User Guide 3500SERIES

Add to my manuals
94 Pages

advertisement

User Guide 3500SERIES | Manualzz

SERIES

ENG

User Guide

Contents

1.

2.

CHAPTER 1 INSTALLATION ........................................................................................................ 3

1.1

What Instrument Do I Have?...........................................................................................................................3

1.2

3504 and 3508 Ordering Code .........................................................................................................................5

1.3

How to Install the Controller ..........................................................................................................................7

1.4

Electrical Connections................................................................................................................................... 10

1.5

Standard Connections................................................................................................................................... 12

1.6

Plug in I/O Module Connections.................................................................................................................... 17

1.7

Digital Communications Connections ........................................................................................................... 24

CHAPTER 2: OPERATION ..........................................................................................................34

3.

2.1

QuickStart - New Controller (Unconfigured) ................................................................................................ 34

2.2

To Re-enter QuickStart Mode ....................................................................................................................... 43

2.3

Normal Operation......................................................................................................................................... 44

2.4

The Operator Buttons ................................................................................................................................... 46

2.5

To Set The Required Temperature (Setpoint) ............................................................................................... 48

2.6

To Select Manual Operation ......................................................................................................................... 49

2.7

Alarm Indication ........................................................................................................................................... 50

2.8

Message Centre............................................................................................................................................. 52

2.9

Introduction to Configuration using iTools................................................................................................... 61

2.10

Device panel ................................................................................................................................................. 64

2.11

User Pages Editor .......................................................................................................................................... 65

2.12

Recipe Editor in iTools .................................................................................................................................. 67

2.13

Program Editor.............................................................................................................................................. 69

2.14

Graphical Wiring Editor................................................................................................................................. 71

CHAPTER 3 SAFETY AND EMC INFORMATION...........................................................................74

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 1

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 2

4.

3.1

GENERAL......................................................................................................................................................74

3.2

Service and repair........................................................................................................................................75

3.3

Installation Safety Requirements.................................................................................................................76

3.4

Installation Requirements for EMC..............................................................................................................79

CHAPTER 4 TECHNICAL SPECIFICATION ..................................................................................80

4.1

Control Options...........................................................................................................................................80

4.2

Display.........................................................................................................................................................80

4.3

Standard Digital I/O.....................................................................................................................................81

4.4

All Analogue and PV Inputs .........................................................................................................................81

4.5

PV Input.......................................................................................................................................................82

4.6

Analogue Input Module ...............................................................................................................................84

4.7

Digital Input Modules ..................................................................................................................................85

4.8

Digital Output Modules ...............................................................................................................................85

4.9

Analogue Output Modules...........................................................................................................................85

4.10

Transmitter PSU ..........................................................................................................................................85

4.11

Transducer PSU ...........................................................................................................................................86

4.12

Potentiometer Input ....................................................................................................................................86

4.13

Digital communications...............................................................................................................................86

4.14

Master communications ..............................................................................................................................86

4.15

Alarms .........................................................................................................................................................86

4.16

User messages .............................................................................................................................................86

4.17

Control functions ........................................................................................................................................87

4.18

Setpoint programmer ..................................................................................................................................87

4.19

I/O Expander................................................................................................................................................87

4.20

Advanced functions .....................................................................................................................................88

4.21

General specification...................................................................................................................................89

3508 and 3504 Process Controllers

1. Chapter 1 Installation

1.1 What Instrument Do I Have?

Thank you for choosing this Controller.

The 3508 controller is supplied in the standard 1/8 DIN size

(48 x 96mm front panel). The 3504 controller is supplied in the standard ¼ DIN size (96 x 96mm front panel). They are intended for permanent installation, for indoor use only, in an electrical panel which encloses the rear housing, terminals and wiring on the back.

1.1.1 Contents of Package

3508 Controller 3504 Controller

When unpacking your controller please check that the following items have been included.

1.1.1.1 3508 or 3504 Controller Mounted in its Sleeve

The 3504 contains up to six plug-in hardware modules; the 3508 has up to three. Additionally digital communications modules can be fitted in two positions.

The modules provide an interface to a wide range of plant devices and those fitted are identified by an ordering code printed on a label fixed to the side of the instrument. Check this against the description of the code given in section

1.2 to ensure that you have the correct modules for your application. This code also defines the basic functionality of the instrument which may be:-

Label showing:-

Instrument

Order

Code

Controller only

Programmer and controller

Control type – Standard PID, valve positioner

Digital communications type

• Options

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 3

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 4

1.1.1.2 Panel Retaining Clips

Two clips are required to secure the instrument sleeve in the panel. These are supplied fitted to the sleeve.

1.1.1.3 Accessories Pack

For each input a 2.49Ohm resistor is supplied for mA measurement. This will need to be fitted across the respective input terminals

1.1.1.4 This User Guide

Issue 2 of this guide applies to instrument software version V1.10 and explains:-

How to install the controller

• Physical wiring to the plant devices

First switch on - ‘out of the box’.

• Principle of operation using the front panel buttons

Introduction to configuration through iTools PC software

Whenever the symbol

appears in this handbook it indicates a helpful hint

1.2 3504 and 3508 Ordering Code

Hardware Coding

Model

Number

Function Supply

Voltage

Number of Loops

Model Number

3504 3504 Standard

3508 3508 Standard

CC

F

Function

Controller only

Profibus controller

Loops

X Single Loop

Supply Voltage

VH 85-254Vac

VL 20-29Vac/dc

Application

XX Standard

ZC Zirconia

VP Dual Valve

Position

Application Programs Recipes Toolkits Colour

1

4

8

Programs

1 1 prog 20 segments

10 10 prog 50 segments

25 25 prog 100 segments

50 50 prog 200 segments

Recipes

1 recipe

4 recipes

8 recipes

Colour

G Eurotherm green

S Silver

XX

60

Toolkit Wires

Std 30 wires

60 wires

120 120 wires

250 250 wires

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 5

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 6

1.2.1 Input and Output Modules

IO Slot 1 IO Slot 2

Config Tools Instrument

Language

IO Slot 3 IO Slot 4

Manual Language

3504 only

IO Slot 5

Extended

Warranty

IO Slot 6 Comms H Comms J

Cal Certificate Custom Label Non-standard

XX

R4

IO Slots 1-3 (3508); 1-6 (3504)

None fitted

Change over relay

R2

RR

T2

2 pin relay

Dual relay

Triac

TK

TP

VU

MS

TT

D4

Dual triac

DC control

AM Analogue input (not slot 2 or

D6

TL

5)

DC retransmission

Triple logic input

Triple contact input

Triple logic output

Potentiometer input

24Vdc transmitter PSU

G3

LO

Transducer PSU 5 or 10Vdc

Isolated single logic output

XX

A2

Y2

F2

AE

YE

FE

ET

PB

DN

H Comms Slot

Not Fitted

232 Modbus

2-wire 485 Modbus

4-wire 485 Modbus

232 EI-Bisynch

2-wire 485 EI-Bisynch

4-wire 485 EI-Bisynch

Ethernet 10base

Profibus

Devicenet

XX

IT

Config Tools

None

Standard iTools

Instrument Language

ENG English

FRA French

GER German

SPA Spanish

Extended Warranty

WL005 Extended 5 year

Cal Certificate

XXXXX None

CAL1 Cert of conformity

CAL2

CAL3

Factory cal cert

Custom Cal Cert

XX

A2

Y2

F2

EX

J Comms Slot

Not Fitted

232 Modbus

2-wire 485 Modbus

4-wire 485 Modbus

IO Expander

Manuals Language

ENG English

FRA French

GER German

SPA Spanish

XXX None

Custom Labels

F1234 Special No

XXXXX None

Non-standard Option

EU1234 Special No

EC1234 Custom curve

EE1234 Custom config

ES1234 Cust software

Example 3504/VH/1/XX/10/4/60/G/TT/XX/XX/XX/XX/XX/Y2/XX/IT/ENG/ENG/WL003

3504 CONTROLLER, 85-264Vac, 10 programs, 4 recipes, 60 wires, dual triac output, 2-wire RS485 comms, iTools, English manual

1.3 How to Install the Controller

This instrument is intended for permanent installation, for indoor use only, and to be enclosed in an electrical panel.

Select a location where minimum vibrations are present and the ambient temperature is within 0 and 50 o

C (32 and

122 o

F).

The instrument can be mounted on a panel up to 15mm thick.

To assure IP65 and NEMA 4 front protection, use a panel with smooth surface texture.

Please read the safety information, at the end of this guide, before proceeding and refer to the EMC Booklet part number HA025464 for further information.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 7

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 8

1.3.1 Dimensions

96mm

(3.78in)

48mm

(1.89in)

Latching ears

96mm

(3.78in)

Panel retaining clips

Panel retaining clips

150mm (5.91in)

1.3.2 To Install the Controller

92 mm - 0.0 + 0.8

3.62 in -0.00, +0.03

45 mm - 0.0 + 0.6

1.77 in -0.00, +0.02

1. Prepare the panel cut-out to the size shown in the diagram

2. Insert the controller through the cutout.

3. Spring the panel retaining clips into place. Secure the controller in position by holding it level and pushing both retaining clips forward.

4. Peel off the protective cover from the display

92 mm -

0.0 + 0.8

3.62 in -

0.00, +0.03

3504

3508

1.3.2.2 Recommended Minimum Spacing

5. The recommended minimum spacing between controllers shown here should not be reduced to allow sufficient natural air flow

1.3.3 Unplugging the Controller

10mm (0.4 in)

38mm

(1.5 in)

(Not to scale)

The controller can be unplugged from its sleeve by easing the latching ears outwards and pulling it forward out of the sleeve. When plugging it back into its sleeve, ensure that the latching ears click back into place to maintain the IP65 sealing.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 9

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 10

3508

Live

Neutral

Ground

Logic I/O A

Logic I/O B

Logic I/O Com

Power

Supply

Digital

Inputs/

Outputs

Fixed Relay

(form C)

T/C RTD mV mA

Polarising Keys* One per module

PV input

3504

Live

Neutral

Ground

Logic I/O A

Logic I/O B

Logic I/O Com

Power

Supply

Digital

Input/Outputs

Fixed Relay

(form C)

PV input

T/C RTD mV mA

Polarising Keys * One per module

* Polarising Keys.

Polarising keys are intended to prevent modules which are not supported in this controller from being fitted into the controller. An example might be an unisolated module (coloured red) from a 2400 controller series. When pointing towards the top, as shown, the key prevents a controller, fitted with an unsupported module, from being plugged into a sleeve which has been previously wired for isolated modules. If an unisolated module is to be fitted, it is the users responsibility to ensure that it is safe to install the controller in the particular application. When this has been verified the polarising key may be adjusted with a screwdriver to point in the down direction.

The screw terminals accept wire sizes from 0.5 to 1.5 mm (16 to 22AWG). Hinged covers prevent hands or metal making accidental contact with live wires. The rear terminal screws should be tightened to 0.4Nm (3.5lb in).

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 11

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 12

VI

V+

V-

These are connections which are common to all instruments in the range.

1.5.1 PV Input (Measuring Input)

Notes:

1. Do not run input wires together with power cables

2. When shielded cable is used, it should be grounded at one point only

3. Any external components (such as zener barriers, etc) connected between sensor and input terminals may cause errors in measurement due to excessive and/or un-balanced line resistance or possible leakage currents

1.5.1.1 Thermocouple or Pyrometer Input

VI

Use the correct type of thermocouple compensating cable, preferably shielded, to extend wiring

V+

V-

T/C

RTD

For 2-wire this is a local link

The resistance of the three wires must be the same

The line resistance may cause errors if it is greater than 22

Note: the RTD wiring is not the same as 2400 series instruments. It is the same as 26/2700 series

1.5.1.3 Linear Input V, mV and High Impedance V

VI

V+

V-

+80mV

0 – 2V

0 – 10V mV range +40mV

or

+80mV

High level range 0 – 10V

High Impedance mid level range 0 – 2V

A line resistance for voltage inputs may cause measurement errors

1.5.1.4 Linear Input mA

VI

V+

V-

0 – 20mA

4- 20mA

Connect the supplied load resistor equal to 2.49

Ω for mA input

The resistor supplied is 1% accuracy 50ppm

A resistor 0.1% accuracy 15ppm resistor can be supplied as an orderable option

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 13

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 14

These terminals may be configured as logic inputs, contact inputs or logic outputs in any combination

.

It is possible to have one input and one output on either channel.

!

The Digital IO is not isolated from the PV input

LA

LB

Input 1

Input 2

Common

Voltage level logic inputs, 12V, 5-40mA

LC

1.5.2.2 Contact Closure Inputs

Active > 10.8V

Inactive < 7.3V

LA

LB

Input 1

Input 2

Common

Contact open > 1200 Ω

Contact closed < 480 Ω

LC

1.5.3 Digital (Logic) Outputs

LA

LB

LC

Output 1

Output 2

Common

The logic outputs are capable of driving SSR or thyristors up to 9mA, 18V

It is possible to parallel the two outputs to supply 18mA, 18V.

Note : The Digital IO terminals are not isolated from the PV.

1.5.4 Relay Output

AA

Relay rating, min: 1V, 1mAdc. Max: 264Vac 2A resistive

AB

Relay shown in de-energised state

AC

1.5.4.1 General Note About Inductive Loads

High voltage transients may occur when switching inductive loads such as some contactors or solenoid valves.

For this type of load it is recommended that a ‘snubber’ is connected across the contact of the relay switching the load. The snubber typically consists of a 15nF capacitor connected in series with a 100

resistor and will also prolong the life of the relay contacts.

!

When the relay contact is open and it is connected to a load, the snubber passes a current (typically 0.6mA at 110Vac and 1.2mA at 240Vac. It is the responsibility of the installer to ensure that this current does not hold on the power to an electrical load. If the load is of this type the snubber should not be connected.

See also section 1.7.9.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 15

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 16

1.5.5 Power Supply Connections

L

N

24

24

85 to 264Vac

50/60Hz

24V ac or dc

1. Before connecting the instrument to the power line, make sure that the line voltage corresponds to the description on the identification label

2. For supply connections use 16AWG or larger wires rated for at least 75 o

C

3. Use copper conductors only

4. For 24V the polarity is not important

5. It is the Users responsibility to provide an external fuse or circuit breaker.

For 24 V ac/dc fuse type T rated 4A 250V

For 85/265Vac fuse type T rated 1A 250V

Safety requirements for permanently connected equipment state:

• a switch or circuit breaker shall be included in the building installation

• it shall be in close proximity to the equipment and within easy reach of the operator

• it shall be marked as the disconnecting device for the equipment

Note: a single switch or circuit breaker can supply more than one instrument

1.6 Plug in I/O Module Connections

Plug in I/O modules can be fitted in three positions in the 3508 and six positions in 3504. The positions are marked

Module 1, 2, 3, 4, 5, 6. With the exception of the Analogue Input module, any other module listed in this section, can be fitted in any of these positions. To find out which modules are fitted check the ordering code printed on a label on the side of the instrument. If modules have been added, removed or changed it is recommended that this is recorded on the instrument code label.

The function of the connections varies depending on the type of module fitted in each position and this is shown below. All modules are isolated.

I/O Module Typical usage

H/W

Code

Connections and examples of use

Note: The order code and terminal number is pre-fixed by the module number.

Module 1 is connected to terminals 1A, 1B, 1C, 1D; module 2 to 2A, 2B, 2C, 2D, etc.

Relay (2 pin) and

Dual Relay

2A, 264Vac max

1mA 1V min

Heating, cooling, alarm, program event, valve raise, valve lower

R2 and

RR

Contactor

Relay

Panel lamp etc

Voltage supply

Contactor

Relay

Panel lamp etc

First relay

A

B

C

D

Second relay

(dual relay only)

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 17

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 18

I/O Module

Change Over

Relay

(2A, 264Vac max)

1mA 1V min

Triple Logic

Output

(18Vdc at

8mA max.)

Triac and Dual

Triac

(0.7A, 30 to

264Vac combined rating)

Typical usage

Heating, cooling, alarm, program event, valve raise, valve lower

Heating, cooling, program events

Heating, cooling, valve raise, valve lower

H/W

Code

R4

TP

T2 and TT

Connections and examples of use

SSR or thyristor unit

-

+

Contactor

Relay

Panel lamp etc

Voltage supply

Output A

Output B

Output C

Common

+

+

+

_

A

B

C

D

A

B

C +

D

Motorise d valve

Raise

Voltage supply

Lower

A

B

C

First triac

Note 1: Dual relay modules may be used in place of dual triac.

Note 2:-

The combined current rating for the two triacs must not exceed 0.7A.

Triple Logic

Input

Triple

Contact

Input

I/O Module

DC Control

(10Vdc,

20mA max)

DC Retransmission

(10Vdc,

20mA max)

Typical usage

Heating, cooling e.g. to a

4-20mA process actuator

Logging of

PV, SP, output power, etc.,

(0 to 10Vdc,

0 to 20mA)

Events e.g. Program

Run, Reset,

Hold

Events e.g. Program

Run, Reset,

Hold

H/W

Code

D4

D6

TL

TK

Actuator

0-20mA or

0-10Vdc

To other controllers

0-20mA or

0-10Vdc

Logic inputs

<5V OFF

>10.8V ON

Limits:

-3V, +30V

Input 1

Input 2

Input 3

Common

External

Switches or

Relays

Contact inputs

<100! ON

>28K! OFF

Connections and examples of use

A

B

A

B

Input 1

Input 2

Input 3

Common

+

-

+

-

A

B

C

D

A

B

C

D

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 19

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 20

I/O Module Typical usage

H/W

Code

Connections and examples of use

24V

Transmitter

Supply

(20mA)

To power an external transmitter

MS

Transmitter

+

-

A

B

+0.5V

A

Potentiomet er input

100 Ω to

15K

0V

B

C

D

Transducer

Transducer

Power

Supply

Configurable

5V or 10Vdc

Minimum load resistance

300

10Vdc power supply

Internal switch to connect Rcal

V+

V-

C

D

Input

A

B

C

D

+

-

Controller

V+

A

B

V-

Calibration resistor Rcal

This may be fitted either in the transducer or in the controller

Input if an analogue input module is used in the appropriate slot

Anologue

Input

(T/C & RTD)

Modules

1, 3, 4 & 6 only

(mV, V and mA)

I/O Module Typical usage

Second or third PV input

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04

H/W

Code

AM

Connections and examples of use

3-wire RTD

A

For 2-wire this is a local link

mV (""""40mV or """"80mV)

B

C

D

Voltage

-3 to 10V or –1.4 to 2V

Current 0 to 20mA

Or (4 to 20mA)

+ mVolt source

-

-

-

+

+

Current source

Thermocouple

Volt source

2.49

Ω resistor supplied

+

-

A

B

C

D

A

B

C

D

A

B

C

D

A

B

C

D

21

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 22

I/O Module

Anologue

Input

(T/C & RTD)

Modules

1, 3, 4 & 6

only

PV Input

Module

Modules

1, 3, 4 & 6

only

Typical usage

Zirconia

Probe

H/W

Code

AM

PV

Connections and examples of use

The temperature sensor of the zirconia probe can be connected to the Fixed PV input, terminals V+ and V-, or to an Analogue Input module, terminals C & D. The

Volt Source connected to an Analogue Input module, terminals A & D.

A

B

+

V+ or C

V- or D

Volt source

-

-

C

D

Fixed PV (or an Analogue Input

Module)

Analogue Input Module

1.6.2 Zirconia Probe Construction

Hot End

Zirconia

Sensor

Ceramic Insulator

Outer Electrode

Inner Electrode

Outer metallic shell of the probe

Screen

-

+

+

-

Zirc. mV

Thermocouple

1.6.3 Zirconia Probe Screening Connections

The zirconia sensor wires should be screened and connected to the outer shell of the probe if it is situated in an area of high interference.

+

A

B

Outer Electrode

Inner Electrode

Screen

Zirc. mV

+

-

+

Screened Cable

-

C

D

A

T.C.

-

+

B

C

-

D

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 23

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 24

1.7 Digital Communications Connections

Digital Communications modules can be fitted in two positions in both 3508 and 3504 controllers. The connections being available on HA to HF and JA to JF depending on the position in which the module is fitted. The two positions could be used, for example, to communicate with ‘iTools’ configuration package on one position, and to a PC running a supervisory package on the second position.

Communications protocols may be ModBus, EIBisynch, DeviceNet, Profibus or Ethernet.

Note:- In order to reduce the effects of RF interference the transmission line should be grounded at both ends of the screened cable. However, if such a course is taken care must be taken to ensure that differences in the earth potentials do not allow circulating currents to flow, as these can induce common mode signals in the data lines.

Where doubt exists it is recommended that the Screen (shield) be grounded at only one section of the network as shown in all of the following diagrams.

1.7.1

Modbus Slave (H or J Module) or EIBisynch

A further description of ModBus and EIBisynch communications is given in 2000 series Communications Handbook,

Part No. HA026230.

RS232 Connections

Com

Tx

Rx

Screen

Local Ground

HA or JA

HB or JB

HC 0r JC

HD or JD Common

HE or JE Rx

HF or JF Tx

RS232 Connections

RS485 2-Wire Connections

Com

Tx

Rx

Screen

Com

Rx

Tx

220 Ω termination resistor on last

Daisy Chain to further controllers controller in the line

HA or JA

HB or JB

220 Ω termination resistor

HC 0r JC

Com

RxA

RxB

TxA

TxB Twisted pairs

HD or JD Com

HE or JE Rx

HF or JF Tx

RS232/RS485 2-wire communications converter

RS422/RS485 4-Wire Connections

Com

Tx

Rx

Screen

Com

Tx

Rx

220 Ω termination resistor on last controller in the line

TxA

TxB

Com

RxA

RxB

RS232 to RS422/RS485

4-wire communications converter

220

Ω termination resistor

Daisy Chain to further controllers

Twisted pairs

HA or JA

HB or JB

HC 0r JC

HD or JD Common

HE or JE Rx

HF or JF Tx

The KD485 communications converter is recommended for interfacing to RS485. This unit is also used to buffer an

RS485 network when it is required to communicate with more than 32 instruments on the same bus, and may also be used to bridge 2-wire RS485 to 4-wire

RS422.

The 261 or KD485 communications converter is recommended for:

Interfacing 4-wire to 2-wire connections.

To buffer an RS422/485 network when more than 32 instruments on the same bus are required

To bridge 2-wire RS485 to 4wire RS422.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 25

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 26

!

A description of DeviceNet is given in the DeviceNet Communications Handbook Part No HA027506 which can be downloaded from www.eurotherm.co.uk

.

Terminal

Reference

CAN

Label

Color

Chip

Description

HA V+

HB CAN_H

Red DeviceNet network power positive terminal. Connect the red wire of the DeviceNet cable here. If the DeviceNet network does not supply the power, connect to the positive terminal of an external 11-25 Vdc power supply.

White DeviceNet CAN_H data bus terminal. Connect the white wire of the DeviceNet cable here.

HC SHIELD None

HD

HE

HF

CAN_L

V-

Blue

Black

Shield/Drain wire connection. Connect the DeviceNet cable shield here. To prevent ground loops, the DeviceNet network should be grounded in only one location.

DeviceNet CAN_L data bus terminal. Connect the blue wire of the DeviceNet cable here.

DeviceNet network power negative terminal. Connect the black wire of the DeviceNet cable here. If the DeviceNet network does not supply the power, connect to the negative terminal of an external 11-25 Vdc power supply.

Connect to instrument earth

Note: Power taps are recommended to connect the DC power supply to the DeviceNet trunk line. Power taps include:

A Schottky Diode to connect the power supply V+ and allows for multiple power supplies to be connected.

2 fuses or circuit breakers to protect the bus from excessive current which could damage the cable and connectors.

The earth connection, HF, to be connected to the main supply earth terminal.

1.7.3 Example Devicenet Wiring Diagram

5-Position COMBICOM

Red

V+ 5

CAN-H 4

Drain 3

Wht

Blu

CAN-L 2

V- 1

Blk

Card

Top

Diag

DB-9M

RDY RUN

NET MON

Typical Interface Card

(MASTER)

Network Supply

24Vdc ( +1%)

250mV p-p Ripple

V+

V-

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04

121! terminating resistor required fitted if not internally

2704 Controller

HA

V+

HB

HC

CAN-H

Drain

HD

HE

HF

CAN-L

V-

(SLAVE)

Address 11

L

N

E

2704 Controller

HA

V+

HB

HC

HD

CAN-H

Drain

CAN-L

HE

HF

V-

(SLAVE)

Address 12

L

N

E

2704 Controller

HA

V+

HB

HC

121! *

L

N

E

HD

HE

HF

V-

(SLAVE)

Address N+1

Daisy chain to further instruments

* Fit to last instrument in the chain

27

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 28

1.7.4 Profibus

A description of ProfiBus is given in the ProfiBus Communications Handbook Part No HA026290 which can be downloaded from www.eurotherm.co.uk

.

1.7.5 Example Profibus Wiring

Master

A B

Connections ‘daisy chained’ to other instruments

Twisted pairs

390 Ω

220

Last controller only requires terminating resistors

390 Ω

HA

HB

HC

Shield

VP (+5V)

HD Rx/Tx +ve

HE

HF

HA

HB

HC

HD

HE

HF

Rx/Tx -ve

Dig Grnd

Shield

VP (+5V)

Rx/Tx +ve

Rx/Tx -ve

Dig Grnd

1.7.6 Ethernet

When the controller is supplied with the Ethernet communications option a special cable assembly is also supplied.

This cable must be used since the magnetic coupling is contained within the RJ45 connector. It consists of an RJ45 connector (socket) and a termination assembly which must be connected to terminals HA to HF.

View of cable which may also be ordered separately as Part No

SUB3500/COMMS/EA

Activity and power on LED indicators

Cable connected to terminals HA to HF

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 29

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 30

1.7.7 I/O Expander (or Additional Digital Input)

An I/O expander (Model No 2000IO) can be used with 3500 series controllers to allow the number of I/O points to be increased by up to a further 20 digital inputs and 20 digital outputs. Data transfer is performed serially via a two wire interface module which is fitted in digital communications slot J.

JE

JF

3500 Controller

Data transfer

E1

E2

#

20 Inputs

IO Expander

20 Outputs

#

For details of the IO Expander refer to the Operating Instructions HA026893. The connections for this unit are reproduced below for convenience.

1.7.8 IO Expander Connections

Comms

E1

E2

Screen

Transmitter

PSU Out

+

-

Outputs

21 to 30

A

C

A

C

A

C

A

C

A

C

A

C

A

B

C

A

B

C

A

B

C

A

B

C

21

22

23

1

2

3

24

4

25

5

26

27

28

29

30

10

8

9

6

7

24

24

E

24V Supply ac or dc dc polarity not important

-

-

-

+

-

-

-

+

Digital Inputs

1 to 10

Outputs

21 to 30

Outputs

31 to 40

A

C

A

C

A

C

A

C

A

C

A

C

A

C

A

C

A

C

A

C

30

10

10 IO Expander Board

Additional IO Expander Board

31

37

11

32

12

33

13

34

14

35

15

36

16

17

38

18

39

40

19

20

-

+

-

+

-

-

-

+

-

+

-

-

-

Digital Inputs

1 to 10

Digital Inputs

11 to 20

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 31

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 32

1.7.9 Example Wiring Diagram

Controller fuse 2A type T

Line

Heater fuse

Neutral

Heater

Solid

State

Relay

(e.g.

TE10)

+

-

Snubber

Cooling or alarm relay

Please refer to the EMC Electromagnetic Compatibility Handbook Part No. HA025464 for details of good wiring practice. This can be downloaded from www.eurotherm.co.uk

.

1.7.10 Snubbers

Snubbers are used to prolong the life of relay contacts and to reduce interference when switching inductive devices such as contactors or solenoid valves. The fixed relay (terminals AA/AB/AC) is not fitted internally with a snubber and it is recommended that a snubber be fitted externally, as shown in the example wiring diagram. If the relay is used to switch a device with a high impedance input, no snubber is necessary.

All relay modules are fitted internally with a snubber since these are generally required to switch inductive devices.

However, snubbers pass 0.6mA at 110V and 1.2mA at 230Vac, which may be sufficient to hold on high impedance loads. If this type of device is used it will be necessary to remove the snubber from the circuit.

The snubber is removed from the relay module as follows:-

1. Unplug the controller from its sleeve

2. Remove the relay module

3. Use a screwdriver or similar tool to snap out the track. The view below shows the tracks in a Dual Relay Output module.

Break out tracks as required to disconnect the snubber

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 33

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 34

2. Chapter 2: Getting Started

A brief start up sequence consists of a self test in which all elements of the display are illuminated and the software version is shown. What happens next depends on one of two conditions;-

1. Power up out of the box – when the controller has no preset configuration and is switched on for the very first time it will start up in 'QuickStart mode. This is an intuitive tool for configuring the controller and is described in section 2.1 below.

2. The controller has been powered up previously and is already configured. In this case go to section 2.3.

2.1 Quick Start - New Controller (Unconfigured)

When the controller is switched on for the very first time it will display the 'Startup' screen shown below.

* Manual mode is always selected when in Quick Start mode because the controller resets to cold start when Quick Start is selected.

Controller Display 3504 3508

2.1.1 To Configure Parameters in Quick Start Mode

Press

▲ or

to select Quick Start Mode or Configuration Mode. ‘Config’ will allow you to enter full configuration mode, covered in detail in later sections of this handbook.

Press $ to scroll through the list of parameters

Edit the parameters using the

▲ or

▼ buttons

Each time $ button is pressed a new parameter will be presented

This is illustrated by the following example:- (The views shown are taken from the 3508 controller but the same information is included in the 3504).

Backscroll – to scroll back through parameters press and hold $ then press

▲ to go back through the list of parameters. You can also press and hold $ +

to go forward - this has the same effect as pressing $ alone.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 35

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 36

Example

Do This Display Additional Notes

1. From the Start view press

$ or

to change the ‘Units’

The first parameter to be configured is ‘Units’. It resides in the ‘PV Input List’ because it is associated with the process variable.

When the required choice is selected a brief blink of the display indicates that it has been accepted

3. A different parameter is selected each time

$ pressed.

is

4. Continue setting up the parameters presented until the ‘Finished’ view is displayed.

If you wish to scroll around the parameters again do not select Yes but continue to press

$

.

When you are satisfied with the selections select ‘Yes’.

The display will then show the ‘HOME’ display shown in section 2.3

5. If all parameters are set up as required press ▲ or

to ‘Yes’

The following table summarises all the parameters which can be set up by the above procedure.

2.1.2 Quick Start Parameters

Parameters shown in Bold are defaults.

Group

PV Input Units

Parameter

Used to select the engineering units for the

PV

PV Input Resolution

Used to select the required decimal point position for the PV

PV Input Range Type

Used to select the linearisation algorithm required and the input sensor.

PV Input Range High

Configures the maximum display range and SP limits

PV Input Range Low

Loop

Configures the minimum display range and SP limits

Control Channel 1

Sets the control type for channel 1 (normally Heat)

Loop Control Channel 2

Sets the control type for channel 2 (normally Cool)

Value

C, F, K

V. mV, A, mA, pH, mmHg, psi, Bar, mBar, %RH, %, mmWG, inWG, inWW, Ohms, PSIG, %O2, PPM,

%CO2, %CP, %/sec, mBar/Pa/T, sec, min, hrs, None

XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX

Thermocouple: J, K, L, R, B, N, T, S, PL2, C.

RTD: Pt100

Linear: 0-50mV, 0-5V, 1-5V, 0-10V, 2-10V, 0-

20mA, 4-20mA

Depends on Range type selected. Default 1200

Depends on Range type selected. Default 0

PID, VPU, VPB, Off, OnOff

PID, VPU, VPB, Off, OnOff

Always

Always

Always

Always

Always

Always

Always

Availability

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 37

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 38

Group Parameter

LgcIO LA Logic OP (or IP) function

The LA Logic I/O port can be an output or an input.

This parameter is used to select its function.

LgcIO LA Min OnTime

This applies to both LA and

LB inputs

Not Used, Chan 1, Chan 2, Alarm 1 to 8, Any

Alarm, New Alarm, ProgEvnt1 to 8, (outputs)

Auto Man, AlarmAck, ProgRun, ProgReset,

ProgHold (Inputs)

Auto

0.01 to 150.00

Value

[Note 1]

[Note 2]

Availability

Only appears if Control Channel

= VPB and the channel is allocated to the LA output

[Note 2]

LgcIO LB Logic OP (or IP) function

The LB Logic I/O port can be an output or an input.

This parameter is used to

Not Used

All parameters the same as LA I/O

Only appears if Control Channel

= VPB and the channel is allocated to the LB output

[Note 2]

RlyOP

AA select its function.

Relay function

This relay is always fitted.

Not Used, Chan 1, Chan 2, Alarm 1 to 8, Any

Alarm, New Alarm, ProgEvnt1 to 8

Always.

[Note 3]

Note 1) Parameters only appear if the function has been turned on, eg If ‘Control Channel 1’ = ‘Off’, ‘Chan 1’ does not appear in this list.

When a control channel is configured for valve positioning, LgcIO LA and LgcIO LB act as a complementary pair. If, for example,

Chan 1 is connected to LgcIO LA (valve raise) then LgcIO LB is automatically set to Chan 1 (valve lower). This ensures the valve is never raised and lowered simultaneously.

The same complementary behaviour also applies to dual output modules and channels A and C of triple output modules

Note 2) If any input function, for example Chan 1, is connected to another input it will not appear in this list

Note 3) For valve position control Chan 1 or Chan 2 will not appear in this list. Valve position outputs can only be dual outputs such as LA and LB or dual relay/triac output modules

Modules

The following parameters configure the plug in I/O modules. I/O Modules can be fitted in any available slot in the instrument (6 slots in 3504,

3 slots in 3508). The controller automatically displays parameters applicable to the module fitted - if no module is fitted in a slot then it does not appear in the list.

Each module can have up to three inputs or outputs. These are shown as A, B or C after the module number and this corresponds to the terminal numbers on the back of the instrument. If the I/O is single only A appears. If it is dual A and C appears if it is triple A, B and C appear.

Module type Parameter Value Availability

Change over relay (R4)

2 pin relay (R2)

Triac output (T2)

Relay (Triac) function

Not Used

All parameters the same as RlyOP AA

Always (if the module is fitted)

Dual Relay (RR)

Dual triac output (TT)

Single Logic Output (LO)

Triple Logic Output (TP)

DC Output (D4)

DC Retransmission (D6)

Relay (Triac) function

Not Used

All parameters the same as RlyOP AA

Relay function

Not Used

All parameters the same as RlyOP AA

Logic Out function Not Used

All parameters the same as RlyOP AA

Logic OP function

Not Used

All parameters the same as RlyOP AA

DC Output function

Not Used

Chan 1

Module fitted but not configured

Channel 1 control output

Chan 2

SP Retran

Channel 2 control output

Setpoint retransmission

PV Retran

ErrRtran

PwrRtran

Process variable retransmission

Error Retransmission

Power output retransmission

Always (if the module is fitted)

Always (if the module is fitted)

Always (if the module is fitted)

Always (if the module is fitted)

Always (if the module is fitted)

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 39

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 40

Module type Parameter Value Availability

Triple Logic Input (TL)

Triple Contact Input (TK)

Analogue Input (AM)

Range Type

Display High

Display Low

Logic Input function

Analogue IP function

0–5V, 1-5V, 1–10V, 2–10V, 0-29mA, 4-20mA

100.0

0

Not Used

Auto Man

AltSP Sel

AlarmAck

ProgRun

ProgReset

ProgHold

Not Used

Loop PV

Remote SP

RemOPH

RemOPL ch1VlvPos ch2VlvPos

Module fitted but not configured

Auto/manual

Alternative SP select

Alarm acknowledge

Programmer run

Programmer reset

Programmer hold

Module fitted but not configured

Loop process variable

Remote setpoint

Remote output power maximum

Remote output power minimum

To read valve position from feedback potentiometer

Range Type

Thermocouple: J, K, L, R, B, N, T, S, PL2, C.

RTD: Pt100

Linear: 0-50mV, 0-5V, 1-5V, 0-10V, 2-10V, 0-

20mA, 4-20mA

Potentiometer Input (VU) Pot Input function

Not Used

Module fitted but not configured

Loop PV

Remote SP

Loop process variable

Remote setpoint

A function can only be allocated to one input. eg if AlarmAck is configured on X*A it is not offered for the other inputs

* is the module number ch1VlvPos and ch2VlvPos only appear if the control channel

1 or control channel 2 is set to VPB.

Remote SP does not appear if the programmer option is supplied

Not shown if analogue

IP function not used

Ch1VlvPos/Ch2VlvPos only appear if the channel = VPB

Remote SP does not

Module type

Transducer Power Supply

(G3)

Transmitter power supply

(M5)

Parameter Value

RemOPH

RemOPL

Remote output power maximum

Remote output power minimum

Ch1VlvPos

Ch2VlvPos

Channel 1 valve position

Channel 1 valve position

TdcrPSU function

5 Volts

10 Volts

No parameters. Used to show the ID of the module if fitted

Availability

appear if the programmer option is supplied

Always (if the module is fitted)

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 41

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 42

Alarms

Group Parameter

Alarm 1 Type to 8

Alarm 1 to 8

Source

Setpoint

None

Abs High

Abs Low

Dev High

Dev Low

Dev Band

None

PV Input

Loop PV

ModX Ip

Value

No alarm type configured

Absolute high

Absolute low

Deviation high

Deviation low

Deviation band

Not connected

Connected to process variable

Connected to loop process variable for deviation alarms

Connected to a suitable module eg Analog IP (X = module number)

To adjust the alarm threshold within the range of the source.

Availability

Always

Always if Type ≠ None

PV Input and ModX Ip do not appear if Type

= Deviation

Always if Type ≠ None Alarm 1 to 8

Alarm 1 to 8

Latch

None

Auto

Manual

Event

No latching

Automatic latching see section 2.7.1

Manual latching see section 2.7.1

Alarm beacon does not light but any output associated with the event will activate and a scrolling message will appear.

Always if Type

None

Finished Exit

No

Yes

Continue back around the quick configuration list

Go to normal operation

2.2 To Re-enter Quick Start Mode

If you have exited from Quick Start mode (by selecting ‘Yes’ to the ‘Finished’ parameter) and you need to make further changes, the Quick start mode can be entered again at any time. The action which takes place depends on one of two previous conditions as follows:-

2.2.1 Power up After a Quick Start Configuration

1. Hold down then power up the controller. Keep this button pressed until the Quick start screen as shown in section 2.1 is displayed.

to enter the quick start list. You will then be asked to enter a passcode.

3. Use or

▼ to enter the passcode – default 4 – the same as the configuration level passcode. If an incorrect code is entered the display reverts to the ‘Quick Start’ view section 2.1.

It is then possible to repeat the quick configuration as described previously.

The Quick Start view shown in section 2.1 now contains an additional parameter - ‘Cancel’. This is now always available after a power up, and, if selected, will take you into normal operating mode, section 2.3.

2.2.2 Power up After A Full Configuration

Repeat 1,2 and 3 above.

Full configuration allows a greater number of parameters to be configured in a deeper level of access. This is described in the Engineering Handbook Part No. HA027988.

If the controller has been re-configured in this level, a ‘WARNING’ message, ‘Delete config?’ - ‘No’ or ‘Yes’, will be displayed. If ‘No’ is selected the display drops back to the ‘GoTo’ screen. or

▼ to select ‘Yes’ to confirm or ! the WARNING message). to cancel. (If no button is pressed for about 10 seconds the display returns to

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 43

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 44

If ‘Yes’ is selected the Quick start defaults will be re-instated. It is then necessary to reset all the Quick start parameters.

Switch on the controller. Following a brief self-test sequence, the controller will start up in AUTO mode and Operator

Level 1. This section describes the operation of the controller in this level.

AUTO is the normal closed loop temperature control mode which means that the output power is adjusted automatically by the controller in response to the measurement from the input sensor. In this mode the format of the display for a new instrument is shown below. It is called the HOME display.

Indicator beacons

(listed below)

Process Variable (PV)

Setpoint (SP)

Message display

Current level of access indication shown 3504 only

Lev1

Lev2

Lev3

3508 3504

2.3.1 Beacon Display and Description

OP1

SPX

ALM

Illuminates when output 1 is ON (normally heating)

OP2 Illuminates when output 2 is ON (normally cooling or alarm)

MAN

Illuminates when manual mode active

REM

Illuminates when remote setpoint active

Illuminates when alternative setpoint active

If an alarm occurs the red alarm beacon flashes. This is accompanied by a message showing the source of the alarm, for example ‘Boiler overheating’.

To acknowledge press

!

and

. The message disappears. If the alarm condition is still present the beacon lights continuously. When cleared it will extinguish. A full description of the alarm operation is given in section 2.7

RUN

HLD

J

H

IR

Illuminates when programmer running – flashing indicates End

Illuminates when programmer held

Flashes when J Channel comms active

Flashes when H Channel comms active

Flashes when infra red communications active

In general throughout this handbook instrument views will use the 3504. The displayed information is similar for the

3508 but in some cases is shortened due to display limitations.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 45

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 46

2.4 The Operator Buttons

A/MAN

This button can be disabled

PROG

RUN/HOLD

This button can be disabled

!

Page Scroll Lower Raise

Manual operation means that the controller output power is adjusted by the user. The input sensor is still connected and reading the PV but the control loop is open.

When pressed, this toggles between automatic and manual operation.

If the controller is in manual mode, ‘MAN’ light will be indicated

If the controller is powered down in Manual operation it will resume this mode when it is powered up again.

To select the programmer summary page

Press once to start a program. ‘RUN’ will be indicated

Press again to hold a program. ‘HLD’ will be indicated

Press and hold for at least two seconds to reset a program.

‘RUN’ will flash at the end of a program

‘HLD’ will flash during holdback

Programmer operation is fully described in chapter 21 of the Engineering Manual

Press to select new PAGE headings

$

Press to select a new parameter in the page

Press to decrease an analogue value, or to change the state of a digital value

Press to increase an analogue value, or to change the state of a digital value

2.4.1 Shortcut Key Presses

Backpage

Press and hold

(With

!

. Then press ! . The page headers scroll backward at each press. still pressed

you can press

to page forward. This action is the same as pressing

!

Backscroll alone).

Press and hold ▲

Press and hold

$

Press

! + $

when in a list. Then press

$

. Parameters scroll backward at each press. when in a list header. Then press.

. Parameters scroll forward at each press.

Jump to the

HOME display

Alarm

Ack/reset

Press

!

+

$ when the HOME screen is being displayed. All active alarms will be acknowledged

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 47

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 48

2.5 To Set The Required Temperature (Setpoint)

button.

WSP is the current Working

SetPoint.

When the

or

▲ button is pressed the mnemonic changes to the setpoint source, e.g. SP1

3504 View

Press and hold

▼ to lower the setpoint

Setpoint Value

Press and hold

▲ to raise the setpoint

3508 View

A momentary press of either button will show the setpoint in use eg SP1.

The new setpoint is accepted when the button is released and is indicated by a brief flash of the setpoint display

From the HOME display, press

or

2.6 To Select Manual Operation

3504 View 3508 View

Press button.

‘Man OP’ will be displayed on 3504

The ‘MAN’ beacon will be lit on both controllers

Press and hold

▼ to lower the output power

Upper display shows

Actual Temperature (or

Process Variable ‘PV’)

Lower display shows output power

Press and hold

▲ to raise the output power

The output power will change continuously while either of these buttons are pressed

If the controller is powered down in either Auto or Manual operation it will resume the same mode when it is powered up again.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 49

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 50

If an alarm occurs it is indicated as follows:-

The red alarm (ALM) beacon in the top left of the display flashes

Alarm number is indicated together with the flashing "

A default message or a pre-programmed message appears showing the source of the alarm

Invitation to acknowledge the new alarm

2.7.1 To Acknowledge an Alarm

Press ! and $ (Ack) together.

The action, which now takes place, will depend on the type of latching, which has been configured

Non Latched Alarms

If the alarm condition is present when the alarm is acknowledged, the alarm beacon will be continuously lit. This state will continue for as long as the alarm condition remains. When the alarm condition disappears the indication will also disappear.

If a relay has been attached to the alarm output, it will de-energise when the alarm condition occurs and remain in this condition until the alarm is acknowledged AND it is no longer present.

If the alarm condition disappears before it is acknowledged the alarm indication disappears as soon as the condition disappears.

Automatic Latched Alarms

The alarm continues to be active until both the alarm condition is removed AND the alarm is acknowledged. The acknowledgement can occur BEFORE the condition causing the alarm is removed.

Manual Latched Alarms

The alarm continues to be active until both the alarm condition is removed AND the alarm is acknowledged. The acknowledgement can only occur AFTER the condition causing the alarm is removed.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 51

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 52

The lower section of the HOME display contains an alpha-numeric set of messages. These messages change between different controller types and operating modes and are grouped in summary pages. The 3504 contains more information than the 3508, and generally the parameter descriptions are longer due to the larger display..

3504 3508

Press !

.

A set of pre-defined summary pages are shown at each press. These are typically a summary of programmer, loop and alarm operation. A further eight customised pages are also possible and these can be programmed off line using iTools programming software.

Loop Summary

The view opposite shows heat only.

For heat/cool the bar graph is bi-directional (+

100%) as shown below:-

For valve position control the user interface will display either heat only or heat/cool summary pages.

Press

At each press a new display will be shown

Programmer Summary

This display is only shown if the Programmer option has been enabled

Alarm Summary

Alarm Settings

All configured alarms will be listed

Control

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 53

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 54

2.8.2 How to Edit Parameters

In the above summary pages, press $ to scroll to further parameters (where applicable).

Press

or

to change the value of the parameter selected.

Any parameter preceded by v is alterable provided the system is in a safe state to allow the parameter to be changed.

For example, ‘Program Number’ cannot be changed if the program is running - it must be in ‘Reset’ or ‘Hold’ mode. If an attempt is made to alter the parameter its value is momentarily replaced by ‘---‘ and no value is entered.

Some parameters are protected under a higher level of security – Level 2. In these cases it will be necessary to select

‘Access Level 2’. This is carried out as follows:-

1. Press and hold

!

until the display shows

to select Level 2

again to enter a security code. This is defaulted to 2. If an incorrect code is entered the display reverts to that shown in 1 above. If the default of 2 is not accepted this means that the code has been changed on your particular controller. It will be necessary to refer to the Engineering Handbook.

4. ‘Pass’ is displayed momentarily. You are now in Level 2.

2.8.3 Programmer Summary Page

Provided it has been ordered and enabled the 3500 series controllers can program the rate of change of setpoint. Up to 50 programs and up to a maximum of 200 segments in total, can be stored and run. Chapter 21 explains setpoint programming in more detail.

2.8.3.1 To Select a Parameter

Press

$ to scroll through a list of parameters. On the ‘Programmer Summary’ shown here, the list of parameters which can be selected are:-

Value Default Available in Level Parameter

Name

Program

Parameter Description

Program number (and name if this has been configured)

Segment Segment number (and type on 3504)

Only appears when the programmer is running

Seg Time Left Segment Time Left

Only appears when the programmer is running

1 to max number of programs

1 to max number of segments

1 L1 Alterable when prog in reset

1 L1 only

L1

PSP Profile setpoint value

Run

Hold

Holdback

Prog running

Prog held

In holdback

Can be changed in Hold L1

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 55

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 56

Parameter

Name

Cycles Left

Advance

SkipSeg

Fast Run

Events or

Rst Events

Prg. TimeLeft

Parameter Description

Number of repeat cycles left to run

Can only be changed in Hold or Reset

Sets the program setpoint equal to the target setpoint and moves to the next segment.

Only operates when the programmer is running (not in Hold)

Moves immediately to the next segment and starts from the current setpoint value.

Only operates when the programmer is running (not in Hold)

This is only available in level 3 as described in later chapters. Set to ‘Yes’ and then run the program. The programmer will run through the segments at a fast rate. It is intended to be used only to test a new program and should not be used on an active process

State of the event outputs when the program is running or when in reset

1 to maximum number of cycles set

No

Yes

No

Yes

No

Yes

Value

This is a momentary action

This is a momentary action

Fast run disabled

Fast run enabled

Event inactive

Event active

Time remaining to end of selected program hrs:mins:secs

Default Available in Level

L1 R/O in Run

No L1

No L1

L3

L1

L1

2.8.3.2 To Select and Run a ProgramProfiBus

In this example it is assumed that the program to be run has already been entered. Setpoint programming is described in detail in Chapter 21 of the Engineering Handbook.

Do This The Display You Should See Additional Notes

1. From any display press

! until the ‘Programmer User

Display’ is shown

to ‘Program’ or

to choose the program number to be run

In this example Program Number 2 is chosen and has been given a user defined name.

In the 3504 Program names can be entered using the offline programming package ‘iTools’.

4. Press or select ‘Status’ and set this to ‘Run’

‘RUN’ is displayed in the indicator beacons section of the main display.

The view shown here shows current working setpoint, program being run, current segment number and time left to complete this segment.

5. To Hold a program press

6. To Reset a program press

for at least 3 seconds

Press again to continue the program.

When the program is complete ‘RUN’ will flash

‘RUN’ will extinguish and the controller will return to the HOME display.

An alternative way to run, hold or reset the program is to scroll to ‘Program Status’ using

$ select ‘Run’, ‘Hold’ or ‘Reset’ using ▲ or

and

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 57

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 58

2.8.4 Alarm Summary Page

This page shows a summary of all analogue alarms. Press $ to scroll through the alarms.

The diagram illustrates that an alarm is present in the system but that none of the alarms need acknowledgement.

A New Alarm occurs when any new alarm becomes active. This parameter may be used to activate a relay output to provide external audible or visual indication.

2.8.5 Alarms Setting Page

Up to eight analogue alarms can be configured. The alarm thresholds can be set in Level 2 in this page.

Press $ to scroll through the alarms.

Press

▲ or

to set the threshold values

Analogue alarm 1, configured as Absolute High and set to operate at 123.00

Analogue alarm 2, configured as Absolute Low and set to operate at -10.00

2.8.6 Control Summary Page

Parameters which define the way a control loop operates can be set in this page. Control parameters are further described in Chapter 20 of the Engineering handbook.

Press $ to scroll through a list of parameters.

Press

▲ or

to change the value of the selected parameter.

On the Control Summary page the following parameters are available:-

Parameter

Name

SP Select

SP1

SP2

SP Rate

Tune

(1)

Parameter Description

To select SP1 or SP2

To set the value of SP1

To set the value of SP2

To set the rate at which the setpoints change

To start self tuning

Value

Between range limits set in higher levels of access

PB

(1)

Ti

(1)

Td

(1)

R2G

(1)

CBH

(1)

CBL (1)

Output Hi

Output Lo

To set proportional band

To set integral time

To set derivative time

To set relative cool gain

To set cut back high

To set cut back low

To set a high limit on the control output

To set a low limit on the control output

Off

On

0 to 99999

Off to 99999

Off to 99999

0.1 to 10.0

Auto to 99999

Auto to 99999

-100.0 to 100.0%

-100.0 to 100.0%

Default

As order code

Off

100.0

0.0

Available in

Level

Lev1

Lev1

Lev1

Lev - alterable in

Lev2

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 59

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 60

Parameter

Name

Ch1 OnOff

Hyst

Ch2 OnOff

Hyst

Ch2 DeadB

Ch1 TravelT

Ch1 TravelT

Safe OP

Parameter Description

Channel 1 hysteresis (Only if configured for On/Off control)

Channel 2 hysteresis (Only if channel 2 is configured and for On/Off control)

Channel 2 deadband. To set the period in which there is no output from either channel. (This does not appear if channel 2 is not configured)

Motor travel time if valve control output on channel 1

Motor travel time if valve control output on channel 1

To set an output level under sensor break conditions

(1)

Does not appear if control is configured for On/Off parameters

Value

0.0 to 200.0

0.0 to 200.0

Off to 100.0

0.0 to 1000.0 seconds

0.0 to 1000.0 seconds

-100.0 to 100.0% 0.0

Default Available in

Level

Lev 1- alterable in

Lev2

2.9 Introduction to Configuration using iTools

iTools is a PC based configuration package which is used to configure instruments. The controller may be connected to the PC in three ways:-

1. Using an infra red clip (IR) attached to the front fascia. Set the parameter ‘IR Mode’ in the ‘Access’ list to ‘On’.

2. Using a configuration clip which plugs into the side of the controller

Both items are available from your supplier

3. Using a RS232, RS485 or RS422 digital communications interface connected to the H or J terminals

iTools provides:-

• Parameter Set up

Device Operation

• Device Recipe

Program Editing

• Configuration of User Pages

Graphical Wiring

• Cloning iTools and handbook part no HA026179 can be downloaded from www.eurotherm.co.uk.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 61

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 62

With the controller connected, press on the iTools menu bar. iTools will search the communications ports and TCPIP connections for recognisable instruments. Controllers connected with the configuration clip (CPI), will be found at address 255 regardless of the address configured in the controller.

2.9.2 Parameter Set Up

Allows parameters to be configured.

1. Press to get this view

2. Open up the parameter list by double clicking the required folder. Right click in the parameter list to reveal or hide columns.

3. To change the value of a parameter, double click the parameter and change its value using the pop-up window

4. The ‘Access’ button puts the controller into configuration mode. In this mode the controller can be set up without its outputs being active. Press ‘Access’ again to return to operating level.

5. The instrument view is optional. Select ‘Panel Views’ in the ‘View’ menu.

6. To find a parameter select the ‘Find’ tab.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 63

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 64

2.10 Device panel

Press for this feature.

T he Panel displays the active instrument panel. This can be used for remote viewing, diagnostics or Training. iTools can be used OFF-LINE to configure the product. The panel view gives an indication of how the instrument will appear when the configuration is downloaded.

The front panel control buttons, shown in the Device

Panel display, are active and clicking on them with the mouse will cause the display to behave as a real instrument.

Clicking on the Page button with Ctrl pressed emulates pressing the page and scroll buttons together.

2.11 User Pages Editor

Up to 8 User Pages with a total of 64 lines can be created and downloaded into the controller so that the controller display shows only the information which is of interest to the user.

Press to select this feature

Text entered here will be shown on the instrument display

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 65

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 66

2.11.1 To create a User Page

1. Press to select the page number 1 to 8

2. Drag and drop parameters from the browser to create the user parameter list

3. Choose the required style. The format is shown in the pop up window

4. Right click in the list to: a. Insert an item b. Remove an item c. Edit Wire. allows you to change the parameter selected d. Edit Text. Allows you to enter your own text for the parameter displayed e. Edit Style. This is shown in the pop up window f. Read Parameter Properties g. Open Parameter Help

5. Select the operator level at which the user page will be displayed

6. If a bar graph is displayed, set the low and high graph axes

The format of the user page is shown in the instrument view

The user page can now be saved and downloaded to the instrument.

2.12 Recipe Editor in iTools

Press for this feature. Up to 8 recipes can be stored. They can also be named by the user.

Recipes allow the operator to change the operating values of up to 24 parameters in an instrument for different batch items/processes by simply selecting a particular recipe to load. Recipes are important for reducing error in setup and they remove the need for operator instructions fixed to the panel next to the instrument.

The Recipe Editor is used during configuration to assign the required parameters and to set up the values to be loaded for each recipe.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 67

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 68

2.12.1.1 Recipe Menu Commands

Load Recipe

Save

Edit Parameter

Delete Parameter

Edit Parameter Value

Rename Parameter Tag

Parameter Properties

Copy Parameter

Paste Parameter

Columns

Load Access Level

Level1

Used to load a recipe file into the instrument

Used to save the current recipe configuration into a file

Used to assign a parameter to a Tag. Parameters can also be assigned by 'drag and drop' from the iTools parameter list

Used to delete an assigned parameter from the recipes

Used to edit the current value of the assigned parameter

Allows the user to rename the Tag of the associated parameter. This tag is used on the instrument to identify assigned parameters (default Value1 - Value24)

Used to find the properties and help information of the selected parameter

Used to copy the currently selected parameter

Used to assign a previously copied parameter to the selected Tag

Used to hide/show the Description and Comment Columns

Used to configure the lowest access level in which the selected recipe is allowed to load

Permitted to load when the instrument is in any of the access levels

Level2

Level3

Config

Permitted to load when the instrument is in Level2, Level3 or Config access levels

Permitted to load when the instrument is in Level3 or Config access levels

Permitted to load when the instrument is in the Config access level

Never

Never permitted to load

Note: Over comms, whilst the instrument is in operator mode, recipes that have been configured to load in Levels 1, 2 and 3 can be loaded. Whilst the instrument is in Config mode all recipes can be loaded.

Edit Data Set Value

Used to edit the value of the selected assigned parameter within the selected recipe. Values can also be edited via double left clicking the value itself

Clear Data Set Value

Rename Data Set

Used to clear the value of the selected assigned parameter within the selected recipe, thus disabling it from loading when the recipe is selected to load

Allows the user to rename the selected recipe. This name is used to identify individual recipes (default Set1 - Set8). Note:

Number of recipes dependent upon features

Clear Data Set

Used to clear all values in the selected recipe, thus disabling all from loading when the recipe is selected to load

Used to copy all of the assigned parameters current values into the selected recipe

Snapshot Values

Copy Data Set

Paste Data Set

Used to copy all values of the selected recipe

Used to paste all values of a previously copied recipe into the selected recipe

2.13 Program Editor

Setpoint programs can be created graphically, stored and downloaded into the controller.

2.13.1 Analog View

1. Press to edit the analog setpoints

2. Select a program number using

and enter a name for the program

4. Right click in the blank area and choose ‘Add

Segment’

5. Select ‘Segment Type’ from the drop down and enter the segment details

6. Repeat for all required segments

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 69

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 70

2.13.2 Event Outputs

1. Press to select the digital events view.

2. Right click in the blank area to ‘Add Segment’

3. Use the pull downs to turn the digital event On or Off in the selected segment

2.14 Graphical Wiring Editor

Select parameter values.

(GWE) to view and edit instrument wiring. You can also add comments and monitor

1. Drag and drop required function blocks into the graphical wiring from the list in the left pane

2. Click on parameter to be wired from and drag the wire to the parameter to be wired to (do not hold mouse button down)

3. Right click to edit parameter values

4. Add comments and notes

5. Add monitor points

Download wiring

Click to view all parameters for an individual function block

Monitor

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 71

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 72

2.14.1 Function Block

A Function Block is an algorithm which may be wired to and from other function blocks to make a control strategy.

The Graphical Wiring Editor groups the instrument parameters into function blocks. Examples are: a control loop and a mathematical calculation.

Each function block has inputs and outputs. Any parameter may be wired from, but only parameters that are alterable may we wired to.

A function block includes any parameters that are needed to configure or operate the algorithm.

2.14.2 Wire

A wire transfers a value from one parameter to another. They are executed by the instrument once per control cycle.

Wires are made from an output of a function block to an input of a function block. It is possible to create a wiring loop, in this case there will be a single execution cycle delay at some point in the loop. This point is shown on by a || symbol and it is possible to choose where that delay will occur.

Dotted lines around a function block show that it requires downloading.

2.14.3 Using Function Blocks

If a function block is not faded in the tree then it can be dragged onto the diagram.

The block can be dragged around the diagram using the mouse.

A labelled loop block is shown here. The label at the top is the name of the block.

When the block type information is alterable click on the box with the arrow in it on the right to edit that value.

The inputs and outputs which are considered to be of most use are always shown.

In most cases all of these will need to be wired up for the block to perform a useful task. There are exceptions to this and the loop is one of those exceptions.

If you wish to wire from a parameter which is not shown as a recommended output click on the icon in the bottom right and a full list of parameters in the block will be shown, click on one of these to start a wire.

To start a wire from a recommended output just click on it.

Click ‘Select Output’ to wire new parameters

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 73

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 74

3. Chapter 3 Safety and EMC Information

This controller is manufactured in the UK by Eurotherm Ltd.

Please read this section carefully before installing the controller

This controller is intended for industrial temperature and process control applications when it will meet the requirements of the European Directives on Safety and EMC. Use in other applications, or failure to observe the installation instructions of this handbook may impair safety or EMC. The installer must ensure the safety and EMC of any particular installation.

3.1 GENERAL

The information contained in this manual is subject to change without notice. While every effort has been made to ensure the accuracy of the information, your supplier shall not be held liable for errors contained herein.

3.1.1 Safety

This controller complies with the European Low Voltage Directive 73/23/EEC, by the application of the safety standard

EN 61010.

This controller conforms with the essential protection requirements of the EMC Directive 89/336/EEC, by the application of appropriate product specific international standards . This instrument satisfies the general requirements of the industrial environment defined in EN 61326. For more information on product compliance refer to the

Technical Construction File.

3.1.3 Unpacking and storage

The packaging should contain an instrument mounted in its sleeve, two mounting brackets for panel installation and an

Installation & Operating guide. Certain ranges are supplied with an input adapter.

If on receipt, the packaging or the instrument are damaged, do not install the product but contact your supplier. If the instrument is to be stored before use, protect from humidity and dust in an ambient temperature range of -10 o

C to +70 o

C.

3.2 Service and repair

This controller has no user serviceable parts. Contact your supplier for repair.

3.2.1 Caution: Charged capacitors

Before removing an instrument from its sleeve, disconnect the supply and wait at least two minutes to allow capacitors to discharge. It may be convenient to partially withdraw the instrument from the sleeve, then pause before completing the removal. In any case, avoid touching the exposed electronics of an instrument when withdrawing it from the sleeve.

Failure to observe these precautions may cause damage to components of the instrument or some discomfort to the user.

3.2.2 Electrostatic discharge precautions

When the controller is removed from its sleeve, some of the exposed electronic components are vulnerable to damage by electrostatic discharge from someone handling the controller. To avoid this, before handling the unplugged controller discharge yourself to ground.

3.2.3 Cleaning

Do not use water or water based products to clean labels or they will become illegible. Isopropyl alcohol may be used to clean labels. A mild soap solution may be used to clean other exterior surfaces of the product.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 75

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 76

3.3 Installation Safety Requirements

Various symbols are used on the instrument, they have the following meaning:

!

3.3.2 Personnel

Installation must only be carried out by suitably qualified personnel.

3.3.3 Enclosure of live parts

To prevent hands or metal tools touching parts that may be electrically live, the controller must be installed in an enclosure.

3.3.4 Caution: Live sensors

The controller is designed to operate with the temperature sensor connected directly to an electrical heating element.

However you must ensure that service personnel do not touch connections to these inputs while they are live. With a live sensor, all cables, connectors and switches for connecting the sensor must be mains rated.

The logic IO is not isolated from the PV inputs.

3.3.5 Wiring

It is important to connect the controller in accordance with the wiring data given in this guide. Take particular care not to connect AC supplies to the low voltage sensor input or other low level inputs and outputs. Only use copper conductors for connections (except thermocouple inputs) and ensure that the wiring of installations comply with all local wiring regulations. For example in the UK use the latest version of the IEE wiring regulations, (BS7671). In the

USA use NEC Class 1 wiring methods.

The installation must include a power isolating switch or circuit breaker. The device should be mounted in close proximity to the controller, within easy reach of the operator and marked as the disconnecting device for the instrument.

The power supply to the system should be fused appropriately to protect the cabling to the units.

The maximum continuous voltage applied between any of the following terminals must not exceed 264Vac:

• relay output to logic, dc or sensor connections;

• any connection to ground.

The controller must not be wired to a three phase supply with an unearthed star connection. Under fault conditions such a supply could rise above 264Vac with respect to ground and the product would not be safe.

Electrically conductive pollution must be excluded from the cabinet in which the controller is mounted. For example, carbon dust is a form of electrically conductive pollution. To secure a suitable atmosphere, install an air filter to the air intake of the cabinet. Where condensation is likely, for example at low temperatures, include a thermostatically controlled heater in the cabinet.

This product has been designed to conform to BSEN61010 installation category II, pollution degree 2. These are defined as follows:-

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 77

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 78

3.3.10 Installation Category II

The rated impulse voltage for equipment on nominal 230V supply is 2500V.

3.3.10.1 Pollution Degree 2

Normally only non conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected.

3.3.11 Grounding of the temperature sensor shield

In some installations it is common practice to replace the temperature sensor while the controller is still powered up.

Under these conditions, as additional protection against electric shock, we recommend that the shield of the temperature sensor is grounded. Do not rely on grounding through the framework of the machine.

3.3.12 Over-Temperature Protection

When designing any control system it is essential to consider what will happen if any part of the system should fail. In temperature control applications the primary danger is that the heating will remain constantly on. Apart from spoiling the product, this could damage any process machinery being controlled, or even cause a fire.

Reasons why the heating might remain constantly on include:

• the temperature sensor becoming detached from the process

• thermocouple wiring becoming short circuit;

• the controller failing with its heating output constantly on

• an external valve or contactor sticking in the heating condition

• the controller setpoint set too high.

Where damage or injury is possible, we recommend fitting a separate over-temperature protection unit, with an independent temperature sensor, which will isolate the heating circuit.

Please note that the alarm relays within the controller will not give protection under all failure conditions.

3.4 Installation Requirements for EMC

To ensure compliance with the European EMC directive certain installation precautions are necessary as follows:

For general guidance refer to EMC Installation Guide, HA025464.

• When using relay outputs it may be necessary to fit a filter suitable for suppressing the conducted emissions. The filter requirements will depend on the type of load. For typical applications we recommend Schaffner FN321 or

FN612.

• If the unit is used in table top equipment which is plugged into a standard power socket, then it is likely that compliance to the commercial and light industrial emissions standard is required. In this case to meet the conducted emissions requirement, a suitable mains filter should be installed. We recommend Schaffner types

FN321 and FN612.

3.4.1 Routing of wires

To minimise the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power cables. Where it is impractical to do this, use shielded cables with the shield grounded at both ends. In general keep cable lengths to a minimum.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 79

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 80

4. Chapter 4 Technical Specification

All figures quoted at an ambient temperature from 0 to 50 o

C unless otherwise stated.

No. of Loops

Control Loops

Control Outputs

1

On/Off, single PID

Analogue, Time proportioned or

Motorised Valve control with or without feedback.

Cooling Algorithms Linear, Water, Fan, Oil

Auto/Manual Control Bumpless transfer or forced manual output.

Setpoint rate Limit

Motorised Valve

Off to 9999.9 engineering units per minute

Valve Position bounded or unbounded. Individual

Control

Tuning

Loop Alarms

Application Specific

Valve Positions for heat and cool

One-shot Auto tune or Manual.

High absolute, Low absolute, Deviation high, Deviation low, Deviation band,

All with separate hysteresis.

Humidity control

4.2 Display

3504

3508

Technology

Primary Large 5 digit display, Information centre 16 character header and 3 lines of 20 characters

Primary Large 41/2 digit display,

Information centre 8 character header and 3 lines of 10 characters

LCD with yellow/green backlight

Red alarm beacon

4.3 Standard Digital I/O

Allocation

Digital inputs

Digital outputs

Changeover relay

2 Off. Not isolated from each other. Not isolated from the PV inputs

Logic Bi-directional input/outputs

Logic or Contact closure input

Voltage level: input Inactive 0 to 7.3Vdc, Active 10.8V to 24Vdc

Contact closure: input active <480ohms, inactive >1200ohms

18Vdc at 9 to 15mA drive capability.

Contact rating

Min Load 1mA at 1V

Max Load 2A at 264Vac resistive

1,000,000 operations with addition of external snubber

4.4 All Analogue and PV Inputs

Sample rate

Input filtering

User calibration

9Hz (110msec.)

OFF to 999.9 seconds of filter time constant (f.t.c.). Default setting is 1.6 seconds

Both the user calibration and a transducer scaling can be applied.

Sensor break

Ranges a.c. sensor break on each input (i.e. fast responding and no dc errors with high impedance sources). mV, mA, volts -2V to +10V, -1V to +2V or RTD (pt100), pyrometer inputs

Thermocouple types Most linearisations including K, J, T, R, B, S, N, L, PII, C, D, E with linearisation error < ±0.2°C

CJC: Automatic (internal), external, 0 o

C, 45 o

C, 50 o

C reference blocks

General Resolution (noise free) is quoted as a typical figure with f.t.c. set to the default value = 1.6 second.

Resolution generally improves by a factor of two with every quadrupling of f.t.c.

Calibration is quoted as offset error + percentage error of absolute reading at ambient temperature of 25 O C

Drift is quoted as extra offset and absolute reading errors per degree of ambient change from 25

O

C.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 81

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 82

Sample rate

Input filter

40mV Range

80mV Range

2V Range

9Hz

Off, 0.2s to 60s filter time constant. Default setting 1.6s.

Range -40mV to +40mV

Resolution 1.9

µ V (unfiltered)

Measurement noise

Linearity error

Calibration error

Temperature coefficient ± 0.2

µ V/C ± 28ppm/C of measurement, from 25C ambient.

Input leakage current

Input resistance

Range

1.0

µ

V peak to peak with 1.6s input filter.

0.003% (best fit straight line)

±

4.6

µ

V

±

0.053% of measurement, at 25C ambient.

±

14nA

100M Ω

-80mV to +80mV

Resolution 3.2

µ V

Measurement noise

Linearity error

3.3

µ

V peak to peak with 1.6s input filter.

0.003% (best fit straight line)

Calibration error ± 7.5

µ V ± 0.052% of measurement, at 25C ambient.

Temperature coefficient ± 0.2

µ V/C ± 28ppm/C of measurement, from 25C ambient.

Input leakage current

Input resistance

± 14nA

100M

Range -1.4V to +2.0V

Resolution 82

µ

V

Measurement noise

Linearity error

90 µ V peak to peak with 1.6s input filter.

0.015% (best fit straight line)

Calibration error ± 420 µ V ± 0.044% of measurement, at 25C ambient.

Temperature coefficient

±

125

µ

V/C

±

28ppm/C of measurement, from 25C ambient.

Input leakage current ± 14nA

10V Range

PT100

Thermocouple

Input resistance

Range

100M Ω

-3.0V to +10V

Resolution 500 µ V

Measurement noise

Linearity error

550

µ

V peak to peak with 1.6s input filter.

0.007% for zero source resistance (best fit straight line)

Calibration error

Add 0.003% for each 10

of source + lead resistance.

± 1.5mV ± 0.063% of measurement, at 25C ambient.

Temperature coefficient

±

66

µ

V/C

±

60ppm/C of measurement, from 25C ambient.

Input resistance

Range

62.5k

Ω to 667k Ω depending on input voltage.

400

(-200C to +850C)

Resolution 50mC

Measurement noise

Linearity error

50mC peak to peak with 1.6s input filter.

0.033% (best fit straight line)

Calibration error ± 310mC ± 0.023% of measurement in C, at 25C ambient.

Temperature coefficient

±

10mC/C

±

25ppm/C of measurement in C, from 25C ambient.

Lead Resistance

Bulb current

0 Ω

200

to 22

µ

A

Ω , matched lead resistances.

Uses 40mV and 80mV ranges.

Types J, K, L, R, B, N, T, S, PL2 and C.

Linearisation error

External Cold Junction

± 0.2C

Internal Cold Junction

Calibration

±

1.0C at 25C ambient.

Ambient rejection ratio 40:1 from 25C ambient.

0C, 45C and 50C.

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 83

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 84

4.6 Analogue Input Module

mV input

0 - 2Vdc input

0 - 10Vdc input

Pt100 input

Thermocouple

100mV range - used for thermocouple, linear mV source, or 0-20mA with 2.49

external burden resistor.

Calibration: + 10 µ V + 0.2% of reading

Resolution: 6 µ V

Drift: < + 0.2

µ V + 0.004% of reading per

O

C

Input impedance: >10M

, Leakage: <10nA

-0.2V to +2.0V range - used for zirconia.

Calibration: + 2mV + 0.2% of reading

Resolution: 30 µ V

Drift: < + 0.1mV + 0.004% of reading per

O

C

Input impedance: >10M Ω , Leakage: <20nA

-3V to +10.0V range - used for voltage input.

Calibration: + 2mV + 0.2% of reading

Resolution: 200

µ

V

Drift: < + 0.1mV + 0.02% of reading per

O

C

Input impedance: >69K Ω

0 to 400ohms (-200°C to +850°C), 3 matched wires - up to 22! in each lead without errors.

Calibration: ±(0.4°C + 0.15% of reading in °C)

Resolution: 0.08°C

Drift: < ±(0.015°C + 0.005% of reading in °C) per °C

Bulb current: 0.3mA.

Internal compensation: CJC rejection ratio >25:1 typical.

CJ Temperature calibration error at 25

O

C: <± 2°C

0°C, 45°C and 50°C external compensation available.

4.7 Digital Input Modules

Module type

Contact closure

Logic inputs

Triple contact input, Triple logic input

Active <100ohms, inactive >28kohms

Current sinking : active 10.8Vdc to 30Vdc at 2.5mA inactive -3 to 5Vdc at <-0.4mA

4.8 Digital Output Modules

Module types

Relay rating

Single Logic drive

Triple logic drive

Triac rating

Single relay, dual relay, single triac, dual triac, triple logic module (isolated)

2A, 264Vac resistive (100mA, 12V minimum)

12Vdc at 24mA

12V at 9mA per output

0.75A, 264Vac resistive

4.9 Analogue Output Modules

Module types

Range

Resolution

1 channel DC control, 1 channel DC retransmission (5 max.)

0-20mA, 0-10Vdc

1 part in 10,000 (2,000-noise free) 0.5% accurate for retransmission

1 part in 10,000 2.5% accurate for control

4.10 Transmitter PSU

Transmitter 24Vdc at 20mA

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 85

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 86

4.11 Transducer PSU

Bridge voltage

Bridge resistance

Software selectable 5 or 10Vdc

300 Ω to 15K Ω

Internal shunt resistor 30.1K

Ω at 0.25%, used for calibration of 350 Ω bridge at 80%

4.12 Potentiometer Input

Pot resistance 330 Ω to 15K Ω , excitation of 0.5 volts

4.13 Digital communications

Allocation

Modbus

Profibus DP

2 modules fitted in slots H & J (isolated)

RS232, 2 wire or 4 wire RS485, max baud 19.2KB in H module & 9.6KB in J module

High Speed, RS485, 1.5Mbaud (Slot H only)

4.14 Master communications

Allocation

Modbus

Parameters

Slot J

RS485 4-wire or RS232

25 read/write

4.15 Alarms

No of Alarms

Alarm types

Modes

4.16 User messages

8 Analogue, 8 digital. Can be wired to any internal parameter

Full scale, deviation, sensor break plus application specific

Latching or non-latching, blocking, time delay

No of messages

Format

Maximum 100, triggered by operator or alarm or used for custom parameter names

Up to 16 characters

4.17 Control functions

No of loops

Modes

Cooling algorithms

PID sets

Manual mode

Setpoint rate limit

One

On/off, PID, motorised valve with or without feedback

Linear, water, oil or fan

3 per loop

Bumpless transfer or forced manual output, manual tracking available

Display units per second, minute or hour

4.18 Setpoint programmer

Programmer modes

Programmer types

No of programs

No of segments

Event outputs

Synchronous

Time to Target or Ramp Rate

A maximum of 50 programs. Programs can be given user defined 16 character names

200 segments total or 50 maximum per program

Up to 8, can be assigned individually to segments or called as part of an event group

4.19 I/O Expander

10 I/O version

20 I/O version

4 changeover relays, 6 normally open relay contacts, 10 logic inputs

4 changeover relays, 16 normally open relay contacts, 20 logic inputs

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 87

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 88

4.20 Advanced functions

Timers

Totalisers

Counters

Real time clock

Application blocks

Software Tools

4, On Pulse, Off delay, one shot and min-On

2, trigger level & reset input

2, up or down counters

Day of week and time

24 digital operations

24 analogue operations

2 eight input logic operators, 2 eight input analogue operators

16 user values

BCD input

Customised input linearisations

Mathematical Add, Subtract, Multiply, Divide, Constant, Absolute difference, Maximum, Minimum,

Sample and Hold, Input 1 to the power of input 2, Square root, Log(10), Ln, 10 to the power of input 1, i.e. to the power of input 1

Logical AND, OR, XOR, Latch, Equal, Not Equal, Greater than, Less than, Greater than or equal to, Less than or equal to.

Humidity Wet and dry bulb technique iTools Configuration Tool

OPC Scope Trending and Data logging iClone Lite Lightweight configuration cloning

Graphical Wiring Editor Drag and drop wiring tool, self-documenting

View Builder Custom Animation Screens iTools Wizard Question and Answer configuration screens

4.21 General specification

Supply

Inrush Current

Operating ambient

Storage temp

Panel sealing

Dimensions and weight

3504

3508

Electromagnetic compatibility

110 to 240Vac -15%, +10%. 48 to 62Hz. 20 watts max

85-264Vac

High Voltage controller – 30A duration 100µs

Low Voltage controller – 15A duration 100µs

0°C - 50°C (32

°F

to 131

°F)

and 5 to 95% RH non condensing

-10°C to +70°C ( 14°F to 158°F)

IP65, plug in from front panel

96H x 96W x 150D (mm) 0.6Kg

96H x 48W x 150D (mm) 0.4kG

EN61326-1 Suitable for domestic, commercial and light industrial as well as heavy industrial environments. ( Domestic/light industrial (Class B) emissions, Industrial (Class A) Environment immunity

emissions).

EN61010, installation category 2 (voltage transients must not exceed 2.5kV)

Not suitable for use above 2000m or in explosive or corrosive atmospheres

Safety standards

Atmospheres

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 89

3500 Series User Guide Part No HA027987 Issue 2.0 Apr-04 90

INTERNATIONAL SALES AND SERVICE

AUSTRALIA Sydney

Eurotherm Pty. Ltd.

Telephone (+61 2) 9838 0099

Fax (+61 2) 98389288

AUSTRIA Vienna

Eurotherm GmbH

Telephone (+43 1) 7987601

Fax (+43 1) 7987605

BELGIUM Moha&

LUXEMBURG Huy

Eurotherm S.A./N.V.

Telephone (+32 ) 85 274080

Fax (+32 ) 85 274081

BRAZIL Campinas-SP

Eurotherm Ltda.

Telephone (+55 19) 3237 3413

Fax (+55 19) 3234 7050

DENMARK Copenhagen

Eurotherm Danmark A/S

Telephone (+45 70) 234670

Fax (+45 70) 234660

FINLAND ABO

Eurotherm Finland

Telephone (+358) 22506030

Fax (+358) 22503201

FRANCE Lyon

Eurotherm Automation SA

Telephone (+33 478) 664500

Fax (+33 478) 352490

GERMANY Limburg

Eurotherm Deutschland GmbH

Telephone (+49 6431) 2980

Fax (+49 6431) 298119

Also regional offices

HONG KONG Aberdeen

Eurotherm Limited

Telephone (+852) 28733826

Fax (+852) 28700148

INDIA Chennai

Eurotherm India Limited

Telephone (+9144) 4961129

Fax (+9144) 4961831

IRELAND Dublin

Eurotherm Ireland Limited

Telephone (+353 01) 4691800

Fax (+353 01) 4691300

ITALY Como

Eurotherm S.r.l

Telephone (+39 031) 975111

Fax (+39 031) 977512

© Copyright Eurotherm Limited 2003

All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm Limited.

Every effort has been taken to ensure the accuracy of this specification. However in order to maintain our technological lead we are continuously improving our products which could, without notice, result in amendments or omissions to this specification.

KOREA Seoul

Eurotherm Korea Limited

Telephone (+82 31) 2868507

Fax (+82 31) 2878508

NETHERLANDS Alphen a/d Ryn

Eurotherm B.V.

Telephone (+31 172) 411752

Fax (+31 172) 417260

NORWAY Oslo

Eurotherm A/S

Telephone (+47 67) 592170

Fax (+47 67) 118301

SPAIN Madrid

Eurotherm España SA

Telephone (+34 91) 6616001

Fax (+34 91) 6619093

SWEDEN Malmo

Eurotherm AB

Telephone (+46 40) 384500

Fax (+46 40) 384545

SWITZERLAND Freienbach

Eurotherm Produkte (Schweiz) AG

Telephone (+41 55) 4154400

Fax (+41 55) 4154415

UNITED KINGDOM Worthing

Eurotherm Limited

CONTROLS &

DATA MANAGEMENT

Telephone (+44 1903) 695888

Fax (+44 1903) 695666

PROCESS AUTOMATION

Telephone (+44 1903) 205277

Fax (+44 1903) 236465

U.S.A Leesburg

Eurotherm Inc.

Telephone (+1 703) 443 0000

Fax (+1 703) 669 1300

Web www.eurotherm.com

ED 36

http://www.eurotherm.co.uk

ENG

HA027987

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals