ON/OFF remote controller Mitsubishi Electric PAC

Add to my manuals
1 Pages

advertisement

ON/OFF remote controller Mitsubishi Electric PAC | Manualzz

GB

WT03777X02

CITY MULTI Control System and Mitsubishi Mr. SLIM Air Conditioners

ON/OFF remote controller

Installation Manual

PAC-YT40ANRA

The content of this instruction manual is limited to the installation of an ON/OFF remote controller (hereafter remote controller) that is capable of managing and controlling a maximum of 50 units comprised of air conditioners, LOSSNAY units and general purpose interface (the units can be spread over a maximum of 16 groups). For information on how to wire and install the air conditioning units, refer to this manual for them.

To ensure a safe environment is maintained, read the following 1 Safety Precautions and perform installation work accordingly.

1 Safety Precautions

● Read these Safety Precautions and perform installation work accordingly.

● The following two symbols are used for dangers that may be caused by incorrect use and their degree of severity:

WARNING

This symbol denotes what could lead to serious injury or death if you misuse the PAC-YT40ANRA.

CAUTION

This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PAC-YT40ANRA.

● After reading this manual, keep in a handy place. When removing or repairning the unit, give this manual to the installer. When the user changes, also give to the new user.

Ask your dealer or technical representative to install the unit.

Any deficiency caused by your own installation may result in an electric shock or fire.

Install in a place which is strong enough to withstand the weight of the

PAC-YT40ANRA.

Any lack of strength may cause the PAC-YT40ANRA to fall down, resulting in personal injury.

Firmly connect the wiring using the specified cables. Carefully check that the cables do not exert any force on the terminals.

Improper wiring connections may produce heat and possibly a fire.

Never modify or repair the PAC-YT40ANRA by yourself.

Any deficiency caused by your modification or repair may result in an electric shock or fire.

Consult with your dealer about repairs.

WARNING

Ensure that installation work is done correctly following this installation manual.

Any deficiency caused by installation may result in an electric shock or fire.

All electrical work must be performed by a licensed technician, according to local regulations and the instructions given in this manual.

Any lack of electric circuit or any deficiency caused by installation may result in an electric shock or fire.

Do not move and re-install the PAC-YT40ANRA yourself.

Any deficiency caused by installation may result in an electric shock or fire.

Ask your distributor or special vendor for moving and installation.

To dispose of this product, consult your dealer.

Do not install in any place exposed to flammable gas leakage.

Flammable gases accumulated around the body of PAC-YT40ANRA may cause an explosion.

Do not use in any special environment.

Using in any place exposed to oil (including machine oil), steam and sulfuric gas may deteriorate the performance significantly or give damage to the component parts.

Wire so that it does not receive any tension.

Tension may cause wire breakage, heating or fire.

Completely seal the wire lead-in port with putty etc.

Any dew, moisture, insects entering the unit may cause an electric shock or a malfunction.

Do not wash with water.

Doing so may cause an electric shock or a malfunction.

Do not install in any place at a temperature of more than 40

°

C or less than

0

°

C or exposed to direct sunlight.

Do not install in any steamy place such as a bathroom or kitchen.

Avoid any place where moisture is condensed into dew. Doing so may cause an electric shock or a malfunction.

Do not install in any place where acidic or alkaline solution or special spray are often used.

Doing so may cause an electric shock or malfunction.

CAUTION

Use standard wires in compliance with the current capacity.

A failure to this may result in an electric leakage, heating or fire.

Do not touch the PCB (Printed Circuit Board) with your hands or with tools. Also do not get dirt on the PCB.

It may cause a fire or mulfunction.

Do not remove the insulation sheet.

Doing so may cause an electric shock.

Do not touch any control switch with wet hands.

Doing so may cause an electric shock or a malfunction.

Do not press any control switch using a sharp object.

Doing so may cause an electric shock or a malfunction.

Never contact the power supply with the control wiring terminals.

Doing so will certainly cause the controller to catch fire.

When installing the remote controller in a hospital or communication facility, take ample countermeasures against noise.

Inverters, emergency power supply generators, high-frequency medical equipment, and wireless communication equipment can cause the remote controller to malfunction or to fail. Radiation from the remote controller may effect communication equipment and prevent medical operations on the human body or interfere with image transmission and cause noise.

2 Confirming the Supplied Parts

Confirm that the box includes the following parts, in addition to this installation manual:

1. Remote controller (cover, body, Remote controller lower case) ................................... 1

2. Cable for external input (5 wire) ................................................................................... 1

3. Cable for external output (4 wire) ................................................................................. 1

4. Cross recessed pan head screw (M4

× 30) ................................................................. 2

5. Wood screw (4.1

× 16, used for directly hooking to the wall) ....................................... 2

6. Room name sheet ....................................................................................................... 8 (Includes 4 spare sheets)

7. Operation Manual ........................................................................................................ 1 1

NOTE: The remote control cord is not supplied with the product.

Prepare electrical wiring that conforms to the specifications given below.

Electrical wiring specification (CVVS)

Use 1.25 mm 2 cable for any extension that exceeds 10m.

• 10m or shorter: 0.75 mm 2 two-wire cable

• Longer than 10m: 1.25 mm 2 two-wire cable

Remote controller wiring entry points can support electrical wiring of maximum 1.25 mm 2 .

However 0.75 mm 2 electrical wiring is recommended for use.

3 System Configuration

M-NET remote controller

Indoor unit Ventilation unit

ON/OFF remote controller

[059]

TB7 TB3

[015] [014] [013] [012] [011] [010] [009]

4 How To Install

1. Choose a location in which to install the system remote controller (electric box) in accordance with the following requirements:

1 The space as shown in the diagram at right is required whether the controller is installed on the wall or in the electric box.

2 Procure the following parts locally.

• Electric box for two units

• Thin-copper wiring pipe

• Locknut and bushing

External size of remote controller

30

Extra space around remote controller

30

2. Seal the remote controller cord lead-in with putty in order to prevent the possible entry of dew, water droplets, other insects.

When using the electric box

• When fitting to the electric box, seal the join between the electric box and the wiring conduit with putty.

When fitting directly on the wall

• When cutting a hole in the wall for the remote controller cord (ie when the remote controller cord exits from the rear of the remote controller), seal this hole in the same way.

• When fitting directly to the wall as in 3, seal the cut-out in the upper case with putty.

Wall

Wiring pipe

Lock nut

Electric box

Remote controller cord

Seal with putty.

Seal with putty.

Bushing

Seal with putty.

Remote controller cords

Cord Taken Through Rear of

Remote Controller

Cord Taken Through Top of Remote Controller

3. Install the lower case on the electric box or directly on the wall.

When installing the electric box

Remote controller cord

(See 4 below)

In the case where external input and output functions are used

Electric box for two units

Cross recessed pan head screws

Connects to CN1 of the remote controller main unit

Refer to 8

Push open the knock-outs covering the entry points for the external input and output cables on the lower case and thread the external input and output cables as described on the left.

External output cable (4 wire)

Connects to CN3

External input cable (5 wire)

Connects to CN2

Seal the cord lead-in hole with putty or silicon rubber. (See 2 above)

External input cable entry point

External output cable entry point

When installing directly on the wall

Remote controller cord

(See 4 below)

Wood screw

Connects to CN1 of the remote controller main unit

Refer to 8

CAUTION Over-tightening the screws may result in deformation or cracking of the lower case.

NOTE: - Choose a flat plane for installation.

- Fasten the electric box at more than two places when installing directly on the wall.

4. Connect the remote controller cord to the terminal block on the lower case.

Install wiring correctly in accordance with the diagram at right.

A.1 B.2

No polarity

Remote controller cord procured locally.

(Terminal block)

CAUTION Do not use crimp terminals to connect to remote controller terminal blocks. It connects to the circuit board and will cause trouble.

5. Set the system remote controller address with the rotary switches.

Rotary switch

Remote controller main unit

× 10 × 1

Example: Address of 201

Rotary switch setting

01-50

Address

201-250

• The address No. that can be set on the remote controller is within the range of 201-250.

The 100 digit is fixed at “2”.

• If an address other than those listed above is set, an address setting error occurs and “AdE” is displayed.

• The rotary switch is set to 01 when shipped from the factory.

CAUTION Addresses between 201 and 250 may be set with the system remote controller. The place of

100 is fixed to “2”.

3

[210]

[051]

TB7 TB3

[001] [002] group 13

[113]

[003]

[112] group 12

[004]

[111] group 11

[005]

[110] group 10

[006] [007] [008]

[101] group 1

[102] group 2

[103] group 3

[201]

Central controller

Model: G-50A

Power supply unit

Model: PAC-SC50KUA

M-NET model address setup (address duplication not possible)

Address setup

Indoor unit / Interlocked unit

Outdoor unit

Any address within the range specified at right.

The smallest address of indoor unit in the same refrigerant system + 50

Remote controller

ON/OFF remote controller

The smallest address of indoor unit in the same group +100

Any address within the range specified at right.

Address

1-50

51-100

101-200

201-250

NOTE: The only indoor unit this device can be used to operate is an M-NET control indoor unit. It will not operate a K control indoor unit, even with a K transmission converter (PAC-SC25KAA).

● To connect the system controller on the transmission line for central control and connect a power supply unit for transmission lines (PAC-SC50KUA), leave the power supply switch connector (CN41) on the outdoor unit as it is.

♦ Up to 2/6/12 system controllers can be connected when a power supply unit (PAC-

SC50KUA) is connected.

Central controller

(G-50A)

1~2 unit(s) (Note 1)

ON/OFF remote controller (AN)

1~6 unit(s)

System remote controller (SR)

Schedule timer (ST)

Group remote controller (GR)

1~12 unit(s)

Power consumption of G-50A and AN are as follows:

· One G-50A unit = Three AN units

One AN consumes 1/3 as much power as one G-50A.

· One AN unit = Two GR units

One GR, SR, or ST consumes half as much power as an one AN.

(Note 1) Up to 2 central controllers (G-50A) can be connected only when different systems are kept separate.

♦ CAUTION4: Using with a certain combination of multiple system controllers.

● To connect the system controller on the transmission line for central control and be powered from the outdoor unit (Applicable only to R410A compatible models), disconnect the male connector from the female CN41 power supply switch connector, and connect it to the female CN40 power supply switch connector on only one of the outdoor units.

Up to three system controllers (AN/SR/ST/GR) can be connected on the transmission line for central control of the M-NET without the need for a power supply unit for transmission lines.

When the system controller is connected on the transmission line for central control and is powered from the outdoor unit, the number of indoor units that are connectable to each refrigerant system is reduced by 3/1/0.5 unit(s) for each system controller that is connected

SR, ST, GR G-50A

Converted into three indoor units

AN

Converted into one indoor unit

Converted into 0.5 indoor unit

[104] group 4

[105] group 5

[106] group 6

[107] group 7

[157]

Central management transmission line

Indoor and outdoor transmission line

Interlocked operation with ventilation unit

CAUTION

1. This diagram shows the configuration of transmission line, and omits power supply line for clarity.

2. Establish one shield ground for M transmission line within the system.

3. Unit remote controllers cannot be used.

4. The number of system controllers which may be supplied with power are found by multiplying the given number by the appropriate capacity coefficient in the following table (decimal fractions are rounded up).

Central controller

(G-50A)

3

Capacity coefficient

Group remote controller (GR)

ON/OFF remote controller (AN)

System remote controller (SR)

Schedule timer (ST)

1 0.5

(e.g) In the case of a system with 1 central controller, 2 ON/OFF remote controllers, and 2 group remote controllers.

These controllers are connectable because the calculation result is 6.

1

× 3 + 2 × 1 + 2 × 0.5 = 6

Total number ( 6 [AN])

Number of connected group remote controller × the coefficient

Number of connected ON/OFF remote controller × the coefficient

Number of connected central controller

× the coefficient

5. The ON/OFF Remote Controller can manage up to 50 air-conditioning or ventilation units.

6. One ON/OFF remote controller can control a maximum of 16 groups. The numbering range of the groups that can be managed can be modified using the initial settings but normally the group numbers starting from last two digits of the remote controller’s own address up until a value 15 higher than that can be managed.

(Example) Case where ON/OFF remote controller’s own address is set to

210 Group number: Groups 10 - 25 can be controlled.

In the case where a problem exists with the controlled group range determined by the remote controller’s address setting; By performing the minimum controlled group No. setting in the initial settings described later in the manual, regardless of whether this remote controller has a master setting or subordinate setting, it is possible to set a controlled group range that has no relationship with the setting value of the remote controller’s own address.

For details, refer to 5 Initial Setting .

7. As current consumption is twice that with remote controller when this equipment is connected to the indoor and outdoor transmission wiring, assume two remote controllers for each of these units when calculating connections.

2

6. When used in conjunction with the master system controller (centralized controller), set the system remote controller to “Slave” with the switch as shown in the diagram below.

• The switch is set to “Master” when shipped from the factory.

SW4-1: OFF = “master”

ON = “slave”

SW4-2, SW4-3 are for switching between external input modes.

7. Wiring hole for fitting directly on the wall

Remote Controller cord

• Cut off the shaded area from the upper cover using a knife, nippers, etc.

• Take out the remote control cord connected to the terminal block via this portion.

External input/output cables (Only in the case when using external input and output functions directly connected to the wall)

• Using a suitable knife or cutting implement, cut and remove the thin walled part on the left and right side of the remote controller main unit.

CN2 side: For external input cable

CN3 side: For external output cable

• Insert the external input/output cables through these points.

slave/ master external input mode switch

8. Connect the lower case connector to connector CN1 on the remote controller main unit.

When using the external input and output function, also connect the external input cable connector (5 wire) to CN2 and connect the external output cable connector (4 wire) to

CN3.

CAUTION • Connect firmly as shown in the diagram at right. The system will not operate unless these connections are made.

• After connecting the wiring, ensure that the upper case does not hang off the cord as shown in the diagram below at the right. This may result in a break in the cord, and thus cause problems with operation.

• Always pass the cord through the hook to hold it in place.

Hook

Connect this to connector CN1

Remote controller main unit

Remote controller lower case

9. Mount the remote controller main unit.

Remote controller main unit

To remove the remote controller main unit, insert a minus screwdriver into one of the open slots and move it in the direction of the arrow as shown in the diagram at right.

The first, hook the two upper claws and then fit it as shown in the above diagram.

When the external input and output functions are used and the lower case cable entry points are being used, mount the remote controller main unit while pushing the external input/output cables to the electric box side.

(Push towards the electric box sides from the lower case until the cable sheath part is reached.)

CAUTION Press the cover until it snaps shut. If not, it may fall off.

CAUTION

Do not turn the screwdriver in the slot. Doing so may damage the slot.

NOTE: A protective sheet has been affixed to the control panel.

Remove it before starting.

4

10. Write the room names on the room name sheet and insert it into the remote controller main unit as described below.

Write the room names with a pencil or print the room names using a commercial sticker printer and stick them on.

GROUP SETTING

ADMINI STERED

GROUP

ERROR CODE

ON

OFF

PAC-YT40ANRA

CENTRALIZED ON/OFF

Room name sheet

1

5

2

6

3

7

4

8

Meeting room 5 Meeting room 6 Meeting room 7 Meeting room 8

NOTE: A protection sheet is stuck to the room name sheet.

Remove the protection sheet before using the room name sheet.

11. Fasten the remote controller cover.

The initial setting is set while the cover is removed. Fasten the cover after performing the initial setting.

To remove the remote controller cover, gently rotate a slotted screwdriver in the claw points as shown in the right diagram.

CAUTION Press the cover until it snaps shut. If not, it may fall off.

CAUTION

When rotating the driver, gently rotate without applying much force. If too much force is applied, it could break the claw parts.

5 Initial Setting

There are the following two types of initial setting mode.

(A) Minimum controlled group No. setting

The remote controller determines the controlled group range using its own address setting. If the controlled group range that is determined by the remote controller’s own address causes trouble, change the controlled group range by performing the minimum group No. setting.

(B) Group setting

This is used to include the controllers controlled by the remote controller in each group. Indoor units, ventilation units, local remote controllers and slave system controllers are entered in each group.

• When setting a master system controller

It is necessary to perform the group setting. Moreover, it is necessary to perform minimum controlled group No. setting when required.

• When setting a slave system controller

It is necessary to perform minimum controlled group No. setting when required. The group setting is not necessary. The group setting is performed on the master system controller side.

• When interlocking control of a ventilation unit with an indoor unit, the interlocking setting is necessary but it is not set on the remote controller.

Perform the interlocking setting on the local remote controller when this remote controller is set as the master system controller or perform it on the system controller of the master system controller setting when this remote controller is set as the slave system controller.

(If a ON/OFF remote controller is set as the system controller in the master system controller setting, set the interlocking setting on the local remote controller.)

(*1) Master system controllers and slave system controller

Management range of PAC-YT40ANRA

Unit

Management range of the master system controller

Management range of PAC-

YT40ANRA

Unit

Unit

NOTE: It is not possible to set the master and slave settings with more than one group remote controller and control the same groups. Also, the groups listed below cannot be set.

Unit group which are not under the management of the master controller and are managed by the slave system controller.

A common group is managed by more than two master controllers.

Master system controller

Slave system controller

Master system controller 1

Master system controller 2

Group Group Group Group Group Group

When using a system consisting only of PAC-YT40ANRA.

PAC-YT40ANRA is set as the master system controller. In this case, the group settings are performed with PAC-YT40ANRA.

When using a system where

PAC-YT40ANRA is controller by a different system controller.

PAC-YT40ANRA is set as the slave system controller. In this case, the group settings are not performed with PAC-YT40ANRA.

A slave system controller which exceeds the management range of the master system controller of two or more.

Master system controller 1

Slave system controller

Master system controller 2

Group Group Group Group

5-1 Initial Setting Method

SW3

ERROR CODE

ON

OFF

PAC-YT40ANRA

CENTRALIZED ON/OFF

Collective ON/OFF switch

GROUP SETTING

ADMINI STERED

GROUP

Individual ON/OFF switch

1

5

2

6

3

7

4

8

1. Remove the cover.

2. Supply power to this remote controller.

Group setting

Controlled group

“HO” is displayed and Centralized Control lamp flashes.

• If groups setting information has already been registered, “H1” is displayed after the power is supplied, then the screen will be blank and normal operation becomes possible.

(This state is described below as normal mode.)

Centralized Control

3. Operation to switch to initial setting mode

• It is possible to switch to initial setting mode on when “HO” of (2) is displayed on the screen or when all groups are off in normal mode. When the

ON/OFF lamp of an individual group is lit during normal mode, press the Collective ON/OFF switch to turn off all groups.

1

Set SW3-1 to “ON”.

ON

OFF

Group setting

Controlled group

[Screen displaying remote controller’s own address]

• The remote controller’s own address flashes for about 2 seconds and then the screen display switches to the initial screen for group setting.

1 2 3 4

Group setting

Controlled group

[Initial screen for group setting]

• The address display part “- - -” and the position mark ( ) on the group setting part of the screen flash.

• If the group setting information has already been registered in the initial screen for group setting, the registered unit No. of the smallest address will be displayed.

2

(Minimum controlled group No. setting) Set SW3-2 to “ON”.

Note: Only change this setting when you want to change the group range controlled by this remote controller.

The group range controlled by this remote controller is determined by this remote controller’s address setting. If trouble arises from the controlled group range that was determined by this remote controller’s address, perform the minimum controlled group No. setting regardless of whether this remote controller is set to master setting or slave setting.

(Example) If you want to control exactly the same groups with two ON/OFF remote controllers, it is not possible to duplicate the remote controller address. Therefore the range of the groups that the two ON/OFF remote controllers can control will not match. In such a case, the minimum controlled group No. setting can be modified to determine a controlled group range that is not relative to the remote controller’s own address setting.

ON

OFF

1 2 3 4

ON/OFF

Group setting

Controlled group

Group setting

Controlled group

[Minimum controlled group No. setting screen]

• The minimum group No. (two digits) controlled by this remote controller will flash on the screen. This group No. is the group No. of Individual ON/OFF switch 1.

The screen will also display the position mark ( ), which will flash on the controlled group part of the screen.

• The group No. (two digits) display is changed by pushing the Collective ON/

OFF switch. Match the display with the group No. you want to set for the Individual ON/OFF switch 1.

01

02

· · · · · · · · · · · · · · · ·

50

Change the direction of modification by setting ON/OFF on SW3-4.

(The displayed direction will alternate between / on the screen.)

• SW3-4 = OFF: ( lit): Pressing the Collective ON/OFF switch will change the value in the + direction.

• SW3-4 = ON: ( lit): Pressing the Collective ON/OFF switch will change the value in the - direction.

• The group No. that can be controlled by this remote controller will become the range from the group No. set here until that group No. + 15.

(Example) When the remote controller’s own address is 210, and the minimum controlled group No. is modified from “10” to “25”

In this case, the controlled group No. range has been changed so that group 25 through group 40 can be controlled;

Individual ON/OFF switch 1 = Group 25, Individual ON/OFF switch 2 = Group 26, and so on to Individual ON/OFF switch 16 = Group 40.

• Switch to the initial screen for group setting of 1 by switching SW3-2 to “OFF”.

5

3

(Group Setting) Display the Address numbers you want to include.

ON/OFF Group setting

Controlled group

• Press the Collective ON/OFF switch to change the address No. display so that it matches the address No. you want to register.

- - -

000

001

002

· · · · · · · · · · · · · ·

250

ON

OFF

1 2 3 4

Group setting

Controlled group

• Switch the direction of modification by setting ON/OFF on SW3-4.

(The displayed direction will alternate between / on the screen.)

SW3-4 = OFF: ( lit): Pressing the Collective ON/OFF switch will change the displayed address in the + direction.

SW3-4 = ON: ( lit): Pressing the Collective ON/OFF switch will change the displayed address in the - direction.

• In the case when the displayed address No. is already registered, the address

No. and the registered group’s Individual ON/OFF lamp will be lit.

4

– 1 (To register) Press the Individual ON/OFF switch of the group in which you want to make an entry.

To register:

Press Individual ON/

OFF switch of desired group

Group setting

Controlled group

Individual ON/OFF lamp when address is registered in the group

• Beginning from the state where the address No. is flashing, press the

Individual ON/OFF switch of the group you want to register the address No. in.

The controller of the displayed address No. will be registered to that group.

• When this address No. is successfully registered, the address No. and lamp of the registered group will change to lit and the address No. will be included in this group.

• If there is no controller for the specified address No., or if you are trying to register different types of units to the same group, an error will occur. In such a case the address No. and the Individual ON/OFF lamp will flash.

4

– 2 (To remove) Press twice, the Individual ON/OFF switch of the group in which you want to remove an entry.

To remove entry:

Press Individual

ON/OFF switch of desired group

(Press twice)

Group setting

Controlled group

Individual ON/OFF lamp when address is removed from group

• Beginning from the state where the address No. is lit, press the Individual ON/

OFF switch of the group you want to remove the displayed entry from twice in succession.

The controller entry of the displayed address No. will be removed.

• When this removal process is performed successfully, the address No. will be flashing and the lamp of the group from which the entry was removed will change from lit to not lit.

4

– 3 (To remove all entry data) Press Individual ON/OFF switch 1 and Individual ON/OFF switch 16 simultaneously for

3 seconds.

Individual ON/OFF switch 1

+

Individual ON/OFF switch 16

Group setting

Controlled group

All Individual ON/OFF lamps

• The display will change to as shown on the left and when the removal process is successfully performed, the initial screen for group setting of 1 will be displayed.

This process also resets the minimum controlled group No. setting to the controlled group range determined by the remote controller’s own address.

5

Repeat operations

3

and

4

to perform the registration operations for all controllers.

• First register all the indoor units, stand-alone LOSSNAY units or general purpose interface, then register the local remote controller, and lastly register the slave system controller. By following this sequence for the setting operation, the registering operation can be performed smoothly.

• You cannot register units of a different type (indoor units, ventilation units) in the one group.

• A single group can have a maximum of 16 units (indoor units or ventilation units) and the combined total of local remote controllers and system controllers in the group can be as many as 4 units.

• When connecting local remote controllers to the system, you must register the local remote controller address in the group.

However, if the local remote controller is an MA remote controller, registration in the group is not required.

6

Set SW3-1 to “OFF”.

ON

OFF

Group setting

Controlled group

1 2 3 4

• Set the dip switch 3-1 to “OFF” to exit from group setting mode.

• “H1” will be displayed and the startup process will be performed.

• The startup process has completed once “H1” is no longer displayed.

The operation state becomes normal mode and normal operation is possible.

6 Using the External Input and Output

When using the external input and output functions, use the external input and output cables provided with the remote controller. (A 5 wire cable for input and 4 wire cable for output are provided.)

1.

External signal input function

(1) External Input

By using an external no voltage contact signal, it is possible to send Emergency stop/Normal, ON/OFF or Prohibit/Permit local remote controller operation commands to all units being controlled. (This is selected by the SW4 setting. SW4 is mounted on the main unit board.)

No.

External input signal functions

No.2

SW4

No.3

Comment

1

Do not use external input signal (This is the factory setting.)

OFF OFF ––––––––––––––––––

2

3

Send a level signal for Emergency stop/Normal

Send a level signal for ON/OFF

OFF

ON

ON

OFF

The Emergency stop state prohibits the ON/OFF operation from the local remote controller and the ON/OFF operation and the change

Prohibit/Permit operation from this unit.

This state prohibits the ON/OFF operation from both the remote controller and this unit.

4

Send a pulse signal for ON/OFF and Prohibit/

Permit

ON ON When the contact is ON, make the pulse duration 0.5sec or longer.

7

(2) Level signal and pulse signal

(A) Level signal

Contact ON

Contact OFF

No. 4

No. 5

Red

OFF

Brown

ON OFF

Not used

Common 0V

(B) Pulse signal

(Example) Case of ON/OFF signal

Signal 1 ON

Contact ON

Contact OFF

CN2

No. 1

No. 2

No. 3

Contact ON

Contact OFF

Normal

Emergency

STOP Normal

(3) External input specification

Lead wires (5 wires)

Green

Yellow

Orange

Signal 2 OFF

Contact ON

Contact OFF

OFF

*The same applies to Prohibit/Permit.

Level signal for Emergency stop/

Normal

Emergency stop/Normal input

Not used

Not used

Level signal for ON/OFF

ON/OFF input

Not used

Not used

Not used

0.5s or longer

ON

0.5s or longer

OFF

Pulse signal for ON/OFF,

Prohibit/Permit

On input

Off input

Prohibit local remote controller operation input

Permit local remote controller operation input

(A) Level signal cases

1 In the case where the Emergency stop/Normal signal is selected, when the external input signal contact OFF changes to contact ON,

“Normal” changes to “Emergency stop”. When contact ON changes to contact OFF, “Emergency stop” changes to “Normal”.

2 In the case where the ON/OFF signal is selected, when the external input signal contact OFF changes to contact ON, “OFF” changes to

“ON”, and when contact ON changes to contact OFF, “ON” changes to “OFF”.

(B) Pulse signal cases

1 If the “ON” signal is sent while the equipment is on, the equipment remains on. (The same applies to OFF, Prohibit and Permit.)

2 In the case where local remote controller operation is prohibited, the ON/OFF operations by the local remote controller are prohibited.

3 Set the pulse duration (contact ON period) to 0.5sec or longer.

(4) Example of a recommended circuit

(A) Level signal cases (B) Pulse signal cases green

ON/OFF or

Emergency stop green yellow orange red brown

ON

OFF

Prohibit

Permit brown

Remote controller main unit

Maximum

10m

Remote controller main unit

Maximum

10m

1 The no voltage contact point and the extension cable are not supplied with the product.

2 The length of the connection cable extension should not exceed 10m. (Use a cable of 0.3 mm 2 or thicker.)

3 Cut off the cable not being used close the connector and properly insulate the cut off ends with tape or the like.

2.

External signal output function

(1) External output

In the case when one or more air conditioner units are “ON”, and an error is occurring on one or more air conditioner units, a signal indicating that an error is occurring is output.

(2) External output specification

Detail of each terminal CN3

No. 1

No. 2

No. 3

No. 4

Lead wires (4 wires, with black tube)

Yellow

Orange

Red

Brown

1 “On” is output even when there is “Error”.

(3) Example of a recommended circuit

In the case of a relay being operated

ON/OFF

Error/Normal yellow orange red

Diode

(*2)

For relay Z1, Z2 use the specifications given below.

Operation coil

Rated voltage: DC12V, DC24V

Power consumption: 0.9 W or less

(*1) Provide a power supply suitable to the relay used.

(DC 12V or DC24V)

(*2) Always insert diodes at both terminals of the relay coil.

brown

Remote controller main unit Maximum

10m

Power supply (*1)

L1: ON/OFF display lamp

L2: Error display lamp

1 When units are “ON” and an error is occurring, each element is ON.

2 The extension length of the connection cable can be up to 10 m.

3 The relay, lamps, diodes and extension cables are not supplied with the product.

6 8