Laars M4-LHS X-BAC BACnet Interface Module, M4-LHS Control Installation and Operation Manual

Laars M4-LHS X-BAC BACnet Interface Module, M4-LHS Control Installation and Operation Manual
Add to My manuals

Below you will find brief information for BACnet Interface Module M4-LHS X-BAC. This device adds BACnet MS/TP communication capability to the Laars M4-LHS control, providing a connection between the control and a BACnet network. The module features LEDs that indicate communication status and is powered through the control's RJ45 connection.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

BACnet Interface Module M4-LHS X-BAC Installation Manual | Manualzz

Installation and Operation Manual

Adds BACnet MSTP Capability to Laars M4-LHS Controls

Document 4233

X-BAC

BACnet Interface Module

X-BAC

BACnet Interface Module

MSTP

A GND B

1 2 3

PRODUCT

COMM

RS485

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

INPUT RATINGS:

115VAC 60Hz , 30VA MAX

USE COPPER WIRE,

CLASS 1 WIRE ONLY.

PWR

L N

1 2

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required to de-energize the equipment before servicing.

SYS A B C D

3 4 5 6 7 8 9 10 11 12

M4-LHS

HYBRID CONTROL

C

D

A

B

PROGRAM RUN

13 mA

+

14

VLT

+

15 16 mA

+

17

VLT

+

18 19 20 21 22 23 24

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

OUTDOOR

TEMP

T O

SYSTEM

TEMP

T O

PROVE

/DHW

O

SHUTDOWN

/TSTAT

/SETBACK

O

25 26 27 28 29 30 31 32

EXTENSION

MODULE

RS-485

To BACnet

MSTP

RJ45 Communication Cable

WArnIng

This control is strictly an operating control; it should never be used as a primary limit or safety control. All equipment must have its own certified limit and safety controls required by local codes.

The installer must verify proper operation and correct any safety problems prior to the installation of this control.

COnTenT

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Item List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

BACnet MS/TP Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Connecting to Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Connecting to extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

BACnet Startup Menu Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

BACnet Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

BACnet Baud Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

MS/TP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

BACnet ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

LeD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

No LED Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

No Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Wiring to Control and extension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2

X-BAC BACnet Interface Module Installation and Configuration Manual

OvervIeW

The BACnet Interface Module adds BACnet MS/TP communication capability to the M4-LHS control. It does that by connecting to both, the control and the BACnet MS/TP network. All the BACnet settings are configured through the control. The BACnet

Interface Module has LEDs that can help in displaying communication status.

X-BAC

BACnet Interface Module

MSTP

A GND B

1 2 3

PRODUCT

COMM

RS485

Mounting

Tab

RS485 to EMS

Operation

LEDs

RJ45

Communication to Control

RJ11 to Extension

ITeM LIST

• X-BAC BACnet Interface Module,

• RJ45 cables (Ethernet Cable),

InSTALLATIOn

The BACnet Interface Module communicates with the M4-LHS control using the RJ45 cable. Thus, it needs to be installed in close proximity to the control.

• Mount the BACnet Interface Module on a flat surface next to the control.

• The module can be mounted horizontally or vertically.

• Keep the module away from extreme heat, cold, or humidity.

• Screw the module to the flat surface using the two side tabs with holes.

• No need to remove the BACnet Interface Module cover.

X-BAC

BACnet Interface Module

WIrIng

• No power wiring is required for the BACnet Interface Module. It gets its power through the control's

RJ45 connection.

• The module's MS/TP terminals are of the removal type. That facilitates easy wiring. Just unscrew the terminal block side screws to remove the full terminal block.

MSTP

A GND B

1 2 3

PRODUCT

COMM

RS485

BACneT MS/TP WIrIng

• Use 18# AWG Twisted Pair cable. The cable length must not exceed 3500 feet.

• Connect the MS/TP cable coming from the BACnet MS/TP network to the MS/TP terminals on the

BACnet Interface Module. Communication on the BACnet MS/TP network is polarity sensitive.

• The ground terminal (GND) MUST be connected to the BMS Ground.

To BACnet

MSTP

3

X-BAC BACnet Interface Module Installation and Configuration Manual

COnneCTIng TO COnTrOL

• The BACnet Interface Module communicates all of its information to the control using RJ45 cable (the cable is provided with the module).

• Both the BACnet Interface Module and the control have RJ45 sockets.

COnneCTIng TO exTenSIOn

• Unlike the heating control, the extension has a RJ11 Socket. In addition, each extension is packaged with an RJ11 cable to connect

to the control. See "Wiring to Control and Extension" on page 7.

• If an extension is being used, use the RJ11 (RS485) socket on the BACnet module to connect to the extension. See "Item List" on page 3.

4

X-BAC BACnet Interface Module Installation and Configuration Manual

BACneT STArTuP Menu SeTuP

-------- SETTINGS ----

Season Winter

System Target 140 F

<System Settings>

<Maintenance>

<System Startup>

BACK ▲ ▼ SELECT

-- ARE YOU SURE? --

No

Yes

BACK ▲ ▼ SAVE

---- BACNET ID ----

477000

[ ]

BACK ▲ ▼ SAVE

----MS/TP ADDRESS----

1

[ ]

BACK ▲ ▼ SAVE

--- BACNET MODE ---

Disable

Enable

BACK ▲ ▼ SAVE

- BACNET BAUDRATE -

9600

19200

38400

BACK ▲ ▼ SAVE

BACneT MODe

Enable, Disable

Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode

Default: Disable

• This menu option enables or disables the BACnet MSTP capability. When enabled, additional BACnet settings shall be available for further customizing.

BACneT BAuD rATe

9600, 19200, 38400 Default: 19200

Button: MENU/<System Startup>/.... Sensor Fault/BACnet Mode/BACnet Baudrate

• For the control to communicate over a BAcnet MS/TP network, it must use the same Baud rate as the rest of the network. The control offers three Baud Rates.

• If communication was not successful, the baud rate could be the cause. Check with the network administrator for the network baud rate. Then match it on the control.

MS/TP ADDreSS

1 to 127 Default: 64

Button: MENU/<System Startup>/.... /BACnet Mode/BACnet Baudrate/ MSTP Address

• Each device on the MS/TP network must have a unique address.

• This is the MS/TP address on a RS485 network. Its MS/TP range is 1 though 127.

• The MS/TP address must be provided by the Network Administrator.

BACneT ID

1 to 4,000,000

Button: MENU/<System Startup>/.... / MSTP Address / BACnet ID

Default:

• The BACnet ID is a unique 32 bit number that identifies the control within the BACnet network. No two ID shall be the same even if dealing across networks.

• It must be provided by the BACnet Network Administrator.

LeD

Yellow LED Flashes on communication between the BACnet Interface Module and the control.

Green LED

Red LED

Flashes on communication between the BACnet Interface Module and the

BACnet network.

Flashes steadily to indicate the BACnet Interface Module is operational.

--- BACNET MODE ---

Disable

Enable

BACK ▲ ▼ SAVE

- BACNET BAUDRATE -

9600

19200

38400

BACK ▲ ▼ SAVE

----MS/TP ADDRESS----

1

[ ]

BACK ▲ ▼ SAVE

[

---- BACNET ID ----

X-BAC

BACK ▲ ▼ SAVE

BACnet Interface Module

MSTP

A GND B

1 2 3

PRODUCT

COMM

RS485

5

X-BAC BACnet Interface Module Installation and Configuration Manual

TrOuBLeSHOOTIng nO LeD LIgHTS

• The RJ45 connection to the control powers the BACnet Interface Module. If all LEDs are off, then check the cable connecting the module to the control. The cable consist of 8 wires. Check each of the color-coded wires continuity in the cable using a continuity meter.

nO COMMunICATIOn

• Check the Yellow and Green LEDs. If the Yellow LED is continuously On or Off, then check the cable connecting the module to the control.

• If the Green LED is continuously On or Off, then check the cable connecting the module to the BACnet network.

• Make sure that the control's Baud Rate and the BACnet Network's are the same. See "BACnet Baud Rate" on page 5.

SPeCIfICATIOn

Control Communication . . . . . . . . . . . . . . . . . . . . . . . . . . RJ45 to control (Cable is provided)

BACnet MS/TP Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-wire

Extension Communication. . . . . . . . . . . RS485 (RJ11) to Extension (Cable packaged with Extension)

LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Red, Yellow, and Green

Dimension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-¾” x 3-⅝” x 1”

Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Pound

6

X-BAC BACnet Interface Module Installation and Configuration Manual

WIrIng TO COnTrOL AnD exTenSIOn

X-BAC

BACnet Interface Module

MSTP

A GND B

1 2 3

PRODUCT

COMM

RS485

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

INPUT RATINGS:

115VAC 60Hz , 30VA MAX

USE COPPER WIRE,

CLASS 1 WIRE ONLY.

PWR

L N

1 2

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

CAUTION: RISK OF ELECTRIC SHOCK to de-energize the equipment before servicing.

SYS A B C D

3 4 5 6 7 8 9 10 11 12

M4-LHS

HYBRID CONTROL

A

B

C

D

PROGRAM

A

CUR / VLT

B

CUR / VLT

RUN

C

CUR / VLT

D

CUR / VLT

13 14 15 16 17 18 19 20 21 22 23 24

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

OUTDOOR

TEMP

T O

SYSTEM

TEMP

T

25 26 27

O

PROVE

/DHW

O

SHUTDOWN

/TSTAT

/SETBACK

O

28 29 30 31 32

EXTENSION

MODULE

RS-485

To BACnet

MSTP

RJ45

Extension

RJ45 Communication Cable

RJ45 RJ11

PWR

L N

1 2

M4Ext

FULL MODULATION SEQUENCING EXTENSION

E

G

I

K

M

O

Comm

F

H

L

N

J P

Power

OUTPUT RATINGS:

120VAC, 6A RESISTIVE

1A PILOT DUTY, 15A TOTAL

FOR ALL CIRCUITS

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

CAUTION: Risk of Electric Shock.

More than one disconnect switch may be required to de-energize the equipment before servicing.

E K F L G M H N I O J P

3 4 5 6 7 8 9 10 11 12 13 14

Ext A Ext B

GND mA VLT

15 16 17 mA VLT

19 20 mA VLT

22 23 mA VLT GND mA VLT

25 26 27 28 29 mA VLT

31 32

RS-485

RJ11

RJ11 Extension Cable

X-BAC BACnet Interface Module Installation and Configuration Manual

7

20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • FAX 603.335.3355

1355 Kuehner Drive, Simi Valley, CA 93063 • 800.900.9267 • FAX 800.559.1583 (Sales, Service)

1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • FAX 905.366.0130

www.laars.com

Litho in U .S .A © Laars Heating Systems 0911 Document 4233

advertisement

Key Features

  • Adds BACnet MSTP capability
  • Connects to control and BACnet network
  • LEDs for communication status
  • Powered through control's RJ45
  • Removable terminal block for easy wiring
  • Supports 18# AWG Twisted Pair cable up to 3500 feet
  • Configuration through the control's menu
  • Supports Baud Rates: 9600, 19200, 38400
  • Unique MS/TP Address and BACnet ID required

Frequently Answers and Questions

How to connect BACnet Interface Module to the control?
Connect the module to the control using the provided RJ45 cable. Plug one end into the RJ45 socket on the module and the other end into the RJ45 socket on the control.
How to connect BACnet Interface Module to the BACnet network?
Connect the BACnet MS/TP cable from the network to the MS/TP terminals on the module. Ensure proper polarity and ground connection.
What are the LEDs on the module for?
Yellow LED indicates communication between the module and the control. Green LED indicates communication between the module and the BACnet network. Red LED indicates the module is operational.
What are the default settings for BACnet mode, baud rate, MS/TP address, and BACnet ID?
The default settings for BACnet Mode are Disabled, Baud Rate is 19200, MS/TP Address is 64, and BACnet ID is provided by the network administrator.

Related manuals