air conditioner Installation manual
Below you will find brief information for air conditioner . This document describes the installation process for the air conditioner, including details on connecting pipes and wiring. It also covers important safety precautions that should be taken during the installation process to ensure the unit operates properly and safely.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
INSTALLATION MANUAL
Middle Static Pressure Duct Type
Thank you very much for purchasing our air conditioner,
Before using your air conditioner , please read this manual carefully and keep it for future reference.
If used as MULTI unit, please refer to the Installation & operation manuals packed with outdoor unit.
CONTENTS PAGE
SAFETY PRECAUTIONS.......................................................................................1
If installation is defective, it will cause water leakage, electrical shock and fire.
INSTALLATION INFORMATION........................................................................... 2
When installing the unit in a small room, take measures
ATTACHED FITTINGS.............................................................................................3
INSPECTING AND HANDLING THE UNIT.........................................................4
INDOOR UNIT INSTALLATION.................................................................................4
OUTDOOR UNIT INSTALLATION............................................................................11
against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage.
Contact the place of purchase for more information.
Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
INSTALL THE CONNECTING PIPE..................................................................15
REFRIGERANT PIPE..........................................................................................16
REFRIGERANT PIPE CONNECTION ...............................................................17
Use the attached accessories parts and specified parts for installation. otherwise, it will cause the set to fall, water leakage, electrical shock and fire.
CONNECTIVE DIAGRAM......................................................................................18
CONNECT THE DRAIN PIPE..............................................................................18
FRESH AIR DUCT INSTALLATION.......................................................................19
CONTROL..............................................................................................20
WIRING.................................................................................................20
TEST OPERATION................................................................................................21
1. SAFETY PRECAUTIONS
Keep this manual where the operator can easily find them.
Read this manual attentively before starting up the units.
For safety reason the operator must read the following cautions carefully.
Installation must be performed in accordance with the requirement of NEC and CEC by authorized personnel only.
The safty precautions listed here are divided into two categories.
WARNING
If you do not follow these instrutions exactly, the unit may cause property damage, personal injury or loss of life.
CAUTION
If you do not follow these instrutions exactly, the unit may cause minor or moderate property damage, personal injury.
After completing the installation, make sure that the unit operates properly during the start-up operation. Please instruct the customers on how to operate the unit and keep it maintained.Also, inform customers that they should store this installation manual along with the owner's manual for future reference.
WARNING
Be sure only trained and qualified service personnel to install, repair or service the equipment.
Improper installation, repair, and maintenance may result in electric shocks, short-circuit, leaks, fire or other damage to the equipment.
Install at a strong and firm location which is able to withstand the set' s weight.
If the strength is not enough or installation is not properly done, the set will drop to cause injury.
The appliance must be installed 2.3m / 7.5ft above floor.
The appliance shall not be installed in the laundry.
Before obtaining access to terminals, all supply circuits must be disconnected.
The appliance must be positioned so that the plug is accessible.
The enclosure of the appliance shall be marked by word, or by symbols, with the direction of the fluid flow.
For electrical work, follow the local national wiring standard, regulation and this installation instructions. An independent circuit and single outlet must be used.
If electrical circuit capacity is not enough or defect in electrical work, it will cause electrical shock or fire.
Use the specified cable and connect tightly and clamp the cable so that no external force will be acted on the terminal.
If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
Wiring routing must be properly arranged so that control board cover is fixed properly.
If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock.
If the supply cord is damaged, it must be replaced by the manufacture or its service agent or a similarly qualified person in order to avoid a hazard.
An all-pole disconnection switch having a contact separation of at least 3mm/0.118in in all poles should be connected in fixed wiring.
When carrying out piping connection, take care not to let air substances go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
Do not modify the length of the power supply cord or use of extension cord, and do not share the single outlet with other electrical appliances.
Otherwise, it will cause fire or electrical shock.
Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling and causing accidents. installation manual
1
If the refrigerant leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant comes into the place contacting with fire.
The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
After completing the installation work, check that the refrigerant does not leak.
Toxic gas may be produced if the refrigerant leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
The appliance shall be installed in accordance with national wiring regulations.
Do not operate your air conditioner in a wet room such as a bathroom or laundry room.
An all-pole disconnection device which has at least 3mm clearances in all poles , and have a leakage current that may exceed 10mA, the residual current device (RCD) having a rated residual operating current not exceeding
30mA, and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
CAUTION
Ground the air conditioner.
Do not connect the ground wire to gas or water pipes, lightning rod or a telephone ground wire.inappropriate grounding may result in electric shocks.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks.
Connect the outdoor unit wires , then connect the indoor unit wires.
You are not allowed to connect the air conditioner with the power supply until the wiring and piping is done.
While following the instructions in this installation manual, install drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation.
Improper drain piping may result in water leakage and property damage.
Install the indoor and outdoor units, power supply wiring and connecting wires should be at least 1 meter away from televisions or radios in order to prevent image interference or noise.
Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.
The appliance is not intended for use by young children or infirm persons without supervision.
Don't install the air conditioner in the following circumstance:
There is petrolatum existing.
There is salty air surrounding (near the coast).
There is caustic gas (the sulfide, for example) existing in the air (near a hot spring).
The Volt vibrates violently (in the factories).
In buses or cabinets.
In kitchen where it is full of oil gas.
There is strong electromagnetic wave existing.
There are inflammable materials or gas.
There is acid or alkaline liquid evaporating.
Other special conditions.
2. INSTALLATION INFORMATION
To install properly, please read this "installation manual" at first.
The air conditioner must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow this manual as strictly as possible.
If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.
When all the installation work is finished, please turn on the power only after a thorough check.
Regret for no further announcement if there is any change of this manual caused by product improvement.
INSTALLATION ORDER
Select the location;
Install the indoor unit;
Install the outdoor unit;
Install the connecting pipe ;
Connect the drain pipe;
Wiring;
Test operation. installation manual
2
3. ATTACHED FITTINGS
Please check whether the following fittings are of full scope. If there are some spare fittings , please restore them carefully.
Table 3-1
NAME
1. Soundproof / insulation sheath
SHAPE QUANTITY
2
2. Binding tape
1
Tubing & Fittings
3.Seal sponge
4.Orifice
1
1
(on some models)
1
1
Drainpipe Fittings
(for cooling & heating)
5. Drain joint
6. Seal ring
7. Remote controller
(on some models)
Remote controller & Its Frame
(Match with
remote controller )
8. Frame
9.Mounting screw(ST2.9×10-C-H)
10.Alkaline dry batteries (AM4)
1
1
(on some models)
2
2
1
1
Wire controller & Its Frame
(Match with wire controller )
EMC & Its Fitting
(for some models)
Others
11. Remote controller manual
12. Wire controller
13. Magnetic ring
(twist the electirc wires L and N around the magnetic ring to five circles)
14. Owner‘s manual
15. Installation manual
16 .Transfer connector(Φ12.7-Φ15.9)/
( )
(Packed with the indoor unit )
(NOTE: Pipe size differ from appliance to appliance.To meet different pipe size requirement, sometimes the pipe connections need the transfer connector to install on the outdoor unit .)
17 .Transfer connector(Φ6.35-Φ9.52)/
(Packed with the indoor unit )
(NOTE: Pipe size differ from appliance to appliance.To meet different pipe size requirement, sometimes the pipe connections need the transfer connector to install on the outdoor unit .)
18 .Transfer connector(Φ9.52-Φ12.7)/
(Packed with the indoor unit,used for
multi-type models only )
(NOTE: Pipe size differ from appliance to appliance.To meet different pipe size requirement, sometimes the pipe connections need the transfer connector to install on the outdoor unit .)
19. Connecting wire for display (2M)
1
1
1
1
(on some models)
1
(on some models)
1
(on some models)
1
(on some models) installation manual
3
3
4
4. INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any damage should be reported immediately to the service agent.
When handling the unit, take into account the following:
1
2
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
Choose on before hand the path along which the unit is to be brought in.
Move this unit as originally package as possible.
When lifting the unit , always use protectors to prevent belt damage and pay attention to the position of the unit’s centre of gravity.
5. INDOOR UNIT INSTALLATION
5.1 Installation place
The indoor unit should be installed in a location that meets the following requirements:
There is enough room for installation and maintenance.
The ceiling is horizontal, and its structure can endure the weight of the indoor unit.
The outlet and the inlet are not impeded, and the influence of external air is the least.
The air flow can reach throughout the room.
The connecting pipe and drainpipe could be extracted out easily.
There is no direct radiation from heaters.
Maintenance roomage
200mm/7.874in or more
300mm/11.811in or more
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from televisions and radios. This is to prevent image interference and noise in those electrical appliances. (Noise may be generated depending on the conditions under which the electric wave is generated, even if 1 meter is kept.)
5.2 Install the main body
1 Installing Ø10/Ø0.394in hanging screw bolts. (4 bolts)
Please refer to the following figures for positioning 4 screw bolts.
Evaluate the ceiling construction and please install with Ø 10
/ Ø 0.394in hanging screw bolts.
Consult the construction personnels for the specific procedures.
Do keep the ceiling flat. Consolidate the roof beam to avoid possible vibration.
Carry out the pipe and line operation in the ceiling after finishing the installation of the main body. While choosing where to start the operation, determine the direction of the pipes to be drawn out. Especially in case there is a ceiling, position the refrigerant pipes, drain pipes,indoor & outdoor lines to the connection places before hanging up the machine.
The installation of hanging screw bolts.
Cut off the roof beam.
Strengthen the place that has been cut off, and consolidatethe roof beam.
After the selection of installation location, position the refrigerant pipes, drain pipes,indoor & outdoor wires to the connection places before hanging up the machine.
The installation of hanging screw bolts.
NOTE
Confirm the minimum drain tilt is 1/100 or more
600mmX600mm/23.622inX23.622in
checking orifice
5.2.1 Wooden construction
Put the square timber traversely over the roof beam, then install the hanging screw bolts. (Refer to Fig.5-2)
Timber over the beam
Fig.5-1
Roof beam
Ceiling
Hanging screw bolts
Fig.5-2 installation manual
4
5.2.2 New concrete bricks
Inlaying or embedding the screw bolts. (Refer to Fig. 5-3)
3. Air inlet and air outlet duct should be apart far enough to avoid air passage short-circuit.
(Blade shape insertion) (Slide insertion)
5.2.3 For Original concrete bricks
Use embedding screw bold, crock and stick harness.
(Refer to Fig.5-4)
Fig.5-3
4. Recommended duct connection
Canvas tie-in Canvas tie-in
Isolation booth
Steel bar
Embedding screw bolt
(Pipe hanging and embedding screw bolt)
Fig.5-4
5.2.4 Steel roof beam structure
Install and use directly the supporting angle steel. (Refer to Fig.5-5)
Hanging screw bolt
Air outlet
Isolation booth
Air inlet checking orifice
Air dust filter
Fig.5-7
5. Please refer to the following static pressure to install
Hanging bolts
Supporting
angle steel
Overhang part
Fig.5-5
2 Overhanging the indoor unit
(1) Overhang the indoor unit onto the hanging screw bolts with
block.
(2) Position the indoor unit in a flat level by using the level indicator,
unless it may cause leakage.
Screw nut
Shockproof cushion
Table.5-1
MODEL
(Btu/h)
12
18
24
30~36
42~60
Static Pressure
(Pa)
30
70
70
80
100
Change the fan motor static pressure corresponding to external duct static pressure.
NOTE
1. Do not put the connecting duct weight on the indoor unit.
2. When connecting duct, use inflammable canvas tie-in to prevent vibrating.
3. Insulation foam should be wrapped outside the duct to avoid condensate and internal duct underlayer shall be added to reduce the noise for special requirement.
Washer
Hanging screw bolt
Fig.5-6
5.3 Duct and accessories installation
1. Install the filter(optional) according to air inlet size.
2. Install the canvas tie-in between the body and duct. installation manual
5
The positioning of ceiling hole
, indoor unit and hanging screw bolts
Dimension and air outlet size
Air inlet size
Position size of descensional ventilation opening
Air filter
Air filter
Electric control box
Size of mounted hook
Electric control box
Unit: mm
Fig.5-8 installation manual
6
Table.5-2 mm
Outline dimension air outlet opening size air return opening size
Size of
mounted lug
A B C D E F G H I J K L M
12 700 210 635 570 65 493 35 119 595 200 80 740 350
12~18 920 210 635 570 65 713 35 119 815 200 80 960 350
24
36
(small model)
920 270 635 570 65 713 35 179 815 260
920 270 635 570 65 713 35 179 815 260
20 960 350
20 1180 490
30~36 1140 270 775 710 65 933 35 179 1035 260 45 1240 500
42~60 1200 300 865 800 80 968 40 204 1094 288 45 1240 500
(in=mm/25.4)
How to adjust the air inlet direction? (From rear side to under-side.)
1. Take off ventilation panel and flange, cut off the staples at side rail.
2. Stick the attached seal sponge as per the indicating place in the following fig, and then change the mounting positions of air return panel and air return flange .
Air return flange
Dentilation panel
3. When install the filter mesh, please plug it into flange inclined from air return opening, and then push up.
Side rail
Seal sponge
4. The installation has finish, upon filter mesh which fixing blocks have been insert to the flange positional holes.
NOTE
All the figures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased.The actual unit shall prevail.
Fig.5-9
7
5.9 Fan performances
Static pressure curve(middle static pressure duct)
12K 18K
Pa
90
80
70
60
50
40
30
20
10
0
Super high speed
High speed
Mid speed
Low speed
300 400 500 600 700
Air volume(m /h)
800 900
Pa
90
80
70
60
50
40
30
20
10
Mid speed
Low speed
Super high speed
High speed
200 300 400 500 600
Air volume(m 3 /h)
700 800 900 1000 1100 1200
24K 30K
50
40
30
20
10
Pa
90
80
70
60
Low speed
Super high speed
High speed
Mid speed
700 800 900 1000 1100
Air volume(m 3 /h)
1200 1300 1400 1500
70
60
50
Pa
90
80
40
30
20
10
Super high speed
High speed
Mid speed
Low speed
1200 1400 1600 1800 2000 2200 2400
Air volume(m 3 /h) installation manual
8
36K
Pa
50
40
30
20
10
90
80
70
60
Low speed
Super high speed
High speed
Mid speed
1100 1200 1400 1600 1800 2000
Air volume(m /h)
2200 2400
36K(small model)
Pa
80
70
60
50
40
30
20
10 high speed
Mid speed
Low speed
900 1000 1100 1200 1300 1400
Air volume(m 3 /h)
1500 1600 1700 1800
48K
90
80
70
60
50
40
30
20
10
Pa
120
110
100
Super high speed
High speed
Mid speed
Low speed
1000 1300 1600 1900 2200 2500
/h)
2800 3100
60K
Pa
120
110
60
50
40
30
100
90
80
70
20
10
Super high speed
High speed
Mid speed
Low speed
1000 1300 1600 1900 2200
Air volume(m 3 /h)
2500 2800 3100 3400 installation manual
9
Static pressure curve(high static pressure duct)
18k
30
20
10
60
50
40
Pa
90
80
70
Super high speed
High speed
Mid speed
Low speed
700 800 900 1000 1100 1200
Air volume(m 3 /h)
1300 1400 1500
30K
40
30
20
70
60
50
10
Pa
100
90
80
Low speed
Super high speed
High speed
Mid speed
Pa
180
160
140
120
100
80
60
40
20
600 800 1000 1200 1400 1600 1800 2000 2200 2400
Air volume(m 3 /h)
48K
Super high speed
High speed
Low speed
Mid speed
800 1000 1600 2000 2200 2400 2600 2800 3000 3200 3400 3600
Air volume(m 3 /h) installation manual
10
24K
50
40
30
20
10
Pa
90
80
70
60
Mid speed
Low speed
Super high speed
High speed
700 800 900 1000 1100 1200 1300 1400 1500 1600
Air volume(m 3 /h)
36K
Pa
100
80
60
40
20
180
160
140
120
Low speed
Super high speed
High speed
Mid speed
600 800 1000 1200 1400 1600 1800 2000 2200 2400
Air volume(m 3 /h)
60K
Pa
100
80
60
40
20
180
160
140
120
Low speed
Super high speed
High speed
Mid speed
800 1000 1600 2000 2200 2400 2600 2800 3000 3200 3400 3600
Air volume(m 3 /h)
6. OUTDOOR UNIT INSTALLATION
6.1 Installation Place
The outdoor unit should be installed in the location that meets the following requiements:
There is enough room for installation and maintenance.
The air outlet and the air inlet are not impeded, and can not be reached by strong wind.
It must be a dry and well ventilating place.
The support is flat and horizontal and can stand the weight of the outdoor unit. And will no additional noise or vibration.
Your neighborhood will not feel uncomfortable with the noise or expelled air.
It is easy to install the connecting pipes or cables.
Determine the air outlet direction where the discharged air is not blocked.
There is no danger of fire due to leakage of inflammable gas.
The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length.
In the case that the installation place is exposed to strong wind such as a seaside, make sure the fan operating properly by putting the unit lengthwise along the wall or using a dust shield.(Refer to Fig.6-1)
If possible, do not install the unit where it is exposed to direct sunlight.
If necessary, install a blind that does not interfere with the air flow.
During the heating mode, the water drained off the outdoor unit ,The condensate should be well drained away by the drain hole to an appropriate place, so as not to interfere other people.
Select the position where it will not be subject to snow drifts, accumulation of leaves or other seasonal debris. If unavoidable, please cover it with a shelter.
Locate the outdoor unit as close to the indoor unit as possible.
If possible, please remove the obstacles nearby to prevent the performance from being impeded by too little of air circulation.
The minimum distance between the outdoor unit and obstacles described in the installation chart does not mean that the same is applicable to the situation of an airtight room. Leave open two of the three directions
(M,N,P) (Refer to Fig.6-5)
6.2 Figure of body size
1. Split type outdoor unit
A
A
B
O X
Fig.6-1
NOTE
All the figures in this manual are for explanation purpose only.
They may be slightly different from the air conditioner you purchased.The actual uint shall prevail.
Fig.6-2
Fig.6-3
Fig.6-4 installation manual
11
Table 6-1
MODEL A B C D E F
12 mm
760 530 290 315 270 285 590
Fig.6-2
18
760 530 290 315 270 285 590 Fig.6-2
842 560 335 360 312 324 695 Fig.6-2
24
30
852 582 368 390 328 340 660 Fig.6-2
900 590 333 355 302 315 860 Fig.6-2
990 624 366 396 340 345 965
Fig.6-2
990 624 366 396 340 345 965 Fig.6-2
900 590 333 355 302 315 860 Fig.6-2
990 624 366 396 340 345 965 Fig.6-2
36
938 634 404 448 368 392
990 624 366 396 340 345
1369 Fig.6-3
965 Fig.6-2
42
938 634 404 448 368 392
990 624 366 396 340 345
1369 Fig.6-3
965 Fig.6-2
48
60
938
900
634 404 448 368 392 1369 Fig.6-3
590 378 400 330 350 1170 Fig.6-3
900 590 378 400 330 350 1170 Fig.6-3
938 634 404 448 368 392 1369 Fig.6-3
(in=mm/25.4)
2. Vertical discharge type outdoor unit
C
A
3. Centrifugal fan type outdoor unit
I J
C
A
B
D
E
F
B
Fig.6-7
G H
Table 6-3
MODEL A B C D E F G H unit:mm
I J
18 1174 1120 680 720 750 475 300 430 265 393
24 1174 1120 680 720 750 475 300 430 265 393
30 1381 1328 702 740 770 520 336 500 296 443
36 1381 1328 702 740 770 520 336 500 296 443
48
1394 1338 783 820 850 568 398 574 342 463
60
1394 1338 783 820 850 568 398 574 342 463
6.3 Space of installation and maintenance
1. Split type outdoor unit
(Wall or obstacle)
Air inlet
>30cm
/11.81in
N
Air inlet
>30cm /1
Maintain channel
>60cm
/23.62in
P
>200cm /78.74in
M Air outlet
Fig.6-8
18
24
36
36
48
60
Table 6-2
Fig.6-5
MODEL
DIMENSIONS
Fig.6-6 unit:mm
REMARK
633/24.92in 554/21.81in 554/21.81in
633/24.92in 554/21.81in 554/21.81in Refore to
759/29.88in 554/21.81in 554/21.81in
Fig.6-5
Fig.6-6
633/24.92in 600/23.62in 600/23.62in
759/29.88in 710/27.95in 710/27.95in
843/33.19in 710/27.95in 710/27.95in
2. Vertical discharge type outdoor unit
(Wall or obstacle)
>120cm /47.24in
Fig.6-9 installation manual
12
(Wall or obstacle)
>30cm /1
NOTE
All the figures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased.The actual unit shall prevail.
>30cm
/11.81in
Air inlet
>30cm
/11.81in
Air inlet
Fig.6-10
3. Centrifugal fan type outdoor unit
a) In case that suspending in the ceiling
6.4 Available configuration for centrifugal fan
type outdoor unit
Four different configuration are available for oudoor unit only changing the panels and fan position.
NOTE
Keep in mind that fan unit weight is aprox 30kg/1058oz ,the unit as well as relevant equipment covered with the vinyl cover during installation work.
Air inlet modification
To change air inlet is only necessary to interchange the indicated panels position. Both panels use screws to be fixed to unit chas s is.
≥300
/11.81in
≥300
/11.81in
b)In case that installing on the floor
Fig.6-11
Change Panel
Fig6-13
To change air outlet is necessary to interchange panels too.
Fan outlet panel is attached to fan structure, which must be mounted as follow.
≥400
/15.75in
Fig.6-12
Fig.6-14 installation manual
13
6.5 Moving and installation
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling.
Never hold the inlet of the outdoor unit to prevent it from deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation accoding to the sepecif-ications of the outdoor units.(Refer to Fig.6-15)
Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind.(Refer to
Fig.6-15)
Table 6-4
No Description
>60cm /23.62in
Table 6-5
MODEL
18~24
30
36
48~60 unit:mm
B C
1120/44.1in 720/28.35in
1338/52.67in 820/32.28in
1338/52.67in 820/32.28in
1338/52.67in 820/32.28in
Fix with bolt
Fig.6-15
Concrete Foundation
1. Foundation could be on flat and is recommended be 100-300mm
/3.94-11.81in higher than ground level.
2.Install a drainage around foundation for smooth drain
3.When installing the outdoor unit fix the unit by anchor bolts of M10
4.When installing the unit on a roof or a veranda, drain water
sometimes turns to ice on the cold weather. Therefore, avoid
draining in an area that people often use because it is slippery.
Suspended unit
1. Suspend the unit as the drawing indicates.
2. Ensure that ceiling can resist the Outdoor unit weight indicated
in specification label plate.
Sling Bolt
Suspension Bracket
≥100
3.94in
Fig.6-17
Fig.6-16
Outfall
Fig.6-18
NOTE: Make sure 3-4 degree of angel is kept between the unit and
the floor when the unit is installed in the low temperauture
and humid environment.
Make sure the ice on the chassis of the outdoor unit can be
dealt with when the unit is installed in the low temperature
and humid enviroment.
The outdoor unit should be installed in mounting rack 30cm
/11.81in high.The enviroment temperature should be above
0°.
The machine must be installed indoor. installation manual
14
7. INSTALL THE CONNECTING PIPE
7.1 Preparation and Caution
Before installation make sure the height difference, the length of refrigerant pipe, and the number of the bends between the indoor unit and outdoor unit meet the following requirements:
Table 7-1 unit:m
The type of models
50Hz T1 condition/R22
Split type air conditioner
50Hz Vertical discharge air conditioner
/60Hz T1 condition/R22 Split type air conditioner and Vertical discharge air conditioner
R410A inverter Split type air conditioner and and Centrifugal fan outdoor unit
R410A Split type air conditioner and and Centrifugal fan outdoor unit
50Hz/60Hz T3 condition
(outdoor unit down)
50Hz/60Hz T3 condition
(outdoor unit up) the unit with quick joint
12K
18K-24K
30K-60K
12K
18K-24K
30K
36K
48K-60K
12K
18K-30K
36K
48K-60K
18K-24K
30K
36K
42K-60K
18K-24K
30K
36K
42K
48K-60K
Model
The length of refrigerant pipe
The max height drop
12K
18K-24K
30K-42K
48K-60K
12K-18K
15/49.21ft
30/98.42ft
50/164.04ft
50/164.04ft
15/49.21ft
30/98.42ft
30/98.42ft
10/32.8ft
25/82.02ft
25/82.02ft
30/98.42ft
50/164.04ft
15/49.21ft
25/82.02ft
30/98.42ft
50/164.04ft
25/82.02ft
30/98.42ft
30/98.42ft
50/164.04ft
25/82.02ft
30/98.42ft
30/98.42ft
50/164.04ft
50/164.04ft
5/16.4ft
8/26.25ft
10/32.8ft
20/65.62ft
25/82.02ft
8/26.25ft
10/32.8ft
20/65.62ft
5/16.4ft
12/39.37ft
15/49.21ft
20/65.62ft
25/82.02ft
8/26.25ft
15/49.21ft
20/65.62ft
25/82.02ft
10/32.8ft
15/49.21ft
20/65.62ft
25/82.02ft
15/49.21ft
20/65.62ft
25/82.02ft
30/98.42ft
35/114.83ft
5/16.4ft
CAUTION
All field piping must be provided by a licensed refrigeration technician and must comply with the relevant local and national codes.
Prevent let air, dust, or other impurities enter in the pipe system during installation.
Insulation pipe shall be used to the gas piping and the liquid piping. Otherwise, the condensate may happen.
7.2 The Procedure of Connecting Pipes
1 Measure the required length of the connecting pipe, then make it by the following way.
Connect the indoor unit first, then the outdoor unit.
Bend the tubing in proper way. Do not twist the pipe.
Bend the pipe with thumb min-radius 100mm/3.94in
Fig.7-1
Put some refrigerant oil on the surfaces of the flare pipe and the joint nuts then wrench it for 3~4 rounds with hands before fasten the flare nuts.(Refer to chart 16)
Use frozen oil
Fig.7-2
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Make the ends straight
The outdoor unit is charged with rating refrigerant amount in the factory.Additional charge refers to the table below:
Table 7-2 liquid tube(mm) R410A R22
Ø6.35 orifice in the indoorunit 0.022kg/m×(L-5) orifice in the outdoorunit 0.011kg/m×(L-5) orifice in the indoorunit 0.060kg/m×(L-5)
Ø9.53 orifice in the outdoorunit 0.030kg/m×(L-5)
Ø12.7 orifice in the indoorunit 0.110kg/m×(L-5) orifice in the outdoorunit 0.060kg/m×(L-5)
0.030kg/m×(L-5)
0.015kg/m×L
0.065kg/m×(L-5)
0.030kg/m×L
0.115kg/m×(L-5)
0.060kg/m×L
Ø15.9 orifice in the indoorunit 0.170kg/m×(L-5) orifice in the outdoorunit 0.085kg/m×(L-5)
0.190kg/m×(L-5)
0.095kg/m×L
Ø19.0 orifice in the indoorunit 0.250kg/m×(L-5) orifice in the outdoorunit 0.125kg/m×(L-5)
0.290kg/m×(L-5)
0.145kg/m×L
NOTE:the table above refer to the liquid tube.
NOTE:The number of bends is up to the length of the max height drop.Usually for each 10m/32.8ft need a bend.
Fig.7-3
The service valves of the outdoor unit should be completely closed(as original status).Every time to connect,first to loosen nuts, then connect the flare pipes within 5 minutes. If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction.So please expel the air out of the pipe with refrigerant before connection.
Expel the air(refer to the “8.1”)after connecting the refrigerant pipe with the indoor unit and the outdoor unit.
Then fasten the nuts at the service valves.
Bend the connecting pipe of small wall thickness.
Cut out a proper concave at the bending part of the insulating pipe.
Then expose the pipe(cover it with tapes after bending).
To prevent twist of deforming, please bend the pipe at a proper radius.
NOTE
The bending angle should not exceed 90 .
Bending position is preferably in the middle of the bendable pipe.
Do not bend the pipe more than three times.
Be sure to use the same insulating materials when you buy the brass pipe. (More than 9mm/0.35in thick) installation manual
15
2. Place The Pipe
Drill a hole in the wall (suitable just for the size of the wall sleeve), then set on the fittings such as the wall sleeve and its cover.
Bind the connecting pipe and the cables together tightly with binding tapes.
Pass the bound connecting pipe through the wall sleeve from outside. Make sure of the pipe allocation not to damage the copper tubes.
3
4
5
6
7
Connect the pipes.
Expel the air with a vacuum pump or refrigerant.
Open the service valves of the outdoor unit .
Check the refrigerant leakage. Check all the joints with the leak detector or soap water.
Cover the joints of the connecting pipe with the insulation foam, and bind them well with the tapes to prevent potential leakage.
Note: All used branch pipe must be produced by Midea, otherweise it causes malfunction. The indoor units should be installed equivalently at the both side of the U type branch pipe.
8.2 Size of joint pipes for indoor unit
Table.8-2 Size of joint pipes for 410A indoor unit
Capacity of indoor unit
(A)
Size of main pipe(mm)
Gas side
Φ12.7/0.5in
Liquid side
Φ6.35/0.25in 18K
24K
30K
Φ15.9/0.626in
Φ15.9/0.626in
Φ9.5/0.375in
Φ9.5/0.375in
Available branching pipe
CE-FQZHN-01C
CE-FQZHN-01C
CE-FQZHN-01C
8. REFRIGERANT PIPE(the unit with the
twins function)
8.1 Length and drop height permitted of the
refrigerant piping
Note: Reduced length of the branching tube is the 0.5m/1.64ft of the equivalent length of the pipe.
Table.8-1
Permitted value Piping
Total pipe length (Actual)
(farthest from the line pipe branch)
(farthest from the line pipe branch)
Indoor unit-outdoor unit drop height
Indoor unit to indoor unit drop height
18K+18K 30m/98.42ft
24K+24K/
30K+30K
50m/164.04ft
15m/49.21ft
10m/32.8ft
20m/65.8ft
0.5m/1.64ft
L1,L2
L1-L2
H1
H2
L+L1+L2
8.3 Size of joint pipes for outdoor unit
Base on the following tables, select the diameters of the outdoor unit connective pipes. In case of the main accessory pipe large than the main pipe, take the large one for the selection.
Table.8-3
Model
36K
48K
60K
Size of joint pipes for 410A outdoor unit the size of main pipe(mm)
Gas side Liquid side
Φ15.9/0.626in Φ9.5/0.375in
The 1st branching pipe
CE-FQZHN-01C
Φ15.9/0.626in Φ9.5/0.375in CE-FQZHN-01C
Φ15.9/0.626in Φ9.5/0.375in CE-FQZHN-01C
Outdoor unit
Indoor unit
installation manual
16
L
A
The line branch pipe
L
2
L
1
Fig.8-1
8.4 Vacuum with vacuum pump
1)
2)
3)
Use the vacuum pump which vacuum level lower than
-0.1MPa and the air discharge capacity above 40L/min.
The outdoor unit is not necessary to vacuum, don’t open the outdoor unit gas and liquid pipe shut-off valves.
Make sure the vacuum pump could result as -0.1MPa or below after 2 hrs or above operation. If the pump operated 3 hrs or above could not achieve to -0.1MPa or below, please check whether water mix or gas leak inside of the pipe.
1) The branching pipe must be installed horizontally, error angle of it should not large than 10°. Otherwise, malfunction will be caused.
U-shaped branching pipe
A
A direction view
Wrong Correct
10°
10°
Connect with vacuum pump
Horizontal surface
Perform the pump (last for 2 hrs or above)
When get the vacuum level
-0.1MPa, the pump should keep running for 20-60 mins
Shut down the vaccun pump
1. Close-off the valve of vacuum meter.
2. Cut off the connection between pressure meter and vacuum pump.
3. Close the vacuum pump.
Fig.8-3
9. REFRIGERANT PIPE CONNECTION
9.1 Expel The Air
1 Flaring
Cut a pipe with a pipe cutter. (Refer to Fig.9-1)
Place the vaccum state unused (1 hrs or above)
90 Lean crude burr
Fig.8-2
CAUTION
Don’t mix up the different refrigerants or abuse the tools and measurements which directly contact with refrigerants.
Don’t adopt refrigerant gas for air vacuuming.
If vacuum level could not get to -0.1MPa, please check whether resulted by leakage and confirm the leakage site.If no leakage, please operate the vacuum pump again 1 or 2 hrs.
2
Fig.9-1
Insert a flare nut into a pipe and flare the pipe.
Fasten the nut
Put the connecting pipes at the proper position, wrench the nuts with hands then fasten it with two wrenches simultaneously. (Refer to Fig.9-2)
8.5 Refrigerant amount to be added
Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor/indoor unit connection. The refrigerant is R410A.
Table.8-4
Pipe size on
liquid side
Φ6.35/0.25in
Φ9.52/0.375in
Refrigerant to be Added per meter
0.015kg/0.033lb
0.030kg/0.066lb
Fig.9-2
CAUTION
Too large torque will harm the bellmouthing and too small will cause leakage. Please determine the torque according to
Table 9-1.
Table 9-1
Pipe gauge Tightening torque
Flare dimensin A
Flare shape
Ø6.35/0.25in
14.2~17.2 N.m
(144~176 kgf.cm)
8.3/0.327in 8.7/0.343in
Ø9.52/0.375in
32.7~39.9 N.m
(333~407 kgf.cm)
12.0/0.472in 12.4/0.488in
Ø12.7/0.5in
49.5~60.3 N.m
(504~616 kgf.cm)
15.4/0.606in 15.80.622in
Ø15.9/0.626in
61.8~75.4 N.m
(630~770 kgf.cm)
18.6/0.732in 19.0/0.748in
Ø19.1/0.725in
97.2~118.6 N.m
(990~1210 kgf.cm)
22.9/0.902in 23.3/0.917in
A
45 ° ±
2
R0.4~0.8 installation manual
17
3 Expel the air with a vacuum pump(Refer to Fig.9-3)
(Please refer to its manual for the way of using manifold valve)
Loosen and remove the nuts of service valves A and B, and connect the charge hose of the manifold valve with the maintenance terminator of service valve A. (Be sure that service valves A and B are both closed)
Connect the joint of the charge hose with the vacuum pump.
Open the Lo-lever of the manifold valve completely.
Turn on the vacuum pump. At the beginning of pumping, loosen the nut of service valve B a little to check whether the air comes in (the sound of the pump changes, and the indicator of compound meter turns below zero). Then fasten the nut.
When the pumping has finished, close the Lo-lever of the manifold valve completely and turn off the vacuum pump.
When you have pumped for over 15 minutes, please confirm that the indicator of multimeter is on -1.0X10
-5 Pa
(-76cmHg)
Loosen and remove the nuts of service valves A and B to open service valve A andB completely, then fasten nuts.
Disassemble the charge hose of service valve A, and fasten the nut.
Manifo ld valv e
Multi-m eter Pressu re meter
-76 c mHg
Lo-lev er
Charg e hos e
Hi-leve r
Charg e hos e
Vac uum p ump
Lo-lev er Fig.9-3
CAUTION
Both service valves should be open before test operation.
Each air conditioner has two service valves of different sizes.(Refer to Fig.8-4)
Flare nut
Stopper
Cap
Valve body
Valve stern
Fig.9-4
9.2 Check the Leakage
Check all the joints with the leak detector or soap water. (Refer
Fig.9-5 as a reference illustration) in the chart
A......Lo-stop valve
B......Hi-stop valve
C,D..Joints of the connecting pipe to the indoor unit.
Check-point of indoor unit
D C
Check-point of outdoor unit
B A
Fig.9-5
9.3 Insulation
Be sure to completely insulate all the exposed parts of the flare pipes.
Incomplete insulation may cause condensate.
10. CONNECTIVE DIAGRAM
Gas side
Liquid side
Orifice
Fig. 10-1
NOTE
For ensuring throttled efficiency , Please mount the Orifice as horizontally as possible; and anti-shock rubber should be wrapped at external of the Orifice for denoise.
Mark the data plate with the Orifice installed.(for some models)
Please purchase the fittings according to the requirements in the manual strictly.
Refer the diagram when installing.
NOTE:the orifice should be horizontally installed.
Liquid side
Indoor Outdoor
Liquid side
Outdoor
Indoor
X
Liquid side
Indoor
Outdoor
X
11. CONNECT THE DRAIN PIPE
Fig. 10-2
Install the drainpipe of the indoor unit
Use a polyethylene tube as the drainpipe (out-dia.29-31mm
/1.14-1.22in, in-dia.25mm/0.984in). It could be bought from the local market.
When extending drainpipe,tighten the connector with water-proof tape to prevent it leakage.
Please lean the drainpipe down toward outdoor (outlet-side) at a degree of over 1/ 50 to avoid water flowing back. And please avoid any bulge.
Do not drag the drainpipe violently. Meanwhile, one supportpoint should be set every 1~1.5m/3.28~4.92ft to prevent the drainpipe from yielding. Or tie the drainpipe with the connecting pipe to fix it.
If the outlet of the drainpipe is higher than the body's pump joint, the pipe should be arranged as vertically as possible.
And the lift distance must be less than 550mm/21.65in, otherwise the water can not be lifted completely and cause overflow.(Only available for the unit with pump.)
The end of the drainpipe should be over 50mm/1.969in higher than the ground , and do not immerse it in water. If you discharge the water directly into sewage, be sure to make a
U-form aquaseal by bending the pipe up to prevent the smelly gas entering the house through the drain pipe.
installation manual
18
The drain pipe installation for the unit with pump.
< 200mm
Lean over 1/50
2
3
Operate the air conditioner in "COOLING" mode. The sound of the drain pump shall be heard. Check whether the water is discharged well (1 min lag is possible, according to the length of the drain pipe), and check whether the water leaks from the joints.
Power off the air conditioner and recover the cap.
The unit without pump.
The drain pipe installation for the unit without pump.
Fig.11-1
Lean over 1/50
Fig.11-2
1
Check whether the drainpipe is unhindered.
New built house should have this test done before paving the ceiling.
The unit with pump.
Remove the test cover, and stow about 2000ml water to the water pan.
Stow tube Fig.11-5
Stow 2000ml water to the water pan through the stow tube,check whether the drainpipe is unhindered.
Install the drain joint of the outdoor unit
(For Heat Pump Models)
Fit the seal into the drain joint, then insert the drain joint into the base pan hole of outdoor, rotate 90° to securely assemble them.
Connect the drain joint with an extension drain hose (Locally purchased)to avoid condensate draining off the outdoor unit during the heating mode.
CLOSED
O
PE
Test cap
LO
SE
D
OPEN
Fig.11-3
Base pan hole
Seal Drain joint
Seal
Base pan
Drain joint
Fig.11-6
NOTE
All the figures in this manual are for explanation purpose only.
They may be slightly different from the air conditioner you purchased.The actual unit shall prevail.
12. FRESH AIR DUCT INSTALLATION
Dimension :
Duct joint for fresh air
Stow tube
Fig.11-4
MODLE
12-24 30-60
Ø125mm/4.92in
Ø160mm/6.3in
Ø90mm/3.54in
80mm/3.15in
Fig.12-1 installation manual
19
12.1Motor and drain pump maintenance
(Take rear ventilated as example)
Motor maintain:
1. Take off the ventilated panel.
2.
3.
Take off the blower housing.
Take off the motor.
Table 13-2
Mofor
Blower housing
Ventilated panel
Fig.12-2
1.
2.
3.
Pump maintainance:
Screw off four screws from drain pump.
Plug off pump power supply and water level switch cable.
Take off pump.
Pump
Fig.12-3
13. CONTROL(ONLY FOR INVERTER UNITS)
The capacity of the system and the network address of the air-conditioner can be set by the switches on the indoor Main Control Board.
Before setting, turn off the power. After setting, restart the unit.
Setting is not allowed when the unit is power on.
13.1 Horsepower code setting
The capacity of the indoor unit has been set in the factory according to the below table.
Horsepowe r code
POWER_S
C
D
E
F
A B
0 1 2
3 4
6 7 8 9
ENC1
Table 13-1
ENC1
Note: The capacity has been set in the factory , anyone can’t adjust it except the qualified person.
Toggle switch
Code
Capacity(kw)
4
5.3
5.6
5 7.1
7 9.0
8 10.5
9
14.0
16.0
13.2 Network address set
Every air-conditioner in network has only one network address to distinguish each other. Address code of air-conditioner in
LAN is set by code switches S1 & S2 on the Main Control Board of the indoor unit, and the set range is 0-63.
14. WIRING
The appliance shall be installed in accordance with national wiring regulations.
The air conditioner should use separate power supply with rated voltage.
The external power supply to the air conditioner should be grounded, which is linked to the ground wiring of the indoor and outdoor unit.
The wiring work should be done by qualified persons according to wiring diagram.
A circuit breaker and a residual current device (RCD) with above 10mA rating shall be installed in the power circuit according to the national rule.
Be sure to locate the power wiring and the signal wring well to avoid cross-disturbance.
Do not turn on the power until you have confirmed proper wiring.
The power cord type is H07RN-F.
NOTE
Refer to EMC Directive 2004/108/EC
To prevent flicker impressions during the start of the compressor,following installation conditions do apply.
1 The power connection for the air conditioner has to be done at the main power distribution. The distribution has to be of a low impedance, normally the required impedance reaches at a 32 A fusing point.
2
3
4
No other equipment has to be connected with this power line.
For detailed installation acceptance please refer to your power supplier, if restrictions do apply for products like washing machines, air conditioners or electrical ovens.
For power details of the air conditioner refer to the rating nameplate of the product.
5 For any question contact your local dealer.
14.1
Connect the cable
Disassemble the cover.(If there isn't a cover on the outdoor unit, disassemble the screw from the maintenance board, and pull it in the direction of the arrow to remove the protection board.) (Refer to Fig.14-1)
Connect the cables to the terminals correspondingly.
Re-install the cover or the protection board.
14.2 The Specification of Power
(Refer to Table14-1~14-8)
14.3 Wiring figure
(Refer to Fig.14-2~Fig.14-5)
1.split type outdoor unit
Cover
Protection board Fig.13-1 installation manual
20
2.Centrifugal fan outdoor unit
Fig.14-2
Protection Board
NOTE
All the figures in this manual are for explanation purpose only.
They may be slightly different from the air conditioner you purchased(depend on model).The actual unit shall prevail.
15. TEST OPERATION
1
2
The test operation must be carried out after the entire installation.
Please confirm the following points before the test operation:
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The length of the tubing and additional charge amount have been recorded.
The power voltage matches rated voltage of the air conditioner.
There is no obstacle at the outlet and inlet of the outdoor and indoor units.
The gas-side and liquid-side service valves are both completely open.
The air conditioner is pre-heated by turning on the power.
3 Test operation
Set the air conditioner in cooling mode with the remote controller, and check the following points. If there is any malfunction, please resolve it according to the chapter
"Troubleshooting" in the "Owner's Manual".
1) The indoor unit a. Whether the buttons on the remote controller works well. b. Whether the air flow louver moves normally. c. Whether the room temperature is adjusted suitable. d. Whether the indicator lights normally. e. Whether the temporary switch on the unit works well. f. Whether the drainage is normal. g. Whether there is abnormal vibration or noise during operation. h. Whether the air conditioner works well in heating mode(heat pump model).
2) The outdoor unit a. Whether there is abnormal vibration and noise during operation. b. Whether the exhaust air, noise, or condensate influence your neighborhood. c. Whether there is any refrigerant leakage during operation.
CAUTION
3 minutes delay is normal when restarting the unit for compressor protection. installation manual
21
The Specification of Power(indoor power supply)
Table 14-1
MODEL
POWER
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
1 P h a s e 1 P h a s e
Table 14-2
MODEL
POWER
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
3 P h a s e
380-420 V
3 P h a s e
380-420 V
1 P h a s e 1 P h a s e
208-2 40V
60
1 P h a s e
208-2 40V
3 P h a s e
208-2 40V
3 P h a s e
208-2 40V
The Specification of Power(outdoor power supply)
Table 14-3
MODEL
POWER
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
1 P h a s e 1 P h a s e 1 P h a s e 1 P h a s e
208-2 40V 208-2 40V 208-2 40V 208-2 40V
40/30 60/40 70/55 70/60
Table 14-4
MODEL
POWER
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
3 P h a s e
380-420 V
3 P h a s e
380-420 V
3 P h a s e
208-2 40V
3 P h a s e
208-2 40V installation manual
22
The Specification of Power(independence power supply)
Table 14-5
MODEL
POWER
(indoor)
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
POWER
(outdoor)
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
1 P h a s e
1 P h a s e
1 P h a s e
1 P h a s e
1 P h a s e
1 P h a s e
1 P h a s e
208-2 40V
60
1 P h a s e
208-2 40V
1 P h a s e
208-2 40V
1 P h a s e
208-2 40V
Table 14-6
MODEL
POWER
(indoor)
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
1 P h a s e
208-2 40V
3 P h a s e
380-420 V
1 P h a s e
208-2 40V
1 P h a s e
208-2 40V
1 P h a s e
208-2 40V
3 P h a s e
380-420 V
3 P h a s e
208-2 40V
3 P h a s e
208-2 40V
The Specification of Power for the invert type air conditioner(independence power supply)
Table 14-7
MODEL
POWER
(indoor)
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
POWER
(outdoor)
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
1 P h a s e
1 P h a s e
1 P h a s e
1 P h a s e
1 P h a s e
1 P h a s e
1 P h a s e
220-2 40V
1 P h a s e
208-2 40V
60
1 P h a s e
220-2 40V
1 P h a s e
208-2 40V
Table 14-8
MODEL
POWER
(indoor)
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
PHASE
FREQUENCY AND VOLT
CIRCUIT BREAKER/FUSE(A)
1 P h a s e
220-2 40V
3 P h a s e
380-420 V
1 P h a s e
220-2 40V
1 P h a s e
220-2 40V
1 P h a s e
220-2 40V
3 P h a s e
380-420 V
3 P h a s e
208-2 40V
3 P h a s e
208-2 40V installation manual
23
CAUTION
The power supply is included in the power supply above mentioned can be applied to the table.
Before obtaining access to terminals, all supply circuits must be disconnected.
Wiring figure
Fig.14-3
Power supply
Switch/Fuse
(Available locally)
Power wiring (indoor)
Power linking wiring (Outdoor)
Indoor
Unit Outdoor
Unit
Ground wiring
Ground wiring
Strong elec-signal link wiring
Weak elec-signal link wiring
Ground the air conditioner properly in case to affect its anti-interference function
Fig.14-4
Power supply
Switch/Fuse
(Available locally)
Power wiring (outdoor)
Power linking wiring (indoor)
Indoor
Unit Outdoor
Unit
Ground wiring
Ground wiring
Strong elec-signal link wiring
Weak elec-signal link wiring
Ground the air conditioner properly in case to affect its anti-interference function installation manual
24
Fig.14-5
Indoor
Unit
Power supply Power supply
Switch/Fuse
(Available locally)
Power wiring (indoor)
Power linking wiring (Outdoor)
Out door
Unit
Ground wiring
Weak elec-signal link wiring
Ground wiring
— — — — — —
Power supply
Switch/Fuse
(Available locally)
Indoor
Unit
Ground wiring
— — — — — —
Ground the air conditioner properly in case to affect its anti-interference function
Fig.14-6
Power supply
Switch/Fuse
(Available locally)
Power wiring (outdoor)
Indoor
Unit
Outdoor
Unit
Ground wiring
Ground wiring
Strong elec-signal link wiring
Weak elec-signal link wiring
Ground the air conditioner properly in case to affect its anti-interference function
CAUTION
A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation.
When wiring, please choose the corresponding chart, or it may cause damage.The signs of the indoor terminal block in the some of following fugures may be replaced by L N L1 N1. installation manual
25
QST2I-013AEN
The design and specifications are subject to change without prior notice for product improvement.Consult with the sales agency or manufacturer for details
202000192509
20130521
advertisement
Key Features
- Middle static pressure duct type
- Installation instructions for indoor and outdoor units
- Connecting pipes (refrigerant and drain)
- Wiring and control diagrams
- Safety precautions
- Test operation
Frequently Answers and Questions
What safety precautions should I take during installation?
How do I connect the refrigerant pipes?
What is the recommended space for the outdoor unit?
How do I connect the drain pipe?
Related manuals
advertisement
Table of contents
- 3 SAFETY PRECAUTIONS
- 4 INSTALLATION INFORMATION
- 5 ATTACHED FITTINGS
- 6 INSPECTING AND HANDLING THE UNIT
- 6 INDOOR UNIT INSTALLATION
- 13 OUTDOOR UNIT INSTALLATION
- 17 INSTALL THE CONNECTING PIPE
- 18 REFRIGERANT PIPE
- 19 REFRIGERANT PIPE CONNECTION
- 20 CONNECTIVE DIAGRAM
- 20 CONNECT THE DRAIN PIPE
- 21 FRESH AIR DUCT INSTALLATION
- 22 CONTROL
- 22 WIRING