Below you will find brief information for split-system air conditioner FSIArt 100HFD, split-system air conditioner FSIArt 180HFD. This document is an electronic service manual. It contains full technical specifications of the device and includes its function, installation, wiring and troubleshooting steps.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
SERVICE MANUAL
Room Airconditioner
Split Wall‐Mounted Type
FSIArt‐100HFD
FSIArt‐180HFD
NOTE:
Before servicing the unit, please read this at first.
Always contact with your service center if meet problem.
FI_SM_FSIArt_100_180HFD_090917
Content
1. Precaution
2. Function
3. Dimension
4. Specification
5. Refrigerant cycle diagram
6. Wiring diagram
7. Installation details
7.1 Wrench torque sheet for installation
7.2 Connecting the cables
7.3 Pipe length and elevation
7.4 Air purging of the piping and indoor unit
7.5 Pumping down (Re‐installation)
7.6 Re‐air purging (Re‐installation)
7.7 Balance refrigerant of the 2‐way, 3‐way valves
7.8 Evacuation
7.9 Gas charging
8. Electronic function
8.1 Abreviation
8.2 Display function
8.3 Protection
8.4 Fan only mode
8.5 Cooling mode
8.6 Dehumidifying mode
8.7 Heating mode
8.8 Auto mode
8.9 Force cooling function
8.10 Action of 4‐way valve
8.11 To speed outdoor fan function
8.12 Timer mode
8.13 Sleep mode
8.14 Auto restart function
8.15 Ionizer
8.16 Self clean function
8.17 Follow me function
8.18 Outdoor unit heating cable function (option)
21
21
25
19
19
20
18
18
18
14
15
15
17
11
12
13
11
11
11
6
8
9
1
3
5
26
26
27
27
25
26
26
27
27
28
9 Troubleshooting
9.1 Indoor Unit Error Display
9.2 Diagnosis and Soéution
9.3 Key parts checking
12 Exploded wiew
29
30
31
34
35
1. Precaution
1
1.1 Safety Precaution
To prevent injury to the user or other people and property damage, the following instructions must be followed.
Incorrect operation due to ignoring instruction will cause harm or damage.
Before service unit, be sure to read this service manual at first.
1.2 Warning
¾ Installation
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an
Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be pulled out or damaged during operation.
There is risk of fire or electric shock.
Do not place anything on the power cable.
There is risk of fire or electric shock.
Do not plug or unplug the power supply plug during operation.
There is risk of fire or electric shock.
Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
Do not place a heater or other appliance near the power cable.
There is risk of fire and electric shock.
Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustible near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off.
There is risk of explosion or fire.
If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the power supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in storm or hurricane. If possible, remove the product from the window before the hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
2
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
When the product is soaked (flooded or submerged), contact an Authorized service center.
There is risk of fire or electric shock.
Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when operating it together with a stove, etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
When the product is not be used for a long time, disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
¾ CAUTION
Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration or water leakage.
Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
¾ Operational
Do not expose the skin directly to cool air for long periods of time. (Do not sit in the draft).
This could harm to your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp.
There is risk of personal injury.
Do not step on pr put anything on the product.
(outdoor units)
There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other object through air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and mew batteries or different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote of the batteries have leaked.
The chemical in batteries could cause burns or other health hazards
2. Function
Indoor unit
Operation by remote controller
Sensing by room temperature
Room temperature sensor.
Pipe temperature sensor.
Room temperature control
Maintain the room temperature in accordance with the setting temperature.
Anti‐freezing control in cooling
Prevent the water being frozen on evaporator by sensing the evaporator pipe temperature in cooling mode
Time Delay Safety control
Restarting is for approx. 3 minutes..
Indoor fan speed control
Turbo, high, med, low, breeze.
Two‐direction air vane
The unit will decide the louver direction according to operation mode.
Sleep mode auto control
The fan is turn to low speed (cooling/heating).
The unit will be turn off at the seventh hour.
Independent dehumidification
The function is usually used in rainy days in springtime or damp areas.
Air flow Direction control
The louver can be set at the desired position or swing up and down automatically
Auto mode
The mode can be change by the room temperature.
Temp. Compensation
3
Golden fin (Optional)
Compact design
Ionizer +
Self clean
Follow me
Self‐diag. function
Anti‐cold function
Prevent the cold wind at the beginning of unit start.
Auto defrost
Auto‐restart function
When the power supply is interrupted and then restore, the air conditioners automatically restore the previous function setting.
Flexible wiring connection
Outdoor unit
Power relay control
The unit has 3 mins delay between continuously ON/OFF operations.
Low noise air flow system
Bird tail propeller fan makes the outdoor unit run more quietly.
Hydrophilic aluminum fin
The hydrophilic fin can improve the heating efficiency at operation mode.
4 way valve control
It is only operated in the heating operation mode except defrosting operation.
Anti‐rust cabinet
Made from electrolytic zinc steel sheet and anti‐rust coated components.
Valve protection cover
It protects the valves and prevents water from dripping.
Discharge pipe temperature protection
Heating cable (Optional)
Driving heating at ‐15
℃
4
5
3. Dimension
3.1 Indoor Unit
Model
FSIArt‐100HFD
W
900
H
285
D
160
FSIArt‐180HFD
3.2 Outdoor Unit
1022 295 185
FSIArt‐100HFD, FSIArt‐180HFD
4. Specification
Model
Power supply
Cooling
Ph‐V‐Hz
Capacity W
Input
Rated current
W
A
Heating
EER
Capacity
Input
Rated current
COP
Moisture Removal
Max. input consumption
W/W
W
W
A w/w
L/h
W
FSIArt‐100HFD
1,220‐240V~,50Hz
2800(900~3370)
730(280~1100)
3.2(1.3~4.8)
3,83
3000(970~3660)
690(300~1150)
3.1(1.4~5.0)
4,34
0,8
1750
FSIArt‐180HFD
1,220‐240V~,50Hz
5300(1800~6450)
1640(530~2300)
7.2(2.4~9.8)
3.23
5300(1880~6740)
1460(480~2000)
6.5(2.3~9.0)
3.63
1.5
2950
6
Max. current
Starting current
Model
Type
Brand
Capacity
Input
Compressor
Rated current(RLA)
Locked rotor Amp(LRA)
Thermal protector
Capacitor
Refrigerant oil
Model
Brand
Indoor
fan motor
A
A
W
W
A
A
uF ml
8,0
5,0
DA108X1C‐20FZ3
Rotary
TOSHIBA
10918
855
5,3
8
CS‐74
No
480
RPG20D
Welling
13.5
10
C‐6RVN93H0N
Rotary
SANYO
5830
1430
7,46
10,7
1NT11L‐3979
No
ESTER OIL VG74 750ml
RPG28D
Welling
Input
Capacitor
Speed a.Number of rows
W uF b.Tube pitch(a)x row pitch(b) mm c.Fin spacing mm
43
1,5 r/min 1290/1250/1000/900/700 1280/1260/1080/900/750
2 2
21x13.37
1,4
51
1,5
21×13.37
1,3
Indoor coil d.Fin type (code) e.Tube outside dia.and type
mm f.Coil length x height x width mm g.Number of circuits
Indoor air flow (Hi/Mi/Lo)
Indoor noise level (Hi/Mi/Lo) m3/h dB(A)
Hydrophilic aluminium
Ф7,innergroove tube
676×336×26.74
2
600/500/400
38/34/28
Hydrophilic aluminium
φ7,innergroove tube
804×336×26.74
4
870/730/520
42/37/32
Indoor unit
Outdoor
fan motor
Dimension (W*H*D)
Packing (W*H*D)
Net/Gross weight
Model
Brand mm mm
Kg
Input
Capacitor
Speed a.Number of rows
W uF r/min
b.Tube pitch(a)x row pitch(b) mm c.Fin spacing mm d.Fin type (code) Outdoor coil e.Tube outside dia.and type mm f.Coil length x height x width mm g.Number of circuits
Outdoor air flow
m3/h
Outdoor noise level
Dimension(W*H*D)
Outdoor unit Packing (W*H*D) dB(A) mm mm
Net/Gross weight
Refrigerant type R410A
Kg g
Design pressure
Liquid side/ Gas side
Refrigerant
piping
MPa mm
Max. refrigerant pipe length m
Max. difference in level m
Thermostat type
900×285×160
990×375×250
9/11.5
YDK24‐6G
Welling
59
2,5
800/550
2
22x19
1,4 hydrophilic aluminium
Ф7.94,innergroove tube
656x550x38
2
2000
54
760×590×285
887×655×355
40.5/43
1100
4,2
Ф6.35/Ф9.53
20
8
Electronic control
℃ 17 ~ 30
Operation temp
Ambient temp cooling/heating
℃
‐15 ~ 50 / ‐15 ~ 34
Notes:Specification are subject to change without prior notice for product improvement.
1022×295×185
1105×385×275
12/15.5
YDK50‐6C
Welling
111/96
2.5
890/540
2
21×13.37
1,4
Hydrophilic aluminium
φ7, innergroove tube
655×546×26.74
2
2200
56
760×590×285
887×655×355
40/42.5
1100
4.2
Ф6.35/Ф12.7
25
10
Electronic control
17 ~ 30
‐15 ~ 50 / ‐15 ~ 34
7
5. Refrigerant cycle diagram
8
9
6. Wiring diagram
6.1 Indoor Unit
FSIArt‐100HFD
FSIArt‐180HFD
6.2 Outdoor Unit
FSIArt‐100HFD
FSIArt‐180HFD
10
7. Installation details
7.1 Wrench torque sheet for installation
Outside diameter mm
Ф6.35
Ф9.52
Ф12.7 inch
1/4
3/8
1/2
Torque
Kgf.m
1.8
4.2
5.5
7.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Unit mm
2
FSIArt‐100HFD
3x1,5
FSIArt‐180HFD
3x2,5
Communication wire between the indoor and outdoor unit:
Unit mm
2
FSIArt‐100HFD
4x1,5
FSIArt‐180HFD
4x2,5
7.3 Pipe length and the elevation
Model
Pipe size
Gas
FSIArt‐100HFD 3/8’’ (Ф9.52)
FSIArt‐180HFD 1/2’’ (Ф12.7)
Liquid
Standard length
(m)
1/4’’ (Ф6.35) 5
1/4’’ (Ф6.35) 5
Max.
Elevation
B (m)
8
10
Max.
Length
A (m)
20
25
Additional refrigerant
(g/m)
30
30
Caution:
Capacity is based on standard length and maximum allowance length is base of reliability.
Oil trap should be installed per 5‐8 meters, (but not definitely needed).
11
7.4 Air purging of the piping and indoor unit
Required tools:
Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector.
Note:
The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect the compressor, reduce the cooling capacity, and could lead to a malfunction of unit.
Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage from the refrigeration cycle.
Procedure
1. Recheck the piping connections.
2. Open the valve stem of the 2‐way valve counterclockwise approximately 90’, wait 10 seconds, and then set it to closed position.
Be sure to use a hexagonal wrench to operate the valve stem.
3. Check for gas leakage.
Check the flare connection for gas leakage
4. Purge the air from the system.
Set the 2‐way valve to the open position and remove the cap from the 3‐way valve’s service port.
Using the hexagonal wrench to press the valve core pin, discharge for three seconds and then wait for one minute.
5. Use torque wrench to tighten the service port cap to a torque of 1.8 kgf.m. (18n.m)
12
6. Set the 3‐way valve to the opened position.
7. Mounted the valve stem nuts to the 2‐way and
3‐way valves.
8. Check for gas leakage.
At this time, especially check for gas leakage from the 2‐way and 3‐way stem nuts, and from the service port.
Caution:
If gas leakage is discovered in step (3) above, take the following measures.
If the leaks stop when the piping connections are tightened further, continue working from step (4).
If the gas leaks do not stop when the connections are retightened, repair the location of the leak, discharge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder.
7.5 Pumping down (Re‐installation)
Procedure
1. Confirm that both the 2‐way and 3‐way valves are set to the opened position.
Remove the valve stem caps and confirm that the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3‐way valve.
Connect the charge hose with the push pin to the gas service port.
5. Air purging of the charge hose.
Open the low‐pressure valve on the charge set slightly to purge air from the charge hose.
6. Set the 2‐way valve to the close position.
7. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
8. Immediately set the 3‐way valve to the closed position.
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and amount the 2‐way and 3‐way valve’s stem nuts and service port caps.
Use a torque wrench to tighten the service port cap to a torque of 1.8 kgf.m.
Be sure to check for gas leakage.
13
7.6 Re‐air purging (Re‐installation)
Procedure:
1. Confirm that both the 2‐way and 3‐way valves are set to the closed position.
2. Connect the charge set and a charging cylinder to the service port of the 3‐way valve.
Leave the valve on the charging cylinder closed.
3. Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2‐way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut to on the 2‐way valve.
4. Check the gas leakage.
Check the flare connections for gas leakage.
5. Discharge the refrigerant.
Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicates 0.3 to 0.5 Mpa.
6. Disconnect the charge set and the charging cylinder, and set the 2‐way and 3‐way valves to the open position.
Be sure to use a hexagonal wrench to operate the valve stems.
7. Mount the valve stems nuts and the service port cap.
Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
Be sure to check the gas leakage.
14
7.7 Balance refrigerant of the 2‐way, 3‐way valves
Procedure:
1. Confirm that both the 2‐way and 3‐way valves are set to the open position.
2. Connect the charge set to the 3‐way valve’s service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.05 to
0.1Mpa.
If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than 0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will not be necessary to apply an evacuation.
Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil still be discharged.
15
7.8 Evacuation
Procedure:
1. Connect the vacuum pump to the charge set’s centre hose.
2. Evacuation for approximately one hour.
Confirm that the gauge needle has moved toward ‐0.1 Mpa (‐76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle.
16
7.9 Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
2. Purge the air from the charge hose.
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful
of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a time
(approximately 150g each time0 while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.(pumping down‐pin).
4. Immediately disconnect the charge hose from the 3‐way valve’s service port.
Stopping partway will allow the refrigerant to be discharged.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
5. Mounted the valve stem caps and the service port
Use torque wrench to tighten the service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
17
8. Electronic function
8.1 Abbreviation
T1: Indoor ambient temperature
T2: Pipe temperature of indoor heat exchanger
T3: Pipe temperature of outdoor heat exchanger
T4: Outdoor ambient temperature
8.2 Display function
8.2.1 Icon explanation on indoor display board.
Lights up when the super ionizer function is energized.
This indicator illuminates when TIMER is set ON/OFF.
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating mode.
This indicator illuminates when the air conditioner is in AUTO operation.
Usually it displays the setting temperature. It will display the room temperature when the air conditioner is in FAN only operation. It will display “SC” when self-clean function is activated. It will also display the malfunction code or protection code.
This indicator appears only when the compressor is in operation and indicates the current operating frequency.
18
8.3 Protection
8.3.1 Three Minutes Delay at restart for compressor.
8.3.2 Temperature protection of compressor top.
If the temperature of compressor top is too high (higher than 115
℃ and the Over‐load Protector is cut, the units stop.
When the Over‐load Protector restore and close (lower than 100
℃), the compressor will restart (In this case the compressor is restricted by Three Minutes Delay protection.)
8.3.3 Temperature protection of compressor exhaust.
If the exhaust temp. of compressor is higher than 115
℃ and lasts for 5 seconds, the compressor stops and does not resume until the exhaust temp. is lower than 90
℃.
8.3.4 Inverter module Protection, Inverter module Protection itself has a protection function against current, voltage and temperature. If these protections happened, the corresponding code will display on indoor unit LED.
8.3.5 Sensor protection at open circuit and breaking disconnection
8.3.6 Fan Speed is out of control. When Indoor Fan Speed is too low (lower than 300RPM for 50 seconds), the unit stops and LED displays failure information and can’t return to normal operation automatically.
8.3.7 Zero‐crossing signal error warning.
If there is no zero‐crossing signal in 4 minutes or the interval is wrong, the unit will enter error warning.
8.3.8 For all modes, when the units are turned on, the indoor fan can operate 10 seconds after the action of louver.
8.3.9 Compressor preheating function.
Preheating permitting condition:
If T4(outdoor ambient temperature)
<3℃ and the machine connects to power supply newly or if T4<3℃ and compressor has stopped for over 3 hours, the compressor heating cable will work.
Preheating mode:
A weak current flow through the coil of compressor from the wiring terminal of compressor, then the compressor is heated without operation.
Preheating release condition:
If T4
>5℃ or user turns on the machine and compressor runs, preheating function will stop.
8.4 Fan‐Only Mode
8.4.1 Temperature setting function is disabled, and no setting temperature display.
8.4.2 In this mode, the action of louver is the same as in cooling mode.
8.4.3 The action of auto fan in fan‐only mode is the same as auto fan in cooling mode with 24
℃ setting
19
temperature.
3.
3.
1.
1.
℃ high medium low
8.5 Cooling Mode
8.5.1 The operation frequency of compressor after starting submits to following rule.
A
1 .5
B
1 .0
0 .5 C
‐0 .5
‐1.0 D
When the machine is running and ΔT(=room temp. – setting temp.) changes, the frequency of compressor will rise or descend a grade (7 minutes after starting).
After starting, if ΔT stays in a zone for 3 minutes, the frequency will change as follow:
Zone A : Current frequency rise a grade till the maximum grade F8.
Zone B: Keep the current frequency of compressor.
Zone C: Descend the current frequency of compressor until F1.
Zone D: Compressor stops after running as the minimum frequency F1 for 60 minutes or ΔT is less than ‐2
℃.
8.5.2 Indoor heat exchanger anti‐freezing function.
If T2 is lower than 0
℃, the compressor stops and resumes when T2>5℃.
8.5.3 Outdoor unit current control in cooling mode. comp. pause
I3COOL
I2COOL freq. descends if curr. rises; freq. remains if curr. descends
I1COOL running normally
8.5.4 Rating capacity test function
1) Set the indoor unit with remote controller as: high fan, 17
℃ in cooling mode, then press “TURBO” button on controller 6 times or more within 10 seconds (make sure indoor unit receives these signals), the machine will turn into rating capacity test mode, the buzzer will make a “di” sound for 2 seconds continuously. Also, indoor fan will change to rating speed, the frequency of compressor will be fixed as rating value. Any condition of above is not satisfied, the machine cannot be turned into rating capacity test mode.
2) The machine will quit from the rating capacity test mode if running for 5 hours or changing fan speed or setting temperature.
20
8.5.5 Turbo function(press the “TURBO” button on remote controller)
Elevate current frequency to a higher grade.
Indoor fan turns to turbo speed.
After running for 30 minutes the machine will turn back to previous setting mode.
8.5.6 Indoor fan operation rule.
In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto.
Auto fan in cooling mode acts as follow:
1.
1.
4.
℃
3.
high medium low
8.5.7 Condenser high temperature protection function(in cooling and drying mode)
If T3
>60℃ for 5 seconds, compressor will stop immediately, and the machine will not resume until T3<52℃.
8.6 Drying mode
8.6.1 Indoor fan speed is fixed at breeze grade and can’t be changed. The horizontal angle is the same as in cooling mode.
8.6.2 Room overlow temperature protection
In drying mode, if room temperature is lower than 10
℃, compressor will stop and not resume until room temperature climbs up to 12
℃.
8.6.3 Evaporator anti‐freezing protection, condenser high temperature protection and outdoor unit frequency limit are valid, and they are the same as that in cooling mode.
8.6.4 Horizontal louver action is the same as that in cooling mode.
8.7 Heating mode
8.7.1 Indoor fan action:
Anti‐cold‐wind function.
21
44
℃
38
37 setting fan speed low fan
34
33 breeze
24
17 super
1.5
1.0 fan stop
If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127 seconds with breeze.
During this period, anti‐cold‐wind is disabled. After this, anti‐cold –wind function is available.
If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and anti‐cold‐wind is disabled.
8.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti‐cold‐wind function is preferential.
Auto fan action in heating mode.
℃
2.5
2.0 low medium
high
8.7.3 The operation frequency of compressor after starting submits to following rule:
5.
4.
3.
3.
2.
D
C
B
A
When the machine runs, if ΔTh stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate the current frequency one grade, and not stop until the maximum grade.
Zone B: Keep the current frequency.
Zone C: Descend the current frequency one grade.
Zone D: Compressor stops after running with F1 for 60 minutes or when ΔTh
>6℃.
22
8.7.4 Outdoor unit current control in heating mode. comp. pause
I3HEAT
I2HEAT freq. descends if curr. rises; freq. remains if curr. descends
I1HEAT running normally
8.7.5 Indoor heat exchanger high temperature protection.
If T2
>60℃, the compressor will stop and not resume until T2<48℃.
8.7.6 Defrosting mode.
Condition of defrosting.
Condition 1: If T4
>0℃,
When the units are running, if the following two items are satisfied the units start defrosting:
The units runs with T3
<3℃ for 40 minutes and T3 keeps lower than ‐6℃ for more than 3 minutes.
The units runs with T3
<3℃ for 80 minutes and T3 keeps lower than ‐4℃ for more than 3 minutes.
Condition 2: If T4
<0℃,
The program judges according to the condition 1, if the two items are satisfied, then judges if T2 has descended for more than 5
℃, if it has the machine starts defrosting, or continues to judge T2 and will not defrost until T2 drops
more than 5
℃.
Condition 3: No matter what value T4 is, if the machine runs with T3
<3℃ for more than 120 minutes and T3 keeps lower than ‐2
℃ for more than 3 minutes, the machine will defrost, no matter if T2 drops for more than 5℃ or not.
Condition of ending defrosting.
If any one of following items is satisfied, defrosting will finish and the machine will turn to normal heating mode.
T3 rises to be higher than 12
℃.
T3 rises to be higher than 8
℃ and remains for 80 seconds.
The machine has run for 10 minutes in defrosting.
23
8.7.7 Defrosting action compressor on off
4‐way valve on off outdoor fan on off indoor fan on off indoor fan breeze
60s
70s no longer than 10
F8
30s
24
8.7.8 Rating capacity test function.
Set the indoor unit with remote controller as: high fan, 30
℃ in heating mode, then press “TURBO” button on controller 6 times or more within 10 seconds (make sure indoor unit receives these signals), the machine will turn into rating capacity test mode, the buzzer will make a “di” sound for 2 seconds continuously. Also, indoor fan will change to rating speed, the frequency of compressor will be fixed as rating value. Any condition of above is not satisfied, the machine cannot be turned into rating capacity test mode.
The machine will quit from the rating capacity test mode if running for 5 hours or changing fan speed or setting
temperature.
8.7.9 Turbo function in heating mode. (press the “TURBO” button on remote controller)
Elevate current frequency (excluding F8) to a higher grade. If indoor fan is in low speed or pause caused by defrosting or anti‐cold‐wind function, frequency of compressor will not be elevated one grade until these limit has been
released.
Indoor fan changes to turbo speed and anti‐cold‐wind function is valid.
8.8 Auto mode function
8.8.1 This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
℃.
In auto mode, the machine will choose cooling, heating or fan‐only mode according to ΔT (ΔT =T1‐Ts).
ΔT=T1‐Ts Running mode
ΔT
>1℃
Cooling
‐1≤ΔT≤1
℃
Fan‐only
ΔT
<‐1℃
Heating
8.8.2 Indoor fan will choose auto speed of relevant mode.
8.8.3 If the machine switches mode between heating and cooling, compressor will keep stopping for 15 minutes and then rechoose mode according to ΔT.
8.8.4 If the setting temperature is modified, the machine will rechoose running function.
8.9 Forced operation function
8.9.1 Forced cooling and auto function can be carried out through a touch button. In these two modes, the machine can be changed by remote controller to any other mode at any moment.
8.9.2 When the machine is off, pressing the touch button will carry the machine to forced auto mode, after this, if pressing the button once again within 5 seconds, the machine will turn into forced cooling mode. In forced auto, forced cooling or any other operation mode, pressing touch button will turn off the machine. In forced operation, remote control is available.
8.9.3 In forced operation mode, all general protections are available.
8.9.4 In forced cooling mode, after running for 30 minutes with compressor frequency F2 and breeze indoor fan speed, the machine will turn to normal auto mode in which setting temperature is 24
℃.
8.9.5 The action of forced auto mode is the same as normal auto mode which temperature is 24
℃.
25
8.10 Action of 4‐way valve
In heating, fan‐only, standby or turning off mode, 4‐way valve is off, while in cooling¥drying and forced cooling mode
4‐way valve is on. If the machine changes operation mode from heating to cooling and rying and forced cooling mode,
4‐way valve will be delayed off 2 minutes after compressor stop. If the machine changes operation mode from
non‐heating mode to heating mode, the 4‐way valve will be turned off immediately.
8.11 Two speeds outdoor fan function
8.11.1 Outdoor fan action in heating mode(including heating in auto mode).
℃
17 low
℃
22 hig
15 high
Outdoor fan action in heating mode
(including heating in auto mode).
20 low
Outdoor fan action in cooling & drying mode
(including cooling in auto & forced mode).
8.11.2 Outdoor fan action in cooling & drying mode(including cooling in auto & forced mode).
Please refer to the pic. above.
8.12 Timer function
8.12.1 Timing range is 24 hours, and the setting time is the relative time.
8.12.2 Timer on.
After turning off, the machine will turn on automatically when reaching the setting time.
8.12.3 Timer off.
After turning on, the machine will turn off automatically when reaching the setting time.
8.12.4 Timer on/off.
After turning off, the machine will turn on automatically when reaching the setting “on” time, and then turn off automatically when reaching the setting “off” time.
8.12.5 Timer off/on.
After turning on, the machine will turn off automatically when reaching the setting “off” time, and then turn on automatically when reaching the setting “on” time.
8.12.6 Timer function will be eliminated when the unit is turned off by remote controller.
8.13 Sleep function mode
8.13.1 Operation time in sleep mode is 7 hours. The unit will quit from this mode and be turned off in 7 hours.
8.13.2 In cooling, heating or auto mode sleep function is available.
8.13.3 Operation process in sleep mode is as follow:
After pressing SLEEP button on remoter controller, the machine will get into sleep mode.
When cooling, the setting temperature rises 1
℃(be lower than 30℃) every one hour, 2 hour later the rising stops and indoor fan is fixed as low speed.
When heating, the setting temperature descends 1
℃(be lower than 30℃) every one hour, 2 hour later the descending stops and indoor fan is fixed as low speed, and anti‐cold‐wind is available.
26
8.13.4 If user uses timer on function in sleep mode, sleep function will pause and not resume until reaches the setting on time.
8.13.5 When user uses timer off function in sleep mode(or sleep function in timer off mode), if the timing time is less than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing time is more than 7 hours, the machine will not stop until reaches the setting off time in sleep mode.
8.14 Auto‐Restart function
In case of a sudden power failure, the indoor main chip will restore the setting conditions before the power failure.
The unit will resume the previous operation setting (including setting mode, temperature, fan speed, vertical swing) automatically after 3 minutes when power returns.
8.15 Super Ionizer function
Super ionizer function which is controlled through remote controller is available only when the unit is on.
After the Aircon being turned on, the Ionizer function is switched on when the unit receives CODE from remote controller at first time, and ionizer is switched off when the unit receives the CODE again. It’s a circle.
After starting the Ionizer function, the ionizer can work only when the indoor fan motor is running. If the indoor fan
motor is off, the ionizer also stops working, even though the Ionizer function is available.Ionizer function will not be off when the running mode is switched. Ionizer function will be off when the unit is turned off.
8.16 Self‐clean function
1) Self‐Clean function is available only at cooling (including auto‐cooling and turbo) and drying mode, when the user presses down the button ”Self‐Clean” on remote controller, “SC” icon will be displayed on the indoor temperature display area. After running for 13 minutes in low fan mode, the unit will get into low heating mode (anti‐cold wind function is not valid). When the unit keeps low heating mode for 1 min or evaporator high temp protection occurs, it will stop heating and get into low fan mode and keep running for another 2 minutes. Then the unit will quit from
Self‐Clean function and turn off.
2) When setting the Self‐Clean function, the unit has been in Timer or Turbo function, the Timer or Turbo function will be cancelled and then execute Self‐Clean function.
3) When the unit is running Self‐Clean function, all other functions will be not available except swing/air
direction/clean air/vent/LED display, and only receiving “Self‐Clean” code again or “turn off” code, the unit will quit from the function.
4) When the unit is running Self‐Clean function, all protection functions are valid.
8.17 Follow me function
If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote controller, the buzzer will emit a sound and this indicates the follow me function is initiated. But when the indoor PCB receives signal which sent from remote controller every 3 minutes, the buzzer will not respond. When the unit is running with follow me function, the PCB will control the unit according to the temperature from follow me signal, and the temperature collection function of room temperature sensor will be shielded, but the error detective function of room temperature sensor will be still valid.
When the follow me function is available, the PCB will control the unit according to the room temperature (T1) from the remote controller and the setting temperature (TS), and the action of compressor is as following:
27
At cooling mode, if T1
<TS, compressor is off; If T1≥TS, compressor is on.
At heating mode, if T1
>TS, compressor is off; If T1≤TS, compressor is on.
The PCB will take action to the mode change information from remote controller signal, but it will not affected by the setting temperature.
When the unit is running with follow me function, if the PCB doesn’t receive any signal from remote controller for 7 minutes or pressing FOLLOW ME button again, the follow me function will be turned off automatically, and the
temperature collection function of room temperature sensor will be available, the PCB will control the unit according to the room temperature detected from its own room temperature sensor and setting temperature.
8.18 Outdoor heating cable (Optional)
A heating cable can be fixed on outdoor chassis to help deicing and to avoid freezing. Another heating cable can be fixed around compressor to help starting the compressor. These heating cables are useful to improve the performance of the air conditioner especially when the outdoor ambient temperature is very low. The rated power voltage for the heating cables is 220V‐240V. The action of the heating cables is controlled by the PCB. If outdoor temperature is lower than 5
℃, the heating cable will begin to work. If outdoor temperature is higher than 15℃, the heating cable will stop working.
28
29
9. Troubleshooting
Safety
Because there are capacitors in PCB and relative circuit in outdoor unit, even shut down the power supply,
electricity power are still kept in capacitors, do not forget to discharge the electricity power in capacitor.
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
Bulb (25‐40W)
9.1 Indoor Unit Error Display
E5
E6
P0
P1
P2
Display
E0
E1
E2
E3
P4
Note: E4 & P3: Reserved function
LED STATUS
EEPROM parameter error
Indoor / outdoor units communication protection
Zero‐crossing signal error
Indoor fan speed out of control
Open or short circuit of outdoor temperature sensors
Open or short circuit of indoor temperature sensors
Inverter module protection--IGBT over‐strong current protection
Over voltage or too low voltage protection
Temperature protection of compressor top.
Inverter compressor drive error
30
31
9.2 Diagnosis and Solution
9.2.1 E0 (EEPROM parameter error) error diagnosis and solution
Circuit or software error on indoor PCB Replace indoor PCB
9.2.2 E1 (indoor / outdoor units communication protection) error diagnosis and solution
Disconnect the power supply, after 1 minute, connect the power supply, turn on the unit with remote controller
Does the unit work normally?
NO
Check the wiring between indoor and outdoor unit. Is the connection of L, N, S and GND good?
Is the GND connection on outdoor PCB good?
Yes
Is the LED4(red) on outdoor
PCB bright and LED1(yellow) blinking?
No
The power supply for outdoor
PCB is fail. Check the wiring on outdoor PCB comparing with wiring plate. Is the connection good?
No
Correct the connection.
Yes
9.2.3 E2(zero‐crossing signal error) diagnosis and solution
Is power supply and connection of connectors good?
NO
YES
NO
Yes
Reconnect and retest again
Replace indoor PCB and repower on. Is the failure cleared?
Replace outdoor e‐box.
Be sure the power supply is good and correct the connection
Indoor PCB is defective. Replace the indoor PCB.
9.2.4 E3(indoor fan speed out of control) diagnosis and solution
Is the indoor fan motor connector and connection good?
YES
NO
Is voltage being applied to the fan motor?
(rang 90v‐160v between mid pin and N on CN1
YES
NO
Repair the connector and reconnect
Indoor PCB is defective.
Replace the indoor PCB.
Replace the indoor fan motor
9.2.5 E5(Open or short circuit of outdoor ambient or condenser temperature sensor) diagnosis and solution.
Is the outdoor temperature sensor connector and connection good?
YES
NO
Repair the connector and reconnect
Replace the sensor and check if E5 display again?
YES
Replace outdoor e‐box
9.2.6 E6(open or short circuit of indoor room or evaporator temperature sensor) diagnosis and solution.
Is the indoor temperature and evaporator sensor connector and connection good?
NO
Repair the connector and reconnect
YES
Replace the sensor and check if E6 display again?
YES
Replace the.indoor PCB
9.2.7 P0(IGBT over‐strong current protection) diagnosis and solution.
Is all connections on PCB and between PCB and compressor good?
YES
NO
Replace the outdoor PCB and then repower on. Is the failure cleared?
NO
32
Repair or correct the connector or connection.
Check the compressor
33
9.2.8 P1(over voltage or too low voltage protection) diagnosis and solution.
NO
Is the power supply good?
Be sure the power supply is normal when using the units
YES
Replace the outdoor e‐box.
9 .2.9 P2(temperature protection of compressor top) diagnosis and solution.
NO NO
Does compressor operate?
Is the connection good?
YES YES
Is refrigerant circulation volume norma l?
NO
Is protector normal?
YES
NO
Charge refrigerant
Check the outdoor main PCB. Is there some problem?
YES
Is abnormality the same after gas charging?
NO
Reconnect and retest.
Replace the protector.
Replace the outdoor PCB.
Check refrigerant system (such as clogging of capillary, etc)
9 .2.10 P4(inverter compressor drive error) diagnosis and solution.
Is the connection of compressor good? Is the wiring sequence right? The voltage range proper?
YES
NO
Replace the outdoor E‐box.
Reconnect and retry
If the problem comes to again, check coil resistance of inverter compressor, is it right?
NO
Replace inverter compressor
9 .3 Checking for temperature sensors
Room temp.(T1) sensor,
Indoor coil temp.(T2) sensor,
Outdoor coil temp.(T3) sensor,
Outdoor ambient temp.(T4) sensor,
Compressor exhaust temp.(Te) sensor.
Measure the resistance value of each winding by using the multi‐meter.
Some frequently‐used R‐T data for T1,T2,T3 and T4 sensor:
Temperature (
℃)
5 10 15 20 25 30 40 50 60
Resistance Value (KΩ) 26.9 20.7 16.1 12.6 10 8 5.2 3.5 2.4
Some frequently‐used R‐T data for Te sensor:
Temperature (Ԩ) 5 15 25 35 60 70 80 90 100
Resistance Value (KΩ) 141.6 88 56.1 36.6 13.8 9.7 6.9 5 3.7
34
℃
FSIArt‐100HFD indoor
5
6
7
3
4
8
9
10
10,1
10,2
10,3
No.
1
1,1
1,2
1,3
2
Part Name
panel assembly panel panel bolt panel shackles
Air cleaner
Air cleaner holder
Left air filter
Right air filter
Screw cap
Window cover for repairing
Display board enclosure panel 's Mandril driven swing connector panel frame initiative swing connector
Louver motor
Louver motor cover panel frame
Quantity
2
1
2
1
2
1
1
1
3
1
1
1
1
1
2
1
1
1
BOM Code
201132590304
P0000350947
P0000350949
201232590012
201130100212
201130100217
201132590297
201132590296
201132590303
201132590298
203332390422
201132590292
201132590300
201132590301
P0000354085
202400200054
201132590289
P0000354080
11,6
20
21
22
23
23,8
23,7
16
17
18
19
12
13
14
15
23,6
23,1
23,9
24
25
23,5
23,4
23,3
23,2
26
27
28
29
11
11,1
11,2
11,3
11,4
11,5
Air out frame assembly
Vertical airflow louver
Horizontal airflow grille
Grille holder
Ion engender
Air out frame
Horizontal louver bolt
Holder stepping motor axis lash‐up switch cover
Drain Hose
Evaporator
Connecting pipe clamp
Baffle of temperature induction
Motor cover fan motor
Bearing holder
Cross flow fan
Chassis
Installation plate
Electric control assy
E‐part box cover
Wire Clip
Chip
Main control board
Electronic control box terminal transformer
Indoor temp sensor
Pipe Temp sensor
Wire clamp
Remote controller
Holder,remote controller
Copper nut
Copper nut connector for watering seal
201532390081
201232500001
201130490002
201132590299
202400300215
202730100201
201100200120
201132590305
201232390012
203332390424
201132390371
201130100209
201300731546
201332390506
201132390370
202301450119
202300900176
202433190000
202301300080
201135210303
203355090362
201155060529
201600320000
201600320001
201101020011
202720090001
201132590327
201132590295
P0000349541
P0000349544
202403000021
P0000350724
201132590294
201133190032
201102010015
202400200006
201131390149
201132590293
201130000011
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
10
2
1
1
FSIArt‐100HFD outdoor
No.
1
16
17
18
19
10
11
12
13
14
15
8
9
6
7
2
3
4
5
Part Name
Indoor temp sensor
Rear net condenser coil assembly
Pipe Temperature Sensor valve plate base pan assembly
Big handle
Water collector
Right clapboard clip, capacitor
Capacitor,Compressor partition plate assembly front panel
Front net motor mounting bracket axial flow fan
Left supporter
Small handle top cover assembly
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
BOM code
202301300160
2011374G0003
201537390033
202440500004
201235120614
201237590027
201135000005
201135270201
201235270204
201200100002
202401090055
201237590008
201237400029
201137590000
201237500005
201100300502
201237400028
201150290006
201235270249
25,2
25,3
25,4
26
24,4
24,5
25
25,1
24
24,1
24,2
24,3
20
21
22
23
26,1
27
27,1
27,2
28
29
30 motor
Reactor
Cover for inductance assembly
Reactor electrical box assembly
E‐Parts box
Radiator
E‐Parts box's cover
Main control board
Holder for E‐parts board of terminal,assy
Wire joint
Washer for wire joint
Wire clamp board of terminal liquid valve assembly
Liquid valve
Low Pressure Valve Ass'y
4‐Ways valve
Gas pipe valve sound‐proof materialI rotary compressor sound‐proof material
Indoor temp sensor
Low ambient kit
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
202400400477
202301000820
201235250802
202301000819
203337390134
201237300171
202301900068
201237300162
201337390055
201137300162
203337390043
202301450113
201135000004
201219900001
201237590009
201637390335
201600740523
201632390037
201600670003
201600720200
202137300000
201400620600
202137390006
202301300079
201319900490
FSIArt‐180HFD indoor
3
12
13
14
15
16
17
10
11
8
9
6
7
4
5
No.
1
2
Front panel
Display board assy
Part Name
Air cleaner holder
Air cleaner
Right air filter
Left air filter
Screw cap
Window cover for repairing
Panel frame assy
Flap
Air out frame assy
Louver motor lash‐up switch cover
Drain hose
Evaporator,assy
Motor cover
Motor
Bearing holder
Quantity
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
BOM Code
201132890178
201132890167
201319900062
201130100217
201130100212
201132890173
201132890174
201132890172
201132890168
201132890170
201132890176
201132890193
202400200006
201132890169
201130000011
201532890029
201132890175
202400300415
202730100201
22,8
23
24
25
22,4
22,5
22,6
22,7
26
27
28
22
22,1
22,2
22,3
18
19
20
21
Cross flow fan chassis
Connecting pipe clamp
Installation plate
Electronic control box,indoor unit
E‐Parts box
E‐Parts box's cover
Main control board
Wire Clip
Indoor temp sensor
Evaporator temp sensor
Wire joint, 5p
Transformer
Remote Controller
Holder,remote controller
Copper nut, TLM‐A01
Copper nut, TLM‐C03 connector for watering seal
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
201100200107
201132890180
201232800001
201232790008
203332890138
201132890148
201132890147
201332890093
201135210303
202433190000
202301300080
202301450119
202300900176
203355090362
201155060529
201600320000
201600320002
201101020011
202720090001
FSIART‐180HFD outdoor
No.
1
16
17
18
19
10
11
12
13
14
15
8
9
6
7
2
3
4
5
Part Name
Indoor temp sensor
Rear net condenser coil assembly
Pipe Temperature Sensor valve plate base pan assembly
Big handle
Water collector
Right clapboard clip, capacitor
Capacitor,Compressor partition plate assembly front panel
Front net motor mounting bracket axial flow fan
Left supporter
Small handle top cover assembly
Quantity
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
BOM code
202301300057
2011374G0003
201537890023
202440500004
201235120614
20123789G006
201135000005
201135270201
201235270204
201200100002
202401090055
20123789G003
201237890018
201137890001
201237890037
201100300514
201237400028
201150290006
201235270249
25,2
25,3
25,4
26
24,4
24,5
25
25,1
24
24,1
24,2
24,3
20
21
22
23
26,1
27
27,1
27,2
28
29
30 motor
Reactor
Cover for inductance assembly
Reactor electrical box assembly
E‐Parts box
Radiator
E‐Parts box's cover
Main control board
Holder for E‐parts board of terminal,assy
Wire joint
Washer for wire joint
Wire clamp board of terminal liquid valve assembly
Liquid valve
4‐Ways valve Ass'y
4‐Ways valve
Gas pipe valve sound‐proof materialI rotary compressor sound‐proof material
Low ambient kit
Indoor temp sensor
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
202400410661
202301000819
20123789G002
202301000834
203337890142
201237300171
202301900089
201237300162
201337790009
201137300162
203337390043
202301450113
201135000004
201219900001
201237590009
201637890228
201600740523
201637890243
201600690011
201600720195
202137300000
201400710680
202137590001
201319900494
202301300079