Quick Reference Air to Water Heat Pump Series 4 – Lot 1 Standard

Add to my manuals
72 Pages

advertisement

Quick Reference Air to Water Heat Pump Series 4 – Lot 1 Standard | Manualzz

Quick Reference

Air to Water Heat Pump

Series 4 – Lot 1

Standard & Powerful Types

Estia Series 4 Standard Type Models:

Hydro unit

HWS-804XWHM3-E1

HWS-804XWHT6-E 1

HWS-804XWHT9-E 1

HWS-1404XWHM3-E1

HWS-1404XWHT6-E1

HWS-1404XWHT9-E1

Outdoor Units

HWS-804H-E1

HWS-1104H-E1

HWS-1404H-E1

HWS-1104H8(R)-E1

HWS-1404H8(R)-E1

HWS-1604H8(R)-E1

Estia Series 4 Powerful Type Models:

Hydro unit

HWS-P804XWHM3-E1

HWS-P804XWHT6-E1

HWS-P804XWHT9-E1

HWS-P1104XWHM3-E1

HWS-P1104XWHT6-E1

HWS-P1104XWHT9-E1

Outdoor Units

HWS-P804HR-E1

HWS-P1104HR-E1

Component Combinations

– Series 4 Standard Type

Hydro Unit

HWS-804XWHM3-E1

HWS-804XWHT6-E1

HWS-804XWHT9-E1

HWS-1404XWHM3-E1

HWS-1404XWHT6-E1

HWS-1404XWHT9-E1

Hydro Unit

HWS-804H-E1 HWS-1104H-E1 HWS-1404H-E1

Outdoor Unit

HWS-

1104H8(R)-E1

P

P

P

-

-

-

-

-

-

-

-

-

-

P

P

P

-

P

P

P

-

P

P

P

HWS-

1501CSHM3-E

HWS-

2101CSHM3-E

HWS-

1404H8(R)-E1

-

-

-

P

P

P

HWS-

1604H8(R)-E1

-

-

-

P

P

P

Back Up

Heater

~, 3kW

3N, 6kW

3N, 9kW

~, 3kW

3N, 6kW

3N, 9kW

Hot Water Cylinder

HWS-

3001CSHM3-E

HWS-

1501CSHM3-UK

HWS-

2101CSHM3-UK

HWS-

3001CSHM3-UK

HWS-804XWHM3-E1

HWS-804XWHT6-E1

HWS-804XWHT9-E1

HWS-1404XWHM3-E1

HWS-1404XWHT6-E1

HWS-1404XWHT9-E1

P

Component Combinations

– Series 4 Powerful Type

Hydro Unit

HWS-P804XWHM3-E1

HWS-P804XWHT6-E1

HWS-P804XWHT9-E1

HWS-P1404XWHM3-E1

HWS-P1404XWHT6-E1

HWS-P1404XWHT9-E1

HWS-P804HR-

E1

P

P

P

-

-

-

Outdoor Unit

HWS-P1104HR-

E1

-

P

P

P

-

-

Back Up Heater

~, 3kW

3N, 6kW

3N, 9kW

~, 3kW

3N, 6kW

3N, 9kW

Hot Water Cylinder

Hydro Unit

HWS-

1501CSHM3-E

HWS-

2101CSHM3-E

HWS-

3001CSHM3-E

HWS-

1501CSHM3-UK

HWS-

2101CSHM3-UK

HWS-

3001CSHM3-UK

HWS-P804XWHM3-E1

HWS-P804XWHT6-E1

HWS-P804XWHT9-E1

HWS-P1404XWHM3-E1

HWS-P1404XWHT6-E1

HWS-P1404XWHT9-E1

P

1

CAUTION

Standard type ESTIA units and Powerful type ESTIA units are not compatible with one another. When selecting your ESTIA system please ensure that you select all units from the either the Standard type model list or the Powerful type model list shown above.

DO NOT DESIGN YOUR SYSTEM USING A MIX OF STANDARD TYPE UNITS AND

POWERFUL TYPE UNITS

Note:

Under floor heating components, fan coil units, radiators, valves and other installation materials must be procured locally.

Notes on System Design

• The input water temperature to the hydro unit must be 50°C or less for ESTIA Series 4 Standard type and

55°C or less for ESTIA Series 4 Powerful type

. This is especially important if the hydro unit is used in conjunction with any other external heating source

(auxiliary boiler, electric booster heaters etc.)

Unit failure or water leaks may result if the return water temperature, to the hydro unit, exceeds the recommended inlet water temperatures shown above

• The minimum flow rate for the circulating water in the heating/cooling circuit must meet the following range:-

11, 14 and 16 kW: 17.5 L/minute or more

8 kW: 13 L/minute or more

If the flow rate becomes less than the flow rate specified above, the flow switch in the hydro unit is activated to stop operation.

When thermostatic devices are used for temperature control a bypass valve must be fitted to the heating circuit, to ensure the minimum water flow rate is maintained in the event of all thermostatic devices closing at the same time

• Only use the water pump, built into the hydro unit, to circulate the water in the heating circuit

• The hydro unit back up heaters will operate to assist the heat pump capacity output during low ambient conditions

• The hydro unit has been designed for indoor installations. Do not install outside where there is a risk of low ambient conditions. This may cause the water in the pipe work to freeze

• Make the water circuit closed. Never use it as an open circuit

• To prevent damage to the system the volume of the circulating water must be 20 litres or more. If total volume of water amount is less than 20 litres, then the unit may not function fully due to the operation of protective controls.

2

Installation Examples

Cooling and Heating with Domestic Hot Water

When both cooling and heating are used, install a 2-way valve (for cooling) to the pipe to the room for heating only.

3

Installation Examples (cont.)

2-Zone Temperature Control with Domestic Hot Water

The following shows an example of the 2-zone temperature control.

A buffer tank and a water pump are required for the 2-zone temperature control. This example is Heating only, if the Fan Coils are to be used for Cooling then a 2-Way valve must be fitted.

4

Installation example of water circuit:-

(1) (2)

(3) (4)

(5) (6)

The water circuit for a system without a buffer tank [ (1) , (2) , (3) , (5) ] requires 17.5l/min (804XWH =

13.0l/min) or more. This water flowing requires 5 or more branches of Floor heating or Radiators etc.

Less than 5 branches may cause a flow deficiency. In this case, please provide a buffer tank and secondary pumps, as shown in (4).

Please check how to install the boiler.

5

Hydro Unit

– Exploded View

1. Expansion vessel

2. Hi Pressure switch (4.15 MPa)

3. Temperature sensor (for Heat pump outlet -TWO)

4. Pressure sensor

5. Heat exchanger

6. Flow switch (13.0 L/min 17.5 L/min)

7. Temperature sensor (for refrigerant -TC)

8. Temperature sensor (for water inlet -TWI)

9. Drain nipple

10. Water inlet connection

11. Refrigerant liquid connection

12. Air relief valve

13. Pressure relief valve (0.3 MPa (3 bar))

14. Thermal protector (auto)

15. Temperature sensor (for water outlet THO)

16. Thermal protector (Single operation)

17. A-rated water pump

18. Backup heater (3 kW, 3 kW x 2, 3 kW x 3)

19. Manometer

20. Water outlet connection

21. Refrigerant gas connection

6

Refrigerant Pipe Lengths and Height

The length and height of the refrigeration pipe must be within the following values.

As long as the Hydro Unit is installed within these ranges, no additional refrigerant is required.

Minimum Pipe Length

All models: 5m

Maximum Pipe Length and Height

H: Max. ±30 m (above or below)

L: Max. 30 m

Note

The maximum pipe length cannot be increased by increasing the refrigerant charge

The minimum pipe length cannot be decreased by reducing the refrigerant charge

Refrigeration and Water Cycle Diagrams

– ESTIA Series 4 Standard Type

Outdoor Unit: HWS-804H-E1

Hydro Units: HWS-804XWH**-E1

Outdoor Units:

Hydro Units:

HWS-1104H**-E, HWS-1404H**-E1

HWS-1404XWH**-E1

7

Outdoor Units:

Hydro Units:

HWS-1104H8(R)-E, HWS-1404H8(R)-E, HWS-1604H8(R)-E1

HWS-1404XWH**-E1

Refrigeration and Water Cycle Diagrams

– ESTIA Series 4 Powerful Type

Outdoor Unit:

Hydro Units:

HWS-P**04HR-E1

HWS-P**04XWH**-E1

8

System Operating Range

– ESTIA Standard Type

1

1

9

System Operating Range

– ESTIA Powerful Type

10

Water Piping

WARNING

• Ensure that the heating circuit, and all components of the heating circuit, are installed in accordance with all National and local regulations

• The water pipes must not be installed where they are exposed to low ambient air temperatures. This is to prevent the water freezing in the pipes

• Make sure that water pipes have sufficient pressure resistance

(The setting value of the pressure relief valve is 0.3 MPa).

CAUTION

Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes.

• The water to be used must meet the water quality standards specified in EN directive 98/83 EC.

Water Circuit

Install a strainer with 30 to 40 meshes (procure locally) at the water inlet of the Hydro Unit

• Install drain cocks (procure locally) for water charge and discharge at the lower part of the Hydro Unit

• The ESTIA system can only be used on pressurised heating circuits. If the system is used on gravity fed heating circuits then system failure may occur

Water Piping Limitations

Design the water pipe length within the QH characteristics of the pump (flow-rate and pump head).

The maximum height difference for the water pipes is 7 metres.

Piping to hot water tank (option)

Water supplied to the hot water cylinder is branched by a motorized 3-way valve (procured locally).

Connect the hot water cylinder to port A (open when energized) of the valve.

11

Piping to 2-zone operation (option)

To perform 2-zone temperature control circulate water using another pump (procured locally) through a motorized mixing valve (procured locally) and a buffer tank (procured locally).

Checking water volume and initial pressure of expansion vessel

The expansion vessel of the Hydro Unit has a capacity of 12 litres.

The initial pressure of the expansion vessel is 0.1 MPa (1 bar).

The pressure of the safety valve is 0.3 MPa (3 bar).

Verify whether the capacity of the expansion vessel is sufficient using the following expression. If the volume is insufficient, install an appropriate external expansion vessel.

V Action

< 12 L Internal Expansion Vessel Size OK

> 12 L

Internal Expansion Vessel Size too small.

Install appropriate external expansion vessel

V: Necessary total vessel capacity (L)

Ɛ:

Water expansion coefficient at average hot water temperature

Vs: Total water volume in the closed system (Do not include Hot Water Cylinder)

P1: System pressure at tank setting position (Mpa_abs*).

(Pipe inner pressure during pump operation before heating device operates = water supply pressure)

P2: Maximum pressure used during operation at tank setting position (MPa_abs*).

(= safety valve setting pressure)

* The absolute pressure value (abs.) is obtained by adding the atmospheric pressure (0.1 MPa (1 bar)) to the gauge pressure.

Water temperature and expansion coefficient (Ɛ) Water temperature and expansion coefficient (Ɛ)

Hot water temperature

(°C)

0

4

5

10

15

20

25

30

35

40

45

Expansion rate

(Ɛ)

0.0002

0.0000

0.0000

0.0003

0.0008

0.0017

0.0029

0.0043

0.0050

0.0078

0.0100

12

Hot water temperature

(°C)

50

55

60

65

70

75

80

85

90

95

-

Expansion rate

(Ɛ)

0.0121

0.0145

0.0171

0.0198

0.0229

0.0258

0.0292

0.0324

0.0961

0.0967

-

Example

Maximum Hot Water temperature: 55°C

Initial water charge: 0.2MPa

System volume: 200 L.

Calculate Vessel capacity (V):-

V = 0.0145 x

1

-

200

(0.2 + 0.1)

(0.3 + 0.1)

V =

11.6L

In this case V < 12 L therefore the internal expansion vessel is sufficient, so there is no need to install an external expansion vessel.

Pump QH curves

Standard Type: HWS-804XWHM3-E1, T6-E1, T9-E1

Powerful Type: HWS-P804XWHM3-E1, T6-E1, T9-E1

13

Standard Type: HWS-1404XWHM3-E1, T6-E1, T9-E1

Powerful Type: HWS-P1104XWHM3-E1, T6-E1, T9-E1

Water charging

Charge the water, in the heating circuit, until the pressure gauge shows 0.2 MPa (2 bar).

The hydraulic pressure may drop when the trial run begins. In this case, add water until the hydraulic pressure returns to 0.2MPa (2 bar)

Air may enter the heating circuit if the hydraulic pressure is low.

Air purge

Loosen the Air relief valve cap by two turns to release air (see diagram):

Either Type A or Type B automatic air purge valve will be fitted to the hydro unit. Type B purge valve cap faces the front as factory standard.

Ensure all air is removed from the system. If air remains in the system then the system operation may

STOP.

14

Loosen the air vent screw on the hydro unit water pump to ensure all the air has been removed from the pump housing. Tighten the air vent screw on completion of the air purge.

Manually operate the pressure relief valve fitted to the hydro unit to release any air that may be trapped in the pressure relief valve pipe (water may be released from the pressure relief valve during this operation).

Note: Due to the design of the electrical back up heater it is not recommended to add any corrosion inhibitors / additives to the heating circuit.

Water quality

The water used must satisfy EN directive 98/83 EC.

Piping insulation

It is recommended that insulation is fitted to all pipes. To perform optional cooling operation, apply insulation with a rating of 20t or more to all pipes.

15

Electrical Connections

E Box layout

Power Lines Schematic

16

Fuses (AC250V T30A):

F1&F2: Hot water cylinder electric heater supply

F3&F4: Back up heater 1 (3kW)

F5&F6: Back up heater 2 (3kW)

F7&F8: Back up heater 3 (3kW)

Fuses (AC250V T3.15A)

F9&F10: A rated water pump

PCB’s:

MCC-1214: TCB-PCMO3E (optional input PCB)

MCC-1217: TCB-PCIN3E (optional output PCB)

MCC-1431: Relay PCB for control of second water pump, 2 way valve and booster heater outputs

MCC-1511: Main hydro unit control / interface

PCB

Contactors & Relays:

RY01: Interlock relay – flow switch / back up heater circuit

RY02: Power contactor for back up heater supply

RY03: Control relay for back up heater s 2 & 3 operation

RY04: Power contactor for back up heater supply

RY05: Power contactor for hot water cylinder electric heater supply

RY06: Control relay for mixing valve (2 zone) operation

Control Lines Schematic

Terminal Block Connections

17

Electrical supply / cable specifications

Wiring specifications (power line)

Description

Model Name

HWS

Power

Supply

Current

(Max)

1404H-E1

220V-230V ~

50Hz

Outdoor

Unit

Power

Power

Input

(P)1104H(R)-E1

P804HR-E1

804H-E1

1604H8(R)-E1

1404H8(R)-E1

1104H8(R)-E1

(

P)1*04XWHM3-E1

220V-230V ~

50Hz

220V-230V ~

50Hz

380-400V

3N~ 50Hz

380-400V

3N~ 50Hz

380-400V

3N~ 50Hz

220V-230V ~

50Hz

Hydro unit electric heater power

Power input for back up heater

(P)1*04XWHT6-E1

(P)1*04XWHT9-E1

(P)804XWHM3-E1

(P)804XWHT6-E1

(P)804XWHT9-E1

Power input for DHW cylinder heater

Outdoor

– hydro unit connection

-

Hydro unit to DHW cylinder

-

Wiring specification (control line)

380-400V

3N~ 50Hz

380-400V

3N~ 50Hz

220V-230V ~

50Hz

380-400V

3N~ 50Hz

380-400V

3N~ 50Hz

220V-230V ~

50Hz

-

-

Description Line Spec Current (Max)

3 way diverting valve

2 way valve

(cooling)

2 or 3 wire

2 wire

100mA

100mA

22.8A

22.8A

19.2A

14.6A

14.6A

14.6A

13A

13A (13Ax2P)

13A (13Ax3P)

13A

13A (13Ax2P)

13A (13Ax3P)

12A

-

-

Length (Max)

12m

12m

Install

Fuse

Rating

25A

25A

20A

16A

16A

16A

16A

16A

16A

16A

16A

16A

16A

-

-

Power

Cable

≥2.5mm

2

≥2.5mm

2

≥2.5mm

2

≥2.5mm

2

≥2.5mm

2

≥2.5mm

2

≥1.5mm

2

≥1.5mm

2

≥1.5mm

2

≥1.5mm

2

≥1.5mm

2

≥1.5mm

2

≥1.5mm

2

≥1.5mm

2

≥1.5mm

2

Cable Diameter

1.0mm

2

1.0mm

2

3 way mixing valve (2 zone)

2 zone thermo sensor (TFI)

HW cylinder thermo sensor

(TTW)

2 nd

remote controller

3 wire

2 wire

2 wire +GND

(screened cable)

2 wire

100mA

100mA

100mA

50mA

18

12m

5m

5m

50m

1.0mm

2

1.0mm

2

1.0mm

2

≥ 0.5mm

2

Connection

Destination

L, N

L1, L2, L3,

N

L, N

L1, L2, L3,

N

L, N

L1, L2, L3,

N

L, N

1, 2, 3

1, 2

Connection

Destination

7, 8, 9 (TB05)

3, 4 (TB05)

1, 2, 3 or

2, 3, 4

(TB04)

C, D (TB06)

A, B (TB06)

1, 2 (TB07)

-

-

TB02

TB03

TB01

TB03

Control parts specifications

Component

3 way diverting valve

2 way valve (cooling )

3 way mixing valve (2 zone control)

Power

AC 230V

AC 230V

AC 230V

Current (Max)

100mA

100mA

100mA

Specification

Default: 2 wire spring return valve or 3 wire SPST valve

Option: 3 wire SPDT valve (set DPSW13_1 to ON)

2 wire spring return valve (normally OPEN)

Default drive time = 60 seconds to 90°

3 wire SPST or SPDT with drive times to 90° between

30 and 240 seconds

Output line specifications

Description Output

Current

(Max)

Voltage

(Max)

Cable

Length

(Max)

External water pump (P2)

External booster heater

AC230V

AC230V

1A

1A

-

-

12m

12m

Alarm output No volt contacts

0.5A AC230V

1A DC24V

0.5A AC230V

12m

12m

12m

Boiler output No volt contacts

1A DC24V 12m

Defrost output No volt contacts

Compressor ON output

No volt contacts

Input line specifications

Description

External stop control

Input

No voltage

Cylinder thermostat No voltage

Room thermostat (cooling) No voltage

Room thermostat (heating) No voltage

0.5A AC230V

1A DC24V

0.5A AC230V

1A DC24V

Cable Length (Max)

12m

12m

12m

12m

12m

12m

12m

12m

19

Comments

Output enabled when outdoor air temperature is

≤ -20°C

Output enabled when outdoor air temperature is ≤ -10°C (output trigger temperature can be changed using FC23)

CAUTION

Earthing arrangements

The Hydro Unit and related equipment must be earthed in accordance with your local and national electrical regulations.

It is essential that the equipment is earthed to prevent the electric shock and damage to the equipment.

Electrical connection to hydro unit

Remove the front cover and the electrical box cover from the Hydro Unit.

• The Hydro Unit power cable, for the electrical back up heaters, must be sized in accordance with the

Wiring Specifications table shown on page 15

• Connect the Hydro Unit power cable, for the electrical back up heaters, to Terminal 02 as shown below.

Single Phase Units: Live conductor

– Terminal L1

Neutral conductor

– Terminal L2

Earth conductor

– Earth terminal

Three Phase Units: Phase 1 conductor

– Terminal L1

Phase 2 conductor

– Terminal L2

Phase 3 conductor

– Terminal L3

Neutral conductor

– Terminal N

Earth conductor

– Earth

• Ensure the Hydro Unit power cable, for the electrical back up heaters, is secured using the cable clamp fitted in the electrical box.

• Ensure the Hydro Unit power cable connection (for the electrical back up heaters) terminals are tight.

Outdoor unit to hydro unit electrical connection

HWS-804H-E1

HWS-1104H-E1

HWS-1404H-E1

HWS-P804HR-E1

HWS-P1104HR-E1

HWS-1104H8-E1, H8R-E1

HWS-1404H8-E1, H8R-E1

HWS-1604H8-E1, H8R-E1

• Ensure electrical circuits are isolated before commencing work.

• The Outdoor Unit to Hydro Unit interconnecting cable must be sized in accordance with the “Wiring

Specification” table shown on page 15

• Connect the Outdoor Unit to Hydro Unit interconnecting cable as shown in the diagram above.

• Ensure the Outdoor Unit to Hydro Unit interconnecting cable is secured using the cable clamp fitted in the electrical box.

• Ensure the Outdoor Unit to Hydro Unit interconnecting cable connection terminals are tight.

20

Electrical connection for external booster heater

CAUTION

The maximum current available from the booster heater output is 1 A. Do not connect the booster heater directly to Terminal Block 05 on the Hydro Unit. A separate contactor, supplied locally, must

be used to supply the booster heater.

• The booster heater can be installed only for room heating and cannot be used for hot water supply.

• Install the booster heater downstream of the 3-way valve on the heating circuit side of the installation

• The booster heater is an external heater, supplied locally, used to assist the Hydro Unit during low ambient conditions.

• The AC230 V 1 A output from the Hydro Unit must only be used to energize an external contactor

(supplied locally).

• The output from the Hydro Unit is only enabled when either the outdoor air temperature to be lower than -

20°C.

• Ensure the external booster heater is installed and set up in accordance with all Local, National and

International regulations.

Connect the external booster heater to the Hydro Unit according to the diagram shown opposite:-

• The contactor will energize in the event of low ambient conditions.

• A separate dedicated electrical supply must be used for the external booster heater. This must be connected through the contacts on the field supplied contactor.

Electrical connection for external additional pumps

CAUTION

The maximum current available from the additional pump output is 1 A. Do not connect the additional pump directly to Terminal Block 05 on the Hydro Unit. A separate contactor, supplied

locally, must be used to supply the additional pump.

• The Hydro Unit has the facility to connect an additional circulating pump, if required, into the heating or cooling system.

• Install the pump so that its motive power does not affect the internal pump.

• The AC230 V 1 A output from the Hydro Unit must only be used to energize an external contactor

(supplied locally).

• The output for the pump is synchronized with the operation of the main circulating pump (P1) inside the

Hydro Unit.

• Ensure the pump is installed and set up in accordance with all Local, National and International regulations.

• Connect the additional pump (P2) as shown in the diagram opposite:-

• The contactor will energize synchronously with operation of the main circulation pump (P1).

• A separate dedicated electrical supply must be used for the pump. This must be connected through the contacts on the field supplied contactor.

21

3-way valve (diverter) connection

Required Valve Specification:

Electrical Specification: 230 V; 50 Hz; <100 mA

Valve Diameters: Port A, Port B: Ø 1 1/4"

Return Mechanism: 3 types of 3-way valve (diverter) can be used.

Set the 3-way valve in use with the DIP switch SW13-1 on the Hydro Unit board

.

Diverter Valve Description DPSW13-1

Type 1

Type 2

2-wire spring return

3-wire SPST

OFF

OFF

Type 3 3-wire SPDT ON

NOTE

Continuous operation of the valve motor at the fully open position is not recommended.

• The 3-way diverter valve is used to select either domestic hot water or zone1 / zone2 space heating

• Connect the 3-way diverter valve in accordance with the diagram below:-

22

3-way mixing valve connection

Required Actuator Specification

Electrical Specification:230 V; 50 Hz; <100 mA

The 3-way mixing valve is used to achieve the temperature differential needed in a 2-zone heating system.

• Connect the 3-way mixing valve in accordance with the diagrams below:-

Hot water cylinder connection (optional)

Please refer to “Electrical supply/cable specifications” for fuse/cable size and for connection details.

Electrical Connection (Hot Water Cylinder Electric Heater)

• The electric heater, incorporated in the hot water cylinder, requires a separate supply to the Hydro Unit.

• Connect the hot water cylinder heater electrical supply in accordance with shown below:

Live conductor: Terminal L on Terminal Block 03

Neutral conductor: Terminal N on Terminal Block 03

Earth Conductor: Earth terminal on Terminal Block 03

• Connect the hot water cylinder heater to the Hydro Unit as shown below:

Live conductor to hot water cylinder: Terminal 1 on Terminal Block 03

Neutral conductor to hot water cylinder: Terminal 2 on Terminal Block 03

Earth conductor to hot water cylinder: Earth terminal on Terminal Block 03

Please ensure that the interconnecting cable, between the Hydro Unit and the hot water cylinder, is connected to earth at both ends of the cable using the shield wire or the earth conductor of the interconnecting cable.

Electrical Connection (Hot Water Cylinder temperature Sensor)

• Connect the hot water cylinder temperature sensor as shown below to terminals A & B on Terminal Block

06 in the Hydro Unit.

23

Second Remote Controller Installation (optional)

It is possible to connect a second remote controller to the ESTIA system.

The remote controller should be installed between 1m to 1.5m above floor level so that the remote controller measures the average room temperature

The remote controller must not be installed in areas of:

Direct sunlight or areas exposed to outside air influences

Poor ventilation (near windows or other openings)

External heat sources (above radiators etc.)

Freezing or refrigerated areas

The remote controller must be installed in a vertical position

Second Remote Controller Connection

2 core shielded cable

– 0.5mm

2 or more.

Maximum cable length

– 50m

Terminal block TB07, for remote controller connection, to hydro unit.

Second remote controller connections. Terminals A and B are not polarity conscious.

The remote controller can be set as either the header or second remote controller and to measure either water temperature or room air temperature.

Remote Controller DIPS Switches - Setting

 Set one of the remote controllers as the header remote controller (remote controller of hydro unit is preset as the header remote controller (DPSW1 = OFF)

 Set the DPSW’s on the other remote controller PC boards to “second” (optional remote controller is preset as “second” – DPSW1 = ON)

For room air temperature control

 set function co de 40 (on the hydro unit) to “1”

Set DPSW2 to ON only on the remote controller used for room temperature measurement

 Either the header or the second remote controller can be set for room temperature measurement. Please do not set DPSW2 to ON on both the header and follower remote

controllers

24

Input / Output Option PCB’s – Installation

Output Options:

It is possible to connect to outputs, using the TCB-

PCIN3E option PCB’s, on the ESTIA hydro unit for the following functions:

Alarm output

Boiler output

Defrost

Compressor ON

System alarm & boiler outputs:

Alarm output (L1): Output ON when the system is in alarm/fault conditions. The output is available through a volt free contact on the TCB-PCIN3E option PCB.

Boiler control output (L2): Output ON when outdoor ambient temperature is less than or equal to the temperature set in FC23. The output is available through a volt free contact on the TCB-

PCIN3E option PCB.

Defrost & compressor ON outputs:

Defrost output (L1): Output ON when the system / outdoor unit is under defrost control. The output is available through a volt free contact on the TCB-PCIN3E option PCB.

Compressor ON output (L2): Output ON when the outdoor unit compressor is operating. The output is available through a volt free contact on the TCB-PCIN3E option PCB.

Volt free contact specification: The volt free contact specification, for the outputs detailed above, is shown below:

AC230V: 0.5A (maximum)

DC24V: 1.0A (maximum)

25

Input Options:

It is possible to connect inputs, using the TCB-

PCMO3E option PCB’s, on the ESTIA hydro unit for the following functions:

External room thermostat

External hot water cylinder thermostat

External STOP

External room thermostat (DPSW02_4 = ON. Default = OFF):

The diagram above shows the thermostat connections for heating and cooling mode. The thermostat must be manually switched between heating and cooling (the operating mode, on the

ESTIA remote controller must also be changed manually). The system cannot change between heating and cooling modes automatically.

For cooling operation connect the cooling contact, on the thermostat, between terminals 2 (COOL) &

3 (COM) on the option PCB (as shown above).

For heating operation connect the heating contact, on the thermostat, between terminals 1 (HEAT) &

3 (COM) on the option PCB (as shown above).

Control Logic:

Option PCB

Terminal Nos.

2 ~ 3

Cooling Operation

ON OFF

OPEN CLOSED

Heating Operation

ON OFF

- -

1 ~ 3 - - CLOSED OPEN

External hot water cylinder thermostat (DPSW02_3 = ON. Default = OFF):

Connect the external hot water cylinder thermostat (S1 in the diagram below) to terminals 2 (COOL) and

3 (COM) on the option PCB.

When the hot water cylinder thermostat contact, S1, is CLOSED then there is a hot water demand and the system will produce hot water (if all DPSW’s and function codes are set correctly)

26

External system STOP:

Connect the external STOP signal / contact (S2 in the diagram above) to terminals 1 (HEAT) and 3 (COM) on the option PCB.

It is possible to set the operating logic of contact S2 (normally OPEN contact, normally CLOSED contact or pulse input) using function code FC52 and the operating mode of the system, on restart, using FC61 (see function code list on page 31 for options).

The external stop option can also be used for TEMPO control where an external signal, from the customers electricity measuring meter, is applied to the option PCB (contact S2 connections). TEMPO control can be used as part of the price contract provided by French electric power company EDF. The TEMPO control options are set using FC61.

Heating & hot water mode control using external no volt contacts

For the ESTIA E1 series it is possible to change the functionality of the TCB-PCM03E option PCB, when connected to CN210 on the hydro unit PCB, to allow hot water mode and heating mode ON/OFF control using S1 and S2 respectively.

The functionality can be changed by completing the following settings:

1. DPSW02_3 = OFF

2. FCB6 = 1 (new function code)

3. FC61 = 3

27

Start up and Configuration

Setting DIP Switches on the Board in the Hydro Unit

• Detach the front cover and the electric parts box cover of the Hydro Unit.

• Set the DIP switches on the main board.

Switch

No.

02

10

11

12

13

Bit

No.

1

2

3

4

1

2

3

4

1

2

3

4

1

2

3

4

1

2

3

4

Description

Determines the position of the auxiliary boiler in the system installation:

OFF = Boiler positioned after the 3 way valve

ON = Boiler installed before the 3 way valve

Not Used

Used when an external cylinder thermostat is connected:

OFF = external cylinder thermostat not connected

ON = external room thermostat connected

Used when an external room thermostat is connected:

OFF = external room thermostat not connected

ON = External room thermostat connected

Synchronises pump P1 with HP during hot water production:

OFF = Pump P1 synchronised with HP during hot water mode when electric cylinder heater is energised

ON = Pump P1 continuous operation

Pump P1 control using TO control (heating mode only):

OFF = Pump P1 continuous operation

ON = Pump P1 OFF when TO > 20°C (temperature can be changed using FC9E)

Synchronises pump P2 with pump P1:

OFF = Pump P2 continuous operation (P2 OFF when remote controller switched OFF)

ON = Pump P2 synchronised with pump P1

Pump P1 ON/OFF cycling (during long periods of system OFF):

OFF = Pump P1 normal operation

ON = Pump P1 ON for 10 minutes duration (if system has been stopped for 75 hours)

Used to enable the hydro unit back up heaters:

OFF = Back up heater control enabled

ON = Back up heater control disabled

Used to enable the hot water cylinder electric heater:

OFF = Hot water cylinder heater control enabled

ON = Hot water cylinder heater control disabled

Used to enable the external booster heater output control:

OFF = External booster heater control ena bled (TO must be ≤ -20°C)

ON = External booster heater control disabled

Not Used

Used to determine hot water cylinder connection to the system:

OFF = Hot water cylinder connected to the system

ON = Hot water cylinder not connected to the system

Used to enable Zone 1 operation:

OFF = Zone 1 control enabled

ON = Zone 1 control disabled

Used to enable Zone 2 operation:

OFF = Zone 2 control disabled

ON = Zone 2 control enabled

Not Used

Used to determine type of 3 way diverting valve connected to system:

OFF = 2 wire spring return or 3 wire SPST valve connected

ON = 3 wire SPDT valve connected

Used to enable the external boiler output control (used with FC23):

OFF = External boiler output control disabled

ON = External boiler output control enabled

Used to enable system auto restart after system power failure:

OFF = Auto restart control enabled

ON = Auto restart control disabled

Used to select hydro unit software (do not change switch position)

OFF = Series 4 Standard hydro unit

ON = Series 4 Powerful type hydro unit

Standard

Type

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

28

Powerful

Type

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

Hydro Unit Remote Control Buttons

1. TEMP. button:

2. SCHEDULE button:

3. TIME button:

4. SET button:

5. CL button:

6. DAY button:

7. STEP button:

Changes the set temperature for each operation mode (ZONE1 /

ZONE2 / HOT WATER) by 1°C step.

10. NIGHT button:

Controls the night set back operation.

Sets the current time and scheduled weekly operation.

11. AUTO TEMP. button:

Switches setting temperature automatically according to outside temperature. (Pressing this button long changes the mode to data setting mode).

Changes time for current time setting and scheduled weekly operation setting with ▼ and ▲ buttons.

Determines the entered current time setting and scheduled weekly operation setting.

Specifies switching STEP number in a day for weekly schedule.

12. OPERATE

MODE button:

13. ZONE1, 2 button:

Selects ZONE1 / ZONE2 operation mode (heating or cooling).

Turns on/off the zone (floor heating/radiator/FCU) operation.

Clears settings for the current time and scheduled weekly operation.

Sets days of the week for current time setting and scheduled weekly operation setting.

14. ANTI BACTERIA button:

Regularly increases the hot water temperature in the tank for sterilization. (Pressing this button long changes the mode to data setting mode).

15. HOT WATER

BOOST button:

Boosts boiling when high tapping temperature is required temporarily.

16. HOT WATER button:

Turns on/off hot water operation.

8. TEST button:

Used for test run or service.

17. SELECT button:

Selects an operation mode when changing the set temperature of each operation mode.

9. FROST

PROTECTION button:

Controls minimum operation for unused period (going out, absence,etc.) for anti freezing.

NOTE

Some functions are not provided depending on the system specification in use.

29

Display Explanation

Display

18: ZONE1, ZONE2

Description

Lights when floor heater or radiator is connected (when the system has floor heater or radiator).

ZONE1 selected for Temperature to be changed.

Lights when system configured to have 2 zones.

ZONE2 selected for Temperature to be changed.

Lights during heating or cooling operation using the heat pump.

Lights when the internal heater is energized during heating operation.

Lights when heating is selected.

°C

Lights when cooling is selected.

Lights when the FROST

PROTECTION button is pressed and goes out when the button is pressed again.

Lights when Auto operation is selected.

Displays heating/cooling set temperature. (Heating: 20 to 55°C, factory setting: Auto, cooling: 7 to

25°C) Goes out when Auto operation is selected.

Lights when the set temperature or sensor's water temperature is displayed with the 7-segment indicator.

Display

20: HOT WATER

Description

Lights when hot water supply system is connected (when the system has hot water supply).

°C

HOT WATER selected for Temperature to be changed.

Lights when hot water supply operation is performed by heat pump.

Lights when the internal heater is energized during hot water supply operation.

Lights during hot water supply operation.

Lights while hot water boost is activated.

Lights when the ANTI BACTERIA button is pressed and goes out when the button is pressed again.

Lights when unit enters the data set mode.

Displays hot water set temperature.

(40 to 75°C, factory setting: 65°C)

Lights when the set temperature or sensor's water temperature is displayed with the 7-segment indicator.

30

Display Explanation (cont.)

19: TIMER

Display Description

Clock: Displays the current time

(AM or PM).

Display

21: CONTROL

Description

Lights while internal pump (P1) or external pump (P2) is driven.

Displays days of the week (Sunday to Saturday).

Lights when the NIGHT button is pressed and goes out when the button is pressed again.

Lights when night time quiet operation is set.

Lights during backup operation only by the heater.

Lights when the unit enters the data set mode and goes out when the unit exits the data set mode.

Lights when the unit enters the service mode and goes out when the unit exits the service mode.

Indicates scheduled operation 1 status (including setting time).

Lights when an error occurs and goes out when the error is cleared.

Displays the scheduled operation step when the scheduled operation

STEP1-5 program is set.

Lights for two seconds when settings are completed.

Lights during time setting and scheduled operation setting.

Lights for two seconds when settings failed.

Remote Controller

– Schedule Timer

It is possible to set up timer control schedules on the ESTIA remote controller (when two remote controllers are fitted to the ESTIA system the schedule timer is only available from the HEADER remote controller).

A maximum of eight control STEPS can be programmed / scheduled, into the ESTIA remote controller, for each day of the week.

Using the schedule timer function (see page 42 for example):

Accessing the schedule timer function:

Press the SCHEDULE button for 4 second or more to enter the schedule timer setting mode. The remote controller will show the following display:

Specifying the day for the schedule timer:

Press the Day button to move the ▼symbol, displayed above the days of the week on the remote controller, to the day when the scheduled timer id to take place. Each press of the DAY button moves the ▼symbol to the next displayed day. When the ▼symbol is above the required day, press the SET button to confirm the day to be set

Specifying the control STEP number:

Press the STEP button to specify the control STEP to be set. The STEP selection increments by 1

STEP for each press of the STEP button from STEP 1 to STEP 8.

Steps “C” and “L” are also available by continuing to press the STEP button when the remote controller display shows STEP 8.

31

If “C” is selected then the control details, already set for the specified day, are copied. These details can be copied to other days of the scheduled timer

If “L” is selected then all of the control details, set for the specified day, are deleted

Specifying the Step ON/OFF time, operation mode & set temperature:

ON/OFF Time: Use the TIME ▲ ▼ buttons to set the required ON/OFF time for the specified control step

Operating Mode: To select or deselect the hot water function press the HOT WATER button on the remote controller

To select or deselect either space heating function press the Zone1, 2 button on the remote controller

When the function is selected to turn ON (at the specified time) then a numerical temperature is displayed in the relevant window on the remote controller. When the function is selected to Turn

OFF (at the specified time) then the remote controller will display - - - -

To select either heating or cooling press the OPERATE MODE button on the remote controller.

When heating is selected then selected then will be displayed on the remote controller. If cooling mode is will be displayed.

Set Point Temperature: Press the SELECT button, on the remote controller to select either space

Zone 1, Zone 2 or HOT WATER. Press the TEMPERATURE ▲ ▼buttons to set the required temperature

When the ON/OFF time, operating mode and set point temperature have been entered into the schedule timer press the SET button to confirm the settings

Leaving the schedule timer function:

When the scheduled timer function has been set for the required days press the SCHEDULE button to end the schedule setting function. The remote controller display will return to the main display screen and the icon, on the remote controller display, will flash. Press the SET button within 5 seconds of the icon flashing

– the icon changes to lit and is continuously displayed. The timer schedule is now in operation

How to copy a program

When specifying the

STEP number (see details above) select “C” and press the SET button. This copies all of the previously set data for that day.

Press the DAY button to move the ▼ above the new schedule timer day. Press the SET button to copy the required data into the new day.

Repeat this process for all days required

32

Function Code Access

Set function codes for various operation modes, input using the remote controller.

There are 2 types of settings:-

1) Hydro Unit function code setting.

2) Remote controller function code setting.

Setting procedure for Hydro Unit function code

1. Press and hold + + buttons for four seconds or more to enter the hydro unit function code setting mode.

2. Set the function code number with the TEMP. buttons

(CODE No.: 01 to B2).

3. Set data with the TIME buttons .

4. Press to confirm the settings.

5. Note that the Clear button is enabled only before the SET button is pressed and the function code is changed.

6. Press to exit the settings menu.

Setting procedure for Remote Controller function code

1. Press and hold + + TEMP. buttons for four seconds

or more to enter the remote controller function code setting mode.

2. Set the function code number with the TEMP. buttons

(CODE No.: 01 to 13).

3. Set data with the TIME buttons .

4. Press to determine the settings.

5. Note that the Clear button is enabled only before the SET button is pressed and the function code is changed.

6. Press to exit the settings menu.

33

Function Code Setting

(values shown in brackets are for Powerful type only)

Function Code

Setting Address

Function Code Setting Range

Hydro

Unit

Remote

Controller

Setting Temperature

Range

Hot Water Operation

Hot Water Cylinder

Heater Control

Hot Water Temperature

Compensation

Hot Water Boost

Anti Bacteria

System Priority Setting

Heating Upper Limit - Zone 1

Heating Lower Limit - Zone 1

Heating Upper Limit - Zone 2

Heating Lower Limit - Zone 2

Cooling - Upper Limit

Cooling - Lower Limit

Hot Water - Upper limit

Hot Water - Lower limit

Heat Pump Start Temperature

Heat Pump Stop Temperature

Determines the time between HP operation and cylinder heater ON time

0=30min, 1=60min, 2=90min, 3=120min

Temperature Compensation Outside Air

Temperature (°C)

Compensation Temperature (K)

Operation Time (x10 min)

Setting Temperature (°C)

Setting Temperature (°C)

Start Cycle (Day)

Start Time (Hour)

Operation Time (min)

Hot water v heating

– switching temperature (°C)

External boiler

– output ON temperature (°C)

Hot water v cooling priority selection:

0 = Cooling priority. Hot water produced by electric cylinder heater

1 = Hot water priority. Hot water produced by HP

Outside Temperature T1 (°C)

Outside Temperature T2 (°C)

Outside Temperature T3 (°C)

18

19

1E

1F

1A

1B

1C

1D

20

21

73

24

25

08

09

0A

-

-

0B

22

23

0F

29

-

2B

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0D

0C

-

-

-

37~55(60)

20~37

37~55 (60)

20~37

18~30

7~20

60~75

40~60

20~45

40~50

0~3

-20~10

0~15

3~18

40~75

65~75

1~10

0~23

0~60

-20~20

-20~20

0~1

-15~0

0

0~15

Heating Auto Curve

Settings (Zone 1)

Heating Auto Curve

Settings (Zone 2)

Frost Protection

Setting Temperature A @ OAT -20°C (°C)

Setting Temperature B @ OAT T1 (°C)

Setting Temperature C @ OAT T2 (°C)

Setting Temperature D @ OAT T3 (°C)

Setting Temperature E @ OAT 20°C (°C)

Auto Curve - Temperature Shift (K)

Outside temperature TO (°C)

Zone 2 water temperature setting method

0 = Percentage of Zone 1 temperature (FC31)

1 = Zone 2 auto curve (FCA3 ~ A5)

Ratio Of Zone 2 In Zone 1 Auto Mode (%)

Setting temperature A’ at TO (°C)

Setting te mperature B’ at T1 (°C)

Setting temperature E’ at 20°C (°C)

Function enabled / disabled

0 = frost protection disabled

1 = frost protection enabled

Frost protection setting temperature (°C)

Frost protection

– schedule end day

Frost protection

– schedule end time

2C

2D

2E

2F

30

27

A1

A2

31

A3

A4

A5

3A

3B

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

12

13

20~55 (60)

20~55 (60)

20~55 (60)

20~55 (60)

20~55(60)

-5~5K

(-30)-20~20

0~1

0~100%

20~55 (60)

20~55 (60)

20~55 (60)

0~1

10~20

0~20

0~23

34

Default

0

0

3

6

75

75

7

22

30

0

-10

25

7

75

40

55

20

55

20

38

45

0

0

80

40

35

20

1

30

25

20

0

-20

-10

0

10

40

35

15

0

0

Back Up Heater Control

Night Setback

CDU Night Time Low

Noise Operation

Pump Control

Function Code Setting

Function Code

Setting Address

Hydro

Unit

Remote

Controller

Sets the time interval before reducing back up heater steps

0=5min, 1=10min, 2=15min, 3=20min

Sets the time interval before increasing back up heater steps

0=10min, 1=20min, 2=30min, 3=40min

Allows the back up heater control to be enabled / disabled by the outside air temperature (TO≥FCB8)

0=normal control, 1=20°C, 2=15°C, 3=10°C,

4=5°C, 5=0°C, 6=-5°C

Allows the back up heater control to be enabled / disabled by the water temperature difference (during defrost) of the system

0=0K, 1=10K, 2=20K,3=30K, 4=40K

Recommended setting FCB9 = 2

Setback temperature (K)

Zone selection

0=Zones 1 & 2, 1=Zone1only

Setback start time (hour)

Setback end time (hour)

Low noise control enabled / disabled

0=control disabled, 1=control enabled

Low noise control start time (hour)

Low noise control end time (hour)

Hydro unit pump (P1) synchronisation:

0 = P1 stops when in DHW mode and the electric cylinder heater is energised (no heating demand)

1 = P1 runs continuously

Pump P1 operation ON/OFF controlled by room temperature:

0 = Pump P1 operates continuously

1 = Pump P1 synchronised with room temperature control. When using the room temperature controller or external room thermostat, pump P1 will STOP when the room air temperature reaches thermo OFF condition

Pump P2 operation in cooling mode:

0 = Pump P2 operates continuously

1 = Pump P2 OFF in when cooling mode selected

Pump P1 control using TO sensor (heating mode only):

P1 OFF when TO>set value in FC9E

(DPSW10_2 must be ON)

A-rated pump (P1) speed control. Changes the percentage duty of the PWM control:

00 = 100% PWM duty (Max. RPM)

01 = 90%

02 = 80%

03 = 70%

04 = 60%

05 = 50%

Pump P1 interval operation depending on outside air temperature (heating mode)

0=continuous run, 1=20°C, 2=15°C, 3=10°C,

4=5°C, 5=0°C, 6=-5°C

Pump P1 interval operation depending on outside air temperature (cooling mode)

0=continuous run, 1=35°C, 2=30°C, 3=25°C

Sets Pump P1 OFF time during system thermostat OFF operation

0=5min, 1=10min, 2=15min, 3=20min,

4=25min, 5=30min

35

33

34

B8

(NEW)

B9

(NEW)

5A

65

64

9E

A0

BA

(NEW)

BB

(NEW)

BC

(NEW)

26

58

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0E

0F

09

0A

0B

Range

0~3

0~3

0~6

0~4

0~1

0~1

0~1

10~30

0~5

0~6

0~3

0~5

3~20

0~1

0~23

0~23

0~1

0~23

0~23

Default

1

0

0

0

0

0

0

20

0

0

0

1

5

0

22

06

0

22

06

Function Code Setting

Auxillary Boiler / Heat

Pump Operation

Room Temperature

Control

Hydro Unit 2 Way Valve

Operation Control

Hydro Unit 3 Way Valve

Operation Control

Boiler / heat pump synchronisation. Allows the controlling device to be set:

0 = Boiler & heat pump synchronised. The heat pump is the controlling device. When TWI reaches the target water temperature of the hydro unit the boiler output switches OFF

1 = Boiler & heat pump not synchronised. The heat pump and auxillary boiler work as independent devices. When TWI reaches the target water temperature of the hydro unit the boiler output remains ON

System operating mode when TO

≤ FC23:

0 = HP & boiler operation

1 = Boiler only operation (pump P1 remains

ON)

2 = Electric heater operation

3 = Boiler only operation (pump P1 OFF)

Allows A02 error detection to be enabled / disabled when the boiler output is ON

0=A02 enabled. When TWI,TWO or THO

70°C then the boiler output is switched OFF

1=A02 disabled. When TWI,TWO or THO

70°C then the boiler output remains ON

Room temperature control (2 nd

RC) selection:

0 = control disabled

1 = control enabled

Setting room temperature range (2 nd

RC):

Cooling room temperature upper limit

Setting room temperature range (2 nd

RC):

Cooling room temperature lower limit

Setting room temperature range (2 nd

RC):

Heating room temperature upper limit

Setting room temperature range (2 nd

RC):

Heating room temperature lower limit

Room temperature offset - HEATING (offset between actual room temperature and measured room temperature)

Room temperature offset - COOLING (offset between actual room temperature and measured room temperature)

Sets water temperature when HP to restart when the control is in A zone (based on TWI control)

Initial target water temperature

– COOLING

(2 nd

RC or external room thermostat)

Initial target water temperature

– HEATING

(2 nd

RC or external room thermostat)

Sets water temperature when HP to restart when the control is in A zone (based on TWI control: FCB1 = 2)

Selects method for setting the initial target water temperature

0=fixed temperature using FC9D, 1=auto curve

Sets the operating logic for the 2 way valve in

COOLING mode:

0 = Valve energised during COOLING

1 = Valve de-energised during COOLING

Sets the operating logic for the 3 way diverting valve:

0 = Valve energised during hot water operation

1 = Valve de-energised during hot water operation

36

Function Code

Setting Address

Hydro

Unit

Remote

Controller

Range Default

3E

5B

62

-10~10

20~37

7~25

20~55

20~37

0~1

0~1

15~30

15~30

15~30

15~30

-10~10

03

-

-

-

-

-

-

-

-

-

-

02

-

B2

96

9D

B2

B5

40

92

93

94

95

-

3C

54

-

-

-

-

-

0~1

0~2

0~1

0~1

0~1

0

3

0

0

0

-1

25

20

40

25

0

0

29

18

29

18

-1

Default Function Code Setting

E-Stop Switch Logic /

System Restart &

TEMPO control

Zone 2 Mixing Valve

Control

Cooling Operation

Remote Controller Time

Display Format

Remote Controller Alarm

Tone

Remote Controller Pump

P2 Icon Display

Function Change for

Option PCB (connected to CN209)

Function Change for

Option PCB (connected to CN210)

Hydro Unit Capacity

Setting

Forced stop input

– switch logic:

0=contacts OPEN > CLOSE system STOP.

System restart with remote controller

1=Contacts CLOSE > OPEN system STOP.

System restart with remote controller

2=Contact CLOSE > OPEN system STOP.

Contact OPEN > CLOSE system restart

3=Contact OPEN > CLOSE system STOP.

Contact OPEN > CLOSE (2 nd

time) system restarts (PULSE INPUT)

System restart logic / TEMPO control:

0=system restarts in heating and hot water mode

1=System restarts in last mode prior to stopping

2=System restarts in hot water mode

3=System restarts in heating mode

4=TEMPO control 1: all electric heaters disabled

5=TEMPO control 2: HP and all electric heaters disabled

Sets the specified drive time for the mixing valve (x10sec)

Sets the sample time (drive OFF) period for the mixing valve control (minutes)

Enables or disables cooling mode

0= Cooling & heating modes enabled

1=Cooling mode disabled

Sets the format for the time display on the remote controller:

0 = 24hr clock display

1 = 12hr clock display

Enables or disables the alarm tone, from the remote controller, when the system generates a fault code alarm:

0 = alarm tone OFF

1 = alarm tone ON

Enables or disables the display icon for pump

P2:

0 = P2 icon not displayed

1 = P2 icon displayed

Sets the output function of the option PCB connected to CN209 on the hydro unit PCB:

0 = EMG terminals

– output ON during defrost,

OPERATION terminals

– output ON when compressor is running

1 = EMG terminals

– output ON when error/alarm detected, OPERATION terminals

– output ON during operation (remote controller

ON)

Sets the input function of the option PCB when connected to CN210

0=S1-external cylinder thermostat, S2-external

STOP

1=S1-hot water mode ON/OFF, S2-heating mode ON/OFF

Must be used in conjunction with DPSW02_3,

FC52 & FC61

Sets the hydro unit capacity (804XWH**E &

1404XWH**E). This code is factory set but setting required for PCB replacement or if FC reset completed

0012 = 804XWH**/P804XWH**E1

0015 = P1104XWH**E1

0017 = 1404XWH**E1

Function Code

Setting Address

Hydro

Unit

Remote

Controller

Range

52

61

0C

59

02

-

-

42

67

B6

01

-

-

-

-

-

05

11

-

-

-

-

0~3

0~5

3~24

1~30

0~1

0~1

0~1

0~1

0~1

0~1

0012~0017

0

0

6

4

0

0

1

0

0

0

Depending on hydro unit model code

37

CAUTION

The following procedures require access to the hydro unit electrical box while the system electrical supply is switched ON

Please ensure all National and Local regulations are followed with regards to working on LIVE equipment

Function Code Reset Procedure:

The following procedure explains how to reset the hydro unit function codes back to the factory default settings:

1. Turn the ESTIA system OFF using the ESTIA remote controller

2. Turn OFF the power supply to the ESTIA system

3. Remove the hydro unit front cover and the cover to the hydro unit electrical box

4. Set DPSW06_1 and DPSW06_2, on the hydro unit PCB, to ON

5. Turn ON the power supply to the ESTIA system

– the yellow LED, near the MCU, will start to flash

(SLOW)

6. Press and hold the tactile switch, SW07, for 15 seconds. During this time the yellow LED will go through a sequence of flashing / LED OFF / LED ON

7. Turn OFF the power supply to the ESTIA system

8. Set DPSW06_01 and DPSW06_2, on the hydro unit PCB, to OFF

9. Replace the cover to the hydro unit electrical box and the front cover for the hydro unit

10. Turn ON the power supply to the ESTIA system

11. Reset function code FC01 to the correct capacity code. L09 fault code will be displayed if FC01 is not set to show the correct capacity setting for the system

SW01, SW07 & DPSW06 Location

SW01

Yellow LED

38

DPSW06

Tactile switch SW07

Component Operation Check Mode using Hydro Unit PCB:

This mode allows the commissioning engineer to check the operation of various components (pump, 2 way valve, 3 way valve etc.) installed in the heating circuit.

1. Turn the ESTIA system OFF using the ESTIA remote controller

2. Turn OFF the power supply to the ESTIA system

3. Remove the hydro unit front cover and the cover to the hydro unit electrical box

4. Set DPSW06_2 to ON

5. Turn ON the electrical supply to the ESTIA system

6. Turn rotary switch SW01 to position 1 and press and hold the tactile switch, SW07, for 8 seconds

7. The operation of the heating circuit components can be checked by rotating SW01 to the relevant

5

6

7

11

12

13

14

15 position detailed in the table below

8. Set DPSW06_2 to OFF

9. Replace the cover to the hydro unit electrical box and the front cover for the hydro unit

SW01

Pos

1

2

3

4

8

9

10

16

None

Heating Circuit

Component

2 way valve

3 way diverting valve

Mixing valve

Component Operation Using Check Mode

-

Cycle: valve ON for 2 sec ~ valve OFF for 3 sec

Cycle: Drive valve OPEN 30 sec ~ Drive valve

CLOSED 30 sec

Hydro unit pump (P1)

External water pump (P2)

Pump ON 20 sec

Pump ON 20 sec

None (reserved) -

Hydro unit back up heaters Cycle: stage 1 ON, stage 2 ON, all OFF every

20 sec

DHW cylinder electrical heater

Booster heater output

Alarm output*

Boiler output*

Defrost output*

Compressor ON output*

None

Hydro unit pump (P1) continuous operation

Cycle: Heater ON 10 sec ~ heater OFF 10 sec

Cycle: heater output ON 10 sec ~ heater output

OFF 10 sec

Cycle: output ON 10 sec ~ output OFF 10 sec

Cycle: output ON 10 sec ~ output OFF 10 sec

Cycle: output ON 10 sec ~ output OFF 10 sec

Cycle: output ON 10 sec ~ output OFF 10 sec

-

Continuous operation of hydro unit pump (P1)

Comments

-

Hydro unit pump will operate

Hydro unit pump will operate

Do not operate the hydro unit pump continuously if there is no water in the heating circuit

SW01, SW07 & DPSW06 Location

SW01

Yellow LED

39

DPSW06

Tactile switch SW07

System Installation

– Set Up Examples

1 Zone Heating

Equipment Required:

DPSW Settings:

NOTE: For ESTIA Powerful type DPSW13_4 = ON

DPSW11_2 = ON: Hot water cylinder electric heater disables

DPSW12_1 = ON: Hot water cylinder not connected to system

All other DPSW’s set in the OFF position.

Function Code Settings:

FC No

1A

1B

FC Description

Heating

– upper temperature set point limit - Zone 1( °C)

Heating

– lower temperature set point limit - Zone 1( °C)

Please check the following pages for the set-up of:

External room thermostat

Auto curve set up

Room temperature controller (HWS-AMS11-E) pg.40 pg.41 pg.43

FC Range Default Setting

37 ~ 55 55

20 ~ 37 20

Note: Care should be taken when setting FC1A if the heating emitter used for Zone 1 is under floor heating. If FC1A is set to high there is a risk that the floor surface could be damaged.

40

1 Zone Heating with Domestic Hot Water

Equipment Required

DPSW Settings:

NOTE: For ESTIA Powerful type DPSW13_4 = ON

All DPSW’s set in the OFF position.

DPSW 13_1 to be set depending on the type of 3 way diverting valve fitted(2 wire / spring return, 3 wire SPST or 3 wire SPDT)

Function Code Settings:

FC No

1A

1B

1E

1F

20

21

22

24

25

FC Description

Heating

– upper temperature set point limit - Zone 1( °C)

Heating

– lower temperature set point limit - Zone 1( °C)

Hot water

– upper temperature set point limit (°C)

Hot water

– lower temperature set point limit (°C)

Heat pump start temperature

– hot water operation (TTW:°C)

Heat pump stop temperature

– hot water operation (TTW:°C)

Hot water / heating priority switching temperature (°C)

Hot water temperature compensation

– OAT start temperature (°C)

Hot water set point temperature

– compensation temperature (°C)

FC Range Default Setting

37 ~ 55 55

20 ~ 37

50 ~ 80

20

75

40 ~ 60

20 ~ 45

40 ~ 50

-20 ~20

-20 ~ 10

0 ~ 15

40

38

45

0

0

3

Please check the following pages for the set-up of:

External room thermostat

Room temperature controller (HWS-AMS11-E)

Auto curve set up

Hot water anti bacteria function

Hot water boost function pg.40 pg.41 pg.43 pg.47 pg.48

Note: Care should be taken when setting FC1A if the heating emitter used for Zone 1 is under floor heating.

If FC1A is set to high there is a risk that the floor surface could be damaged.

41

Zone 1 Heating With Existing Auxiliary Boiler

Equipment Selection:

DPSW Settings:

NOTE: For ESTIA Powerful type DPSW13_4 = ON

DPSW11_2 = ON: Hot water cylinder electric heater disables

DPSW12_1 = ON: Hot water cylinder not connected to system

DPSW13_2 = ON: Boiler output control enabled (use in conjunction with FC23)

All other DPSW’s set in the OFF position.

Function Code Settings:

FC No FC Description

1A Heating

– upper temperature set point limit - Zone 1( °C)

1B Heating

– lower temperature set point limit - Zone 1( °C)

FC Range Default Setting

37 ~ 55 55

20 ~ 37 20

-10 23 Trigger temperature to turn boiler output (on TCB-PCIN3E) ON (°C) -20 ~ 20

Boiler / heat pump synchronisation: 0 = synchronised; 1 = not

3E synchronised

0 ~ 1 0

Please check the following pages for the set-up of:

External room thermostat

Room temperature controller (HWS-AMS11-E)

Auto curve set up

Auxiliary boiler output pg.40 pg.41 pg.43 pg.44

42

1 Zone Heating & Cooling With Domestic Hot Water

Equipment Selection:

DPSW Settings:

NOTE: For ESTIA Powerful type DPSW13_4 = ON

All DPSW’s set in the OFF position.

DPSW 13_1 to be set depending on the type of 3 way diverting valve fitted

Function Code Settings:

FC No FC Description

1A Heating

– upper temperature set point limit - Zone 1( °C)

1B Heating

– lower temperature set point limit - Zone 1( °C)

1E Hot water

– upper temperature set point limit (°C)

1F Hot water

– lower temperature set point limit (°C)

20 Heat pump start temperature

– hot water operation (TTW:°C)

21 Heat pump stop temperature

– hot water operation (TTW:°C)

Please check the following pages for the set-up of:

External room thermostat

Room temperature controller (HWS-AMS11-E)

Auto curve set up

Hot water anti bacteria function

Hot water boost function pg.40 pg.41 pg.43 pg.47 pg.48

FC Range Default Setting

37 ~ 55

20 ~ 37

50 ~ 80

40 ~ 60

20 ~ 45

40 ~ 50

22 Hot water / heating priority switching temperature (°C) -20 ~20

24 Hot water temperature compensation

– OAT start temperature (°C)

-20 ~ 10

25 Hot water set point temperature

– compensation temperature (°C)

0 ~ 15

02

0F

Cooling operation: 0 = heating & cooling available; 1 = heating only available

Cooling / hot water priority setting: 0 = cooling priority

– hot water produced by electric cylinder heater; 1 = hot water priority

– hot water produced by heat pump

0 ~ 1

0 ~ 1

55

20

75

40

38

45

0

0

3

1

0

43

2 Zone Heating With Domestic Hot Water

Equipment Selection:

DPSW Settings:

NOTE: For ESTIA Powerful type DPSW13_4 = ON

DPSW 10_3: Set switch to ON if end user requests pump P2 (Zone 2 pump) is synchronised with pump

P1 (hydro unit)

DPSW12_3 = ON: Zone 2 control enabled

DPSW 13_1 to be set depending on type of 3 way diverter valve fitted (2 wire / spring return, 3 wire

SPST or 3 wire SPDT)

All other DPSW’s set in the OFF position

Function Code Settings:

FC No FC Description FC Range

1A Heating

– upper temperature set point limit - Zone 1( °C)

1B Heating

– lower temperature set point limit - Zone 1( °C)

1C Heating

– upper temperature set point limit – Zone 2 (°C)

1D Heating

– lower temperature set point limit – Zone 2 (°C)

1E Hot water

– upper temperature set point limit (°C)

1F Hot water

– lower temperature set point limit (°C)

20 Heat pump start temperature

– hot water operation (TTW:°C)

21 Heat pump stop temperature

– hot water operation (TTW:°C)

37 ~ 55

20 ~ 37

37 ~ 55

20 ~ 37

50 ~ 80

40 ~ 60

20 ~ 45

40 ~ 50

22 Hot water / heating priority switching temperature (°C) -20 ~20

24 Hot water temperature compensation

– OAT start temperature (°C)

-20 ~ 10

25 Hot water set point temperature

– compensation temperature (°C)

0C Specified drive time for mixing valve

– 0° ~ 90° (10sec)

0 ~ 15

3 ~ 24

59

Sets the sample time (drive OFF) period, for the mixing valve control (mins)

1 ~ 30

44

Default

Setting

55

20

55

20

75

40

38

45

0

0

3

6

4

Please check the following pages for the set-up of:

External room thermostat

Room temperature controller (HWS-AMS11-E)

Auto curve set up

Mixing valve set up

Hot water anti bacteria function

Hot water boost function pg.40 pg.41 pg.43

pg.46 pg.47 pg.48

Note: Care should be taken when setting FC1C if the heating emitter used for Zone 2 is under floor heating. If FC1C is set to high there is a risk that the floor surface could be damaged.

2 Zone Heating with Auxiliary Boiler

Equipment Selection:

DPSW Settings

NOTE: For ESTIA Powerful type DPSW13_4 = ON

DPSW12_3 = ON: Zone 2 control enabled

DPSW 13_1 to be set depending on type of 3 way diverter valve fitted (2 wire / spring return, 3 wire

SPST or 3 wire SPDT)

DPSW13_2 = ON: Boiler output control enabled (use in conjunction with FC23)

All other DPSW’s set in the OFF position

45

Function Code Settings:

FC No FC Description FC Range

1A Heating

– upper temperature set point limit - Zone 1( °C)

1B Heating

– lower temperature set point limit - Zone 1( °C)

1C Heating

– upper temperature set point limit – Zone 2 (°C)

1D Heating

– lower temperature set point limit – Zone 2 (°C)

1E Hot water

– upper temperature set point limit (°C)

1F Hot water

– lower temperature set point limit (°C)

20 Heat pump start temperature

– hot water operation (TTW:°C)

21 Heat pump stop temperature

– hot water operation (TTW:°C)

22 Hot water / heating priority switching temperature (°C)

37 ~ 55

20 ~ 37

37 ~ 55

20 ~ 37

50 ~ 80

40 ~ 60

20 ~ 45

40 ~ 50

-20 ~20

23 Trigger temperature to turn boiler output (on TCB-PCIN3E) ON (°C) -20 ~ 20

24 Hot water temperature compensation

– OAT start temperature (°C)

-20 ~ 10

25 Hot water set point temperature

– compensation temperature (°C)

0 ~ 15

Boiler / heat pump synchronisation: 0 = synchronised; 1 = not

3E synchronised

0C Specified drive time for mixing valve

– 0° ~ 90° (10sec)

0 ~ 1

3 ~ 24

59

Sets the sample time (drive OFF) period, for the mixing valve control (mins)

Please check the following pages for the set-up of:

External room thermostat

Room temperature controller (HWS-AMS11-E)

Auto curve set up

Auxiliary boiler output

Mixing valve set up pg.40 pg.41 pg.43 pg.44 pg.46

46

1 ~ 30

Default

Setting

55

20

55

20

75

40

38

45

0

-10

0

3

0

6

4

Remote Controller Schedule Timer

On an ESTIA site the customer requires the hot water function to be ON between the hours of 01:00 and 06:00. The customer requires the set point for the domestic hot water to be set to 65°C

For space heating the customer requires the ESTIA to run in heating mode for the following periods:

Period 1: 07:00 ~ 10:00

Period 2: 15:00 ~ 22:00

The customer is using radiators as the heating emitters and requires the water set point temperature to be set to 50°C. The schedule timer must be set the same for all days of the week.

For each day the timer function will be set as shown below:

STEP No. Time Function

STEP 1 01:00 DHW ON, DHW set point = 65°C

STEP 2 06:00 DHW OFF

STEP 3 07:00 Zone 1 ON, heating mode, water set point = 50°C

STEP 4 10:00 Zone 1 OFF

STEP 5 15:00 Zone 1 ON, heating mode, water set point = 50°C

STEP 6 22:00 Zone 1 OFF

Schedule Timer Set Up

1. Access remote controller (RC) timer function

– press the SCHEDULE button for a minimum of 4 seconds. Check the RC display changes to show the schedule timer display

2. Select the required day for the schedule timer

– press the DAY button until the ▼symbol is displayed above the required day. Press the SET button to accept the command

3. Set up the required timer steps for the selected day

– press the STEP button until STEP 1 is displayed on the RC:

Press the STEP button > check STEP 1 is displayed on the RC

Press the SET button

Press the TIME

▼▲buttons to set 01:00 on the time display of the RC

Press the HOT WATER button to set the hot water function ON > check that a numerical temperature is displayed on the RC for the hot water function

Press the TEMPERATURE

▼▲ buttons to set the 65°C hot water set point

Press the SET button

Press the STEP button > check STEP 2 is displayed on the RC

Press the SET button

Press the TIME

▼▲buttons to set 06:00 on the time display of the RC

Press the HOT WATER button to set the hot water function to OFF > check that the

RC display changes to - - - - for the hot water function

Press the SET button

Press the STEP button > check STEP 3 is displayed on the RC

Press the TIME

▼▲buttons to set 07:00 on the time display of the RC

Press the ZONE1, 2 button to set the space heating function ON > check that a numerical temperature is displayed on the RC for the zone 1 function

Press the OPERATING MODE button > check that the heating mode symbol is displayed on the RC

Press the TEMPERATURE

▼▲ buttons to set the 50°C zone 1 set point

Press the SET button

Press the STEP button > check STEP 4 is displayed on the RC

Press the SET button

Press the TIME

▼▲buttons to set 10:00 on the time display of the RC

Press the ZONE1, 2 button to set the space heating function OFF > check that the

RC display changes to - - - - for zone 1

47

Press the SET button

Press the STEP button > check STEP 5 is displayed on the RC

Press the SET button

Press the TIME

▼▲buttons to set 07:00 on the time display of the RC

Press the ZONE1, 2 button to set the space heating function ON > check that a numerical temperature is displayed on the RC for the zone 1 function

Press the OPERATING MODE button > check that the heating mode symbol is displayed on the RC

Press the TEMPERATURE

▼▲ buttons to set the 50°C zone 1 set point

Press the SET button

Press the STEP button > check STEP 4 is displayed on the RC

Press the SET button

Press the TIME

▼▲buttons to set 10:00 on the time display of the RC

Press the ZONE1, 2 button to set the space heating function OFF > check that the

RC display changes to - - - - for zone 1

Press the SET button

4. Copy the data, shown above, for use on other days of the week:

Press the STEP button until STEP C is displayed on the RC

Press the SET button

5. Paste the copied timer schedule into the other days of the week

Press the DAY button until the

▼symbol is displayed above all day’s of the week

(timer schedule to run on all days of the week)

Press the SET button

Repeat the above steps for all the days of the week

6. Exit schedule timer function

Press the SCHEDULE button > check that the RC display changes back to the main screen and that CLOCK icon, on the RC display is flashing

Press the SET button > check that the CLOCK icon changes from flashing to continuously lit.

The timer schedule is now set

48

ESTIA - System Set Up

Please refer to the ESTIA Service Manual for a detailed description for each of the controls / functions listed below

1. External room thermostat

Isolate the electrical supply to the ESTIA system and remove the cover to the electrical box in the hydro unit

Install the room thermostat into the room to be monitored / controlled. Care must be taken to ensure that the thermostat is installed in the correct position and away from the influences of other external heat sources (sunlight, radiators etc.). Follow the thermostat manufacturers installation instructions for correct positioning

Connect the room thermostat as to the TCB-PCBMO3E option PCB as shown in the diagram above

In the hydro unit set DPSW 02_4 to ON

For HEATING mode:

Set FC1A to the required setting. This will set the maximum target water temperature of the system when running in heating mode. This setting is particularly important

– if the heating emitter used is under floor heating then damage may be caused to the floor surface if FC1A is set too high

Set FC1B to the required setting. This will set the minimum target water temperature of the system when running in heating mode

Set FC9D to the required setting. This will set the initial target water temperature of the system, when the electrical supply is restored to the ESTIA system, when running in heating mode

For COOLING mode:

Set FC18 to the required setting (only required if cooling mode is available). This will set the maximum target water temperature, of the system when running in cooling mode

Set FC19 to the required setting (only required if cooling mode is available). This will set the minimum target water temperature, of the system when running in cooling mode

Set FC96 to the required setting. This will set the initial target water temperature of the system, when the electrical supply is restored to the ESTIA system, when running in cooling mode

Replace the cover on the electrical box in the hydro unit and restore the electrical supply to the ESTIA system

NOTE:

When the external thermostat is connected the end user will be unable to set any water temperatures, for the space heating or space cooling functions, on the remote controller. The system is controlled by the OPEN or CLOSED contact on the room thermostat.

49

2. Room temperature control

Isolate the electrical supply to the ESTIA system

Install the 2 nd

ESTIA remote controller (RC), for room temperature control, using 2 core screened cable. The maximum cable length specified, for the 2 nd

RC is 50m

Position the 2 nd

RC as detailed in the installation instructions supplied with the controller. It is important to position the 2 nd

RC correctly as poor positioning will affect the accuracy of the room temperature control

The remote controllers need to be configured as header and follower controllers using the

DPSW’s on the back of each remote controller (see below).

For example a customer requests that the remote controller on the hydro unit is set as the header device and the 2 nd

RC, in the room, is set as the follower to measure r oom air temperature. Set the DPSW’s as shown below:

Remote Controller DPSW

– Bit Number

1 2 3 4

Hydro unit

(HEADER)

2 nd

RC

(FOLLOWER)

OFF

ON

OFF

ON

OFF

OFF

OFF

OFF

Note:

Do not set DPSW2, on both the HEADER and FOLLOWER remote controllers, to ON.

This will result in poor temperature control in the room

Restore the electrical supply to the ESTIA system

Change FC40 from 0 to 1. This will allow the ESTIA system to control using the air temperature measurement form the 2 nd

RC

For HEATING mode:

Set FC94 to the required setting. This will set the maximum room air temperature that can be selected on the remote controllers when running in heating mode.

Set FC95 to the required setting. This will set the minimum room air temperature that can be selected on the remote controllers when running in heating mode.

Set FC9D to the required setting. This will set the initial target water temperature of the system, when the electrical supply is restored to the ESTIA system, when running in heating mode

Set FCB1 to the required setting. This will select the required control option for the room temperature control when running in heating mode

For COOLING mode:

Set FC92 to the required setting. This will set the maximum room air temperature that can be selected on the remote controllers when running in cooling mode

Set FC93 to the required setting. This will set the minimum room air temperature that can be selected on the remote controllers when running in cooling mode.

Set FC96 to the required setting. This will set the initial target water temperature of the system, when the electrical supply is restored to the ESTIA system, when running in cooling mode

System Commissioning:

Measure the actual room temperature using a locally supplied temperature measuring device.

Measure the room temperature using the sensor temperature monitoring function on the remote controller (see page 51 -use code no. 03). This must process be completed on the remote controller that will be used to measure the room temperature

Compare the 2 temperature readings. If the temperature readings are the same then there is no requirement to adjust the room temperature offset FC’s. If there is a difference between the 2 temperature readings then adjust the room temperature offset using remote controller function codes (RCFC) RCFC02 for heating mode and RCFC03 for cooling mode

50

For example:

Temperature

Measurement

Actual

Remote Controller

Measured

Temperature

23°C

23°C

RCFC Adjustment*

No adjustment required

Temperature

Measurement

Actual

Remote Controller

Measured

Temperature

23°C

25°C

RCFC Adjustment*

Change from -1 to -3

Temperature

Measurement

Actual

Remote Controller

Measured

Temperature

25°C

23°C

RCFC Adjustment*

Change from -1 to +1

REMEMBER: The default offset setting is -1. Please consider the default offset when making any changes to either RCFC02 or RCFC03

51

3. Auto curve control

The auto curve function allows the software on the hydro unit PCB to automatically calculate the target water temperature of the system depending the outdoor air temperature (OAT). This function is only available for 1 zone space heating (water temperature control).

The auto curve function is NOT available when:

Using an external room thermostat

Using a 2 nd

RC for room temperature control

Running the system in cooling mode

The auto curve control is set using function codes and by pressing the “Auto” button on the remote controller.

To set the auto curve temperatures:

STOP the ESTIA system using the remote controller

Set the following function codes to the required setting:

FC27: Sets the auto curve temperature shift / curve adjustment

FC29: Sets the OAT control temperature at point T1 on the diagram above

FC2B: Sets the OAT control temperature at point T3 on the diagram above

FC2C: Sets the target water temperature for the system when the OAT is -20°C

FC2D: Sets the target water temperature for the system when the OAT is at T1 position

FC2E: Sets the target water temperature for the system when the OAT is at T2 position (0°C)

FC2F: Sets the target water temperature for the system when the OAT is at T3 position

FC30: Sets the target water temperature for the system when the OAT is 20°C

FC31: Sets the percentage ratio of the Zone 1 target water temperature to be applied for

Zone 2 control

To activate the auto curve control:

Press on the remote controller to activate space heating

Press on the remote controller to activate the auto curve control

When the auto curve control is active the numerical temperature display for Zone 1 and Zone

2, on the remote controller, is displayed with “A” for each zone

NOTE: If the heating emitter for Zone 2 is an under floor heating circuit then care should be taken when setting FC31 to prevent any risk of damaging the floor surface due to high water temperatures

52

Zone 2 Auto Curve:.

To set Zone 2 auto curve temperatures:

STOP the ESTIA system using the remote controller

Set the following function codes to the required setting:

FC27: Sets the auto curve temperature shift / curve adjustment

FCA1: Sets the OAT control temperature at point T0 on the diagram above

FCA2: Sets the water temperature setting method for Zone 2

FCA3: Sets the target water temperature for the system when the OAT is -20°C

FCA4: Sets the target water temperature for the system when the OAT is -10°C

FCA5: Sets the target water temperature for the system when the OAT is 20°C

To activate the auto curve control:

Press on the remote controller to activate space heating

Press on the remote controller to activate the auto curve control

When the auto curve control is active the numerical temperature display for Zone 1 and Zone

2, on the remote con troller, is displayed with “A” for each zone

NOTE:

For the system to operate correctly with Zone 1 and Zone 2 auto curve selected the

temperatures set for Zone 1 auto curve operation must be greater or equal to the temperatures set for Zone 2 auto curve operation

If the heating emitter for Zone 2 is an under floor heating circuit then care should be

taken when setting FC31 to prevent any risk of damaging the floor surface due to high water temperatures

53

4. Auxilliary boiler control

Isolate the electrical supply to the ESTIA system and remove the cover to the electrical box in the hydro unit

Connect the start signal for the auxillary boiler to terminals 3 & 4 (EMG) of the TCB-PCIN3E option PCB as shown in the diagram above

Set DPSW 13_2 to ON. This enables the control for boiler output control

Replace the cover on the electrical box in the hydro unit and restore the electrical supply to the ESTIA system

Set the following function codes to the required setting:

FC23: Sets the OAT where the boiler output is switched ON

FC3E: Allows the boiler output to be synchronised with the heat pump or to run as an independent device

If FC3E is set to 0 then the boiler is synchronised with the heat pump. In this condition the heat pump and the boiler will run at the same time. When the water temperature, inside the hydro unit, reaches thermo OFF conditions then the heat pump will STOP and the boiler output will turn OFF

If FC3E is set to 1 then the heat pump and the boiler will run as independent devices. When the water temperature, inside the hydro unit, reaches thermo OFF conditions then the heat pump will STOP. However with FC3E = 1 the boiler output will remain ON. The temperature of the water, from the boiler, will be controlled by the boilers’ own thermostat

FC5B: Sets the operating mode for the system when the boiler output is ON:

FC5B = 0: The heat pump and the boiler will operate when OAT ≤ FC23

FC5B = 1: Boiler only operation (in this mode of operation the hydro unit pump will continue to run)

FC5B = 2: Electric heater only operation (in this mode of operation the hydro unit pump will continue to run)

FC5B = 3: Boiler only operation (in this mode of operation the hydro unit pump will

STOP and the boiler output will stay ON)

54

How to determine the setting for FC23:

The boiler output is used to switch an external boiler ON / OFF to support the ESTIA system during low ambient conditions. It is possible to estimate the switching temperature, required for the boiler output, using the system/installation capacity graph generated by the ESTIA Sales Support Software

(see graph below).

Additional heat source required

A

Required capacity supplied by heat pump capacity only

On the graph above:

The heat pump output capacity is represented by the red line

The heat load for the installation / site is represented by the blue line

The point where the 2 lines cross, point A, represents the equilibrium point of the system.

This is where the capacity output from the heat pump is equal to the heat load requirements of the installation / site. On the example above the equilibrium point is reached when the outdoor air temperature (OAT) is approximately 1°C

The area to the left of the equilibrium point and between the red and blue lines represents the area where an additional heat source is required to support the heat pump output

From the graph it can be seen that when the outdoor air temperature is -4°C there is a requirement for an additional heat source (electric back up heaters, existing boiler etc.) to supply the installation with approximately 3.5kW of heating

For the example above with FC23 set to 1°C then the boiler output will turn ON when the

OAT decreases to 1°C. The boiler will support the output of the heat pump if the OAT is 1°C or less

There is a 5K temperature differential between the boiler output ON / OFF temperatures. If the boiler output is set to turn ON when the OAT is 1 °C then the boiler output will not turn

OFF until the OAT has reached 6°C

It is possible to set FC23 lower than 1°C however this result in the electric back up heaters supplying some of the heating capacity required from the additional heat source.

55

5. 2 zone heating

– mixing valve set up

The ESTIA system has the ability to control the water temperature in 2 zones using different heating emitters (e.g. zone 1: radiators, zone 2: under floor heating circuits). This is achieved by installing a mixing valve to control the temperature of zone 2.

The mixing valve position is controlled by comparing the water set point temperature for zone 2

(entered on the ESTIA remote controller) and the actual water temperature in zone 2 (measured by the TFI sensor). Depending on the result of the comparison between the two temperatures the mixing valve will either OPEN or CLOSE (in steps) to control the temperature. The hydro unit software has been designed to drive the valve from CLOSED to OPEN in 12 steps (see the ESTIA service manual for a detailed description for the mixing valve control).

It is important that the settings for the mixing valve are set correctly using the hydro unit function codes to achieve accurate temperature control of zone 2.

Connect the mixing valve as shown in the diagram above. The valve connection to

TB04 (in the hydro unit) will depend on whether the valve is an SPST or SPDT type valve

Set DPSW 12_3 to ON. This enables 2 zone control and will allow the end user to enter a temperature set point (for zone 2) on the ESTIA remote controller

Set the following function codes:

Set FC1C to the required setting. This will set the maximum target water temperature of the system when running in heating mode. This setting is particularly important

– if the heating emitter used is under floor heating then damage may be caused to the floor surface if FC1A is set too high

Set FC1D to the required setting. This will set the minimum target water temperature of the system when running in heating mode

Set FC0C. This sets the specified drive time for the mixing valve. The drive time is the time measured to drive the valve through 90°. The drive time for the valve will be displayed in the valve specification data. It is important that this value is set correctly

– this value sets the duration of the mixing valve drive time for each of the 12 steps.

For example

– if the specified drive time for the valve is 60 seconds then the drive time for each of the 12 steps will be 5 seconds (60/12 = 5). For each step of the control power will be applied to the drive valve for a 5 second period.

Setting the value of FC0C bigger or smaller than the actual specified drive time for the valve will result in poor position control of the mixing valve and therefore poor temperature control for zone 2

Set FC59 to the required setting. This sets the temperature measuring period (measured by the TFI sensor) or sampling period between each step drive of the mixing valve. The value of this function code will depend on a number of factors (thermal efficiency of the house, type of heating emitters, size of heating circuits etc.) and so the value set will depend on the knowledge of the installer / commissioning engineer

56

Zone 2 Set: Target water temperature for zone 2

TFI: Actual water temperature of zone 2 measured by the TFI sensor a: 4 minute off time (sample period) between 230V~ pulses (sample period set using FC59) b: AC230V pulse duration determined by dividing the valve opening time (from valve specification) by 12 (the maximum number of pulses available from the hydro unit software)

Example: for a valve with a drive time specification of 60 seconds: b = 60 / 12 = 5 seconds pulse duration

On initial power up the mixing valve drives to the fully CLOSED position and then back to the mid position. This gives the mixing valve a reference position to start the temperature control for zone

2

Once the valve has reached the mid-point reference position there is a 4 minute OFF delay

(sampling period) before the valve drive to the next position. During this time the hydro unit software measures the value of TFI and compares the measured temperature to the target water temperature, for zone 2, set on the ESTIA remote controller

If the temperature, measured by the TFI sensor, is lower than the target water temperature setpoint, then the mixing valve will OPEN by one step and then the software will recalculate the required operation during the next 4 minute OFF period

If the temperature, measured by the TFI sensor, is higher than the target water temperature setpoint, then the mixing valve will CLOSE by one step and then the software will recalculate the required operation during the next 4 minute OFF period

6. Anti bacteria control (hot water mode)

The anti-bacteria control on ESTIA is used to prevent Legionella bacteria in the hot water system.

Set the following function codes:

Hydro unit function code

– FC0A: Sets the water temperature, inside the hot water cylinder, during the anti-bacteria cycle

Hydro unit function code

– FC0B: Sets the duration of the anti-bacteria function once the cylinder water temperature has reached the cycle start temperature set by FC0A

Remote controller function code

– RCFC0C: Sets the anti-bacteria cycle start time

Remote controller function code

– RCFC0D: Sets the anti-bacteria cycle operating frequency

When the function codes have been set press the button on the ESTIA remote controller. This will activate the anti-bacteria cycle set in the function codes above

When the anti-bacteria cycle is activated the anti-bacteria symbol (shown below) will be shown on the ESTIA remote controller display

57

7. Hot water boost control (hot water mode)

The hot water boost function can be used when there is a high demand for hot water. The boost function will heat the cylinder water to the set point temperature quicker than the time taken during normal hot water production.

Set the following function codes for the hot water boost function:

FC08: Sets the duration of the hot water boost function

FC09: Sets the set point temperature, of the water in the cylinder, to be achieved during the hot water boost function

When the above function codes have been set then the hot water boost function is activated by pressing on the ESTIA remote controller

When the hot water boost function is active the following symbol is shown on the ESTIA remote controller display

Test Run

Once you have competed the installation and system configuration conduct a test run (see below). Since the protection setting is disabled in the TEST mode, do not continue a test run longer than 10 minutes.

• Press the TEST button on the remote controller. An indication “TEST” appears on the remote controller.

• Press the ZONE1, 2

butt on and select “heating” with the OPERATE MODE

The pump is activated in 30 seconds.

button.

If air is not released completely, the flow switch is activated to stop operation. Release air again according to the piping procedure. Little air bite is discharged from the purge valve.

• Check that the air bite sound disappears.

• Check that the hydraulic pressure has become the predetermined pressure 0.1 to 0.2 MPa (1 to 2 bar). If the hydraulic pressure is insufficient, replenish water.

• Heating operation starts. Check that the hydro unit starts heating.

• Press the OPERATE MODE button and select “cooling.”

• Cooling operation starts. Check that the hydro unit starts cooling and that the floor heating system is not cooled.

• Press the ZONE1, 2

button to stop operation.

• Press the HOT WATER

• Check that there is no air bite.

button to start hot water supply operation.

• Check that hot water is present at the connection port of the hot water cylinder.

• Press the HOT WATER

• Press the TEST

button to stop the hot water supply operation.

button to exit the test mode.

58

Sensor Temperature Monitoring Function

The sensor sensing temperature is displayed on the remote controller. This function allows you to make sure whether the sensor is installed properly.

1) Press + buttons for four seconds or more.

F1

F2

F3

F4

F5

6A

6D

70

72

73

74

7A

F0

2) Select the Code No. with the TEMP.

Code No. Location Indication

00

buttons.

Control Temperature (Hot water cylinder)

01

02

03

04

06

Hydro unit

Control Temperature (Zone1)

Control Temperature (Zone2)

Remote controller sensor temperature

Condensed temperature (TC)

Water inlet temperature (TWI)

07

08

09

Water outlet temperature (TWO)

Water heater outlet temperature (THO)

Floor inlet temperature (TFI)

0A

0B

0E

60

61

62

63

65

Hot water cylinder temperature sensor (TTW)

Motorized mixing valve position

Lo pressure (Ps)

Heat exchanger temperature (TE)

Outside air temperature (TO)

Refrigerant discharge temperature (TD)

Refrigerant suction temperature (TS)

Heat sink temperature (THS)

Outdoor unit

Service Data

Current value (in the inverter)

Heat exchanger coil temperature (TL)

Compressor operating frequency

Number of revolutions of outdoor fan (lower)

Number of revolutions of outdoor fan (upper)

Outdoor PMV position x1/10

Discharge pressure (PD)

POWERFUL TYPE ONLY

Micro computer energized accumulation time

Hot water compressor ON accumulation time

Cooling compressor ON accumulation time

Heating compressor ON accumulation time

Hydro unit AC pump operation accumulation time

Hot water cylinder heater operation accumulation time

F6 Hydro unit heater operation accumulation time

F7 Booster heater operation accumulation time

3) Press button to exit the test mode.

59

°C

°C

°C

A

°C

Hz rpm rpm pls

X10kPa x100hrs x100hrs x100hrs x100hrs x100hrs x100hrs x100hrs x100hrs

°C

°C

°C

°C step

MPa

°C

°C

Unit

°C

°C

°C

°C

°C

°C

Nondefective operation (program operation)…….No Check code displayed

In order to control the heat pump unit, there are the following operations as the built-in program operations in the microcomputer. If a claim occurs about the operation, please confirm whether it falls under any of the contents in the following table.

If it does, please understand that the symptom is not a defect of the equipment, and it is an operation necessary for the control and maintenance of the heat pump unit.

No. Operation of the heat pump system Explanation

1

2

The compressor sometimes does not operate even within the range of compressor “ON”.

During the hot water supply or heating operation, without reaching the set temperature, the compressor operation frequency stays at a frequency of less than the maximum Hz or lowers down.

The compressor does not operate during the operation of the compressor reboot timer (3 min).

Even after the power activation, the compressor reboot timer continues to be active.

It may be caused by the high temperature release control (release protection control by the temperature of the water heat exchanger) or the current release control.

3

4

5

The “Stop” operation on the remote control will not stop the circulating pump. (The same for hot water supply, heating and cooling)

“ON” on the remote control will not operate the compressor. (It will not operate even after the reboot delay timer elapsed)

When the power is turned ON it starts operation without operating the remote controller

In order to deal with the temperature increase in the heat exchanger after stopping, the operation continues for 1 min after the compressor is stopped.

When the outdoor temperature (TO sensor detection temperature) is -20°C or lower, the heat pump will not operate in order to protect the compressor, and the heater will operate instead.

The auto restart operation may be working.

The antifreeze operation may be working. If the TWI, TWO or THO sensor detects a temperature below 4°C, the operation changes from circulating pump --->> circulating pump + heater.)

Defective operation check codes

How to determine from the check code on the remote control

If the defect is limited by the check code displayed on the remote control, please repair the defect based on the table on the next page.

The check codes are separated into two groups: software and hardware errors.

Since a hardware error cannot be cancelled without a part replacement etc., please perform a repair.

If its abnormality is determined, the abnormality is noticed by indicating the check code on the remote control check code display part while letting off a buzzer.

How to cancel a check code on the remote controller

(1) Press or button (on the operation side) to clear the check code.

(2) Press to stop a buzzer for an abnormality only.

Although the above procedure cancels the check code, the hardware error will be displayed again until the hardware repair is completed.

60

Hydro Unit check codes

Diagnostic functional operation

Check

code

Operational cause

Backup

present

Pump or flowing quantity error

1) Detected by TC sensor TC 63°C is detected in the heating or hot water supply heat pump operation (except for defrosting).

A01

2) Detected by flow switch abnormality When no signal of the flow switch is showing 2 min after the built-in pump operation started.

3) Detection of chattering abnormality in the flow switch input Chattering detection: Detects input changes (OFF

⇔ON) 4 times within 10 seconds during operation.

×

4) Disconnection of the flow switch connector

When the stopped built-in pump starts its operation, the flow switch status is detecting

"water flow".

Automatic

reset

×

Determination and action o…...…. Possible x…. Not possible

Defect frequency confirmation

1. Almost no or little water flow. •

Not enough vent air • Dirt clogging in the water piping system. • The water piping is too long. •

Installation of buffer tank and secondary pump

1. Disconnection of the flow switch connector.

2. Defect of the flow switch.

4

2

4

2

A02

Temperature increase error (heating)

When one of the TWI, TWO and THO sensors exceeds 70°C.

Heating O

Hot water ×

O

1. Check the water inlet, water outlet and heater outlet (TWI,

TWO, THO) sensors.

2. Defect of the backup heater

(defect automatic reset thermostat).

1

A03

Temperature increase error (hot water supply)

When the TTW sensor exceeds 85°C.

Heating O

Hot water ×

A04

Antifreeze operation (1)

1)TWO>20°C condition: 2×TC+TWO < -12°C is detected.

2)TWO 20°C condition: TC+TWO < 4°C is detected.

3)TWI 10°C is detected during defrosting.

A05

Piping antifreeze operation

Activating the heater under the condition of

TWO<4orTWI<4orTHO<4 does not achieve

TWO,TWI,THO 5°C after 30 min elapsed.

A07

Series 4 Standard Type

Pressure switch operation

The pressure switch operates for 300 sec continuously during the heat pump operation

Series 4 Powerful Type

Incorrect outdoor / hydro unit matching (system set up)

A08

Low pressure sensor operation error

The low pressure sensor detected 0.2 MPa or less.

O

O

O

O

O

×

O

×

1. Check the hot water cylinder sensor (TTW).

2. Check the hot water cylinder thermal cut-out.

1

1. Almost no or little water flow. •

Dirt clogging in the water piping system. • The water piping is too long.

2. Check the heater power circuit. •

Power supply voltage, breaker, power supply connection

3. Set the presence of the backup heater.

4. Check the water inlet, water outlet and heat exchange (TWI,

TWO, TC) sensors.

1. Ch eck the heater power circuit. •

Power supply voltage, breaker, power supply connection

2. Check the water inlet, water outlet and heater outlet sensors

(TWI,. TWO, THO).

3. Disconnection of the backup heater.

1. Almost no or little water flow.

2. Defect of the flow switch.

3. On-load operation under the above conditions.

4. Defect in the pressure switch

5. DPSW13_4 setting (OFF =

Standard, ON = Powerful

Heating 8

Hot water 8

Cooling 4

1

1

1. Almost no or little water flow.

2. Defect of the flow switch.

3. On-load cooling or prolonged defrosting (a lot of frost formation) under the above conditions.

8

×

4. Defect in the low pressure sensor.

8

61

Check

code

A09

Diagnostic functional operation

Operational cause

Backup

present

Overheat protection operation

When the thermostat of the backup heater activates during the operation of the heat pump or backup heater. When the thermostat operation is activated while it has been stopped.

O

Automatic

reset

×

A10

Antifreeze operation (2)- cooling mode only

When TC + TWO < -15°C

x ×

Determination and action

1. No water (heating without water) or no water flow.

2. Defect of the flow switch.

3. Defect of the backup heater

(poor automatic reset thermostat).

1. Almost no water flow

2. Defect of the flow switch

3. Low refrigerant charge

Defect frequency confirmation

2

1

10

A11

Operation of the release protection

When the TWO release counts to 10.

A12

Heating, hot water heater

The antifreeze control is detected under the condition of TWI<20°C while TWI>15°C,

TTW>20°C is not detected after the heater backup.

O O

1. Almost no water flow.

2. Defect of the flow switch.

3. Check the water outlet temperature sensor (TWO).

1. Activated by a large load of heating or hot water supply.

2. Check the heater power circuit

(backup or hot water cylinder heater). • Power supply voltage, breaker, power supply connection

10

1

E03

E04

Regular communication error between hydro unit and remote controller

When there is no regular communication from the remote control for 3 min, or when no remote control is equipped.

Regular communication error between hydro unit and outdoor unit

The serial signal cannot be received from outdoor.

F03

TC sensor error

Open or short circuit in the heat exchange temperature sensor.

×

O

O

O

O

O

1. Check remote control connection. 2. Defect in the remote control.

1. Check the serial circuit. •

Miswiring of the crossover between the water heat exchanger and the outdoor unit

1. Check the resistance value and connection of the heat exchange temperature sensor (TC).

1

1

1

F10

TWI sensor error

Open or short circuit in the water inlet temperature sensor.

O O

1. Check the resistance value and connection of the water inlet temperature sensor (TWI).

1

F11

TWO sensor error

Open or short circuit in the water outlet temperature sensor.

F14

TTW sensor error

Open or short circuit in the hot water cylinder sensor.

F17

TFI sensor error

Open or short circuit in the floor temperature sensor.

F18

THO sensor error

Open or short circuit in the heater outlet temperature sensor.

F19

Detection of THO disconnection error

When TWO

–THO>15K is detected and 30 sec elapsed.

F20

TFI sensor error

When TWO

–TFI>30K is detected and

TFI<TWI

–5K is detected.

×

×

×

×

×

×

62

O

O

O

O

×

×

1. Check the resistance value and connection of the water outlet temperature sensor (TWO).

1. Check the resistance value and connection of the hot water cylinder sensor (TTW).

1. Check the resistance value and connection of the floor-inlet temperature sensor (TFI).

1. Check the resistance value and connection of the heater outlet temperature sensor (THO).

1. Check for any disconnection of the heater outlet temperature sensor (THO).

1. Check the connection of the floor-inlet temperature sensor

(TFI).

1

1

1

1

1

1

Check

code

F23

Diagnostic functional operation

Operational cause

Backup

present

Automatic reset

Low pressure sensor error

When PS<0.07 MPa is detected for 90 sec or more (cooling, defrosting).

When PS<0.07 MPa is detected for 10 minutes or more (hot water supply, heating)

O O

Determination and action

Defect frequency confirmation

1. Check the connection (body or connection wiring) of the low pressure sensor.

1

2. Check the resistance value of the low pressure sensor.

F29

F30

L07

EEROM error

Inconsistency is detected once without verify

ACK after writing to EEPROM.

Extended IC error

When the extended IC is abnormal.

Communication error

Individual hydro units have a group line.

×

×

×

L09

Communication error

The capability of the hydro unit has not been set.

×

L15

Combination error

Model code of the hydro unit is different

Series 4 Powerful Type ONLY

O

L16

Setting error

When ZONE1 has not been set, while ZONE2 has been set.

Outdoor Unit check codes

Diagnostic functional operation

×

Check

code

Operational cause

Backup

present

F04

TD sensor error Open or short circuit in the discharge temperature sensor.

O

×

×

×

× x

×

1. Replace the water heat exchange control board.

1. Replace the water heat exchange control board.

1. Replace the water heat exchange control board.

1. Check the setting of the FC01 capability specifications.

HWS-803xx-E = 0012

HWS-1403xx-E = 0017

1. Check the model code of the hydro unit

1. Check the body DP-SW12_2,3.

1

1

1

1

1

1

F06

TE sensor error Open or short circuit in the heat exchange temperature sensor.

F07

TL sensor error Open or short circuit in the heat exchange temperature sensor.

F08

TO sensor error

Open or short circuit in the outdoor temperature sensor.

F12

TS sensor error

Open or short circuit in the suction temperature sensor.

F13

TH sensor error

Open or short circuit in the heat-sink temperature sensor.

F15

TE, TS sensors error

Open or short circuit in the temperature sensors.

F31

EEPROM error

O

O

O

O

O

O

O

Automatic

reset

×

×

×

×

×

×

×

Determination and action

o…...…. Possible x..…Not Possible

Defect frequency

confirmation

1. Check the resistance value and connection of the discharge sensor (TD).

1. Check the resistance value and connection of the heat exchange temperature sensor

(TE).

1. Check the resistance value and connection of the heat exchange temperature sensor

(TL).

1. Check the resistance value and connection of the outdoor temperature sensor (TO).

1. Check the resistance value and connection of the suction temperature sensor (TS).

1. Check the resistance value and connection of the heat-sink temperature sensor (TH).

1. Check for any wrong installation of the heat exchange temperature sensor (TE) and the suction temperature sensor

(TS).

1

1

1

1

1

1

1

×

1

63

Check

code

H01

H02

Diagnostic functional operation

Operational cause

Backup

present

Compressor breakdown

1 When the operation frequency lowers due to the current release 40 sec or later after the compressor activation and it stops by under running the minimum frequency.

2 When the operation frequency lowers due to the current limit control and it stops by under running the minimum frequency.

3 When an excess current is detected 0.8 sec or later after the compressor activation.

Compressor lock

When the input current is more than zero 20 sec or later after the compressor activation and the activation has not been completed.

O

O

H03 Defect in the current detection circuit O

H04

Operation of case thermostat

When the case thermostat exceeds 125°C.

L02

L10

L29

Combination error

Model name of the outdoor unit is different

Series 4 Powerful Type ONLY

Unset service PC board jumper

Jumpers J800-J803 have not been cut.

The communication between the outdoor

PC board MUCs error

No communication signal between IPDU and

CDB.

P03

The outlet temperature error

When the discharge temperature sensor (TD) exceeds 111°C.

P04 The high pressure switch error

P05

The power supply voltage error

When the power supply voltage is extremely high or low.

P07

Overheating of heat-sink error

When the heat-sink exceeds 105°C.

P15

Detection of gas leak

When the discharge temperature sensor (TD) exceeds 106°C for consecutive 10 min. When the suction temperature sensor (TS) exceeds

60°C for cooling or 40°C for heating for 10 consecutive min.

O x

O

O

O

O

O

O

O

Automatic

reset

×

×

×

× x

Determination and action

1. Check the power supply voltage

(AC220 -230 V±10% single phase type).

(AC380

– 400V ± 10% 3 phase type)

2. Over-loaded condition of the refrigeration cycle.

3. Check that the service valve is fully open.

1. Defect of compressor (lock)

Replace the compressor.

2. Defect of compressor wiring

(open phase).

1. Replace the outdoor inverter control board.

1. Check the refrigeration cycle

(gas leak).

2. Check the case thermostat and connector.

3. Check that the service valve is fully open.

4. Defect of the pulse motor valve. 5. Check for kinked piping.

2. Check the model name of the outdoor unit

Defect frequency

confirmation

8

8

8

4

1

×

1. Cut J800-J803. 1

×

1. Replace the outdoor control board.

×

×

1. Check the refrigeration cycle

(gas leak).

2. Defect of the pulse motor valve.

3. Check the resistance value of the discharge temperature sensor (TD).

×

1. Check the power supply voltage. (AC230 V±23 V)

×

×

1. Check the thread fastening and heat-sink grease between the outdoor control board and the heat-sink.

2. Check the heat-sink fan duct.

3. Check the resistance value of the heat-sink temperature sensor (TH).

1. Check the refrigeration cycle

(gas leak).

2. Check that the service valve is fully open.

3. Defect of the pulse motor valve.

4. Check for kinked piping.

5. Check the resistance value of the discharge temperature sensor (TD) and the suction temperature sensor (TS).

1

4

10

4

4

4

64

Check

code

Diagnostic functional operation

Operational cause

Backup

present

P19

The 4-way valve inversion error

When the heat exchange temperature sensor

(TE) exceeds 30°C or the suction temperature sensor (TS) exceeds 50°C during the heat pump operation.

O

Automatic

reset

×

Determination and action

1. Check the operation of the 4way valve unit or the coil characteristics.

2. Defect of the pulse motor valve.

3. Check the resistance value of the heat exchange temperature sensor (TE) and the suction temperature sensor (TS).

Defect frequency

confirmation

4

P20

High pressure protection operation

When an abnormal stop occurs due to the high pressure release control. When the heat exchange temperature sensor (TL) detects

63°C during the cooling operation. When the water outlet sensor (TWO) detects 60°C during the heating or hot water supply operation.

P22

Outdoor fan system error

When a DC fan rotor position detection NG, element short circuit, loss of synchronization, or abnormal motor current occurs.

P26

Short circuit of the compressor driver element error

When an abnormal short circuit of IGBT is detected.

P29

Compressor rotor position error

The rotor position in the compressor cannot be detected.

O

O

O

O

×

×

×

×

1. Check that the service valve is fully open.

2. Defect of the pulse motor valve.

3. Check the outdoor fan system

(including clogging).

4. Over-filling of refrigerant.

5. Check the resistance value of the heat exchange temperature sensor (TL) and the water outlet temperature sensor (TWO).

1. Check the lock status of the motor fan.

2. Check the connection of the fan motor cable connector.

3. Check the power supply voltage (AC230 V±23 V).

1. P26 abnormality occurs when operating with the compressor wiring disconnected … Check the control board.

2. No abnormality occurs when operating with the compressor wiring disconnected …

Compressor rare short.

1. Even if the connection lead wire of the compressor is disconnected, it stops due to an abnormality in the position detection … Replace the inverter control board.

2. Check the wire wound resistor of the compressor. Short circuit

… Replace the compressor.

10

1-4

8

8

65

Remote controller check codes

Outdoor Fault Diagnosis

You can perform fault diagnosis of the outdoor unit with the LED's on the P.C. board of the outdoor unit in addition to check codes displayed on the wired remote controller of the hydro unit.

Use the LED

’s and check codes for various check

Check of the current abnormal status

1. Check that DIP switch SW803 is set to all OFF.

2. Jot down the states of LED800 to LED804. (Display mode 1)

3. Press SW800 for at least one second. The LED status changes to display mode 2.

4. Check the code whose display mode 1 equals the jotted LED status and display mode 2 equals the current flashing status of

LED800 to LED804 from the following table to identify the cause.

66

Check of the abnormal status in the past although the abnormal status is not occurred now.

1. Set bit 1 of DIP switch SW803 to

ON.

2. Jot down the states of LED800 to

LED804. (Display mode 1)

3. Press SW800 for at least one second. The LED status changes to display mode 2.

4. Find an error whose display mode

1 equals the jotted LED status and display mode 2 equals the current flashing status of LED800 to LED804 from the following table to identify the error.

• An outside air temperature (TO)

sensor error can be checked only while an error occurs.

67

No. Cause

1 Normal

2 Discharge sensor (TD) error

3 Heat exchanger sensor (TE) error

4 Heat exchanger sensor (TL) error

5 Outside air temperature sensor (TO) error

6 Suction sensor (TS) error

7 Heat sink sensor (TH) error

8

Outdoor temperature sensor (TE/TS) connection error

9 Outdoor EEPROM error

10 Compressor lock

11 Compressor lock

12 Current detect circuit error

13 Thermostat for compressor activated

14 Model data not set (on the service P.C. board)

15 MCU-MCU communication error

16 Discharge temperature error

17

Abnormal power (open phase detected or abnormal voltage)

18 Heat sink overheat

19 refrigerant leak detected

20 4-way valve reverse error

21 High pressure release operation

22 Outdoor fan motor error

23 Compressor driver short circuit protection

24 Position detect circuit error in one-line display

D800 D801 D802 D803 D804 D800 D801 D802 D803 D804

○ ○ ● ● ○

◎ ◎

DISPLAY MODE 1

: ON

: OFF

DISPLAY MODE 2

: FLASHING

Notes:

68

Notes:

69

Notes:

70

AIRTREND Ltd - KOVENT DOO

Kumanovska 14, 11000 Beograd

Tel: 011 3836886, 3085740

Faks: 011 3444113 e-mail: [email protected], [email protected]

web: www.airtrend.rs, www.kovent.rs

web: www.toshiba-klima.rs, www.toshiba-estia.rs

1402285601R03