advertisement
SERIES
ENG
User Guide
Contents
1.
2.
CHAPTER 1 INSTALLATION ........................................................................................................ 3
1.1
What Instrument Do I Have?...........................................................................................................................3
1.2
3504 and 3508 Ordering Code .........................................................................................................................5
1.3
How to Install the Controller ..........................................................................................................................7
1.4
Electrical Connections................................................................................................................................... 10
1.5
Standard Connections................................................................................................................................... 12
1.6
Plug in I/O Module Connections.................................................................................................................... 17
1.7
Digital Communications Connections ........................................................................................................... 24
CHAPTER 2: OPERATION ..........................................................................................................34
3.
2.1
QuickStart - New Controller (Unconfigured) ................................................................................................ 34
2.2
To Re-enter QuickStart Mode ....................................................................................................................... 43
2.3
Normal Operation......................................................................................................................................... 44
2.4
The Operator Buttons ................................................................................................................................... 46
2.5
To Set The Required Temperature (Setpoint) ............................................................................................... 48
2.6
To Select Manual Operation ......................................................................................................................... 49
2.7
Alarm Indication ........................................................................................................................................... 50
2.8
Message Centre............................................................................................................................................. 52
2.9
Introduction to Configuration using iTools................................................................................................... 61
2.10
Device panel ................................................................................................................................................. 64
2.11
User Pages Editor .......................................................................................................................................... 65
2.12
Recipe Editor in iTools .................................................................................................................................. 67
2.13
Program Editor.............................................................................................................................................. 69
2.14
Graphical Wiring Editor................................................................................................................................. 71
CHAPTER 3 SAFETY AND EMC INFORMATION...........................................................................74
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 1
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 2
4.
3.1
GENERAL......................................................................................................................................................74
3.2
Service and repair........................................................................................................................................75
3.3
Installation Safety Requirements.................................................................................................................76
3.4
Installation Requirements for EMC..............................................................................................................79
CHAPTER 4 TECHNICAL SPECIFICATION ..................................................................................80
4.1
Control Options...........................................................................................................................................80
4.2
Display.........................................................................................................................................................80
4.3
Standard Digital I/O.....................................................................................................................................81
4.4
All Analogue and PV Inputs .........................................................................................................................81
4.5
PV Input.......................................................................................................................................................82
4.6
Analogue Input Module ...............................................................................................................................84
4.7
Digital Input Modules ..................................................................................................................................85
4.8
Digital Output Modules ...............................................................................................................................85
4.9
Analogue Output Modules...........................................................................................................................85
4.10
Transmitter PSU ..........................................................................................................................................85
4.11
Transducer PSU ...........................................................................................................................................86
4.12
Potentiometer Input ....................................................................................................................................86
4.13
Digital communications...............................................................................................................................86
4.14
Master communications ..............................................................................................................................86
4.15
Alarms .........................................................................................................................................................86
4.16
User messages .............................................................................................................................................86
4.17
Control functions ........................................................................................................................................87
4.18
Setpoint programmer ..................................................................................................................................87
4.19
I/O Expander................................................................................................................................................87
4.20
Advanced functions .....................................................................................................................................88
4.21
General specification...................................................................................................................................89
3508 and 3504 Process Controllers
1. Chapter 1 Installation
1.1 What Instrument Do I Have?
Thank you for choosing this Controller.
The 3508 controller is supplied in the standard 1/8 DIN size
(48 x 96mm front panel). The 3504 controller is supplied in the standard ¼ DIN size (96 x 96mm front panel). They are intended for permanent installation, for indoor use only, in an electrical panel which encloses the rear housing, terminals and wiring on the back.
1.1.1 Contents of Package
3508 Controller 3504 Controller
When unpacking your controller please check that the following items have been included.
1.1.1.1 3508 or 3504 Controller Mounted in its Sleeve
The 3504 contains up to six plug-in hardware modules; the 3508 has up to three. Additionally digital communications modules can be fitted in two positions.
The modules provide an interface to a wide range of plant devices and those fitted are identified by an ordering code printed on a label fixed to the side of the instrument. Check this against the description of the code given in section
1.2 to ensure that you have the correct modules for your application. This code also defines the basic functionality of the instrument which may be:-
Label showing:-
Instrument
Order
Code
•
•
•
•
Controller only
Programmer and controller
Control type – Standard PID, valve positioner
Digital communications type
• Options
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 3
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 4
1.1.1.2 Panel Retaining Clips
Two clips are required to secure the instrument sleeve in the panel. These are supplied fitted to the sleeve.
1.1.1.3 Accessories Pack
For each input a 2.49Ohm resistor is supplied for mA measurement. This will need to be fitted across the respective input terminals
1.1.1.4 This User Guide
Issue 2 of this guide applies to instrument software version V1.10 and explains:-
•
How to install the controller
• Physical wiring to the plant devices
•
First switch on - ‘out of the box’.
• Principle of operation using the front panel buttons
•
Introduction to configuration through iTools PC software
Whenever the symbol
☺
appears in this handbook it indicates a helpful hint
1.2 3504 and 3508 Ordering Code
Hardware Coding
Model
Number
Function Supply
Voltage
Number of Loops
Model Number
3504 3504 Standard
3508 3508 Standard
CC
F
Function
Controller only
Profibus controller
Loops
X Single Loop
Supply Voltage
VH 85-254Vac
VL 20-29Vac/dc
Application
XX Standard
ZC Zirconia
VP Dual Valve
Position
Application Programs Recipes Toolkits Colour
1
4
8
Programs
1 1 prog 20 segments
10 10 prog 50 segments
25 25 prog 100 segments
50 50 prog 200 segments
Recipes
1 recipe
4 recipes
8 recipes
Colour
G Eurotherm green
S Silver
XX
60
Toolkit Wires
Std 30 wires
60 wires
120 120 wires
250 250 wires
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 5
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 6
1.2.1 Input and Output Modules
IO Slot 1 IO Slot 2
Config Tools Instrument
Language
IO Slot 3 IO Slot 4
Manual Language
3504 only
IO Slot 5
Extended
Warranty
IO Slot 6 Comms H Comms J
Cal Certificate Custom Label Non-standard
XX
R4
IO Slots 1-3 (3508); 1-6 (3504)
None fitted
Change over relay
R2
RR
T2
2 pin relay
Dual relay
Triac
TK
TP
VU
MS
TT
D4
Dual triac
DC control
AM Analogue input (not slot 2 or
D6
TL
5)
DC retransmission
Triple logic input
Triple contact input
Triple logic output
Potentiometer input
24Vdc transmitter PSU
G3
LO
Transducer PSU 5 or 10Vdc
Isolated single logic output
XX
A2
Y2
F2
AE
YE
FE
ET
PB
DN
H Comms Slot
Not Fitted
232 Modbus
2-wire 485 Modbus
4-wire 485 Modbus
232 EI-Bisynch
2-wire 485 EI-Bisynch
4-wire 485 EI-Bisynch
Ethernet 10base
Profibus
Devicenet
XX
IT
Config Tools
None
Standard iTools
Instrument Language
ENG English
FRA French
GER German
SPA Spanish
Extended Warranty
WL005 Extended 5 year
Cal Certificate
XXXXX None
CAL1 Cert of conformity
CAL2
CAL3
Factory cal cert
Custom Cal Cert
XX
A2
Y2
F2
EX
J Comms Slot
Not Fitted
232 Modbus
2-wire 485 Modbus
4-wire 485 Modbus
IO Expander
Manuals Language
ENG English
FRA French
GER German
SPA Spanish
XXX None
Custom Labels
F1234 Special No
XXXXX None
Non-standard Option
EU1234 Special No
EC1234 Custom curve
EE1234 Custom config
ES1234 Cust software
Example 3504/VH/1/XX/10/4/60/G/TT/XX/XX/XX/XX/XX/Y2/XX/IT/ENG/ENG/WL003
3504 CONTROLLER, 85-264Vac, 10 programs, 4 recipes, 60 wires, dual triac output, 2-wire RS485 comms, iTools, English manual
1.3 How to Install the Controller
This instrument is intended for permanent installation, for indoor use only, and to be enclosed in an electrical panel.
Select a location where minimum vibrations are present and the ambient temperature is within 0 and 50 o
C (32 and
122 o
F).
The instrument can be mounted on a panel up to 15mm thick.
To assure IP65 and NEMA 4 front protection, use a panel with smooth surface texture.
Please read the safety information, at the end of this guide, before proceeding and refer to the EMC Booklet part number HA025464 for further information.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 7
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 8
1.3.1 Dimensions
96mm
(3.78in)
48mm
(1.89in)
Latching ears
96mm
(3.78in)
Panel retaining clips
Panel retaining clips
150mm (5.91in)
1.3.2 To Install the Controller
92 mm - 0.0 + 0.8
3.62 in -0.00, +0.03
45 mm - 0.0 + 0.6
1.77 in -0.00, +0.02
1. Prepare the panel cut-out to the size shown in the diagram
2. Insert the controller through the cutout.
3. Spring the panel retaining clips into place. Secure the controller in position by holding it level and pushing both retaining clips forward.
4. Peel off the protective cover from the display
92 mm -
0.0 + 0.8
3.62 in -
0.00, +0.03
3504
3508
1.3.2.2 Recommended Minimum Spacing
5. The recommended minimum spacing between controllers shown here should not be reduced to allow sufficient natural air flow
1.3.3 Unplugging the Controller
10mm (0.4 in)
38mm
(1.5 in)
(Not to scale)
The controller can be unplugged from its sleeve by easing the latching ears outwards and pulling it forward out of the sleeve. When plugging it back into its sleeve, ensure that the latching ears click back into place to maintain the IP65 sealing.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 9
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 10
3508
Live
Neutral
Ground
Logic I/O A
Logic I/O B
Logic I/O Com
Power
Supply
Digital
Inputs/
Outputs
Fixed Relay
(form C)
T/C RTD mV mA
Polarising Keys* One per module
PV input
3504
Live
Neutral
Ground
Logic I/O A
Logic I/O B
Logic I/O Com
Power
Supply
Digital
Input/Outputs
Fixed Relay
(form C)
PV input
T/C RTD mV mA
Polarising Keys * One per module
* Polarising Keys.
Polarising keys are intended to prevent modules which are not supported in this controller from being fitted into the controller. An example might be an unisolated module (coloured red) from a 2400 controller series. When pointing towards the top, as shown, the key prevents a controller, fitted with an unsupported module, from being plugged into a sleeve which has been previously wired for isolated modules. If an unisolated module is to be fitted, it is the users responsibility to ensure that it is safe to install the controller in the particular application. When this has been verified the polarising key may be adjusted with a screwdriver to point in the down direction.
The screw terminals accept wire sizes from 0.5 to 1.5 mm (16 to 22AWG). Hinged covers prevent hands or metal making accidental contact with live wires. The rear terminal screws should be tightened to 0.4Nm (3.5lb in).
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 11
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 12
VI
V+
V-
These are connections which are common to all instruments in the range.
1.5.1 PV Input (Measuring Input)
Notes:
1. Do not run input wires together with power cables
2. When shielded cable is used, it should be grounded at one point only
3. Any external components (such as zener barriers, etc) connected between sensor and input terminals may cause errors in measurement due to excessive and/or un-balanced line resistance or possible leakage currents
1.5.1.1 Thermocouple or Pyrometer Input
VI
Use the correct type of thermocouple compensating cable, preferably shielded, to extend wiring
V+
V-
T/C
RTD
For 2-wire this is a local link
The resistance of the three wires must be the same
The line resistance may cause errors if it is greater than 22
Ω
Note: the RTD wiring is not the same as 2400 series instruments. It is the same as 26/2700 series
1.5.1.3 Linear Input V, mV and High Impedance V
VI
V+
V-
+80mV
0 – 2V
0 – 10V mV range +40mV
or
+80mV
High level range 0 – 10V
High Impedance mid level range 0 – 2V
A line resistance for voltage inputs may cause measurement errors
1.5.1.4 Linear Input mA
VI
V+
V-
0 – 20mA
4- 20mA
Connect the supplied load resistor equal to 2.49
Ω for mA input
The resistor supplied is 1% accuracy 50ppm
A resistor 0.1% accuracy 15ppm resistor can be supplied as an orderable option
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 13
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 14
These terminals may be configured as logic inputs, contact inputs or logic outputs in any combination
.
It is possible to have one input and one output on either channel.
!
The Digital IO is not isolated from the PV input
LA
LB
Input 1
Input 2
Common
Voltage level logic inputs, 12V, 5-40mA
LC
1.5.2.2 Contact Closure Inputs
Active > 10.8V
Inactive < 7.3V
LA
LB
Input 1
Input 2
Common
Contact open > 1200 Ω
Contact closed < 480 Ω
LC
1.5.3 Digital (Logic) Outputs
LA
LB
LC
Output 1
Output 2
Common
The logic outputs are capable of driving SSR or thyristors up to 9mA, 18V
It is possible to parallel the two outputs to supply 18mA, 18V.
Note : The Digital IO terminals are not isolated from the PV.
1.5.4 Relay Output
AA
Relay rating, min: 1V, 1mAdc. Max: 264Vac 2A resistive
AB
Relay shown in de-energised state
AC
1.5.4.1 General Note About Inductive Loads
High voltage transients may occur when switching inductive loads such as some contactors or solenoid valves.
For this type of load it is recommended that a ‘snubber’ is connected across the contact of the relay switching the load. The snubber typically consists of a 15nF capacitor connected in series with a 100
Ω
resistor and will also prolong the life of the relay contacts.
!
When the relay contact is open and it is connected to a load, the snubber passes a current (typically 0.6mA at 110Vac and 1.2mA at 240Vac. It is the responsibility of the installer to ensure that this current does not hold on the power to an electrical load. If the load is of this type the snubber should not be connected.
See also section 1.7.9.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 15
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 16
1.5.5 Power Supply Connections
L
N
24
24
85 to 264Vac
50/60Hz
24V ac or dc
1. Before connecting the instrument to the power line, make sure that the line voltage corresponds to the description on the identification label
2. For supply connections use 16AWG or larger wires rated for at least 75 o
C
3. Use copper conductors only
4. For 24V the polarity is not important
5. It is the Users responsibility to provide an external fuse or circuit breaker.
For 24 V ac/dc fuse type T rated 4A 250V
For 85/265Vac fuse type T rated 1A 250V
Safety requirements for permanently connected equipment state:
• a switch or circuit breaker shall be included in the building installation
• it shall be in close proximity to the equipment and within easy reach of the operator
• it shall be marked as the disconnecting device for the equipment
Note: a single switch or circuit breaker can supply more than one instrument
1.6 Plug in I/O Module Connections
Plug in I/O modules can be fitted in three positions in the 3508 and six positions in 3504. The positions are marked
Module 1, 2, 3, 4, 5, 6. With the exception of the Analogue Input module, any other module listed in this section, can be fitted in any of these positions. To find out which modules are fitted check the ordering code printed on a label on the side of the instrument. If modules have been added, removed or changed it is recommended that this is recorded on the instrument code label.
The function of the connections varies depending on the type of module fitted in each position and this is shown below. All modules are isolated.
I/O Module Typical usage
H/W
Code
Connections and examples of use
Note: The order code and terminal number is pre-fixed by the module number.
Module 1 is connected to terminals 1A, 1B, 1C, 1D; module 2 to 2A, 2B, 2C, 2D, etc.
Relay (2 pin) and
Dual Relay
2A, 264Vac max
1mA 1V min
Heating, cooling, alarm, program event, valve raise, valve lower
R2 and
RR
Contactor
Relay
Panel lamp etc
Voltage supply
Contactor
Relay
Panel lamp etc
First relay
A
B
C
D
Second relay
(dual relay only)
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 17
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 18
I/O Module
Change Over
Relay
(2A, 264Vac max)
1mA 1V min
Triple Logic
Output
(18Vdc at
8mA max.)
Triac and Dual
Triac
(0.7A, 30 to
264Vac combined rating)
Typical usage
Heating, cooling, alarm, program event, valve raise, valve lower
Heating, cooling, program events
Heating, cooling, valve raise, valve lower
H/W
Code
R4
TP
T2 and TT
Connections and examples of use
SSR or thyristor unit
-
+
Contactor
Relay
Panel lamp etc
Voltage supply
Output A
Output B
Output C
Common
+
+
+
_
A
B
C
D
A
B
C +
D
Motorise d valve
Raise
Voltage supply
Lower
A
B
C
First triac
Note 1: Dual relay modules may be used in place of dual triac.
Note 2:-
The combined current rating for the two triacs must not exceed 0.7A.
Triple Logic
Input
Triple
Contact
Input
I/O Module
DC Control
(10Vdc,
20mA max)
DC Retransmission
(10Vdc,
20mA max)
Typical usage
Heating, cooling e.g. to a
4-20mA process actuator
Logging of
PV, SP, output power, etc.,
(0 to 10Vdc,
0 to 20mA)
Events e.g. Program
Run, Reset,
Hold
Events e.g. Program
Run, Reset,
Hold
H/W
Code
D4
D6
TL
TK
Actuator
0-20mA or
0-10Vdc
To other controllers
0-20mA or
0-10Vdc
Logic inputs
<5V OFF
>10.8V ON
Limits:
-3V, +30V
Input 1
Input 2
Input 3
Common
External
Switches or
Relays
Contact inputs
<100! ON
>28K! OFF
Connections and examples of use
A
B
A
B
Input 1
Input 2
Input 3
Common
+
-
+
-
A
B
C
D
A
B
C
D
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 19
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 20
I/O Module Typical usage
H/W
Code
Connections and examples of use
24V
Transmitter
Supply
(20mA)
To power an external transmitter
MS
Transmitter
+
-
A
B
+0.5V
A
Potentiomet er input
100 Ω to
15K
Ω
0V
B
C
D
Transducer
Transducer
Power
Supply
Configurable
5V or 10Vdc
Minimum load resistance
300
Ω
10Vdc power supply
Internal switch to connect Rcal
V+
V-
C
D
Input
A
B
C
D
+
-
Controller
V+
A
B
V-
Calibration resistor Rcal
This may be fitted either in the transducer or in the controller
Input if an analogue input module is used in the appropriate slot
Anologue
Input
(T/C & RTD)
Modules
1, 3, 4 & 6 only
(mV, V and mA)
I/O Module Typical usage
Second or third PV input
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04
H/W
Code
AM
Connections and examples of use
3-wire RTD
A
For 2-wire this is a local link
mV (""""40mV or """"80mV)
B
C
D
Voltage
-3 to 10V or –1.4 to 2V
Current 0 to 20mA
Or (4 to 20mA)
+ mVolt source
-
-
-
+
+
Current source
Thermocouple
Volt source
2.49
Ω resistor supplied
+
-
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
21
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 22
I/O Module
Anologue
Input
(T/C & RTD)
Modules
1, 3, 4 & 6
only
PV Input
Module
Modules
1, 3, 4 & 6
only
Typical usage
Zirconia
Probe
H/W
Code
AM
PV
Connections and examples of use
The temperature sensor of the zirconia probe can be connected to the Fixed PV input, terminals V+ and V-, or to an Analogue Input module, terminals C & D. The
Volt Source connected to an Analogue Input module, terminals A & D.
A
B
+
V+ or C
V- or D
Volt source
-
-
C
D
Fixed PV (or an Analogue Input
Module)
Analogue Input Module
1.6.2 Zirconia Probe Construction
Hot End
Zirconia
Sensor
Ceramic Insulator
Outer Electrode
Inner Electrode
Outer metallic shell of the probe
Screen
-
+
+
-
Zirc. mV
Thermocouple
1.6.3 Zirconia Probe Screening Connections
The zirconia sensor wires should be screened and connected to the outer shell of the probe if it is situated in an area of high interference.
+
A
B
Outer Electrode
Inner Electrode
Screen
Zirc. mV
+
-
+
Screened Cable
-
C
D
A
T.C.
-
+
B
C
-
D
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 23
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 24
1.7 Digital Communications Connections
Digital Communications modules can be fitted in two positions in both 3508 and 3504 controllers. The connections being available on HA to HF and JA to JF depending on the position in which the module is fitted. The two positions could be used, for example, to communicate with ‘iTools’ configuration package on one position, and to a PC running a supervisory package on the second position.
Communications protocols may be ModBus, EIBisynch, DeviceNet, Profibus or Ethernet.
Note:- In order to reduce the effects of RF interference the transmission line should be grounded at both ends of the screened cable. However, if such a course is taken care must be taken to ensure that differences in the earth potentials do not allow circulating currents to flow, as these can induce common mode signals in the data lines.
Where doubt exists it is recommended that the Screen (shield) be grounded at only one section of the network as shown in all of the following diagrams.
1.7.1
Modbus Slave (H or J Module) or EIBisynch
A further description of ModBus and EIBisynch communications is given in 2000 series Communications Handbook,
Part No. HA026230.
RS232 Connections
Com
Tx
Rx
Screen
Local Ground
HA or JA
HB or JB
HC 0r JC
HD or JD Common
HE or JE Rx
HF or JF Tx
RS232 Connections
RS485 2-Wire Connections
Com
Tx
Rx
Screen
Com
Rx
Tx
220 Ω termination resistor on last
Daisy Chain to further controllers controller in the line
HA or JA
HB or JB
220 Ω termination resistor
HC 0r JC
Com
RxA
RxB
TxA
TxB Twisted pairs
HD or JD Com
HE or JE Rx
HF or JF Tx
RS232/RS485 2-wire communications converter
RS422/RS485 4-Wire Connections
Com
Tx
Rx
Screen
Com
Tx
Rx
220 Ω termination resistor on last controller in the line
TxA
TxB
Com
RxA
RxB
RS232 to RS422/RS485
4-wire communications converter
220
Ω termination resistor
Daisy Chain to further controllers
Twisted pairs
HA or JA
HB or JB
HC 0r JC
HD or JD Common
HE or JE Rx
HF or JF Tx
The KD485 communications converter is recommended for interfacing to RS485. This unit is also used to buffer an
RS485 network when it is required to communicate with more than 32 instruments on the same bus, and may also be used to bridge 2-wire RS485 to 4-wire
RS422.
The 261 or KD485 communications converter is recommended for:
Interfacing 4-wire to 2-wire connections.
To buffer an RS422/485 network when more than 32 instruments on the same bus are required
To bridge 2-wire RS485 to 4wire RS422.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 25
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 26
!
A description of DeviceNet is given in the DeviceNet Communications Handbook Part No HA027506 which can be downloaded from www.eurotherm.co.uk
.
Terminal
Reference
CAN
Label
Color
Chip
Description
HA V+
HB CAN_H
Red DeviceNet network power positive terminal. Connect the red wire of the DeviceNet cable here. If the DeviceNet network does not supply the power, connect to the positive terminal of an external 11-25 Vdc power supply.
White DeviceNet CAN_H data bus terminal. Connect the white wire of the DeviceNet cable here.
HC SHIELD None
HD
HE
HF
CAN_L
V-
Blue
Black
Shield/Drain wire connection. Connect the DeviceNet cable shield here. To prevent ground loops, the DeviceNet network should be grounded in only one location.
DeviceNet CAN_L data bus terminal. Connect the blue wire of the DeviceNet cable here.
DeviceNet network power negative terminal. Connect the black wire of the DeviceNet cable here. If the DeviceNet network does not supply the power, connect to the negative terminal of an external 11-25 Vdc power supply.
Connect to instrument earth
Note: Power taps are recommended to connect the DC power supply to the DeviceNet trunk line. Power taps include:
A Schottky Diode to connect the power supply V+ and allows for multiple power supplies to be connected.
2 fuses or circuit breakers to protect the bus from excessive current which could damage the cable and connectors.
The earth connection, HF, to be connected to the main supply earth terminal.
1.7.3 Example Devicenet Wiring Diagram
5-Position COMBICOM
Red
V+ 5
CAN-H 4
Drain 3
Wht
Blu
CAN-L 2
V- 1
Blk
Card
Top
Diag
DB-9M
RDY RUN
NET MON
Typical Interface Card
(MASTER)
Network Supply
24Vdc ( +1%)
250mV p-p Ripple
V+
V-
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04
121! terminating resistor required fitted if not internally
2704 Controller
HA
V+
HB
HC
CAN-H
Drain
HD
HE
HF
CAN-L
V-
(SLAVE)
Address 11
L
N
E
2704 Controller
HA
V+
HB
HC
HD
CAN-H
Drain
CAN-L
HE
HF
V-
(SLAVE)
Address 12
L
N
E
2704 Controller
HA
V+
HB
HC
121! *
L
N
E
HD
HE
HF
V-
(SLAVE)
Address N+1
Daisy chain to further instruments
* Fit to last instrument in the chain
27
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 28
1.7.4 Profibus
A description of ProfiBus is given in the ProfiBus Communications Handbook Part No HA026290 which can be downloaded from www.eurotherm.co.uk
.
1.7.5 Example Profibus Wiring
Master
A B
Connections ‘daisy chained’ to other instruments
Twisted pairs
390 Ω
220
Ω
Last controller only requires terminating resistors
390 Ω
HA
HB
HC
Shield
VP (+5V)
HD Rx/Tx +ve
HE
HF
HA
HB
HC
HD
HE
HF
Rx/Tx -ve
Dig Grnd
Shield
VP (+5V)
Rx/Tx +ve
Rx/Tx -ve
Dig Grnd
1.7.6 Ethernet
When the controller is supplied with the Ethernet communications option a special cable assembly is also supplied.
This cable must be used since the magnetic coupling is contained within the RJ45 connector. It consists of an RJ45 connector (socket) and a termination assembly which must be connected to terminals HA to HF.
View of cable which may also be ordered separately as Part No
SUB3500/COMMS/EA
Activity and power on LED indicators
Cable connected to terminals HA to HF
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 29
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 30
1.7.7 I/O Expander (or Additional Digital Input)
An I/O expander (Model No 2000IO) can be used with 3500 series controllers to allow the number of I/O points to be increased by up to a further 20 digital inputs and 20 digital outputs. Data transfer is performed serially via a two wire interface module which is fitted in digital communications slot J.
JE
JF
3500 Controller
Data transfer
E1
E2
#
20 Inputs
IO Expander
20 Outputs
#
For details of the IO Expander refer to the Operating Instructions HA026893. The connections for this unit are reproduced below for convenience.
1.7.8 IO Expander Connections
Comms
E1
E2
Screen
Transmitter
PSU Out
+
-
Outputs
21 to 30
A
C
A
C
A
C
A
C
A
C
A
C
A
B
C
A
B
C
A
B
C
A
B
C
21
22
23
1
2
3
24
4
25
5
26
27
28
29
30
10
8
9
6
7
24
24
E
24V Supply ac or dc dc polarity not important
-
-
-
+
-
-
-
+
Digital Inputs
1 to 10
Outputs
21 to 30
Outputs
31 to 40
A
C
A
C
A
C
A
C
A
C
A
C
A
C
A
C
A
C
A
C
30
10
10 IO Expander Board
Additional IO Expander Board
31
37
11
32
12
33
13
34
14
35
15
36
16
17
38
18
39
40
19
20
-
+
-
+
-
-
-
+
-
+
-
-
-
Digital Inputs
1 to 10
Digital Inputs
11 to 20
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 31
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 32
1.7.9 Example Wiring Diagram
Controller fuse 2A type T
Line
Heater fuse
Neutral
Heater
Solid
State
Relay
(e.g.
TE10)
+
-
Snubber
Cooling or alarm relay
Please refer to the EMC Electromagnetic Compatibility Handbook Part No. HA025464 for details of good wiring practice. This can be downloaded from www.eurotherm.co.uk
.
1.7.10 Snubbers
Snubbers are used to prolong the life of relay contacts and to reduce interference when switching inductive devices such as contactors or solenoid valves. The fixed relay (terminals AA/AB/AC) is not fitted internally with a snubber and it is recommended that a snubber be fitted externally, as shown in the example wiring diagram. If the relay is used to switch a device with a high impedance input, no snubber is necessary.
All relay modules are fitted internally with a snubber since these are generally required to switch inductive devices.
However, snubbers pass 0.6mA at 110V and 1.2mA at 230Vac, which may be sufficient to hold on high impedance loads. If this type of device is used it will be necessary to remove the snubber from the circuit.
The snubber is removed from the relay module as follows:-
1. Unplug the controller from its sleeve
2. Remove the relay module
3. Use a screwdriver or similar tool to snap out the track. The view below shows the tracks in a Dual Relay Output module.
Break out tracks as required to disconnect the snubber
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 33
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 34
2. Chapter 2: Getting Started
A brief start up sequence consists of a self test in which all elements of the display are illuminated and the software version is shown. What happens next depends on one of two conditions;-
1. Power up out of the box – when the controller has no preset configuration and is switched on for the very first time it will start up in 'QuickStart mode. This is an intuitive tool for configuring the controller and is described in section 2.1 below.
2. The controller has been powered up previously and is already configured. In this case go to section 2.3.
2.1 Quick Start - New Controller (Unconfigured)
When the controller is switched on for the very first time it will display the 'Startup' screen shown below.
* Manual mode is always selected when in Quick Start mode because the controller resets to cold start when Quick Start is selected.
Controller Display 3504 3508
2.1.1 To Configure Parameters in Quick Start Mode
Press
▲ or
▼
to select Quick Start Mode or Configuration Mode. ‘Config’ will allow you to enter full configuration mode, covered in detail in later sections of this handbook.
Press $ to scroll through the list of parameters
Edit the parameters using the
▲ or
▼ buttons
Each time $ button is pressed a new parameter will be presented
This is illustrated by the following example:- (The views shown are taken from the 3508 controller but the same information is included in the 3504).
☺
Backscroll – to scroll back through parameters press and hold $ then press
▲ to go back through the list of parameters. You can also press and hold $ +
▼
to go forward - this has the same effect as pressing $ alone.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 35
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 36
Example
Do This Display Additional Notes
1. From the Start view press
$ or
▼
to change the ‘Units’
The first parameter to be configured is ‘Units’. It resides in the ‘PV Input List’ because it is associated with the process variable.
When the required choice is selected a brief blink of the display indicates that it has been accepted
3. A different parameter is selected each time
$ pressed.
is
4. Continue setting up the parameters presented until the ‘Finished’ view is displayed.
If you wish to scroll around the parameters again do not select Yes but continue to press
$
.
When you are satisfied with the selections select ‘Yes’.
The display will then show the ‘HOME’ display shown in section 2.3
5. If all parameters are set up as required press ▲ or
▼
to ‘Yes’
The following table summarises all the parameters which can be set up by the above procedure.
2.1.2 Quick Start Parameters
Parameters shown in Bold are defaults.
Group
PV Input Units
Parameter
Used to select the engineering units for the
PV
PV Input Resolution
Used to select the required decimal point position for the PV
PV Input Range Type
Used to select the linearisation algorithm required and the input sensor.
PV Input Range High
Configures the maximum display range and SP limits
PV Input Range Low
Loop
Configures the minimum display range and SP limits
Control Channel 1
Sets the control type for channel 1 (normally Heat)
Loop Control Channel 2
Sets the control type for channel 2 (normally Cool)
Value
C, F, K
V. mV, A, mA, pH, mmHg, psi, Bar, mBar, %RH, %, mmWG, inWG, inWW, Ohms, PSIG, %O2, PPM,
%CO2, %CP, %/sec, mBar/Pa/T, sec, min, hrs, None
XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX
Thermocouple: J, K, L, R, B, N, T, S, PL2, C.
RTD: Pt100
Linear: 0-50mV, 0-5V, 1-5V, 0-10V, 2-10V, 0-
20mA, 4-20mA
Depends on Range type selected. Default 1200
Depends on Range type selected. Default 0
PID, VPU, VPB, Off, OnOff
PID, VPU, VPB, Off, OnOff
Always
Always
Always
Always
Always
Always
Always
Availability
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 37
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 38
Group Parameter
LgcIO LA Logic OP (or IP) function
The LA Logic I/O port can be an output or an input.
This parameter is used to select its function.
LgcIO LA Min OnTime
This applies to both LA and
LB inputs
Not Used, Chan 1, Chan 2, Alarm 1 to 8, Any
Alarm, New Alarm, ProgEvnt1 to 8, (outputs)
Auto Man, AlarmAck, ProgRun, ProgReset,
ProgHold (Inputs)
Auto
0.01 to 150.00
Value
[Note 1]
[Note 2]
Availability
Only appears if Control Channel
= VPB and the channel is allocated to the LA output
[Note 2]
LgcIO LB Logic OP (or IP) function
The LB Logic I/O port can be an output or an input.
This parameter is used to
Not Used
All parameters the same as LA I/O
Only appears if Control Channel
= VPB and the channel is allocated to the LB output
[Note 2]
RlyOP
AA select its function.
Relay function
This relay is always fitted.
Not Used, Chan 1, Chan 2, Alarm 1 to 8, Any
Alarm, New Alarm, ProgEvnt1 to 8
Always.
[Note 3]
Note 1) Parameters only appear if the function has been turned on, eg If ‘Control Channel 1’ = ‘Off’, ‘Chan 1’ does not appear in this list.
When a control channel is configured for valve positioning, LgcIO LA and LgcIO LB act as a complementary pair. If, for example,
Chan 1 is connected to LgcIO LA (valve raise) then LgcIO LB is automatically set to Chan 1 (valve lower). This ensures the valve is never raised and lowered simultaneously.
The same complementary behaviour also applies to dual output modules and channels A and C of triple output modules
Note 2) If any input function, for example Chan 1, is connected to another input it will not appear in this list
Note 3) For valve position control Chan 1 or Chan 2 will not appear in this list. Valve position outputs can only be dual outputs such as LA and LB or dual relay/triac output modules
Modules
The following parameters configure the plug in I/O modules. I/O Modules can be fitted in any available slot in the instrument (6 slots in 3504,
3 slots in 3508). The controller automatically displays parameters applicable to the module fitted - if no module is fitted in a slot then it does not appear in the list.
Each module can have up to three inputs or outputs. These are shown as A, B or C after the module number and this corresponds to the terminal numbers on the back of the instrument. If the I/O is single only A appears. If it is dual A and C appears if it is triple A, B and C appear.
Module type Parameter Value Availability
Change over relay (R4)
2 pin relay (R2)
Triac output (T2)
Relay (Triac) function
Not Used
All parameters the same as RlyOP AA
Always (if the module is fitted)
Dual Relay (RR)
Dual triac output (TT)
Single Logic Output (LO)
Triple Logic Output (TP)
DC Output (D4)
DC Retransmission (D6)
Relay (Triac) function
Not Used
All parameters the same as RlyOP AA
Relay function
Not Used
All parameters the same as RlyOP AA
Logic Out function Not Used
All parameters the same as RlyOP AA
Logic OP function
Not Used
All parameters the same as RlyOP AA
DC Output function
Not Used
Chan 1
Module fitted but not configured
Channel 1 control output
Chan 2
SP Retran
Channel 2 control output
Setpoint retransmission
PV Retran
ErrRtran
PwrRtran
Process variable retransmission
Error Retransmission
Power output retransmission
Always (if the module is fitted)
Always (if the module is fitted)
Always (if the module is fitted)
Always (if the module is fitted)
Always (if the module is fitted)
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 39
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 40
Module type Parameter Value Availability
Triple Logic Input (TL)
Triple Contact Input (TK)
Analogue Input (AM)
Range Type
Display High
Display Low
Logic Input function
Analogue IP function
0–5V, 1-5V, 1–10V, 2–10V, 0-29mA, 4-20mA
100.0
0
Not Used
Auto Man
AltSP Sel
AlarmAck
ProgRun
ProgReset
ProgHold
Not Used
Loop PV
Remote SP
RemOPH
RemOPL ch1VlvPos ch2VlvPos
Module fitted but not configured
Auto/manual
Alternative SP select
Alarm acknowledge
Programmer run
Programmer reset
Programmer hold
Module fitted but not configured
Loop process variable
Remote setpoint
Remote output power maximum
Remote output power minimum
To read valve position from feedback potentiometer
Range Type
Thermocouple: J, K, L, R, B, N, T, S, PL2, C.
RTD: Pt100
Linear: 0-50mV, 0-5V, 1-5V, 0-10V, 2-10V, 0-
20mA, 4-20mA
Potentiometer Input (VU) Pot Input function
Not Used
Module fitted but not configured
Loop PV
Remote SP
Loop process variable
Remote setpoint
A function can only be allocated to one input. eg if AlarmAck is configured on X*A it is not offered for the other inputs
* is the module number ch1VlvPos and ch2VlvPos only appear if the control channel
1 or control channel 2 is set to VPB.
Remote SP does not appear if the programmer option is supplied
Not shown if analogue
IP function not used
Ch1VlvPos/Ch2VlvPos only appear if the channel = VPB
Remote SP does not
Module type
Transducer Power Supply
(G3)
Transmitter power supply
(M5)
Parameter Value
RemOPH
RemOPL
Remote output power maximum
Remote output power minimum
Ch1VlvPos
Ch2VlvPos
Channel 1 valve position
Channel 1 valve position
TdcrPSU function
5 Volts
10 Volts
No parameters. Used to show the ID of the module if fitted
Availability
appear if the programmer option is supplied
Always (if the module is fitted)
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 41
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 42
Alarms
Group Parameter
Alarm 1 Type to 8
Alarm 1 to 8
Source
Setpoint
None
Abs High
Abs Low
Dev High
Dev Low
Dev Band
None
PV Input
Loop PV
ModX Ip
Value
No alarm type configured
Absolute high
Absolute low
Deviation high
Deviation low
Deviation band
Not connected
Connected to process variable
Connected to loop process variable for deviation alarms
Connected to a suitable module eg Analog IP (X = module number)
To adjust the alarm threshold within the range of the source.
Availability
Always
Always if Type ≠ None
PV Input and ModX Ip do not appear if Type
= Deviation
Always if Type ≠ None Alarm 1 to 8
Alarm 1 to 8
Latch
None
Auto
Manual
Event
No latching
Automatic latching see section 2.7.1
Manual latching see section 2.7.1
Alarm beacon does not light but any output associated with the event will activate and a scrolling message will appear.
Always if Type
≠
None
Finished Exit
No
Yes
Continue back around the quick configuration list
Go to normal operation
2.2 To Re-enter Quick Start Mode
If you have exited from Quick Start mode (by selecting ‘Yes’ to the ‘Finished’ parameter) and you need to make further changes, the Quick start mode can be entered again at any time. The action which takes place depends on one of two previous conditions as follows:-
2.2.1 Power up After a Quick Start Configuration
1. Hold down then power up the controller. Keep this button pressed until the Quick start screen as shown in section 2.1 is displayed.
to enter the quick start list. You will then be asked to enter a passcode.
3. Use or
▼ to enter the passcode – default 4 – the same as the configuration level passcode. If an incorrect code is entered the display reverts to the ‘Quick Start’ view section 2.1.
It is then possible to repeat the quick configuration as described previously.
The Quick Start view shown in section 2.1 now contains an additional parameter - ‘Cancel’. This is now always available after a power up, and, if selected, will take you into normal operating mode, section 2.3.
2.2.2 Power up After A Full Configuration
Repeat 1,2 and 3 above.
Full configuration allows a greater number of parameters to be configured in a deeper level of access. This is described in the Engineering Handbook Part No. HA027988.
If the controller has been re-configured in this level, a ‘WARNING’ message, ‘Delete config?’ - ‘No’ or ‘Yes’, will be displayed. If ‘No’ is selected the display drops back to the ‘GoTo’ screen. or
▼ to select ‘Yes’ to confirm or ! the WARNING message). to cancel. (If no button is pressed for about 10 seconds the display returns to
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 43
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 44
If ‘Yes’ is selected the Quick start defaults will be re-instated. It is then necessary to reset all the Quick start parameters.
Switch on the controller. Following a brief self-test sequence, the controller will start up in AUTO mode and Operator
Level 1. This section describes the operation of the controller in this level.
AUTO is the normal closed loop temperature control mode which means that the output power is adjusted automatically by the controller in response to the measurement from the input sensor. In this mode the format of the display for a new instrument is shown below. It is called the HOME display.
Indicator beacons
(listed below)
Process Variable (PV)
Setpoint (SP)
Message display
Current level of access indication shown 3504 only
Lev1
Lev2
Lev3
3508 3504
2.3.1 Beacon Display and Description
OP1
SPX
ALM
Illuminates when output 1 is ON (normally heating)
OP2 Illuminates when output 2 is ON (normally cooling or alarm)
MAN
Illuminates when manual mode active
REM
Illuminates when remote setpoint active
Illuminates when alternative setpoint active
If an alarm occurs the red alarm beacon flashes. This is accompanied by a message showing the source of the alarm, for example ‘Boiler overheating’.
To acknowledge press
!
and
▼
. The message disappears. If the alarm condition is still present the beacon lights continuously. When cleared it will extinguish. A full description of the alarm operation is given in section 2.7
RUN
HLD
J
H
IR
Illuminates when programmer running – flashing indicates End
Illuminates when programmer held
Flashes when J Channel comms active
Flashes when H Channel comms active
Flashes when infra red communications active
In general throughout this handbook instrument views will use the 3504. The displayed information is similar for the
3508 but in some cases is shortened due to display limitations.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 45
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 46
2.4 The Operator Buttons
A/MAN
This button can be disabled
PROG
RUN/HOLD
This button can be disabled
!
Page Scroll Lower Raise
Manual operation means that the controller output power is adjusted by the user. The input sensor is still connected and reading the PV but the control loop is open.
When pressed, this toggles between automatic and manual operation.
•
If the controller is in manual mode, ‘MAN’ light will be indicated
If the controller is powered down in Manual operation it will resume this mode when it is powered up again.
To select the programmer summary page
•
Press once to start a program. ‘RUN’ will be indicated
•
Press again to hold a program. ‘HLD’ will be indicated
•
Press and hold for at least two seconds to reset a program.
‘RUN’ will flash at the end of a program
‘HLD’ will flash during holdback
Programmer operation is fully described in chapter 21 of the Engineering Manual
Press to select new PAGE headings
$
Press to select a new parameter in the page
▼
Press to decrease an analogue value, or to change the state of a digital value
▲
Press to increase an analogue value, or to change the state of a digital value
2.4.1 Shortcut Key Presses
Backpage
Press and hold
▲
(With
!
. Then press ! . The page headers scroll backward at each press. still pressed
you can press
▼
to page forward. This action is the same as pressing
!
Backscroll alone).
Press and hold ▲
Press and hold
$
Press
! + $
when in a list. Then press
$
. Parameters scroll backward at each press. when in a list header. Then press.
▼
. Parameters scroll forward at each press.
Jump to the
HOME display
Alarm
Ack/reset
Press
!
+
$ when the HOME screen is being displayed. All active alarms will be acknowledged
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 47
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 48
2.5 To Set The Required Temperature (Setpoint)
button.
WSP is the current Working
SetPoint.
When the
▼
or
▲ button is pressed the mnemonic changes to the setpoint source, e.g. SP1
3504 View
Press and hold
▼ to lower the setpoint
Setpoint Value
Press and hold
▲ to raise the setpoint
3508 View
A momentary press of either button will show the setpoint in use eg SP1.
The new setpoint is accepted when the button is released and is indicated by a brief flash of the setpoint display
From the HOME display, press
▼
or
▲
2.6 To Select Manual Operation
3504 View 3508 View
Press button.
‘Man OP’ will be displayed on 3504
The ‘MAN’ beacon will be lit on both controllers
Press and hold
▼ to lower the output power
Upper display shows
Actual Temperature (or
Process Variable ‘PV’)
Lower display shows output power
Press and hold
▲ to raise the output power
The output power will change continuously while either of these buttons are pressed
If the controller is powered down in either Auto or Manual operation it will resume the same mode when it is powered up again.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 49
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 50
If an alarm occurs it is indicated as follows:-
The red alarm (ALM) beacon in the top left of the display flashes
Alarm number is indicated together with the flashing "
A default message or a pre-programmed message appears showing the source of the alarm
Invitation to acknowledge the new alarm
2.7.1 To Acknowledge an Alarm
Press ! and $ (Ack) together.
The action, which now takes place, will depend on the type of latching, which has been configured
Non Latched Alarms
If the alarm condition is present when the alarm is acknowledged, the alarm beacon will be continuously lit. This state will continue for as long as the alarm condition remains. When the alarm condition disappears the indication will also disappear.
If a relay has been attached to the alarm output, it will de-energise when the alarm condition occurs and remain in this condition until the alarm is acknowledged AND it is no longer present.
If the alarm condition disappears before it is acknowledged the alarm indication disappears as soon as the condition disappears.
Automatic Latched Alarms
The alarm continues to be active until both the alarm condition is removed AND the alarm is acknowledged. The acknowledgement can occur BEFORE the condition causing the alarm is removed.
Manual Latched Alarms
The alarm continues to be active until both the alarm condition is removed AND the alarm is acknowledged. The acknowledgement can only occur AFTER the condition causing the alarm is removed.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 51
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 52
The lower section of the HOME display contains an alpha-numeric set of messages. These messages change between different controller types and operating modes and are grouped in summary pages. The 3504 contains more information than the 3508, and generally the parameter descriptions are longer due to the larger display..
3504 3508
Press !
.
A set of pre-defined summary pages are shown at each press. These are typically a summary of programmer, loop and alarm operation. A further eight customised pages are also possible and these can be programmed off line using iTools programming software.
Loop Summary
The view opposite shows heat only.
For heat/cool the bar graph is bi-directional (+
100%) as shown below:-
For valve position control the user interface will display either heat only or heat/cool summary pages.
Press
At each press a new display will be shown
Programmer Summary
This display is only shown if the Programmer option has been enabled
Alarm Summary
Alarm Settings
All configured alarms will be listed
Control
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 53
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 54
2.8.2 How to Edit Parameters
In the above summary pages, press $ to scroll to further parameters (where applicable).
Press
▼
or
▲
to change the value of the parameter selected.
Any parameter preceded by v is alterable provided the system is in a safe state to allow the parameter to be changed.
For example, ‘Program Number’ cannot be changed if the program is running - it must be in ‘Reset’ or ‘Hold’ mode. If an attempt is made to alter the parameter its value is momentarily replaced by ‘---‘ and no value is entered.
Some parameters are protected under a higher level of security – Level 2. In these cases it will be necessary to select
‘Access Level 2’. This is carried out as follows:-
1. Press and hold
!
until the display shows
to select Level 2
again to enter a security code. This is defaulted to 2. If an incorrect code is entered the display reverts to that shown in 1 above. If the default of 2 is not accepted this means that the code has been changed on your particular controller. It will be necessary to refer to the Engineering Handbook.
4. ‘Pass’ is displayed momentarily. You are now in Level 2.
2.8.3 Programmer Summary Page
Provided it has been ordered and enabled the 3500 series controllers can program the rate of change of setpoint. Up to 50 programs and up to a maximum of 200 segments in total, can be stored and run. Chapter 21 explains setpoint programming in more detail.
2.8.3.1 To Select a Parameter
Press
$ to scroll through a list of parameters. On the ‘Programmer Summary’ shown here, the list of parameters which can be selected are:-
Value Default Available in Level Parameter
Name
Program
Parameter Description
Program number (and name if this has been configured)
Segment Segment number (and type on 3504)
Only appears when the programmer is running
Seg Time Left Segment Time Left
Only appears when the programmer is running
1 to max number of programs
1 to max number of segments
1 L1 Alterable when prog in reset
1 L1 only
L1
PSP Profile setpoint value
Run
Hold
Holdback
Prog running
Prog held
In holdback
Can be changed in Hold L1
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 55
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 56
Parameter
Name
Cycles Left
Advance
SkipSeg
Fast Run
Events or
Rst Events
Prg. TimeLeft
Parameter Description
Number of repeat cycles left to run
Can only be changed in Hold or Reset
Sets the program setpoint equal to the target setpoint and moves to the next segment.
Only operates when the programmer is running (not in Hold)
Moves immediately to the next segment and starts from the current setpoint value.
Only operates when the programmer is running (not in Hold)
This is only available in level 3 as described in later chapters. Set to ‘Yes’ and then run the program. The programmer will run through the segments at a fast rate. It is intended to be used only to test a new program and should not be used on an active process
State of the event outputs when the program is running or when in reset
1 to maximum number of cycles set
No
Yes
No
Yes
No
Yes
Value
This is a momentary action
This is a momentary action
Fast run disabled
Fast run enabled
Event inactive
Event active
Time remaining to end of selected program hrs:mins:secs
Default Available in Level
L1 R/O in Run
No L1
No L1
L3
L1
L1
2.8.3.2 To Select and Run a ProgramProfiBus
In this example it is assumed that the program to be run has already been entered. Setpoint programming is described in detail in Chapter 21 of the Engineering Handbook.
Do This The Display You Should See Additional Notes
1. From any display press
! until the ‘Programmer User
Display’ is shown
to ‘Program’ or
▼
to choose the program number to be run
In this example Program Number 2 is chosen and has been given a user defined name.
In the 3504 Program names can be entered using the offline programming package ‘iTools’.
4. Press or select ‘Status’ and set this to ‘Run’
‘RUN’ is displayed in the indicator beacons section of the main display.
The view shown here shows current working setpoint, program being run, current segment number and time left to complete this segment.
5. To Hold a program press
6. To Reset a program press
for at least 3 seconds
Press again to continue the program.
When the program is complete ‘RUN’ will flash
‘RUN’ will extinguish and the controller will return to the HOME display.
An alternative way to run, hold or reset the program is to scroll to ‘Program Status’ using
$ select ‘Run’, ‘Hold’ or ‘Reset’ using ▲ or
▼
and
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 57
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 58
2.8.4 Alarm Summary Page
This page shows a summary of all analogue alarms. Press $ to scroll through the alarms.
The diagram illustrates that an alarm is present in the system but that none of the alarms need acknowledgement.
A New Alarm occurs when any new alarm becomes active. This parameter may be used to activate a relay output to provide external audible or visual indication.
2.8.5 Alarms Setting Page
Up to eight analogue alarms can be configured. The alarm thresholds can be set in Level 2 in this page.
Press $ to scroll through the alarms.
Press
▲ or
▼
to set the threshold values
Analogue alarm 1, configured as Absolute High and set to operate at 123.00
Analogue alarm 2, configured as Absolute Low and set to operate at -10.00
2.8.6 Control Summary Page
Parameters which define the way a control loop operates can be set in this page. Control parameters are further described in Chapter 20 of the Engineering handbook.
Press $ to scroll through a list of parameters.
Press
▲ or
▼
to change the value of the selected parameter.
On the Control Summary page the following parameters are available:-
Parameter
Name
SP Select
SP1
SP2
SP Rate
Tune
(1)
Parameter Description
To select SP1 or SP2
To set the value of SP1
To set the value of SP2
To set the rate at which the setpoints change
To start self tuning
Value
Between range limits set in higher levels of access
PB
(1)
Ti
(1)
Td
(1)
R2G
(1)
CBH
(1)
CBL (1)
Output Hi
Output Lo
To set proportional band
To set integral time
To set derivative time
To set relative cool gain
To set cut back high
To set cut back low
To set a high limit on the control output
To set a low limit on the control output
Off
On
0 to 99999
Off to 99999
Off to 99999
0.1 to 10.0
Auto to 99999
Auto to 99999
-100.0 to 100.0%
-100.0 to 100.0%
Default
As order code
Off
100.0
0.0
Available in
Level
Lev1
Lev1
Lev1
Lev - alterable in
Lev2
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 59
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 60
Parameter
Name
Ch1 OnOff
Hyst
Ch2 OnOff
Hyst
Ch2 DeadB
Ch1 TravelT
Ch1 TravelT
Safe OP
Parameter Description
Channel 1 hysteresis (Only if configured for On/Off control)
Channel 2 hysteresis (Only if channel 2 is configured and for On/Off control)
Channel 2 deadband. To set the period in which there is no output from either channel. (This does not appear if channel 2 is not configured)
Motor travel time if valve control output on channel 1
Motor travel time if valve control output on channel 1
To set an output level under sensor break conditions
(1)
Does not appear if control is configured for On/Off parameters
Value
0.0 to 200.0
0.0 to 200.0
Off to 100.0
0.0 to 1000.0 seconds
0.0 to 1000.0 seconds
-100.0 to 100.0% 0.0
Default Available in
Level
Lev 1- alterable in
Lev2
2.9 Introduction to Configuration using iTools
iTools is a PC based configuration package which is used to configure instruments. The controller may be connected to the PC in three ways:-
1. Using an infra red clip (IR) attached to the front fascia. Set the parameter ‘IR Mode’ in the ‘Access’ list to ‘On’.
2. Using a configuration clip which plugs into the side of the controller
Both items are available from your supplier
3. Using a RS232, RS485 or RS422 digital communications interface connected to the H or J terminals
iTools provides:-
• Parameter Set up
•
Device Operation
• Device Recipe
•
Program Editing
• Configuration of User Pages
•
Graphical Wiring
• Cloning iTools and handbook part no HA026179 can be downloaded from www.eurotherm.co.uk.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 61
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 62
With the controller connected, press on the iTools menu bar. iTools will search the communications ports and TCPIP connections for recognisable instruments. Controllers connected with the configuration clip (CPI), will be found at address 255 regardless of the address configured in the controller.
2.9.2 Parameter Set Up
Allows parameters to be configured.
1. Press to get this view
2. Open up the parameter list by double clicking the required folder. Right click in the parameter list to reveal or hide columns.
3. To change the value of a parameter, double click the parameter and change its value using the pop-up window
4. The ‘Access’ button puts the controller into configuration mode. In this mode the controller can be set up without its outputs being active. Press ‘Access’ again to return to operating level.
5. The instrument view is optional. Select ‘Panel Views’ in the ‘View’ menu.
6. To find a parameter select the ‘Find’ tab.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 63
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 64
2.10 Device panel
Press for this feature.
T he Panel displays the active instrument panel. This can be used for remote viewing, diagnostics or Training. iTools can be used OFF-LINE to configure the product. The panel view gives an indication of how the instrument will appear when the configuration is downloaded.
The front panel control buttons, shown in the Device
Panel display, are active and clicking on them with the mouse will cause the display to behave as a real instrument.
☺
Clicking on the Page button with Ctrl pressed emulates pressing the page and scroll buttons together.
2.11 User Pages Editor
Up to 8 User Pages with a total of 64 lines can be created and downloaded into the controller so that the controller display shows only the information which is of interest to the user.
Press to select this feature
Text entered here will be shown on the instrument display
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 65
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 66
2.11.1 To create a User Page
1. Press to select the page number 1 to 8
2. Drag and drop parameters from the browser to create the user parameter list
3. Choose the required style. The format is shown in the pop up window
4. Right click in the list to: a. Insert an item b. Remove an item c. Edit Wire. allows you to change the parameter selected d. Edit Text. Allows you to enter your own text for the parameter displayed e. Edit Style. This is shown in the pop up window f. Read Parameter Properties g. Open Parameter Help
5. Select the operator level at which the user page will be displayed
6. If a bar graph is displayed, set the low and high graph axes
The format of the user page is shown in the instrument view
The user page can now be saved and downloaded to the instrument.
2.12 Recipe Editor in iTools
Press for this feature. Up to 8 recipes can be stored. They can also be named by the user.
Recipes allow the operator to change the operating values of up to 24 parameters in an instrument for different batch items/processes by simply selecting a particular recipe to load. Recipes are important for reducing error in setup and they remove the need for operator instructions fixed to the panel next to the instrument.
The Recipe Editor is used during configuration to assign the required parameters and to set up the values to be loaded for each recipe.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 67
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 68
2.12.1.1 Recipe Menu Commands
Load Recipe
Save
Edit Parameter
Delete Parameter
Edit Parameter Value
Rename Parameter Tag
Parameter Properties
Copy Parameter
Paste Parameter
Columns
Load Access Level
Level1
Used to load a recipe file into the instrument
Used to save the current recipe configuration into a file
Used to assign a parameter to a Tag. Parameters can also be assigned by 'drag and drop' from the iTools parameter list
Used to delete an assigned parameter from the recipes
Used to edit the current value of the assigned parameter
Allows the user to rename the Tag of the associated parameter. This tag is used on the instrument to identify assigned parameters (default Value1 - Value24)
Used to find the properties and help information of the selected parameter
Used to copy the currently selected parameter
Used to assign a previously copied parameter to the selected Tag
Used to hide/show the Description and Comment Columns
Used to configure the lowest access level in which the selected recipe is allowed to load
Permitted to load when the instrument is in any of the access levels
Level2
Level3
Config
Permitted to load when the instrument is in Level2, Level3 or Config access levels
Permitted to load when the instrument is in Level3 or Config access levels
Permitted to load when the instrument is in the Config access level
Never
Never permitted to load
Note: Over comms, whilst the instrument is in operator mode, recipes that have been configured to load in Levels 1, 2 and 3 can be loaded. Whilst the instrument is in Config mode all recipes can be loaded.
Edit Data Set Value
Used to edit the value of the selected assigned parameter within the selected recipe. Values can also be edited via double left clicking the value itself
Clear Data Set Value
Rename Data Set
Used to clear the value of the selected assigned parameter within the selected recipe, thus disabling it from loading when the recipe is selected to load
Allows the user to rename the selected recipe. This name is used to identify individual recipes (default Set1 - Set8). Note:
Number of recipes dependent upon features
Clear Data Set
Used to clear all values in the selected recipe, thus disabling all from loading when the recipe is selected to load
Used to copy all of the assigned parameters current values into the selected recipe
Snapshot Values
Copy Data Set
Paste Data Set
Used to copy all values of the selected recipe
Used to paste all values of a previously copied recipe into the selected recipe
2.13 Program Editor
Setpoint programs can be created graphically, stored and downloaded into the controller.
2.13.1 Analog View
1. Press to edit the analog setpoints
2. Select a program number using
and enter a name for the program
4. Right click in the blank area and choose ‘Add
Segment’
5. Select ‘Segment Type’ from the drop down and enter the segment details
6. Repeat for all required segments
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 69
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 70
2.13.2 Event Outputs
1. Press to select the digital events view.
2. Right click in the blank area to ‘Add Segment’
3. Use the pull downs to turn the digital event On or Off in the selected segment
2.14 Graphical Wiring Editor
Select parameter values.
(GWE) to view and edit instrument wiring. You can also add comments and monitor
1. Drag and drop required function blocks into the graphical wiring from the list in the left pane
2. Click on parameter to be wired from and drag the wire to the parameter to be wired to (do not hold mouse button down)
3. Right click to edit parameter values
4. Add comments and notes
5. Add monitor points
Download wiring
Click to view all parameters for an individual function block
Monitor
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 71
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 72
2.14.1 Function Block
A Function Block is an algorithm which may be wired to and from other function blocks to make a control strategy.
The Graphical Wiring Editor groups the instrument parameters into function blocks. Examples are: a control loop and a mathematical calculation.
Each function block has inputs and outputs. Any parameter may be wired from, but only parameters that are alterable may we wired to.
A function block includes any parameters that are needed to configure or operate the algorithm.
2.14.2 Wire
A wire transfers a value from one parameter to another. They are executed by the instrument once per control cycle.
Wires are made from an output of a function block to an input of a function block. It is possible to create a wiring loop, in this case there will be a single execution cycle delay at some point in the loop. This point is shown on by a || symbol and it is possible to choose where that delay will occur.
Dotted lines around a function block show that it requires downloading.
2.14.3 Using Function Blocks
If a function block is not faded in the tree then it can be dragged onto the diagram.
The block can be dragged around the diagram using the mouse.
A labelled loop block is shown here. The label at the top is the name of the block.
When the block type information is alterable click on the box with the arrow in it on the right to edit that value.
The inputs and outputs which are considered to be of most use are always shown.
In most cases all of these will need to be wired up for the block to perform a useful task. There are exceptions to this and the loop is one of those exceptions.
If you wish to wire from a parameter which is not shown as a recommended output click on the icon in the bottom right and a full list of parameters in the block will be shown, click on one of these to start a wire.
To start a wire from a recommended output just click on it.
Click ‘Select Output’ to wire new parameters
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 73
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 74
3. Chapter 3 Safety and EMC Information
This controller is manufactured in the UK by Eurotherm Ltd.
Please read this section carefully before installing the controller
This controller is intended for industrial temperature and process control applications when it will meet the requirements of the European Directives on Safety and EMC. Use in other applications, or failure to observe the installation instructions of this handbook may impair safety or EMC. The installer must ensure the safety and EMC of any particular installation.
3.1 GENERAL
The information contained in this manual is subject to change without notice. While every effort has been made to ensure the accuracy of the information, your supplier shall not be held liable for errors contained herein.
3.1.1 Safety
This controller complies with the European Low Voltage Directive 73/23/EEC, by the application of the safety standard
EN 61010.
This controller conforms with the essential protection requirements of the EMC Directive 89/336/EEC, by the application of appropriate product specific international standards . This instrument satisfies the general requirements of the industrial environment defined in EN 61326. For more information on product compliance refer to the
Technical Construction File.
3.1.3 Unpacking and storage
The packaging should contain an instrument mounted in its sleeve, two mounting brackets for panel installation and an
Installation & Operating guide. Certain ranges are supplied with an input adapter.
If on receipt, the packaging or the instrument are damaged, do not install the product but contact your supplier. If the instrument is to be stored before use, protect from humidity and dust in an ambient temperature range of -10 o
C to +70 o
C.
3.2 Service and repair
This controller has no user serviceable parts. Contact your supplier for repair.
3.2.1 Caution: Charged capacitors
Before removing an instrument from its sleeve, disconnect the supply and wait at least two minutes to allow capacitors to discharge. It may be convenient to partially withdraw the instrument from the sleeve, then pause before completing the removal. In any case, avoid touching the exposed electronics of an instrument when withdrawing it from the sleeve.
Failure to observe these precautions may cause damage to components of the instrument or some discomfort to the user.
3.2.2 Electrostatic discharge precautions
When the controller is removed from its sleeve, some of the exposed electronic components are vulnerable to damage by electrostatic discharge from someone handling the controller. To avoid this, before handling the unplugged controller discharge yourself to ground.
3.2.3 Cleaning
Do not use water or water based products to clean labels or they will become illegible. Isopropyl alcohol may be used to clean labels. A mild soap solution may be used to clean other exterior surfaces of the product.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 75
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 76
3.3 Installation Safety Requirements
Various symbols are used on the instrument, they have the following meaning:
!
3.3.2 Personnel
Installation must only be carried out by suitably qualified personnel.
3.3.3 Enclosure of live parts
To prevent hands or metal tools touching parts that may be electrically live, the controller must be installed in an enclosure.
3.3.4 Caution: Live sensors
The controller is designed to operate with the temperature sensor connected directly to an electrical heating element.
However you must ensure that service personnel do not touch connections to these inputs while they are live. With a live sensor, all cables, connectors and switches for connecting the sensor must be mains rated.
The logic IO is not isolated from the PV inputs.
3.3.5 Wiring
It is important to connect the controller in accordance with the wiring data given in this guide. Take particular care not to connect AC supplies to the low voltage sensor input or other low level inputs and outputs. Only use copper conductors for connections (except thermocouple inputs) and ensure that the wiring of installations comply with all local wiring regulations. For example in the UK use the latest version of the IEE wiring regulations, (BS7671). In the
USA use NEC Class 1 wiring methods.
The installation must include a power isolating switch or circuit breaker. The device should be mounted in close proximity to the controller, within easy reach of the operator and marked as the disconnecting device for the instrument.
The power supply to the system should be fused appropriately to protect the cabling to the units.
The maximum continuous voltage applied between any of the following terminals must not exceed 264Vac:
• relay output to logic, dc or sensor connections;
• any connection to ground.
The controller must not be wired to a three phase supply with an unearthed star connection. Under fault conditions such a supply could rise above 264Vac with respect to ground and the product would not be safe.
Electrically conductive pollution must be excluded from the cabinet in which the controller is mounted. For example, carbon dust is a form of electrically conductive pollution. To secure a suitable atmosphere, install an air filter to the air intake of the cabinet. Where condensation is likely, for example at low temperatures, include a thermostatically controlled heater in the cabinet.
This product has been designed to conform to BSEN61010 installation category II, pollution degree 2. These are defined as follows:-
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 77
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 78
3.3.10 Installation Category II
The rated impulse voltage for equipment on nominal 230V supply is 2500V.
3.3.10.1 Pollution Degree 2
Normally only non conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected.
3.3.11 Grounding of the temperature sensor shield
In some installations it is common practice to replace the temperature sensor while the controller is still powered up.
Under these conditions, as additional protection against electric shock, we recommend that the shield of the temperature sensor is grounded. Do not rely on grounding through the framework of the machine.
3.3.12 Over-Temperature Protection
When designing any control system it is essential to consider what will happen if any part of the system should fail. In temperature control applications the primary danger is that the heating will remain constantly on. Apart from spoiling the product, this could damage any process machinery being controlled, or even cause a fire.
Reasons why the heating might remain constantly on include:
• the temperature sensor becoming detached from the process
• thermocouple wiring becoming short circuit;
• the controller failing with its heating output constantly on
• an external valve or contactor sticking in the heating condition
• the controller setpoint set too high.
Where damage or injury is possible, we recommend fitting a separate over-temperature protection unit, with an independent temperature sensor, which will isolate the heating circuit.
Please note that the alarm relays within the controller will not give protection under all failure conditions.
3.4 Installation Requirements for EMC
To ensure compliance with the European EMC directive certain installation precautions are necessary as follows:
•
For general guidance refer to EMC Installation Guide, HA025464.
• When using relay outputs it may be necessary to fit a filter suitable for suppressing the conducted emissions. The filter requirements will depend on the type of load. For typical applications we recommend Schaffner FN321 or
FN612.
• If the unit is used in table top equipment which is plugged into a standard power socket, then it is likely that compliance to the commercial and light industrial emissions standard is required. In this case to meet the conducted emissions requirement, a suitable mains filter should be installed. We recommend Schaffner types
FN321 and FN612.
3.4.1 Routing of wires
To minimise the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power cables. Where it is impractical to do this, use shielded cables with the shield grounded at both ends. In general keep cable lengths to a minimum.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 79
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 80
4. Chapter 4 Technical Specification
All figures quoted at an ambient temperature from 0 to 50 o
C unless otherwise stated.
No. of Loops
Control Loops
Control Outputs
1
On/Off, single PID
Analogue, Time proportioned or
Motorised Valve control with or without feedback.
Cooling Algorithms Linear, Water, Fan, Oil
Auto/Manual Control Bumpless transfer or forced manual output.
Setpoint rate Limit
Motorised Valve
Off to 9999.9 engineering units per minute
Valve Position bounded or unbounded. Individual
Control
Tuning
Loop Alarms
Application Specific
Valve Positions for heat and cool
One-shot Auto tune or Manual.
High absolute, Low absolute, Deviation high, Deviation low, Deviation band,
All with separate hysteresis.
Humidity control
4.2 Display
3504
3508
Technology
Primary Large 5 digit display, Information centre 16 character header and 3 lines of 20 characters
Primary Large 41/2 digit display,
Information centre 8 character header and 3 lines of 10 characters
LCD with yellow/green backlight
Red alarm beacon
4.3 Standard Digital I/O
Allocation
Digital inputs
Digital outputs
Changeover relay
2 Off. Not isolated from each other. Not isolated from the PV inputs
Logic Bi-directional input/outputs
Logic or Contact closure input
Voltage level: input Inactive 0 to 7.3Vdc, Active 10.8V to 24Vdc
Contact closure: input active <480ohms, inactive >1200ohms
18Vdc at 9 to 15mA drive capability.
Contact rating
Min Load 1mA at 1V
Max Load 2A at 264Vac resistive
1,000,000 operations with addition of external snubber
4.4 All Analogue and PV Inputs
Sample rate
Input filtering
User calibration
9Hz (110msec.)
OFF to 999.9 seconds of filter time constant (f.t.c.). Default setting is 1.6 seconds
Both the user calibration and a transducer scaling can be applied.
Sensor break
Ranges a.c. sensor break on each input (i.e. fast responding and no dc errors with high impedance sources). mV, mA, volts -2V to +10V, -1V to +2V or RTD (pt100), pyrometer inputs
Thermocouple types Most linearisations including K, J, T, R, B, S, N, L, PII, C, D, E with linearisation error < ±0.2°C
CJC: Automatic (internal), external, 0 o
C, 45 o
C, 50 o
C reference blocks
General Resolution (noise free) is quoted as a typical figure with f.t.c. set to the default value = 1.6 second.
Resolution generally improves by a factor of two with every quadrupling of f.t.c.
Calibration is quoted as offset error + percentage error of absolute reading at ambient temperature of 25 O C
Drift is quoted as extra offset and absolute reading errors per degree of ambient change from 25
O
C.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 81
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 82
Sample rate
Input filter
40mV Range
80mV Range
2V Range
9Hz
Off, 0.2s to 60s filter time constant. Default setting 1.6s.
Range -40mV to +40mV
Resolution 1.9
µ V (unfiltered)
Measurement noise
Linearity error
Calibration error
Temperature coefficient ± 0.2
µ V/C ± 28ppm/C of measurement, from 25C ambient.
Input leakage current
Input resistance
Range
1.0
µ
V peak to peak with 1.6s input filter.
0.003% (best fit straight line)
±
4.6
µ
V
±
0.053% of measurement, at 25C ambient.
±
14nA
100M Ω
-80mV to +80mV
Resolution 3.2
µ V
Measurement noise
Linearity error
3.3
µ
V peak to peak with 1.6s input filter.
0.003% (best fit straight line)
Calibration error ± 7.5
µ V ± 0.052% of measurement, at 25C ambient.
Temperature coefficient ± 0.2
µ V/C ± 28ppm/C of measurement, from 25C ambient.
Input leakage current
Input resistance
± 14nA
100M
Ω
Range -1.4V to +2.0V
Resolution 82
µ
V
Measurement noise
Linearity error
90 µ V peak to peak with 1.6s input filter.
0.015% (best fit straight line)
Calibration error ± 420 µ V ± 0.044% of measurement, at 25C ambient.
Temperature coefficient
±
125
µ
V/C
±
28ppm/C of measurement, from 25C ambient.
Input leakage current ± 14nA
10V Range
PT100
Thermocouple
Input resistance
Range
100M Ω
-3.0V to +10V
Resolution 500 µ V
Measurement noise
Linearity error
550
µ
V peak to peak with 1.6s input filter.
0.007% for zero source resistance (best fit straight line)
Calibration error
Add 0.003% for each 10
Ω
of source + lead resistance.
± 1.5mV ± 0.063% of measurement, at 25C ambient.
Temperature coefficient
±
66
µ
V/C
±
60ppm/C of measurement, from 25C ambient.
Input resistance
Range
62.5k
Ω to 667k Ω depending on input voltage.
400
Ω
(-200C to +850C)
Resolution 50mC
Measurement noise
Linearity error
50mC peak to peak with 1.6s input filter.
0.033% (best fit straight line)
Calibration error ± 310mC ± 0.023% of measurement in C, at 25C ambient.
Temperature coefficient
±
10mC/C
±
25ppm/C of measurement in C, from 25C ambient.
Lead Resistance
Bulb current
0 Ω
200
to 22
µ
A
Ω , matched lead resistances.
Uses 40mV and 80mV ranges.
Types J, K, L, R, B, N, T, S, PL2 and C.
Linearisation error
External Cold Junction
± 0.2C
Internal Cold Junction
Calibration
±
1.0C at 25C ambient.
Ambient rejection ratio 40:1 from 25C ambient.
0C, 45C and 50C.
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 83
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 84
4.6 Analogue Input Module
mV input
0 - 2Vdc input
0 - 10Vdc input
Pt100 input
Thermocouple
100mV range - used for thermocouple, linear mV source, or 0-20mA with 2.49
Ω
external burden resistor.
Calibration: + 10 µ V + 0.2% of reading
Resolution: 6 µ V
Drift: < + 0.2
µ V + 0.004% of reading per
O
C
Input impedance: >10M
Ω
, Leakage: <10nA
-0.2V to +2.0V range - used for zirconia.
Calibration: + 2mV + 0.2% of reading
Resolution: 30 µ V
Drift: < + 0.1mV + 0.004% of reading per
O
C
Input impedance: >10M Ω , Leakage: <20nA
-3V to +10.0V range - used for voltage input.
Calibration: + 2mV + 0.2% of reading
Resolution: 200
µ
V
Drift: < + 0.1mV + 0.02% of reading per
O
C
Input impedance: >69K Ω
0 to 400ohms (-200°C to +850°C), 3 matched wires - up to 22! in each lead without errors.
Calibration: ±(0.4°C + 0.15% of reading in °C)
Resolution: 0.08°C
Drift: < ±(0.015°C + 0.005% of reading in °C) per °C
Bulb current: 0.3mA.
Internal compensation: CJC rejection ratio >25:1 typical.
CJ Temperature calibration error at 25
O
C: <± 2°C
0°C, 45°C and 50°C external compensation available.
4.7 Digital Input Modules
Module type
Contact closure
Logic inputs
Triple contact input, Triple logic input
Active <100ohms, inactive >28kohms
Current sinking : active 10.8Vdc to 30Vdc at 2.5mA inactive -3 to 5Vdc at <-0.4mA
4.8 Digital Output Modules
Module types
Relay rating
Single Logic drive
Triple logic drive
Triac rating
Single relay, dual relay, single triac, dual triac, triple logic module (isolated)
2A, 264Vac resistive (100mA, 12V minimum)
12Vdc at 24mA
12V at 9mA per output
0.75A, 264Vac resistive
4.9 Analogue Output Modules
Module types
Range
Resolution
1 channel DC control, 1 channel DC retransmission (5 max.)
0-20mA, 0-10Vdc
1 part in 10,000 (2,000-noise free) 0.5% accurate for retransmission
1 part in 10,000 2.5% accurate for control
4.10 Transmitter PSU
Transmitter 24Vdc at 20mA
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 85
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 86
4.11 Transducer PSU
Bridge voltage
Bridge resistance
Software selectable 5 or 10Vdc
300 Ω to 15K Ω
Internal shunt resistor 30.1K
Ω at 0.25%, used for calibration of 350 Ω bridge at 80%
4.12 Potentiometer Input
Pot resistance 330 Ω to 15K Ω , excitation of 0.5 volts
4.13 Digital communications
Allocation
Modbus
Profibus DP
2 modules fitted in slots H & J (isolated)
RS232, 2 wire or 4 wire RS485, max baud 19.2KB in H module & 9.6KB in J module
High Speed, RS485, 1.5Mbaud (Slot H only)
4.14 Master communications
Allocation
Modbus
Parameters
Slot J
RS485 4-wire or RS232
25 read/write
4.15 Alarms
No of Alarms
Alarm types
Modes
4.16 User messages
8 Analogue, 8 digital. Can be wired to any internal parameter
Full scale, deviation, sensor break plus application specific
Latching or non-latching, blocking, time delay
No of messages
Format
Maximum 100, triggered by operator or alarm or used for custom parameter names
Up to 16 characters
4.17 Control functions
No of loops
Modes
Cooling algorithms
PID sets
Manual mode
Setpoint rate limit
One
On/off, PID, motorised valve with or without feedback
Linear, water, oil or fan
3 per loop
Bumpless transfer or forced manual output, manual tracking available
Display units per second, minute or hour
4.18 Setpoint programmer
Programmer modes
Programmer types
No of programs
No of segments
Event outputs
Synchronous
Time to Target or Ramp Rate
A maximum of 50 programs. Programs can be given user defined 16 character names
200 segments total or 50 maximum per program
Up to 8, can be assigned individually to segments or called as part of an event group
4.19 I/O Expander
10 I/O version
20 I/O version
4 changeover relays, 6 normally open relay contacts, 10 logic inputs
4 changeover relays, 16 normally open relay contacts, 20 logic inputs
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 87
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 88
4.20 Advanced functions
Timers
Totalisers
Counters
Real time clock
Application blocks
Software Tools
4, On Pulse, Off delay, one shot and min-On
2, trigger level & reset input
2, up or down counters
Day of week and time
24 digital operations
24 analogue operations
2 eight input logic operators, 2 eight input analogue operators
16 user values
BCD input
Customised input linearisations
Mathematical Add, Subtract, Multiply, Divide, Constant, Absolute difference, Maximum, Minimum,
Sample and Hold, Input 1 to the power of input 2, Square root, Log(10), Ln, 10 to the power of input 1, i.e. to the power of input 1
Logical AND, OR, XOR, Latch, Equal, Not Equal, Greater than, Less than, Greater than or equal to, Less than or equal to.
Humidity Wet and dry bulb technique iTools Configuration Tool
OPC Scope Trending and Data logging iClone Lite Lightweight configuration cloning
Graphical Wiring Editor Drag and drop wiring tool, self-documenting
View Builder Custom Animation Screens iTools Wizard Question and Answer configuration screens
4.21 General specification
Supply
Inrush Current
Operating ambient
Storage temp
Panel sealing
Dimensions and weight
3504
3508
Electromagnetic compatibility
110 to 240Vac -15%, +10%. 48 to 62Hz. 20 watts max
85-264Vac
High Voltage controller – 30A duration 100µs
Low Voltage controller – 15A duration 100µs
0°C - 50°C (32
°F
to 131
°F)
and 5 to 95% RH non condensing
-10°C to +70°C ( 14°F to 158°F)
IP65, plug in from front panel
96H x 96W x 150D (mm) 0.6Kg
96H x 48W x 150D (mm) 0.4kG
EN61326-1 Suitable for domestic, commercial and light industrial as well as heavy industrial environments. ( Domestic/light industrial (Class B) emissions, Industrial (Class A) Environment immunity
emissions).
EN61010, installation category 2 (voltage transients must not exceed 2.5kV)
Not suitable for use above 2000m or in explosive or corrosive atmospheres
Safety standards
Atmospheres
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 89
3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 90
INTERNATIONAL SALES AND SERVICE
AUSTRALIA Sydney
Eurotherm Pty. Ltd.
Telephone (+61 2) 9838 0099
Fax (+61 2) 98389288
AUSTRIA Vienna
Eurotherm GmbH
Telephone (+43 1) 7987601
Fax (+43 1) 7987605
BELGIUM Moha&
LUXEMBURG Huy
Eurotherm S.A./N.V.
Telephone (+32 ) 85 274080
Fax (+32 ) 85 274081
BRAZIL Campinas-SP
Eurotherm Ltda.
Telephone (+55 19) 3237 3413
Fax (+55 19) 3234 7050
DENMARK Copenhagen
Eurotherm Danmark A/S
Telephone (+45 70) 234670
Fax (+45 70) 234660
FINLAND ABO
Eurotherm Finland
Telephone (+358) 22506030
Fax (+358) 22503201
FRANCE Lyon
Eurotherm Automation SA
Telephone (+33 478) 664500
Fax (+33 478) 352490
GERMANY Limburg
Eurotherm Deutschland GmbH
Telephone (+49 6431) 2980
Fax (+49 6431) 298119
Also regional offices
HONG KONG Aberdeen
Eurotherm Limited
Telephone (+852) 28733826
Fax (+852) 28700148
INDIA Chennai
Eurotherm India Limited
Telephone (+9144) 4961129
Fax (+9144) 4961831
IRELAND Dublin
Eurotherm Ireland Limited
Telephone (+353 01) 4691800
Fax (+353 01) 4691300
ITALY Como
Eurotherm S.r.l
Telephone (+39 031) 975111
Fax (+39 031) 977512
© Copyright Eurotherm Limited 2003
All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm Limited.
Every effort has been taken to ensure the accuracy of this specification. However in order to maintain our technological lead we are continuously improving our products which could, without notice, result in amendments or omissions to this specification.
KOREA Seoul
Eurotherm Korea Limited
Telephone (+82 31) 2868507
Fax (+82 31) 2878508
NETHERLANDS Alphen a/d Ryn
Eurotherm B.V.
Telephone (+31 172) 411752
Fax (+31 172) 417260
NORWAY Oslo
Eurotherm A/S
Telephone (+47 67) 592170
Fax (+47 67) 118301
SPAIN Madrid
Eurotherm España SA
Telephone (+34 91) 6616001
Fax (+34 91) 6619093
SWEDEN Malmo
Eurotherm AB
Telephone (+46 40) 384500
Fax (+46 40) 384545
SWITZERLAND Freienbach
Eurotherm Produkte (Schweiz) AG
Telephone (+41 55) 4154400
Fax (+41 55) 4154415
UNITED KINGDOM Worthing
Eurotherm Limited
CONTROLS &
DATA MANAGEMENT
Telephone (+44 1903) 695888
Fax (+44 1903) 695666
PROCESS AUTOMATION
Telephone (+44 1903) 205277
Fax (+44 1903) 236465
U.S.A Leesburg
Eurotherm Inc.
Telephone (+1 703) 443 0000
Fax (+1 703) 669 1300
Web www.eurotherm.com
ED 36
http://www.eurotherm.co.uk
ENG
HA027987
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 CHAPTER 1 INSTALLATION
- 5 What Instrument Do I Have?
- 7 3504 and 3508 Ordering Code
- 9 How to Install the Controller
- 12 Electrical Connections
- 14 Standard Connections
- 19 Plug in I/O Module Connections
- 26 Digital Communications Connections
- 36 CHAPTER 2: OPERATION
- 36 QuickStart - New Controller (Unconfigured)
- 45 To Re-enter QuickStart Mode
- 46 Normal Operation
- 48 The Operator Buttons
- 50 To Set The Required Temperature (Setpoint)
- 51 To Select Manual Operation
- 52 Alarm Indication
- 54 Message Centre
- 63 Introduction to Configuration using iTools
- 66 Device panel
- 67 User Pages Editor
- 69 Recipe Editor in iTools
- 71 Program Editor
- 73 Graphical Wiring Editor
- 76 CHAPTER 3 SAFETY AND EMC INFORMATION
- 76 GENERAL
- 77 Service and repair
- 78 Installation Safety Requirements
- 81 Installation Requirements for EMC
- 82 CHAPTER 4 TECHNICAL SPECIFICATION
- 82 Control Options
- 82 Display
- 83 Standard Digital I/O
- 83 All Analogue and PV Inputs
- 84 PV Input
- 86 Analogue Input Module
- 87 Digital Input Modules
- 87 Digital Output Modules
- 87 Analogue Output Modules
- 87 Transmitter PSU
- 88 Transducer PSU
- 88 Potentiometer Input
- 88 Digital communications
- 88 Master communications
- 88 Alarms
- 88 User messages
- 89 Control functions
- 89 Setpoint programmer
- 89 I/O Expander
- 90 Advanced functions
- 91 General specification