Seaward PrimeTest ERT 1557 earth resistance tester Operating Instructions

Seaward PrimeTest ERT 1557 earth resistance tester Operating Instructions
Add to My manuals

Below you will find brief information for earth resistance tester PrimeTest ERT 1557. The ERT 1557 is a fully featured earth resistance and soil resistivity tester, housed in a rugged PrimeTest series enclosure, and supplied complete with all necessary test leads and test spikes. The instrument will perform tests in accordance with BS7671 and IEC61557. The instrument is capable of 2, 3 and 4 pole resistance measurement and earth resistance using a current clamp.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Earth Resistance Tester PrimeTest ERT 1557 Operating Instructions | Manualzz

ERT1557

Operating Instructions

Bracken Hill, South West Industrial Estate,

Peterlee, Co. Durham. SR8 2SW. England.

Tel: +44 (0)191 586 3511 Fax: +44 (0)191 586 0227 www.seaward.co.uk [email protected] [email protected]

ERT1557

Operating Instructions

© 2007 Seaward Electronic

Figure 1 ERT 1557 Front View

Figure 2 ERT 1557 End View

- 2 -

ERT1557

Operating Instructions

Limited Warranty & Limitation of Liability

SEAWARD Electronic Limited guarantees this product to be free from defects in material and workmanship under normal use and service for a period of 1 year.

The period of warranty will be effective at the day of delivery.

(c) Copyright 2008

All rights reserved. Nothing from this edition may be multiplied, or made public in any form or manner, either electronically, mechanically, by photocopying, recording, or in any manner, without prior written consent from SEAWARD Electronic Limited. This also applies to accompanying drawings and diagrams.

Due to a policy of continuous development SEAWARD

Electronic Limited reserves the right to alter the equipment specification and description outlined in this publication without prior notice and no part of this publication shall be deemed to be part of any contract for the equipment unless specifically referred to as an inclusion within such contract.

- 3 -

ERT1557

Operating Instructions

Disposal of Old Product

This product has been designed and manufactured with high quality materials and components that can be recycled and reused.

When the crossed out wheelie bin symbol is attached to a product it means the product is covered by the

European Directive 2002/96/EC.

Please familiarise yourself with the appropriate local separate collection system for electrical and electronic products.

Please dispose of this product according to local regulations. Do not dispose of this product along with normal waste material. The correct disposal of this product will help prevent potential negative consequences for the environment and human health.

- 4 -

ERT1557

Operating Instructions

Table of Contents

Table of Contents ...................................................5

CERTIFICATE OF CONFORMITY............................6

Introduction............................................................7

1 User Notes ..........................................................8

2 Safety Notes........................................................9

3 Accessories.......................................................10

3.1 Standard Accessories.................................10

3.2 Optional Accessories..................................10

4 Unit Description.................................................11

4.1 Identifying parts of the unit .........................11

4.2 LCD display messages ...............................11

4.3 Keypad operation .......................................12

5 Using the ERT 1557...........................................13

5.1 Power On ...................................................13

5.2 Battery Health Check..................................13

5.3 RA 3 Pole ...................................................13

5.4 R

A

Using current clamp...............................14

5.5 RA 4 Pole ...................................................15

6 Memory Functions .............................................16

6.1 Memory locations .......................................16

6.2 Storing results ............................................16

6.3 Recalling Results ........................................17

6.4 Erasing individual results ............................18

6.5 Clearing all the memory ..............................18

7 Download Function ............................................20

7.1 COM Port Identification ..............................20

7.2 Hyper Terminal Setup Procedure................21

7.3 Download Data...........................................22

7.4 View Download Data ..................................23

8 Electrical Specifications .....................................25

8.1 Earth Resistance Two/Three Pole Method ..25

8.2 Earth Resistance Current Clamp Method....25

8.3 Specific Earth Resistance ...........................26

9 Environmental Conditions ..................................27

10 Maintenance....................................................28

10.1 Securing the ERT 1557 .............................28

10.2 Cleaning ...................................................28

10.3 Battery Replacement ................................29

10.4 Service and Calibration.............................29

10.5 Spare Parts...............................................30

- 5 -

ERT1557

Operating Instructions

CERTIFICATE OF CONFORMITY

As the manufacturer of the apparatus listed, Seaward declare under our sole responsibility that the product:

ERT 1557

To which this declaration relates are in conformity with the relevant clauses of the following standard:

BS EN 61010-1:2001

Safety requirements for electrical equipment for measurement, control, and laboratory use – Part 1:

General requirements.

BS EN 61557-1, -5 :1997

Electrical safety in low voltage distribution systems up to 1000V a.c. and 1500V d.c. – Equipment for testing, measuring and monitoring of protective measures

BS EN 61326:1998

Electrical equipment for measurement, control and laboratory user-EMC Requirements

Performance: The instrument operates within specification when used under the conditions in the above standards EMC and Safety Standards.

The product identified above conforms to the requirements of Council Directive 89/336/EEC and

73/23 EEC.

Seaward Electronic Ltd is registered under BS EN

ISO9001:2000 Certificate No: Q05356.

- 6 -

ERT1557

Operating Instructions

Introduction

The ERT 1557 is a fully featured earth resistance and soil resistivity tester, housed in a rugged PrimeTest series enclosure, and supplied complete with all necessary test leads and test spikes. The instrument will perform tests in accordance with BS7671 and

IEC61557.

The instrument is capable of 2, 3 and 4 pole resistance measurement and earth resistance using a current clamp. Up to 500 measurements can be stored in memory, indexed via a simple reference numbering system. Results can be downloaded to PC.

- 7 -

ERT1557

Operating Instructions

1 User Notes

This instrument and its operating instructions are intended for use by adequately trained personnel.

The following symbols are used in these operating instructions and on the ERT 1557.

Warning of electrical danger!

Indicates instructions must be followed to avoid danger to persons.

Important, follow the documentation! This symbol indicates that the operating instructions must be adhered to in order to avoid danger.

- 8 -

ERT1557

Operating Instructions

2 Safety Notes

This ERT 1557 is fully compliant with the requirements of:

BS EN 61010-1: 2001.

BS EN 61557 part 1 and 5.

In order to ensure safe operation of this instrument, all notes and warnings in these instructions must be observed at all times.

The ERT 1557 has been designed to make measurements in a dry environment.

The ERT 1557 may be used to test circuits with a maximum overvoltage Category II, 300V

AC/DC with reference to earth.

The ERT 1557 and all associated cables and leads must be checked for signs of damage before equipment is operated.

Where safe operation of the ERT 1557 is no longer possible it should be immediately shut down and secured to prevent accidental operation.

It must be assumed that safe operation is no longer possible:

- if the instrument or leads show visible signs of damage or

- the instrument does not function or

- after long periods of storage under adverse environmental conditions.

If the ERT 1557 is used in a manner not specified by this document then the protection provided by the equipment may be impaired.

- 9 -

ERT1557

Operating Instructions

3 Accessories

3.1 Standard Accessories

The ERT 1557 is supplied with the following items:

1 off ERT 1557 unit

1 off 5 m black test lead

1 off 20 m red test lead

1 off 5 m green test lead

1 off 20 m blue test lead

1 off USB to MiniDIN Lead Assembly

1 off Operating Instruction Manual

4 off test spikes

3.2 Optional Accessories

Current Clamp Seaward Part No 278A923

Seaward Part No 270A951 Carry case

Do not open unit no serviceable parts

- 10 -

ERT1557

Operating Instructions

4 Unit Description

The ERT 1557 is a hand held, earth resistance tester.

Tests are selected using the rotary switch.

4.1 Identifying parts of the unit

The numbering below refers to fig. 1 and fig. 2.

1. LCD Display

2. Function keys F1, F2, F3 and F4

3. TEST key

4. Rotary Switch

5. Test lead inputs Es, E, S and H

6. Current clamp input

7. Current clamp input

8. Data port

4.2 LCD display messages

Display Meaning

>50k

W

>2k

W

Result is above the measuring range for 2 and 3 point earth resistance

Result is above the measuring range for current clamp earth resistance

>1999k Wm Result is above the measuring range for earth resistivity

More than 20Veff noise present. The

ERT 1557 is unable to make a measurement.

RP

RC

No

001

0.0.1

Alternate

E-ES/ES-S

Stor

RCL

Prt

The resistance between the Potential test spike and earth is too high.

The resistance between the Current test spike and earth is too high.

Request cannot be executed e.g. result cannot be stored in a particular memory location or particular result cannot be recalled.

Memory location identifier

Measurement location identifier

The ES and E connections are reversed. Correct the problem to proceed

Storing result

Recalling result

Downloading data mode

- 11 -

ERT1557

Operating Instructions

Clr Deleting a result from memory

4.3 Keypad operation

F1

Key Function

Increase numerical value

F4 + F1 Recall data from memory

F2

F4 + F2 Save result to memory

F3

Decrease numerical value

Select distance between test spikes.

F4 + F3 Clear memory

TEST Start measurement

- 12 -

ERT1557

Operating Instructions

5 Using the ERT 1557

5.1 Power On

To turn the ERT 1557 on simply rotate the rotary switch to the required test type.

5.2 Battery Health Check

The ERT 1557 will automatically perform battery health checks prior to a test performing.

Note: When the battery symbol is flashing all tests will be inhibited and the batteries should be replaced as described in section 8.4.

Do not connect any voltage or power source to the current clamp inputs. Damage to the ERT

1557 will occur.

5.3 RA 3 Pole

Always ensure that the circuit under test is

<30Vrms.

5.3.1 Rotate the rotary switch until the R

A

3pole test is selected.

ERT 1557

E ES S H

Earth

Electrode

Potential

Electrode

Current

Electrode

Figure 3

- 13 -

ERT1557

Operating Instructions

5.3.2 Connect the Es and E test leads to the test point.

5.3.3 Connect the H and S test leads to the 2 test spikes as shown in figure 3.

5.3.4 Press and release the TEST key. The measured resistance will appear on the LCD after a few seconds. To save the result, refer to section 6.2.

5.4 R

A

Using current clamp

Always ensure that the circuit under test is

<30Vrms.

5.4.1 Rotate the rotary switch until the R

A test is selected.

5.4.2 Connect the Es and E test leads to the test point.

5.4.3 Connect the H and S test leads to the 2 test spikes as shown in figure 4.

ERT 1557

End Panel

Clamp input

E

Top panel

ES S H

R

E1

R

E2

R

E3

R

En

Figure 4

Potential

Electrode

Current

Electrode

- 14 -

ERT1557

Operating Instructions

5.4.4 Press and release the TEST key. The measured resistance will appear on the LCD after a few seconds. To save the result, refer to section 6.2.

5.5 RA 4 Pole

5.5.1 Rotate the rotary switch until the R

A selected.

4pole test is

5.5.2 Connect the Es, E, H and S test leads to the test spikes.

5.5.3 Insert the test spikes into the ground in the order

E, Es, S and H. Ensure the spikes are equispaced.

5.5.4 Input the appropriate distance between the test spikes into the ERT1557 by pressing the F3

(Distance) function key. Press F1 (

D) or F2 (Ñ) function keys to either increment or decrement the distance, in metres.

5.5.5 To perform the soil resistivity test press and release the TEST function key.

5.5.6 The measured soil resistivity will appear on the

LCD after a few seconds. To save the result, refer to section 6.2

ERT 1557

E ES S H

Figure 5

- 15 -

Potential

Electrode

Current

Electrode

ERT1557

Operating Instructions

6 Memory

Functions

6.1 Memory locations

All memory locations are allocated a unique index number that is comprised of an identification code, object identification number and measuring place.

Function code numbers are:-

1 = R

A

2 = R

A

Soil Resistivity test 3 = R

A

Two-point & Three-point test

Clamp System Earth Resistance test

Object identification numbers can be selected between 001 and 999.

Measuring place can be selected between

0.0.1 and

9.9.9.

6.2 Storing results

6.2.1. Begin test measurement, the value of the measured resistance is displayed on LCD.

6.2.2. To store the result displayed on the LCD press the F4 (shift) + F2 (save) function keys to enter the storage mode. As an indication the small object identification number is displayed on the

LCD.

6.2.3. Press F1 (

D) or F2 (Ñ) function keys to select the desired object identification number.

6.2.4. Press F4 (Shift) + F2 (

Ñ) function keys once again to select the measuring place number.

6.2.5. Press F1 (

D) or F2 (Ñ) function keys to select the desired measuring place.

- 16 -

ERT1557

Operating Instructions

Each test resistance result can only be stored once at any selected object identification number or measuring place. If an attempt is made to store a result in a location already utilised the LCD displays no.

6.2.6. Press F4 (Shift) + F2 (

Ñ) function keys once again to save the test result under both the selected object identification number and measuring place. The LCD displays

Stor on the viewing screen before storing the resistance value.

6.3 Recalling Results

6.3.1. To Recall a stored result press F4 (Shift) + F1

(Recall) function keys to enter recall mode. As an indication the small object identification number and RCL are displayed in the bottom right hand corner of the LCD.

6.3.2. Press F1 (

D) or F2 (Ñ) function keys to select the desired object identification number.

6.3.3. Press (F4) Shift + F1 (Recall) function keys once again to select the measuring place field.

6.3.4. Press F4 (Shift) + F2 (

Ñ) function keys once again to select the measuring place number.

6.3.5. Press (F4) Shift + F1 (Recall) function keys once again to recall the result at the selected memory location and identified by both the selected object code and measuring place number.

6.3.6. The LCD display firstly indicates the function test code for one second,

followed by the optional distance measurement (a requirement of the R

A

Clamp test) followed by the stored earth resistance value.

- 17 -

ERT1557

Operating Instructions

6.3.7. If there are no stored results in the selected memory location then a message no is displayed on the LCD.

6.3.8. Repeat step 6.3.1 to recall results from other memory locations.

6.4 Erasing individual results

6.4.1. Press F4 (Shift) + F1 (Recall) function keys to enter recall mode. As an indication the small object identification number and

RCL are displayed in the bottom right hand corner of the

LCD.

6.4.2. Press F1 (

D) or F2 (Ñ) function keys to select the desired object identification number.

6.4.3. Press (F4) Shift + F1 (Recall) function keys once again to select the measuring place field.

6.4.4. Press F4 (Shift) + F2 (

Ñ) function keys once again to select the measuring place number.

6.4.5. Press F4 (Shift) +F3 (Distance) function keys to clear the displayed earth resistance. The LCD display will indicate Clr.

6.4.6. When an attempt is made to clear a memory location where no result is stored then the message

no is displayed on the LCD.

6.5 Clearing all the memory

6.5.1. Select the rotary switch to Data Clear position.

6.5.2. Press F4 (Shift) +F3 (Distance) function keys to clear all memory locations. As an indication message

Clr starts blinking on the LCD display.

6.5.3. Press F4 (Shift) +F3 (Distance) function keys once again to erase the whole memory. The LCD

- 18 -

ERT1557

Operating Instructions display goes blank indicating that erasing of memory is in progress. Once the memory is erased a message Clr is indicated on the display.

- 19 -

ERT1557

Operating Instructions

7 Download Function

To download data the operator must connect the

ERT1557 to a computer using the supplied USB to miniDin connector and the hyper terminal communications program supplied with the computer.

Always ensure that the USB cable assembly is not connected to a computer before performing any of the test functions available with an ERT

1557.

7.1 COM Port Identification

7.1.1 Identification of the COM port, utilised by the

ERT1557, is dependent on the operating system used by that computer.

7.1.2 The following is a guide for a computer with an

XP operating system and should be viewed for reference only where computers with alternative operating systems are employed.

7.1.3 Right click on the My Computer icon from the computer desktop menu. Select the Manage function from the displayed list.

7.1.4 Select Device Manager from the Computer

Management pop up box. From the list of devices select Ports (COM & LPT).

- 20 -

ERT1557

Operating Instructions

7.1.5 Identify the COM port associated with CP210x

USB to UART Bridge Controller. This is COM4, in the example shown.

7.2 Hyper Terminal Setup Procedure

7.2.1. Install the USB driver provided as part of the supplied accessories on a PC (Depending on the computer operating system).

7.2.2 Some computer operating systems are not supplied with the hyper terminal program. In this case the program can be downloaded free from the internet.

7.2.2 Open the hyper terminal communications program on the PC (Path:-start / All Programs /

Accessories / Communications / HyperTerminal).

7.2.3 Enter the name of the hyper terminal connection e.g. ERT Download. Click on the OK prompt softkey and select the appropriate COM port to which the USB is connected. Click on the

OK prompt softkey.

7.2.4 Hyper Terminal configuration port settings are:-

Baud Rate

No of Data bits

Parity

Stop bit

Flow Control

4800 Bps

8

None

1

None

Click on the OK Prompt softkey.

7.2.5 The following screen is displayed on the PC monitor.

- 21 -

ERT1557

Operating Instructions

7.3 Download Data

7.3.1 Select the Data Send function on the rotary switch. As an indication

Prt is displayed on the

LCD display.

7.3.2 Select

Transfer pull-down menu in the hyper terminal window. Select the

Receive File option.

7.3.3 Using the Browse softkey select the destination folder where the data file in the ERT1557 can be stored. Use the receiving protocol drop-down box to select the Xmodem protocol from the available list.

7.3.4 Click on the

Receive prompt softkey and enter a filename that the ERT1557 data will be stored within.

- 22 -

ERT1557

Operating Instructions

7.3.5 Press the TEST button on the ERT1557 then click on the OK prompt softkey. The data file from the ERT1557 is now downloaded to the previously specified file Example Download.txt.

7.3.6 The Xmodem window is displayed during downloading of data and closed on successful completion of the download function.

7.4 View Download Data

7.4.1 The operator can now access the data download file specified in 7.2.4.

7.4.2 The data is displayed in the format indicated below

7.4.3 Where OBJ and PLACE represent the object identification number and measuring place respectively. These identify the memory location where the result has been stored.

- 23 -

ERT1557

Operating Instructions

7.4.4 Earth Resis identifies the 2 and 3 point earth resistance test method.

7.4.5 Clamp Resis identifies the earth resistance clamp test method.

7.4.6. SRT Resis identifies the soil Resistivity test method.

7.4.7 Where D is the repeatable distance between all earth spikes in metres. E.g. D = 01 specifies a distance of 1 metre.

- 24 -

ERT1557

Operating Instructions

8 Electrical Specifications

8.1 Earth Resistance Two/Three Pole Method

Display Range 0.00W to 50.0kW

Measurement

Ranges

Accuracy

0Ω - 19.99Ω Resolution 0.01Ω

20Ω - 199.9Ω Resolution 0.1Ω

200Ω - 199.9Ω Resolution 1Ω

1.00KΩ - 9.99KΩ Resolution 10Ω

10.0KΩ - 50.0KΩ Resolution 100Ω

2% ± 2 counts from 0Ω - 999Ω

5% ± 2 counts from 1.00kΩ - 50.0kΩ

125 Hz ± 1HZ Measuring frequency

Measuring current

Measuring voltage

Distortion

<20mA effective

<30V effective sine wave

Max 5V p-p / 50Hz

8.2 Earth Resistance Current Clamp Method

Display Range 0.00W to 2.0kW

Measurement

Ranges

Accuracy

Measuring frequency

Measuring current

Measuring voltage

0.5Ω - 19.9Ω Resolution 0.1Ω

20Ω – 999Ω Resolution 1Ω

1.00Ω - 2.00kΩ Resolution 10Ω

5% + 2 counts

125 Hz ± 1Hz

<20mA effective

<30V effective sine wave

Distortion Max 5V p-p / 50Hz

Note: the stated accuracy of the earth resistance current clamp method does not include errors introduced by the current clamp

- 25 -

ERT1557

Operating Instructions

8.3 Specific Earth Resistance

Display

Range

Measurement

Ranges

0.00

Wm to 320kWm

Accuracy

0

Wm –19.99Wm

Resolution 0.01

Wm

20

Wm – 199.9Wm

Resolution 0.1

Wm

200

Wm - 999Wm

Resolution 1

Wm

1.00k

Wm – 9.99kWm Resolution 10Wm

10.00k

Wm –99.9kWm Resolution 100Wm

100k

Wm – 320kWm Resolution 1kWm

2% ± 2 counts 0

Wm – 6.3kWm

5% 6.3k

Wm – 320kWm

125 Hz ± 1Hz Measuring frequency

Measuring current

Measuring voltage

Distortion

<20mA effective

<30V effective sine wave

Max 5V p-p / 50Hz

- 26 -

ERT1557

Operating Instructions

9 Environmental Conditions

9.1 The ERT 1557 has been designed to perform tests and measurements in a dry environment.

9.2 Maximum barometric elevation for making measurements is 2000M.

9.3 Overvoltage category IEC 60664/IEC 61010, 300V

Category II.

9.4 Pollution degree 2 according to IEC 61010-1.

9.5 Protective system IP40 according to IEC 60529.

9.6 Electromagnetic compatibility (EMC). Interference immunity and emitted interference conforming to

IEC 61326-1.

9.7 Operating temperature range of 0°C to 40°C, without moisture condensation.

9.8 The ERT 1557 can be stored at any temperature in the range -25°C to +65°C (relative humidity up to

90%). The batteries should be taken out of the instrument for storage.

9.9 Operating Altitude 0 to 2000 metres

- 27 -

ERT1557

Operating Instructions

10 Maintenance

10.1 Securing the ERT 1557

Under certain conditions safe operation of the ERT

1557 can no longer be assumed:

10.1.1 Visible damage of the instrument case.

10.1.2 Incorrect measurement results.

10.1.3 Recognisable abuse to the instrument due to prolonged storage under improper conditions.

10.1.4 Recognisable abuse to the instrument due to extraordinary transportation stress.

10.1.5 Check the battery compartment for signs of battery electrolyte leakage.

10.1.6 In these cases, the ERT 1557 should be immediately switched off, disconnected from any test or measurement function and secured to prevent any further use.

10.2 Cleaning

10.2.1 Clean the external case of the ERT 1557 with a clean dry cloth.

10.2.1 Avoid using solvents and abrasive scouring agents to clean the external case of the ERT

1557.

10.2.3 Check the battery contacts and compartment are free of electrolytic contamination.

10.2.4 Any contamination of the battery contacts or compartment should be cleaned with a dry cloth.

- 28 -

ERT1557

Operating Instructions

10.3 Battery Replacement

Before opening the ERT1557 ensure that it is disconnected from all voltages! Electric shock danger!

10.3.1 Power the unit off by selecting the Off position on the rotary switch.

10.3.2 Disconnect all the test leads from the unit

10.3.3 Position the ERT 1557 face down and release the captive screw in the battery compartment cover.

10.3.4 Remove the battery compartment cover.

10.3.5 Remove the discharged batteries from the compartment.

10.3.6 Fit a new set of alkaline batteries.

10.3.7 Relocate the battery cover over the battery compartment and fasten in position with the battery cover captive screw.

10.4 Service and Calibration.

To maintain the specified accuracy of the measurement results, the instrument must be recalibrated at regular intervals by either the manufacturer or an authorised Seaward Service Agent.

We recommend a recalibration period of one year.

- 29 -

ERT1557

Operating Instructions

10.5 Spare Parts.

Test Cable Kit

USB to MiniDIN Lead

Assembly

Seaward Part No.

44B167

362W505

Carrying Case 270A951

For Service and Calibration contact:

Service Department

Seaward Electronic

Bracken Hill

South West Industrial Estate

Peterlee

Co Durham SR8 2SW

England

Tel: 0191 5878739 / 0191 5878737

Email: [email protected]

- 30 -

ERT1557

Operating Instructions

362A550 Rev 1

- 31 -

advertisement

Key Features

  • 2, 3 & 4 pole resistance measurement
  • Earth resistance using current clamp
  • Data storage
  • Data download
  • Rugged enclosure

Frequently Answers and Questions

What is the purpose of the ERT 1557?
The ERT 1557 is a fully featured earth resistance and soil resistivity tester used for testing in accordance with BS7671 and IEC61557.
What types of tests can the ERT 1557 perform?
The ERT 1557 can perform 2, 3 and 4 pole resistance measurement and earth resistance using a current clamp.
What is the display range of the ERT 1557?
The display range for earth resistance is 0.00W to 50.0kW, for earth resistance using a current clamp is 0.00W to 2.0kW and for soil resistivity is 0.00Wm to 320kWm.
How many measurements can be stored in the memory of the ERT 1557?
Up to 500 measurements can be stored in the memory.
How can I download data from the ERT 1557 to my PC?
You can download data to your PC using the USB to miniDIN connector and the hyper terminal communications program.