Industrial Inverter Floor Mount 120VDC

Industrial Inverter Floor Mount 120VDC
Industrial Inverter
Floor Mount 120VDC
Series 1000
DC to AC Inverter Features

True On-line Technology for Maximum Power Protection

True “Zero Break” Fully Rated Solid State Static Transfer
Switch Standard

Pure Sine Wave Output

Transistor Power Block Technology

20-Year Design Life

Copper Wound Transformers

Easy Access Front Door

Input to Output Isolation

Battery Noise Less than 32dBrnC

Low Audible Noise

Short Circuit Protection

Heavy Duty Casters

Handles 5:1 Crest Factor Loads

DC Input Circuit Breaker

AC Output Circuit Breaker

Form “C” Alarm Interface Contacts

ANSI 61 Gray Powder Coat Finish

Built to Meet UL1778, NEMA, NEC, ANSI and FCC
Standards
OPTIONS
 Multiple Voltage Outputs Available
 50Hz/60Hz Models
 External Maintenance Bypass Switch
 Direct Inverter (No Static Switch)
 Customizable Designs for Unique Applications
Industrial Inverter
Floor Mount 120VDC
Technical Specifications
Model
3kva
Nominal DC Voltage (V)
Max Current (A)
Protection (Breaker Amps)
3kva / 3kw
8kva
120
DC INPUT
5kva / 5kw
3kva
120
7.5kva / 5kw
7.5kva
120
28
32
46
50
69
80
Noise Feedback
Less than 32dBrnC
Power Rating
3kva
Nominal
Voltage
Frequency
Frequency Stability
Acceptable Bypass
Synchronization
Regulation
Waveform
Crest Factor
Harmonic Distortion
Overload
Protection Circuitry
3kva / 3kw
8kva
50 / 60Hz
Operating Temperature
Ventilation
Heat Dissipation (BTU/Hr)
Humidity
Audible Noise
Operational Altitude
AC OUTPUT
5kva / 5kw
7.5kva / 5kw
3kva
7.5kva
120 VAC Standard,
100/127/200/208/220/230/240
Optional
50 / 60Hz
50 / 60Hz
±0.1% Internal Crystal Controlled
10kva / 10kw
50 / 60Hz
Standard 58.8 Hz to 61.2 Hz
±2% over entire input voltage and load range
Pure Sine Wave
5:1
< 1% with linear load from .8 leading to .8 lagging power factor
125% for 10 min, 150% for 1 min
Circuit Breaker and Fusing
AC BYPASS INPUT
120 VAC Standard, other voltages available as an option
50 / 60Hz (Bypass freq. must match output freq.)
ENVIRONMENT
Voltage (V)
Frequency (Hz)
Model
Height (inches)
Width (inches)
Depth (inches)
Weight (lbs)
10kva / 10kw
120
92
125
32°F to 122°F (0°C to 50°C)
1,535
3kva / 3kw
27
13
31
230
Forced Air (front to back)
3,839
0 – 95% non-condensing
< 50 dB(A) Scale @ 1 meter
5,000 ft. (1,500m)
DIMENSIONS
5kva / 5kw
7.5kva / 5kw
2,559
27
13
31
275
ENCLOSURE
36
16
31
380
Color
Rating
ANSI 61 Gray
NEMA1
Cable Entry
Rear
Note: All data is subject to change without notice.
LTI Power Systems • 10800 Middle Ave., Bldg. B • Elyria, OH 44035
Phone 888 327 5050 • Fax 440 458 8140 • www.ltipowersystems.com
5,118
10kva / 10kw
36
16
31
400