stopped rotating before opening the inspection panel. The air pressure inside the fan section is positive, which means that the door can fly open. We reserve the right to alter specifications without notice. www.swegon.com 5 GB.GOLDLP.160901 3 INSTALLATION See the specific installation instructions. 4 COMMISSIONING 4.1 General Sequence for commissioning: 1. Check that there are no foreign objects in unit, ducting system or functional sections. 2. Turn the safety isolating switch to the ON position (I). 3. Select the language desired, if you have not already done so. See Section 6.2 or 14.1. 4. The unit has factory settings which make it ready to use. See Section 21.2 Commissioning record. However, in many cases, these settings need to be adjusted to suit the current installation. Program the switch clock, operating conditions, temperatures, airflows and functions according to the procedures in Sections 5-16. Select whether l/s, m3/s or m3/h shall be used as the flow unit. (INSTALLATION LEVEL in the HAND-HELD MICRO TERMINAL menu). Fill out the Commissioning Record and save it in the document pocket of the unit. 5. Activate, if needed, manual or auto operation (MAIN MENU) or lock the speed of the fans (AIR ADJUSTMENT menu). Adjust the ducting system and air devices as described in Section 4.2. 6. Finish off with a filter calibration as described in Section 7.4.2. 6 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 4.2 Adjusting the Duct System and Air Devices In order to prevent the fans from consuming more power than necessary, it is important to keep the pressure drop in the system as low as possible. It is also important that ducting systems and air devices are correctly adjusted to provide the comfort expected. When adjusting air devices and the duct system installed in combination with the GOLD, it is appropriate to follow the proportionality method. This means that the proportion between the airflows in branch ducts stays constant even if the airflow in the main ducts is changed. The same proportion applies to the air devices in the installation. When adjusting the ducting system there is provision for locking the speed of the fans in the unit to a specific preset flow rate, see Section 6.5. 4.2.1 Adjustment Sequence The system should be adjusted in the following order: 1. Adjust of the air devices in each branch duct. 2. Adjust the branch ducts. 3. Adjust the main ducts. 4.2.2 Adjustment Procedure 1. Set all the air devices and dampers to the fully open position. 2. Calculate the ratio of the airflow reading to the design airflow of all the air devices, branch ducts and main ducts. The air device in every branch that has the lowest ratio should be fully open. Use this air device as an INDEX AIR DEVICE. The same applies to branch dampers and main dampers. When you’ve completed the adjustments, one air device in every branch, one branch damper and one main damper should consequently be fully open. 3. Start adjusting the main duct that has the highest ratio and the branch duct in the main duct that has the highest ratio. Starting from this point enables you to “press” the air in front of you toward the sections of the system that have the least air. 4. Adjust the last air device on the duct branch so that it will have the same ratio as the index device. This air device will serve as the REFERENCE AIR DEVICE. Often it is the last air device on the branch that has the lowest ratio and should be open. In this case, the same air device serves as the index device and reference device. 5. Throttle the other air devices in the branch to the same ratio as the reference device. Note! The ratio in the reference device will change every time another air device is throttled, so in practice the ratio for the reference device can be set slightly higher. The reference device must be measured in between each air device throttled. 6. Go to the branch that had the next highest ratio and adjust the air devices there, etc. Note! All branch dampers should be fully open until all air devices have been adjusted. 7. Throttle the branch damper that had the highest ratio to the same ratio that the branch of the lowest ratio had. Note! Keep in mind that the index damper changes ratio; proceed as described in item 5. 8. When all branches have been adjusted, throttle the main dampers in the same manner. Also see the example below on how to carry out adjustments. Example on how to carry out adjustments – Start adjusting duct branch B, since this one has the highest ratio. – The last air device, B3, has the lowest ratio and should be fully open. Adjust the other air devices, B1 and B2, so that these will have the same ratio as air device B3 (see item 5 above). – Now adjust the air devices in branch duct C. Air device C4 should be fully open; throttle the others to the same ratio. – Adjust the air devices in branch duct A. The index air device here is air device A3, which means that you first throttle air device A4 (the reference device) to device A3:s ratio. Thereafter the others are adjusted to the same ratio as air device A4. – Throttle branch damper B to the same ratio as branch damper A, throttle branch damper C to the same ratio as branch damper A. Check that all dampers have the same ratio. When the adjustment has been completed, 3 air devices and one branch damper should stand fully open to obtain the lowest possible pressure in the system. We reserve the right to alter specifications without notice. qp = design airflow (l/s) qm = airflow reading (l/s) qm K (Ratio) = qp www.swegon.com 7 GB.GOLDLP.160901 4.3 To Adjust the Pressure Balance 4.3.1 General There should be a certain degree of negative pressure in the extract air section so that the direction of air leakage through the heat exchanger and the function of the purging sector will be correct. This ensures that extract air will not be transferred to the supply air. The pressure balance in the unit should be adjusted when the ventilation system has been fully installed and the airflows discharged from all the air diffusers and registers have been adjusted, and when the supply air and extract airflows are as they should be while the air handling unit is operating normally. 4.3.2 To Ensure the Correct Leakage Direction The pressure balance in the AHU is adjusted by repositioning a commissioning plate mounted in the extract air inlet. The commissioning plate is supplied separately and should be fitted by the fitter when the extract air duct is connected. See illustration. Connect a pressure gauge to the pressure measurement tappings of the air handling unit. The AHU has four pressure measurement tappings. The two tappings closest to the extract air duct should be used. The blue pressure measurement tapping is used for measuring the negative pressure in the extract air section and the white pressure measurement tapping is used for measuring the negative pressure in the supply air section. The pressure measurement tappings are situated by the junction hood. Commissioning plate Pressure measurement tappings – leakage direction (AHU shown in the right-hand version) Note that both pressure measurement tappings are used for measuring negative pressure. MEASURED VALUES The negative pressure in the extract air section should be greater or the same as the negative pressure in the supply air section. - (blue) + (white) If the negative pressure in the extract air section is the same or up to 20 Pa greater than the negative pressure in the supply air section, then you have finished commissioning the unit. DEVIATIONS If the negative pressure in the extract air section is less than that in the supply air section, then you must carry out the following adjustment: EXTRACT AIR 2 1. Stop the air handling unit, open the inspection door to access the extract air filter. Blank off an appropriate number of holes in the commissioning plate using the plastic plugs supplied. 3. Close the inspection door and restart the AHU. 4. Measure the pressures. Repeat this procedure until the negative pressure in the extract air section is just as great or up to 20 Pa greater than the negative pressure in the supply air section (0–20 Pa). 8 www.swegon.com 5. If the negative pressure in the extract air section is greater than 20 Pa compared with the supply air section, although the commissioning plate is dismantled, the leakage and purging air flow will be greater than anticipated. This means that the actual extract air flow will deviate from the preset extract airflow. The deviation increases as the difference in pressure increases. We reserve the right to alter specifications without notice. GB.GOLDLP.160901 5 HAND-HELD MICRO TERMINAL AND HOW TO USE THE MENUS GOLD LP TUE 14:40 STOP MANUAL OPERATION STOP? 5.1 HAND-HELD MICRO TERMINAL 5.1.1 General The hand-held micro terminal consists of an encapsulated control box with a 3-metre long cable for connection to the air handling unit by means of a quick connector. The hand-held terminal has an illuminated display, 6 pushbuttons and a red LED for indicating alarms. 5.1.2 Buttons The buttons have the following functions: ENTER confirms your selection and proceeds to next menu level. ESCAPE reverts to the previous menu. ADVANCE UPWARD or to the LEFT. ADVANCE DOWNWARD or to the RIGHT. DECREASES the value of the highlighted setting. INCREASES the value of the highlighted setting. 5.1.3 Display Screen The display screen has 4 lines. Many of the menus however have several lines and these are shown line for line as you press the ADVANCE DOWNWARD button. The position indicator shows where you are in the menu. GOLD LP TUE 14:40 STOP MANUAL OPERATION STOP? Position indicator MAN/AUTO.OP SETTINGS 5.1.4 Abbreviations The following abbreviations are used in the menus SA = Supply air (E.g. SA FAN = Supply air fan) EA = Extract air OUTD = Outdoor air FV = Anti-frosting monitor HEAT EXCH = Heat exchanger We reserve the right to alter specifications without notice. www.swegon.com 9 GB.GOLDLP.160901 5.2 Menu tree MAIN MENU (Section 6) Important! The appearance of the menus varies depending on the type of air handling unit and functions selected. GOLD LP TUE 14:40 STOP MANUAL OPERATION STOP? GOLD LP TUE 14:40 MANUAL OPERATION STOP? MAN/AUTO.OP AUTO OPERATION MANUAL LOW SPEED MANUAL HIGH SPEED GOLD LP TUE 14:40 STOP? MAN/AUTO.OP SETTINGS USER LEVEL (Section 7) TEMPERATURE *TEMPERATURE* READINGS SETTINGS ALL YEAR COMFORT *ALL YEAR COMFORT* READINGS SETTINGS FLOW/PRESSURE *FLOW/PRESSURE* READINGS SETTINGS SWITCH CLOCK *SWITCH CLOCK* TIME/DATE TIME CHANNEL YEAR CHANNEL FILTERS *FILTERS* READINGS CALIBRATION AIR ADJUSTMENT *AIR ADJUSTMENT* LOCKS FAN SPEED TIME SETTING: 0 h ALARMS *ALARMS* ACTIVE ALARMS ALARM HISTORY INSTALLATION LEVEL (Section 8-16) 10 www.swegon.com INSTALLATION We reserve the right to alter specifications without notice. GB.GOLDLP.160901 6 MAIN MENU 6.1 General The main menu is normally shown if no other menu has been selected. The display automatically returns to the main menu after 30 minutes. The content in the menu changes depending on the operating mode selected other functions that affect the present operating mode and possible tripped alarms. GOLD LP TUE14:40 STOP MANUAL OPERATION STOP? GOLD LP TUE14:40 MANUAL OPERATION STOP? MAN/AUTO.OP GOLD LP TUE14:40 STOP? MAN/AUTO.OP SETTINGS AUTO OPERATION MANUAL LOW SPEED MANUAL HIGH SPEED 6.2 Selection of Language When the air handling unit is started up for the first time, a language selection menu is displayed. Select the language desired. If you want to change language at a later opportunity – or if you’ve selected the wrong language – you can change the language at INSTALLATION LEVEL under HAND TERMINAL. See Section 14.1. USER LEVEL INSTALLATION LEVEL 6.3 Changing Operating Mode You can start and stop the air handling unit or change over to manual or automatic operation from the main menu. The air handling unit should normally be started and stopped from the hand-held micro terminal; not by switching the safety isolating switch on and off. When the air handling unit is started up, menus for the various delays that are part of the starting sequence are shown. See also Section 10.1.1, Starting Sequence. 6.4 Settings When selecting SETTINGS in the main menu, you will advance to User Level and Installation Level. See Section 7. We reserve the right to alter specifications without notice. www.swegon.com 11 GB.GOLDLP.160901 7 USER LEVEL 7.1 Temperature The basic functions can be preset at INSTALLATION LEVEL and the values can be read and set at USER LEVEL. See also Section 9.2 in which the functions for temperature are described in detail. IMPORTANT! If you intend to substantially alter the temperature settings, you should first stop the air handling unit before doing so. 7.1.1 Readings Important! The appearance of the menus varies depending on the type of air handling unit and functions selected. TEMPERATURE *TEMPERATURE* READINGS SETTINGS *TEMPERATURE* READINGS SETTINGS ERS REGULATION 1 Used for checking the performance. 7.1.2 Settings ERS REGULATION 2 SUPPLY AIR REG. ERS REGULATION 1 The control unit regulates the relationship between the supply air and the extract air temperatures according to a factory preset curve. Settings (see the chart to the right as well): Value Setting Factory rangesettings Extract air temperature X1 10-40 °C 15 °C X2 10-40 °C 20 °C X3 10-40 °C 22 °C Supply air temperature Y1 10-40 °C 20 °C Y2 10-40 °C 18 °C Y3 10-40 °C 14 °C SUPPLY AIR REG. Settings: Value Setting Factory rangesettings Supply air temperature setpoint 15-40 °C* 21.5 °C EXTRACT AIR REG. Settings: Value Setting Factory rangesettings Extract air/room temp. Setpoint 15-40 °C* 21.5 °C Min. supply air temperature 13-25 °C* 15 °C Max. supply air temperature 18-45 °C* 28 °C *) The setting range can be changed. See 14.3, Min/Max Adjustment. Supply air temperature setpoint °C ERS REGULATION 2 The control unit regulates the relationship between the supply air and extract air temperatures according to a custom-plotted curve. The curve has three adjustable breakpoints. ERS Regulation 1 p Ste 20 1 Step 2 Breakpoint l tia 15 n re Step 3 e ff A /S EA di Step 4 10 15 20 25 Extract air temperature °C ERS Regulation 2 Y = Supply air temperature setpoint °C Settings (see the chart to the right as well): Value Setting Factory rangesettings Step 1-4 1 EA/SA Differential 1-5 °C* 2 °C Breakpoint (refers to 15-23 °C* 20 °C extract air temperature) EXTRACT AIR REG. 22 20 1 2 15 3 10 9 12 15 20 25 27 X = Extract air temperature °C 12 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 7.2 Air flow/Pressure Basic functions are set at INSTALLATION LEVEL and values are read and set at USER LEVEL. Therefore see also Section 9.3, in which the functions for flow/pressure are described in detail. AIR FLOW/PRESSURE *FLOW/PRESSURE* READINGS SETTINGS 7.2.1 Readings Used for performance checks. 7.2.2 Settings The functions selected at INSTALLATION LEVEL and the min. and max. airflows of each unit size (see the table below) determine which values can be set. Values for airflow (l/s, m3/s, m3/h), pressure (Pa) or input signal strength (%) can be preset depending on the function selected. LOW SPEED Must always be preset! The value for low fan speed cannot be higher than the value for high speed. Low speed can be set to 0, which means that the fan is standing still. HIGH SPEED Must always be preset! The value or pressure for high fan speed cannot be lower than the value for low fan speed. *FLOW/PRESSURE* READINGS SETTINGS LOW SPEED HIGH SPEED MAX. SPEED MIN/MAX. SPEED MAX SPEED Max speed is only appropriate for functions such as pressure regulation, Heating BOOST or Cooling BOOST. The value for max fan speed cannot be lower than the value for high fan speed. MIN/MAX SPEED Min/max fan speed is only appropriate for demand-controlled operation. The lowest and highest permissible flows are preset for each of the fans. This means that the fans will not operate outside these limits, regardless the load. Min/Max Airflows AIRFLOW MIN. FLOW GOLD LP MAX. FLOW GOLD LP m3/h * m3/s m3/h m3/s 05 300 0.08 1900 0.53 08 720 0.20 2600 0.74 SIZE * When entering settings, round off the values to the nearest adjustable step. We reserve the right to alter specifications without notice. www.swegon.com 13 GB.GOLDLP.160901 7.3 Switch clock Basic functions for the switch clock can be preset at INSTALLATION LEVEL under FUNCTIONS/OPERATION and the values can be read and set at USER LEVEL. SWITCH CLOCK *SWITCH CLOCK* TIME/DATE TIME CHANNEL YEAR CHANNEL TIME/DATE Settings: The current date and time can be set and adjusted whenever required. The switch clock automatically takes leap years into consideration. Automatic changeover between summer time/winter time to EU Standard has been preset. This changeover function can be blocked at INSTALLATION LEVEL under FUNCTIONS/OPERATION. Value TIME/DATE Day Time Date TIME CHANNEL Times and days can be set when the unit is to run at high speed, low speed or be stopped. Eight different time channels can be set. If the same in-operation times are to apply every day of the week (Mon-Sun), you need only program one time channel. Different operation times for each day of the week can be programmed by programming a time channel for each day (Mon-Fri, Sat-Sun or Mon, Tues, Wed, etc) The time can be set as 00:00-00:00 if the deviating in-operation period is desirable for the entire 24 hours period. YEAR CHANNEL The year channels make it possible to set deviating in-service times for parts of the day during certain parts of the year. Eight different year channels (yearly time schedules) can be set. The year channels over-modulate the time channel during the hours of the day and the days that the year channel is active. The year channel dates indicate the dates between which the year channel shall apply and the year channel hours indicate the hours of the day between which the year channel will steer the controller to operate the rotary heat exchanger at a specified speed. Other times within the year channel still apply to that time channel. The time can be set as 00:00-00:00 if the deviating in-operation period is desirable for the entire 24 hours period. Functions for summer night cooling, prolonged operation, etc., operate also when the year channel is active. 7.4 Filters (and anti-frosting function of rotary heat exchanger) There are two types of filter monitoring: Calculated filter monitoring (preset at factory) monitors the fan’s speed increase conditional on the degree of fouling in the filter. The calibration involves taking airflow and fan speed readings. An alarm is initiated when the fan speed has increased by 10% above the preset alarm limit. Filter monitoring with a pressure sensor (accessory) measures the pressure drop across the filter. The alarm limit is preset in Pa. 7.4.1 Readings When reading the filter status, the first value shows current value and the second value shows current alarm limit. 7.4.2 Calibration - Filters The filters should be calibrated for the first time in conjunction with commissioning, when the duct system, air devices and eventual adjustment plates have been fitted and adjusted; after that every time the filter media are changed. 14 www.swegon.com Setting Factory rangesetting Mon-Sun 00:00-23:59 Day/Month/Year Automatic Current Current TIME CHANNEL 1-8 Operation Time Period Low speed/High speed* High speed 00:00-23:59 00:00-00:00 Not active Not active Mon, Tues, Wed etc Mon-Fri Mon-Sun Sat-Sun YEAR CHANNEL 1-8 Operation Time Period Not active Stop/Low sp./High sp. 00:00-23:59 From Day/Month/Year To Day/Month/Year Not active 00:00-00:00 01/01/2005 01/01/2005 *) Shows Stop/Low speed/High speed if this function is selected at INSTALLATION LEVEL under FUNCTIONS/OPERATION. FILTERS *FILTERS* READINGS CALIBRATION *FILTERS* READINGS CALIBRATION *FILTER CALIBRATION* STD.FILTER PREFILTER HEAT EXCHANGER Calibration should be activated for both the supply air and the extract air if both filters are changed or for only for one airflow direction if only one filter has been changed. When filter calibration has been activated, the unit runs at high speed for about 3 minutes. After the filter has been calibrated, a speed increase of 10%, or a pressure rise (= fouling of the filters) of 100 Pa is permissible, after which an alarm is initiated indicating a fouled filter. The alarm limit can be changed at INSTALLATION LEVEL under ALARM SETTINGS. 7.4.3 Calibration - Rotary Heat Exchanger If the anti-frosting function accessory for heat exchanger is installed (see 9.6.1.1) calibration can be selected from this menu. When calibration R-HX is activated the fans are accelerated to high speed for about 3 minutes. We reserve the right to alter specifications without notice. GB.GOLDLP.160901 7.5 Air Adjustment The speed of the fans can be locked for up to 72 hours. This is practical when making air adjustments in the duct system and air devices. AIR ADJUSTMENT *AIR ADJUSTMENT* LOCKS FAN SPEED. TIME SETTING: 0 h The period desired is preset but can be interrupted earlier by selecting STOP in the menu or by changing the time setting to 0. 7.6 Alarms If an alarm is initiated, this is shown in the hand-held terminal both as clear text and by a blinking red diode. This menu enables you to read alarms quickly. ALARMS *ALARMS* ACTIVE ALARMS ALARM HISTORY ACTIVE ALARMS Shows alarms that are active but have not initiated an alarm signal in the display. This applies to alarms that have a long delay, i.e. airflow or temperature alarms. ALARM HISTORY The 10 most recent tripped alarms are shown. Alarm settings can be entered at INSTALLATION LEVEL under ALARM SETTINGS. For complete description of alarms, see Section 18. We reserve the right to alter specifications without notice. www.swegon.com 15 GB.GOLDLP.160901 8 INSTALLATION LEVEL 8.1 Menu Survey Important! The appearance of the menus varies depending on the type of air handling unit and functions selected. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER READINGS MANUAL TEST ALARM SET HAND TERMINAL COMMUNICATION SERVICE LEV. OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE *INSTALLATION* CODE: 0000 Code = 1111 *READINGS* TEMPERATURE FANS HEAT EXCHANGE Section 10 Automatic functions Section 9 Section 11 REGULATION SIGNALS IN/OUTPUTS HUMIDITY IQnomic Plus ALL YEAR COMFORT OPERATION TIME PROGRAMVERSIONS *MANUAL TEST* TEMPERATURE FANS HEAT EXCHANGE Section 12 REHEAT IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT *ALARM SETTINGS* FIRE ALARM EXTERNAL ALARMS ALARM LIMITS Section 13 ALARM PRIORITY *HAND TERMINAL INST* LANGUAGE AIR FLOW UNIT MIN/MAX SETTING Section 14 BASE SETTINGS *COMMUNICATION* EIA-485 ETHERNET *SERVICE LEV.* CODE: 0000 16 www.swegon.com Section 15 Section 16 We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9 FUNCTIONS 9.1 Temperature Basic functions can be set at INSTALLATION LEVEL and values are read and set at USER LEVEL. IMPORTANT! If you intend to substantially alter the temperature settings, you should first stop the air handling unit before doing so. 9.2 Temperature Regulation Select ERS Regulation, Supply air regulation or Extract air regulation. If ERS Regulation is selected, select between 1 and 2. Control sequence for ERS regulation and Supply air regulation: 1. The temperature efficiency of the air handling unit’s heat exchanger is modulated to provide max. heat recovery. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE * TEMPERATURE * TEMPERATURE REG OUTDOOR TEMP COMP SUMMER NIGHT COOL INTERM. NIGHT HEAT MORNING BOOST SETPOINT TEMP DISPL EXT. SENSORS Important! The appearance of the menus varies depending on the type of air handling unit and functions selected. 2. After that the air heater, if installed, will begin to generate heat. 3. If a downstream heating coil is not installed, or if the its output is not adequate, the supply air fan will be automatically and variably downspeed-regulated to convey air at a lower flow rate. A neutral zone can be preset, which allows a lower supply air temperature setpoint before regulation to a lower flow rate begins. See 8.3.4 When the supply airflow is regulated to a lower rate, the heat exchanger will have ”excess heat”, i.e. warm extract air, giving it capacity to maintain the supply air temperature required. As the supply airflow is regulated to a lower rate, the air pressure in the premises will become negative and this will instead cause outdoor air to be sucked in through leakage spots such as doors and windows. This outdoor air will then be heated by the ordinary heating system of the premises. Downspeed regulation to lower the airflow rate occurs from the current preset flow (high speed or low speed), down to half of this flow rate. The degree of regulation to a lower rate is also limited by the min flow setting of the unit. When preset flow for low speed is near the min flow rate, the effect of this regulation to a lower rate will be small. Control sequence for Extract air regulation: 1. The temperature efficiency of the air handling unit’s heat exchanger is modulated to provide max. heat recovery. 2. After that, the re-heating coil, if installed, will begin to generate heat. We reserve the right to alter specifications without notice. www.swegon.com 17 GB.GOLDLP.160901 FRT-reglering 1 Supply air temperature setpoint °C 9.2.1.1 ERS Regulation ERS regulation means Extract air temperature-Related Supply air temperature regulation. This means that the temperature of the supply air is regulated in relation to the temperature of the extract air. Under normal circumstances, the supply air temperature is regulated to be a few degrees lower than the extract air temperature. In this way, the heat exchanger will provide optimal performance, and this means excellent operating economy. ERS regulation is suitable for use when there is excess heat in the premises generated, for example, by machinery, lighting or people and the supply air devices in the premises are suitable diffusing air below room temperature. ERS REGULATION 1 The control unit regulates the relationship between the supply air and extract air temperatures according to a factory-preset curve. p Ste 20 Value range Step Breakpoint (refers to extract air temp.) EA/SA-Differential Setting setting 1 – 4 15-23 °C Factory 1-5 °C 2 °C 1 20 °C The setting range for the breakpoint and EA/SA differential is limited by the Min. and Max. settings at INSTALLATION LEVEL under HAND TERMINAL. ERS REGULATION 2 This is used when special needs and conditions are such that the factory preset ERS regulation 1 curve cannot provide the results required. Conditional on which settings are made, it may be necessary to install a post-heating coil. An individually adapted curve regulates the relationship between the supply air and extract air temperature. See the chart to the right. The following settings are possible at USER LEVEL under TEMPERATURE/SETTINGS: Value Extract air temperature Supply air temperature setpoint Setting Factory rangesetting X1 10-38 °C X2 11-39 °C X3 12-40 °C 15 °C 20 °C 22 °C Y1 10-40 °C Y2 10-40 °C Y3 10-40 °C 20 °C 18 °C 14 °C The setpoint displacement and summer night cooling functions can also affect the preset temperatures. 18 www.swegon.com Step 3 ff A -/S di EA Step 4 10 15 20 Extract air temperature °C 25 Factory setting means: If the extract air temperature is below 20 °C (breakpoint), the supply air temperature setpoint will be automatically regulated to be 2 °C (EA/SA differential) lower. If the extract air temperature is above 20 °C, the supply air temperature setpoint will follow the curve according to Step 1. ERS regulation 2 22 Y = Setpoint supply air temperature °C Settings: e er l ia nt See the chart to the right. The steps, breakpoint and EA/SA differential plotted in the curve can be changed at USER LEVEL under TEMPERATURE/SETTINGS. Step 2 Breakpoint 15 1 20 1 2 15 3 10 9 12 15 20 25 27 X = Extract air temperature °C Breakpoints according to factory setting means: If the extract air temperature is below 15 °C (X1) the setpoint for supply air temperature is constant 20 °C (Y1). If the extract air temperature is 20 °C (X2) the supply air temperature set point will be 18 °C (Y2). If the extract air temperature is above 22 °C (X3), the supply air temperature setpoint will be constantly 14 °C (Y3). We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9.2.1.2 Supply Air Regulation Supply air regulation involves keeping a constant supply air temperature without consideration to the load in the premises. This type of regulation can be used when the load and temperatures of the premises are predictable. In most cases a reheating coil needs to be installed; possibly a cooling coil as well. The following settings can be entered at USER LEVEL under TEMPERATURE/SETTINGS: Value Setting Factory rangesetting Supply air temperature setpoint 15-40 °C 21.5 °C Setting range for the setpoint is limited by Min. and Max. settings at INSTALLATION LEVEL under HAND TERMINAL. 9.2.1.3 Extract Air Regulation Extract air regulation involves keeping a constant temperature in the extract air duct (premises), by regulating the supply air temperature. This provides a uniform temperature in the premises regardless of the load and this type of regulation requires the installation of a reheating coil; possibly a cooling coil as well. The extract air temperature is measured by the temperature sensor inside the GOLD unit. If this internal temperature sensor does not give an adequate representative extract air temperature readings, an external room temperature sensor can be installed and wired to the control unit’s connection marked “Internal Bus-1”. The following settings can be entered at USER LEVEL under TEMPERATURE/SETTINGS: Value Setting Factory rangesetting Extract air-/room temp. setpoint 15-40 °C 21.5 °C Min. Supply air temperature 13-18 °C 15 °C Max. Supply air temperature 25-45 °C 28 °C Setting range for the various values is limited by Min. and Max. settings at INSTALLATION LEVEL under HAND TERMINAL. We reserve the right to alter specifications without notice. www.swegon.com 19 GB.GOLDLP.160901 9.2.2 Outdoor Temperature Compensation INSTALLATION Temperature Outdoor temperature compensation can be activated if the premises are abnormally subjected to the effects of seasonal cold air or hot air due to leakage through large windows, for instance. FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER The supply air temperature setpoint is compensated if the air handling unit is operating in the supply air regulation mode, and the extract air temperature setpoint is compensated if the air handling unit is operating in the extract air regulation mode. This function will have no effect if the unit is operating in the ERS regulation mode. The preset temperature setpoint is influenced if the outdoor temperature drops below the preset X2 breakpoint (winter compensation) and above the preset X3 breakpoint (summer compensation). OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE * TEMPERATURE * TEMPERATURE REG OUTDOOR TEMP COMP SUMMER NIGHT COOL INTERM. NIGHT HEAT MORNING BOOST SETPOINT TEMP DISPL EXT. SENSORS Outdoor temperature compensation See the chart to the right. It is possible to set negative summer compensation. Value Winter compensation Temperature displacement Y1 Breakpoint X1 Breakpoint X2 Summer compensation Breakpoint X3 Breakpoint X4 Temperature displacement Y2 Setting Factory rangesetting +0 – +20 °C +3 °C -30 – -10 °C -20 °C -10 – +15 °C +10 °C +15 – +25 °C +25 °C +25 – +40 °C +40 °C -10 – +20 °C +2 °C Y = Temperature displacement °C Settings: Y1 X1 X4 X2 Y2 X3 X = Outdoor temperature °C Winter compensation in accordance with factory setting involves: Outdoor temperature +10 °C (Breakpoint X2): Compensation starts and gradually takes place between 0–3 °C down to outdoor temperature -20 °C. Outdoor temperature -20 °C (Breakpoint X1): Constant compensation takes place with 3 °C (temperature displacement Y1). Summer compensation in accordance with factory setting involves: Outdoor temperature +25 °C (Breakpoint X3): Compensation starts and gradually takes place between 0–2 °C up to outdoor temperature +40 °C. Outdoor temperature +40 °C (Breakpoint X4): Constant compensation takes place with 2 °C (temperature displacement Y2). 20 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9.2.3 Summer Night Cooling The lower temperature at night is utilised to cool down the building structure. This reduces the cooling load during the first hours of the day. If a cooling unit is installed, its in-operation hours will be minimised, thus offering savings. If no cooling unit is installed, a certain cooling effect will still be realised. When summer night cooling function is activated, the unit fans operate at high speed, with a supply air setpoint of 10°C, from the preset time until the conditions necessary for stop are satisfied. Conditions to be met to start summer night cooling at the preset time: • The extract air temperature should be higher than the preset value INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE * TEMPERATURE * TEMPERATURE REG OUTDOOR TEMP COMP SUMMER NIGHT COOL INTERM. NIGHT HEAT MORNING BOOST SETPOINT TEMP DISPL EXT. SENSORS • The extract air should be at least 2°C warmer than the outdoor air. • The outdoor temperature should be above the preset value. • Heating has not been required between 12.00–23.00 hours. • The unit must not operate in the high speed mode or be stopped from an external source or manually from the hand-held micro terminal. Conditions to be met to stop summer night cooling at the preset time: • The extract air temperature drops below the preset value. • The outdoor temperature drops below the preset value. • Switch clock or external input calls for high speed. • The extract air is less than 1 °C warmer than the outdoor air. The function starts once per set time period. Settings: Value Extract air temperature for start Extract air temperature for stop Outdoor temperature for stop Supply air setpoint Operating period Setting Factory rangesetting 17 - 27 °C 22 °C 12 - 22 °C 16 °C 5 - 15 °C 10 °C 10 - 20 °C 10 °C 00:00-00:00 23:00-06:00 We reserve the right to alter specifications without notice. www.swegon.com 21 GB.GOLDLP.160901 9.2.4 Intermittent Night-time Heating The unit is utilised to heat the premises when it is normally stopped by the switch clock. The function requires that an external room sensor is connected and that the air handling unit is provided with air heater for reheating the air. Connect the TBLZ-1-24-2 Room sensor by means of the modular cable supplied, to an optional connection marked Internal BUS 1. The capacity of the function will be best if the GOLD is provided with a recirculation damper (not Swegon supply) and a shut-off damper for outdoor air and exhaust air. When the function is activated, the air handling unit detects when the room temperature drops below the preset start temperature. The unit starts with preset flows and the supply air temperature setpoint. If extract air fan operation is not desirable, the extract airflow can be set to 0. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE * TEMPERATURE * TEMPERATURE REG OUTDOOR TEMP COMP SUMMER NIGHT COOL INTERM. NIGHT HEAT MORNING BOOST SETPOINT TEMP DISPL EXT. SENSORS EXTRACT AIR The damper output can be set to 0. This means that the connected dampers (such as shut-off dampers for outdoor air and extract air) will not be affected. These dampers are normally closed when the air handling unit is stopped and they also remain closed. At the same time, the damper in the air recirculation section, if included, will open. SUPPLY AIR Conditions to be met for intermittent night-time heating to start: Intermittent night-time heating with air recirculation section: • The unit should operate in a time channel/switch clock stop. If the extract airflow is set to 0 and the damper output is not activated, the following takes place: • The room temperature should be below set start temperature. When conditions for start are met, outdoor air and exhaust air shut-off dampers remain closed. The damper in the air recirculation section is opened. The extract air fan is idle. Conditions to be met for intermittent night-time heating to stop: • High speed or external/manual stop should be activated. • Room temperature should be above the preset stop temperature. The supply air fan operates according to the preset supply airflow and the heating coil downstream of the air handling unit operates according to the supply air temperature setpoint, until the conditions for stop are met. • Alarm with preset stop priority has tripped. If the needed, the air handling unit fans will continue to operate to cool the electric air heater although other conditions for stop have been met.) Settings: Value Setting Factory rangesetting Room temperature for start 5 - 25 °C 16 °C Room temperature for stop 5 - 25 °C 18 °C Supply air temperature setpoint 10 - 40 °C 28 °C Supply airflow *) m3/s/Pa **) m3/s/Pa Extract airflow *) m3/s/Pa 0 m3/s/Pa Damper output 0=not activated 0 1= activated Control output 0=IQnomic 0 1 =IQnomic Plus *) The setting range is the same as the min/max settings of the air handling unit. **) According to the setting for low speed at USER LEVEL under FLOW/PRESSURE. 22 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9.2.5 Morning BOOST The unit is utilised to heat the premises during a preset period prior to the switch-in time set on the switch clock. The function is used if the air recirculation section is installed. The unit starts early and uses the same operation and temperature regulation settings as it would at the regular start time. If the extract air fan is not required to operate, the extract airflow can be set to 0. Damper output can be set to be inactive. This means that connected dampers (e.g. outdoor air and exhaust air shutoff dampers) are not affected. Normally these dampers are closed when the unit is stopped and thus they remain closed. At the same time, the damper in the air recirculation section, if included, will open. Settings: Value Setting Factory rangesetting Time for start prior to regular start time according to switch clock hour, min. 00:00 Damper output Inactive Inactive Extract air fan Inactive Inactive FL/Rum-temp 10 - 30 °C 22 °C TL-min 8 - 20 °C 15 °C TL-max 16 - 50 °C 28 °C INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE Setting range FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING HUMIDITY COOLING IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE Factory setting We reserve the right to alter specifications without notice. Setpoint temp displacement °C External Extract air/Room Inactive//IQnomic Inactive Communication External Outdoor Inactive//IQnomic Inactive Communication Alarms 0 - 9990 min. 5 min. 9.2.6 Setpoint Temperature Displacement Used for changing the supply air and extract air temperature setpoints by means of an external 0-10 VDC signal (control unit terminals 35 (-), 37 (+)). The temperature can be increased or decreased at certain times of the day by means of an external switch clock or potentiometer, for instance. The setpoint can be influenced ±5 °C. If the unit is operating in the supply air regulation mode, the supply air temperature is displaced and if the unit is operating in the extract air regulation mode, the extract air temperature is displaced. When the unit is operating in the ERS regulation 1 mode, the difference between extract air and supply air is influenced. The difference cannot be less than 0 °C. The difference will decrease as the input signal increases. If the unit is operating in the ERS regulation 2 mode, the supply air setpoint will be offset. When the function is activated, the setpoint is offset as illustrated in the chart to the right. INTERM. NIGHT HEAT MORNING BOOST SETPOINT TEMP DISPL EXT. SENSORS INSTALLATION Settings: Value * TEMPERATURE * TEMPERATURE REG OUTDOOR TEMP COMP SUMMER NIGHT COOL +5 +4 +3 +2 +1 0 -1 -2 -3 -4 -5 0 * TEMPERATURE * TEMPERATURE REG OUTDOOR TEMP COMP SUMMER NIGHT COOL INTERM. NIGHT HEAT MORNING BOOST SETPOINT TEMP DISPL EXT. SENSORS 5 Control signal V DC 10 Setpoint temp displacement involves: Control signal 0 V DC: The setpoint is lowered by 5 °C. Control signal 5 V DC: Unchanged setpoint. Control signal 10 V DC: The setpoint is increased by 5 °C. Settings: Value Setpoint temp displacement Setting Factory rangesetting Inactive/active Inactive www.swegon.com 23 GB.GOLDLP.160901 9.2.7 External Temperature Sensors The IQnomic control unit has provision for wiring an external room sensor and/or external outdoor sensor. The sensor can be used when the internal sensor of the unit does not provide representative values. External Extract air/Room can measure the extract air temperature in a larger room instead of the temperature inside the air handling unit. External Outdoor measures the outdoor air temperature outdoors, instead of the temperature inside the air handling unit. Connect the TBLZ-1-24-2 sensor by means of the modular cable supplied, to an optional connection marked Internal BUS 1. Sensor TBLZ-1-24-2 can be used both as a room sensor and an outdoor sensor. They must therefore be addressed according to function using the function selector switch on the sensor. The function selector switch must be in Position 1 if the sensor is used as a room sensor and in Position 2 if it is used as an outdoor sensor. If the TBLZ-1-24-2 sensor is installed outdoors, it must be mounted inside an air-tight enclosure. As an alternative, a temperature reading can be communicated to the air handling via communication from e.g. a main system. The alarm setting indicates how long the alarm will be delayed if communication is lost. 24 www.swegon.com INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING HUMIDITY COOLING IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE * TEMPERATURE * TEMPERATURE REG OUTDOOR TEMP COMP SUMMER NIGHT COOL INTERM. NIGHT HEAT MORNING BOOST SETPOINT TEMP DISPL EXT. SENSORS We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9.3 Flow/Pressure Basic functions are set at INSTALLATION LEVEL and the values are read and set at USER LEVEL. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE * AIRFLOW/PRESSURE * FILTER SA FAN REGULATION OPERATION EA FAN REGULATION HEATING CLEAN AIR CONTROL COOLING 9.3.1 Fan Regulation The type of regulation used for the supply air fan and the extract air fan respectively can be selected individually. 9.3.1.1 Flow Regulation Flow regulation involves operating the air handling unit to keep the preset airflow constant. The speed of the fans is automatically regulated to provide correct airflow even if the filters begin to become clogged, air devices are blocked, etc. HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE Constant airflow is advantageous, since the airflow always is exactly as it was from the beginning. It should however be noted that everything that increases the pressure drop in the ventilation system, such as the blocking of air devices and dust accumulating in the filters, causes the fans to run at a higher speed. This causes higher power consumption and may also cause discomfort in the form of noise. 9.3.1.2 Pressure Regulation The airflow automatically varies to provide constant pressure in the ducting. This type of regulation is also called VAV regulation (Variable Air Volume). Pressure regulation is used when damper operations increase the air volume in parts of the ventilation system. The duct pressure is measured by an external in-duct pressure transducer which is wired to the BUS communication of the control unit. The setpoint setting required (separate for low speed and high speed) is entered in Pa. OUTDOOR TEMP COMP. SA DOWN REGULATION SLAVE CONTROL * AIRFLOW/PRESSURE * SA FAN REGULATION EA FAN REGULATION CLEAN AIR CONTROL OUTDOOR TEMP COMP. SA DOWN REGULATION SLAVE CONTROL Settings: Value Fan regulation (SA/EA) Detting Flow regulation Pressure regulation Demand control Slave control The function can be limited so that the fan speed will not exceed the preset max. permissible values. 9.3.1.3 Demand Control The flow demand is regulated via a 0-10 V input signal from an external sensor, such as a carbon dioxide sensor that is wired to control unit terminals 35(-) and 37(+). The required setpoint (separate for low speed and high speed) is set as a percentage of the input signal. The function can be limited so that the flow will not be higher or lower than the preset max. and min. permissible values respectively. 9.3.1.4 Slave Control The flow is constantly regulated to be the same from the one fan as from the other fan. If one fan is pressure-controlled or demand-controlled, the other one can be controlled as a slave to generate the same airflow. The performance of the fan controlled as a slave can be restricted if its maximum flow is set to a lower airflow rate. Both fans cannot be controlled as slaves. If both are selected by mistake, the extract air fan will be forced to operate in the flow regulation mode. We reserve the right to alter specifications without notice. www.swegon.com 25 GB.GOLDLP.160901 9.3.1.5 Clean Air Control The Clean Air Control function is used in ventilation systems where the aim is to regulate the airflow according to the content of emission/impurities in the room air. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE * AIRFLOW/PRESSURE * FILTER SA FAN REGULATION OPERATION EA FAN REGULATION HEATING CLEAN AIR CONTROL COOLING The TBLZ-1-60 VOC sensor accessory (Volatile Organic Compounds) is required. The VOC sensor measures the content of emissions/impurities in % VOC. When an occupant emits CO2, this creates a proportional amount of emissions/impurities which are measurable by the VOC sensor. For an approximate translation of the % VOC to CO2 content, see the diagram. HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE When the air handling unit is energised for the first time, the VOC sensor is initialised and this involves transmitting a steady signal of approx. 50% VOC for 6 hours (applies to the VOC sensors with Part No. 328964-01. VOC sensors with Part No. 328964-02 are initiated at the factory). If the unit at a later time is de-energised, and is subsequently reenergised, the sensor is reinitialised for 15 minutes (provided that initialisation during the first energising occasion was not interrupted). When the Clean Air Control function is activated, the fan regulation modes are automatically selected (extract air fan demand controlled, supply air fan slave controlled). Later on, they can only be read under Functions in the menu. 2000 CO2 content, ppm When the VOC sensor measures contents of emissions/ impurities that are lower than the preset value; the air handling unit’s supply air and extract air flows are then equivalent to the preset min. flows. When the VOC sensor instead measures contents of emissions/impurities that are higher than the preset value, the supply air and extract air flows are variably increased until the preset value or max. flow is reached. OUTDOOR TEMP COMP. SA DOWN REGULATION SLAVE CONTROL 1500 1000 400 10 20 30 40 50 60 70 80 90 % VOC Settings: Example: Value Setting Factory range setting Clean Air Control Inactive/Active Inactive VOC low speed 10 - 90 % 50 % VOC high speed 10-90 % 30 % Min. flow * m3/s 0.08/0.20 m3/s** Max. flow * m3/s 0.53/0.74 m3/s*** *) The setting range is the same as the min. - max. settings of the air handling unit. ** Size 05 = 0.08 m3/s, Size 08 = 0.20 m3/s *** Size 05 = 0.53 m3/s, Size 08 = 0.74 m3/s 800 ppm is equivalent to approx. 30% VOC. 26 www.swegon.com If influenced by other emissions/impurities in the air, such as cooking odours, cigarette smoke, etc., the VOC content increases in relation to the CO2 content. We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9.3.2 Outdoor Temperature Compensation INSTALLATION Airflow Outdoor temperature compensation of the airflow can be activated if it is desired to reduce the airflow in the wintertime. FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE * AIRFLOW/PRESSURE * FILTER SA FAN REGULATION OPERATION EA FAN REGULATION HEATING CLEAN AIR CONTROL COOLING OUTDOOR TEMP COMP. HUMIDITY SA DOWN REGULATION IN/OUTPUTS SLAVE CONTROL IQnomic Plus ALL YEAR COMFORT OPTIMIZE In the flow regulation mode, the current airflow is reduced. In the pressure regulation mode, the current setpoint for pressure is reduced. The function has no effect if the airflow is demand-controlled. The airflow is reduced as a percentage of the current airflow/pressure. Value Y1, max permissible reduction X1, breakpoint X2, breakpoint Setting Factory rangesetting 0-50% 30 % -30 – -10 °C -20 °C -10 – +15 °C +10 °C Y = Reduction of the airflow in % Settings: 0% X2 -10% -20% -30% Y1 -40% X1 -50% -30 -20 -10 0 +10 +20 X = Outdoor air temperature °C Outdoor air compensation according to factory settings involves: Outdoor temperature +10 °C (Breakpoint X2): Compensation starts and gradually proceeds between 0–30 % down to outdoor air temperature -20 °C. Outdoor air temperature -20 °C (Breakpoint X1): Constant compensation proceeds at 30 % (max reduction Y1). We reserve the right to alter specifications without notice. www.swegon.com 27 GB.GOLDLP.160901 9.3.3 Downspeed Control of Fan Speed to Min. Set Point, Airflow/pressure Regulation of the supply airflow to a lower flow rate is the last step in the regulation sequence on increasing heating load for ERS regulation or supply air regulation. The extract air fan cannot be selected alone; only the supply air fan or both the supply air and extract air fans can be selected. See Section 9.2 as well. An adjustable temperature decrease allows a lower supply air temperature setpoint, before down regulation begins. This neutral zone can be set on line NZ SA DOWN REGULATION in the appropriate menu. Settings: Value Function Neutral zone Setting Factory range settings Inactive/SA/SA+EAActive 0.0-10.0 °C 0.0 °C 9.3.4 To adjust the flow of the slave fan It is possible to preset the set point of the slave fan to provide a higher or lower airflow than the current airflow of the controlling fan. The deviation from the airflow of the controlling fan can be preset by entering a COP. A cooling COP of 0.5 denotes that the airflow of the slave will be 50% of the master fan’s airflow. Settings: Value Cooling COP Setting range 0.5-1.5 Factory settings 1,0 9.4 To Activate the GOLD SD Filter Monitoring Function The filter monitoring function must be activated for the filters that are to be monitored. Settings: Value Setting Factory rangesettings Standard filter Inactive/SA/EA SA+EA SA+EA Prefilter Inactive/SA/EA SA+EA SA+EA 28 www.swegon.com INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE * AIRFLOW/PRESSURE * FILTER SA FAN REGULATION OPERATION EA FAN REGULATION HEATING CLEAN AIR CONTROL COOLING OUTDOOR TEMP COMP. HUMIDITY SA DOWN REGULATION IN/OUTPUTS SLAVE CONTROL IQnomic Plus ALL YEAR COMFORT OPTIMIZE INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE * AIRFLOW/PRESSURE * FILTER SA FAN REGULATION OPERATION EA FAN REGULATION HEATING CLEAN AIR CONTROL COOLING OUTDOOR TEMP COMP. HUMIDITY SA DOWN REGULATION IN/OUTPUTS SLAVE CONTROL IQnomic Plus ALL YEAR COMFORT OPTIMIZE INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9.5 Operation INSTALLATION 9.5.1 Switch clock Basic functions are set at INSTALLATION LEVEL and the values are read and set at USER LEVEL. The switch clock controls the operating times of the unit. The following two basic functions can be set: LOW SPEED – HIGH SPEED Low speed is the basic level and times for high speed operation are set at USER LEVEL under SWITCH CLOCK. STOP – LOW SPEED – HIGH SPEED Stop is basic level and times for low speed and high speed operation are set at USER LEVEL under SWITCH CLOCK. FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE *OPERATION FUNCTION* SWITCH CLOCK EXTENDED OPERATION SUMMER/WINTER TIME Settings: Value Function Setting range Factory settings Low speed/High speed Low speed/High speed Stop/Low speed/High speed 9.5.2 Extended Operation The inputs for external low speed and external high speed respectively, can be supplemented with extended operation. They can be used for overtime running activated by a pushbutton, for example. *OPERATION FUNCTION* SWITCH CLOCK EXTENDED OPERATION SUMMER/WINTER TIME Desired time in hours and minutes can be set as follows. Settings: Value External low speed External high speed Setting Factory rangesettings 0:00 - 23:59 0:00 0:00 - 23:59 0:05 (hour:min)(hour:min) 9.5.3 Summer time/Winter time The time and date readings include factory-preset automatic changeover from summer time to normal time and vice versa, thus conforming to EU standard (the last Sunday in March and the last Sunday in October respectively). *OPERATION FUNCTION* SWITCH CLOCK EXTENDED OPERATION SUMMER/WINTER TIME This automatic changeover can be blocked and set as inactive. Settings: Value Summer time/Winter time Setting Factory rangesettings Inactive/active Active We reserve the right to alter specifications without notice. www.swegon.com 29 GB.GOLDLP.160901 9.6 Heating INSTALLATION 9.6.1 Heat exchanger FUNCTIONS 8.6.1.1 Defrosting the rotary heat exchanger In environments where the extract air can occasionally be humid, the defrosting function can be activated to protect the heat exchanger from frosting. The function continuously monitors the condition of the heat exchanger rotor to prevent condensate from freezing in the rotor passages and clogging them. The function requires a separate pressure transducer (preset for heat exchanger defrosting) wired to the control unit inputs for external BUS communication and connected by hoses to the pressure measuring tappings of the unit. *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE *HEATING* HEAT EXCHANGER PRE/REHEAT HEATING BOOST See special installation instruction for the TBLZ-1-23-aa Pressure sensor. The pressure drop across the rotor must then be calibrated to establish a reference pressure drop for monitoring purposes. See 7.4.3 Calibration - Heat exchanger. When the function is activated the pressure drop across the heat exchanger is continuously measured and the value is compared with the calibration value. If the pressure drop exceeds the preset limit value, a defrosting sequence is implemented where the rotor speed is gradually ramped down (ramp time of max. 4 minutes) to the speed at which the pressure drop across the heat exchanger has decreased to half of the preset limit value. The rotor speed can be 0.5 rpm but not slower. During the defrosting operation, warm extract air thaws any possible ice coating. A time delay of 4 minutes gives the heat exchanger a chance to dry, before the rotor once again is ramped up (ramp time max. 4 minutes) to its ordinary speed. The max. duration of the defrosting operation is 30 minutes. If the pressure drop has not decreased within this max. duration on six occasions during a 24-hour period, an alarm is tripped. EXTRACT AIR Defrosting function with separate pressure transducers, in principle Note that the heat exchanger performs less efficiently while defrosting is in progress and that the supply air temperature will decrease downstream of the heat exchanger. Settings: Value Defrosting 30 www.swegon.com Setting Factory rangesettings Inactive/active Inactive We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9.6.2 Pre-/Reheating INSTALLATION AIR HEATER FOR HOT WATER On selecting the exercising pump or pump+valve function, the selected relay output will be activated if reheating is needed and this starts the circulation pump of the air heater. If the outdoor temperature is low (colder than +12 °C), the pump output contact is continuously activated. During other times, the pump output contact is activated 2 min/24 hours for exercising of circulation pump. ELECTRIC AIR HEATER If “pump exercising mode inactive” has been selected, the relay output is activated whenever heating is required. The relay output can be used for indicating or blocking the external function. FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE *HEATING* HEAT EXCHANGER PRE/REHEAT HEATING BOOST EXERCISING MODE Settings: Value Setting Factory rangesettings Function Inactive/pump/Pump pump+valve/ valve Exercise period 1 – 60 min. 3 min. Interval 1 – 168 hrs. 24 hrs. 9.6.3 Heating BOOST Heating boost means that the air handling unit, operating in the normal flow regulation mode, increases both the supply airflow and the extract airflow in order to carry more heat into the premises. The fans are allowed to work in the range between current flows (low speed, high speed) and preset max speed flow. The function only works if the air handling unit is operating in the extract air regulation mode. If demand control or boost is selected in combination with heating boost, the flow is controlled by the function that transmits the highest output signal to the fans. This function cannot be combined with pressure regulation. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE *HEATING* HEAT EXCHANGER PRE/REHEAT HEATING BOOST A regulated ramp function begins and increases the airflow if the temperature exceeds its setpoint and it differs 2-10°C (3°C has been factory preset) to the preset max. supply air temperature. The control reaction speed (ramp time = % flow increase/minute) can be set. The highest possible airflow is limited by the max. flow. For particulars on setting the max. flow, see Section 7.2. Settings: Value Heating BOOST Start limit Ramp time Setting Factory rangesettings Inactive/active Inactive 2-10 °C 3 °C 0.5-15% 2.5% We reserve the right to alter specifications without notice. www.swegon.com 31 GB.GOLDLP.160901 9.7 Cooling Control of cooling units is primarily wired to Outp.1 or Outp. 2. If none of these outputs are vacant, connect the control means to the IQnomic Plus module. The module’s function selector switch must be set to Position 6. 9.7.1 Operation Activate the cooling function. 9.7.2 Cooling Regulation (Control) Stepless 0-10 V DC Used when variable cooling control is connected. The GOLD air handling unit’s cooling controller modulates a 0-10 V DC signal that is linear with the cooling load. Connect to the IQnomic Plus module, terminals 15-16. Both the cooling relays of the air handling unit operate in parallel with the signal and are energised when the cooling signal exceeds 0.5 V DC and are de-energised when the signal drops below 0.2 V DC. The output for Cooling Relay 1 is connected to IQnomic Plus terminals 1-2 and for Cooling Relay 2 to terminals 4-5. Stepless 10-0 V DC Same as above, but the control signal is inverted where a 10 V output signal means a 0 % cooling load. On/off, 1 step Used if cooling in one step is connected. Connect to the IQnomic Plus module, Cooling relay 1, terminals 1-2. The cooling controller of the air handling unit regulates the cooling load at 1-100%. Cooling relays 1 and 2 are energised when the cooling load exceeds 5 % and are de-energised when the cooling load is less than 2 %. The 0-10 V DC control signal output operates in parallel with the 0-100 % cooling demand and can be used for indicating the cooling demand, for instance. Connect to the IQnomic Plus module, terminals 15-16. On/off, 2 steps Used when cooling in 2 steps is connected. Connect to the IQnomic Plus module, Cooling relay 1, terminals 1-2, and Cooling relay 2, terminals 4-5. The cooling controller of the unit regulates the cooling demand at 0-100 %. Cooling relay 1 is energised when the cooling load exceeds 5 % and is de-energised when the cooling load is less than 2 %. Cooling relay 2 is energised when the cooling load exceeds 55 % and is de-energised when the cooling load is less than 50 %. The 0-10 V DC control signal output operates in parallel with the 0-100 % cooling demand and can be used for indicating the cooling demand, for instance. Connect to the IQnomic Plus module, terminals 15-16. On/off, 3 Steps - Binary Used when cooling with two inputs controlled with three binary steps is connected. Connect to the IQnomic Plus module, Cooling relay 1, terminals 1-2, and Cooling relay 2, terminals 4-5. The cooling controller of the unit regulates the cooling demand at 0-100 %.. On an increasing cooling load: Cooling relay 1 is energised when the cooling load is above 5 % and is de-energised when the cooling load is between 40-70 %. Cooling relay 2 is energised when the cooling load is above 40 %. Cooling relay 1 is energised again (together with cooling relay 2) when the cooling load is above 70%. On a decreasing cooling load: Cooling relay 1 is deenergised when cooling load is below 60 %, it is energised again when cooling load is below 30 % and is deenergised again when cooling load is below 2 %. Cooling relay 2 drops when cooling load is below 30 %. The 0-10 V DC control signal output operates in parallel with the 0-100 % cooling demand and can be used for indicating the cooling demand, for instance. Connect to the IQnomic Plus module, terminals 15-16. 32 www.swegon.com INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE * COOLING * OPERATION MODE COOL REGULATION PERIODIC OPERATION REGULATION SPEED OUTDOOR TEMP LIMIT RESTART TIME COOL MIN AIR FLOW NEUTRAL ZONE COOLING BOOST On a decreasing cooling load: Cooling relay 1 drops when cooling load is below 60 %, it is energised again when cooling load is below 30 % and drops again when cooling load is below 2 %. Cooling relay 2 drops when cooling load is below 30 %. The output for 0-10 V DC control signals (terminals 42-43) operates in parallel with the 0-100 % cooling load and can be used for indicating the cooling demand, for instance. Settings for cooling functions on this page and the next: Value Setting Factory rangesettings Operation mode Inactive/active Inactive Cooling regulation Stepless 0-10 V On/Off 1 step Stepless10-0 V On/Off 1 step On/Off 2 step On/Off 3 step binary Periodic operation Cooling relay 1 Inactive/pump/ Inactive pump+valve/valve Cooling relay 2 Inactive/pump/ Inactive pump+valve/ valve Exercise period 1 – 60 min. 3 min. Interval 1 – 168 hrs. 24 hrs. Regulation speed between steps 0-600 sec 300 sec Outdoor temperature limit Step 1 0-25 °C 3 °C Step 2 0-25 °C 5 °C Step 3 0-25 °C 7 °C Restart time 0-900 sec 480 sec Cooling min air flow Supply air 0-Max flow – Extract air 0-Max flow – Neutral zone 0-10 °C 2.0 °C Cooling BOOST Inactive Inactive Comfort Economy Sequence Comfort+economy Economy+ sequence Start limit in connection to min supply air temp 2-10 °C 3 °C Ramp time 0.5-15% 2.5% We reserve the right to alter specifications without notice. GB.GOLDLP.160901 See preceding page for possibilities of setting. 9.7.3 Periodic Operation Can be selected to run pumps if cooling relay 1 and/or 2 are used. The exercising mode can be selected for “pump, pump + valve” or “valve” only (0 - 10 V output). The pumps are exercised 2 minutes per day if this is activated. 9.7.4 Regulation Speed The required delay period between the various cooling steps can be set. This is done so that a compressor, for instance, will have time generate required cooling capacity before the next cooling step is switched in. This applies to changeover from step 1 to step 2 and from step 2 to step 3; and only on an increasing cooling load. 9.7.5 Outdoor Temperature Limit Provision is available for setting an outdoor temperaturerelated blocking function in 3 steps. If the outdoor temperature is below each step limit, the function of the cooling relays will be blocked. This function also restricts the 0-10 V output signal to transmission in steps. Step 1 maximises the output signal to 2.5 V, step 2 to 5.0 V and step 3 to 7.5 V. 9.7.6 Restart Time The time should be set in such a way that it follows the recommendations of the cooling machine supplier for the number of starts per hour. The restart time is calculated from the time when a relay is energised to when it is allowed to be energised again. The 0-10 V signal is delayed during the same period. 9.7.7 Cooling Min Air Flow In order for the cooling function to operate the supply air and extract air airflows must be greater than their respective limit values (preset at USER LEVEL under FLOW/PRESSURE). The cooling min flow function can be blocked by setting both flow limits to 0. 9.7.8 Neutral Zone The neutral zone prevents the cooling and heating systems from counteracting each other. Preset neutral zone is added to the setpoint for heating and the sum of these provides the setpoint for cooling. 9.7.9 Cooling BOOST Cooling BOOST means that the supply air and extract air airflows are increased to convey more cooling energy to the premises. Cooling BOOST cannot be combined with pressure reguWe reserve the right to alter specifications without notice. lation. The flow increase takes place between current flow and preset max flow. The function can be selected in five variants as follows: Comfort The cooling outputs are activated if there is a cooling load. When the temperature exceeds its setpoint and the supply air temperature is within the preset limit, a regulated ramp function begins and increases the flow. The control reaction speed (ramp time = % flow increase/minute) can be set. The highest possible airflow is limited by the max. flow. For particulars on setting the max. flow, see Section 7.2. Economy Cooling BOOST Economy first uses a higher airflow to cool the premises, before a start signal is transmitted to the cooling machines. The function can also operate without the cooling function being activated. On a cooling load, the flows are slowly increased up to preset maximum flow. When the flows are up to max and if a cooing load is still present, the output contacts for cooling are activated. The cooling boost function requires an outdoor air temperature of at least 2 °C lower than the extract air temperature for it to be activated. Normal cooling operation is activated if the temperature difference is too small. Sequence The cooling BOOST Sequence is used if a cooling machine is sized for a higher than normal cooling flow. If there is a cooling load, the flow is increased up to the preset max flow before the cooling function is activated. The cooling function is delayed 1 minute after the airflow is increased. The cooling boost sequence is blocked if no cooling function has been selected. Comfort + Economy Cooling BOOST Comfort + Economy is a combination of the two variants for increasing the airflow. If the conditions for Cooling BOOST Economy are met, the unit will begin increasing the airflow before the cooling unit starts up. If the conditions for outdoor air are not met, the flow increase will begin when the supply air temperature reaches the preset Min. permissible temperature. Economy + Sequence Cooling BOOST Economy + Sequence is a combination of the two variants for increasing the airflow. If the conditions for Cooling BOOST Economy are met, the unit will begin increasing the airflow before the cooling unit starts up. If the conditions for outdoor air are not met, the unit will begin increasing the airflow when the cooling unit starts up. www.swegon.com 33 GB.GOLDLP.160901 9.8 Humidity Dehumidification control The dehumidification function controls the moisture in the supply air duct by switching in and switching out a cooling coil and a postheating coil. The function requires that a cooling coil be mounted upstream of a postheating coil in the supply air duct, see the example to the right. The TBLZ-1-31-1 moisture sensor is mounted in the supply air duct and its cable is connected to the appropriate terminal on the GOLD unit. Cooling energy is emitted to condense the moisture in the supply air flow, which then is heated to the desired supply air temperature. This causes a reduction in the moisture content of the supply air. The cooling unit used must be sized so that the temperature of the supply air will be below the dew point, otherwise no condensation will arise and no dehumidification will occur. Settings: Value Setting Factory rangesettings Dehumidification Inactive/activeInactive Supply air – rel. humidity (%RH) 10-90% 50% INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY *HUMIDITY* IN/OUTPUTS DEHUMIDIF. CTRL. IQnomic Plus ALL YEAR COMFORT OPTIMIZE Example of dehumidification control Temp. sensor, supply air Moisture sensor, TBLZ-1-31-1 34 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9.9 Input/output connections Outputs The control unit has two relay-controlled outputs, terminals 1-2 and 3-4. They must be individually set to the function they are to have. N.B.! A maximum of two of the functions below can be combined as standard. The number of combinations can be increased to four using the TBIQ IQnomic Plus module accessory. See separate instructions. Optional functions: - Damper, output: For control of the outdoor air/exhaust air damper - Operation, output: For indicating unit in operation. - Low speed, output: For indicating low speed operation. - High speed, output: For indicating high speed operation. - A Alarm, output: For group alarm A. - B Alarm, output: For group alarm B. - Heating, output: For indicating that the reheater is operating. - Cooling, output 1: For controlling external cooling. - Cooling, output 2: For controlling external cooling. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE Inputs The control unit has two digital outputs, terminals 5-6 and 7-8. They must be individually set to the function they are to have. N.B.! A maximum of two of the functions below can be combined as standard. The number of combinations can be increased to four using the TBIQ IQnomic Plus module accessory. See separate instructions. Optional functions: – External stop. The unit will stop if the input is not closed. – External LS: For external overtime operation via timer (switch clock), from stop to low speed operation. – External HS: For external overtime operation via timer (switch clock), from stop or low speed operation to high speed operation. – External Alarm 1: For connection of External Alarm 1. – External Alarm 2: For connection of External Alarm 2. – External reset: For connection of pushbutton for resetting a tripped alarm. External fire alarm: A fire alarm will trip if the input is not connected. We reserve the right to alter specifications without notice. www.swegon.com 35 GB.GOLDLP.160901 9.10 IQnomic Plus IQnomic Plus is a name given to additional modules for extra control functions. See special instructions. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus *IQNOMIC PLUS* ALL YEAR COMFORT OPTIMIZE 36 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 9.11 All Year Comfort The All Year Comfort function controls the supply flow temperature to comfort modules, chilled beams, perimeter climate systems, etc. via regulating valves. Two strap-on temperature sensors fitted either to the water pipe or the regulating valve are used for measuring the water temperature. The function requires the electrical equipment cubicle accessory (TBLZ-1-59-a-b-cc) for controlling the supply flow water temperature. The function selector switch of the electrical equipment cubicle must be set to position 7. All Year Comfort has functions for outdoor compensation, room compensation, night compensation, dew point compensation and for controlling pump and valve exercising. For further information, see the Guide to the All Year Comfort Function. Settings: Value Setting Factory rangesettings All Year Comfort Inactive Inactive Cooling Heating Cool.+Heat. Heating water temperature (°C) 10-80°C 30 Cooling water temperature (°C) 5-30°C 14 Outdoor comp. Heat. water Active Inactive Inactive Outdoor temp. (X1) (°C) -40 - 40°C -20 Heating water (Y1)(°C) 10 - 80°C 40 Outdoor temp. (X2)(°C) -40 - 40°C 5 Heating water (Y2)(°C) 10 - 80°C 30 Outdoor temp. (X3)(°C) -40 - 40°C 15 Heating water (Y3)(°C) 10 - 80°C 20 Outdoor comp., Cool. water Active Inactive Inactive Outdoor temp. (X1) (°C) -40 - 40°C 10 Cooling water (Y1)(°C) 5 - 30°C 22 Outdoor temp. (X2)(°C) -40 - 40°C 20 Cooling water (Y2)(°C) 5 - 30°C 18 Outdoor temp. (X3)(°C) -40 - 40°C 25 Cooling water (Y3)(°C) 5 - 30°C 14 Room comp., Heating water Active Inactive Inactive Room temperature (°C) 0 - 40°C 21 P-band (°C) 1 - 10°C 5 Night blocking Active Active Inactive Room comp., Cooling water Active Inactive Inactive Room temperature (°C) 0 - 40°C 21 P-band(°C) 1 - 10°C 5 Night blocking Active Active Inactive Night comp., heating water Active Inactive Inactive Temp. comp. (°C) -10 - +10°C -2 Night comp., Cooling water Active Inactive Inactive Temp. comp. (°C) -10-+10 °C 2 We reserve the right to alter specifications without notice. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING *ALL YEAR COMFORT* HUMIDITY FUNCTION ON/OFF IN/OUTPUTS SETTINGS IQnomic Plus ALL YEAR COMFORT OPTIMIZE Night comp. Inactive Inactive Monday Tuesday Wednesday Thursday Friday Saturday Sunday Monday-Friday Monday-Sunday Saturday-Sunday Channel 1-2 Pump op., Heating water Outdoor temp. Start (°C) -40 - 40°C 15 Pump op., Heating water Outdoor temp. Stop (°C) -40 - 40°C 18 Pump op., Cooling water Outdoor temp. Start (°C) -40 - 40°C -20 Pump op., Cooling water Outdoor temp. Stop (°C) -40 - 40°C -25 Pump/valve Pump alarm, heating water Inactive Inactive Normally closed Normally open Contactor Valve, heating water Active Inactive Inactive Pump alarm, cooling water Inactive Inactive Normally closed Normally open Contactor Valve, cooling water Active Inactive Inactive Exercising, heating water Inactive Inactive Pump Pump+Valve Valve Exercising period, (min) 1-60 min 3 Interval (h) 1-168 h 24 Exercising, Cooling water Inactive Inactive Pump Pump+Valve Valve Exercising period, (min) 1-60 min 3 Interval (h) 1-168 h 24 Dew point comp. Active Inactive Inactive Neutral zone(°C) 0-5°C 2 Comp. flow (%) 0-30% 10 www.swegon.com 37 GB.GOLDLP.160901 9.12 OPTIMIZE The OPTIMIZE function optimizes the GOLD unit’s airflow rates for the connected WISE system. See the special documentation for WISE. INSTALLATION FUNCTIONS *FUNCTIONS* TEMPERATURE AIR FLOW/PRESSURE FILTER OPERATION HEATING COOLING HUMIDITY IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT OPTIMIZE 38 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 10 AUTOMATIC FUNCTIONS 10.1 General The GOLD has a number of automatic functions. The operation of the unit is influenced when certain functions are activated. 10.1.1 Starting Sequence The GOLD has a starting sequence with factory-preset time delay between every step as follows: 1. The damper relay is energised and opens the shut-off damper (if installed). Time delay: 30 seconds. 2. The extract air fan starts and the heat exchanger is controlled to provide max. heat recovery. Additional heating (if installed) is activated to generate 40% of its max capacity. Time delay: 90 seconds. 3. The supply air fan starts. Time delay: 180 seconds (from the time when the extract air fan has started). 4. The temperature regulation function begins according to its regular settings. The starting sequence prevents the extract air fan from starting if the shut-off damper is closed. By starting the extract air fan first, and the heat exchanger as well, the system also avoids chilling the premises with cool supply air under cold weather conditions. 10.1.2 Cooling Recovery Cooling energy recovery is an automatic function that helps the air handling unit utilize the relative “cooling energy” that may be present indoors if cooling is required and the outdoor temperature is high. The heat exchanger rotates at max. speed and in this way recovers the relative cooling energy or chilliness in the extract air. The conditions for this function to be activated are that there is a cooling demand and that the outdoor temperature is 1 °C higher than the extract air. The function is switched out when the cooling load ceases to exist or when the outdoor temperature is the same as that of the extract air. The text COOLING RECOVERY is shown in the hand-held micro terminal. 10.1.4 Anti-frost Monitoring Function – Air Heater for Hot Water The anti frost monitoring function is always active if the air heater for hot water connected has been supplied by Swegon. The function activates a heating device that maintains 13 °C in the coil while the air handling unit is in operation and 25 °C in the coil when the unit is stopped. An alarm is initiated and the unit is stopped if the temperature sensor senses a temperature below 7 °C. 10.1.5 Additional cooling – Electric Air Heater The fans continue to operate at min speed for 3 minutes after the air handling unit has been stopped to cool the electric heating elements if the electric air heater has been operating. The text ADD COOLING appears in the hand-held micro terminal. 10.1.6 Additional running - Heat Exchanger The rotary heat exchanger automatically continues to rotate ca 1 minute after the air handling unit has been stopped. It takes a little time for the fans to stop rotating after a stop order has been entered in the micro terminal. This prevents the admission of cool supply air into the premises. 10.1.7 Density-corrected Airflow The density of the air is different at different temperatures. This means that a specific volume of air will change at different air densities. The GOLD automatically corrects this, so that correct air volume is always obtained. The control equipment always shows the corrected airflow. 10.1.8 Carry-over Control Whenever the fans generate low airflows, the speed of the rotary heat exchanger is reduced to an appropriate level for correct purging airflow through the heat exchanger. 10.1.9 Calculaton of the efficiency of the rotary heat exchanger The efficiency is calculated and displayed (0 – 100%). 10.1.3 Zero Point Calibration The pressure transducer of the unit is automatically calibrated. This calibration is carried out 3 minutes after the unit has been stopped. The text ZERO PT CALIBR is shown in the hand-held micro terminal. The fans cannot start while calibration is in progress. We reserve the right to alter specifications without notice. www.swegon.com 39 GB.GOLDLP.160901 11 READINGS The operating status and the values can be read. Used for performance checks and for generally checking values, settings, power consumption, etc. INSTALLATION READINGS *READINGS* TEMPERATURE FANS HEAT EXCHANGE No values can be altered in this menu group. Each menu indicates which values can be read. The operation times per 24 hour period are given under the OPERATION TIME menu. REGULATION SIGNALS IN/OUTPUTS HUMIDITY IQnomic Plus ALL YEAR COMFORT OPERATION TIME PROGRAMVERSIONS 12 MANUAL TEST Note! Manual test running can cause indoor comfort problems. There is also risk of overloading the system. The responsibility for discomfort and overload rests totally on the person who activates the function. Manual test run can take place for testing the inputs and outputs, fans and heat exchanger, etc. Used when the air handling unit is first installed to make sure that all the connections have been correctly wired. Most alarms, functions and normal control modes will be blocked while manual testing is in progress. INSTALLATION MANUAL TEST *MANUAL TEST* TEMPERATURE FANS HEAT EXCHANGE REHEAT IN/OUTPUTS IQnomic Plus ALL YEAR COMFORT On a return to the other menu groups, the controller resumes normal operation and all settings for manual testing will be terminated. Each menu indicates which functions can be test run. 40 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 13 ALARM SETTINGS INSTALLATION 13.1 Fire Alarms ALARM SET EXTERNAL FIRE ALARM The Inp. 1 and Inp. 2 inputs can be used for external fire protection equipment The resetting of alarms can be selected to occur manually or automatically. *ALARM SETTINGS* FIRE ALARM EXTERNAL ALARMS ALARM LIMITS INTERNAL FIRE ALARM The air handling unit’s internal temperature sensors serve as fire protection thermostats. An alarm is initiated if the supply air temperature sensor registers more than 70 °C or when the extract air temperature sensor registers more than 50 °C. If an external Extract air/Room temperature sensor is connected and activated, this works parallel with the extract air temperature sensor of the unit. ALARM PRIORITY FANS IN THE EVENT OF A FIRE The fans in the air handling unit can be used for evacuating gases, etc. The activated function works together with the External fire/smoke function or Internal fire alarm. If the air handling unit is idle, the pre-selected fans will start up regardless of whether External Stop or Manual Stop has been activated in the hand-held micro terminal. The damper relay in the air handling unit is energised and the operating relay drops. The dampers pre-selected for service in the event of a fire, should be wired to the damper relay and these dampers will open. The dampers that are meant to close in the event of a fire, should be wired to the in-operation relay and these dampers will close. FAN SPEED IN THE EVENT OF FIRE Will be activated automatically if the fans have been activated in event of fire (see above), and make it possible to restrict the max speed of the fans. Settings: Value Setting range Factory setting Internal fire alarm 0=inactive 1=activated auto/manual Inactive/EA/SA/ SA+EA 10-100% 0 10-100% 100% External fire alarm Fan in event of fire Fan speed in event of fire, SA Fan speed in event of fire, EA manual Inactive 100% 13.2 External Alarms EXTERNAL ALARMS 1 and 2 Input Inp. 1 and Inp. 2 can be used for external alarms (can be selected under Inputs/Outputs). Typical uses: – Motor protection for the circulation pump in the heating or cooling circuit. – Service alarm actuated by smoke detectors. Set the time delay and set whether the alarm shall be activated on closure or disconnection of the input. Settings: Value Setting Factory rangesettings Time delay 1-600 sec 10 sec Alarm at closure 1=closure 1 0=disconnection Alarm reset 0=auto/1=man0 We reserve the right to alter specifications without notice. 13.3 Alarm Limits Changes in the factory-preset alarm limits should only be made if you have special reasons for doing so and you should be aware of the consequences. TEMPERATURE DEVIATION SA-TEMP (deviating supply air temperature) indicates how much the supply air temperature is allowed to be below the supply air temperature setpoint before an alarm is initiated. MIN EA-TEMP (min extract air temperature) indicates how low the extract air temperature is allowed to be before alarm is initiated. FILTERS SUPPLY AIR/EXTRACT AIR indicates at which level of contamination in the supply air filter that an alarm will trip. HEAT EXCHANGER ALARM LIMIT indicates at which pressure rise an alarm will trip, if there is an extra installed pressure transducer for the defrosting function of the heat exchanger. SERVICE PERIOD SERVICE PERIOD indicates the period until the next service. Settings: Value Setting Factory rangesettings TEMPERATURE Deviating supply air temp. 2-15 °C 5 °C Min extract air temp. 8-20 °C 15 °C FILTERS Supply air 50-300 Pa/ 100 Pa/ 5-20%*10%* Extract air 50-300 Pa/ 100 Pa/ 5-20%*10%* Supply air, prefilter. 50-300 Pa 100 Pa Extract air, prefilter. 50-300 Pa 100 Pa HEAT EXCHANGER Alarm limit 30-100 Pa 50 Pa SERVICE PERIOD Alarm limit 0-99 months 12 months *Depending on the choice of monitor function. 13.4 Alarm Priority There should be special reasons for alteration of alarm priority and you should be aware of the consequences. Changes in priority should only be made if you have special reasons for doing so and you should be aware of the consequences. The priority of certain alarms cannot be changed. Settings: See 18.2 Alarm Descriptions. www.swegon.com 41 GB.GOLDLP.160901 14 HAND-HELD TERMINAL INSTALLATION 14.1 Language HAND TERMINAL The language desired can be set here. Normally this setting is entered when the air handling unit is started for the first time and the question ÄNDRA/CHANGE? automatically appears in the hand-held terminal. *HANDTERMINAL SET* LANGUAGE AIR FLOW UNIT MIN/MAX SETTING However, the language setting can be changed at any time. BASE SETTINGS Settings: Value Language Setting Factory rangesettings Current languages English is listed in the menu. 14.4 Base Settings Used for saving and resetting the settings. BASE SETTINGS 1 and 2 are two levels where the user him-/herself saves current settings and activates them when needed. The two base settings can be used as a summer setting and as a winter setting of the air handling unit. 14.2 Air flow unit The air flow unit desired can be set here. Settings: Value Setting Factory rangesettings Flow unit l/s m3/s m3/s m3/h The values in INITIAL SETTING 1 and 2 saved in the internal memory can be transferred to the external MMC memory by entering SAVE SETTINGS. EXTERNAL MEMORY. The values can be transferred from the external MMC memory to the internal memory by entering FETCH EXTERNAL MEMORY. 14.3 Min/Max Adjustment INITIAL SETTING 1 and 2 must be downloaded into the control unit by entering INTERNAL MEMORY, LOAD NEW SETTINGS. Used for restricting the setting range at user level for setpoints as well as for min. and max. temperature limits. Under SAVE EXTERNAL MEMORY, there is a function that can save current settings to the MMC memory. Settings: Current settings can be stored directly in the control unit under FETCH EXTERNAL MEMORY Value For EA and SA regulation Setpoint, min Setpoint, max Setting Factory rangesettings 10-30°C 10-40°C 15°C 40°C For EA regulation Min SA, min Max SA, min Min SA, max Max SA, max 8-20°C 8-20°C 16-50°C 16-50°C 13°C 18°C 25°C 45°C For ERS regulation 1 Breakpoint, min Breakpoint, max EA/SA Diff, min EA/SA Diff, max 12-26°C 12-26°C 1-7°C 1-7°C 15°C 23°C 1°C 5°C EA = Extract air SA = Supply air ERS= Extract air temperature-related supply air temperature-regulation 42 www.swegon.com FACTORY SETTINGS resets the air handling unit’s settings to the original values it had when it was supplied (See 21.2 Commissioning Record). The preset values for communication and alarm priority are not reset if the factory settings are reinstated. Settings: Value Setting range Save/fetch setting Save setting –internal memory external memory Save new setting 1 Save new setting 2 Save setting 1 Save setting 2 Save current setting Save all Load/fetch –internal memory external memory Load new setting 1 Load new setting 2 Fetch setting 1 Fetch setting 2 Fetch current setting Fetch all Factory setting Activate We reserve the right to alter specifications without notice. GB.GOLDLP.160901 15 COMMUNICATION Provision for communication and supervision is integrated as standard into the GOLD. The unit is ready to be connected via EIA-485 and Ethernet. For particulars of connecting and wiring the air handling unit, see Section 20.2.2 Wiring to Terminals. Communication can also be established via Ethernet without software other than an ordinary web browser such as Internet Explorer. Further information about interfaces, protocols and configuration is available at www. swegon.com. INSTALLATION COMMUNICATION *COMMUNICATION* EIA-485 ETHERNET 15.1 EIA-485 Protocol and settings for EIA-485 is specified. Settings: Value Modbus RTU Metasys N2 OPEN Lon Works Exolinc Setting range Address, speed, parity, stop bits 15.2 Ethernet Protocol and settings for Ethernet is specified. Settings: Value Setting range Ethernet MAC ID DHCP SERVER (active or inactive) IP ADDRESS (static or dynamic) SUBNETM. GATEWAY DNS-SERVER MODBUS TCP CLIENT (IP address, netmask and port number) BACNet IP (active or inactive, Device ID, Port no.) 16 SERVICE LEVEL A code and special training are required for access to this menu group. We reserve the right to alter specifications without notice. INSTALLATION SERVICE LEV. *SERVICE LEV.* CODE:0000 www.swegon.com 43 GB.GOLDLP.160901 17MAINTENANCE Warning Before carrying out any work, make sure that the power supply to the air handling unit has been switched off. 17.1 Filter Change The filters should be changed when the filter alarm has been activated. Order new filters from Swegon or your nearest Swegon representative. State the type of air handling unit, and whether the change involves one or two airflow directions. N.B.! There are two types of replacement filter. One variant is for units installed in a false ceiling/horizontally, the other is for units mounted by a wall. Therefore also specify where and how the unit is located. 17.1.1 To Remove the Filters The filters can be changed from two directions, from the ordinary inspection side, but also from the extra inspection panel situated on the long sides of the unit. open the inspection panel that is simplest to access. Unfasten the filter locking piece that retains the filter cassette (located inside the air handling unit toward the inspection side). Withdraw the filters. It is advisable to clean inside the filter space while the filters are removed. 17.1.2 To Install New Filters Place the filter in the appropriate groove (located inside the unit toward the back side) and refit the filter locking piece. Check that the filter cassettes fit tightly. Close the inspection panel. Carry out a filter calibration as described in Section 7.4.2. 17.2 Cleaning and Inspection 17.2.1 General Clean the interior of the air handling unit if needed. Inspect the air handling unit when you change filters or at least twice a year. Also inspect the air handling unit fasteners that secure it to the false ceiling, wall or floor. 17.2.3 Heat Exchanger Check at least twice a year whether cleaning is necessary. Cleaning can be done from the filter space. The heat exchanger should above all be cleaned by vacuum cleaning with a soft nozzle to prevent damage to the air passages in the rotor. Turn the rotor by hand to reach everywhere. If the heat exchanger is substantially fouled, its surfaces can be blown clean with compressed air. If needed, the heat exchanger can be withdrawn from the unit casing and washed with degreasing solvent. Only service personnel trained by Swegon shall be permitted to wash it in this way. FABRIC SEAL Lift up the fabric seal and inspect its underside. Clean if needed by brushing or vacuum cleaning. If the fabric seal is worn or substantially fouled, it should be replaced. Do not lubricate it! BELT TENSION Replace the drive belt if it feels loose or worn and slightly slips if it meets resistance. Contact service personnel trained by Swegon. 18.2.4 Fans and Fan Spaces Inspect and, if needed, clean the fan impellers to remove dirt deposits. Check the impeller to make sure that it is not out of balance. Clean or brush off the fan motor. It can also be cleaned by carefully wiping it with a damp cloth and with dishwashing detergent. Clean the fan space, if needed. 17.3 Performance Checks General performance checks should be carried out in conjunction with a filter change or at least once a year. It is then appropriate to compare the current performance values of the unit with the Commissioning Record. Remedial measures should be taken to correct any possible deviations. 17.2.2 Filter Spaces The most appropriate time to clean the unit is when you change the filters. 44 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 18 ALARMS AND FAULT TRACING 18.1 General Alarms are indicated by an alarm text and flashing LED in the hand-held micro terminal. Fire alarms and frost alarms are shown in all the menu images. Other alarms are only shown if you are in the Main menu. Active, but time-delayed alarms can be viewed quickly at USER LEVEL under ALARMS. The 10 most recently initiated alarms can also be read in this menu. A fault can be traced by examining the function or function section indicated in the alarm text. Faults can also be traced via the READINGS menu or the MANUAL TEST menu at Installation level. If the fault cannot immediately be remedied: Consider whether the air handling unit can continue to operate until the fault has been remedied. Choose to block the alarm and/or to change it from STOP to OPERATION (See Section 12, Alarm settings). 18.1.1 A and B Alarms For particulars of type A alarm indication to output for Alarm Relay A (Inp. 1 and Inp. 2), see also 9.9. For particulars of type B alarm indication to output for Alarm Relay B (Inp. 1 and Inp. 2), see also 9.9. From these terminals, alarms can be forwarded with different priority. 18.1.2 Resetting of alarms Alarms that require manual resetting can be reset from the hand-held micro terminal. Select RESET in the current alarm menu. Alarms that reset themselves automatically do so as soon as the fault has been remedied. Alarms can also be reset via a communication network. 18.1.3 Changing Alarm Settings See Section: 13 Alarm Settings. We reserve the right to alter specifications without notice. www.swegon.com 45 GB.GOLDLP.160901 Alarm no. 18.2 Alarm Descriptions with Factory Settings Alarm text Function Priority Stop Indication LED Delay Resetting 0=blocked 0=In operat. 0=Off s=seconds M=manual A=A alarm 1=Stop 1=On m=minutes A=automatic B=B alarm 1 EXTERNAL FIRE ALARM TRIPPED For the fire protection function connected to inputs Inp. 1 or Inp. 2. A**** 1* 1 3s M 2 INTERNAL FIRE ALARM TRIPPED The air handling unit’s supply air sensor measures a temperature more than 70 °C and/or its extract air sensor measures a temperature more than 50 °C. The function must be activated manually in the ALARM SETTINGS menu. A **** 1* 1 3s M 3 FROST PROTECTION BELOW ALARM LIMIT The anti-frosting monitor sensor measures a temperature lower than the preset temperature. Factory setting: 7 °C. A **** 1* 1 3s M 4 R.HX.SPEED MONITOR TRIPPED No impulses from the rotation detector are registered with the heat exchanger controller. The air handling unit will be switched out only if the outdoor temperature drops below 5 °C. A 0** 1 3s M 5 FROST PROTECTION SENSOR DEFECTIVE The anti-frosting monitor temperature sensor is lacking, is not connected or is faulty; an air heater for hot water is connected. A **** 1* 1 3s A 6 7 SUPPLY AIR TEMP SENSOR DEFECTIVE EXTRACT AIR TEMP SENSOR DEFECTIVE The supply air/extract air temperature sensor is not connected or is faulty. A A 1 1 1 1 3s 3s A A 8 OUTDOOR AIR TEMP SENSOR DEFECTIVE The outdoor air temperature sensor is not connected or is faulty. B 0 1 3s A 9 NO COMMUNICATION TO R.HX. CONTROLLER The air handling unit’s control unit cannot establish correct communication with the heat exchanger controller. A*** 1 1 10 s A 10 11 NO COMMUNICATION TO SA FREQUENCY CONV. NO COMMUNICATION TO EA FREQUENCY CONV. The air handling unit’s control unit cannot establish correct communication with frequency inverter. A *** A *** 1 1 1 1 10 s 10 s A A 12 13 OVER CURRENT IN SA FREQUENCY CONV. OVER CURRENT IN EA FREQUENCY CONV. Current above the normal level is supplied to the motors. A *** A *** 1 1 1 1 3s 3s M M 14 15 UNDER VOLTAGE IN SA FREQUENCY CONV. UNDER VOLTAGE IN EA FREQUENCY CONV. Voltage below the normal level is supplied. A *** A *** 1 1 1 1 3s 3s M M * Not adjustable, always stops the air handling unit. ** Not adjustable, stops the air handling unit if the temperature to below +5 ºC. *** Blocked if the hand terminal does not display the main menu. **** Cannot be blocked. 46 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 Stop Indication LED Delay Resetting 0=blocked 0=In operat. 0=Off s=seconds M=manual A=A alarm B=B alarm 1=Stop 1=On m=minutes A=automatic Alarm no. Priority Alarm text Function 18 19 OVER TEMPERATURE IN SA FREQUENCY CONV. OVER TEMPERATURE IN EA FREQUENCY CONV. High temperature inside the inverter. A *** A *** 1 1 1 1 3s 3s M M 20 21 NO COMMUNICATION WITH SA FREQUENCY CONV. GATEWAY NO COMMUNICATION WITH EA FREQUENCY CONV. GATEWAY The air handling unit’s control unit cannot establish correct communication with the fan’s communication gateway. A*** A*** 1 1 1 1 10 s 10 s A A 22 23 SA FREQUENCY CONV. HALL SENSOR DEFECTIVE HALL SENSOR DEFECTIVE EA FREQUENCY CONV. Internal fault in hall sensor. A*** A*** 1 1 1 1 10 s 10 s M M 24 25 EA FREQUENCY CONV. BLOCKED EA FREQUENCY CONV. BLOCKED. Motor does not rotate during start up. A*** A*** 1 1 1 1 3s 3s M M 26 27 EA FREQUENCY CONV. START-UP FAILURE START-UP FAILURE EA FREQUENCY CONV. Wrong rotation during start up. A*** A**** 1 1 1 1 3s 3s M M 30 EXT.EA/ROOM TEMP SENSOR DEFECTIVE Temperature sensor in extract air duct or room is not connected (”Internal bus 1” contact) or is faulty; or has been selected with communication. Applicable if the External sensor, extract air/room or Intermittent night-time heating function is selected. A*** 1 1 3s A 31 EXT.OUTDOOR TEMP SENSOR DEFECTIVE Temperature sensor for outdoor temperature is not connected (”Internal bus 1” contact) or is faulty; or has been selected with communication. Applicable if the External outdoor sensor function is selected. B*** 0 1 3s A 34 OVER CURRENT IN R.HX. CONTROLLER Current above the normal level is supplied to the rotary heat exchanger’s drive motor. A *** 1 1 3s M 35 UNDER VOLTAGE IN R.HX. CONTROLLER Feed voltage (25V) is supplied to the rotary heat exchanger’s drive motor. A *** 1 1 3s M 36 OVER VOLTAGE IN R.HX. CONTROLLER Voltage above the normal level (55 V) is supplied to the rotary heat exchanger’s drive motor. A *** 1 1 3s M 37 OVER TEMPERATURE IN R.HX. CONTROLLER High internal temperature (90°C for the rotary heat exchanger’s controller). A *** 1 1 3s M 38 R.HX. PRESSURE DROP ABOVE ALARM LIMIT The heat exchanger’s defrosting function has operated for the full max period 6 times during one 24-hour period. B *** 0 1 3s M *** Blocked if the hand terminal does not display the main menu. We reserve the right to alter specifications without notice. www.swegon.com 47 GB.GOLDLP.160901 Stop Indication LED Delay Resetting 0=blocked 0=In operat. 0=Off s=seconds M=manual A=A alarm B=B alarm 1=Stop 1=On m=minutes A=automatic Alarm no. Priority Alarm text Function 39 EL.HEATING COIL TRIPPED The thermal overload protection has tripped or is not connected. A *** 1 1 3s M 40 EXTRACT AIR TEMP BELOW ALARM LIMIT The extract air temperature is below preset alarm limit for more than 20 minutes. A *** 1 1 20 m M 41 SUPPLY AIR TEMP BELOW SETPOINT The supply air temperature is below the preset setpoint (for ERS and Supply air regulation) or Min SA temp (for Extract air regulation) longer than 20 minutes. A *** 1 1 20 m M 42 EXT. ALARM No.1 TRIPPED External alarm, connected to control unit input Inp. 1 or Inp. 2, has tripped. A *** 1 1 Set time M 43 EXT. ALARM No.2 TRIPPED External alarm, connected to control unit input Inp. 1 or Inp. 2, has tripped. B *** 0 1 Set time M 44 45 SA DUCT PRESSURE BELOW SETPOINT EA DUCT PRESSURE BELOW SETPOINT Pressure in supply/extract air duct, if pressure transducers are connected, has been more than 10% below its setpoint for more than 20 minutes. B *** B *** 0 0 1 1 20 m 20 m M M 46 47 SA DUCT PRESSURE ABOVE SETPOINT EA DUCT PRESSURE ABOVE SETPOINT Pressure in supply/extract air duct, if pressure transducers are connected, has been more than 10% above its setpoint for more than 20 minutes. B *** B *** 0 0 1 1 20 m 20 m M M 48 49 SUPPLY AIRFLOW BELOW SETPOINT EXTRACT AIRFLOW BELOW SETPOINT The supply/extract airflow has been more than 10% below its setpoint for more than 20 minutes. B *** B *** 0 0 1 1 20 m 20 m M M 50 51 SUPPLY AIRFLOW ABOVE SETPOINT EXTRACT AIRFLOW ABOVE SETPOINT The supply/extract airflow has been more than 10% above its setpoint for more than 20 minutes. B *** B *** 0 0 1 1 20 m 20 m M M 52 53 SUPPLY AIR FILTER DIRTY EXTRACT AIR FILTER DIRTY The pressure across the supply /extract air filters has exceeded the preset alarm limit for more than 10 minutes. B *** B *** 0 0 1 1 10 m 10 m M M 54 SERVICE PERIOD PAST ALARM LIMIT The preset service period has expired. If the alarm is RESET via the hand-held micro terminal, the alarm will be initiated again after 7 days. A new service period can be set in the ALARM SETTINGS menu. B *** 0 1 Set time M *** Blocked if the hand terminal does not display the main menu. 48 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 Stop Indication LED Delay Resetting 0=blocked 0=In operat. 0=Off s=seconds M=manual A=A alarm B=B alarm 1=Stop 1=On m=minutes A=automatic Alarm no. Priority Alarm text Function 55 56 NO COMM. SA AIR FLOW PRESSURE SENSOR NO COMM. EA AIR FLOW PRESSURE SENSOR The air handling unit’s control unit cannot establish correct communication with the supply/extract air flow pressure transducer. A *** A *** 1 1 1 1 10 s 10 s A A 57 58 NO COMM. SA FILTER PRESSURE SENSOR NO COMM. EA FILTER PRESSURE SENSOR The air handling unit’s control unit cannot establish correct communication with the supply/extract air filter pressure transducer. B *** B *** 1 1 1 1 10 s 10 s A A 59 60 NO COMM. SA DUCT PRESSURE SENSOR NO COMM. EA DUCT PRESSURE SENSOR The air handling unit’s control unit cannot establish correct communication with the pressure transducer connected in the supply/extract air ducting. Applicable to SA /EA pressure regulation only. A *** A *** 1 1 1 1 10 s 10 s A A 61 NO COMM. R.HX. PRESSURE SENSOR The air handling unit’s control unit cannot establish correct communication with the pressure transducer connected for the heat exchanger. Applicable to the defrosting function only. B *** 0 1 10 s A B *** 0 1 3s A 62-71 NO COMMUNICATION TO I/O-MODUL NR 1–9 The air handling unit’s control unit cannot establish correct communication with the connected I/O module 1–9 72 Correct communication can be established between the CPU circuit card and the control unit*s I/O processor. A 1 1 30 s A 75 SUPPLY AIR HUMIDITY SENSOR FAULTY The communication with the humidity sensor in the supply air duct is faulty or the sensor reading is erroneous. A *** 1 1 10 s A 76 EXTRACT AIR HUMIDITY SENSOR FAULTY The communication with the humidity sensor in the extract air duct is faulty or the sensor reading is erroneous. A *** 1 1 10 s A 83 SA PREFILTER FOULED The pressure across the supply air prefilter has constantly exceeded the preset alarm limit for 0 minutes. B *** 0 1 600 s M 84 EA PREFILTER FOULED The pressure across the extract air prefilter has constantly exceeded the preset alarm limit for 0 minutes. B *** 0 1 600 s M 85 COOLING OUTPUT 1 TRIPPED Broken signal is obtained at D11 for I/0-module 6. Motor protection or pressure switch may have tripped. A 0 1 3s M 86 COOLING OUTPUT 2 TRIPPED Broken signal is obtained at DI2 for I/0-module 6. The motor protection or pressure switch may have tripped. A 0 1 3s M *** Blocked if the hand terminal does not display the main menu. We reserve the right to alter specifications without notice. www.swegon.com 49 GB.GOLDLP.160901 Stop Indication LED Delay Resetting 0=blocked 0=In operat. 0=Off s=seconds M=manual A=A alarm B=B alarm 1=Stop 1=On m=minutes A=automatic Alarm no. Priority Alarm text Function 89 NO COMM. SA PREFILTER PRESS. SENSOR The air handling unit’s control unit cannot establish correct communication with supply air prefilter pressure sensor. B*** 0 1 10 s A 90 NO COMM. EA PREFILTER PRESS. SENSOR The air handling unit’s control unit cannot establish correct communication with extract air prefilter pressure sensor. B*** 0 1 10 s A 91 FROST PROTECTION, PREHEATING, BELOW ALARM LIMIT The sensor for the frost protection monitor, preheating, has measured a temperature lower than the preset temperature. Factory setting: 7 °C. A 1 1 3s M 92 FROST PROTECTION PREHEATING SENSOR DEFECTIVE The sensor for the frosting protection monitor, preheating, is lacking, is not connected or is faulty, if an air heater for hot water is connected. A 1 1 3s A 93 PREHEATING SENSOR DEFECTIVE The sensor for preheating is lacking, is not connected or is faulty, if an air heater for hot water is connected. A 1 1 3s A 94 EL. AIR HEATER, PREHEATING, TRIPPED The thermal overload protection for the connected electric air preheater, has tripped or is not connected. A*** 1 1 3s M 95 PREHEATING BELOW SETPOINT The preheating temperature is below the preset setpoint (for ERS and Supply air control) or Min SA temp (for Extract air control) longer than 0 minutes. A*** 1 1 20 m M 96 LOST SETTINGS An incorrect checksum for the backup file is obtained on reboot. When an alarm is generated, set values in the hand-held terminal return to the factory settings or are inaccurate. Compare and restore values in accordance with the commissioning protocol. A 1 1 3s M 99 TIME LOCK TRIPPED Contact Swegon or their representative. – – – –**** M 102 COOLING VALVE I/O-7 DEFECTIVE Controls of the Cooling valve do not obtain the same signal on AI 1 as on AU1 on I/O-module. B*** 1 0 10 m M 103 HEATING VALVE I/O-7 DEFECTIVE Controls of the Heating valve do not obtain the same signal on AI 2 as on AU2 on I/O-module A*** 1 0 10 m M 104 COOL. CIRCUIT PUMP I/O-7 TRIPPED. Controls of the cooling circuit pump do not obtain correct signal according to set function. B*** 1 0 30 s M 105 HEAT. CIRCUIT PUMP I/O-7 TRIPPED Controls of the heating circuit pump do not obtain correct signal according to set function. A*** 1 1 30 s M 106 COOLING WATER TEMP I/O-7 BELOW SET POINT Temperature for cooling water control on I/O module is continuously 7°C below its current set point. B*** 1 0 30 m M *** Blocked if the hand terminal does not display the main menu. **** Adjustable: 0-99 months. 50 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 Stop Indication LED Delay Resetting 0=blocked 0=In operat. 0=Off s=seconds M=manual A=A alarm B=B alarm 1=Stop 1=On m=minutes A=automatic Alarm no. Priority Alarm text Function 107 HEATING WATER TEMP I/O-7 BELOW SET POINT. Temperature for heating water control on I/O module is continuously 7°C below its current set point. A*** 1 0 30 m M 108 COOLING WATER TEMP I/O-7 ABOVE SET POINT Temperature for cooling water control on I/O module is continuously 7°C above its current set point. 0*** 1 0 30 m M 109 HEATING WATER TEMP I/O-7 ABOVE SET POINT Temperature for heating water control on I/O module is continuously 7°C above its current set point. 0*** 1 0 30 m M 110 COOLING WATER TEMP SENSOR I/O-7 DEFECTIVE Obtained if the cooling water temperature sensor temp is not connected or is defective. B 1 0 3s A 111 HEATING WATER TEMP SENSOR I/O-7 DEFECTIVE Obtained if the heating water temperature sensor is not connected or is defective. A 1 0 3s A 143 NO COMMUNICATION W OPTIMIZE The AHU control unit cannot establish correct communication with OPTIMIZE. B*** 0 1 10 s A *** Blocked if the hand terminal does not display the main menu. We reserve the right to alter specifications without notice. www.swegon.com 51 GB.GOLDLP.160901 19 INFORMATIVE MESSAGES Informative messages are displayed in the hand-held micro terminal. Informative messages are displayed only when the user is viewing the Main menu. Informative messages provide particulars about necessary settings that have not been entered or unfavourable operating scenarios, for instance. Message No. 52 Message Text 1 FILTER CALIBRATION NOT EXECUTED The pressure across the filters was not calibrated after the first start. Recurrent at 24-hour intervals. The message will not be received after the pressure across the filters has been calibrated. 2 H EXCH CALIBRATION NOT EXECUTED The pressure across the heat exchanger was not calibrated after the function was activated for the first time. Recurrent at 24-hour intervals. The message will not be received after the pressure across the heat exchanger has been calibrated. 3 SPARE 4 INCORRECT DIP SWITCH SETTINGS DIL switches on the control circuit card are set in a forbidden combination. 5 SPARE 6 MODEM/E-MAIL ERROR Error in communication to the modem or error when e-mail is being delivered. The message will be displayed after ten attempts. 7 PREFILTER CAL NOT EXECUTED The pressure across the prefilters was not calibrated after the first start. Recurrent at 24-hour intervals. The message will not be received after the pressure across the prefilters has been calibrated. www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 20 TECHNICAL DATA 20.1 Dimensions, GOLD LP one-piece unit Clear service space Electrical equipment cubicle A 500 A clear space of 500 mm open space must be provided in front of inspection panels on the inspection side or in front of the extra inspection panel on the long sides for changing the filters. A clear space of at least 200 mm must be provided above the electrical equipment cubicle for opening its cover. C F Excluding slide rails. Ø 11 D Centre-to-centre dimension between holes in the mounting brackets E B1 62 L 30 J 72 95 J 12 36 12 36 Power connection G 150 Extra inspection panel. 340 H2 K H1 Slide rail B2 I Including slide rails. GOLD LP 05 08 A B1 B2 C D E F G H1 H2 I J K L kg 731 807 1052 1210 1100 1258 635 675 1210 1410 481 480 1111 1269 425 500 507 582 560 635 50 48 454 533 400 475 2172 2370 247 301 www.swegon.com 53 We reserve the right to alter specifications without notice. GB.GOLDLP.160901 20.2 Electrical Equipment Cubicle The electrical equipment cubicle contains two units: the control unit and the power unit. The GOLD LP control unit and the power unit are located inside the electrical equipment cubicle. For access, remove the cover of the electrical equipment cubicle. 54 Pressure sensor, supply air fan Red Brown Black VOC sensor, TBLZ-60 (accessory) Pressure sensor, extract air fan Brown Blue Orange Violet Red Green 32-36 V AC from transformer www.swegon.com 18 V AC from transformer 24 V AC from transformer Brown Blue Black Heat exchanger motor w d llo ack Re Ye Bl Rotation monitor sensor Control unit Temperature sensor, extract air 20.2.1 Internal Connections Temperature sensor, outdoor air Sensor, supply air temperature Communication, hand-held micro terminal Air heater (accessory). Electrical equipment cubicle We reserve the right to alter specifications without notice. GB.GOLDLP.160901 Cable, 230 V power supply Power unit LP 05 230 control voltage, output PE L N PE L N 201 202 3A Yellow Yellow Extract air fan Yellow/Green Brown Blue Blue Brown Yellow/Green Transformer Supply air fan LP 08 Cable, 400 V power supply 230 control voltage, output L N PE PE L1 L2 L3 N 3A Yellow Yellow Yellow/Green Extract air fan Yellow/Green Brown Brown Black Black Grey Grey We reserve the right to alter specifications without notice. Transformer Supply air fan www.swegon.com 55 GB.GOLDLP.160901 20.2.2 Connection to Terminal Blocks External sensor and Memory card for logIQnomic Plus modules DIL selector switch ging and upgrading 3 4 5 6 7 8 9 10 1112 13 Communication, hand-held micro terminal ON 1 2 Network connection Temperature sensor, supply air Controller, air heater Pressure sensor, extract air fan* Pressure sensor, supply air fan* 1415 16 17 18 19 20 21 22 2324 2526 272829 303132 3334353637 Digital inputs, terminals 5–8, are of extra-low voltage type. Analogue inputs, terminal 37 has an input impedance of 66 k.Ω. Temperature sensor, outdoor air* Temperature sensor, extract air* * The designations apply to the right-hand version. In the left-hand version, the sensors change function and designation (the components are named according to whether they are for supply air or extract air). Terminal Function Remarks 1,2 Output 1 Select function individually. Independent contact, max. 5 A/AC1, 1A/AC3, 250 V AC. 3,4 Output 2 Select function individually. Independent contact, max. 5 A/AC1, 1A/AC3, 250 V AC. 5,6 Input 1 Select function individually. 7,8 Input 2 Select function individually. 9,10 Control voltage Control voltage: 24 V AC, max. permissible load : 28 VA. 9 (G), 10 (G0). 11,12,13 Connections for EIA 485 11 communication connection A/RT+, 12 communication connection B/RT–, 13 = GND/COM. 14,15,16, 17 Heat exchanger motor 14 Earth, 15 Red, 16 Yellow, 17 Black. 18,19,20 Rotation monitor sensor 18 Brown, 19 Blue, 20 Black. 21,22 Supply voltage, H EXCH control 36 V AC, in 23,24 Supply voltage, control unit 18 V AC, in 25,26 Supply voltage, outputs 24 V 24 V AC, in 27,28,29 Not used. 30,31,32 Damper actuator, air recirculation damper 30 (G0) Black 24 V AC(-), 31 (G) Red 24 V AC(+), 32 (NO) White 24 V AC out if active. 33 Output, fixed power supply: 12 V DC out 12 V DC to GND. Max permissible load: 500 mA 34 PWM input for Clean Air Control VOC sensor 35 Measuring zero, GND 36 Output, fixed power supply: 10 V DC out 10 V DC to GND Max. permissible load: 20 mA. 37 Input, 0–10 V DC, for demand-controlled control of the airflow or set point displacement Air quality sensor DIL selector switches: GOLD LP, right-hand version: DIL switch 6 must be set to the ON position, the other switches must be set to the OFF position. GOLD LP, left-hand version: DIL switches 1 and 6 must be set to the ON position, the other switches must be set to the OFF position. 56 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 20.3 Electrical Data 20.3.1 Air Handling Unit MIN. POWER SUPPLY Size 05: 1-phase, 3-wire, 230 V -10/+15%, 50/60 Hz, 10 AT Size 08: 3-phase, 5-wire, 400 V -10/+15%, 50/60 Hz, 10 AT 20.3.2 Fans RATED DATA PER FAN Size 05: 1 x 230 V, 50/60 Hz, 0.74 kW. Size 08: 3 x 400 V, 50/60 Hz, 1.0 kW. 20.3.3 Electrical equipment cubicle One 2-pole 3A Automatic circuit breaker for 230V control current 20.3.4 Heat Exchanger Motor Step motor, 3-phase, 5.8 A (2A)*, 50 V max 90 V. *) The motor controls limit the output power to the value specified. 20.3.5 Control Inaccuracy Temperature ± 1oC. Airflow ± 5%. We reserve the right to alter specifications without notice. www.swegon.com 57 (Great Britain) GB.GOLDLP.160901 21ANNEXES EC DECLARATION OF CONFORMITY FOR THE MACHINERY Original 21.1 Compliancy Declaration Directive 2006/42/EC Swegon AB Box 300 S-535 23 Kvänum, Sweden declare under our own sole responsibility that Air handling units with the following designation: GOLD RX, GOLD PX, GOLD CX, GOLD LP, GOLD SD and any accessories to the respective designation covered by these directives comply with the Machinery Directive 2006/42/EC and also to the following directives 2004/108/EG EMC, (Electromagnetic Compatibility Directive) 2006/95/EG LVD, (Low voltage directive) The following harmonised standards have been applied: EN ISO 12100:2010 (Machinery safety – General principle for design – Risk assessment and risk reduction) EN ISO 13857:2008 (Safety of Machinery -, Safety distances from machinery to prevent hazard zones being reached by upper and lower limbs) EN 60204-1 (Safety of machinery – Electrical equipment of machines) EN 61000-6-2, -3 (Electromagnetic compatibility) EN 61800-3 (Adjustable speed electrical power drive systems) The following other standards and specifications have been applied: EN 1886:2007 (Ventilation for buildings, air handling units – Mechanical performance) EN 13053:2006 (Ventilation for buildings, air handling units - Rating and performance for units, components and sections) Person authorised to compile the technical documentation: Dan Örtengren Box 300 SE-535 23 Kvänum, Sweden This declaration is applicable only if the air handling unit(s) has/have been installed according to Swegon’s instructions and provided that the air handling unit(s) has/have not been modified in any way. Kvänum, 01/28/2011 Thord Gustafsson, Quality and Environmental Manager, Swegon AB 58 www.swegon.com We reserve the right to alter specifications without notice. GB.GOLDLP.160901 21.2 Commissioning Record Company Our reference Client Date SO No. Plant Project/Air handling unit Subject No. Plant address Type/Size Program version: Filter calibration done Time sw. clock, current time set Other controls Settings – time channels (scheduling), time switch clock Channel Operating mode Times Week day 1 Low High : – : : 2 Low High : – : : 3 Low High : – : : 4 Low High : – : : 5 Low High : – : : 6 Low High : – : : 7 Low High : – : : 8 Low High : – : : Settings – year channel (scheduling), time switch clock Channel Operating mode Times Period 1 Inactive Stop High Low : – : / – – / – 2 Inactive Stop High Low : – : / – – / – 3 Inactive Stop High Low : – : / – – / – 4 Inactive Stop High Low : – : / – – / – 5 Inactive Stop High Low : – : / – – / – 6 Inactive Stop High Low : – : / – – / – 7 Inactive Stop High Low : – : / – – / – 8 Inactive Stop High Low : – : / – – / – We reserve the right to alter specifications without notice. www.swegon.com 59 GB.GOLDLP.160901 Function Factory-preset value Adjusted value Temperature Temp. Reg. (Control) function Difference SA/EA (°C) Step Breakpoint (°C) X1 Y1 X2 Y2 X3 Y3 Setpoint (°C) Min. SA temp. (°C) Min. SA temp. (°C) Outdoor temp. compensation Temperature Winter comp. Y1 (°C) End point, winter X1 (°C) Starting point, winter X2 (°C) Startpoint summer X3 (°C) Endpoint summer X4 (°C) Summer comp. Y2 (°C) Summer night cooling X ERS 1 21.5 X Inactive 60 www.swegon.com ERS 2 SA 21.5 15.0 28.0 Inactive Active Active Inactive Active Active Inactive Active X Inactive Active Inactive Active X Inactive Active Inactive Active X Inactive Active Inactive Active X Inactive IQnom Comm. Inactive IQnom Comm. X Inactive IQnom Comm. Inactive IQnom Comm. 3.0 -20.0 10.0 25.0 40.0 2.0 X Inactive 16.0 18.0 28.0 External outdoor ERS 1 Active EA/Room start (°C) EA/Room stop (°C) SA Night setpoint (°C) SA flow (m²/s / Pa) SA flow (m²/s / Pa) Damper output Morning BOOST Time (hh:mm) Damper External sensor External EA/Room EA 15,0 20.0 20.0 18.0 22.0 14.0 22.0 16.0 10.0 10.0 23:00 06:00 EA/Room temp EA min SA max Set point displacement SA 3,0 2 22,0 EA temp. start (°C) EA temp. stop (°C) Outdoor air temp. stop (°C) SA Setpoint (°C) In-oper. time start (hh:mm) In-oper. stop (hh:mm) Intermittent night-time heating EA fan ERS 2 X Inactive 2) 0.0 =0 00:00 22.0°C 15.0°C 28.0°C We reserve the right to alter specifications without notice. EA GB.GOLDLP.160901 Function Factory-preset value Flow/pressure Fan Regulation, SA* Fan Regulation, EA* Flow, low speed* Flow, high speed* Flow, max speed Flow, min. speed Pressure, low speed* Pressure, high speed* Max. fan speed* Pressure, max speed * Demand-contr., low speed Demand-contr., high speed Clean Air Control Outdoor temp. compen. Flow Winter compens. Y1 (%) End point, winter X1 (°C) Start. point, winter X2 (°C) Down-speed regulation Function Neutral zone (°C) In-operation Time switch clock function Slave control C-Factor Filter function Prefilter Extended operation External low speed (h:mm) External low speed (h:mm) X Flow X Flow SA EA SA EA SA EA SA EA SA (Pa) EA (Pa) SA (Pa) EA (Pa) SA (%) EA (%) SA (Pa) EA (Pa) SA (%) EA (%) SA (%) EA (%) Adjusted value Pressure Need Slave Flow Pressure Need Slave Pressure Need Slave Flow Pressure Need Slave 1) 1) 1) 1) 2) 2) 2) 2) 4) 3) 4) 4) 3) 4) 5) 5) 100 100 200 200 100% 100% 400 4) 400 4) 25 25 50 50 X Inactive Active Inactive Active X Inactive Active Inactive Active 30 -20 10 Inactive X SA SA + EA Inactive SA SA + EA 0,0 X 1. Low – high 2. Stop – low – high 1. Low – high 2. Stop - low - high 1,0 Inact. SA EA X SA+EA Inact. SA EA SA+EA X Inact. SA EA SA+EA Inact. SA EA SA+EA 0:00 0:00 * Not used for Clean Air Control We reserve the right to alter specifications without notice. www.swegon.com 61 GB.GOLDLP.160901 Function Factory-preset value Summer/winter time Adjusted value Inactive X Active Heating Heat exchanger Defrosting X Inactive Active Inactive Active Inactive Active Reheating Exercising X Inact. Exercise period Interval "Heating BOOST" Function, Off/On 3 Min. 24 hrs. Pump X Inactive Start limit, SA temp. (°C) Active Cooling Cooling unit controls Stepless Stepless 0-10 V 10-0 V On/off X On/off 1-step 2-step On/off 3-step binary mode Auto operation Active Inactive Auto operation Pump P+V Valve Inactive Pump P+V Valve Cooling relay 2 X Inactive Pump P+V Valve Inactive Pump P+V Valve Comf. Econ. Sequ. Inactive Comf. Econ. Sequ. 3 Min. 24 hrs. Step 1 (°C) Step 2 (°C) Step 3 (°C) 300 3,0 5,0 7,0 480 0,1 0,1 2,0 X Inactive (%) Econ.+sequ. Comf.+econ. Econ.+sequ. 3,0 2,5 X Inactive Active Inactive Active 50% A Alarm output 6) B Alarm output 6) External low speed 7) External high speed 7) I/O Module No. 3 Input/Output connections Ext. monitoring I/O Module No. 6 Ext. cooling I/O Module No. 9 Preheating www.swegon.com P+V Stepless Stepless 0-10 V 10-0 V On/off On/off 1-step 2-step On/off 3-step binary mode Comf.+econ. 62 Valve X Inactive "Cooling BOOST" Rel. hum., SA (%RH Inputs/Outputs Relay 1 Relay 2 Input 1 Input 2 "IQnomic Plus" I/O Module No. 0 Inactive Pump Cooling relay 1 Reset time (s) Cool. min. SA flow (m³s) Cool. min. EA flow (m³s) Neutral zone (°C) Start limit SA temp. (°C) Ramp time Humidity Dehumidification control Inact. 2.5 X Inactive Exercise period Interval Control reaction speed Step duration (s) Outdoor temp. limit P+V 3,0 Ramp time (%) Exercising Valve X Inactive Active Inactive Active X Inactive Active Inactive Active X Inactive Active Inactive Active X Inactive Active Inactive Active We reserve the right to alter specifications without notice. GB.GOLDLP.160901 Function All Year Comfort Factory preset value X Inact. Inact. Cool. Active Inact. Active Active Inact. Active Active Inact. Active Inact. Active Inact. Active X Inact. Active Inact. Active Inact. Active Inact. Active X Inact. Active Inact. Active X Inact. 2 Active Inact. Active X Inact. Active Inact. Active Inact. Open Inact. Active Inact. Open Inact. Active Heating water temp. (°C) Cooling water temp. (°C) Outdoor comp., Heating water 30 14 Outdoor temp. (X1) (°C) Heating water (Y1)(°C) Outdoor temp. (X2)(°C) Heating water (Y2)(°C) Outdoor temp. (X3)(°C) Heating water (Y3)(°C) Outdoor comp., Cooling water -20 40 5 30 15 20 Outdoor temp. (X1) (°C) Cooling water (Y1)(°C) Outdoor temp. (X2)(°C) Cooling water (Y2)(°C) Outdoor temp. (X3)(°C) Cooling water (Y3)(°C) Room comp., Heating water 10 22 20 18 25 14 Room temperature (°C) P-band (°C) Night blocking 21 5 Room comp., Cooling water Room temperature (°C) P-band (°C) Night blocking Night comp., Heating water Temp. comp. (°C) Night comp., Cooling water Temp. comp. (°C) Night comp. Channel 1, Start, Stop, Weekday Channel 2, Start, Stop, Weekday Pump operation, Heating water Outdoor temp. Start (°C) Outdoor temp. Stop (°C) Pump operation, Cooling water Outdoor temp. Start (°C) Outdoor temp. Stop (°C) Alarm function, Heating water Pump alarm Valve Alarm function, Cooling water Pump alarm Valve X Inact. X Inact. X Inact. Cool. Adjusted value Heat. C+H Heat. C+H Close Cont. Close Cont. 21 5 -2 Inactive Inactive 15 18 -20 -25 X Inact. X Inact. X Inact. X Inact. Open Close Cont. Active Open Close Cont. Active Exercising, Heating water X Inact. Pump P+V Valve Inact. Pump P+V Valve Exercising period, (min) Interval (h) Exercising, Cooling water 3 24 X Inact. Pump P+V Valvev Inact. Pump P+V Valve Inact. Active Exercising period, (min) Interval (h) Dew point comp. 3 24 Neutral zone (°C) Comp. air flow (%) 2 10 X Inact. We reserve the right to alter specifications without notice. Active www.swegon.com 63 GB.GOLDLP.160901 Function Factory preset value OPTIMIZE X Upper damper limit (%) Lower damper limit (%) Step size (Pa) Interval (min) Permissible deviation (Pa) Power up start delay (min) Min. pressure (Pa) Max. pressure (Pa) Inactive Active Adjusted value Inactive Active 90 70 20 2 10 15 50 400 "IQnomic Plus" I/O module Nr 0 Input/Output I/O module Nr 3 Ext. monitoring X Inactive Active Inactive Active X Inactive Active Inactive Active If active, function: I/O module Nr 6 Ext. cooling I/O module Nr 7 All Year Comfort I/O module Nr 8 I/O module Nr 9 Booster air diffusers Preheating I/O module Nr A Heating zone I/O module Nr B Cooling zone 64 www.swegon.com X Inactive Active Inactive Active X Inactive Active Inactive Active X Inactive Active Inactive Active X Inactive Active Inactive Active X Inactive Active Inactive Active X Inactive Active Inactive Active We reserve the right to alter specifications without notice. GB.GOLDLP.160901 Function Factory-preset value Alarm setting Fire alarm function Internal fire alarms External fire alarm X Inactive Alarm resetting Fan oper. in the event of a fire X X Inactive SA fan speed in event of fire (%) EA fan speed in event of fire (%) External alarms Time delay Alarm 1 (s) Alarm on closure, Alarm 1 Alarm reset 100 100 Time delay Alarm 2 (s) Alarm on closure, Alarm 2 Alarm reset 10 1 Alarm limit temperature Deviation, SA setpoint Min. EA temperature Filter function Filter alarm limit SA (%/Pa) EA (%/Pa) H EXCH defrosting Alarm limit (Pa) Service period Alarm limit (month) Alarm priority See the following pages Hand-held micro terminal settings Language Flow unit Min./max. setting Setpoint, SA/EA (°C) Min. limit, SA (°C) Max. limit, SA (°C) Break point, ERS Regulation (°C) SA/EA Difference (°C) Initial setting Communication EIA-485 Protocol Address Speed Parity Stop bit Man. Adjusted value Active Inactive Active Auto Man. Auto SA EA SA+EA Inactive SA Auto Man. Auto Auto Man. Auto l/s m3/s EA SA+EA 10 1 X Man. X Man. 5,0 15,0 10/100 10/100 50 12 English l/s X m3/s m3/h m3/h 15,0/40,0 13,0/18,0 25,0/45,0 15,0/23,0 1,0/5,0 – Modbus RTU 1 PLA (Exoline) 1 ELA (Exoline) 1 9600 None 1 We reserve the right to alter specifications without notice. www.swegon.com 65 GB.GOLDLP.160901 Function Ethernet Mac Id DHCP server IP address Port no. Net mask GateWay DNS server No. 1 No. 2 Modbus TCP IP Port no. Net mask BACNet IP Function Device ID Port nr. Factory-preset value Adjusted value Individual Inactive 10.200.1.1 80 255.0.0.0 000.000.000.000 000.000.000.000 000.000.000.000 000.000.000.000 502 000.000.000.000 Inactive 0000000 47808 The values by turns refer to sizes 05 and 08. 1) 0.2, 03 m3/s. 2) 0.3, 0.4 m3/s. 3) 0.53, 0.74 m3/s. 4) Only in combination with Cooling BOOST. 0.53, 0.74 m3/s. 5) Only in combination with Demand control. 0.08, 0.20 m3/s. 6) Possible options: Control of outdoor air/exhaust air damper, in-operation indication, low speed operation indication, indication or high speed operation, group alarm A, group alarm B, control of external heating, control of external cooling. 7) Possible options: External stop, external low speed operation, external high speed operation, external alarm 1, external alarm 2, external reset, external heating, external fire alarm. 66 www.swegon.com We reserve the right to alter specifications without notice. Alarm No.: GB.GOLDLP.160901 Factory preset value Priority Function Indication 0=blocked LED A=A alarm 0=Off B=B alarm 1=On Adjusted value Effect 1=Stop External fire alarm tripped A**** 1 1* 2 Internal fire alarm tripped A**** 1 1* 3 Frost protection below alarm limit A**** 1 1* 4 R.hx. speed monitor tripped A 1 0** 5 Frost protection sensor defective A**** 1 1* 6 Supply air temp sensor defective A 1 1 7 Extract air temp sensor defective A 1 1 8 Outdoor air temp sensor defective B 1 0 9 No communication to r.hx. controller A *** 1 1 10 No communication to SA frequency conv. A *** 1 1 11 No communication to EA frequency conv. A *** 1 1 12 Over current in SA frequency conv. A *** 1 1 13 Over current in EA frequency conv. A *** 1 1 14 Under voltage in SA frequency conv. A *** 1 1 15 Under voltage in EA frequency conv. A *** 1 1 18 Excess temperature in SA frequency inverter A*** 1 1 19 Excess temperature in EA frequency inverter A*** 1 1 20 No communication SA frequency range gateway A*** 1 1 No communication EA frequency range gateway A*** 1 1 22 Hall sensor defective SA frequency range A*** 1 1 23 Hall sensor defective EA frequency range A*** 1 1 24 SA frequency range blocked A*** 1 1 25 EA frequency range blocked A*** 1 1 26 Start-up failure SA frequency range A*** 1 1 27 Over voltage in EA-2 frequency conv. A *** 1 1 30 Ext. EA/room temp sensor defective A *** 1 1 31 Ext. outdoor temp sensor defective B *** 1 0 34 Over current in r.hx. controller A *** 1 1 35 Under voltage in r.hx. controller A *** 1 1 36 Over voltage in r.hx. controller A *** 1 1 37 Over temperature in r.hx. controller A *** 1 1 38 R.hx pressure drop above alarm limit B *** 1 0 39 El.heating coil tripped A *** 1 1 40 Extract air temp below alarm limit A *** 1 1 41 Supply air temp below setpoint A *** 1 1 42 Ext.alarm No.1 tripped A*** 1 1 We reserve the right to alter specifications without notice. Indication Effect LED 0=Operat. A=A alarm 0=Off 1=Stop B=B alarm 1=On 0=Operat. 0=blockedt 1 21 Priority www.swegon.com 67 GB.GOLDLP.160901 Alarm No.: Factory preset value 68 Function Priority Indication 0=blocked LED A=A alarm 0=Off B=B alarm 1=On Adjusted value Effect 1=Stop 43 Ext. alarm No.2 tripped B *** 1 0 44 SA duct pressure below setpoint B *** 1 0 45 EA duct pressure below setpoint B *** 1 0 46 SA duct pressure above setpoint B *** 1 0 47 EA duct pressure above setpoint B *** 1 0 48 Supply airflow below setpoint B *** 1 0 49 Extract airflow below setpoint B *** 1 0 50 Supply airflow above setpoint B *** 1 0 51 Extract airflow above setpoint B *** 1 0 52 Supply air filter dirty B *** 1 0 53 Extract air filter dirty B *** 1 0 54 Service period past alarm limit B *** 1 0 55 No comm. SA air flow pressure sensor A *** 1 1 56 No comm. EA air flow pressure sensor A *** 1 1 57 No comm. SA filter pressure sensor B *** 1 0 58 No comm. EA filter pressure sensor B *** 1 0 59 No comm. SA duct pressure sensor A *** 1 1 60 No comm. EA duct pressure sensor A *** 1 1 61 No comm. r.hx. pressure sensor B *** 1 0 62 No communication to I/O-module No:0 B *** 1 0 63 No communication to I/O-module No:1 B *** 1 0 64 No communication to I/O-module No:2 B *** 1 0 65 No communication to I/O-module No:3 B *** 1 0 66 No communication to I/O-module No:4 B *** 1 0 67 No communication to I/O-module No:5 B *** 1 0 68 No communication to I/O-module No:6 B *** 1 0 69 No communication to I/O-module No:7 B *** 1 0 70 No communication to I/O-module No:8 B *** 1 0 71 No communication to I/O-module No:9 B *** 1 0 72 No communication to main controller I/O A 1 1 75 Supply air humidity sensor faulty A *** 1 1 76 Extract air humidity sensor faulty A *** 1 1 83 Supply air, prefilter fouled. B*** 1 0 84 Exhaust air prefilter, fouled B*** 1 0 85 Cooling Output 1 tripped A 1 0 86 Cooling Output 2 tripped A 1 0 89 No comm. with press. sensor by SA prefilter B*** 1 0 www.swegon.com Priority Indication Effect LED 0=Operat. A=A alarm 0=Off 1=Stop B=B alarm 1=On 0=Operat. 0=blockedt We reserve the right to alter specifications without notice. GB.GOLDLP.160901 Adjusted value Alarm No.: Factory preset value Function 90 No comm. with press. sensor by EA prefilter B*** 1 0 91 Frost prot. for preheating, below alarm limit A 1 1 92 Frost prot. for preheating sensor, faulty A 1 1 93 Preheating sensor faulty A 1 1 94 Electric air heater for preheating, tripped A*** 1 1 95 Preheating below setpoint A*** 1 1 96 Lost settings A 1 1 99 Time lock tripped A 1 1 Priority Indication 0=blocked LED A=A alarm 0=Off B=B alarm 1=On Effect Priority Indication Effect LED 0=Operat. A=A alarm 0=Off 1=Stop B=B alarm 1=On 0=Operat. 0=blockedt 1=Stop 102 Cooling valve I/O-7 defective B*** 1 0 103 Heating valve I/O-7 defective A*** 1 0 104 Cool. circuit pump I/O-7 tripped B*** 1 0 105 Heat. circuit pump I/O-7 tripped A*** 1 1 106 Cooling water temp. I/O-7 below set point B*** 1 0 107 Heat. water temp. l I/O-7 below set point A*** 1 0 108 Cooling water temp. I/O-7 above set point 0*** 1 0 109 Heating water temp. I/O-7 above set point 0*** 1 0 110 Cooling water temp. sensor I/0-7 defective B 1 0 111 Heating water temp. sensor I/0-7 defective A 1 0 143 No communication - OPTIMIZE B*** 1 0 * Not adjustable, always stops the air handling unit ** Not adjustable, stops the air handling unit at temperature below +5 °C *** Blocked if the hand terminal does not display the main menu. **** Cannot be blocked. Adjustments carried out by: Date Company Name We reserve the right to alter specifications without notice. www.swegon.com 69 70 www.swegon.com Available static pressure, Pa 08 05 Size Full face Duct Full face Duct In and outlet connections Remark Min. - low Min. - high Average Max. - high Max. - low Min. - low Min. - high Average Max. - high Max. - low Min. - low Min. - high Average Max. - high Max. - low Min. - low Min. - high Average Max. - high Max. - low Colour Red Red Yellow Blue Red Red Red Yellow Blue Red Red Red Yellow Blue Red Red Red Yellow Blue Red Working point NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU NRVU, BVU AHU type variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed variable speed Type of drive Other Other Other Other Other Other Other Other Other Other Other Other Other Other Other Other Other Other Other Other Type of HRS Recommended average working point. Remaining outer limits. Nominal flow rate m³/s 0,08 0,08 0,34 0,49 0,49 0,08 0,08 0,34 0,50 0,50 0,10 0,10 0,48 0,72 0,72 0,10 0,10 0,48 0,73 0,73 Thermal efficiency % 71 71 81 79 79 71 71 81 79 79 66 78 80 78 78 66 78 80 78 78 Part of information requirements for NRVU according to Regulation (EU) No 1253/2014 Overall fan Internal Nominal Effective efficiency Face pressure drop external electric SFPint (EU) No velocity vent. comp. pressure power 327/2011 kW W/(m³/s) m/s Pa Pa % 0,04 495 0,4 0 24 59,3 0,54 166 0,4 994 24 59,3 0,42 647 1,6 300 148 59,3 0,67 1244 2,4 241 255 59,3 0,54 1463 2,4 0 255 59,3 0,04 491 0,4 0 24 59,3 0,54 164 0,4 994 24 59,3 0,42 624 1,6 300 143 59,3 0,67 1206 2,4 243 244 59,3 0,53 1433 2,4 0 244 59,3 0,03 0 0,4 0 24 65,8 0,89 1248 2,5 211 277 65,8 0,60 613 1,7 350 157 65,8 0,89 1248 2,5 211 277 65,8 0,73 1417 2,5 0 277 65,8 0,03 0 0,4 0 23 65,8 0,88 1142 2,6 220 246 65,8 0,58 553 1,7 350 141 65,8 0,88 1142 2,6 220 246 65,8 0,71 1323 2,6 0 246 65,8 The lower limit for the airflow when the unit is operating in the airflow regulation mode. Air flow, m3/s % 5 5 1 1 - Maximum external leaking rate Outer limit - largest permissible air flow at maximum speed. Max. limit, Ecodesign 2016. % 1 1 1 1 - Maximum internal leakage kWh/year 2170 2200 2930 3090 - Energy performance of filters dB(A) 18 58 48 52 52 17 58 48 52 52 19 55 50 55 55 19 55 50 55 55 Casing sound power level, LwA Permissible operating range in accordance with regulation 1253/2014 Working point with the highest air flow shall be found within the permissible area. In case of unbalanced air flows; mean working point, supply extract shall be used. Working points with less air flow is allowed to be found outside the permissible range e.g. in case of variable air flow. Permissible operating range when the fan is controlled to operate at a lower speed. If pressure regulation is used, the airflow can be regulated to zero, however this presupposes a certain static pressure drop in the ducting (approx. 50 Pa). Recommended range for the design working point. GB.GOLDLP.160901 21.3 Ecodesign data We reserve the right to alter specifications without notice. GB.GOLDLP.160901 We reserve the right to alter specifications without notice. www.swegon.com 71 GB.GOLDLP.160901 All documentation is available in digital form and can be downloaded from www.swegon.com 72 www.swegon.com We reserve the right to alter specifications without notice.
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement