- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Mitsubishi Electric
- GA MUZ-GA35VAH
- Service manual
- 52 Pages
Mitsubishi Electric GA MUZ-GA25VA, GA MUZ-GA35VA, GA MUZ-GA25VAH, GA MUZ-GA35VAH air conditioner Service manual
The GA MUZ-GA25VA, GA MUZ-GA35VA, GA MUZ-GA25VAH, GA MUZ-GA35VAH are split-type, heat pump air conditioners that utilize R410A refrigerant and are wireless-controlled. These manuals detail the technical specifications, component information and service procedures for the outdoor units of these models. For indoor units MSZ-GA22VA, MSZ-GA25VA and MSZ-GA35VA, refer to service manual OB378.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
OB379 --1qxp 05.1.17 16:39 Page 1
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
Wireless type
Models
MUZ-GA25VA -
MUZ-GA35VA -
E1
E1
MUZ-GA25VAH -
MUZ-GA35VAH -
E1
E1
HFC utilized
R410A
No. OB379
Indication of model name
MUZ-GA25VA -
MUZ-GA35VA -
E1
E1
MUZ-GA25VAH -
E1
MUZ-GA35VAH -
E1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················6
3. SPECIFICATION·················································7
4. NOISE CRITERIA CURVES ·······························9
5. OUTLINES AND DIMENSIONS ·······················10
6. WIRING DIAGRAM···········································11
7. REFRIGERANT SYSTEM DIAGRAM ··············15
8. PERFORMANCE CURVES ······························17
9. ACTUATOR CONTROL····································25
10. SERVICE FUNCTIONS·····································26
11. TROUBLESHOOTING ······································26
12. DISASSEMBLY INSTRUCTIONS·····················45
13. PARTS LIST······················································48
NOTE:
This service manual describes technical data of the outdoor units.
•As for indoor units MSZ-GA22VAE1 , MSZ-GA25VAE1 and MSZ-GA35VAE1 , refer to the service manual OB378.
www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 2
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
1 TECHNICAL CHANGES
MUZ-A09YV -
E1
MUZ-A09YVH -
E1
➔ MUZ-GA25VA -
E1
➔ MUZ-GA25VAH -
E1
1.Indication of capacity has been changed.(BTU base ➔ kW base)
2.Control method between indoor and outdoor unit has been changed.
3.Power supply method has been changed (change to supply from outdoor unit).
4.Terminal block for power supply has been added.
5.Power P.C. board has been changed.
6.Inverter P.C. board has been changed.
7.Refrigerant circuit has been changed.
• Compressor has been changed.(KNB073FBVH ➔ KNB065FDTH)
• LEV has been removed and capillary tube has been added.
• Bypass circuit for low outside temperature operation has been added.
• Specification and position of muffler have been changed.
• Path of outdoor heat exchanger has been changed.
• 4-way valve and R.V. coil have been changed.
• Stop valve has been changed.
8.Fan motor has been changed. (AC)
9.Shape of grille has been changed.
10.Shape of service panel has been changed.
11.Shape of propeller has been changed.
12.Quick Clean Kit has been added.
13.Symbol on terminal block has been changed (to S1/S2/S3).
MUZ-A12YV -
E1
MUZ-A12YVH -
E1
➔ MUZ-GA35VA -
E1
➔ MUZ-GA35VAH -
E1
1.Indication of capacity has been changed.(BTU base ➔ kW base)
2.Control method between indoor and outdoor unit has been changed.
3.Power supply method has been changed (change to supply from outdoor unit).
4.Terminal block for power supply has been added.
5.Power P.C. board has been changed.
6.Inverter P.C. board has been changed.
7.Refrigerant circuit has been changed.
• Compressor has been changed.(KNB092FAAH ➔ KNB073FDVH)
• Specification and position of muffler have been changed.
• Path of outdoor heat exchanger has been changed.
• 4-way valve and R.V. coil have been changed.
• Stop valve has been changed.
8.Fan motor has been changed.(AC ➔ DC)
9.Shape of grille has been changed.
10.Shape of service panel has been changed.
11.Shape of propeller has been changed.
12.Quick Clean Kit has been added.
13.Symbol on terminal block has been changed (to S1/S2/S3).
2 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 3
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 air conditioners.
1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/ materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent composition change.
New refrigerant
Refrigerant
Composition (Ratio)
Refrigerant handling
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included Chlorine
Safety group (ASHRAE)
Molecular weight
Boiling point ( : )
Steam pressure [25
Combustibility
ODP
GWP w w
1
2
: ](Mpa)
Saturated steam density [25 : ](Kg/ K )
Refrigerant charge method
Additional charge on leakage
Kind
Color
Smell w 1 :Ozone Destruction Parameter : based on CFC-11 w 2 :Global Warmth Parameter : based on CO
2
A1/A1
72.6
-51.4
1.557
64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non
Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055
1700
Gas phase
Possible
Compatible oil
Light yellow
Non
New Specification Current Specification
The incompatible refrigeration oil easily separates from refrigerant and is in the upper layer inside the suction muffler.
Raising position of the oil back hole enables to back the refrigeration oil of the upper layer to flow back to the compressor.
Suction muffler
Since refrigerant and refrigeration oil are compatible each, refrigeration oil goes back to the compressor through the lower position oil back hole.
Suction muffler
Compressor
Oil back hole
Refrigeration oil
Compressor
Oil back hole
Refrigerant Refrigeration oil /Refrigerant
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ f [Gauge])
3 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 4
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
Conversion chart of refrigerant temperature and pressure
(MPa [Gauge])
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
R410A
R22
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ f [Gauge])
-0.5
-30 -20 -10 0 10 20 30 40 50 60 ( : )
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.
The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
R410A tools Can R22 tools be used?
Gauge manifold
Charge hose
Gas leak detector
Torque wrench
Flare tool
Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No
No
No
Yes
No
Yes
New
New
New
Description
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
12.7 mm
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No : Not Substitutable for R410A Yes : Substitutable for R410A
2.Refrigerant piping
1 Specifications
Use the refrigerant pipes that meet the following specifications.
Pipe
For liquid
For gas
Outside diameter mm
6.35
9.52
12.7
Wall thickness
0.8 mm
0.8 mm
0.8 mm
Insulation material
Heat resisting foam plastic
Specific gravity 0.045 Thickness 8 mm
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient.
4 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 5
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe.
For details of flaring work, refer to Installation manual “FLARING WORK”.
Pipe diameter mm
6.35
9.52
12.7
R410A
17
22
26
Dimension of flare nut
R22
17
22
24
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigeration cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Union
Stop valve
Indoor unit
Liquid pipe
Gas pipe
Outdoor unit
Refrigerant gas cylinder operating valve
Service port
Gauge manifold valve (for R410A)
Charge hose (for R410A)
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Electronic scale for refrigerant charging
5 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 6
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
2 PART NAMES AND FUNCTIONS
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
OUTDOOR UNIT
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
ACCESSORIES
1 Drain socket
2 Quick clean kit
MUZ-GA25VA E1
MUZ-GA35VA E1
1
1
MUZ-GA25VAH E1
MUZ-GA35VAH E1
–
1
6 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 7
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
3 SPECIFICATION
Outdoor model
MUZ-GA25VA E1
MUZ-GA25VAH E1
MUZ-GA35VA E1
MUZ-GA35VAH E1
Function
Power supply
Capacity Rated frequency(Min.-Max.) kW
Dehumidification
Air flow ✽ 1 r
K
/h
/h
Starting current ✽ 1 A
Compressor motor current ✽ 1
Fan motor current ✽ 1
A
A
Coefficient of performance(C.O.P) ✽ 1
Cooling Heating
Single phase
1.4
2.71
230V,50Hz
2.5 (0.9-3.0)
1,890
3.6
3.2 (0.9-4.5)
0.24
—
3.11
Cooling Heating
Single phase
2.0
4.44
0.31
230V,50Hz
3.5 (1.0-3.9)
2,058
4.0 (0.9-5.0)
5.0
—
2,178
4.20
0.35
3.91
500
4.21
KNB065FDTH
3.24
3.79
Model
Output W
KNB073FDVH
550
U-V 1.53
U-W 1.53
Winding resistance(at 20 : )
Model
Winding resistance(at 20 : )
"
" mm kg dB(A) rpm
U-V 1.88
U-W 1.88
V-W 1.88
RA6V21-AB
WHT-BLK 347
BLK-RED 281
V-W 1.53
RC0J50-AL
WHT-BLK 37.5
BLK-RED 37.5
Dimensions W
Weight
Sound level ✽ 1
Fan speed(High
W
/Low
W
O H
, High
O D
W
/Med.
W
/Low
W
)
800 o 550 o 285
31
46
810
1
RED-WHT 37.5
800 o 550 o 285
33
47
810
W
/750
W
48
880
W
/810
W
/650
W
2 3
Fan speed regulator
Refrigerant filling
Thermistor RT61(at 0 : )
Thermistor RT62(at 100 : ) kg cc k " k " k "
0.85
320 (NEO22)
32.6
13.4
17
10
0.90
capacity(R410A)
Refrigeration oil (Model)
Thermistor RT64(at 50
Thermistor RT65(at 25
:
: )
) k "
NOTE : Test conditions are based on ISO 5151
Cooling : Indoor Dry-bulb temperature 27 : Wet-bulb temperature 19 :
Outdoor Dry-bulb temperature 35 : Wet-bulb temperature(24 : )
Heating : Indoor Dry-bulb temperature 20 : Wet-bulb temperature 15 :
Outdoor Dry-bulb temperature 7 : Wet-bulb temperature 6 :
Refrigerant piping length (one way): 5m
✽ 1 Measured under rated operating frequency w Reference value
320 (NEO22)
32.6
13.4
17
10
7 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 8
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
Specifications and rating conditions of main electric parts
OUTDOOR UNIT
Item
Model
MUZ-GA25VA - E1 MUZ-GA25VAH - E1 MUZ-GA35VA - E1 MUZ-GA35VAH -
Current transformer
Fuse
(CT)
(F61)
ETA19Z59BZ
ETQ19Z71AY
620 + 420V
D25XB60
250V 20A
Defrost heater (H) — 230V 130W
250V 3.15A
PS21244-A-203
— 230V 130W
Expansion valve coil
Reactor
Current-detecting resistor
(LEV)
(L61)
(R61)
—
10A 23.0mH
CAM-MD12ME 12VDC
45m " 5W (1 element)
Current-detecting resistor
Current-limiting resistor (R64A, R64B)
Terminal block (TB1,TB2)
Relay
Relay
Relay
(R831)
(X63)
(X64)
(X66) — G5NB-1a
Relay
R.V. coil
(X69)
(21S4)
G5NB-1a
SHF-4-10W5
Solid state relay (SR61) G3MC-202PL
Solenoid valve coil (21R1) FQ-208-RK
Heater protector (26H) —
Outdoor fan motor thermal fuse :
Open 45 :
25m
10 "
"
5W
3P
5W
G5NB-1a
G4A-1A-PS
—
—
—
STF-01AJ503
—
—
—
G5NB-1a
Open 45 :
E1
8 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 9
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
4 NOISE CRITERIA CURVES
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
FUNCTION SPL(dB(A))
COOLING 46
HEATING 46
LINE
Test conditions,
Cooling : Dry-bulb temperature 35 : Wet-bulb temperature (24 : )
Heating : Dry-bulb temperature 7 : Wet-bulb temperature 6 :
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
20
10
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63 125
NC-20
250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
FAN SPEED FUNCTION SPL(dB(A))
COOLING 47
High
Med.
HEATING 48
LINE
Test conditions,
Cooling : Dry-bulb temperature 35 : Wet-bulb temperature (24 : )
Heating : Dry-bulb temperature 7 : Wet-bulb temperature 6 :
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
20
10
NC-30
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63 125
NC-20
250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
OUTDOORUNIT
1m
MICROPHONE
9 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 10
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
5 OUTLINES AND DIMENSIONS
MUZ-GA25VA -
E1
MUZ-GA35VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VAH -
E1
OUTDOOR UNIT
Unit: mm
REQUIRED SPACE
Drain hole [ 42 (MUZ-GA25/GA35VA)
Drain hole [ 33 (MUZ-GA25/GA35VAH) 100mm or more
400
Air in
Air in
22.3
2 holes 10X21
Air out
Handle
150
302.5
500 Bolt pitch for installation
800
40
69
23
200mm or more
Open two sides of left, right, or rear side.
Service panel
170.5
Service port
Liquid refrigerant pipe joint
Refrigerant pipe (flared) [ 6.35
35
-
43
Gas refrigerant pipe joint
Refrigerant pipe (flared) [ 9.52
Basically open 100mm or more without any obstruction in front and on both sides of the unit.
100mm or more
350mm or more
10 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 11
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
6 WIRING DIAGRAM
MUZ-GA25VA -
E1
OUTDOOR UNIT
MODEL WIRING DIAGRAM
BLK
GRN
CONNECTING
TO INDDOR UNIT
11 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 12
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
MUZ-GA25VAH -
E1
MODEL WIRING DIAGRAM
OUTDOOR UNIT
GRN
BLK
CONNECTING
TO INDDOR UNIT
TB1 L
12 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 13
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
MUZ-GA35VA -
E1
OUTDOOR UNIT
MODEL WIRING DIAGRAM
BLK
GRN
CONNECTING
TO INDDOR UNIT
13 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 14
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
MUZ-GA35VAH -
E1
MODEL WIRING DIAGRAM
OUTDOOR UNIT
BLK
GRN
CONNECTING
TO INDDOR UNIT
14 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 15
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
7 REFRIGERANT SYSTEM DIAGRAM
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
OUTDOOR UNIT
Refrigerant pipe [ 9.52
(with heat insulator)
Muffler
Stop valve
(with service port)
Flared connection
4-way valve
Discharge temperatuer thermistor
RT62
Muffler
Compressor
Defrost thermistor
RT61
Unit:mm
Outdoor heat exchanger
Ambient temperature thermistor
RT65
Flared connection
Refrigerant pipe [ 6.35
(with heat insulator)
Stop valve
(with strainar)
Capillary tube
[ 3.0
✕[ 1.4
✕ 500
Solenoid valve
Strainer
#100
Check valve
R.V. coil heating ON cooling OFF
Capillary tube
[ 3.0
✕[ 1.4
✕ 800
Refrigerant flow in cooling
Refrigerant flow in heating
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
OUTDOOR UNIT
Refrigerant pipe [ 9.52
(with heat insulator)
Muffler
Stop valve
(with service port)
Flared connection
4-way valve
Discharge temperatuer thermistor
RT62
Muffler
Compressor
Defrost thermistor
RT61
Unit:mm
Outdoor heat exchanger
Ambient temperature thermistor
RT65
Flared connection
Capillary tube
[ 3.0
✕[ 2.0
✕ 240
Expansion valve
Muffler
Refrigerant pipe [ 6.35
(with heat insulator)
Stop valve
(with strainar)
Strainer
#100
R.V. coil heating ON cooling OFF
Refrigerant flow in cooling
Refrigerant flow in heating
15 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 16
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
MAX. REFRIGERANT PIPING LENGTH
Model
MUZ-GA25VA - E1
MUZ-GA25VAH - E1
MUZ-GA35VA - E1
MUZ-GA35VAH - E1
MAX. HEIGHT DIFFERENCE
Refrigerant piping
Max. length : m
A
20
Piping size O.D : mm
Gas Liquid
9.52
6.35
Length of connecting pipe : m
Indoor unit Outdoor unit
Gas 0.43
Liquid 0.5
Indoor unit w Max. Height difference 12m
Refrigerant Piping
Max. length
A
Outdoor unit w Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Model
Outdoor unit precharged
5m 6m 7m
Refrigerant piping length (one way)
8m 9m 10m 11m 12m 13m 14m 15m 20m
MUZ-GA25VA - E1
MUZ-GA25VAH - E1
850 0 0 0 90 120 150 180 210 240 270 300 450
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
900 0 0 0 90 120 150 180 210 240 270 300 450
Calculation : Xg=30g/m o
(Refrigerant piping length(m) - 5)
16 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 17
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
8 PERFORMANCE CURVES
MUZ-GA25VA -
E1
MUZ-GA35VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VAH -
E1
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
207 ~ 253V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :
(2) Indoor outlet air wet-bulb temperature :
(3) Outdoor intake air dry-bulb temperature :
°C WB
°C WB
°C DB
}
Cooling
(4) Total input:
(5) Indoor intake air dry-bulb temperature :
W
°C DB
(6) Outdoor intake air wet-bulb temperature : °C WB
}
Heating
(7) Total input : W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on next page shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb / dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT OUTDOOR UNIT
Wet and dry-bulb thermometers
Wet and dry-bulb thermometers
6.4
5.8
5.3
4.9
4.4
3.9
9.1
8.3
7.6
6.8
6.1
5.5
Indoor intake air W et-bulb temperature (
:
)
Outdoor intake air Dry-bulb temperature ( : )
Indoor intake air W et-bulb temperature (
:
)
Outdoor intake air Dry-bulb temperature ( : )
17 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 18
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
19.7
18.2
16.7
15.2
13.7
12.1
10.6
9.1
24.7
22.8
20.9
19.0
17.1
15.2
13.3
11.4
:
)
Indoor intake air Dry-bulb temperature (
:
)
Indoor intake air Dry-bulb temperature (
Outdoor intake air Wet-bulb temperature ( : ) Outdoor intake air Wet-bulb temperature ( : )
NOTE:The above curves are for the heating operation without any frost.
MUZ-GA25VA -
MUZ-GA25VAH -
E1
E1
1.5
Correction of Cooling capacity
MUZ-GA25VA -
MUZ-GA25VAH -
E1
E1
1.5
Correction of Cooling total input
MUZ-GA25VA E1
MUZ-GA25VAH E1
2.0
Correction of Heating capacity
MUZ-GA25VA -
MUZ-GA25VAH -
E1
E1
2.0
Correction of Heating total input
1.5
1.5
1.0
1.0
1.0
1.0
0.5
0.5
0.5
0.5
0.0
0 50 100 150(Hz)
The operational frequency of compressor
0.0
0 50 100 150(Hz)
The operational frequency of compressor
0.0
0 50 100 150(Hz)
The operational frequency of compressor
0.0
0 50 100 150(Hz)
The operational frequency of compressor
MUZ-GA35VA -
MUZ-GA35VAH -
E1
1.5
Correction of Cooling capacity
MUZ-GA35VA -
MUZ-GA35VAH -
E1
1.5
Correction of Cooling total input
MUZ-GA35VA -
MUZ-GA35VAH -
E1
2.0
Correction of Heating capacity
MUZ-GA35VA -
MUZ-GA35VAH -
E1
2.0
Correction of Heating total input
1.5
1.5
1.0
1.0
0.5
0.5
1.0
1.0
0.5
0.5
0.0
0 50 100 150(Hz)
The operational frequency of compressor
0.0
0 50 100 150(Hz)
The operational frequency of compressor
0.0
0 50 100 150(Hz)
The operational frequency of compressor
0.0
0 50 100 150(Hz)
The operational frequency of compressor
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
<How to operate fixed-frequency operation (Test run operation)>
1. Press EMERGENCY OPERATION switch to COOL or HEAT mode (COOL : Press once, HEAT : Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (Operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ f [Gauge])
18 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 19
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
Dry-bulb temperature
1 Both indoor and outdoor unit are under the same temperature/humidity condition.
2 Air flow : High speed
3 Operational frequency : 65Hz(MUZ-GA25VA, MUZ-GA25VAH)
88Hz(MUZ-GA35VA, MUZ-GA35VAH)
20
25
30
12
10
1.2
1.0
MUZ-GA25VA -
MUZ-GA25VAH -
E1
(kgf/ F [Gauge]) (MPa [Gauge])
14 1.4
E1
65Hz
MUZ-GA35VA -
MUZ-GA35VAH -
(kgf/ F [Gauge]) (MPa [Gauge])
14
1.4
12 1.2
88Hz
10 1.0
8 0.8
8 0.8
6 0.6
4 0.4
2 0.2
15 18 20 25 30 32 35(˚C)
50 60 70 (%)
Ambient temperature(˚C) Ambient humidity(%)
6 0.6
4 0.4
2 0.2
15 18 20 25 30 32 35(˚C)
50 60 70 (%)
Ambient temperature(˚C) Ambient humidity(%)
4
MUZ-GA25VA -
MUZ-GA25VAH -
E1
E1
3.5
3
65Hz
2.5
2
15 18 20
50
25
60
30 32 35(˚C)
70 (%)
Ambient temperature(˚C) Ambient humidity(%)
6
MUZ-GA35VA -
MUZ-GA35VAH -
E1
E1
88Hz
5
4
3
2
15 18 20
50
25
60
30 32 35(˚C)
70 (%)
Ambient temperature(˚C) Ambient humidity(%)
Relative humidity(%)
50
60
70
HEAT operation
Condition indoor: Dry bulb temperature 20.0°C
Wet bulb temperature 14.5°C
Condition outdoor: Dry bulb temperature 2,7,15,20.0°C
Wet bulb temperature 1,6,12,14.5°C
MUZ-GA25VA -
MUZ-GA25VAH -
E1
E1
MUZ-GA35VA -
MUZ-GA35VAH -
3.0
4.0
58Hz
2.5
3.5
58Hz
2.0
3.0
1.5
2.5
1.0
2.0
0.5
1.5
0.0
2 5 10 15 20 25(
Ambient temperature(˚C)
: )
1.0
2 5 10 15 20 25(
Ambient temperature(˚C)
: )
19 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 20
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
PERFORMANCE DATA COOL operation Rated frequency 65Hz
MSZ-GA25VA -
E1
: MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
CAPACITY:2.5(kW) SHF:0.79
INPUT:640(W)
OUTDOOR DB( : )
INDOOR INDOOR
DB(
25
25
25
25
24
24
24
24
22
23
23
23
21
21
22
22
: ) WB( : )
18
20
22
24
18
20
22
24
22
18
20
22
18
20
18
20
21
Q SHC SHF
2.94 1.79 0.61
3.06 1.50 0.49
2.94 1.91 0.65
3.06 1.62 0.53
3.19 1.31 0.41
2.94 2.03 0.69
3.06 1.75 0.57
3.19 1.43 0.45
2.94 2.14 0.73
3.06 1.87 0.61
3.19 1.56 0.49
3.35 1.24 0.37
2.94 2.26 0.77
3.06 1.99 0.65
INPUT
512
538
512
538
557
512
538
557
512
538
557
582
512
538
25
Q SHC SHF
2.81 1.72 0.61
2.94 1.44 0.49
2.81 1.83 0.65
2.94 1.56 0.53
3.08 1.26 0.41
2.81 1.94 0.69
2.94 1.67 0.57
3.08 1.38 0.45
2.81 2.05 0.73
2.94 1.79 0.61
3.08 1.51 0.49
3.23 1.19 0.37
2.81 2.17 0.77
2.94 1.91 0.65
INPUT
538
570
538
570
592
538
570
592
538
570
592
614
538
570
27
Q SHC SHF
2.70 1.65 0.61
2.85 1.40 0.49
2.70 1.76 0.65
2.85 1.51 0.53
3.00 1.23 0.41
2.70 1.86 0.69
2.85 1.62 0.57
3.00 1.35 0.45
2.70 1.97 0.73
2.85 1.74 0.61
3.00 1.47 0.49
3.15 1.17 0.37
2.70 2.08 0.77
2.85 1.85 0.65
INPUT
563
582
563
582
608
563
582
608
563
582
608
634
563
582
30
Q SHC SHF
2.60 1.59 0.61
2.75 1.35 0.49
2.60 1.69 0.65
2.75 1.46 0.53
2.88 1.18 0.41
2.60 1.79 0.69
2.75 1.57 0.57
2.88 1.29 0.45
2.60 1.90 0.73
2.75 1.68 0.61
2.88 1.41 0.49
3.05 1.13 0.37
2.60 2.00 0.77
2.75 1.79 0.65
INPUT
589
608
589
608
634
589
608
634
589
608
634
666
589
608
28
28
28
29
27
27
28
28
26
27
27
27
26
26
26
26
22
24
26
18
24
26
18
20
26
18
20
22
18
20
22
24
3.19 1.69 0.53
557 3.08 1.63 0.53
592 3.00 1.59 0.53
608 2.88 1.52 0.53
634
3.35 1.37 0.41
582 3.23 1.32 0.41
614 3.15 1.29 0.41
634 3.05 1.25 0.41
666
2.94 2.38 0.81
3.06 2.11 0.69
3.19 1.82 0.57
3.35 1.51 0.45
3.45 1.14 0.33
2.94 2.50 0.85
3.06 2.24 0.73
3.19 1.94 0.61
3.35 1.64 0.49
3.45 1.28 0.37
2.94 2.61 0.89
3.06 2.36 0.77
3.19 2.07 0.65
3.35 1.78 0.53
512
538
557
582
614
512
538
557
582
614
512
538
557
582
2.81 2.28 0.81
2.94 2.03 0.69
3.08 1.75 0.57
3.23 1.45 0.45
3.35 1.11 0.33
2.81 2.39 0.85
2.94 2.14 0.73
3.08 1.88 0.61
3.23 1.58 0.49
3.35 1.24 0.37
2.81 2.50 0.89
2.94 2.26 0.77
3.08 2.00 0.65
3.23 1.71 0.53
538
570
592
614
646
538
570
592
614
646
538
570
592
614
2.70 2.19 0.81
2.85 1.97 0.69
3.00 1.71 0.57
3.15 1.42 0.45
3.30 1.09 0.33
2.70 2.30 0.85
2.85 2.08 0.73
3.00 1.83 0.61
3.15 1.54 0.49
3.30 1.22 0.37
2.70 2.40 0.89
2.85 2.19 0.77
3.00 1.95 0.65
3.15 1.67 0.53
563
582
608
634
666
563
582
608
634
666
563
582
608
634
2.60 2.11 0.81
2.75 1.90 0.69
2.88 1.64 0.57
3.05 1.37 0.45
3.20 1.06 0.33
2.60 2.21 0.85
2.75 2.01 0.73
2.88 1.75 0.61
3.05 1.49 0.49
3.20 1.18 0.37
2.60 2.31 0.89
2.75 2.12 0.77
2.88 1.87 0.65
3.05 1.62 0.53
589
608
634
666
685
589
608
634
666
685
589
608
634
666
31
31
32
32
30
31
31
31
30
30
30
30
29
29
29
29
20
22
24
26
18
20
22
24
26
18
20
22
24
26
18
20
3.45 1.41 0.41
614 3.35 1.37 0.41
646 3.30 1.35 0.41
666 3.20 1.31 0.41
685
2.94 2.73 0.93
512 2.81 2.62 0.93
538 2.70 2.51 0.93
563 2.60 2.42 0.93
589
3.06 2.48 0.81
538 2.94 2.38 0.81
570 2.85 2.31 0.81
582 2.75 2.23 0.81
608
3.19 2.20 0.69
557 3.08 2.12 0.69
592 3.00 2.07 0.69
608 2.88 1.98 0.69
634
3.35 1.91 0.57
582 3.23 1.84 0.57
614 3.15 1.80 0.57
634 3.05 1.74 0.57
666
3.45 1.55 0.45
614 3.35 1.51 0.45
646 3.30 1.49 0.45
666 3.20 1.44 0.45
685
2.94 2.85 0.97
512 2.81 2.73 0.97
538 2.70 2.62 0.97
563 2.60 2.52 0.97
589
3.06 2.60 0.85
538 2.94 2.50 0.85
570 2.85 2.42 0.85
582 2.75 2.34 0.85
608
3.19 2.33 0.73
557 3.08 2.24 0.73
592 3.00 2.19 0.73
608 2.88 2.10 0.73
634
3.35 2.04 0.61
582 3.23 1.97 0.61
614 3.15 1.92 0.61
634 3.05 1.86 0.61
666
3.45 1.69 0.49
614 3.35 1.64 0.49
646 3.30 1.62 0.49
666 3.20 1.57 0.49
685
2.94 2.97 1.01
512 2.81 2.84 1.01
538 2.70 2.73 1.01
563 2.60 2.63 1.01
589
3.06 2.73 0.89
538 2.94 2.61 0.89
570 2.85 2.54 0.89
582 2.75 2.45 0.89
608
3.19 2.45 0.77
557 3.08 2.37 0.77
592 3.00 2.31 0.77
608 2.88 2.21 0.77
634
3.35 2.18 0.65
582 3.23 2.10 0.65
614 3.15 2.05 0.65
634 3.05 1.98 0.65
666
3.45 1.83 0.53
614 3.35 1.78 0.53
646 3.30 1.75 0.53
666 3.20 1.70 0.53
685
2.94 3.08 1.05
512 2.81 2.95 1.05
538 2.70 2.84 1.05
563 2.60 2.73 1.05
589
3.06 2.85 0.93
538 2.94 2.73 0.93
570 2.85 2.65 0.93
582 2.75 2.56 0.93
608
32
32
22
24
3.19 2.58 0.81
3.35 2.31 0.69
557
582
3.08 2.49 0.81
3.23 2.23 0.69
592
614
3.00 2.43 0.81
3.15 2.17 0.69
608
634
2.88 2.33 0.81
3.05 2.10 0.69
634
666
32 26 3.45 1.97 0.57
614 3.35 1.91 0.57
646 3.30 1.88 0.57
666 3.20 1.82 0.57
685
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
20 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 21
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
PERFORMANCE DATA COOL operation Rated frequency 65Hz
MSZ-GA25VA -
E1
: MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
CAPACITY:2.5(kW) SHF:0.79
INPUT:640(W)
INDOOR INDOOR
DB ( : ) WB ( : )
OUTDOOR DB( : )
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
28
28
28
29
27
27
28
28
26
27
27
27
26
26
26
26
25
25
25
25
24
24
24
24
22
23
23
23
21
21
22
22
18
20
18
20
22
18
20
22
18
20
22
24
18
20
22
24
18
20
22
24
26
18
20
22
24
26
18
20
22
24
26
18
2.45 1.49 0.61
2.58 1.26 0.49
2.45 1.59 0.65
2.58 1.36 0.53
2.73 1.12 0.41
2.45 1.69 0.69
2.58 1.47 0.57
2.73 1.23 0.45
2.45 1.79 0.73
2.58 1.57 0.61
2.73 1.34 0.49
2.88 1.06 0.37
2.45 1.89 0.77
2.58 1.67 0.65
2.73 1.44 0.53
2.88 1.18 0.41
2.45 1.98 0.81
2.58 1.78 0.69
2.73 1.55 0.57
2.88 1.29 0.45
3.03 1.00 0.33
2.45 2.08 0.85
2.58 1.88 0.73
2.73 1.66 0.61
2.88 1.41 0.49
3.03 1.12 0.37
2.45 2.18 0.89
2.58 1.98 0.77
2.73 1.77 0.65
2.88 1.52 0.53
3.03 1.24 0.41
2.45 2.28 0.93
627
653
627
653
678
627
653
678
627
653
678
704
627
653
678
704
627
653
678
704
730
627
653
678
704
730
627
653
678
704
730
627
2.25 1.37 0.61
2.40 1.18 0.49
2.25 1.46 0.65
2.40 1.27 0.53
2.55 1.05 0.41
2.25 1.55 0.69
2.40 1.37 0.57
2.55 1.15 0.45
2.25 1.64 0.73
2.40 1.46 0.61
2.55 1.25 0.49
2.70 1.00 0.37
2.25 1.73 0.77
2.40 1.56 0.65
2.55 1.35 0.53
2.70 1.11 0.41
2.25 1.82 0.81
2.40 1.66 0.69
2.55 1.45 0.57
2.70 1.22 0.45
2.85 0.94 0.33
2.25 1.91 0.85
2.40 1.75 0.73
2.55 1.56 0.61
2.70 1.32 0.49
2.85 1.05 0.37
2.25 2.00 0.89
2.40 1.85 0.77
2.55 1.66 0.65
2.70 1.43 0.53
2.85 1.17 0.41
2.25 2.09 0.93
666
685
666
685
717
666
685
717
666
685
717
736
666
685
717
736
666
685
717
736
762
666
685
717
736
762
666
685
717
736
762
666
2.08 1.27 0.61
2.23 1.09 0.49
2.08 1.35 0.65
2.23 1.18 0.53
2.38 0.97 0.41
2.08 1.43 0.69
2.23 1.27 0.57
2.38 1.07 0.45
2.08 1.51 0.73
2.23 1.36 0.61
2.38 1.16 0.49
2.55 0.94 0.37
2.08 1.60 0.77
2.23 1.45 0.65
2.38 1.26 0.53
2.55 1.05 0.41
2.08 1.68 0.81
2.23 1.54 0.69
2.38 1.35 0.57
2.55 1.15 0.45
2.68 0.88 0.33
2.08 1.76 0.85
2.23 1.62 0.73
2.38 1.45 0.61
2.55 1.25 0.49
2.68 0.99 0.37
2.08 1.85 0.89
2.23 1.71 0.77
2.38 1.54 0.65
2.55 1.35 0.53
2.68 1.10 0.41
2.08 1.93 0.93
691
723
691
723
742
691
723
742
691
723
742
768
691
723
742
768
691
723
742
768
794
691
723
742
768
794
691
723
742
768
794
691
31
31
32
32
30
31
31
31
30
30
30
30
29
29
29
29
20
22
24
26
18
20
22
24
26
18
20
22
24
26
18
20
2.58 2.09 0.81
2.73 1.88 0.69
2.88 1.64 0.57
3.03 1.36 0.45
2.45 2.38 0.97
2.58 2.19 0.85
2.73 1.99 0.73
2.88 1.75 0.61
3.03 1.48 0.49
2.45 2.47 1.01
2.58 2.29 0.89
2.73 2.10 0.77
2.88 1.87 0.65
3.03 1.60 0.53
2.45 2.57 1.05
2.58 2.39 0.93
653
678
704
730
627
653
678
704
730
627
653
678
704
730
627
653
2.40 1.94 0.81
2.55 1.76 0.69
2.70 1.54 0.57
2.85 1.28 0.45
2.25 2.18 0.97
2.40 2.04 0.85
2.55 1.86 0.73
2.70 1.65 0.61
2.85 1.40 0.49
2.25 2.27 1.01
2.40 2.14 0.89
2.55 1.96 0.77
2.70 1.76 0.65
2.85 1.51 0.53
2.25 2.36 1.05
2.40 2.23 0.93
685
717
736
762
666
685
717
736
762
666
685
717
736
762
666
685
2.23 1.80 0.81
2.38 1.64 0.69
2.55 1.45 0.57
2.68 1.20 0.45
2.08 2.01 0.97
2.23 1.89 0.85
2.38 1.73 0.73
2.55 1.56 0.61
2.68 1.31 0.49
2.08 2.10 1.01
2.23 1.98 0.89
2.38 1.83 0.77
2.55 1.66 0.65
2.68 1.42 0.53
2.08 2.18 1.05
2.23 2.07 0.93
723
742
768
794
691
723
742
768
794
691
723
742
768
794
691
723
32
32
22
24
2.73 2.21 0.81
2.88 1.98 0.69
678
704
2.55 2.07 0.81
2.70 1.86 0.69
717
736
2.38 1.92 0.81
2.55 1.76 0.69
742
768
32 26 3.03 1.72 0.57
730 2.85 1.62 0.57
762 2.68 1.52 0.57
794
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
21 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 22
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
PERFORMANCE DATA COOL operation Rated frequency 88Hz
MSZ-GA35VA -
E1
: MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
CAPACITY:3.5(kW) SHF:0.76
INPUT:1080(W)
INDOOR INDOOR
DB( : ) WB( : )
Q
21
SHC SHF INPUT
25
Q SHC SHF
OUTDOOR DB( : )
INPUT Q
27
SHC SHF INPUT Q
30
SHC SHF INPUT
28
28
28
29
27
27
28
28
26
27
27
27
26
26
26
26
25
25
25
25
24
24
24
24
22
23
23
23
21
21
22
22
18
20
18
20
22
18
20
22
18
20
22
24
18
20
22
24
18
20
22
24
26
18
20
22
24
26
18
20
22
24
26
18
4.11 2.39 0.58
4.29 1.97 0.46
4.11 2.55 0.62
4.29 2.14 0.50
4.46 1.70 0.38
4.11 2.71 0.66
4.29 2.32 0.54
4.46 1.87 0.42
4.11 2.88 0.70
4.29 2.49 0.58
4.46 2.05 0.46
4.69 1.59 0.34
4.11 3.04 0.74
4.29 2.66 0.62
4.46 2.23 0.50
4.69 1.78 0.38
4.11 3.21 0.78
4.29 2.83 0.66
4.46 2.41 0.54
4.69 1.97 0.42
4.83 1.45 0.30
4.11 3.37 0.82
4.29 3.00 0.70
4.46 2.59 0.58
4.69 2.16 0.46
4.83 1.64 0.34
4.11 3.54 0.86
4.29 3.17 0.74
4.46 2.77 0.62
4.69 2.35 0.50
4.83 1.84 0.38
4.11 3.70 0.90
864
907
864
907
940
864
907
940
864
907
940
983
864
907
940
983
864
907
940
983
1037
864
907
940
983
1037
864
907
940
983
1037
864
3.94 2.28 0.58
4.11 1.89 0.46
3.94 2.44 0.62
4.11 2.06 0.50
4.31 1.64 0.38
3.94 2.60 0.66
4.11 2.22 0.54
4.31 1.81 0.42
3.94 2.76 0.70
4.11 2.39 0.58
4.31 1.98 0.46
4.52 1.54 0.34
3.94 2.91 0.74
4.11 2.55 0.62
4.31 2.15 0.50
4.52 1.72 0.38
3.94 3.07 0.78
4.11 2.71 0.66
4.31 2.32 0.54
4.52 1.90 0.42
4.69 1.41 0.30
3.94 3.23 0.82
4.11 2.88 0.70
4.31 2.50 0.58
4.52 2.08 0.46
4.69 1.59 0.34
3.94 3.39 0.86
4.11 3.04 0.74
4.31 2.67 0.62
4.52 2.26 0.50
4.69 1.78 0.38
3.94 3.54 0.90
907
961
907
961
999
907
961
999
907
961
999
1037
907
961
999
1037
907
961
999
1037
1091
907
961
999
1037
1091
907
961
999
1037
1091
907
3.78 2.19 0.58
3.99 1.84 0.46
3.78 2.34 0.62
3.99 2.00 0.50
4.20 1.60 0.38
3.78 2.49 0.66
3.99 2.15 0.54
4.20 1.76 0.42
3.78 2.65 0.70
3.99 2.31 0.58
4.20 1.93 0.46
4.41 1.50 0.34
3.78 2.80 0.74
3.99 2.47 0.62
4.20 2.10 0.50
4.41 1.68 0.38
3.78 2.95 0.78
3.99 2.63 0.66
4.20 2.27 0.54
4.41 1.85 0.42
4.62 1.39 0.30
3.78 3.10 0.82
3.99 2.79 0.70
4.20 2.44 0.58
4.41 2.03 0.46
4.62 1.57 0.34
3.78 3.25 0.86
3.99 2.95 0.74
4.20 2.60 0.62
4.41 2.21 0.50
4.62 1.76 0.38
3.78 3.40 0.90
950
983
950
983
1026
950
983
1026
950
983
1026
1069
950
983
1026
1069
950
983
1026
1069
1123
950
983
1026
1069
1123
950
983
1026
1069
1123
950
3.64 2.11 0.58
3.85 1.77 0.46
3.64 2.26 0.62
3.85 1.93 0.50
4.03 1.53 0.38
3.64 2.40 0.66
3.85 2.08 0.54
4.03 1.69 0.42
3.64 2.55 0.70
3.85 2.23 0.58
4.03 1.85 0.46
4.27 1.45 0.34
3.64 2.69 0.74
3.85 2.39 0.62
4.03 2.01 0.50
4.27 1.62 0.38
3.64 2.84 0.78
3.85 2.54 0.66
4.03 2.17 0.54
4.27 1.79 0.42
4.48 1.34 0.30
3.64 2.98 0.82
3.85 2.70 0.70
4.03 2.33 0.58
4.27 1.96 0.46
4.48 1.52 0.34
3.64 3.13 0.86
3.85 2.85 0.74
4.03 2.50 0.62
4.27 2.14 0.50
4.48 1.70 0.38
3.64 3.28 0.90
994
1026
994
1026
1069
994
1026
1069
994
1026
1069
1123
994
1026
1069
1123
994
1026
1069
1123
1156
994
1026
1069
1123
1156
994
1026
1069
1123
1156
994
31
31
32
32
30
31
31
31
30
30
30
30
29
29
29
29
20
22
24
26
18
20
22
24
26
18
20
22
24
26
18
20
4.29 3.34 0.78
4.46 2.95 0.66
4.69 2.53 0.54
4.83 2.03 0.42
4.11 3.87 0.94
4.29 3.52 0.82
4.46 3.12 0.70
4.69 2.72 0.58
4.83 2.22 0.46
4.11 4.03 0.98
4.29 3.69 0.86
4.46 3.30 0.74
4.69 2.91 0.62
4.83 2.42 0.50
4.11 4.19 1.02
4.29 3.86 0.90
907
940
983
1037
864
907
940
983
1037
864
907
940
983
1037
864
907
4.11 3.21 0.78
4.31 2.84 0.66
4.52 2.44 0.54
4.69 1.97 0.42
3.94 3.70 0.94
4.11 3.37 0.82
4.31 3.01 0.70
4.52 2.62 0.58
4.69 2.16 0.46
3.94 3.86 0.98
4.11 3.54 0.86
4.31 3.19 0.74
4.52 2.80 0.62
4.69 2.35 0.50
3.94 4.02 1.02
4.11 3.70 0.90
961
999
1037
1091
907
961
999
1037
1091
907
961
999
1037
1091
907
961
3.99 3.11 0.78
4.20 2.77 0.66
4.41 2.38 0.54
4.62 1.94 0.42
3.78 3.55 0.94
3.99 3.27 0.82
4.20 2.94 0.70
4.41 2.56 0.58
4.62 2.13 0.46
3.78 3.70 0.98
3.99 3.43 0.86
4.20 3.11 0.74
4.41 2.73 0.62
4.62 2.31 0.50
3.78 3.86 1.02
3.99 3.59 0.90
983
1026
1069
1123
950
983
1026
1069
1123
950
983
1026
1069
1123
950
983
3.85 3.00 0.78
4.03 2.66 0.66
4.27 2.31 0.54
4.48 1.88 0.42
3.64 3.42 0.94
3.85 3.16 0.82
4.03 2.82 0.70
4.27 2.48 0.58
4.48 2.06 0.46
3.64 3.57 0.98
3.85 3.31 0.86
4.03 2.98 0.74
4.27 2.65 0.62
4.48 2.24 0.50
3.64 3.71 1.02
3.85 3.47 0.90
1026
1069
1123
1156
994
1026
1069
1123
1156
994
1026
1069
1123
1156
994
1026
32
32
22
24
4.46 3.48 0.78
4.69 3.10 0.66
940
983
4.31 3.36 0.78
4.52 2.98 0.66
999
1037
4.20 3.28 0.78
4.41 2.91 0.66
1026
1069
4.03 3.14 0.78
4.27 2.82 0.66
1069
1123
32 26 4.83 2.61 0.54
1037 4.69 2.53 0.54
1091 4.62 2.49 0.54
1123 4.48 2.42 0.54
1156
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
22 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 23
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
PERFORMANCE DATA COOL operation Rated frequency 88Hz
MSZ-GA35VA -
E1
: MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
CAPACITY:3.5(kW) SHF:0.76
INPUT:1080(W)
INDOOR INDOOR
DB ( : ) WB ( : )
OUTDOOR DB( : )
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
28
28
28
29
27
27
28
28
26
27
27
27
26
26
26
26
25
25
25
25
24
24
24
24
22
23
23
23
21
21
22
22
18
20
18
20
22
18
20
22
18
20
22
24
18
20
22
24
18
20
22
24
26
18
20
22
24
26
18
20
22
24
26
18
3.43 1.99 0.58
3.61 1.66 0.46
3.43 2.13 0.62
3.61 1.80 0.50
3.82 1.45 0.38
3.43 2.26 0.66
3.61 1.95 0.54
3.82 1.60 0.42
3.43 2.40 0.70
3.61 2.09 0.58
3.82 1.75 0.46
4.03 1.37 0.34
3.43 2.54 0.74
3.61 2.24 0.62
3.82 1.91 0.50
4.03 1.53 0.38
3.43 2.68 0.78
3.61 2.38 0.66
3.82 2.06 0.54
4.03 1.69 0.42
4.24 1.27 0.30
3.43 2.81 0.82
3.61 2.52 0.70
3.82 2.21 0.58
4.03 1.85 0.46
4.24 1.44 0.34
3.43 2.95 0.86
3.61 2.67 0.74
3.82 2.37 0.62
4.03 2.01 0.50
4.24 1.61 0.38
3.43 3.09 0.90
1058
1102
1058
1102
1145
1058
1102
1145
1058
1102
1145
1188
1058
1102
1145
1188
1058
1102
1145
1188
1231
1058
1102
1145
1188
1231
1058
1102
1145
1188
1231
1058
3.15 1.83 0.58
3.36 1.55 0.46
3.15 1.95 0.62
3.36 1.68 0.50
3.57 1.36 0.38
3.15 2.08 0.66
3.36 1.81 0.54
3.57 1.50 0.42
3.15 2.21 0.70
3.36 1.95 0.58
3.57 1.64 0.46
3.78 1.29 0.34
3.15 2.33 0.74
3.36 2.08 0.62
3.57 1.79 0.50
3.78 1.44 0.38
3.15 2.46 0.78
3.36 2.22 0.66
3.57 1.93 0.54
3.78 1.59 0.42
3.99 1.20 0.30
3.15 2.58 0.82
3.36 2.35 0.70
3.57 2.07 0.58
3.78 1.74 0.46
3.99 1.36 0.34
3.15 2.71 0.86
3.36 2.49 0.74
3.57 2.21 0.62
3.78 1.89 0.50
3.99 1.52 0.38
3.15 2.84 0.90
1123
1156
1123
1156
1210
1123
1156
1210
1123
1156
1210
1242
1123
1156
1210
1242
1123
1156
1210
1242
1285
1123
1156
1210
1242
1285
1123
1156
1210
1242
1285
1123
2.91 1.68 0.58
3.12 1.43 0.46
2.91 1.80 0.62
3.12 1.56 0.50
3.33 1.26 0.38
2.91 1.92 0.66
3.12 1.68 0.54
3.33 1.40 0.42
2.91 2.03 0.70
3.12 1.81 0.58
3.33 1.53 0.46
3.57 1.21 0.34
2.91 2.15 0.74
3.12 1.93 0.62
3.33 1.66 0.50
3.57 1.36 0.38
2.91 2.27 0.78
3.12 2.06 0.66
3.33 1.80 0.54
3.57 1.50 0.42
3.75 1.12 0.30
2.91 2.38 0.82
3.12 2.18 0.70
3.33 1.93 0.58
3.57 1.64 0.46
3.75 1.27 0.34
2.91 2.50 0.86
3.12 2.31 0.74
3.33 2.06 0.62
3.57 1.79 0.50
3.75 1.42 0.38
2.91 2.61 0.90
1166
1220
1166
1220
1253
1166
1220
1253
1166
1220
1253
1296
1166
1220
1253
1296
1166
1220
1253
1296
1339
1166
1220
1253
1296
1339
1166
1220
1253
1296
1339
1166
31
31
32
32
30
31
31
31
30
30
30
30
29
29
29
29
20
22
24
26
18
20
22
24
26
18
20
22
24
26
18
20
3.61 2.81 0.78
3.82 2.52 0.66
4.03 2.17 0.54
4.24 1.78 0.42
3.43 3.22 0.94
3.61 2.96 0.82
3.82 2.67 0.70
4.03 2.33 0.58
4.24 1.95 0.46
3.43 3.36 0.98
3.61 3.10 0.86
3.82 2.82 0.74
4.03 2.50 0.62
4.24 2.12 0.50
3.43 3.50 1.02
3.61 3.24 0.90
1102
1145
1188
1231
1058
1102
1145
1188
1231
1058
1102
1145
1188
1231
1058
1102
3.36 2.62 0.78
3.57 2.36 0.66
3.78 2.04 0.54
3.99 1.68 0.42
3.15 2.96 0.94
3.36 2.76 0.82
3.57 2.50 0.70
3.78 2.19 0.58
3.99 1.84 0.46
3.15 3.09 0.98
3.36 2.89 0.86
3.57 2.64 0.74
3.78 2.34 0.62
3.99 2.00 0.50
3.15 3.21 1.02
3.36 3.02 0.90
1156
1210
1242
1285
1123
1156
1210
1242
1285
1123
1156
1210
1242
1285
1123
1156
3.12 2.43 0.78
3.33 2.19 0.66
3.57 1.93 0.54
3.75 1.57 0.42
2.91 2.73 0.94
3.12 2.55 0.82
3.33 2.33 0.70
3.57 2.07 0.58
3.75 1.72 0.46
2.91 2.85 0.98
3.12 2.68 0.86
3.33 2.46 0.74
3.57 2.21 0.62
3.75 1.87 0.50
2.91 2.96 1.02
3.12 2.80 0.90
1220
1253
1296
1339
1166
1220
1253
1296
1339
1166
1220
1253
1296
1339
1166
1220
32
32
22
24
3.82 2.98 0.78
4.03 2.66 0.66
1145
1188
3.57 2.78 0.78
3.78 2.49 0.66
1210
1242
3.33 2.59 0.78
3.57 2.36 0.66
1253
1296
32 26 4.24 2.29 0.54
1231 3.99 2.15 0.54
1285 3.75 2.02 0.54
1339
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
23 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 24
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
PERFORMANCE DATA HEAT operation
MSZ-GA25VA -
E1
: MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1 Rated frequency 85Hz
CAPACITY:3.2(kW) INPUT:760(W)
INDOOR
DB( :
15
21
26
)
OUTDOOR WB( : )
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
2.02
494 2.43
593 2.85
669 3.26
722 3.68
768 4.06
790 4.48
806
1.92
532 2.30
631 2.72
699 3.10
752 3.52
790 3.90
813 4.30
844
1.73
570 2.14
669 2.53
737 2.94
790 3.36
828 3.74
851 4.16
874
NOTE Q:Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature
MSZ-GA35VA -
E1
: MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1 Rated frequency 96Hz
CAPACITY:4.0(kW) INPUT:1055(W)
INDOOR
DB( :
15
21
26
)
-10 -5 0
OUTDOOR WB( : )
5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
2.52
686 3.04
823 3.56
928 4.08
1002 4.60
1066 5.08
1097 5.60
1118
2.40
739 2.88
876 3.40
971 3.88
1044 4.40
1097 4.88
1129 5.38
1171
2.16
791 2.68
928 3.16
1023 3.68
1097 4.20
1150 4.68
1182 5.20
1213
NOTE Q:Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature WB : Wet-bulb temperature
24 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 25
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
9 ACTUATOR CONTROL
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
9-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
5 seconds 15 seconds
ON
Compressor
OFF
ON
Outdoor fan motor
OFF
9-2. R.V. coil control
Heating . . . . . . . . . . . . . . . . ON
Cooling. . . . . . . . . . . . . . . . . OFF
Dry . . . . . . . . . . . . . . . . . . . . OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
<COOL> <HEAT>
5 seconds 5 seconds
Compressor
ON
OFF
R.V.coil
ON
OFF
ON or OFF
Outdoor fan
ON motor
OFF
ON or OFF
9-3. Relation between main sensor and actuator
Sensor
Discharge temperature thermistor
Indoor coil temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Purpose
Protection
Cooling : Coil frost prevention
Compressor LEV w
1
Actuator
Outdoor fan motor
R.V. coil
Heating : High pressure protection
Cooling : High pressure protection
Heating : Defrosting w
1 w
1 w
1
Protection w
1
Cooling : Low ambient temperature operation w
1
Heating : Defrosting (Heater)
Indoor fan motor
Defrost heater w
1 MUZ-GA35VA
MUZ-GA35VAH w
2 MUZ-GA25VA
MUZ-GA25VAH
Solenoid valve w
2
25 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 26
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
10 SERVICE FUNCTIONS
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
CHANGE IN DEFROST SETTING
<JS> When the JS wire of the outdoor Inverter P.C. board is cut/ soldered, the defrost finish temperature is changed.
(Refer to 11-7-1.)
Jumper wire
JS soldered
(Initial setting) none
(cut)
MUZ-GA25VA -
E1
Defrost finish temperature
MUZ-GA25VAH -
E1
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
5 : 8 : 5 : 8 :
8 : 15 : 8 : 15 :
11 TROUBLESHOOTING
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn off the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful to the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring Housing point
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) When troubleshooting, refer to 11-2., 11-3. and 11-4.
26 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 27
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
11-2. Failure mode recall function
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (11-4.) disappears, the memorized failure details can be recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of the indoor/outdoor unit failure mode recall function
Operational procedure
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Turn ON the power supply.
1 While pressing both OPERATION SELECT button and TOO COOL
button on the remote controller at the same time, press RESET button.
2 First, release RESET button.
And release the other two buttons since all LCD in operation display
section of the remote controller is displayed after 3 seconds.
1 While pressing both OPERATION SELECT
button and TOO COOL button on the remote controller at the same time,
press RESET button.
2 First, release RESET button.
And release the other two buttons since all LCD
in operation display section of the remote controller
is displayed after 3 seconds.
W 1
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed).
With the remote controller headed towards the indoor unit, press TOO COOL or TOO
WARM button to adjust the set temperature to 24 : .
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal.
Beep sounds are emitted at the same
timing of the blinking of the left lamp of
OPERATION INDICATOR lamp. W 2
Judgment of indoor/outdoor abnormality
Yes
(Blinks)
Before blinking, does the left lamp of
OPERATION INDICATOR lamp stay ON for 3 seconds?
Stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
No
No
(OFF)
Yes
W
1. Regardless of normal or abnormal, a short
beep is emitted once as the signal is received.
Indoor unit is normal.
There is a possibility that the outdoor unit is abnormal.
Confirm the presence of abnormality according to the flow chart of the detailed outdoor unit failure mode recall function.
The indoor unit is abnormal.
Check the blinking pattern, and refer to confirm the abnormal point.
Make sure to check at least two consecutive blinking cycles. W 2
The outdoor unit is abnormal.
Check the blinking pattern, and refer to confirm the abnormal point (11-2.3.).
Make sure to check at least two consecutive blinking cycles. W 3
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
1
With the remote controller headed towards the indoor unit, press any button
that is not used in this failure mode recall function (e.g. TIMER button) .
OR
1
Turn OFF the power supply and turn ON it again.
2
Press RESET button of the remote controller.
•As for indoor unit, refer to service manual OB378.
Repair the defective parts.
Deleting the abnormal condition
1
After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2
Press EMERGENCY OPERATION switch so that the memorized
abnormal condition is deleted.
3
Release the failure mode recall function according to "Releasing the
failure mode recall function" mentioned above.
Note1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W 2. Blinking pattern when the indoor unit is abnormal:
2.5-second OFF
Blinking at 0.5second interval 2.5-second OFF
Blinking at 0.5second interval
ON
OFF
Beeps
Repeated cycle
Beeps
Repeated cycle
Beeps
Repeated cycle
W 3.Blinking pattern when the outdoor unit is abnormal:
Blinking at 0.5-
2.5-second OFF 3-second ON second interval
ON
OFF
No beep
Repeated cycle
Beeps
2.5-second OFF 3-second ON
No beep
Repeated cycle
Blinking at 0.5second interval
Beeps
27 www.ilmalämpöpumput.com
Repeated cycle
OB379 --1qxp 05.1.17 16:39 Page 28
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
2. Flow chart of the detailed outdoor unit failure mode recall function
Operational procedure
There is a possibility that the outdoor unit is abnormal.
Confirm the presence of abnormality according to the following procedures.
Confirm that the remote controller is in the failure mode recall function.
W 1
With the remote controller headed towards the indoor unit, press TOO COOL or TOO
WARM button to adjust the set temperature to 25 : .
Confirmation of abnormality presence
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? W 2
Blinks: The outdoor unit is abnormal.
Beep sounds are emitted at the same timing of the blinking of the left lamp of OPERATION INDICATOR
lamp.
Yes
(Blinks)
The outdoor unit is abnormal.
Check the blinking pattern, and refer to confirm the abnormal point(11-2.3.).
Make sure to check at least two consecutive blinking cycles. W 2
No
(OFF)
W 1. Regardless of normal or abnormal, 2 short
beeps are emitted as the signal is received.
The outdoor unit is normal.
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
1
With the remote controller headed towards the indoor unit, press any button
that is not used in this failure mode recall function (e.g. TIMER button) .
OR
1 Turn OFF the power supply and turn ON it again.
2 Press RESET button of the remote controller.
Release the failure mode recall function according to the left mentioned procedure.
Repair the defective parts.
Deleting the abnormal condition
1 After repairing the unit, recall the failure mode again according to
"Setting up the failure mode recall function" mentioned above.
2
Press EMERGENCY OPERATION switch so that the memorized
abnormal condition is deleted.
3
Release the failure mode recall function according to "Releasing the
failure mode recall function" mentioned above.
Note1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W 2.Blinking pattern when outdoor unit is abnormal:
2.5-second OFF 3-second ON
Blinking at 0.5second interval 2.5-second OFF 3-second ON
Blinking at 0.5second interval
ON
OFF
No beep
Repeated cycle
Beeps No beep
Repeated cycle
Beeps
Repeated cycle
28 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 29
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
3. Outdoor unit failure mode table
Abnormal point (Failure mode)
29 www.ilmalämpöpumput.com
OB379 --1qxp 05.1.17 16:39 Page 30
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
11-3. Instruction of troubleshooting
Start
Indoor unit operates.
Outdoor unit doesn't operate.
Indoor unit operates.
Outdoor unit doesn't operate normally.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation. w
Outdoor unit doesn't operate even in
Test Run operation. w
Unit doesn't operate normal operation in
COOL or
HEAT mode.
Indoor unit operates, when
EMERGENCY
OPERATION switch is pressed.
Indoor unit doesn't operate, when
EMERGENCY
OPERATION switch is pressed.
Check room temperature thermistor.
Refer to
"Test point diagram and voltage".
Refer to 11-6.
A
"How to check inverter/ compressor".
Refer to 11-6.
H
"Check of
R.V. coil".
Refer to
"Check of remote controller and receiver
P.C. board".
1. Check indoor / outdoor
connecting wire.
(Check if the power
is supplied to the
indoor unit.)
2. Refer to
"Check of indoor
electronic control
P.C. board and indoor
fan motor".
If blinking of OPERATION
INDICATOR lamp cannot be checked, it can be checked with failure mode recall function.
w As for "Test run opearation",
refer to indoor unit service
manual OB378.
As for indoor unit, refer to service manual OB378.
All lamps
Flash on and off at 0.5-second intervals
Cause:
Indoor unit
• The horizontal
vane is not
installed
correctly.
Left lamp
Flash on and off at
0.5-second intervals
Cause:
Indoor/
Outdoor unit
• Mis-wiring or
trouble of
serial signal.
Left lamp
2-time flash
Cause:
Indoor unit
• Trouble of
room temp-
erature/
indoor coil
thermistor
Left lamp
3-time flash
Cause:
Indoor unit
• Trouble of
indoor fan
motor
Left lamp
4-time flash
Cause:
Indoor unit
• Trouble of
indoor unit
control
system
Left lamp
5-time flash
Cause:
Outdoor unit
• Outdoor
power
system
abnormality
Left lamp
6-time flash
Cause:
Outdoor unit
• Trouble of
thermistor
in outdoor
unit
Left lamp
7-time flash
Cause:
Outdoor unit
• Trouble of
outdoor
control
system
Left lamp
14-time flash
Cause:
Outdoor unit
• Other
abnormality
Refer to
"Check of installation of the horizontal vane".
Refer to 11-6.
o
"How to check
of mis-wiring and serial signal error
(when outdoor unit doesn't work)".
Check room temperature thermistor and indoor coil thermistor.
Refer to
"Test point diagram and voltage".
Refer to
"Check of indoor fan motor".
Replace the indoor electronic control
P.C. board.
Refer to 11-6.
A
"How to check inverter/ compressor".
Refer to 11-6.
G
"Check of outdoor thermistors".
Replace inverter P.C. board.
Check 11-2.2.
"Flow chart of the detailed outdoor unit failure mode recall function."
30 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 31
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
11-4. Troubleshooting check table
NOTE 1. The location of LED is illustrated at the right figure. Refer to 11-7.1.
2. LED lights up during normal operation.
Inverter P.C. board (Parts side)
LED
Flashing
No.
1
2
3
4
5
6
7
Symptom
Outdoor unit does not operate
LED indication Abnormal point/ Condition
1-time flash every
2.5 seconds
Outdoor power system
Detection method
When it consecutively occurs 3times that the compressor stops for overcurrent protection or start-up failure protection within
1minute start-up.
Check point
· Check stop valve.
· Reconnect connector of compressor.
· Refer to 11-6.
A "How to check inverter/ compressor".
· Refer to 11-6.
C "Check of intelligent power module".
· Refer to 11-6.
G "Check of outdoor thermistors".
'Outdoor unit stops and restarts 3 minutes later' is repeated
NOTE:
For abnormality location, refer to
'Indoor troubleshooting check table'.
Refer to service manual OB371.
Outdoor thermistors
Outdoor control system
When discharge temperature thermistor, fin temperature thermistor, defrost thermistor, P.C. board temperature thermistor or ambient temperature thermistor shorts or opens during compressor running, compressor stops.
When nonvolatile memory data cannot be read properly, compressor stops.
6-time flash
2.5 seconds OFF serial signal
(When the left lamp of OPERATION INDICATOR lamp of indoor unit lights up or flashes 7-time.)
When the communication failure between the indoor and outdoor unit for 3 minutes.
14-time flash
2.5 seconds OFF
Outdoor unit
(Other abnormality)
When outdoor unit is failure.
2-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
Overcurrent protection
Discharge temperature overheat protection
When 14A(MUZ-GA25VA, MUZ-GA25VAH)/ 24A(MUZ-
GA35VA, MUZ-GA35VAH) current flows into intelligent power module, compressor stops and restarts 3 minutes later.
When discharge temperature thermistor exceeds 116 compressor stops. Compressor can restart if discharge temperature thermistor reads 100 :
: ,
or less 3 minutes later.
Replace inverter P.C. board.
Refer to 11-6.
O "How to check miswiring and serial signal error.
Refer to 11-2.2. Flow chart of the detailed outdoor unit failure mode recall function.
· Check stop valve.
· Reconnect connector of compressor.
· Refer to 11-6.
A "How to check
inverter/compressor".
· Refer to 11-6.
C
"Check of
intelligent power module".
· Check refrigerant circuit and refrigerant amount.
· Refer to 11-6.
L "Check of LEV".
8
9
10
11
12
13
14
15
16
17
18
19
4-time flash
2.5 seconds OFF
Fin temperature
/P.C. board temperature thermistor overheat protection
High pressure protection
When temperature of fin temperature thermistor on the heat sink exceeds 82 : (MUZ-GA25VA, MUZ-GA25VAH)/
83 : (MUZ-GA35VA, MUZ-GA35VAH) or temperature of P.C. board temperature thermistor exceeds 81 : (MUZ-GA25VA,
MUZ-GA25VAH)/ 85 : (MUZ-GA35VA, MUZ-GA35VAH), compressor stops and restarts 3 minutes later.
When indoor coil thermistor exceeds 70 : in HEAT mode.
When the defrost thermistor exceeds 70 : in COOL mode.
· Check around outdoor unit.
· Check outdoor unit air passage.
· Refer to 11-6.
fan motor".
I "Check of outdoor
5-time flash
2.5 seconds OFF
· Check refrigerant circuit and refrigerant amount.
· Check stop valve.
8-time flash
2.5 seconds OFF
10-time flash
2.5 seconds OFF
Compressor synchronous abnormality
Outdoor fan
When the waveform of compressor current is distorted.
When outdoor fan has stopped within 30 seconds 3-times a row after outdoor fan start-up, unit stops.
· Reconnect connector of compressor.
· Refer to 11-6.
A
"How to check
inverter/compressor".
· Refer to 11-6.
C "Check of
intelligent power module".
· Refer to 11-6.
I "Check of outdoor fan motor.
· Refer to 11-6.
N "Check of inverter
P.C. board.
· Refer to 11-6.
A "How to check inverter/compresssor".
12-time flash
2.5 seconds OFF
Compressor each phase current
9-time flash
2.5 seconds OFF
Inverter check mode
When compressor each phase current cannot be detected normally
When DC voltage of inverter cannot be detected normally.
Outdoor unit operates
1-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
Frequency drop by current protection
When current from power outlet exceeds 5.2A(MUZ-GA25VA,
MUZ-GA25VAH)/ 6.1A(MUZ-GA35VA, MUZ-GA35VAH), compressor frequency lowers.
Frequency drop by high pressure protection
Frequency drop by defrosting in COOL mode
Frequency drop by discharge temperature protection
When indoor coil thermistor exceeds 55 : in HEAT mode, compressor frequency lowers.
When indoor coil thermistor reads 8 : or less in COOL mode, compressor frequency lowers.
When discharge temperature thermistor exceeds 111 compressor frequency lowers.
: ,
Outdoor unit operates
13-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
8-time flash
2.5 seconds OFF
DC voltage
Low discharge temperature protection
PAM protection
PAM:
Pulse
Amplitude
Modulation
· Check for short time power failure by such as lightning strike.
· Refer to 11-6.
A "How to check inverter/compresssor".
The unit is normal, but check the following.
· Check if indoor filters are clogged.
· Check if refrigerant is short.
· Check if indoor/outdoor unit air circulation is short cycled.
When discharge temperature has been 50 minutes.
When the connector of compressor is disconnected, inverter check mode starts.
: or less for 20
When the overcurrent flows into IGBT(Insulated Gate Bipolar transistor : TR821) or when the bus-bar voltage reaches 320V or more, PAM stops and restarts.
· Check refrigerant circuit and refrigerant amount.
· Refer to 11-6.
L "Check of
LEV".
· Refer to 11-6.
G "Check of outdoor thermistors".
· Refer to 11-6.
L "Check of LEV".
· Check refrigerant circuit and refrigerant amount.
This is not malfunction.
PAM protection will be activated in the following cases;
1 Instantaneous power voltage drop
(Short time power failure)
2 When the power supply voltage is
high.
Check if the connector of the compressor is correctly connected.
Refer to 11-6.
A "How to check inverter/ compressor".
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
0.5-second ON 0.5-second ON
ON
OFF
2.5-second OFF 2.5-second OFF
31 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 32
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
11-5. Trouble criterion of main parts
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
Check method and criterion Part name
Defrost thermistor
(RT61)
Measure the resistance with a tester. (Part temperature –10˚C ~ 40˚C)
5 k
Normal
" ~ 55 k "
Abnormal
Open or short-circuit
Ambient temperature thermistor(RT65)
Discharge temperature thermistor(RT62)
Fin temperature thermistor(RT64)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
(Part temperature 0˚C ~ 40˚C)
Normal
150 k " ~ 600 k "
Abnormal
Open or short-circuit
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
(Part temperature 0˚C ~ 40˚C)
Normal
30 k " ~ 180 k "
Abnormal
Open or short-circuit
Compressor(MC)
Outdoor fan motor(MF)
INNER FUSE
(Only MUZ-GA25VA/H)
152 i 0
5
: CUT OFF
R.V. coil(21S4)
Measure the resistance between the terminals with a tester.
(Part temperature –20˚C ~ 40˚C)
MUZ-GA25VA
Normal
MUZ-GA25VAH
MUZ-GA35VA
MUZ-GA35VAH
Abnormal
U-V
U-W
V-W
1.58 " ~ 2.03
" 1.28 " ~ 1.66 "
Open or short-circuit
Measure the resistance between the terminals with a tester.
(Part temperature –20˚C ~ 40˚C)
Color of the lead wire
WHT – BLK
BLK – RED
RED – WHT
Normal
MUZ-GA25VA
MUZ-GA25VAH
292 " ~ 374 "
236 " ~ 304 "
MUZ-GA35VA
MUZ-GA35VAH
31 " ~ 41 "
31 " ~ 41 "
31 " ~ 41 "
Abnormal
Open or short-circuit
Measure the resistance between the terminals with a tester.
(Part temperature –20˚C ~ 40˚C)
Normal Abnormal
MUZ-GA25VA
MUZ-GA25VAH
MUZ-GA35VA
MUZ-GA35VAH Open or short-circuit
1.26 k " ~ 1.62 k " 1.20 k " ~ 1.55 k "
WHT
2
V
BLK RED WHT
Figure
V
RED BLK
3
W
1
U
MUZ-GA25VA MUZ-GA35VA
MUZ-GA25VAH MUZ-GA35VAH
WHT
2
RED BLK
3 1
W
FUSE
U
Expansion valve coil(LEV)
MUZ-GA35VA
MUZ-GA35VAH
Measure the resistance with a tester.
(Part temperature : –20˚C ~ 40˚C)
Normal Color of the lead wire
WHT – RED
RED – ORN
YLW – BRN
BRN – BLU
38 " ~ 50 "
Defrost heater(H)
Solenoid valve coil
(21R1)
MUZ-GA25VA
MUZ-GA25VAH
Measure the resistance with a tester.
(Part temperature -20˚C ~ 40˚C)
Normal
333 " ~ 428 "
Abnormal
Open or short-circuit
Measure the resistance with a tester.
(Part temperature -20˚C ~ 40˚C)
Normal
1,220 " ~ 1,580 "
Abnormal
Open or short-circuit
Abnormal
Open or short-circuit
WHT
6
RED
1
ORN
4
LEV
32 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 33
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
11-6. Troubleshooting flow
When OPERATION INDICATOR lamp flashes 5-time.
Outdoor unit does not operate.
A How to check inverter/ compressor
Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).
Check the voltage between terminals.
See 11-6.
B “Check of open phase” .
Are the voltages balanced?
Yes
Check the compressor.
No
Check the resistance of the intelligent power module.
See 11-6.
D “Check of compressor” .
B Check of open phase
● With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if the inverter is normal by measuring the balance of voltage between the terminals.
Output voltage [V]
115V
<< Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (test-run mode : refer to page 18)
<<Measurement point>> at 3 points
BLK (U)-WHT (V)
BLK (U)-RED (W)
WHT(V)-RED (W) w
Measure AC voltage between
the lead wires at 3 points.
NOTE 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of inverter P.C. board flashes 9 times.
See 11-6.
C 'Check of intelligent power module'.
Yes
Is the resistance infinite?
No
(0~several " )
Replace the inverter P.C.
board.
Replace the inverter P.C.
board and compressor.
Inverter P.C. board
(Parts side)
LED
9-time flash
2.5-second OFF
Flashing
C Check of intelligent power module
● Disconnect the connector (CN61) between the compressor and the intelligent power module, and measure the resistance between the terminals on the intelligent power module.
<<Measurement point>>
at 6 points
BLK-WHT, WHT-BLK
BLK-RED, RED-BLK
WHT-RED, RED-WHT
<<Judgement>>
Infinite [ " ]···········Normal
0~dozens of ······Abnormal (short) ohmmeter indication
"
X1
Normal
(infinite)
"
X1
Abnormal
(0~dozens of " )
33 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 34
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
D Check of compressor
Start
11-6.
E "Check of compressor winding".
Is the compressor normal?
Yes
No
11-6.
F "Check of compressor operation time".
Does the compressor operate continuously?
Yes
No
Ok
Replace the compressor.
Is the compressor operation time more than
10 seconds?
Yes
Check the refrigerant circuit.
No
Replace the compressor.
E Check of compressor winding
● Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between the compressor terminals.
<<Measurement point>> at 3 points
BLK-WHT
BLK-RED
WHT-RED
<<Judgement>> w
Measure the resistance between the
lead wires at 3 points.
Refer to 11-5..
0[ " ] ···············Abnormal [short]
Infinite[ " ] ·······Abnormal [open]
NOTE 1. Be sure to zero the ohmmeter before measurement.
2. Winding resistance for each phase at 20 : .
Refer to 3.SPECIFICATION.
Ohmmeter indication
"
X1
"
X1
Normal
(1~several " )
V
U
Compressor motor
Abnormal
(0 " ····· short)
WHT
2
RED BLK
3
W
1
"
X1
Abnormal
(infinite····· open)
F Check of compressor operation time
● Connect the compressor and activate the inverter. Then measure the time until the inverter stops due to over current.
<<Operation method>>
Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit. (Test-run mode)
<<Measurement>>
Measure the time from the start of outdoor fan running to the stop of compressor due to over current.
<<Judgement>>
For reference
0~10 seconds·····················Abnormal (compressor short or poor contact)
10~60 seconds···················Abnormal (compressor lock-out)
60 seconds~5 minutes·······Abnormal (refrigerant circuit defect) more than 5 minutes···········Normal
0 second
10 seconds
60 seconds
5 minutes
Outdoor fan starts
Abnormal
(Compressor winding short or layer short)
(Compressor connector poor contact)
Abnormal
(Compressor lock-out)
Abnormal
(Refrigerant circuit defect, etc.)
Normal
34 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 35
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
When OPERATION INDICATOR lamp flashes 6-time.
The thermistors in the outdoor unit are abnormal.
G Check of outdoor thermistors
Disconnect the connectors CN641, CN642 and CN643 from the inverter P.C. board.
(Check the characteristics of each thermistor.) Defrost thermistor RT61
Measure the resistance between CN641
1 and 2 .
Discharge temperature thermistor RT62
Measure the resistance between CN641
3 and 4 .
1 Reconnect the connectors CN641,
CN642 and CN643.
2 Disconnect the connector (CN61) between the compressor and intelligent power module.
Replace the inverter
P.C. board.
Fin temperature thermistor RT64
Measure the resistance between CN642
1 and 2 .
Ambient temperature thermistor RT65
Measure the resistance between CN643
1 and 2 .
Does the resistance of the thermistor have the characteristics (11-
7.1.)?
No
Yes
Replace the thermistor except RT64.
In case of RT64, replace the inverter P.C. board.
Since RT64 is combined with the inverter P.C. board.
Turn ON the power supply and press
EMERGENCY
OPERATION switch.
No
Does the unit operate
10 minutes or more except RT65?
Yes
Reconnect the
connector or the connecting wire.
H Check of R.V. coil w
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-5..
w
In case CN721 is not connected or R.V. coil is open, voltage is generated between the
terminal pins of the connector although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Disconnect connector (CN61) between the compressor and intelligent power module.
Turn ON the power supply and press
EMERGENCY OPERATION switch twice (HEAT mode).
Is there 230V AC between CN721 1 and
2 on the power P.C.board 3 minutes after the power supply is turned ON?
Yes
Replace the 4-way valve.
No Replace the power P.C. board.
CN721
Power P.C. board
(Soldered side)
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61) between the compressor and the intelligent power module.
Turn ON the power supply and press
EMERGENCY OPERATION switch once
(COOL mode).
Is there 230V AC between CN721 1 and
2 on the power P.C. board 3 minutes after the power supply is turned ON?
No
•Defective R.V. coil
•Defective 4-way valve
Yes Replace the power P.C. board.
35 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 36
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
Outdoor fan motor does not operate.
I Check of outdoor fan motor
MUZ-GA25VA
-
MUZ-GA25VAH
-
E1
E1
Check the resistance of fan motor. (Refer to 11-5.)
Is the resistance of fan motor normal?
Yes
No
Disconnect the connector CN771 on the power P.C. board.
Disconnect the connector (CN61) between compressor and power transistor module.
Turn ON the power supply and press the
EMERGENCY OPERATION switch.
Does the left lamp of
OPERATION INDICATOR lamp on the indoor unit light up?
No
Replace the outdoor fan motor.
Rectify indoor/ outdoor connecting wire.
Yes
Is there voltage 230V
AC between indoor terminal block S1 and
S2?
Yes
Fan motor
Indoor/ outdoor connecting wire
Outdoor terminal block
S3
S2
S1
1 2 3
CN771
Power P.C. board
3 minutes after, is there voltage 230V AC between CN771 2 and
3 on the power P.C. board?
Yes
Replace the outdoor fan motor.
No
No
Replace the indoor electronic control
P.C. board.
Replace the power P.C. board.
36 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 37
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
Outdoor fan motor does not operate.
I Check of outdoor fan motor
MUZ-GA35VA
-
E1
MUZ-GA35VAH
-
E1
Is the resistance between each terminal of outdoor fan motor
No
Yes
Disconnect CN932 from the inverter
P.C. board.
Inverter P.C. board
(Solder side)
CN931
CN932
Replace the outdoor fan motor.
Turn ON the power supply.
Rotate the outdoor fan slowly by hand, and measure the voltage of CN931 (Measurement of feedback output).
Between 1 (+) and 5 (-)
Between 2 (+) and 5 (-)
Between 3 (+) and 5 (-)
No
( Fixed to either 5V or 0V DC)
Does the voltage between each terminal become 5V and 0V DC repeatedly?
No
Yes
Does the outdoor fan rotate smoothly?
Ok
Yes
Inverter does not operate.
J Check of power supply
Disconnect the connector
(CN61) between compressor and intelligent power module.
Turn ON power supply and press
EMERGENCY OPERATION switch.
Does the left lamp of
OPERATION INDICATOR lamp on the indoor unit light up?
Yes
Is there voltage
280V ~ 370V DC between DB61 (+) and
DB61 (–) on the inverter P.C. board?
Refer to 11-7.1.
No
Check the electric parts in main circuit.
Yes
No
Indoor/ outdoor connecting wire
Outdoor terminal block
S3
S2
S1
Rectify indoor/ outdoor connecting wire.
Yes
Is there voltage 230V AC between the indoor terminal block S1 and
S2?
No
Replace the indoor electronic control
P.C. board.
Dose LED on the inverter
P.C. board light up or flash? Refer to 11-7.1.
Yes
No
Ok.
If flash, refer to
11-4.
DB61
Replace the inverter
P.C. board.
280V~370V DC
Inverter P.C. board
(Solder side)
37 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 38
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
Outdoor unit does not operate at all, or stops immediately due to overcurrent.
K Check of current-limiting resistor
When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.
Does the current-limiting resistor
(R64A or R64B) on the power P.C.
board short out? (Normal resistance : 5 ' )
No
Turn ON the power supply and press
EMERGENCY
OPERATION switch of the indoor unit.
Does LED on the inverter
P.C. board light up?
No Replace the power P.C.
board or the inverter P.C.
board.
Yes
Replace the power P.C. board.
Does the rush current limiting relay(X64) work properly? (Normally it close 1 minutes after outdoor unit power ON.)
No
Replace the power P.C.board.
● Check other electric parts in the main circuit together in the case of the defective current-limiting resistor.
Yes
Replace the power P.C.
board or the compressor.
Heating/Cooling does not work sufficiently.
L Check of LEV (Expansion valve)
Turn ON the power supply.
1
While pressing both OPERATION SELECT
button and TOO COOL button on the remote controller at the same time,
press RESET button.
2 First, release RESET button.
And release the other two buttons since all LCD
in operation display section of the remote controller
is displayed after 3 seconds.
With remote controller set toward the indoor unit, press
OPERATE/ STOP(ON/ OFF) button and confirm one beep tone.
1 While pressing both OPERATION SELECT
button and TOO COOL button on the remote controller at the same time,
press RESET button.
2 First, release RESET button.
And release the other two buttons since all LCD
in operation display section of the remote controller
is displayed after 3 seconds.
LEV operates in full-opening direction.
Do you hear the expansion valve "click, click·······"?
Do you feel the expansion valve vibrate on touching it ?
No
Is LEV properly fixed to the expansion valve?
Yes
Yes
No
Does the resistance of LEV have the characteristics?
Refer to 11-5.
No
Replace the LEV.
Ok
Yes
Properly fix the LEV to the expansion valve.
NOTE : After check of LEV, do the undermentioned
operations.
1. Turn OFF the power supply and
turn ON it again.
2. Press RESET button on the remote
controller.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1.Pin
3 (-) Pin 1 (+)
2.Pin
4 (-) Pin 1 (+)
3.Pin
5 (-) Pin 1 (+)
4.Pin
6 (-) Pin 1 (+)
Is there about 3~5V AC between each?
NOTE: Measure the voltage by an analog tester.
Yes
Replace the expansion valve.
No
Replace the inverter P.C. board.
38 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 39
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
Outdoor base gets frozen.
M Check of defrost heater <MUZ-GA25VAH MUZ-GA35VAH>
Check the following points before checking electric continuity.
1) Does the resistance of ambient temperature thermistor have the characteristics? Refer to 11-7.1.
2) Is the resistance of defrost heater normal? Refer to 11-5.
3) Does the heater protector remain conducted (not open)?
4) Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5 : or less, and let the defrost thermistor continue to read -1 : or less.
NOTE: In case both thermistors are more than the above
temperature, cool them with cold water etc...
Yes
Is there 230V AC between CN722 1 and 3 on the power P.C. board? Refer to 11-7.2.
No problem of the power P.C. board.
No
Yes
Is the voltage between CN726 2 (+)3 (-) on the power P.C. board 0V DC? Refer to 11-7.2.
No
Replace the power
P.C. board.
Replace the inverter P.C. board.
2 3
CN726
3
2
1
CN722
26H
H
230V AC
Outdoor fan motor does not operate, or stops immediately after starting up.
N Check of inverter P.C. board
Check the outdoor fan motor.
Refer to11-6.
I .
Check the connection of the connectors.
CN932 : driving output
CN931 : feedback signal
Inverter P.C.board
(Solder side)
CN931
CN932
Make the outdoor unit operate by starting EMERGENCY OPERATION .
Check the LED indication on the inverter P.C. board.
Does LED indicate 10-time flash?
No Check the corresponding section by
LED indication.
Yes
(10-time flash)
Outdoor fan motor protection
Replace the inverter P.C. board.
39 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 40
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second.
Outdoor unit doesn’t operate.
O How to check mis-wiring and serial signal error (when outdoor unit does not work)
Inverter P.C.board
(Parts side)
LED
Blinking
A
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON it again.
· Press EMERGENCY OPERATION switch.
Is serial signal error indicated
6 minutes later?
B
Yes
No
· Reinstall either the unit or the light each other away.
· Attach a filter on receiving section of the indoor unit.
Turn OFF the power supply.
Is there rated voltage of
230V AC in the power supply?
Yes
Turn ON the power supply.
No
Is there 230V AC between outdoor terminal block S1 and
S2?
No
Yes
Press EMERGENCY OPERATION switch.
Check the power supply.
Check the wiring.
Does the left lamp of OPERATION
INDICATOR lamp light up?
<Confirmation of the power to the indoor unit>
Yes
Is the self-check of the indoor unit displayed 6 minutes after?
Serial signal error display
The left lamp of
OPERATION
INDICATOR lamp blinks quickly.
Yes
A
No
No
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
No
Yes
Make them sure.
B
Turn OFF the power supply.
Check once more if the indoor/outdoor connecting wire is not mis-wiring.
Short-circuit outdoor terminal block S2 and
S3.
W
1
W
1. Mis-wiring may damage indoor electronic control
P.C. board during the operation.
Be sure to confirm the wiring is correct before the
operation starts.
Turn ON the power supply of the outdoor unit.
In 3 minutes after turning ON the power supply of the outdoor unit, does the LED on the inverter P.C. board repeat quick blinking "3.6-second-OFF and 0.8-second-ON"?
Be sure to check above in 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. When the inverter P.C.
board is normal, LED also blinks 6 times after 3 minutes.
No
(Lighting)
Replace the inverter
P.C. board.
W
2
W
2 Be careful to the residual
voltage of smoothing capacitor.
Yes
Remove the short-circuit between outdoor terminal block S2 and S3.
Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Be sure to release the failure-mode recall function after checking.
No
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Yes
Is there 230V AC between outdoor terminal block S1 and S2?
<Confirmation of power voltage>
No
Yes
Replace the indoor electronic control P.C. board.
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
As for indoor unit, refer to service manual OB378.
40 www.ilmalämpöpumput.com
Yes
Replace the indoor/outdoor connecting.
Yes Replace the indoor/outdoor connecting.
OB379 --2qxp 05.1.17 16:38 Page 41
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
When the cool air does not blow out from the indoor unit in Low Outside Temperature Operation, or the condensed water drops from the indoor unit.
P Operation check of the solenoid valve.
Enter the failure mode recall function.
Correct the connection.
No
Do you hear the operation sound
(click sound) of the solenoid valve every 5 seconds?
No
Is CN923 on the outdoor power P.C. board firmly connected without disconnection or loose connection?
Yes
Disconnect CN923 and measure the voltage between the pins using tester.
Yes
The solenoid valve is normal.
Check the ambient temperature thermistor (RT65) in the outdoor unit.
Trouble of the solenoid valve.
Trouble of the solenoid valve itself.
Yes
Measure the solenoid valve resistance.
Is the resistance normal ? (Open or short: abnormal) Refer to 11-5.
No
Trouble of the solenoid valve coil.
Yes
Does it repeat to go 0V and 230VAC at 5 second interval?
No
Are the cords between CN726, CN727 on the outdoor power P.C. board and CN725 on the outdoor inverter P.C. board firmly connected without disconnection or loose connection?
Yes
Measure the voltage between CN725 8 (+) and 2 (GND) on the outdoor inverter P.C.
board.
No
Correct the connection.
Does it repeat to go 0V and 12VDC at 5
second interval?
No
Replace the inverter P.C. board.
Yes
Replace the power P.C. board.
41 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 42
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
Q Electromagnetic noise enters into TV sets or radios
No
Is the unit earthed?
Earth the unit.
Yes
Is the distance between the antennas and the indoor unit within 3m, or is the distance between the antennas and the outdoor unit within 3m?
Yes
Extend the distance between the antennas and the indoor unit, or the antennas and the outdoor unit.
No
Is the distance between the
TV sets or radios and the indoor unit within 1m, or is the distance between the TV sets or radios and the outdoor unit within 3m?
No
Is there any antennas damage by rust or something , coaxial cable damage, or poor contact such as loosing of the connectors or wire disconnection of wiring of the antennas?
No
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas in close?
No
Yes
Yes
Yes
Extend the distance between the TV sets or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Replace the antennas.
Replace the coaxial cable.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
Even if all of the above conditions is fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring).
Check the followings before asking for service.
1.Devices affected by the electromagnetic noise
TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ;
indoor/outdoor unit of the air condioner, indoor/outdoor wiring, grounding wire, antennas, wiring
from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in.
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation check for
the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button
on the remote controller for power-on, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During
operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power off, when the
outdoor unit stops but the indoor/outdoor communication still runs on. In this situation check for
the electromagnetic noise.
After checking the above, consult the service representative.
42 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 43
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
11-7. Test point diagram and voltage.
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
1. Inverter P.C. board
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
Back side of unit
Output to drive compressor
(LDV,LDW,LDU)
Smoothing capacitor
(C63C)
Smoothing capacitor
(C63B)
Smoothing capacitor
(C63A)
DB61
280V ~ 370V
DC
(+) (-)
1 (+)
2 (+)
3 (+)
4 5V
5 GND
LED monitor lamp
Jumper wire for change in defrost setting (JS)
Front side of unit
Connecting wire with power P.C.
board
(CN725)
230V AC
DB61
LEV connector
(CN724)
Output to drive outdoor fan motor
(CN932)
MUZ-GA35VA
MUZ-GA35VAH
200
Fin temperature thermistor(RT64)
180
160
140
120
100
80
60
40
20
0
0 10 20 30 40 50 60 70 80
Temperature( : )
100
Defrost thermistor(RT61)
Ambient temperature thermistor(RT65)
90
80
70
60
50
40
30
20
10
0
-20 -10 0 10 20 30 40
Temperature( : )
700
Discharge temperature thermistor(RT62)
600
500
400
300
200
100
0
0 10 20 30 40 50 60 70 80 90 100 110 120
Temperature( : )
43 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 44
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
2. Power P.C. board
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
Back side of unit
MUZ-GA25VA
MUZ-GA25VAH
Solenoid valve coil
(CN923)
230V AC
Varistor
(NR63)
Varistor
(NR62)
Varistor
(NR64)
Front side of unit
230V AC
MUZ-GA25VA
MUZ-GA25VAH
Output to drive outdoor
Fan motor(CN771)
230V AC
R.V.coil(CN721)
230V AC
Connecting wire with inverter P.C.board
(CN726)
Refer to 11-6.
M
230V AC
Heater connector
(CN722)
Refer to 11-6.
M
MUZ-GA25VAH
MUZ-GA35VAH
44 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 45
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
12 DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
(2) The terminal with this connector has the
locking mechanism.
Sleeve
Locking lever
1 Slide the sleeve.
2 Pull the terminal while
pushing the locking
lever.
1 Hold the sleeve, and
pull out the terminal
slowly.
Connector
MUZ-GA25VA -
E1
MUZ-GA35VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VAH -
OUTDOOR UNIT
E1
OPERATING PROCEDURE
1. Removing the cabinet.
(1) Remove the screw fixing the service panel. (See Photo 2.)
(2) Pull down the service panel and remove it. (See Photo 2.)
(3) Disconnect the power supply and indoor/outdoor connecting wire.
(4) Remove the screws fixing the top panel. (See Photo 1.)
(5) Remove the top panel. (See Photo 1.)
(6) Remove the screws fixing the cabinet.
(7) Remove the cabinet.
(8) Remove the screws fixing the back panel.
(9) Remove the back panel.
PHOTOS
Photo 1
Screws of the top panel
Screws of the cabinet Screws of the top panel
Photo 2
Back panel
Screw of the service panel
Direction to remove
Screws of the cabinet
Hooks
Service panel
Screws of the cabinet
45 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 46
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
OPERATING PROCEDURE
2. Removing the inverter assembly, inverter P.C. board and power P.C. board
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor connecting wire and remove the back panel. (Refer to 1.)
(3) Disconnect the ground wires (See Photo 3.), the lead wire to the reactor and the following connectors;
<Power P.C. board>
CN721 (4-way valve)
CN771 (Fan motor) MUZ-GA25VA/GA25VAHE1
CN722 (Defrost heater) MUZ-GA25/GA35VAHE1
CN923 (Solenoid valve coil) MUZ-GA25VA/GA25VAH-
<Inverter P.C. board>
E1
CN931,CN932 (Fan motor) MUZ-GA35VA/GA35VAHE1
CN641 (Defrost thermistor and discharge temperature thermistor)
CN643 (Ambient temperature thermistor)
CN724 (LEV) MUZ-GA35VA/GA35VAHE1
(4) Remove the compressor connector (CN61).
(5) Remove the screws fixing the relay panel. (See Photo 3.)
(6) Remove the inverter assembly. (See Photo 3.)
(7) Disconnect all connectors and lead wires on the inverter
P.C. board. (See Photo 4.)
(8) Remove the inverter P.C. board from the inverter assembly.
(9) Remove the screw fixing the power P.C. board. (See Photo
4.)
(10) Disconnect all connectors and lead wires on the power P.C.
board.
(11) Remove the power P.C. board from the inverter assembly.
Photo 3
Photo 4
Heat sink
PHOTOS
Screws of the relay panel
Inverter
P.C. board
Screws of the ground wires
Power
P.C. board
3. Removing R.V. coil
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor connecting wire and remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Remove the R.V. coil. (See Photo 5.)
Screw of the power P.C. board
R.V. coil
4. Removing the discharge temperature thermistor and defrost thermistor
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor connecting wire and remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Pull out the discharge temperature thermistor from its holder. (See Photo 5.)
(5) Pull out the defrost thermistor from its holder. (See Photo 6.)
Photo 5
46 www.ilmalämpöpumput.com
Discharge temperature thermistor
OB379 --2qxp 05.1.17 16:38 Page 47
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
OPERATING PROCEDURE
5. Removing outdoor fan motor
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor connecting wire and remove the back panel. (Refer to 1.)
(3) Disconnect the connectors for outdoor fan motor.
(4) Remove the propeller nut.
(5) Remove the propeller.
(6) Remove the screws fixing the fan motor. (See Photo 7.)
(7) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Disconnect the power supply and indoor/outdoor connecting wire and remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge shows 0 kg/cm 2 (0 MPa).
(5) Detach the welded part of the suction and the discharge pipe connected with compressor.
(6) Remove the nuts of compressor legs.
(7) Remove the compressor.
(8) Detach the welded part of pipes connected with 4-way valve. (See Photo 8.)
Photo 6
PHOTOS
Photo 7
Defrost thermistor
Screws of the outdoor fan motor
Propeller
Photo 8
47 www.ilmalämpöpumput.com
Welded parts of 4-way valve
OB379 --2qxp 05.1.17 16:38 Page 48
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
13 PARTS LIST
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
13-1. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
23 20 19 18 17 16 15 14 10 9
24
1
2
22
21
13
11
12
3 4 5 6
7 8
48 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 49
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
13-1. OUTDOOR UNIT STRUCTURAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
No.
Part No.
Part Name
1
2
3
4
5
10
11
12
8
9
6
7
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
E02 928 525
E02 928 523
E02 838 523
E02 927 293
E02 928 293
E02 838 515
E02 927 515
E02 927 297
E02 927 630
E02 931 301
E02 927 301
E02 840 526
E02 840 381
E02 927 937
E02 096 936
E02 156 936
E02 096 642
E02 932 490
E02 931 492
E02 927 232
E02 927 521
E02 931 501
E02 927 501
E02 927 290
E02 928 290
E02 928 900
E02 927 900
E02 065 506
E02 927 661
E02 927 662
E02 927 245
E02 927 233
E02 838 640
E02 927 493
E02 927 961
E02 931 961
E02 928 079
CABINET
GRILLE
PROPELLER
PROPELLER
BASE
BASE
COMPRESSOR
COMPRESSOR
COMPRESSOR RUBBER SET
STOP VALVE (GAS)
STOP VALVE (LIQUID)
SERVICE PANEL
BACK PANEL
EXPANSION VALVE
EXPANSION VALVE COIL
4-WAY VALVE
4-WAY VALVE
THERMO HOLDER
CONDENSER WIRE NET
CONDENSER NET
CONDENSER NET
SEPARATOR
SEPARATOR
MOTOR SUPPORT
MOTOR SUPPORT
TOP PANEL
OUTDOOR HEAT EXCHANGER
OUTDOOR FAN MOTOR
OUTDOOR FAN MOTOR
DEFROST HEATER
HEATER PROTECTOR
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
CHECK VALVE
SOLENOID VALVE COIL
SOLENOID VALVE
Symbol Q'ty/unit in Wiring
Diagram
MUZMUZ-
GA25VA- GA25VAH-
E1 E1
MUZMUZ-
GA35VA- GA35VAH-
E1 E1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MC
MC
1
1
1
1
LEV
3
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
3
Remarks
KNB065FDTH
KNB073FDVH
3RUBBERS/SET
{ 9.52
{ 6.35
1 1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MF
MF
H
26H
21R1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
RA6V21-
RC0J50-
{ 3.0
✕{ 2.0
✕ 240
{ 3.0
✕{ 1.4
✕ 800
{ 3.0
✕{ 1.4
✕ 500
49 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 50
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
13-2. OUTDOOR UNIT ELECTRICAL PARTS
9
10
8
7
6
1 2 3 4 5
Part numbers that are circled are not shown in the illustration.
No.
1
2
3
4
7
8
5
6
9
10
11
12
Part No.
E02 838 337
E02 927 444
E02 931 444
E02 928 444
E02 932 444
E02 927 490
E02 928 490
E02 927 306
E02 927 308
E02 735 241
E02 735 382
E02 573 375
E02 927 374
E02 928 451
E02 932 451
E02 931 451
E02 934 451
E02 127 382
E02 661 385
Part Name
Symbol
Q'ty/unit in Wiring
Diagram
MUZ-
GA25VA-
E1
MUZ-
GA25VAH-
MUZ-
GA35VA-
E1 E1
MUZ-
GA35VAH-
E1
REACTOR
POWER P.C. BOARD
POWER P.C. BOARD
POWER P.C. BOARD
POWER P.C. BOARD
R.V. COIL
R.V. COIL
THERMISTOR SET
AMBIENT TEMPERATURE THERMISTOR
FUSE HOLDER
FUSE
TERMINAL BLOCK
TERMINAL BLOCK
INVERTER P.C. BOARD
INVERTER P.C. BOARD
INVERTER P.C. BOARD
INVERTER P.C. BOARD
FUSE
VARISTOR
L61
21S4
21S4
RT61,RT62
RT65
F61
TB1
TB2
F71,F801
NR62,NR63,NR64
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
DEFROST, DISCHARGE
250V/20A
3P
3P
Including heat sink and RT64
Including heat sink and RT64
Including heat sink and RT64
Including heat sink and RT64
250V/3.15A
50 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 51
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
MUZ-GA25VA -
E1
MUZ-GA35VA -
13-3. DRAIN SOCKET
E1
Outdoor unit { 42 drain hole
1
Soft vinyl chloride hose of
25mm inside diameter.
No.
Parts No.
Parts Name
1 E02 838 704 DRAIN SOCKET
Symbol in Wiring
Diagram
MUZ-GA25VA-
Q'ty/unit
E1 MUZ-GA35VAE1
1 1
Remarks
MUZ-GA25VA -
E1
MUZ-GA25VAH -
E1
MUZ-GA35VA -
E1
MUZ-GA35VAH -
E1
13-4. QUICK CLEAN KIT
● You can clean the surface of the heat exchanger and line flow fan if you attach QUICK CLEAN KIT to your vacuum cleaner.
2 3 4
No.
Parts No.
Parts Name
2
3
4
E02 927 113
E02 927 115
E02 927 112
BRUSH
NOZZLE
UNIVERSAL ADAPTER heat exchanger
Symbol in Wiring
Diagram
Q'ty/unit
MUZMUZMUZ-
GA25VA- GA25VAH- GA35VA-
E1 E1 E1
1
1
1
1
1
1
1
1
1
MUZ-
E1
1
1
1
Remarks
51 www.ilmalämpöpumput.com
OB379 --2qxp 05.1.17 16:38 Page 52
Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
C Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Jan. 2005. No. OB379 6
Made in Japan
New publication, effective Jan. 2005
Specifications subject to change without notice.
www.ilmalämpöpumput.com
advertisement
Key Features
- Split-type design
- Heat pump functionality
- R410A refrigerant
- Wireless control
- Technical data
- Component information
- Service procedures
- Outdoor unit specific