G3PB Datasheet
Solid State Relays (Single-phase)
G3PB
New Single-phase Solid State Relays with
Compact Size for Heater Control
• Slim models with a thickness of only 22.5 mm are also available.
• Compact design achieved by optimizing heat sink shape.
• DIN track mounting possible in addition to screw mounting.
• Comply with EN60947-4-3 (IEC947-4-3) UL508, and
CSA22.2 No. 14, and bear CE marking.
Model Number Structure
■ Model Number Legend
[email protected]@@[email protected]@[email protected]
1
2 3 4
5 6
7
SSR
1. Basic Model Name
G3PB:
Solid State Relay
2. Rated Load Power Supply Voltage
2:
200 VAC
3. Rated Load Current
15:
15 A
25:
25 A
35:
35 A
45:
45 A
4. Terminal Type
B:
Screw terminals
5. Single-phase/3-phase and Number of Elements for 3-phase
Blank:
Single-phase models
6. Single-phase Type
Blank:
DIN track mounting and built-in heat sink
7. Certification
VD:
Certified by UL, CSA, and VDE
Solid State Relays (Single-phase)
G3PB
J-37
Ordering Information
■ List of Models
Isolation method
Phototriac coupler
Zero cross
function
Yes
Operation
indicator
Yes (yellow)
Rated input
voltage
12 to 24 VDC
Rated output load
Model number
15 A, 100 to 240 VAC
G3PB-215B-VD 12 to 24 VDC
25 A, 100 to 240 VAC
G3PB-225B-VD 12 to 24 VDC
35 A, 100 to 240 VAC
G3PB-235B-VD 12 to 24 VDC
45 A, 100 to 240 VAC
G3PB-245B-VD 12 to 24 VDC
Note: When ordering, specify the rated input voltage.
■ Accessories (Order Separately)
Mounting Track
50 cm (1) x 7.3 mm (t)
PFP-50N
1 m (1) x 7.3 mm (t)
PFP-100N
1 m (1) x 16 mm (t)
PFP-100N2
Specifications
■ Ratings (at an Ambient Temperature of 25°C)
Input
Item
Common
Rated voltage
12 to 24 VDC
Operating voltage range
9.6 to 30 VDC
Rated input current
7 mA max.
Must operate voltage
9.6 VDC max.
Must release voltage
1 VDC min.
Insulation method
Phototriac
Operation indicator
Yellow LED
Output
Item
G3PB-215B-VD
G3PB-225B-VD
G3PB-235B-VD
Rated load voltage
100 to 240 VAC
Load voltage range
75 to 264 VAC
Applicable load current (See note.)
0.1 to 15 A
0.1 to 25 A
0.5 to 35 A
Inrush current resistance (peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
260 A2s
260 A2s
2,660 A2s
Applicable load
(with Class-1 AC resistive load)
3 kW max.
(at 200 VAC)
5 kW max.
(at 200 VAC)
7 kW max.
(at 200 VAC)
G3PB-245B-VD
0.5 to 45 A
9 kW max.
(at 200 VAC)
Note: The applicable load current varies depending on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in
Engineering Data.
J-38
Solid State Relays (Single-phase) G3PB
■ Characteristics
Item
G3PB-215B-VD
G3PB-225B-VD
G3PB-235B-VD
G3PB-245B-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
10 mA max. (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.375-mm single amplitude (Mounted to DIN track)
Shock resistance
Destruction: 294 m/s2 (DIN track mounting)
Ambient temperature
Operating:
Storage:
Ambient humidity
Operating: 45% to 85%
Certified standards
UL508 File No. E64562
CSA22.2 No. 14 File No. LR35535
IEC947-4-3 File No. 6825 UG
Weight
Approx. 240 g
–30°C to 80°C (with no icing or condensation)
–30°C to 100°C (with no icing or condensation)
Approx. 400 g
Approx. 400 g
SSR
Approx. 240 g
Solid State Relays (Single-phase)
G3PB
J-39
Engineering Data
G3PB-215B-VD
G3PB-225B-VD
G3PB-235B-VD
G3PB-245B-VD
Load current (A)
Load current (A)
Load Current vs. Ambient Temperature
G3PB-225B-VD
G3PB-245B-VD
G3PB-235B-VD
G3PB-215B-VD
Ambient temperature (°C)
Ambient temperature (°C)
Close Mounting (3 Relays, 8 Relays)
G3PB-225B-VD
Load current (A)
Load current (A)
G3PB-215B-VD
3 Relays
3 Relays
8 Relays
8 Relays
Ambient temperature (°C)
Ambient temperature (°C)
G3PB-245B-VD
Load current (A)
Load current (A)
G3PB-235B-VD
3 Relays
8 Relays
Ambient temperature (°C)
Close Mounting Example
DIN track
J-40
Solid State Relays (Single-phase) G3PB
3 Relays
8 Relays
Ambient temperature (°C)
Input impedance (kΩ)
Input current (mA)
Input Voltage vs. Input Current and Input Voltage vs. Input Impedance
Input current
Input impedance
Input voltage (V)
One Cycle Surge Current: Non-repetitive
Note: Keep the inrush current to half the rated value if it occurs repetitively.
G3PB-225B-VD
G3PB-235B-VD
G3PB-245B-VD
Energized time (ms)
Energized time (ms)
SSR
Energized time (ms)
Inrush current
Inrush current
Inrush current
G3PB-215B-VD
Solid State Relays (Single-phase)
G3PB
J-41
Dimensions
Note: All units are in millimeters unless otherwise indicated.
G3PB-215B-VD
G3PB-225B-VD
Two, 4.6 dia.
Two, M4
68
100 max. 90±0.2 80
24
Two, M3.5
4.5
13±0.2
4.2
6.3
Elliptical hole: 4.6 x 5.6
22.5 max.
Note: Without terminal cover.
Terminal Arrangement/
Internal Circuit Diagram
Note: With terminal cover.
Mounting Holes
(+)
1
13±0.3
Input side
90±0.3
Input circuit
88.6
83.2
Trigger circuit
100 max.
Output side
A1
A2
2
Three, 4.5 dia. or M4
G3PB-235B-VD
G3PB-245B-VD
)−(
4.6 dia.
Two, M5
68
100 max. 90±0.2 80
24
Two, M3.5
13.4
6.1
Elliptical hole: 4.6 x 5.6
4.5
25±0.2
44.5 max.
Note: Without terminal cover.
Terminal Arrangement/
Internal Circuit Diagram
Note: With terminal cover.
Mounting Holes
1
25±0.3
(+)
90±0.3
A2
Two, 4.5 dia. or M4
J-42
Solid State Relays (Single-phase) G3PB
2
)−(
Input side
88.6
Input circuit
83.2
Trigger circuit
100 max.
Output side
A1
Accessories (Order Separately)
Mounting Tracks
PFP-100N, PFP-50N
PFP-100N2
16
7.3±0.15
4.5
35±0.3
15 25 10 25
25
25
10
1,000 (500)
(see note)
4.5
27±0.15
15 (5)
(see note)
35±0.3 27 24
15 25
10
25
25
1,000
10
25 15
1
29.2
1.5
SSR
Note: Values in parentheses indicate dimensions for the
PFP-50N.
Solid State Relays (Single-phase)
G3PB
J-43
Safety Precautions
Relationship between SSRs and Ducts
Countermeasure 1
Mounting surface
Vertical mounting
Vertical Mounting
G3PB
Vertical
direction
→
Duct or
airflow
obstruction
Mounting Method
Countermeasure 2
50 mm max.
(A height of no more
than half
the SSR's
height is
recommended)
G3PB
G3PB
Airflow
Mounting surface
Duct Height
Please observe the following precautions to prevent failure to
operate, malfunction, or undesirable effect on product performance.
Mounting surface
■ Precautions for Correct Use
Duct or
airflow
obstruction
Panel
Do not surround the SSR
with ducts, otherwise
the heat radiation of the
SSR will be adversely
affected.
Horizontal Mounting
Use short ducts.
If the ducts cannot be
shortened, place the
SSR on a metal
base so that it is not
surrounded by the
ducts.
Ventilation
Be aware of air flow
Duct or air flow
obstruction
Panel
Note: Make sure that the load current is 50% of the rated load current
when the G3PB is mounted horizontally.
Ventilation
outlet
G3PB
G3PB
G3PB
Close Mounting
Air inlet
SSR Mounting Pitch
If the air inlet or air outlet has a filter, clean the filter regularly to
prevent it from clogging and ensure an efficient flow of air.
Panel Mounting
Between duct or
airflow
obstruction
and SSR
Duct or airflow obstruction
SSR
60 mm min.
Mounting direction
Host and
slave
Vertical direction
30 mm min.
80 mm min.
Close
mounting
10 mm min.
Do not locate any objects around the air inlet or air outlet, otherwise
the objects may obstruct the proper ventilation of the control panel.
A heat exchanger, if used, should be located in front of the SSR Units
to ensure the efficiency of the heat exchanger.
Please reduce the ambient temperature of SSRs.
The rated load current of an SSR is measured at an ambient
temperature of 25 or 40 °C.
An SSR uses a semiconductor in the output element. This causes
the temperature inside the control panel to increase due to heating
resulting from the passage of electrical current through the load. To
restrict heating, attach a fan to the ventilation outlet or air inlet of the
control panel to ventilate the panel. This will reduce the ambient
temperature of the SSRs and thus increase reliability. (Generally,
each 10 °C reduction in temperature will double the expected life.)
Load current (A)
15 A
Required number of fans 0.23
per SSR
25 A
0.39
35 A
0.54
45 A
0.70
Example: For 10 SSRs with load currents of 20 A,
0.23 x 10 = 2.3
Thus, 3 fans would be required.
Size of fans: 92 mm2, Air volume: 0.7 m3/min,
Ambient temperature of control panel: 30 °C
If there are other instruments that generate heat in the control
panel other than SSRs, additional ventilation will be required.
J-44
Solid State Relays (Single-phase) G3PB
Wiring
• When using crimp terminals, refer to the terminal clearances shown
below.
Output Terminal Section
(Single-phase Models)
15-A and
25-A Models
Input Terminal Section
35-A and
45-A Models
10
7.0
13
12.4
10
12.9
M4 (15 A, 25 A)
M5 (35 A, 45 A)
M3.5
• Make sure that all lead wires are appropriate for the current.
• Output terminals are charged even when the Relay is turned OFF.
Touching the terminals may result in electric shock. To isolate the
Relay from the power supply, install an appropriate circuit breaker
between the power supply and the Relay.
Be sure to turn OFF the power supply before wiring the Relay.
Tightening Torque
• Refer to the following and be sure to tighten each screw of the
Relay to the specified torque in order to prevent the Relay from
malfunctioning.
Screw terminal
diameter
Tightening torque
Input terminal
M3.5
0.8 N·m
Output terminal
M4
1.2 N·m
M5
2.0 N·m
SSR
Item
Solid State Relays (Single-phase)
G3PB
J-45
J-46
Solid State Relays (Single-phase) G3PB
Solid State Contactors (Three-phase)
G3PB
Space and working time saved with new heat
sink construction. Series now includes
480-VAC models to allow use in a greater
range of applications.
• A comprehensive lineup that now includes 480-VAC models.
• Slim design with 3-phase output and built-in heat sinks.
• New heat sink construction with smaller mounting section.
• DIN track mounting supported as standard. (Screw mounting is
also possible.)
• Certified by UL, CSA, and VDE.
Model Number Structure
■ Model Number Legend
[email protected]@@[email protected]@[email protected]
1
2 3 4
5 6
7
SSR
1. Basic Model Name
G3PB:
Solid State Relay
2. Rated Load Power Supply Voltage
2:
200 VAC
5:
480 VAC
3. Rated Load Current
15:
15 A
25:
25 A
35:
35 A
45:
45 A
4. Terminal Type
B:
Screw terminals
5. Single-phase/3-phase and Number of Elements for 3-phase
2:
3-phase, 2-element models
3:
3-phase, 3-element models
6. 3-phase Type
N:
DIN track mounting and built-in heat sink
7. Certification
VD:
Certified by UL, CSA, and VDE
Solid State Contactors (Three-phase)
G3PB
J-47
Ordering Information
■ List of Models (Built-in Heat Sinks)
Applicable
phase
3
Main circuit voltage
100 to 240 VAC
Zero cross
function
Yes
Applicable heater capacity (with
Class-1 AC resistive load)
5.1 kW max. (15 A)
8.6 kW max. (25 A)
12.1 kW max. (35 A)
200 to 480 VAC
Model
3
G3PB-215B-3N-VD
2
G3PB-215B-2N-VD
3
G3PB-225B-3N-VD
2
G3PB-225B-2N-VD
3
G3PB-235B-3N-VD
2
G3PB-235B-2N-VD
15.5 kW max. (45 A)
3
G3PB-245B-3N-VD
2
G3PB-245B-2N-VD
12.5 kW max. (15 A)
3
G3PB-515B-3N-VD
2
G3PB-515B-2N-VD
20.7 kW max. (25 A)
3
G3PB-525B-3N-VD
2
G3PB-525B-2N-VD
29.0 kW max. (35 A)
3
G3PB-535B-3N-VD
2
G3PB-535B-2N-VD
37.4 kW max. (45 A)
3
G3PB-545B-3N-VD
2
G3PB-545B-2N-VD
Note: When ordering, specify the rated input voltage.
J-48
Number of
poles
Solid State Contactors (Three-phase) G3PB
Specifications
■ Ratings (at an Ambient Temperature of 25°C)
Operating Circuit (Common)
Item
Common
Rated voltage
12 to 24 VDC
Operating voltage range
9.6 to 30 VDC
Rated input current (Impedance)
10 mA max. (at 24 VDC)
Must operate voltage
9.6 VDC max.
Must release voltage
1 VDC min.
Insulation method
Phototriac coupler
Operation indicator
Yellow LED
Main Circuit of Models with Built-in Heat Sinks
Item
G3PB215B3N-VD
G3PB215B2N-VD
G3PB225B3N-VD
G3PB225B2N-VD
G3PB235B3N-VD
Rated load voltage
100 to 240 VAC
Load voltage range
75 to 264 VAC
Applicable load current
(See note.)
0.2 to 15 A
0.2 to 25 A
0.5 to 35 A
Inrush current resistance
(peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
260 A2s
2,660 A2s
2,660 A2s
Item
G3PB515B3N-VD
Rated load voltage
200 to 480 VAC
Load voltage range
180 to 528 VAC
Applicable load current
(See note.)
0.5 to 15 A
Inrush current resistance
(peak value)
220 A
(60 Hz, 1 cycle)
Permissible I2t
(half 60-Hz wave)
260 A2s
G3PB515B2N-VD
G3PB525B3N-VD
0.5 to 25 A
G3PB525B2N-VD
G3PB535B3N-VD
0.5 to 35 A
G3PB235B2N-VD
G3PB245B3N-VD
G3PB245B2N-VD
0.5 to 45 A
G3PB535B2N-VD
G3PB545B3N-VD
G3PB545B2N-VD
0.5 to 45 A
440 A
(60 Hz, 1 cycle)
1,040 A2s
1,040 A2s
SSR
Note: Applicable load current varies depending on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in
Engineering Data.
Solid State Contactors (Three-phase)
G3PB
J-49
■ Characteristics
Models with Built-in Heat Sinks
Item
G3PB215B3N-VD
G3PB215B2N-VD
G3PB225B3N-VD
G3PB225B2N-VD
G3PB235B3N-VD
G3PB235B2N-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
(See note.)
10 mA (at 200 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.175-mm single amplitude (Mounted to DIN track)
Shock resistance
Destruction: 294 m/s2 (98 m/s2 with reverse mounting)
Ambient temperature
Operating: –30°C to 80°C (with no icing or condensation)
Storage: –30°C to 100°C (with no icing or condensation)
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 1.25 kg
Certified standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3); Certified by VDE
(From April 2001)
EMC
Emission
Immunity
ESD
Immunity
Electromagnetic
Immunity
EFT
Immunity
Surge transient
Immunity
RF disturbance
Immunity
Dips
Approx. 1.45 kg
Note: The leakage current of phase S will be approximately
J-50
Approx. 1.65 kg
EN55011 Group 1 Class B
IEC947-4-3, EN61000-4-2
4 kV contact discharge
8 kV air discharge
IEC947-4-3, EN61000-4-3
10 V/m (80 MHz to 1 GHz)
IEC947-4-3, EN61000-4-4
2 kV AC power-signal line
IEC947-4-3, EN61000-4-5
Normal mode ±1 kV, Common mode ±2 kV
IEC947-4-3, EN61000-4-6
10 V (0.15 to 80 MHz)
IEC947-4-3, EN61000-4-11
3 times larger if the 2-element model is applied.
Solid State Contactors (Three-phase) G3PB
G3PB245B3N-VD
Approx. 2.0 kg
G3PB245B2N-VD
Item
G3PB515B3N-VD
G3PB515B2N-VD
G3PB525B3N-VD
G3PB525B2N-VD
G3PB535B3N-VD
G3PB535B2N-VD
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
Output ON voltage drop
1.8 V (RMS) max.
Leakage current
(See note.)
20 mA (at 480 VAC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.175-mm single amplitude (Mounted to DIN track)
Shock resistance
Destruction: 294 m/s2 (98 m/s2 with reverse mounting)
Ambient temperature
Operating: –30°C to 80°C (with no icing or condensation)
Storage:
–30°C to 100°C (with no icing or condensation)
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 1.25 kg
Certified standards
UL508, CSA22.2 No. 14, EN60947-4-3 (IEC947-4-3); Certified by VDE
(From April 2001)
EMC
Emission
Immunity
ESD
Immunity
Electromagnetic
Immunity
EFT
Immunity
Surge transient
Immunity
RF disturbance
Immunity
Dips
Approx. 1.45 kg
G3PB545B2N-VD
Approx. 2.0 kg
EN55011 Group 1 Class B
IEC947-4-3, EN61000-4-2
4 kV contact discharge
8 kV air discharge
IEC947-4-3, EN61000-4-3
10 V/m (80 MHz to 1 GHz)
IEC947-4-3, EN61000-4-4
2 kV AC power-signal line
IEC947-4-3, EN61000-4-5
Normal mode ±1 kV, Common mode ±2 kV
IEC947-4-3, EN61000-4-6
10 V (0.15 to 80 MHz)
IEC947-4-3, EN61000-4-11
3 times larger if the 2-element model is applied.
SSR
Note: The leakage current of phase S will be approximately
Approx. 1.65 kg
G3PB545B3N-VD
Solid State Contactors (Three-phase)
G3PB
J-51
Engineering Data
Load Current vs. Ambient Temperature
Models with Built-in Heat Sinks
G3PB-225B-3N-VD
G3PB-225B-2N-VD
G3PB-525B-3N-VD
G3PB-525B-2N-VD
G3PB-235B-3N-VD
G3PB-235B-2N-VD
G3PB-535B-3N-VD
G3PB-535B-2N-VD
Load current (A)
Load current (A)
G3PB-215B-3N-VD
G3PB-215B-2N-VD
G3PB-515B-3N-VD
G3PB-515B-2N-VD
G3PB-225B-3N-VD
G3PB-225B-2N-VD
G3PB-525B-3N-VD
G3PB-525B-2N-VD
G3PB-245B-3N-VD
G3PB-245B-2N-VD
G3PB-545B-3N-VD
G3PB-545B-2N-VD
G3PB-245B-3N-VD
G3PB-245B-2N-VD
G3PB-545B-3N-VD
G3PB-545B-2N-VD
G3PB-235B-3N-VD
G3PB-235B-2N-VD
G3PB-535B-3N-VD
G3PB-535B-2N-VD
G3PB-215B-3N-VD
G3PB-215B-2N-VD
G3PB-515B-3N-VD
G3PB-515B-2N-VD
Ambient temperature (°C)
Ambient temperature (°C)
Input impedance (kΩ )
Input current (mA)
Input Voltage vs. Input Current and Input Voltage vs. Input Impedance
Input current
Input impedance
Input voltage (V)
One Cycle Surge Current: Non-repetitive
Note: Keep the inrush current to half the rated value if it occurs repetitively.
G3PB-225B-3N-VD G3PB-225B-2N-VD
G3PB-515B-3N-VD G3PB-515B-2N-VD
G3PB-525B-3N-VD G3PB-525B-2N-VD
Energized time (ms)
J-52
G3PB-235B-3N-VD
G3PB-235B-2N-VD
G3PB-535B-3N-VD
G3PB-535B-2N-VD
G3PB-245B-3N-VD
G3PB-245B-2N-VD
G3PB-545B-3N-VD
G3PB-545B-2N-VD
Inrush current
Inrush current
Inrush current
G3PB-215B-3N-VD
G3PB-215B-2N-VD
Energized time (ms)
Solid State Contactors (Three-phase) G3PB
Energized time (ms)
Dimensions
Note: All units are in millimeters unless otherwise indicated.
G3PB-215B-3N-VD G3PB-515B-3N-VD
G3PB-215B-2N-VD G3PB-515B-2N-VD
G3PB-225B-2N-VD G3PB-525B-2N-VD
Without Terminal Cover
With Terminal Cover
Two, 4.6-dia. mounting holes
Four, 8 dia.
Two, M3.5
80.5
max.
100 max.
Two, R2.3
mounting
holes
Six, M4
Terminal Arrangement/
Internal Connections
80 max.
[email protected]@@B-3N-VD
Input circuit
Mounting Hole Dimensions
30.5 max.
120 max.
[email protected]@@B-2N-VD
SSR
Input circuit
Four, 4.5-dia. or M4
Solid State Contactors (Three-phase)
G3PB
J-53
G3PB-225B-3N-VD
G3PB-235B-2N-VD
G3PB-525B-3N-VD
G3PB-535B-2N-VD
Without Terminal Cover
With Terminal Cover
Two, 4.6-dia. mounting holes
Four, 8 dia.
Two, M3.5
80.5
max.
120
max.
Two, R2.3
mounting
holes
Six, M5 (35 A type)
Six, M4 (25 A type)
Terminal Arrangement/
Internal Connections
80 max.
[email protected]@@B-3N-VD
30.5 max.
120 max.
Input circuit
Mounting Hole Dimensions
[email protected]@@B-2N-VD
Input circuit
Four, 4.5-dia. or M4
J-54
Solid State Contactors (Three-phase) G3PB
G3PB-235B-3N-VD
G3PB-245B-2N-VD
G3PB-535B-3N-VD
G3PB-545B-2N-VD
Without Terminal Cover
With Terminal Cover
Two, 4.6-dia. mounting holes
Four, 8 dia.
Two, M3.5
80.5
max.
140
max.
Two, R2.3
mounting
holes
Six, M5
Terminal Arrangement/
Internal Connections
80 max.
[email protected]@@B-3N-VD
Input circuit
Mounting Hole Dimensions
30.5 max.
[email protected]@@B-2N-VD
120 max.
SSR
Input circuit
Four, 4.5-dia. or M4
Solid State Contactors (Three-phase)
G3PB
J-55
G3PB-245B-3N-VD
G3PB-545B-3N-VD
Without Terminal Cover
With Terminal Cover
Two, 4.6-dia. mounting holes
Four, 8 dia.
Two, M3.5
80.5
max.
140
max.
Two, R2.3
mounting
holes
Six, M5
80 max.
110 max.
Terminal Arrangement/
Internal Connections
[email protected]@@B-3N-VD
Mounting Hole Dimensions
Input circuit
30.5 max.
120 max.
Four, 4.5-dia.
or M4
J-56
Solid State Contactors (Three-phase) G3PB
Safety Precautions
Since the Relay is heavy, firmly mount the DIN track and fix both
ends with End Plates for DIN-track-mounting models.
Applicable DIN Tracks
The G3PB can be mounted to TH35-15Fe (IEC60715) DIN tracks.
The manufacturers and models of DIN tracks to which mounting is
possible are shown in the following table.
Manufacturer
Thickness
1.5 mm
2.3 mm
Schneider
AM1-DE200
---
WAGO
210-114, 210-197
210-118
PHOENIX
NS35/15
NS35/15-2.3
150.5mm
Countermeasure 1
75mm max.
Duct or
airflow
obstruction
150.5mm
SSR
Vertical
direction
(A height of no
more than half
the SSR's
height is
recommended)
SSR
If the ducts cannot be
shortened, place the SSR
on a metal base so that it
is not surrounded by the
ducts.
Use short ducts.
Ventilation
Direct Mounting
Be aware of air flow
Duct or
air flow
obstruction
Ventilation
outlet
SSR
SSR
SSR
When mounting directly onto a panel, mount securely under the
following conditions.
Screw diameter: M4
Tightening torque: 0.98 to 1.47 N·m
Air inlet
Mounted State
Horizontal Mounting
Vertical direction
Vertical Mounting
Airflow
SSR
Duct or
airflow
obstruction
Do not surround the SSR
with ducts, otherwise the
heat radiation of the SSR
will be adversely affected.
Countermeasure 2
Mounting surface
Mounting Method
Duct Height
Mounting surface
Please observe the following precautions to prevent failure to
operate, malfunction, or undesirable effect on product performance.
Relationship between SSRs and Ducts
Mounting surface
■ Precautions for Correct Use
If the air inlet or air outlet has a filter, clean the filter regularly to
prevent it from clogging and ensure an efficient flow of air.
Do not locate any objects around the air inlet or air outlet, otherwise
the objects may obstruct the proper ventilation of the control panel.
A heat exchanger, if used, should be located in front of the SSR Units
to ensure the efficiency of the heat exchanger.
Please reduce the ambient temperature of SSRs.
Panel
Note: Mount the G3PB so
that the markings
can be read.
Note: When the G3PB is
mounted horizontally,
use at 50% of the rated
load current.
Close Mounting
The rated load current of an SSR is measured at an ambient
temperature of 25 or 40 °C.
An SSR uses a semiconductor in the output element. This causes
the temperature inside the control panel to increase due to heating
resulting from the passage of electrical current through the load. To
restrict heating, attach a fan to the ventilation outlet or air inlet of the
control panel to ventilate the panel. This will reduce the ambient
temperature of the SSRs and thus increase reliability. (Generally,
each 10 °C reduction in temperature will double the expected life.)
Three-element Devices
SSR Mounting Pitch
Load current (A)
15 A
Required number of fans 0.70
per SSR
Panel Mounting
25 A
1.06
35 A
1.63
45 A
2.09
Duct or airflow obstruction
Two-element Devices
80 mm min.
SSR
Between duct
or airflow
obstruction
and SSR
Mounting direction
Vertical direction
80 mm min.
80 mm min.
Space between
SSRs
10mm min.
Close mounting
Load current (A)
15 A
Required number of fans 0.47
per SSR
25 A
0.78
35 A
1.09
45 A
1.40
Example: For 10 SSRs with load currents of 11 A (3-element
devices,
1.63 x 10 = 16.3
Thus, 17 fans would be required.
Size of fans: 92 mm2, Air volume: 0.7 m3/min,
Ambient temperature of control panel: 30 °C
If there are other instruments that generate heat in the control
panel other than SSRs, additional ventilation will be required.
Solid State Contactors (Three-phase)
G3PB
J-57
SSR
Panel
Wiring
Tightening Torque
When using crimp terminals, refer to the terminal clearances shown
below.
Refer to the following and be sure to tighten each screw of the Unit to
the specified torque in order to prevent the Unit from malfunctioning.
Output Terminals
Input Terminals
Item
Screw terminal
diameter
Tightening torque
Input terminal
M3.5
0.59 to 1.18 N·m
Output terminal
M4
0.98 to 1.47 N·m
M5
1.47 to 2.45 N·m
M4 (15 A, 25 A)
M5 (35 A, 45 A)
• Make sure that all lead wires are thick enough for the current.
• Output terminals T1, T2, and T3 are charged regardless of whether
the Unit is a 2- or 3-element model that is turned on or off. Do not
touch these terminals, otherwise an electric shock may be
received.
To isolate the Unit from the power supply, install an appropriate
circuit breaker between the power supply and Unit.
Be sure to turn off the power supply before wiring the Unit.
• Terminal L2 and terminal T2 of the 2-element model are internally
short-circuited to each other. Therefore, connect terminal L2 to the
ground terminal side of the power supply. If terminal L2 is
connected to a terminal other than the ground terminal, cover all
the charged terminals, such as heater terminals, for the prevention
of electric shock accidents and ground faults.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. J135-E1-03
J-58
In the interest of product improvement, specifications are subject to change without notice.