DELTA VFD-L 200W-400W, 200W-2HP AC Drive User Manual

DELTA VFD-L 200W-400W, 200W-2HP AC Drive User Manual

Below you will find brief information for VFD-L 200W-400W, VFD-L 200W-2HP. The VFD-L series AC drive is a simple general-purpose device, manufactured with high-quality components and incorporating the latest microprocessor technology. This manual will help in the installation, parameter setting, troubleshooting, and daily maintenance of the AC motor drive. The VFD-L series provides comprehensive fault diagnostic system that includes several different alarms and fault messages.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

VFD-L 200W-400W, VFD-L 200W-2HP User Manual | Manualzz
VFD-L Series User Manual
115V 200W-400W
230V 200W-2HP
Simple General Purpose AC Drive
ASIA
NORTH/SOUTH AMERICA
EUROPE
DELTA ELECTRONICS, INC.
DELTA PRODUCTS
DELTRONICS (Netherlands)
TAOYUAN Plant/
CORPORATION
B.V.
31-1, SHIEN PAN ROAD,
Sales Office/
Sales Office/
KUEI SAN INDUSTRIAL ZONE P.O. BOX 12173
Industriegebied Venlo Nr. 9031
TAOYUAN 333, TAIWAN, R.O.C 5101 DAVIS DRIVE
Columbusweg 20
TEL: 886-3-362-6301
RTP, NC 27709 U. S. A.
NL-5928 LC Venlo
FAX: 886-3-362-7267
TEL: 1-919-767-3813
The Netherlands
http://www.deltaww.com/acdrives FAX: 1-919-767-3969
TEL: 31-77-342-1930
http://www.deltaww.com/acdrives FAX: 31-77-342-1931
Preface
Thank you for choosing DELTA’s VFD-L series AC Drive. The VFD-L series is manufactured using
high-quality components, material and incorporating the latest microprocessor technology available.
This manual will help in the installation, parameter setting, troubleshooting, and daily maintenance of
the AC motor drive. To guarantee safe operation of the equipment, read the following safety
guidelines before connecting power to the AC motor drive. Keep this operating manual handy and
distribute to all users for reference.
Important Notes:
T
DANGER! AC input power must be disconnected before any maintenance. Do not connect or
disconnect wires while power is applied to the circuit. Only qualified technicians should perform
maintenance on the VFD-L.
T
CAUTION! There are highly sensitive MOS components on the printed circuit boards. These
T
DANGER! A charge may still remain in the DC-link capacitor with hazardous voltages even
T
T
components are especially sensitive to static electricity. To avoid damaging these components,
do not touch the circuit boards with metal objects or your bare hands.
after the power has been turned off. To avoid personal injury, do not remove the cover of the AC
drive until all “DISPLAY LED” lights on the digital keypad are off. Please note that there are live
components exposed when the AC drive is open,. Be careful to not touch these live parts.
The grounding method must
CAUTION! Ground the VFD-L using the ground terminal.
comply with the laws of the country where the AC drive is to be installed.
DANGER! The AC drive may be destroyed beyond repair if power is misapplied to the
input/output terminals. Never connect the AC drive output terminals U/T1, V/T2, W/T3 directly
to the AC main circuit power supply.
1
Chapter 1 Receiving and Inspection
This VFD-L AC drive has gone through rigorous quality control tests at the factory before shipment.
Since many things may happen during shipping, please check for the following after receiving the
AC motor drive.
è Inspect the unit to insure it was not damaged during shipment.
è Make sure that the part number indicated on the nameplate corresponds with the part number of
your order.
Nameplate Information: Example of 1HP230V
A C D riv e M o d e l
In p u t S p e c .
O u tp u t S p e c .
O u tp u t F re q . R a n g e
Bar C ode
S e ria l N O .
MODE
:V F D 0 0 7 L 2 1 A
IN P U T :1 P H /9 .7 A 3 P H /5 .1 A 2 0 0 - 2 4 0 V 5 0 - 6 0 H z
O U T P U T :3 P H 0 - 2 4 0 V 4 . 2 A 1 .6 k V A 1 H P
F r e q . R a n g e:1 .0 ~ 4 0 0 H z
0 0 7 L 2 1 AT 1 0 1 0 0 1
D E LTA E L E C T R O N IC S , IN C .
M A D E IN X X X X X
Model Explanation:
VFD 007 L 21 A
v e rs io n
A
B
šs ta n d a r d
šin c lu d in g E M I F i lte r
In p u t v o lta g e
V F D -L s e rie s
A p p lic a b le m o to r c a p a c ity
0 0 2 : 0 .2 k W
0 0 4 : 0 .4 k W
0 0 7 : 0 .7 5 k W
0 1 5 : 1 .5 k W
V a r ia b le F r e q u e n c y D r iv e
Series Number Explanation:
T 3 10 001
P ro d u c tio n n u m b e r
P ro d u c tio n w e e k
P ro d u c tio n y e a r 2 0 0 3
P ro d u c tio n fa c to ry
(T: Ta o y u a n , W : W u ju a n g )
If there is any nameplate information not corresponding to your purchase order or any problem,
please contact your distributor.
2
Dimension
STOP
RUN
FWD
REV
MODE
RESET
PROG
DATA
RUN
STOP
VFD-L
MIN.
MAX.
0.75KW
230V IPHASE
WARNING
Do not connect AC power to output
terminals (U,V,W).
Do not inspect components until LEDs
are turned off for at least 1min.
Read the user manual before operation.
8
+
RA RC
+ 10V AVI
M0 M1 M2 M3 GND
RS-485
3
Chapter 2 Wiring
Basic Wiring Diagram
Users must connect wiring according to the circuit diagram shown below. Please follow all National
and State wiring codes, when wiring the VFD-L.
M a i n C ir c u i t P o w e r
5/
87
6/
6/
97
7/
7/
:7
5/
F a c to r y d e fa u lt s e tt in g s
è
4 .7 K è
M o tor
+18V
M 0 4 .7 K
F o r w a r d / S to p
RA
M u l t i- f u n c ti o n in d i c a t i o n
o utp ut c on tacts
1 2 0 VA C / 2 8 V D C 3 A
RC
F a c to r y d e fa u lt :
F a u lt I n d ic a t io n
+18V
R e v e r s e /S to p
M1
R eset
M 2 4 .7 K
è
+18V
M 3 4 .7 K
è
+18V
M u l t i- s te p 1
R J - 11
C o m m o n S ig n a l
GND
'
6 1
R S-485
C o m m u n ica tio n
port
P o w e r s u p p l y f o r P o t e n t io m e t e r
+10V 10m A(M AX )
š è
0 10VD C
1
VR 3K 5K
A n a lo g cu rr e n t
1 :+ E V
2 :G N D
3 :S G 4 :S G +
+10V
M a s t e r F r e q . s e t ti n g 3
A n a lo g vo lta g e VR
,0
a
2
M a in cir c u it (p o w e r )
te rm in a ls
AV I
C o n t r o l c i r c u it t e r m i n a l s
GND
S h ie ld e d le a d s
N O T E : D o n o t p l u g i n a M o d e m o r te l e p h o n e li n e t o t h e R S - 4 8 5 c o m m u n i c a ti o n p o r t ,
p e r m a n e n t d a m a g e m a y r e s u l t . Te r m in a l s 1 & 2 a r e t h e p o w e r s o u r c e fo r t h e
o p t i o n a l c o p y k e y p a d a n d s h o u l d n o t b e u s e d w h il e u s i n g R S - 4 8 5
c o m m u n ic a tio n .
* I f t h e A C D r i v e m o d e l i s V F D 0 0 2 L 11 A / B , V F D 0 0 4 L 11 A / B , V F D 0 0 2 L 2 1 B , V F D 0 0 4 L 2 1 B
o r V F D 0 0 7 L 2 1 B , p le a s e u s e p o w e r te rm in a ls R /L 1 a n d S /L 2 .
* I f th e A C D r iv e m o d e l i s V F D 0 0 2 L 2 1 A , V F D 0 0 4 L 2 1 A o r V F D 0 0 7 L 2 1 A , 3 p h a s e p o w e r
m a y b e u s e d o n R /L 1 , S /L 2 , T /L 3 .
* I f th e A C D r iv e m o d e l i s V F D 0 1 5 L 2 3 A , s i n g l e p h a s e p o w e r i s n o t a l l o w e d .
4
Main circuit wiring
A C lin e in p u t te r m in a ls
g ro u n d i n g
S in g le p h a s e m o d e ls in p u t fr o m R / L 1 , S /L 2
R /L 1 S / L 2 T /L 3
U P /D O W N
L E D d is p l a y
F u n ctio n
D i s p la y k e y
D a ta
C o n f ir m a t i o n k e y
Frequency
s e t t in g k n o b
R U N /S T O P
M o t o r c a p a c it y
a n d in p u t p o w e r
T h e s ig n a l s e le c t io n
f o r AV I t o in p u t
DC 0~+10V
or 4~20 m A
RS485
c o m m u n ic a ti o n
port
U / T 1 V /T 2 W /T 3
M o t o r c o n n e c t io n s U /T 1 , V / T 2 , W / T 3
G ro u n d in g
Control circuit wiring
W ire G a u g e :2 2 -2 4 A W G
To rq u e : 4 K g f-c m
RA
+ 1 0 V AV I M 0 M 1 M 2
M3 GND
C o m m o n s ig n a l
M u lti- fu n c tio n in p u t s e le c tio n 3
M u lti- fu n c tio n in p u t s e le c tio n 2
M u lti- fu n c tio n in p u t s e le c tio n 1
5
M u lti-fu n c tio n a s s is ta n t te rm in a l
A n a lo g Vo lta g e , c u r re n t
fre q u e n c y c o m m a n d
P o w e r fo r s p e e d s e ttin g
M u lti- fu n c tio n in d ic a tio n
o u tp u t c o n ta c t
( 1 2 0 VA C /D C 2 8 V 3 A )
R e la y
RC
Wiring Notes: PLEASE READ PRIOR TO INSTALLATION.
1.
2.
CAUTION: Do not connect the AC input to any of the U/T1, V/T2, W/T3 terminals, as it will
damage the AC drive.
WARNING: Ensure all screws are tightened to the proper torque rating.
3. During installation, follow all national and local electrical, construction, and safety codes for the
country the drive is to be installed in.
4. Ensure the appropriate protective devices (circuit breaker or fuses) are connected between the
power supply and AC drive.
5. Make sure that the leads are connected correctly and the AC drive is properly grounded. (Ground
resistance should not exceed 0.1Ö .)
6. Use ground leads that comply with AWG/MCM standards and keep them as short as possible.
7. Multiple VFD-L units can be installed in one location. All the units should be grounded directly to
a common ground terminal. The VFD-L ground terminals may also be connected in parallel, as
shown in the figure below. Ensure there are no ground loops.
Forward
running
9/ When the AC drive output terminals U/T1, V/T2, and W/T3 are connected to the motor terminals
U, V, and W, respectively, the motor will rotate counterclockwise (as viewed from the shaft ends
of the motor) when a forward operation command is received. To reverse the direction of motor
rotation, switch over any of the two motor leads.
9. Make sure that the power is capable of supplying the correct voltage and required current to the
AC drive.
10. Do not attach or remove wiring when power is applied to the AC drive.
11. Do not monitor the signals on the circuit board while the AC drive is in operation.
12. Route the power and control wires separately, or orthogonal to each other.
13. If a filter is required for reducing EMI (Electro-Magnetic Interference), install it as close as
possible to AC drive. EMI can also be reduced by lowering the Carrier Frequency.
14. If the AC drive is installed in the place where a load reactor is needed, install the filter close to
U/T1, V/T2, W/T3 side of AC drive. Do not use a Capacitor or L-C Filter (Inductance-Capacitance)
or R-C Filter (Resistance-Capacitance).
15. When using a GFCI (Ground Fault Circuit Interrupt), select current sensor with minimum current
200mA, and minimum detection time 0.1-second to avoid nuisance tripping.
6
Chapter 3 Summary of Parameters
Group 0: User Parameters
Parameters
0-00
0-01
=
=
=
0-02
0-03
0-04
0-05
0-06
0-07
0-08
=The parameter may be set during operation.
Functions
Settings
Factory
Setting
Identity code of drive
(Read only)
1: 40W
2: 100W
3: 200W
4: 400W
5: 750W
6: 1.5KW
Rated current display
40W: 0.4A
(Read only)
100W: 0.8A
200W: 1.6A
400W: 2.5A
750W: 4.2A
1.5K: 7.0A
Parameter reset
10: Reset Parameters to Factory Setting
Start-up display of AC
0: F (Frequency command)
1: H (output frequency)
drive
2: U (user-defined unit)
3: A (output current)
User-defined Unit
0: Display User-Defined Unit (u)
1: Display Counter Value (C)
2: Display Process Operation (1=tt)
3: Display DC-BUS voltage (U)
4: Display output voltage (E)
User-defined coefficient K 0.1 ~ 160
Software version
Read only
Password input
0 ~ 999
Password configuration
0 ~ 999
0
0
0
1.0
#.#
0
0
Group 1: Basic Parameters
=
=
=
Parameters
Functions
1-00
1-01
1-02
1-03
1-04
1-05
1-06
1-07
1-08
1-09
1-10
1-11
Maximum operation Freq.
Maximum setting Freq.
Maximum output voltage
Mid-point freq.
Mid-point voltage
Minimum output freq.
Minimum output voltage
Upper bound of freq.
Lower bound of freq.
Accel time 1 (Tacc1)
Decel time 1 (Tdec1)
Accel time 2
Settings
50.0 ~ 400Hz
10.0 ~ 400Hz
2.0 ~ 255V
1.0 ~ 400Hz
2.0 ~ 255V
1.0 ~ 60.0Hz
2.0 ~ 255V
1 ~ 110%
0 ~ 100%
0.1 ~ 600 Sec
0.1 ~ 600 Sec
0.1 ~ 600 Sec
7
Factory
Setting
60.0
60.0
220
1.0
12.0
1.0
12.0
100
0.0
10.0
10.0
10.0
=
=
=
=
Parameters
1-12
1-13
1-14
1-15
1-16
1-17
1-18
Functions
Decel time 2
JOG Accel time
JOG Decel time
JOG frequency
Auto-accel/decel
S-curve setting in
acceleration
S-curve setting in
deceleration
Settings
0.1 ~ 600 Sec
0.1 ~ 600 Sec
0.0 ~ 600 Sec
1.0Hz~400Hz
0: Linear Accel/Decel
1: Auto accel, linear decel
2: Linear accel, auto decel,
3: Auto Accel/Decel
4: Linear accel. Auto decel, stall prevention
during deceleration
5: Auto accel. Auto decel, stall prevention
during deceleration
Factory
Setting
10.0
10.0
10.0
6.0
0
0~7
0
0~7
0
Group 2: Operation Method Parameters
Parameters
Functions
2-00
Source of frequency
command
2-01
Source of operation
command
Settings
0: Digital keypad
1: 0 ~ 10V from AVI
2: 4 ~ 20mA from AVI
3: Controlled by V.R on drive
4: RS-485 communication interface
0: By digital keypad
1: By external terminals, keypad STOP
enable
2: By external terminals, keypad STOP
disable
3: By RS-485 communication interface, keypad
STOP enable
Factory
Setting
0
0
4: By RS-485 communication interface, keypad
STOP disable
2-02
Stop method
2-03
2-04
Carrier freq.
Reverse operation inhibit
2-05
ACI (4 ~ 20mA)
input loss detection
0: Decel to 0Hz
1: Stop immediately, display EF
2: Run with the last freq.
0
2-06
Line Start Lockout
0: Enable
1: Disable
0
0: Ramp stop
1: Coast stop
3 ~10K Hz
0: Enable reverse
1: Disable reverse
2: Disable forward
8
0
10
0
Group 3: Output Function Parameters
Parameters
3-00
3-01
3-02
3-03
Functions
Settings
Desired freq. attained 1.0 ~ 400 Hz
Terminal count value 0 ~ 999
Preliminary count value 0 ~ 999
Multi-function (relay
0: not used
output)
1: AC drive operational
2: Max. Output Freq. Attained
3: Zero Speed
4: Over Torque
5: Base-Block (B.B.)
6: Low Voltage Detection
7: AC Drive Operation Mode
8: Fault Indication
9: Desired Freq. Attained
10: PLC Program Running
11: PLC Program Step Complete
12: PLC Program Complete
13: PLC Program Operation Pause
14: Terminal Count Value Attained
15: Preliminary Count Value Attained
16: Ready State Indicator
Factory
Setting
1.0
0
0
8
Group 4: Input Function Parameters
=
=
=
Parameters Functions
4-00
4-01
4-02
4-03
4-04
4-05
4-06
Potentiometer bias freq.
Potentiometer bias
polarity
Potentiometer freq. gain
Potentiometer
reverse motion
enable
Multi-function input
terminal1 (M1)
(d 0 d 20)
Multi-function input
terminal 2(M2)
Multi-function input
terminal 3(M3)
(d 0, d 4 d 20)
0.0
350Hz
0: positive bias
&
Settings
1: negative bias
1 200
0: not used
1: reverse motion enable
2: forward motion only
0: not used
1: M0: FWD/STOP, M1: REV/STOP
2: M0: RUN/STOP, M1: FWD/REV
3: M0, M1, M2: 3-wire operation control mode
4: External fault, normally open (N.O.)
5: External fault, normally closed (N.C.)
6: RESET
7: multi-step speed command 1
8: multi-step speed command 2
9: jog operation
10: accel/decel speed inhibit
11: first or second accel/decel time selection
12: base-block (B.B.),normally open (N.O.)
13: base-block (B.B.),normally closed (N.C)
9
Factory
setting
0.0
0
100
0
1
6
7
Parameters Functions
4-06
Multi-function input
terminal 3(M3)
(d 0, d 4 d 20)
Settings
14: increase master freq.
15: decrease master freq.
16: run PLC program
17: pause PLC
18: counter trigger signal
19: counter reset
20: select ACI/deselect AVI
Factory
setting
7
Group 5: Multi-step Speed and PLC Parameters
Parameters
5-00
5-01
5-02
5-03
5-04
5-05
5-06
5-07
5-08
Functions
Settings
1st step speed freq.
2nd step speed freq.
3rd step speed freq.
PLC mode
0.0 ~ 400Hz
0.0 ~ 400Hz
0.0 ~ 400Hz
0: Disable PLC operation
1: Execute one program cycle
2: Continuously execute program cycles
3: Execute one program cycle step by step
(separate by STOP)
4: Continuously execute one program cycle step by
step (separate by STOP)
PLC forward/reverse 0 ~ 15 (0: Forward 1: Reverse)
motion
Time duration step 0 0 ~ 65500 Sec
Time duration step 1 0 ~ 65500 Sec
Time duration step 2 0 ~ 65500 Sec
Time duration step 3 0 ~ 65500 Sec
Factory
Setting
0.0
0.0
0.0
0
0
0
0
0
0
Group 6: Protection Parameters
Parameters
6-00
6-01
6-02
6-03
Functions
Over-Voltage
Prevention Level
Over-current
Prevention Level
Over-torque
detection
Over-torque
detection level
Settings
0:disable
350~410V
0: disable
20~200%
0:disable
1:enable during constant speed operation and
continues until the continuous limit is reached.
2:enabled during constant speed operation and
halted after detection.
3:enabled during accel and continues before
continuous output time limit is reached.
4:enabled during accel and halted after over-torque
detection.
30 ~ 200%
10
Factory
Setting
390
170
0
150
Parameters
6-04
6-05
6-06
6-07
6-08
6-09
6-10
6-11
6-12
Functions
Over-torque
detection time
Electronic thermal
overload relay
Electronic thermal
characteristic
Present fault record
Second most recent
fault record
Third most recent
fault record
Forth most recent
fault record
Fifth most recent
fault record
Sixth most recent
fault record
Settings
0.1 ~ 10.0 Sec
Factory
Setting
0.1
0: Not used
1: Act with standard motor
2: Act with special motor
0
30~600 Sec
60
0: No fault occurred
1: oc (over current)
2: ov (over voltage)
3: oH (over heat)
4: oL (over load)
5: oL1 (electronic thermal)
6: EF (external fault)
7: Reserved
8: Reserved
9: ocA (current exceed during acceleration)
10: ocd (current exceed during deceleration)
11: ocn (current exceed during steady state)
0
Group 7: Motor Parameters
=
=
=
=
Parameters
Functions
7-00
7-01
Motor rated current
Motor no-load current
Torque
compensation
Slip compensation
7-02
7-03
Settings
30~120 %
0 ~ 90 %
0 ~ 10
Factory
Setting
85
50
1
0.0 ~ 10.0
0.0
Group 8: Special Parameters
Parameters
8-00
8-01
8-02
8-03
8-04
Functions
DC braking voltage level
DC braking time during
start-up
DC braking time during
stopping
Start-point for DC braking
Momentary power loss
Settings
0 ~ 30%
Factory
Setting
0
0.0 ~ 60.0 Sec
0.0
0.0 ~ 60.0 Sec
0.0
0.0 ~ 400.0 Sec
0: Stop operation after momentary power
loss.
1: Continues after momentary power loss,
speed search starts with master freq.
2: Continues after momentary power loss,
speed search starts with min. output
freq.
0.0
0
11
Parameters
Functions
8-08
8-09
8-10
8-11
8-12
8-13
8-14
8-15
Max. allowable power loss
time
B.B. time for speed search
Max. speed search current
level
Skip freq. 1 upper bound
Skip freq. 1 lower bound
Skip freq. 2 upper bound
Skip freq. 2 lower bound
Skip freq. 3 upper bound
Skip freq. 3 lower bound
Auto restart after fault
AVR function
8-16
8-17
Dynamic braking voltage
DC braking lower bound limit
8-05
8-06
8-07
Settings
Factory
Setting
0.3 ~ 5.0 Sec
2.0
0.3~5.0 Sec
0.5
30~200%
150
0.0~400 Hz
0.0~400 Hz
0.0~400 Hz
0.0~400 Hz
0.0~400 Hz
0.0~400 Hz
0~10
0: AVR function enable
1: AVR function disable
2: AVR function disable when decel
350 ~ 450V
0.0 ~ 400 Hz
0.0
0.0
0.0
0.0
0.0
0.0
0
2
380
0.0
Group 9: Communication Parameters
=
=
=
=
=
Parameters
Functions
9-00
9-01
Communication address
Transmission speed
9-02
Transmission fault
treatment
9-03
9-04
Modbus communication
watchdog timer
Settings
1 ~ 247
0: Baud rate 4800
1: Baud rate 9600
2: Baud rate 19200
0: Warn and continue running
1: Warn and ramp to stop
2: Warn and coasting stop
3: No warn and keep running
0: Disable
Factory
Setting
1
1
0
0
1~20: 1 ~ 20 Sec
Communication
protocol
ASCII
mode
RTU
mode
12
0:
1:
2:
3:
4:
5:
6:
7:
8:
7,N,2
7,E,1
7,O,1
8,N,2
8,E,1
8,O,1
8,N,2
8,E,1
8,O,1
0
CHAPTER 4 Troubleshooting and Fault Information
The VFD-L AC drive has a comprehensive fault diagnostic system that includes several different
alarms and fault messages. Once a fault is detected, the corresponding protective functions will be
activated. The following faults are displayed on the AC drive digital keypad. The six most recent
faults can be read on the digital keypad display by viewing Pr.6-07 to Pr.6-12.
NOTE: faults can be cleared by pressing the Reset key on the keypad or Input Terminal.
Common Problems and Solutions:
Fault
Fault Descriptions
Corrective Actions
Name
1. Check whether the motors horsepower
corresponds to the AC drive output power.
2. Check the wiring connections between the
AC drive and motor for possible short circuits.
3. Increase the Acceleration time (Pr.1-09,
Pr.1-11).
The AC drive detects an abnormal
increase in current.
4. Check for possible excessive loading
conditions at the motor.
5. If there are any abnormal conditions when
operating the AC drive after the short-circuit
is removed, the drive should be sent back to
manufacturer.
1. Check whether the input voltage falls within
The AC drive detects that the DC bus
the rated AC drive input voltage.
voltage has exceeded its maximum 2. Check for possible voltage transients.
3. Bus over-voltage may also be caused by
allowable value.
motor regeneration. Increase the decel time.
1. Ensure that the ambient temperature falls
within the specified temperature range.
2. Make sure that the ventilation holes are not
The AC drive temperature sensor
obstructed.
detects excessive heat.
3. Remove any foreign objects on the heat sink
and check for possible dirty heat-sink fins.
4. Provide enough spacing for adequate
ventilation.
The AC drive detects that the DC bus
Check whether the input voltage falls within the
voltage has fallen below its minimum
rated AC drive’s input voltage.
value.
1. Check for possible motor overload.
2. Check electronic thermal overload setting.
3. Increase motor capacity.
Internal electronic overload trip
4. Reduce the current level so that the drive
output current does not exceed the value set
by the Motor Rated Current Pr.7-00.
The external terminal EF-GND goes When external terminal EF-GND is closed, the
from OFF to ON.
output will be turned off. (under N.O.   ( )
Motor overload. Check the
1. Reduce the motor load.
2. Adjust the over-torque detection setting to an
parameter settings ( Pr.6-03 to
Pr.6-05)
appropriate setting.
13
Fault
Name
Fault Descriptions
Over-current during acceleration:
1. Short-circuit at motor output.
2. Torque boost too high.
3. Acceleration time too short.
4. AC drive output capacity is too
small.
Over-current during deceleration:
1. Short-circuit at motor output.
2. Deceleration time too short.
3. AC drive output capacity is too
small.
Over-current during steady state
operation:
1. Short-circuit at motor output.
2. Sudden increase in motor loading.
3. AC drive output capacity is too
small.
Corrective Actions
1. Check for possible poor insulation at the
output line.
2. Decrease the torque boost setting in Pr.7-02.
3. Increase the acceleration time.
4. Replace with the AC drive with one that has a
higher output capacity (next HP size).
1. Check for possible poor insulation at the
output line.
2. Increase the deceleration time.
3. Replace with the AC drive with one that has a
higher output capacity (next HP size).
1. Check for possible poor insulation at the
output line.
2. Check for possible motor stall.
3. Replace with the AC drive with one that has a
higher output capacity (next HP size).
1. Switch off power supply.
Internal memory IC can not be
2. Check whether the input voltage falls within
programmed.
the rated AC drive input voltage.
3. Switch the AC drive back on.
1. Check the connections between the main
Internal memory IC can not be read.
control board and the power board.
2. Reset drive to factory defaults.
1. Switch off power supply.
2. Check whether the input voltage falls within
Drive’s internal circuitry abnormal.
the rated AC drive input voltage. Switch on
the AC drive.
Hardware protection failure
Return to the factory.
Software protection failure
Return to the factory.
Don’t use the function of auto acceleration/
Auto accel/decel failure
deceleration.
1. Check the connection between the AC drive
and computer for loose wires.
Communication Error
2. Check if the communication protocol is
properly set.
External Base Block.
1. When the external input terminal (B.B) is
AC drive output is turned off.
active, the AC drive output will be turned off.
2. Disable this connection and the AC drive will
begin to work again.
The AC drive detects excessive drive 1. Check whether the motor is overloaded.
output current.
2. Reduce torque compensation setting as set in
Pr.7-02.
3. Increase the AC drive’s output capacity.
4. Note: The AC drive can withstand up to 150%
of the rated current for a maximum of 60
seconds.
14
Standard Specifications
Voltage Class
115V
Model Number VFD-
L
A/B
Output Rating
Applicable Motor Output (kW)
Rated Output Capacity (KVA)
Rated Output Current (A)
Max. Output Voltage (V)
230V
002
004
002
004
007
015
0.2
0.4
0.2
0.4
0.7
1.5
0.6
1.0
0.6
1.0
1.6
2.7
1.6
2.5
4.2
7.0
1.6
2.5
3-phase corresponds
to double input
voltage
Three-phase corresponds to input voltage
Rated Frequency (Hz)
Power
Rated Input Current (A)
Input voltage Tolerance
1.0~400Hz
6
9
4.9/1.9
Control
Characteristics
Operating Characteristics
Overload Endurance
Accel/Decel Time
V/F pattern
Stall Prevention Level
Keypad
Frequency
Setting External Signal
External Signal
Multi-function Input Signal
Multi-function Output Signal
Other Function
Protection
Environment
Other
Cooling
Installation Location
Ambient Temperature
Storage Temperature
Ambient Humidity
Vibration
3-phase
180~264V
50/60Hz
SVPWM (Sinusoidal Pulse Width Modulation, carried frequency 3kHz~10kHz)
0.1Hz
Including the auto-torque, auto-slip compensation, starting torque can be 150% at
5 Hz
150% of rated current for 1 minute
0.1~600Sec. (can be set individually)
V/F pattern adjustable
20~200%, setting of Rated Current
Setting by
keys or V.R
Potentiometer-5KΩ/0.5W, DC 0 ~ +10V (input impedance 47KΩ), 4~20mA (output
impedance 250Ω), multi-function inputs1 to 3 (3steps, JOG, UP/DOWN
command), communication setting
Operation
Keypad
Setting
Signal
Ì/9
±5%
Output Frequency Resolution
Torque Characteristics
9.7/5.1
Single / 3-phase
180~264V 50/60Hz
Single phase
90~132V 50/60Hz
Frequency tolerance
Control system
6.5/2.7
Setting by RUN//STOP keys
M0,M1,M2,M3 can be combined to offer various modes of operation, RS-485
communication port
Multi-step selection 0 to 3, Jog, accel/decel inhibit, first/second accel/decel switch,
counter, PLC Operation, external Base Block (NC,NO) selection
AC Drive Operating, Frequency Attained, Non-zero speed, Base Block, Fault
Indication, Local/Remote indication, PLC Operation indication.
AVR, S-curve, Over-Voltage Stall Prevention, DC Braking, Fault Records,
Adjustable Carried Frequency, Starting Frequency Setting of DC Braking ,
Over-Current Stall Prevention, Momentary Power Loss restart, Reverse Inhibition,
Frequency Limits, Parameter Lock/Reset
Over Voltage, Over Current, Under Voltage, Overload, Electronic thermal,
Overheating, Self-testing
Including EMI Filter
Forced air-cooling
Altitude 1,000 m or below, keep from corrosive gasses, liquid and dust
¬-40¬ (Non-Condensing and not frozen)
-20¬ to 60¬
-10
Below 90%RH (non-condensing)
2
9.80665m/s (1G) less than 20Hz, 5.88m/s (0.6Gat) 20 to 50Hz
2
15

advertisement

Key Features

  • Simple general-purpose AC drive
  • High-quality components
  • Latest microprocessor technology
  • Installation guide
  • Parameter setting guide
  • Troubleshooting guide
  • Daily maintenance guide
  • Comprehensive fault diagnostic system
  • Different alarms and fault messages

Frequently Answers and Questions

What is the purpose of the VFD-L series AC drive?
The VFD-L series AC drive is a simple general-purpose device used for controlling and regulating the speed of AC motors.
What are the key features of the VFD-L series AC drive?
The VFD-L series AC drive is designed with high-quality components and incorporates the latest microprocessor technology. It offers features such as comprehensive fault diagnostics, easy installation, and versatile parameter setting options.
What kind of information does this user manual provide?
This manual guides you through the installation, parameter setting, troubleshooting, and daily maintenance of the VFD-L AC drive. It also includes information about the fault diagnostic system and provides solutions for common problems.
What are some common problems that can occur with the VFD-L series AC drive?
Common problems include over-current, over-voltage, over-heating, and communication errors. The manual provides troubleshooting steps and corrective actions for each of these issues.

Related manuals