ENDA EDT5411 TEMPERATURE CONTROLLER

ENDA EDT5411 TEMPERATURE CONTROLLER
ENVIRONMENTAL CONDITIONS
Please read this document carefully before using this product. The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the manual.
The company shall not be responsible for any damage or losses however caused, which
may be experienced as a result of the installation or use of this product.
Ambient/storage temperature 0 ... +50°C/-25 ... 70°C (without icing)
%80,up to 31°C decreasing linearly %50 at 40°C.
Relative humidity
According to En60529;
Front panel: IP65
Protection class
Rear panel : IP20
Max. 2000m
Height
ENDA EDT5411 TEMPERATURE CONTROLLER
Do not use the device in locations subject to corrosive and flammable gasses.
ELECTRICAL CHARACTERISTICS
Thank you for choosing ENDA EDT5411 temperature controller.
3
2
4
6
5
7
8
°F
*54x94mm sized.
*On-Off control.
*Relay output for cooling or heating control.
*Single NTC probe input.
*Offset value can be entered for NTC probe.
*Compressor protection parameters can be entered.
*In the case of probe failure,output state can be selected as on,
off or periodical running.
*Upper and lower limits of the setpoint can be adjusted.
*Defrosting duration and interval can be adjusted.
*6 different warning tones.
*Upper and lower limits of the alarm value can be adjusted
depending on the setpoint value.
*Temperature unit can be selected as °C or °F.
*External alarm can be given by using digital input.
*Defrosting can be started by using digital input.
*Parameter can be transferred by using “CALKEY” without
connecting the device to mains supply.
*Communication feature over RS485 ModBus protocol(optional).
*With Real Time Clock making defrost and energy-saving
feature(optional).
*CE marked according to European Norms.
9
°C
°C
ENDA
CAL
EDT5411
SET
EDT5411
10
Order Code: EDT5411-
11
12
13
1
14
15
17
16
2
18
3
4
2-Output
4-ModBus
3- RTC
R....... 8A relay output
P....... 20A relay output
RS.......ModBus (optional)
Real time clock (optional)
(Only valid for 8A relay output devices)
For EDT5411-X-P ; Relay: NO 277V AC,20A (for resistive load),
2hp 250V AC (for inductive load)
For EDT5411-X-R ; Without load 30.000.000 mechanical;
250V AC, 8A resistive load 100.000 electrical operation.
Life expectancy for relay
For EDT5411-X-P ; Without load 10.000.000 switching;
277V AC,20A (for resistive load) 100.000 electrical operation.
CONTROL
Single set-point control
On-Off control
Adjustable between 1 ... 20.0°C.
HOUSING
Mounted to TH35 type rail that is in accordance with EN60715 standarts
W54xH94xD68mm
Approx. 190g (After packing)
Self extinguishing plastics.
While cleaning the device,solvents (thinner,benzine,acid etc.) or corrosive materials must not be used.
DIMENSIONS
EDT5411-230-P-RS
46
mm
DIGITAL THERMOSTAT
DIGITAL THERMOSTAT
8 680407 709892
8 680407 710058
230V AC +10% -20%
NTC
50/60Hz 5VA
230V AC +10% -20%
50/60Hz 5VA
NTC
ENDAKEY
A
GND
Made in Turkey
SN: XXXXXXXXX
DIG INP
COMPRESSOR
250V AC 20A
RESISTIVE LOAD
ENDAKEY
GND
COM
B
Made in Turkey
SN: XXXXXXXXX
GND
COM
B
A
GND
DIG INP
DLA4111
A
T5541
EN
C
T
ED
ED
T
SE
For mounting the device to the panel;
Push the device in direction 1 , the rails
provide the key to keeping the rail.
1 2 3 4 5 6 7 8 9
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
°F
68mm
ENDA INDUSTRIAL ELECTRONICS
EDT5411-230-R-RS
15 14 13 12 11 10
ENDA INDUSTRIAL ELECTRONICS
1 2 3 4 5 6 7 8 9
Holding screw
0.4-0.5Nm.
For EDT5411-X-R ; Relay: NO+NC 250V AC,8A (for resistive load),
1/2hp 240V AC (for inductive load)
Relay output
°C °C
15 14 13 12 11 10
Equipment is protected throughout by
DOUBLE INSULATION
OUTPUTS
Housing type
Dimensions
Weight
Enclosure material
ENDA EDT5411 is a rail mounted device. Make sure that the device is used only for intended purpose. The
electrical connections must be carried out by a qualified staff and must be according to the relevant locally
applicable regulations. During an installation, all of the cables that are connected to the device must be free
of electrical power. The device must be protected against inadmissible humidity, vibrations, severe soiling
and make sure that the operation temperature is not exceeded. The cables should not be close to the
power cables or components.
CONNECTION DIAGRAM
230V AC +%10 -%20, 50/60Hz or 12/24 V AC/DC ± %10
Max. 5VA
2.5mm² screw-terminal connections
-60.0 ... +150.0°C (-76.0 ... +302.0°F)
0.1°C (Can be chosen as 0.1ºC or 1ºC.)
±1°C
±%1
4 digits, 12.5mm, 7 segment LED
EN 61326-1: 2012
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
Control type
Control algorithm
Hysteresis
1 - Supply Voltage
110........110V AC
230........230V AC
24..........24V AC/DC
12..........12V AC/DC
SM.........9-30V DC/7-24V AC
Supply voltage
Power consumption
Connection
Scale
Sensitivity
Accuracy
Time accuracy
Display
EMC
Safety requirements
46,5mm
1
3
2
94
mm
1
NOTE:
SUPPLY:
184-253V AC
50/60Hz 4VA
10
Line
11
Neutral
Fuse
F 100 mA
250V AC
54
mm
For removing the device from rail;
Push the rail lock in direction 2 with a
screwdriver and pull the device in
direction 3.
Note:
Switch
230V AC
Supply
Fuse should
be connected Cable size: 1,5mm²
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Şerifali Mah. Barbaros Cad. No:18 Y.Dudullu 34775
ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
1/6
EDT5411-E-01-201409
1
3
2
4
5
6
7
8
9
°F
FAHRENHEIT LED: In parameter value or the measured temperature value “°F” unit while this
LED lights up.In the hidden menu,at the same time the user menu parameter is shown the LED lights up.
HEATING LED :Heating is being checked;while the output is active,the LED lights.
°F
°C
DEFROST LED : With the defrost lights up.
°C
COMPRESSOR LED: If compressor output is active,this LED lights up.While these compressor
delays expected,this LED flashes.
SET
ENDA
ENDA
EDT5411
SET
While in the operating mode set value,while in the programming mode shows selected
parameter’s value.
EDT5411
10
11
12
13
14
15
16
17
While in programming mode,provides the transition to the next parameter.If parameter is being
adjusted,it increases parameter’s value.Constantly holding this key,the parameter value rapidly
increases.
While in programming mode,provides the transiton to the previous parameter.If parameter is
being adjusted,it decreases parameter’s value.Constantly holding this key,the parameter value
rapidly decreases.
18
FRONT PANEL COMMANDS
1.Viewing and Changing The Set Value
-24.0
1000
Measurement
value
-30.0
SET
While in the running mode, if
SET
-29.9
-30.0
key is pressed, set value is displayed for 3 seconds.While in this case,the set value is changed with
keys.
2.Locking and Unlocking Keys
-24.0
1000
Measurement
value
Loc
Keys are locked.
SET
unl Keys are unlocked.
While in the operating mode,if
SET
SET
keys are pressed together among 2 seconds the Loc message is displayed and the keys are locked.If the keys are locked
keys are pressed for 2 seconds again unL message is displayed and key lock is opened and is returned to the normal way of working.While keys are locked,if
key is pressed ,the set value can be displayed but the value can not be changed. While the keys are locked,
SET
SET
key outside if a key is pressed the Loc message is seen.
3.Manuel Defrost Process
While in the operating mode,if
key is pressed for 2 seconds the defrost process is started as manual.If d.dur = 0 ,the manuel defrost will also be disabled.
4.Activating / Inactivating The Control Outputs
-24.0
1000
Measurement
value
When in the running mode,if
C.dIs
The control ouput becomes inactive.
C.enb
The control output becomes active.
key is pressed for 2 seconds, C.dIs message is displayed and control outputs becomes to the inactive position,the device works as
key is pressed for 2 seconds C.enB is disabled and the device continues to do control function.
the indicator. When the control outputs are disabled;if
5. Changing Parameter Values
Keys are pressed together for 2 seconds
name is displayed in the user menu.
is displayed and the user menu is entered,afterwards first parameter’s
While a parameter was selected,by pressing to SET key parameter’s value is displayed,the displayed this parametercan be changed with
keys.
When the parameter name is shown, no action is done after 3 seconds or to the SET key is pressing again to return to the parameter’s name. When the
parameter name is shown,
keys are pressed together immediately without waiting to get out of this process.
6. The Hidden Menu
Program mode
While in the user menu,if
key is pressed for 7 seconds the
message is displayed and is entered the
hidden menu. Then upl parameter is displayed. Selected the parameter’s value,by pressing the SET key is
displayed and with
keys can be changed. Parameter access and saving functions ,user menu is like. All
parameters can be accessed from this menu.
uPL
HYS
7. How can we to transfer parameter between menus?
If SET
keys are pressed together for 2 seconds;parameter is transferred to the user menu. In this way the user
menu up to 8 parameters can be transferred.In the user menu SET
keys are pressed together along the 2 seconds
the parameter is removed from the user menu.When a parameter is displayed in the user menu °F LED lights up in
the hidden menu. If the user menu have not any parameter np message is displayed.
uPL
C.Fos
ERROR MESSAGES
Pfa
Means, thermostat probe is broken.
PsC
Temperature value is higher than the scale.
Means,thermostat probe is short circuit.
Temperature value is lower than the scale.
ALARM SITUATION
1.When the alarm situation occured,the measured value flashes in the indicator and if “Snd” parameter is not “0” is given audible alarm by the device.
-24.0
1000
EA
SA
While there are a audible warning ;
key is pressed,the audible warning will be disabled.
2.External alarm is activated but output’s is not affected by this situation.
3.Except that the alarm has been activated and external alarm output relay is active when the show shut down. (off situation).
4.Buzzer voice warning is given;if any key is pressed the buzzer will be silenced.
HOW CAN WE RETURN THE DEVICE TO THE FACTORY SETTINGS
Key is held down while the device is powered up the d.PAr message will see and restore the factory parameters.
2/6
EDT5411-E-01-201409
OUTPUT GRAPHICS
Power
D.dPo
(Ifd.Pon = y
d.dPo timer
runs.)D.int
D.dur
Defrost
LED
HEAT
LED
HE
How Can We Dowload The Parameters From ENDAKEY To The Device?
(heating)
control
HEAT
OUTPUT
COMPRESSOR
LED
COMPRESSOR
OUTPUT
Read
button
Defrost
mode
While in the running mode;if
key or “Read” button (in ENDAKEY) are
pressed; is displayed “dL” message and parameters are read in ENDAKEY.
Co
(cooling)
C.Pon
“dL” message appears when the
key is pressed again,reading parameter
values from the ENDAKEY are transferred to the device.
If the parameter transfer is successful,”rEF”message is displayed and the
device begins to work with dowloaded parameters value.
The parameter in the ENDAKEY,while belonging to a different device of if there
is a malfunction in the ENDAKEY “Err” message is displayed and the
parameters of the device unchanged.
control
enable
A.uPl
A.uPl-A.HYS
SET+ r.HYS
SET
SET- r.HYS
A.LoL+A.HYS
A.LoL
A.dPo
disable
enable
disable
How Can We Upload The Parameters From Device To The ENDAKEY?
A.dFL
While in the running mode; if
key is pressed “uL” message is displayed
and again
key is pressed; if there is no error ,the parameters in the device
are loaded in to the ENDAKEY and “Suc” message is displayed.
If there is a malfunction in the device and the installation failed “Err” message
is displayed.
Temperature
alarm
Digital
input
ddi
digital input
delay
NOTE 1:To the device without energy,the parameter transfer is done with
ENDAKEY.
The battery inside the ENDAKEY for a longer period of time; after the parameter
transfer process,the connection between the ENDAKEY and the device should
be disconnected.
NOTE 2:ENDAKEY device,is supplied with orders if requested.
External alarm
situation
CONTROL PARAMETERS
uPL
LoL
HYS
oFF
The upper limit of the setpoint
The lower limit of the setpoint
Switch hysteresis for compressor (hysteresis)
The offset value for the refrigeration
MIN.
-60.0
LoL
0.1
MAX.
uPL
150.0
20.0
-20.0
20.0
UNIT
°C
°C
°C
°C
DEF. SET
150
-60
2
0
CONFIGURATION PARAMETERS
Unit
Control type selection( HE=(*) heating control is selected, Co= Cooling control is selected.)
C.tYp parameter as HE is selected,the defrost function of the device is disabled.
Temperature unit
°C
Dpnt
Decimal point (no= decimal point isn’t shown 22°C,YES=decimal point is shown 22.3°C.)
No
C.typ
Snd
d.inp
ddi
dpo
Type of buzzer sound (6 different voice types can be selected.Alarm during 0 is chosen,the voice warning is
canceled.)For Relay-8A is valid.
Digital input types. nd:Digital input unused. EA:External alarm. EA message flashes in the display.Output
unchanged. SA: Important external alarm. SA message flashes in the display.Relay output is turned off. HC:
Control type. Ctyp parameter is changed.( If HE = Co, If Co = HE ) df:Defrost operation is started .
Digital input delay. The period of the digital inputs to be active.
Digital input polarity.
cL = While a digital input contact is closed,it is activated.
oP= While a digital input is opened, it is activated.
Co
HE
Co
°F
°C
YES
No
0
6
nd
dF
nd
0:00
99:00
0:00
CL
oP
Cl
0
COMPRESSOR PROTECTION PARAMETERS
C.pon
Delay time for the compressor after power is on.
0:00
99:00 min:sec
1:00
C.FoS
C.PPn
C.PPF
Delay time required for the compressor to restart following a stop.
0:00
99:00 min:sec
1:00
On time for the compressor output in the case of probe failure.
Off time for the compressor output in the case of probe failure
0:00
0:00
99:00 min:sec
99:00 min:sec
0:00
1:00
DEFROST CONTROL PARAMETERS
D.dur
Defrost duration (If d.dur=0 , automatic and manual defrost are disabled.)
D.int
The time between 2 consecutive defrosts.
D.dSP
D.drE
D.Pon
D.dPo
0:00
1:00
During defrost,display configuration (rE= Real temperature is displayed during defrost.
(Lc= The temperature which is measured before defrost is displayed
during defrost.
Delay time for display real temperature after defrost is over.
Defrosting process begins with energy (no=Defrost process doesn’t start when,the energy comes.
YES=Defrost process starts when the energy comes.)
Delay time for defrosting after power is on.
Lc.
99:00 min:sec
1:00
99:00 hr:min
1:00
0:00 99:00
No
0:00
Lc.
RE
min:sec
No
YES
99:00
1:00
min:sec
1:00
ALARM CONTROL PARAMETERS
A.uPL
A.LoL
A.HYS
Limit for upper alarm level. When A.tYP is changed, AuPL should be readjusted.
Limit for lower alarm level. When A.tYP is changed, ALoL should be readjusted.
Switch hysteresis for alarm.
A.typ
Alarm configuration. (ABS=Absolute alarm.Alarm values are A.LoL and A.uPL .)
(rEF= Relative alarm.Alarm values are SET-A.LoL and SET+A.uPL.)
A.LoL
150.0
°C
150
-60.0
0.1
A.uPL
20.0
°C
°C
-60
2
AbS
rEF
AbS
NOTE: Upper and Lower alarm level variables are determined according to the “A.tYP” parameter.
If A.tYP = A.bS , A.LoL and A.uPL.
A.dFL
A.dPo
c.Sr
t.Sr
If A.tYP =rEF,LoL=SET-A.LoL and A.uPL.
Time delay to display alarm message after alarm is on.
Time delay to display alarm message after power is on.
0:00
0:00
Control state parameter
Keypad lock parameter
3/6
99:00 min:sec
hr:min
24:00
no
yes
no
yes
0:00
0:10
yes
no
EDT5411-E-01-201409
ENDA EDT5411 DIGITAL THERMOSTAT MODBUS PROTOCOL ADDRESS MAP
1.1 HOLDING REGISTERS
Holding Register
Addresses
Data Content
Data
Type
Parameter
Name
Read/Write
Permission
Status
Value
Decimal
Hex
0000d
0x0000
word
Set value
--
Readable/Writeable
-20
0001d
0x0001
word
Set point upper limit
uPL
Readable/Writeable
150
0002d
0x0002
word
Upper level alarm
A.uPL
Readable/Writeable
150
0003d
0x0003
word
Set point lower limit
LoL
Readable/Writeable
-60
0004d
0x0004
word
Lower level alarm
A.LoL
Readable/Writeable
-60
0005d
0x0005
word
The offset value for the cooling
oFF
Readable/Writeable
0
0006d
0x0006
word
Cooling hysteresis
HYS
Readable/Writeable
2
0007d
0x0007
word
Switch hysteresis for alarm
A.HYS
Readable/Writeable
2
0008d
0x0008
word
Type of buzzer sound
Snd
Readable/Writeable
0
nd
0009d
0x0009
word
Digital input types .0=nd;1=EA;2=SA;3=HC;4=dF
d.inp
Readable/Writeable
0010d
0x000A
word
Digital input delay
ddi
Readable/Writeable 0:00(0 sec)
0011d
0x000B
word
Delay time for the compressor after power is on.
C.Pon
Readable/Writeable 1:00(60 sec)
0012d
0x000C
word
C.Fos
Readable/Writeable 0:00(0 sec)
0013d
0x000D
word
Delay time required for the compressor to restart following
a stop.
On time for the compressor output in the case of probe failure
C.PPn
Readable/Writeable 0:00(0 sec)
0014d
0x000E
word
Off time for the compressor output in the case of probe failure
C.PPf
Readable/Writeable 1:00(60 sec)
0015d
0x000F
word
Defrost duration
d.dur
Readable/Writeable 1:00(60 sec)
0016d
0x0010
word
The time between 2 consecutive defrosts.
d.int
Readable/Writeable 1:00(60 min)
0017d
0x0011
word
Delay time for defrosting after power is on.
d.dpo
Readable/Writeable 1:00(60 sec)
0018d
0x0012
word
After the cooling process of cooling start-up delay
d.dRe
Readable/Writeable 1:00(60 sec)
0019d
0x0013
word
Time delay to display alarm message after alarm is on.
A.dfl
Readable/Writeable 0:00(0 sec)
0020d
0x0014
word
Time delay to display alarm message after power is on.
A.dpo
Readable/Writeable 0:10(10 min)
RTC REAL TIME CLOCK PARAMETERS
0021d
0x0015
word The device time setting
hour Readable/Writeable
0022d
0x0016
word
min
0023d
0x0017
word The device day setting
0024d
0x0018
word The first day of the week holiday
0025d
0026d
0027d
The device minute setting
Readable/Writeable
0
0
day
Readable/Writeable
0(Sun)
ht1
Readable/Writeable
7(nu)
0x0019
word The second day of the week holiday (Sun,Mon,Ued,thu,Fri,Sat,nu) ht2
Readable/Writeable
7(nu)
0x001A
word Defrost start time of the 1. workday
id1
Readable/Writeable 24:00(hr:min)
0x001B
word Defrost start time of the 2 workday
id2
Readable/Writeable 24:00(hr:min)
0028d
0x001C
word Defrost start time of the 3. workday
id3
Readable/Writeable 24:00(hr:min)
0029d
0x001D
word Defrost start time of the 4. workday
id4
Readable/Writeable 24:00(hr:min)
0030d
0x001E
word Defrost start time of the 5. workday
id5
Readable/Writeable 24:00(hr:min)
0031d
0x001F
word Defrost start time of the 6. workday
id6
Readable/Writeable 24:00(hr:min)
0032d
0x0020
word Defrost start time of the 1. holiday
td1
Readable/Writeable 24:00(hr:min)
0033d
0x0021
word Defrost start time of the 2. holiday
td2
Readable/Writeable 24:00(hr:min)
0034d
0x0022
word Defrost start time of the 3.holiday
td3
Readable/Writeable 24:00(hr:min)
0035d
0x0023
word Defrost start time of the 4. holiday
td4
Readable/Writeable 24:00(hr:min)
0036d
0x0024
word Defrost start time of the 5. holiday
td5
Readable/Writeable 24:00(hr:min)
0037d
0x0025
word Defrost start time of the 6.holiday
td6
Readable/Writeable 24:00(hr:min)
0038d
0x0026
word Energy-saving value of the difference set
Add
Readable/Writeable
0039d
0x0027
word Energy-saving start time of the workday
iEt
Readable/Writeable 24:00(hr:min)
0040d
0x0028
word Workday energy-saving time
iES
Readable/Writeable
0041d
0x0029
word Energy-saving start time of the holiday
TeT
Readable/Writeable 24:00(hr:min)
0042d
0x002A
word Holiday energy-saving time
Tes
Readable/Writeable
0043d
0x002B
word
0044d
0x002C
word Baudrate (0=Off; 1=1200; 2=2400; 3=4800;
4=9600; 5=19200)
(Sun,Mon,tue,Ued,thu,Fri,Sat)
(Sun,Mon,Ued,thu,Fri,Sat,nu)
RS485 Network address for the connection of the device.
Adjutable between 1-247.
4/6
Adrs Readable/Writeable
Baud Readable/Writeable
0
00:00
00:00
1
9600
EDT5411-E-01-201409
*Holding Register parameter of type integer,those “signed integer” is defined as the decimal port of and associated with these parameters.
(So,”14.0” is a parameter value of “140” will be read in.)Relevant parameters for a period of “mm:ss”type ones in seconds,”hh:mm”while
those species defined in minutes.
*Devices without RTC;0021d and 0022d parameters,the RTC in 0043d and 0044d addresses correspend to the devices.
1.2 INPUT REGISTERS
Input Register
Addresses
Decimal
Hex
0000d
0x0000
0001d
0x0001
Data
Type
Data Content
Parameter
Name
Read/Write
Permission
word
Measured temperature value (°C / °F)
--
Only readable
word
Defrost time(sn).During the defrost mode to defrost
for the normal,for the remaining period of the
termination of the defrost process. If the defrost is
finished,the remaining time for the start of the next
defrost.
--
Only readable
*Input Register parameter value of the temperature reading,is defined as a signed integer.This value is associated with a
portion.(So,”23,5°C”value of temperature “235” will be read in.)
1.3 DISCRETE INPUTS
Discrete Input
Addresses
Decimal
Hex
0000d
0x00
Data
Type
Bit
Data Content
Control output situation (0=OFF; 1=ON)
Parameter
Name
--
Read/Write
Permission
Only readable
1.4 COILS
Coil
Addresses
Decimal
00d
Hex
0x00
Data Content
Data
Type
Bit
01d
0x01
Bit
02d
0x02
Bit
03d
0x03
Bit
04d
0x04
Bit
05d
0x05
Bit
06d
0x06
Bit
07d
0x07
Bit
08d
0x08
Bit
Control type selection. OFF=Cooling control (Co)
ON=Heating control(HE)
Temperature unit. OFF=°C
ON=°F
Decimal point . OFF=no
ON=YES
Digital input polarity.OFF=While a digital input
contact is closed,it is activated.(cL) ON=While a
digital input is opened,it is activated(oP)
During defrost,display configuration.
OFF=The temperature which is measured before
defrost is displayed.(Lc) ON=Real temperature
is displayed during defrost process. (rE)
Defrosting process begins with energy.OFF=Defrost
process doesn’t start when,the energy comes.(no)
ON=Defrost process starts when the energy comes.
(Yes)
Alarm configuration .OFF=Absolute alarm (AbS)
ON=Relative alarm (rEF)
Defrost type (OFF=The normal operation of the
defrost.(nor) ON=Defrost operation with RTC (rtc)
Control situaiton. OFF=Control passive.(C.dis)
ON=Control active(C.Enb)
Parameter
Name
Status
Value
Read/Write
Permission
C.typ
Readable/Writeable
Co
Unit
Readable/Writeable
°C
D.PNT
Readable/Writeable
no
Dpo
Readable/Writeable
cL
D.dsp
Readable/Writeable
D.poN
Readable/Writeable
no
A.tYP
Readable/Writeable
aBs
d.typ
Readable/Writeable
nor
--
Readable/Writeable
C.enb
Lc
*”07d” address parameter,only the RTC and the RTC are not located in the devices and the device have a total of 7 parameter “”08d”
with address parameter 7. the order.
SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Şerifali Mah. Barbaros Cad. No:18 Y.Dudullu 34775
ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
5/6
EDT5411-E-01-201409
ENDA EDT5411 DIGITAL THERMOSTAT RTC PARAMETERS
RTC SET PARAMETERS
Min.
Max.
Unit
Status
hour
The device time setting
0
23
hour
0
mIn
The device minute setting
0
59
minute
0
day
ht1
The device day settingSun,mon,tue,Ued,thu,Fri,Sat
The first day of the week holiday.Sun,Mon,tuE,Ued,thu,Fri,
Sat,nu. (If nu is chosen,holidays are not selected and it is perceived
as working days.)
Sun
Sat
day
Sun
Sun
nu
day
nu
day
nu
-
nor
The second day of the week holiday.(Sun,mon,tue,Ued,thu,Fri,
ht2
Sat,nu. (If nu is chosen,holiday are not selected and it is perceived
as working days.)
Sun
nu
nor
rtc
00:00
24:00
hr:min
24:00
00:00
24:00
hr:min
24:00
-20
20
00:00
24:00
hr:min
24:00
00:00
24:00
hr:min
24:00
00:00
24:00
hr:min
24:00
00:00
24:00
hr:min
24:00
DEFROST CONTROL PARAMETERS
d.typ
ad1
The device defrost type. (nor:with interval times defrost, rtc:with real
time clock defrost)
ad1,Id2,Id3,Id4,Id5,Id6 Defrost status time in the range of
Id1-Id6 workdays.(If this status time=24:00,defrost process is
Id6 not performed.
td1
td1,td2,td3,td4,td5,td6.Defrost status time in the range of
td1-td6 holidays. (If this status time= 24:00 defrost process is not
td6 performed.)
ENERGY-SAVING PARAMETERS
add
A Et
A Es
tEt
tES
Energy-saving value of the difference set (During the energy-saving
SET=SET+Add. Energy-saving during ,the set value does not change.
Energy-saving start time of the workday.(If this status time=24:00
energy-saving will not be made.)
Workday energy-saving time(If this status time= 00:00 energy-saving
will not be made. )
Energy-saving start time of the holiday.(If this status time 24:00
energy-saving will not be made. )
Holiday energy-saving time(If this status time: 00:00 energy-saving will
not be made. )
°C/°F
0
REAL TIME CLOCK FEATURE
At first power up of the device;hour,minute,day must be adjusted.In addition,an optional holiday in each week can be
assigned to the desired days.All the days of the week “workday” is entered as requested,ht1 and ht2 parameters should
be chosen as “nu”.This sets the device is powered down,even after the 2500 real time clock continuous to run throughout
the day. With this feature ,defrost control and energy-saving can be requested.
SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Şerifali Mah. Barbaros Cad. No:18 Y.Dudullu 34775
ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
6/6
EDT5411-E-01-201409