JTL Systems LAPI Refrigeration Controller User guide
The JTL Systems LAPI Refrigeration Controller is a versatile device designed for controlling and monitoring refrigeration systems. It features a comprehensive set of adjustable parameters and control strategies, making it suitable for a wide range of applications. You can use it to control cabinet temperature, air off temperature, and superheat, adjust defrost cycles, and manage fan operation with various strategies. It also supports network communication for remote monitoring and control.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
JTL USER GUIDE CONTROLLER TYPE:
LAPI
Electrical Installation Requirements
Care should be taken to separate the power and signal cables to prevent electrical interference and possible damage due to inadvertent connection.
The power outputs are fitted with suppressors to protect against electrical interference when switching off solenoid valves or contactors. It is therefore essential to observe the output polarity. The line voltage should be connected to the terminals marked LN and the switched loads to NO or NC.
The plant inputs are electrically isolated. A line voltage should be connected for the logical conditions lighting override and shutdown. The terminals marked C should be connected to the supply voltage neutral.
CE Conformance
This unit conforms with the relevant EU standards when installed according to the JTL Installation Requirements for this product
Refrigerant Type
This controller will operate for Carbon Dioxide (R744) and various HFC refrigerants as well as HCFC type R408A. The refrigerant choice is made on item 157. CO
2
(R744) operation is only allowed for frozen food applications and requires the pressure transducer to be selected as -1 to 34 bar (item 175 set to 3). Other refrigerants require the transducer to be -1 to 7 bar (item 175 set to 4).
Control Strategy
The controller can control to the cabinet temperature or the air off temperature selected using item 275.
The control strategy for HGD/well operation is that the temperature is controlled to the worst case of the 2 sections. Each case section has its own temperature factor to enable the case temperature to be calculated from the air on and air off temperatures.
The air off temperature is controlled to a computed setpoint shown on item 28, by controlling pulsed expansion valve.
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
OUTPUT 5
1
NO
LN
NO
4 LN
NC
5
NO
NC
2
NO
LN
3
NO
LN
CON3
RL1
RL2
RL3
RL5
RL4
CON4
CON66
CON8
TEMPERATURE
SENSORS
AIR ON
AIR OFF
EVAPORATOR
SUCTION
TERMINATION
-
+
AIR ON 2
SUCTION PRESSURE
BL
RD
JTL NETWORK
WIRING
TO JTL DISPLAY
Inputs
Input (CON 2)
INPUT 1
INPUT 2
N1
C
N2
C
CON2
CON55
CON7
BL
RD
JTL NETWORK
WIRING
TO JTL DISPLAY
I1
C
I2
C
(LINE)
(NEUTRAL)
(LINE)
(NEUTRAL)
SHUTDOWN
LIGHTING
OVERRIDE
Where the second case option is selected, 2 displays can be driven. This is selected using item 502. If this option is selected a JTL display splitter is required. Either of the displays support the keyswitch function but it is not recommended that both displays be keyswitch type.
The LCD9 display incorporates a keyswitch. This switch can be used to select various functions as described below. A maximum of 2 additional functions can be selected. On LCD9 if only one additional function is selected, then it is available in either of the extra 2 positions.
The CAB55 cable is available in various lengths.
The computed air off temperature setpoint is calculated by comparing the displayed temperature with the cabinet temperature setpoint. The computed setpoint is raised or lowered depending on whether the cabinet temperature is below or above the cabinet temperature setpoint. The computed air off setpoint cannot go below the value set on item 31.
Backup Defrost Initiation Strategies
For network initiated defrost, 2 defrost backup strategies are included. The strategy choice is made on item 107.
For learned backup the last 24 hours defrost operation is continuously monitored and the defrost schedule is learned. For real time backup the defrost schedule as set up for real time defrost on items 51-56 is used.
If network communication fails, the selected backup strategy is automatically used. The unit reverts to network control whenever the network communications is operational.
230V 1ph
50Hz 1A
N
L
E
CON1
Temperatures and Pressure (CON 4)
1, 2
3, 4
5, 6
7, 8
9, 10
11, 12
13, 14
AIR ON TEMP
AIR OFF TEMP
SUCTION LINE
EVAPORATOR
ENERGY SAVING OR TERMINATION
AIR ON 2 TEMP
SUCTION PRESSURE - +
The LAPI controller can be set to operate from 2 cabinet temperature setpoints by setting item 123. The setpoint to be used is then selected using the display keyswitch. The setpoints are set on items 124 and
125 and the current setpoint is displayed on item 30.
Supeheat Control
The superheat control can be set to operate in 3 ways using item 188.
a) SUCCEEDS. In SUCCEEDS strategy the air temperature is controlled and the superheat allowed to float.
Outputs
Outputs (CON 3)
1 NO
1 LN
OUTPUT 1 (N/O LOAD)
(LINE)
LIGHTING & BLINDS
CONTACTOR
The pulsed expansion valve opening is controlled primarily using a PI strategy on the control temperature. The valve is opened and shut over a fixed period of time (6.25 s) to meter the appropriate amount of refrigeration. The proportional gain and the integral time constant for the PI control are adjustable.
2 NO
2 LN
OUTPUT 2 (N/O LOAD)
(LINE)
FANS / HEATERS b) SUCCEEDS with limit. The superheat is allowed to float to the maximum set on item 189. If the case control temperature error is negative and the superheat is greater that the maximum set on item 189 the expansion valve is closed. It is reopened again with a deadband adjustment on item 140.
3 NO
3 LN
OUTPUT 3 (N/O LOAD)
(LINE)
TRIM HEATER
4 NO
4 LN
4 NC
OUTPUT 4 (N/O LOAD)
(LINE)
(N/C LOAD)
DEFROST c) Fixed. The superheat is controlled using PI control on the superheat temperature. When the case temperature is achieved the PEV is shut. It is reopened again with a deadband adjustment on item 140.
5 NO
5 LN
OUTPUT 5 (N/O LOAD)
(LINE)
PULSED EXPANSION
VALVE
In all cases if the superheat falls below the minimum level set on item 162 or
186, the PEV is progressively shut to effect recovery from excess liquid supply.
This is called override.
Use of Maintenance Unit
The controller can be checked and the operation adjusted using a JTL portable maintenance unit which plugs into the controller. Each item of information has an item number. The more important items are listed in the tables overleaf.
After override is complete, ie. superheat recovers, PI control will be resumed but with a modified (reduced) value. The modifier is shown on item 190 and the output to the PEV valve is shown on item 168.
The superheat is calculated using the suction pressure and temperature. A backup strategy uses the evaporator and suction line temperatures to calculate the superheat.
Examples:
To read item 21 press:
To set item 31 to -20.0
To correct errors press: press:
Pressure Transducer Failure Strategies
There are 3 strategies (set on item 177):
1. Open circuit. Automatic switch to 2 temperature control and raise transducer fault alarm.
2. Auto zero adjust.
3. Network zero range check against average plant pressure, high pressure gives automatic switch to 2 temperature control. Outside range raise transducer fault alarm.
To select next or previous
Initial Commissioning and Bitswitch Settings
The controller has 4 sets of data built in to its program for use during commissioning. These can be accessed by setting the bitswitches as shown in the table overleaf and then setting item 9 to 1234. From v0.01.3 this controller has virtual bitswitches which replace the physical bitswitches. The virtual bitswitches are set using item 966. This loads into the controller a suitable set of data for the selected type of case. Adjustments should then be made as necessary. The range over which the settings can be adjusted is also defined by the bitswitch setting.
If a JTL communications network is connected to the controller then the unit number should be set on item 1.
All 3 strategies are subject to a 5 minute delay timer. The delay is symmetrical i.e. the condition must be present/clear for 5 minutes to set/clear alarm.
7 bar transducers are alarmed at +/- 5 psi and auto zero range limited to +/- 7.5
psi. 34 bar transducers are alarmed at +/- 15 psi and auto zero range limited to
+/- 22.5 psi. Auto switch to 2 temperature control is on upper limit of range i.e.
+75 and +22.5 psi.
External Shutdown Facilities
If item 273 is set on then when input 1 is energized the expansion valve is closed. This override input is to prevent “flooding back” in the event of plant failure.
Second Case Option items press: and
From v0.01.1 firmware the controller can control and monitor a single evaporator half glass door (HGD) and well case. This option is selected on item
500.
There is also a shutdown feature which can be enabled using item 174. High suction pressure on the transducer input can also shut the pulsed expansion valve.
Where the second case option is selected the second case unit number should be set on item 501.
Defrost Initiation Strategies
The defrost strategy can be initiated in 2 fundamental ways using item 107.
Defrost initiation can be by real time clock, or by command on the JTL communications network.
Temperature Display
The temperature displayed is computed from the air on and air off temperatures. A factor is used to proportion the air off and air on temperatures. The temperature can be displayed in Celsius or Fahrenheit as selected by item 122.
The LAPI controller will drive the following JTL displays when used with the
CAB55 extension cable.
Display
LCD8
LCD9
INPUT 1
INPUT 2
Cable
CAB55
CAB55
Switch
None
3 position
Network initiated defrost can be divided into 3 groups; PREDICT, coordinated and scheduled.
This controller uses the PREDICT 1 method which monitors the PEV override operation.
PREDICT defrost requires that a JTL PREDICT defrost coordinator unit is available on the network. This unit receives requests from the PREDICT controllers and coordinates these requests so that the defrosts are organised ensuring the electrical and refrigeration requirements are met. When the controller requests a defrost the PREDICT coordinator will send out a defrost command at a suitable time. If the backup strategy is invoked the controller reverts to real time schedule.
Coordinated timed defrost requires a defrost coordinator to be present in the network. When coordinated timed request is selected then the controller requests a defrost as defined by the number of defrosts a day as set on item 69.
The defrost coordinator coordinates the defrost as required. The backup strategy can be chosen to fall to learned defrost schedule or real time backup.
DOC 03071 ISS 2 heater are energised. During pump down the PEV output is deenergised.
The display shows "dEF "
Defrost Termination selected it is energised.
The display shows "dEF".
Forced Refrigeration and Defrost not act locally.
Fan Control
The fans can be controlled in various ways.
occurred.
to 00:00.
deadband of ±0.5°C
Lighting and Night Blind Control either fans only or shutdown are selected.
High Temperature Alarms recovery.
CON10 CON9
MAINTENANCE
UNIT
The controller stays in defrost at least until the minimum defrost time, on item
145, is exceeded. If the termination temperature is reached before the minimum defrost time then the defrost heater is cycled.
Defrost Recovery
When the termination temperature or time is reached the controller enters defrost recovery. The heater is de-energised. The termination method can be chosen using item 144.
A time delay can be applied (item 49) after defrost before the PEV is reopened.
A drain down time delay can be applied (item 59) after defrost before the liquid valve is reopened. During drain down if the auxiliary heater output is
The maintenance unit can be used to force controller into a particular mode.
This is done using items 77-79. While the maintenance unit is plugged in the controller will remain in the selected mode permanently. Once the maintenance unit is unplugged the controller will revert to normal control after 30 minutes.
When the network initiated defrost strategy is selected, forced defrost will send a command to the JTL defrost scheduler to initiate a defrost and does
If item 108 is set to “fans off during defrost” then during defrost recovery the fans can be controlled depending on the evaporator temperature or time delay after defrost. If item 109 is set to 00:00 when the evaporator temperature is low enough, the fans start. There is a 5 degree deadband. If item 109 is set to a time then the fans are held off until the time delay has
If item 108 is set to “fan control during defrost”; the fans are turned off during defrost when the evaporating temperature goes above the setting on item
146. After defrost the fans are turned on when the evaporating temperature falls below the setting on item 150 or the time delay on item 109, if it is not set
If energy saving is selected using item 130, then the fans will be cycled during normal refrigeration. When the energy saving temperature, item 131, goes below the energy saving setpoint, item 132, the fans stop. There is a
The cabinet lights and night blinds can be sequenced on and off by command from the JTL network. An override switch input facility is provided which raises the blinds and turns the lights on. The lights can be switched off from the display keyswitch if item 119 is set to 1 (enabled). The lights are switched off if
The cabinet and air off temperatures are monitored continually. The temperatures are averaged over the period set on item 47. If either of the average temperatures exceeds the alarm level then an alarm is given which is shown on the display and available, for remote indication, on the JTL alarm system. High temperature alarms are cancelled during defrost and defrost
The cabinet temperature tolerance is set on item 32 and the air off tolerance on item 34. Setting either of these tolerances to 0.0°C disables the relevant alarm.
Excessive Superheat Alarms
If the measured Superheat exceeds 50°C then a sensor fault is assumed and the maximum opening of the expansion valve is reduced to 33% of the maximum allowed. When the measured Superheat is between 30 and 50°C the fault condition is activated if the suction temperature exceeds the air on temperature.
Network Shutdown and Fans Only Mode
This controller supports the JTL Network shutdown and fans only facilities.
When these facilities are enabled by item 62. If a shutdown or fans only command is received over the JTL Network, the refrigeration is stopped and alarms are disabled. The high temperature alarm sequence is initialised.
Display Controlled Shutdown
The controller can be shutdown for servicing purposes using the display switch. This feature is enabled by item 138.
The backup strategy is also invoked if the network signals that communications has failed to the defrost scheduler or if there is a fault at the defrost scheduler.
Defrost
The defrost output relay is energised during the defrost period.
The liquid solenoid is closed during defrost. The auxiliary output can be selected for fan or heater control. During defrost the fans can be stopped or the auxiliary heater energised.
A pump down delay can be applied (item 61) before the defrost/output and
Display Controlled Fans Only Mode
The controller can be put into fans only mode using the display switch. This feature is enabled by item 136.
Suction Pressure Optimisation
When used in conjunction with JTL pack control and suction optimisers this unit is normally included in the suction pressure optimiser algorithm. It can be explicitly excluded by setting item 200 to 1.
Daylight Saving
When connected to a JTL network this controller can operate by displaying daylight saving time for its time and defrost schedule. Daylight saving operation is selected by setting item 18. The connected network controller then adjusts the times automatically during the daylight saving period.
108
146
109
150
130
132
144
50
145
57
59
49
110
118
119
214
223
225
226
242
69
61
51-56
60
211
210
213
1
501
62
133
134
200
18
122
136
138
502
162
186
163
187
164
170
157
158
161
188
189
171
174
175
177
179
273
275
123
124
125
31
140
106
500
107 item
33
36-39
147
32
34
47
533
532
Function
Cabinet temperature ratio
Sensor selections
Termination sensor selection
Cabinet overtemperature tolerance
Air off over temperature tolerance
Alarm averaging time
Cabinet temperature rate (second case)
Cabinet overtemperature tolerance (second case)
Control temperature
Enable 2nd setpoint
Primary cabinet temperature setpoint
Secondary cabinet temperature setpoint
Air off temperature setpoint
Temperature control deadband
Auxiliary output selection
Enable second case
Refrigerant type
Pressure transducers zero offset
Superheat measurement method
Superheat control strategy
Superheat setpoint
Minimum superheat (pressure)
Minimum superheat (2 temperature)
Maximum valve opening (pressure)
Minimum valve opening (2 temperature)
Minimum valve opening
PEV proportional gain
PEV integral time constant
High suction pressure shutdown
Pressure transducer type
Auto zero pressure enable
Pressure display choice
PEV override input
Defrost strategy
Number of defrosts expected or required
Pump down time
Defrost schedule
Defrost schedule 12/24 hour clock
Evaporator group
Electrical supply distribution panel no
Defrost heater circuit
Defrost method
Defrost requirement priority
PREDICT Minimum time between defrosts
PREDICT Maximum time between defrosts
PREDICT override initiation
Defrost termination method
Defrost termination temp
Minimum defrost time
Defrost termination time
Drain down time
Refrigeration delay after defrost
Fan control
Temperature to turn fans off during defrost
Fan delay after defrost
Temperature to turn fans on after defrost
Fan control sensor selection
Fan control temperature setpoint
Jnet lighting control selection
Lighting contractor selection
Enable lights during shutdown
Unit number
Unit number second case
Jnet network shutdown selection
Enable plant to override temp control
Enable plant to cut off refrigeration
Exclude from suction optimisation
Daylight saving operation
Temperature display choice
Enable fans only mode from display
Enable display controlled shutdown
Enable 2nd display
ADJUSTABLE PARAMETERS
Range
20 to 80
0=off 1=on
0=off 1=on
0 to +20
0 to +30
00:30 to 03:00
20 - 100
0 - 120
1=Air off 2=cabinet temp
0=disabled 1=enabled
-30 to +10
-30 to +10
-39 to +5
0.4 to 3.0
0=off 1=Fan 2=Heater
0=Disabled 1=Enabled
3 - 9 (R type shown on MU display)
-7 to +7
1=2 temperature 2=pressure
0=SUCCEEDS, 1=SUCCEEDS with limit, 2=fixed
6.0 - 12.0
0 - 10
0 - 5
10 - 100
5 - 50
0 -50
1 - 100
1 - 250
0=disabled 1=enabled
3=-1 to 34 bar 4=-1 to 7 bar
0=disabled 1=auto 2=network
1=psi 2=bar 3=kPa
0=disable 1=enable
0=none 2=Network (learned backup)3=Time 5=PREDICT
7=Network (real time backup) 8=Coordinated (learned) 9=Coordinated (real time)
0 to 12
00:00 - 00:10
00:01 - 23:59
0=24hr 1=12hr
0=none 1=Lt 2=Ht 3=Satellite
1 to 15 panel no
1-15=circuit
0=brown phase 1=black phase 2=grey phase 3=3 phase 6=off cycle
1 to 8
2 to 8
6 to 72
0 - 100
1=Evaporator 2= Air off 3=Termination 4=Time only
0 to +20
00:00 - 00:30
00:05 to 00:59
00:00 to 00:10
00:00 to 00:10
1=run always 2=off during defrost 3=fan controlled during defrost
-12 to +20
00:00 - 00:10
-20 to +5
0=disabled 1=enabled
-30 to +8
0=disabled 1=enabled
0=n.o 1=n.c
0=disabled 1=enabled
0.1 - 899.8
0.1 - 899.8
0=disabled 1=enabled
0=off 1=on
0=disabled 1=enabled
0=include 1=exclude
0=standard time 1=daylight saving time
0=Celsius 1=Fahrenheit
0=disabled 1=enabled
O=Off 1=On
0=Disabled 1=Enabled
Bitswitch settings 21, o(CC) Frozen food (CO
2
), 1(CO) Frozen food (HFC), 2(OC) Chillers (HFC), 3(OO) Produce (HFC), where C = closed, O = open, closed = dot visible (0 to 3 is the virtual bitswitch setting on item 966)
Units hr:mn
°C
°C
°C
°C
%
%
%
K
K
K
K
K hr:mn
K psi hr:mn hr:mn hours hours
%
°C hr:mn hr:mn hr:mn hr:mn
°C hr:mn
°C
°C
LAPI
20
21
22
23
24
520
521
131
141
Item Function
30
28
240
241
TEMPERATURES
Cabinet temperature
Air on temperature
Air off temperature
Evaporator temperature
Suction line temperature
Cabinet temperature (second case)
Air on temperature (second case)
Energy saving temperature
Termination sensor temperature
CONTROL
Cabinet temperature setpoint
Effective air off setpoint
Liquid valve open %
Average liquid valve open %
154
155
156
159
166
168
169
181
182
190
Item
OTHER USEFUL ITEMS
Item
PULSED EXPANSION VALVE FUNCTIONS
Force pressure average to current reading
Suction pressure
Superheat
Auto zero offset
Force PEV opening (%)
PEV valve opening (%)
PEV status
Time since last override (hr:mn)
Duration of last override (sec)
Modifier output (%)
70
274
72
74
111
112
113
114
115
Function
MODE INPUTS & OUTPUTS
Operating mode
PEV override input state
Defrost output state
Auxiliary output state
LIGHTING
Communications lighting command
Lighting override input state
Lighting output state
Force lights on
Force lights off
Item
40
41
42
46
77
78
79
261-272
219
221
222
243
63
203
Function
DEFROST
Duration of last defrost
Time since end of last defrost
Duration of this defrost
Communications defrost command
Forced defrost
Inhibit defrost
Forced refrigeration
Learned defrost schedule
Defrost arrangement from network
Forced defrost requirement
Enable forced defrost requirement
PREDICT override average (%)
Jnet NETWORK FUNCTIONS
Network shutdown and fans only command states
Associated plant suction lin
OUTPUT STATE DIAGRAM FOR JTL CONTROLLER
MODE OF OPERATION
RL2
AUXILIARY (N/O) can be set to run always [108]
See Note 2
Heater Fans
OUTPUT & FUNCTION (See note 5)
RL3 RL4
TRIM HEATER (N/O) DEFROST (C/O)
LAPI
RL5
PULSED EXPANSION
VALVE (N/O)
Solid state output
I
G
E
R
R
E
F
R
R
M
A
L
N
O
C
L
C
Y
E
A
TI
O
N
REFRIGERATION
PUMP DOWN Adjustable time [61]
DEFROST Time/temp terminated
[57]/[50]
DRAIN DOWN Adjustable time [59]
LIQUID HOLD OFF
Adjustable time [49]
RECOVERY TIME Time/temp terminated
REFRIGERATION
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
(See note 3)
OFF
OFF
OFF
OFF
TEMPERATURE
OR TIME
CONTROLLED
(See Note 6)
ON
(See note 3)
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
CYCLES
ON TERMINATION
TEMP
OFF
OFF
OFF
OFF
CYCLES
ON AIR OFF TEMPERATURE
OFF
OFF
OFF
OFF
CYCLES
ON TEMPERATURE
CYCLES
ON TEMPERATURE
PLANT FAULT
UNIT SHUTDOWN
FANS ONLY SHUTDOWN
FORCED DEFROST
FORCED REFRIGERATION
INHIBIT DEFROST
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
CYCLES
ON TEMPERATURE
CYCLES
ON TEMPERATURE
NOTE 2: CAN BE SET TO OFF USING ITEM 106
NOTE 5: RL1 IS FOR LIGHTING CONTROL
NOTE 6: FANS OFF UNTIL TIME SET ON ITEM 109 REACHED.
Relay Output Rating
5A resistive.
Note
NOTE 3: CAN CYCLE ON ENERGY SAVING TEMPERATURE (SELECTED
BY ITEM 130)
The information contained in this document applies to the current version of the unit supplied with it. Full operating manuals, item number and software variation information can be obtained from your supplier or JTL Systems.
Supply Requirements
230 V ac 48-62 Hz Supply 6 VA maximum inputs 2 mA maximum
This unit conforms with the relevant EU standards when fitted in accordance with its installation instructions.
Applicable Documentation
Item Numbers
Doc No. 03396
Firmware Variations
Doc No. 03404
Connections Diagram
Doc No. 03408
Evaporator Manual
Doc No. 01923
Installation Requirements Schematic Diagram
Doc No. 03036 Doc No. 03491
SUCCEEDS® is the patented JTL algorithm for control of liquid injection into an evaporator using electronic expansion valves.
PREDICT® is the patented JTL pattern recognition algorithm for providing defrost on demand for the cabinets on a system.
03397-LAPI.wpd Issue 5 Aug 2014 Doc No. 03397 www.jtl.co.uk
JTL Systems Ltd . 41 Kingfisher Court . Hambridge Road . Newbury . Berks . RG14 5SJ Tel: (01635) 263646 Fax: (01635) 263647
JTL Help Desk Tel: 0871 315 7535
advertisement
Key Features
- Cabinet temperature control
- Air off temperature control
- Superheat control
- Defrost cycle management
- Fan control
- Network communication
- Second case option
- Energy saving mode
- Predictive Defrost