- No category
advertisement
TEMPERATURE and HUMIDITY
TRANSDUCER
P19 TYPE
USER’S MANUAL
1
2
Contents
1. APPLICATION .................................................................. 5
2. TRANSDUCER SET .......................................................... 5
3. BASIC REQUIREMENTS, OPERATIONAL SAFETY ....... 6
4. INSTALLATION .................................................................. 6
4.1. Overall dimensions and working position ................... 6
4.2. Electrical connections ................................................. 7
4.3. Assembly .................................................................... 8
5. SERVICING ...................................................................... 10
5.1. Messages after supply is switched on ...................... 10
5.2. Functions of the P19 transducer .............................. 10
5.2.1. Calculated values .................................................. 11
5.2.2. Default parameters ................................................ 12
6. MODBUS PROTOCOL ON RS-485 SERIAL PORT ....... 12
6.1. Serial interface connection ....................................... 12
6.2. Description of the MODBUS protocol ...................... 13
6.3 Description of implemented MODBUS functions ....... 13
6.4 Register map ............................................................. 18
6.5 Read/Write registers .................................................. 19
6.6 Read only registers ............................................... 21
7. EMERGENCY RESTORATION OF RS-485 PARAMETERS......22
8. TECHNICAL DATA .......................................................... 23
9. ORDERING CODE ........................................................... 25
3
4
1. APPLICATION
The P19 transducer is device destined for the continuous
measurement and conversion of relative humidity and ambient temperature into a digital form (protocol MODBUS RS-485). The transducer is fixed on a wall. The programming of the transducer is possible by means of the RS-485 interface.
Fig. 1. View of the P19 transducer.
2. TRANSDUCER SET
The delivered controller set is composed of:
1. transducer P19 ................................... 1 pc
2. user’s manual ..................................... 1 pc
3. guarantee card.................................... 1 pc
5
3. BASIC REQUIREMENTS, OPERATIONAL SAFETY
In the security scope, the transducer meets the requirements of the EN 61010 -1 standard.
Remarks concerning the operator safety: l
All operations concerning transport, installation, and commissioning
as well as maintenance must be carried out by qualified, skilled
personnel.
l
Before switching the transducer on, one must check the correctness
of connections to the network.
l
The device is destined to be installed and used in industrial
electromagnetic environment conditions.
When unpacking the P19 transducer, please check whether the type and version code on the data plate correspond to the order code.
4. INSTALLATION
4.1. Overall dimensions and working position
The P19 transducer is designed to be mounted on a wall by means of a screw connection. Transducer housing is assembled of two parts: front part and back part. The transducer has screw connectors placed inside the transducer, which enable the connection of external wires of 1 mm 2 cross-section.
25
120
6
Fig. 2. Overall dimensions of the P19 transducer and correct working position
Fig. 3. Lay-out of assembly holes in back part of housing
4.2. Electrical connections
The P19 transducer has 4 connecting terminals to which there is access after removing the front part of the transducer housing.
ZW
J2
J1
Fig 4. Marking of terminals for the connection of external signals
7
Fig. 5. Way of electrical signal connection
Transducer is equipped with two LED indicator: RX (green color) , TX (red color), which indicates the state of RS-485 communication lines. Indicators works only first 60 sec after power is on or after switching “ZW” jumper (section 7).
4.3. Assembly
On the beginning one must separate front part of housing from back part of housing with printed circuit board using flat screwdriver as shown on Fig. 6.
8
Fig. 6. Disassembly housing method
Back part of housing is equipped with hole at the middle of housing through which electrical cords should be passed. Then back part of housing should be screwed on to the wall. Electrical cords should be passed through the hole on the printed circuit board (Fig. 7) and connected to the screw connectors with the right way (Fig. 5)
Fig. 7. The way of assembly electrical cords
After connecting cords and pushing the front part of housing transducer is ready to work.
To connect the input signals in an environment with high interference, one must apply shielded wires. The shield must be connected to the nearest PE point from the feeder side.
9
5. SERVICING
After connecting cords, closing the housing, and connecting to the supply, the transducer is ready to work with manufacturer’s settings
(table 2). The transducer can be programmed through the RS-485 interface.
One can program following parameters in the transducer:
- communication parameters
- averaging time of the measurement
There is the possibility to connect the transducer through another transmission media, like: ETHERNET, USB, using LUMEL S.A.’s converters.
5.1. Messages after supply is switched on
After connecting external signals and switching the supply on, the transducer indicates its ready to work by switching on two LED indicators RX(green color) i TX(red color). After about 5 seconds, the transducer automatically switches to the mode in which it measures and converts into the digital value.
5.2. Functions of the P19 transducer l measurement of ambient temperature and relative humidity, l calculation of chosen physical quantities (dew-point temperature,
absolute humidity), l memory storage of maximal and minimal values for each of the
measured and calculated value, l programming of the measurement averaging time, l RS-485 interface servicing in the MODBUS protocol, in RTU mode.
10
5.2.1. Calculated values
Based on measured temperature and relative humidity the P19 transducer calculates dew-point and absolute humidity from the following relations.
DP → dew point:
DP=
T n m
RH
10000 . A
- 1
AH → absolute humidity: where:
AH= 2.1668
.
T → measured temperature [oC]
RH → measured relative humidity [%]
P ws
.
RH
100 . (T + 273.2)
DP → dew-point temperature [oC]
P ws
→ pressure of the satured water vapor
(water vapor pressure) [mbar]
AH → absolute humidity [g/m3]
Table 1
Coefficients used for the dew-point calculations
T [ o C] A m Tn
< 0
0 … 50
6.119866
6.1078
50 ...100
5.9987
7.926104
7.5
7.3313
250.4138
237.3
229.1
11
5.2.2. Default parameters
Table 2 shows the default parameters of P19 transducer.
These settings can be restored using the RS-485 interface by writing into the 4009 register the value „1”.
Table 2
Parameter description
Address
Baud rate
Mode
Averaging time
Parameter address
4001
4002
4003
4005
Default value
1
9600
RTU 8N2
30 [s]
When standard communication parameters have been changed and the new configuration has been lost, one can set temporary parameters by switching the jumper marked with the symbol “ZW” (section 7).
6. MODBUS PROTOCOL ON RS-485 SERIAL PORT
Digital P19 transducers are equipped with serial RS-485 link port with implemented MODBUS protocol to enable digital communication between computer systems and other devices which have
MODBUS Master functions implemented. The implemented protocol is in compliance with thePI-MBUS-300 Rev G Modicon Company specification.
6.1. Serial interface connection
Standard RS-485 port allows direct connection of up to 32 devices on a single serial link with a length of 1200 m (at a baud rate of 9600 b/s). To connect more devices it is necessary to use additional intermediate-separating devices.
12
Interface line location are shown in the figure 5. To obtain a correct transmission it is necessary to connect the A and B line parallel with their counterparts in other devices. To connect to the PC, the RS-485 interface card or the converter, e.g. PD10 is required.
6.2. Description of the MODBUS protocol
The implemented protocol is in compliance with the PI-MBUS-
300Rev G Modicon Company specification. Parameters of the transducer serial link : transducer address baud rate: working modes: maximal response time:
1..247
4800, 9600, 19200, 38400, 57600 [b/s]
RTU: 8N2, 8E1, 8O1, 8N1
500 ms
The configuration of serial link parameters consists on settlement of baud rate, device address and protocol (working mode).
Note: Each transducer connected to the communication network must
have: l unique address, different from other devices connected to
the network, l the same baud rate and information unit type (working
mode).
6.3 Description of implemented MODBUS functions
Functions of the Modbus protocol implemented in P19 transducer:: l 03 (03h) – Read Holding Registers l 04 (04h) – Read Input Registers l 06 (06h) – Write Single Register
13
l 16 (10h) – Write Multiple registers l 17 (11h) – Report Slave ID.
Read Holding Registers (code 03h)
Example 1. Reading two float(32 bits) registers, first register address is 1D4Dh (7501) , register values (7501, 7502): 25.68, 20.25.
Request:
Table 3
Device address
01h
Function
03h
Register address
B1
1Dh
B0
4Dh
Number of registers
B1
00h
B0
02h
CRC
5270h
Response:
Table 4
1DB0h (7501) 1DB1h (7502)
CRC
Device address
Number of bytes B3 B2 B1 B0 B3 B2 B1 B0
01h 03h 08h 41h CDh 70h A4h 41h A2h 00h 00h 83D0h
Example 2 . Reading two float 32-bit registers (7501,7502) located in 2x2 following 16-bit registers (7002, 7003, 7004, 7005), first register address is 1B5Ah (7002) – 32-bit register values : 25.68, 20.25.
14
Request:
Table 5
Device address
Function
Register address
Number of registers
CRC
01h 03h
B1
1Bh
B0
5Ah
B1
00h
B0
04h 62FEh
Response:
Table 6
Register value
1B5Ah
(7002)
Register value
1B5Bh
(7003)
Register value
1B5Ch
(7004)
Register value
1B5Dh
(7005)
CRC
Device address
Number of bytes
Register 7501 (32 bit) value
Register 7502 (32 bit) value
B3 B2 B1 B0 B3 B2 B1 B0
01h 03h 08h 41h CDh 70h A4h 41h A2h 00h 00h 83D0h
Example 3. Reading two float 32-bit registers (7501,7502) located in
2x2 following 16-bit registers (6002, 6003, 6004, 6005), first register address is 1772h (6002) - 32-bit register values : 25.68, 20.25.
Request:
Table 7
Device address
Function Register address
Number of registers
CRC
B1 B0 B1 B0
01h 03h 17h 72h 00h 04h E1A6h
15
Response:
Table 8
Register value
1B5Ah
(7002)
Register value
1B5Bh
(7003)
Register value
1B5Ch
(7004)
Register value
1B5Dh
(7005)
CRC
Device address
Number of bytes
Register 7501 (32 bit) value
Register 7502 (32 bit) value
B1 B0 B1 B0 B3 B2 B1 B0
01h 03h 08h 70h A4h 41h CDh 00h 00h 41h A2h E411h
Write Single Register (code 06h)
Example 4. Writing value “3” to the register 0FA1h (4001)
Request:
Table 9
Device address
Function Register address
Number of registers
CRC
B1 B0 B1 B0
01h 06h 0Fh A1h 00h 03h 983Dh
Response:
Table 10
Device address
Function Register address
Number of registers
CRC
B1 B0 B1 B0
01h 06h 0Fh A1h 00h 03h 983Dh
16
Write Multiple registers (code 10h)
Example 5. Writing value “3” and “4” to registers FA1h (4001) and
FA2h (4002)
Request:
Device address
Register address
Number of registers Num- ber of bytes
Table 11
Register value
(4001)
Register value
(4002)
CRC
B1 B0 B1 B0 B1 B0 B1 B0
01h 10h 0Fh A1h 00h 02h 04h 00h 03h 00h 04h 8828h
Response:
Table 12
Device address
Function Register address
Number of registers
CRC
B1 B0 B1 B0
01h 10h 0Fh A1h 00h 02h 133Eh
Report Slave ID (code 11h)
Example 6. Report slave ID
Request: Table 13
Device address
Function
CRC
01h 11h C02Ch
Response:
Table 14
Number of bytes
Device state
Variable bytes depending on device firmware ver. And serial number (neg. ver. 0.95, serial number. 13040001)
CRC
01h 11h 08h D0h FFh 00h 95h 40h 01h 80h 0Dh DFC3h
17
6.4 Register map
In the P19 transducer the data is stored in 16- and 32-bit registers. The process variables and parameters of the device are stored in the different address space depending on the variable type. The bits in the 16-bit registers are numbered from the least significant to the most significant (b0 … b15). The 32-bit registers (4 Bytes) contain floatingpoint values in IEEE-754 standard. Bytes sequence: B3 B2 B1 B0 – the most significant byte is sent as the first one. 16-bit registers which represents 32-bit values on a two following registers are multiplied at different address field with different bytes (word) order. Registers
6000...6024 (B1, B0, B3, B2) , Registers 7000...7024 (B3, B2, B1, B0).
Register map of the P19 transducer is shown in Table 15.
Note:
All the given addresses are physical addresses. In some computer programs logical addressing is applied, then the addresses should be increased by 1.
Table 15
Address range
Value type
Description
4000
- 4011 integer
(16 bits)
The value is located in the 16-bit register
6000-6024 float
(32 bits)
7000-7024 float
(32 bits)
7500-7512 float
(32 bits)
The value is located in two following 16-bit registers. Registers contain the same data as 32-bit registers from the area 7500-7512.
Registers are readout type only. Byte order
(B1, B0, B3, B2)
The value is located in two following 16-bit registers. Registers contain the same data as 32-bit registers from the area 7500-7512.
Registers are readout type only. Byte order
(B3, B2, B1, B0)
The value is located in the 32-bit register.
Registers contain measured and calculated data by the transducer. Registers are readout type only. Byte order (B3, B2, B1, B0)
18
6.5 Read/Write registers
Table 16
Description
4000 Identifier r 208 Identifier of the P19 transducer
4001 Address
4002 Baud rate of the RS-
485 link r/w r/w
4003 Transmission mode of the RS-
485 link r/w
4004 Acceptation of RS-
485 link parameter changes
4005 Averaging time r/w r/w
1...247
Device address
0...5
Value
0
Description
4800 bit/s
1
2
3
9600 bit/s
19200 bit/s
38400 bit/s
0...3
0...1
4 57600 bit/s
Value Description
2
3
0
1
RTU 8N1
RTU 8N2
RTU 8E1
RTU 8O1
Value Description
0 no changes
1 acceptation of changes
6...3600
Measurement averaging time [s]
19
4006 Erasing of extremes
4007 Status register r/w r/w
0...1
-32768...
32767
Value Description
0
1 no changes
Erasing of min and max value
Transducer status. Describe current state and device configuration. Bits representing specific events.
Value bit ‘1’ means that specific event occurred.
Bit15 Supply reset, writing value
-32768 ( 8000h ) clears status bit
Bit14
Bit13
Calibrations parameters error
Incorrect transducer parameters – new parameters required unused Bit12
Bit11
Bit10
Bit9
Bit1
Bit0 unused
Min/max erasing status, writing value 1024 ( 400h ) clears status bit
Temporary communication parameters set (short circuit
„ZW” jumper) unused Bit8
Bit7 Communication with sensor error
Bit5,6 unused
Bit3,4 unused
Bit2 Exceeding of measurement averaging time unused unused
20
4008 Firmware ver.
4009 Restore default parameters r r/w
1...999
Firmware version x100
0...1
Value Description
0 no changes
1 Force restoring default parameters (value of register will automatically change to “0’)
4010 reserved
4011 reserved
6.6 Read only registers
Name
Read
(r)/
Write
(w)
Unit
Table 17
Description
7000/6000
7002/6002
7004/6004
7006/6006
7008/6008
7010/6010
7500
7501
7502
7503
7504
7505
ID
T
RH
DP
AH min T w w w w w w
o o o
C
%
C g/m
3
C
P19 identifier
Measured temperature
Measured relative humidity
Calculated dew point
Calculated absolute humidity
Min. measured temperature
21
7012/6012
7014/6014
7016/6016
7018/6018
7020/6020
7022/6022
7024/6024
7506 max T
7507 min RH
7508 max RH
7509 min DP
7510 max DP
7511 min AH
7512 max AH w w w w w w w o o o
C
%
%
C
C g/m
3 g/m
3
Max. measured temperature
Min. measured relative humidity
Max. measured relative humidity
Min. calculated dew point
Max. calculated dew point
Min. calculated absolute humidity
Max. calculated absolute humidity
7. EMERGENCY RESTORATION OF RS-485 PARAMETERS
When standard communication parameters have been changed and the new configuration has been lost, one can set temporary
RS-485 parameters by switching jumper marked with the symbol „ZW”
(Fig. 4.) Temporary RS-485 parameters are shown below: l l l address baud rate mode
247
9600 kb/s
RTU 8N2
The changes of parameters must be made before removing the jumper, otherwise the device will return to its previous configuration.
22
8. TECHNICAL DATA
Basic parameters:
- relative humidity range
- relative humidity measurement
accuracy
- hysteresis of measuring
relative humidity
- temperature range
- temperature measurement
accuracy
- calculated values
RS-485 interface:
- protocol
- baud rate
- mode
- maximal response time
Rated operating conditions:
- supply voltage
- power consumption
- ambient temperature
- storage temperature
- relative humidity:
- warm-up time
- insured protection grade
ensured by the housing
- mounting
- weight:
- dimensions
0...100 %
1
±3% in range 10...90%
±5% for the remaining range
± 1%
– 20...60 °C
2
±0.6
o
C in range 10...40
o
C
±1.0
o
C for the remaining range absolute humidity (a) [g/m
3
] dew point (Td) [°C]
MODBUS slave
4800, 9600, 19200, 38400,
57600 bit/s
RTU: 8N2, 8E1, 8O1, 8N1
500 ms
9...24 V a.c. / d.c.
< 0.3 VA
– 20...23…60 °C
– 30...23…85 °C
< 95%
1
<15 min.
IP 20 on the wall
<0.2 kg
120 x 80 x 25 mm
23
working position: according Fig. 2.
Galvanic isolation
- between supply and RS-485 interface 1 kV
Electromagnetic compatibility:
- disturbance immunity
- disturbance emission acc. to EN 61000-6-2 acc. to EN 61000-6-4
Security requirements acc. to EN 61010-1
- installation category III
- pollution grade
- phase-to-earth working voltage
- altitude above sea level
2
50V
< 2000m
1
- In case of condensation of water vapor on the sensor surface,
the error measurement does not exceed the basic error till
the moment of drying up the sensor structure.
2 - The absolute temperature measurement range is -30...85°C,
but beyond the basic range, the measurement class is not
guaranteed.
24
9. ORDERING CODE
Table 18
P19 - XX X X
Version: standard custom-made*
Language: polish english other
Acceptance tests: without extra quality requirements with an extra quality inspection certificate acc. to customer’s requirements*
00
XX
P
E
X
0
1
X
*After agreeing with the manufacturer
Example of Order:
The code: P19 - 00E0 means:
P19 – humidity and temperature transducer
00 – standard version
E – English language version
0 – without additional quality requirements.
25
26
27
LUMEL S.A.
ul. Słubicka 1, 65-127 Zielona Góra, Poland
Tel.: (48-68) 45 75 100
Fax: (48-68) 45 75 508 e-mail:[email protected]
http://www.lumel.com.pl
Export Department :
Tel.: (48-68) 45 75 302
Fax: (48-68) 32 54 091 e-mail: [email protected]
28
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 1. APPLICATION
- 5 2. TRANSDUCER SET
- 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETY
- 6 4. INSTALLATION
- 6 4.1. Overall dimensions and working position
- 7 4.2. Electrical connections
- 8 4.3. Assembly
- 10 5. SERVICING
- 10 5.1. Messages after supply is switched on
- 10 5.2. Functions of the P19 transducer
- 11 5.2.1. Calculated values
- 12 5.2.2. Default parameters
- 12 6. MODBUS PROTOCOL ON RS-485 SERIAL PORT
- 12 6.1. Serial interface connection
- 13 6.2. Description of the MODBUS protocol
- 13 6.3 Description of implemented MODBUS functions
- 18 6.4 Register map
- 19 6.5 Read/Write registers
- 21 6.6 Read only registers
- 22 7. EMERGENCY RESTORATION OF RS-485 PARAMETERS
- 23 8. TECHNICAL DATA