Programmable platform
Programmable platform
General description
Eliwell's programmable platform
FREE Way: the new Eliwell approach to programmability, giving customers
the tools to find their own faster and more effective solutions.
FREE Way is the new programmable platform from Eliwell, consisting
of the FREE Studio software Suite, FREE Smart, FREE Panel and FREE
Evolution, the new programmable controller range available in various
sizes to choose from.
FREE Studio software suite, simple and flexible, is compatible with the
5 standard programming languages (IEC 61131-3), and is structured
to manage a whole range of controllers of different sizes and with
varying levels of complexity, in order to satisfy all the customer's system
customisation requirements.
FREE Smart
Specifications
FREE Studio
•
Unique software suite for fast and easy programming
•
Advanced debugging and simulation options and complete, efficient online Help
•
Protection of applications and different use levels
•
Application revision log
•
Customisable interface
Free Smart
•
User interface with configurable keys.
•
Available in three formats, in versions 100...240V~ and 12...24V~/ 24VC:
•FREE Smart SMP Panel mounting (32x74mm) with LED display
•FREE Smart SMD 4 DIN with LED display, FREE Smart SMC 4 DIN with no display
•
Can be connected to RS-485, Modbus RTU, or standard Eliwell peripherals and user interfaces.
FREE Panel
•
FREE Panel EVP system controller, with gateway functions and backlit LCD graphic display
•
High connectivity: can be integrated in industrial systems and BMS
•
Connects to standard Eliwell and third-party peripheral devices
•
Can be panel or wall-mounted
FREE Advance
•
Fully customisable graphic user interface.
•
Available in formats: 8 Din FREE Advance AVD with backlit LCD graphic display, FREE Advance AVC without display
•
High connectivity on board as standard for integration with industrial systems and BMS without optional modes
•
Connects to standard Eliwell and third party peripheral devices (including FREE Smart)
FREE Evolution
•
Fully customisable graphic user interface.
•
Available in formats: 8 Din FREE Evolution EVD with backlit LCD graphic display, FREE Evolution EVC without display
•
High connectivity: integrates into industrial systems and BMS using dedicated plug-in modules.
•
Connects to standard Eliwell and third party peripheral devices (including FREE Smart)
Certification
2
C
US
based on the model indicated in the UL reference file no. E233482
Plus points
Speed
One of the main goals of the free programmable platform is to give
our customers the tools to find faster, more effective solutions for their
customers. Many features of FREE make it possible to effectively reduce the
time between defining a new application and putting it into production.
Compact dimensions
FREE Panel
The FREE programmable platform enables customers to keep costs at a
competitive level. The FREE controllers are made with particular emphasis
placed on technological solutions and physical size, for significant results in
terms of simplicity, modularity and compactness. The integrated solutions
and small size of FREE controllers provide real, immediate economic
advantages for customers.
Efficiency
The FREE programmable platform, complete and scalable across various
levels of complexity, offers customers great freedom in choosing the
solution they feel is best suited to their own requirements. This makes it
easier to find solutions which take account of costs and/or the reduction
of product codes, including solutions which are more open to future
development or future system requirements, with particular reference to
connectivity.
FREE Advance
Reliability
The high quality of the new FREE Way programmable platform allows
customers to reduce any costs linked to a lack of quality, during both
the production process and on-site installation procedures. The FREE
Smart, FREE Panel, FREE Advance, and FREE Evolution controllers
and FREE Studio development environment were designed using
innovative but carefully reconstructed criteria, adopting advanced and
stable technological solutions as well as certified, monitored production
processes. Eliwell has always been a byword for reliability.
FREE Evolution
The FREE Way targets
Manufacturers of:
•
A.T.U. (Air Treatment Units)
•
Chillers
•
Heat Pumps
•
Rooftops
•
Precision conditioning systems
•
Compressor Racks
Installers/integrators of:
Remote display
•
All air systems
•
Hydronic systems
•
Combo systems (air/water)
•
Commercial automation
3
FREE Studio
FREE Studio software suite is compatible with all 5 standard programming
languages (IEC61131-3).
Each project may be composed of several programs; the developer can
use one or more languages in the same project.
Each new program offers the choice of 5 programming languages, 2 textbased and 3 graphics-based:
•
•
•
•
•
ST, Structured Text
FBD, Functional Block Diagram
LD, Ladder
IL, Instruction List
SFC, Sequential Function Chart
IEC61131-3 development software
Main Functions
Display variables with application running
Debugging of variables by displaying their status in numerical format when the application is running and
connected to FREE Smart, FREE Panel and FREE Evolution
Function libraries
Management of default function libraries and/or those created by the developer.
Any additional boards are managed by that developer.
Display variables graph
Debugging of variables by displaying their status in graphics-based format when the application is running
and connected to FREE Smart, FREE Panel and FREE Evolution
Reading / writing of variables.
The operating environment makes the following possible:
• Creation of special menus to be shown on the controller display.
• reading and writing BIOS parameters (parameters + I/O values)
• reading and writing parameters and variables defined by the developer in Applications linked to the
menu.
Online Help for programmers at all stages of the programme development process, accessible from the
work screen by simply pressing F1.
The entire help is also available in a printable pdf.
Baselines and Libraries ready for use for downloading from the web
ST
4
FBD
LD
IL
SFC
FREE Studio
Components
FREE Studio allows the developer to program in different work environments,
having releases at his disposal that are always updated with new functions
and optimizations, available in the dedicated area of the Eliwell site.
Baselines
Applications ready for use, in
compliance with the rules of
architecture, easily modified for all
requirements.
The applications and object libraries
will help to speed up your work even
more, making FREE Studio easier to
use.
Application
Device
Connection
User Interface
Simulation
Component for software
developers to allow them
to develop and modify
applications in the 5
standard programming
languages.
Component dedicated
to less skilled users for
the
management
of
parameters, application
downloads, field tests,
etc.
C o n f i g u r a t i o n
component for both field
and open networks, for
integration with other
systems.
Component
for
developing
and
customising the graphic
user interface.
Component
for
simulating the application
on a PC.
Installation and system requirements
Operating Systems
• Windows 10
• Windows 8, 8.1
• Windows 7 Home / Professional / Ultimate
Installation setup, software updates, reference libraries and documentation are also available from the
Restricted Area of the website eliwell.com once you have registered.
5
FREE Smart Models
The models are available as a DIN rail-mounted version (SMD with display,
SMC with no display) and in the compact 32x74 Eliwell (SMP) size for panelmounting.
Various expansion modules (SME) and terminals (SKP, SKW) are also
supplied for use in conjunction with the corresponding models in the FREE
Smart range.
All inputs and outputs are independent and configurable to maximise the
units’ adaptability to any system
SMD
SMC
SMP
FREE Smart 12...24V~ / 24VC /C indicates the presence of Real-Time Clock (RTC)
Digital
outputs
TRIAC
outputs
O.C. outputs:
PWM/PPM
dangerous
voltage
dangerous
voltage
safety extra low
voltage SELV
5
5
5
5
3
5
5
2
-
SME3200
SME3200000400 3
SME5500
SME5500000450 5
Model
SMP5500/C/S
SMP5500/C
SMD5500/C/S
SMD5500/C
SMD3600/C/S
SMC5500/C/S
SMC5500/C
Code
SMP5500050450
SMP5500010450
SMD5500050450
SMD5500010450
SMD3600050450
SMC5500050450
SMC5500010450
Analogue outputs
Digital
0..10V
outputs
Analogue
inputs
RS 485
O.C.
on
outputs board
safety extra low
voltage SELV
no voltage
safety extra low
voltage SELV
2
2
2
2
1
2
2
3
3
3
3
3
3
3
6
6
6
6
6
6
6
5
5
5
5
5
5
5
1
1
1
1
1
1
1
yes
yes
yes
yes
-
-
2
-
6
3
1
-
-
2
3
6
5
1
-
Expansion modules
FREE Smart 100...240V~ /C indicates the presence of Real-Time Clock (RTC); /S indicates integrated on-board RS485 serial port
O.C. outputs:
PWM / DI
Outputs
0..10V
safety extra low
voltage SELV
SMD4500/C/S SMD4500050H00 4
SMD4500/C
Analogue
inputs
safety extra low
voltage SELV
Outputs
4...20mA
0...20mA
safety extra low
voltage SELV
2
2
1
5
SMD4500010H00 4
2
2
1
5
SMC4500/C/S SMC4500050H00 4
2
2
1
5
2
2
1
5
Model
Code
Digital
outputs
dangerous voltage
Expansion module
SME4500
SME4500000H00 4
Terminals with power supply from the base
Analogue inputs
Model
Code
Installation
Dimensions
Display
SKP10
SKP100G000000
Panel
74x32x30 mm
LED / 4 digit
SKW22
SKW220G000000 Wall
137x96.5x31.3 mm LCD
1 integrated NTC
1 NTC/DI/4...20mA input
SKW22L
SKW22LG000000 Wall
137x96.5x31.3 mm Backlit LCD
1 integrated NTC
1 NTC/DI/4...20mA input
SKP22
SKP220G000000
Panel;
Wall: see
160x96x10mm
page 17 (accessories)
LCD
safety extra low voltage SELV
-
1 NTC input
1 NTC/DI/4...20mA input
KEY: SELV = Safety Extra Low Voltage; PPM = Pulse Position Modulation; PWM = Pulse Width Modulation; O.C. = Open Collector
Resources available - FREE Smart (model /C/S, msk 412)
•
FREE Studio installation setup
CPU
14.7 MHz
•
1 FREE Smart SMxxxx*
Available memory for Application
190 KByte
•
1 DMI 100-3 Manufacturer + yellow TTL cable
2300 Byte
•
1 optional MFK + blue TTL cable
•
FREE Smart* power cables and transformer
RAM memory - automatic mapping
6
Minimum kit for the developer - FREE Smart
The IEC programmer includes the following resources:
RAM memory - Modbus mapping
1024 Byte
EEPROM variables
1024 Byte
* alternatively, request the Demo Case
FREE Smart Connectivity
FREE Smart controllers are equipped with a serial port for easy integration
with the supervision systems of the plant in which they are installed.
ModBus standard protocol makes it possible to access all the controller
resources, thereby guaranteeing complete system control.
All models have TTL supplied as standard; /S models have an integrated
RS485 serial port.
SKW22(L)
A special firmware version also offers Modbus MASTER functions.
SKP22
SKP10
FREE Smart maximum configuration
•
•
•
•
•
Max 1 FREE Smart model
Max 1 SME expansion module via LAN serial port
Max 1 SKP10 terminal with controller ECHO function
Max 1 SKW22(L) or SKP22 terminal with dedicated menu, with the
possibility of monitoring the environment temperature and humidity
Maximum LAN distance: 100 m
FREE Smart Update Function
The Multi Function Key (MFK 100) can be used to upload and download the parameters map for rapid configuration,
to upload IEC and BIOS applications.
Multi Function Key / DMI
PC ÎÍFREE
USB
MFK
MFK
USB
FREE Smart
TT
TTL
DMI
use yellow TTL cable
for MFK - target connection
use blue TTL cable
for DMI - MFK connection
FREE Smart
use yellow TTL cable
for DMI - target connection
Direction
of download
Î
Í
Direction
of download
Î
Í
-
Parameters map
9
9
Parameters map
9
9
9
-
IEC application
9
-
IEC application
9
-
9
-
BIOS
9
-
BIOS
9
-
Î
Í
-
IEC application
BIOS
Parameters map
Network
PC ÎÍFREE
TTL
TT
TTL
DMI
Direction
of download
Multi Function Key
MFK ÎÍFREE
Example of connection in Modbus Slave or Master mode
Example of Modbus Slave
Example of Modbus Master
For models without RS485 use exclusively BusAdapter 150
7
SMP, SMD, SMC5500
SMP5500
SMD5500
SMC5500
Technical Data
SMP5500
SMD5500
SMC5500
format
32x74x80mm (Lxhxd)
4DIN
4DIN
display
LED 4 digits - 7 segments
LED 4 digits - 7 segments
-
power supply
12...24V~ / 24VC not insulated
12...24V~ / 24VC not insulated
12...24V~ / 24VC not insulated
relay digital outputs
5 x 2A 250V~
5 x 2A 250V~
5 x 2A 250V~
2 x O.C. PPM/PWM
2 x O.C. PPM/PWM
2 x O.C. PPM/PWM
3 x 0...10V
3 x 0...10V
3 x 0...10V
O.C. digital outputs
1 x Open Collector
1 x Open Collector
1 x Open Collector
digital inputs
6 voltage free
6 voltage free
6 voltage free
analogue outputs
3 x NTC/ D.I.
3 x NTC/ D.I.
3 x NTC/ D.I.
2 x NTC/ D.I. / 0...20mA /
4...20mA / 0-10V / 0-5V / 0-1V
2 x NTC/ D.I. / 0...20mA /
4...20mA / 0-10V / 0-5V / 0-1V
2 x NTC/ D.I. / 0...20mA /
4...20mA / 0-10V / 0-5V / 0-1V
TTL
TTL
TTL
RS485 (only /S models)
RS485
RS485 (only /S models)
connectivity
LAN for connection to SKP/SKW
terminal or to SME expansion
module
LAN for connection to SKP/SKW
terminal or to SME expansion
module
LAN for connection to SKP/SKW
terminal or to SME expansion
module
operating temperature
-20...+55°C
-20...+55°C
-20...+55°C
analogue inputs
Wiring, assembly and dimensional diagrams
6 .6
70.2mm
71mm
74mm
76mm
5.2mm
43.6mm
56.4mm
28mm
32mm
70.2mm
87mm
29mm
76mm
70mm
-
Dimensional diagrams
SMD, SMC, SME
5
+ G
6
7
9
8
10
11
12
RS-485
5 3 G 4
Supply
GND GND AI5
AI4
AI3
AI2
AI1
Supply
AO2 DI6
DI4
DI3
DI2
DI1
DI5
6
-
DO3
+ G
6
/S Models
only
AO
RED BLACK
BLUE
DO3
RS-485
/S Models
only
RED
BLUE
BLACK
4
G 3 5
AO
SMP5500/C - SMP5500/C/S
8
DI1
DI2
DI3
DI4
DI5
DI6 AO2
Supply
AI1
AI2
AI3
AI4
AI5 GND GND
Supply
SMD5500/C/S - SMC 5500/C - SMC5500/C/S
SMD3600, Expansion modules SME
SMD3600
SME3200
SME5500
Technical Data
SMD3600
SME3200
SME5500
format
4DIN
4DIN
4DIN
display
LED 4 digits - 7 segments
-
-
power supply
12...24V~ not insulated
12...24V~ / 24VC not insulated
12...24V~ / 24VC not insulated
relay digital outputs
3 x 2A 250V~
3 x 2A 250V~
5 x 2A 250V~
O.C. digital outputs
2 x TRIAC 3A250V~
1 x Open Collector PPM/PWM
3 x 0...10V
2 x Open Collector
1 x TRIAC 3A250V~
2 x Open Collector PPM/PWM
1 x Open Collector
1 x TRIAC 3A250V~
2 x Open Collector PPM/PWM
3 x 0...10V
1 x Open Collector
digital inputs
6 voltage free
6 voltage free
6 voltage free
3 x NTC/ D.I.
3 x NTC/ D.I.
3 x NTC/ D.I.
-
2 x NTC/ D.I. / 0...20mA /
4...20mA / 0-10V / 0-5V / 0-1V
analogue outputs
analogue inputs
2 x NTC/ D.I. / 0...20mA /
4...20mA / 0-10V / 0-5V / 0-1V
TTL
TTL
TTL
RS485
-
-
connectivity
LAN for connection to SKP/SKW
terminal or to SME expansion
module
LAN for connection to
FREE Smart
LAN for connection to
FREE Smart
operating temperature
-20...+55°C
-20...+55°C
-20...+55°C
Wiring diagrams
-
5
+ G
6
7
9
8
10
11
12
7
9
8
5
10
6
7
9
8
10
11
12
RS-485
DO3
DO3
RED
BLUE
RED
BLUE
RED
BLUE
BLACK
BLACK
BLACK
4
G 3 5
AO
4
DI1
DI2
DI3
DI4
DI5
DI6 DO4
Supply
DI1
DI2
DI3
DI4
DI5
AI1
AI2
AI3
AI4
AI5 GND GND
Supply
AI1
AI2
NC
NC
AI5 GND GND
SMD3600/C/S
6
SME3200
G 3 5
Supply
DI6 AO2
NC
Supply
AO
DI1
DI2
DI3
DI4
DI5
DI6 AO2
Supply
AI1
AI2
AI3
AI4
AI5 GND GND
Supply
SME5500
9
SMD, SMC4500, Expansion module SME4500
SMD4500
SMC4500
SME4500
Technical Data
SMD4500
SMC4500
SME4500
format
4DIN
4DIN
4DIN
display
LED 4 digits - 7 segments
-
-
power supply
100...240V~
100...240V~
100...240V~
relay digital outputs
4 x 2A 250V~
4 x 2A 250V~
4 x 2A 250V~
analogue outputs
2 x Open Collector PWM/D.I.
2 x 0...10V
1 x 4..20mA / 0…20mA
2 x Open Collector PWM/D.I.
2 x 0...10V
1 x 4..20mA / 0…20mA
2 x Open Collector PWM/D.I.
2 x 0...10V
1 x 4..20mA / 0…20mA
3 x NTC / Pt1000 / D.I.
3 x NTC / Pt1000 / D.I.
3 x NTC/ D.I.
2 x NTC/ D.I. / 0...20mA /
4...20mA / 0-10V / 0-5V / 0-1V
2 x NTC/ D.I. / 0...20mA /
4...20mA / 0-10V / 0-5V / 0-1V
2 x NTC/ D.I. / 0...20mA /
4...20mA / 0-10V / 0-5V / 0-1V
TTL
TTL
TTL
analogue inputs
RS485
RS485
-
connectivity
LAN for connection to SKP/SKW
terminal or to SME expansion
module
LAN for connection to SKP/SKW
terminal or to SME expansion
module
LAN for connection to FREE Smart
operating temperature
-20...+55°C
-20...+55°C
-20...+55°C
Wiring diagrams
-
+ G
RS-485
6
7
8
9
10
DI2 AO3 AO4 AO5
AI1
12
DO3
6
7
8
9
10
AI2
AI3
AI4
AI5
GND
DO3
100-240Vac
AO1 AO2
Supply Supply
DI1
SMD4500/C/S - SMC4500/C/S
10
6
11
12
BLACK RED
BLUE
BLACK RED
BLUE
AO1 AO2
DI1
11
DI2 AO3 AO4 AO5
6
100-240Vac
AI1
AI2
AI3
AI4
AI5
GND
Supply Supply
SME4500 expansion module
Interfaces, FREE Smart terminals
SKP10
SKW22/22L
SKP22
Technical Data
SKP10
SKW22 - SKW22L
SKP22
format (LxDxH)
74x32x30 mm
4DIN
4DIN
mounting
Panel
Wall
Panel
display
LED 4 digits - 7 segments
LCD
(model 22L: backlit LCD)
LCD
power supply
From base
From base
From base
-
1 x integrated NTC
1 x remote NTC
-
1 x NTC/ D.I. / 0...20mA / 4...20mA
remote
1 x NTC/ D.I. / 0...20mA / 4...20mA
remote
connectivity
LAN for connection to
FREE Smart
LAN for connection to
FREE Smart
LAN for connection to
FREE Smart
wiring
cable COLV000033200
Included in the package
cable COLV000033200
Included in the package
cable COLV000033200
Included in the package
operating temperature
-20...+55°C
-5...+60°C
-5...+60°C
-
KP100000 - not included
(see Accessories page)
-
analogue inputs
humidity module
Wiring and assembly diagrams
138
68
E
C
D
90
7
2. 6)
(x
to Smart
LAN
F
mm
84
B
A
150
Probe
30mm
29mm
70mm
SKW22(L)
30mm
possibilità di alimentare
il trasduttore mediante
il morsetto +12Vdc
black / GND
blue / signal
red /+12Vdc
red /+12Vdc
blue / signal
black / GND
28mm
74mm
32mm
Digital input
71mm
red /+12Vdc
Probe
GND +12V LAN
GND AIR1 AIR2
Probes
B
L
A
C
K
R
E
D
B
L
U
E
SKP22(L)
Ext. Transducer
Remote
Probe
PROBE NOT INCLUDED
SONDE NON INCLUSE
LAN
SKW22(L)
SKP 10
B
L
U
E
B
L
A
C
K
red /+12Vdc
green / signal
black / GND
AIR2
R
E
D
RH Sensor
SKP10
RH Optional Module
SKW22 - SWK22L
SKP22
11
FREE Panel models
FREE Panel (EVP) is the solution with LCD display that can be used as a
system controller, with gateway functions, used in association with other
FREE Evolution and FREE Smart or third-party controllers.
FREE Panel guarantees high performance in terms of memory, user interface,
Master/Slave connectivity as well as expandability (by CANbus ‘field’ up to
12 expansion modules), straightforward programming, maintenance, and
servicing.
A special backplate is available as an accessory for wall-mounting.
FREE Panel
FREE Panel /C indicates the presence of the RTC – Real Time Clock. /RH: humidity sensor
Model
Code
EVP3300/C
EVP3300010B00
Installation
Display
Panel
LCD
backlit
(for wall-mounting see
Accessories page)
Panel
EVP3300/C/RH EVP3500010B00
(for wall-mounting see
Accessories page)
LCD
backlit
Inputs
Serial
safety extra low voltage SELV
1 x NTC integrated;
1 x NTC remote;
1 x 4...20mA remote
1 x NTC integrated;
1 x NTC remote;
1 x integrated %RH
CANbus; RS485;
Ethernet
CANbus; RS485;
Ethernet
KEY: SELV = Safety Extra Low Voltage
USB-RS485; Ethernet
PC ÎÍFREE
Technical Data
EVP3300/C
EVP3300/C/RH
format
160x96x10mm
160x96x10mm
display
LCD graphic display 128x64px
backlit
LCD graphic display 128x64px
backlit
24V~/C - 48VC
AI1 1 x integrated NTC
AI2 1 x remote NTC / D.I.
AI3 1 x 4...20mA / 0-5V / 0-10V
remote
CANBus: CANopen
RS485: Modbus RTU, BACnet MSTP
Ethernet: Modbus TCP - BACnet IP - HTTP
24V~/C - 48VC
AI1 1 x integrated NTC
AI2 1 x remote NTC / D.I.
CANBus: CANopen
RS485: Modbus RTU, BACnet MSTP
Ethernet: Modbus TCP - BACnet IP - HTTP
-5...+55°C
-5...+55°C
power supply
analogue
inputs
connectivity
operating
temperature
USB
RS485
SB/RS48
USB/RS485
FREE Panel
Ethernet
FREE Panel
AI4 1 x integrated %RH
Data downloading
direction
Parameters map
IEC application
HMI application
Data files
BIOS
Commissioning
Î
Í
9
9
9
9
9
9
9
9
9
27
Wiring, assembly and connectivity diagrams
145
160
RS485 Modbus /CANopen®
Master
RS485 Modbus
R
1.
5
90
57
80
Ethernet
mm
90
83
59
CANopen®
24 Va/c
48 Vc
Remote
Probes
AI2 AI3 G
RS485
+
Ethernet
- GS
GS H
RS485
CAN
RTERM
EVP3300/C
EVP3500/C/RH
AI1
NTC Sensor Built-in
LAN
CAN
L POWER
Probes
Built-in
Remote
EVP3300 AI1
EVP3500 AI1
AI2
AI4
AI4
RH Sensor Built-in
EVP3300/C - EVP3300/C/RH
12
AI3
AI2
FREE Smart, FREE Panel and FREE Evolution connectivity
FREE Advance models
FREE Advance models (AVD with display, AVC without display) are
available in the 8 DIN rail-mounted version, with removable screw terminals
to make installation easier and faster.
Each AVD or AVC can be expanded by CANbus (field) up to 12 expansion
modules and 2 terminals (EVK). By CANbus (network) it is also possible to
connect up to 10 controllers to one another.
Up to 127 devices can be managed with the Modbus Master, by RS485.
FREE Advance
FREE Advance with or without display /C indicates the presence of the RTC – Real Time Clock; RS485 and CANbus
integrated as standard
Relay
outputs
Model
Code
AVC8400/C/L/U
AVD8400/C/L/U
AVD8400/C/L/U/SSR
AVC12600/C/L/U
AVC8400060500
AVD8400060500
AVD84SS060500
AVC1260060500
8
8
6
12
AVD12600/C/L/U
AVD1260060500
AVD12600/C/L/U/SSR AVD126S060500
12
10
SSR
Outputs
dangerous
voltage
2
2
Analogue outputs Digital inputs
Analogue
inputs
low voltage
SELV
safety extra low voltage SELV
Including 2 high-speed pulse /
frequency counters up to 2 kHz
4
4
4
6
8
8
8
12
8
8
8
12
6
6
12
12
12
12
safety extra low
voltage SELV
Expansion modules RS485 (only EVE7500) and CANbus integrated as standard
Model
Code
SSR
Outputs
Relay
outputs
dangerous
voltage
EVE7500
EVE7500000B00 7
EVE4200
EVE4200000500 4
*high-speed pulse/ frequency counter 1 kHz
-
Analogue outputs
Digital
inputs
Digital
inputs
Analogue
inputs
safety extra low
voltage SELV
no
voltage
safety extra low
voltage SELV
8
4
1*
-
6
4
safety extra low voltage SELV
A04/A05 configurable as Open
Collector 12VC 100mA max each
5
2
Terminals
Model
Code
Installation
EVK1000
Panel
EVK1000000B00 (for wall-mounting see
Dimensions
Display
Serial
160x96x10mm
Backlit LCD
CANBus
Accessories page)
Plug-in 2DIN models; power supply from the base AVD / AVC
Output
Model
Code
EVS RS232
EVS10R2000000 1 x SPDT 5A 250V~
Modbus ASCII
EVS RS485
EVS00R4000000 -
Modbus RTU
EVS CAN
EVS00CA000000 -
CANopen
EVS BACnet
EVS00BM000000 -
Connectivity protocol
dangerous voltage
Modbus RTU - BACnet MSTP
EVS LONWORKS EVS0LON000000 -
LON
KEY: SSR = Solid State Relay; SELV = Safety Extra Low Voltage
Resources Available - FREE Advance
Minimum kit for the developer - FREE Advance
The IEC programmer includes the following resources:
•
FREE Studio installation setup.
CPU
120MHz, 32MB RAM
•
1 FREE Advance AVD8400/C/L/U
1 MByte
•
Mini-USB cable for PC connection
1.5 MByte
•
Ethernet cable for network connection
8 MByte
•
FREE Advance power transformer
Available memory for Application
Available memory for User Interface
FLASH memory data
RAM memory - automatic mapping
RAM memory - Modbus mapping
EEPROM variables
512 KByte
5000 word
4000 word (application)
+ 10000 word (BACnet objects)
13
FREE Advance connectivity
FREE Advance models have ETHERNET and RS-485 and CANbus serials as standard. They can be integrated
into industrial systems and BMS and through the range of plug-ins and 2DIN modules that connect quickly and
intuitively to the main AVD/AVC module.
Ethernet (Modbus TCP, BACnet/IP, HTML5)
BACnet MS/TP, Modbus SL
LONwork, BACnet MS/TP, Modbus SL
CAN (Binding)
Expansion bus (CAN)
Modbus SL
Connectivity and functionality
Advance FREE controllers are equipped with advanced capabilities, incorporating Ethernet, Modbus
and BACnet IP protocols as standard, in addition to the optional LON protocol by plug-in.
Internet and integrated Web Server connection offer machine builders and system integrators complete
remote access, drastically reducing support and maintenance costs.
This is also beneficial for end users, who can control their system from multiple devices.
• Integrated WebServer
• Local and remote system control, including alarms management and e-mail notifications.
• Remote reading and support.
• Preventive and predictive maintenance.
• Next generation system interface on PC, Tablet and Smartphone
SD card Datalogging
SD card ÎÍFREE
USB Host
PC ÎÍFREE
Ethernet / USB Device / RS485
PC ÎÍFREE
Ethernet
FREE Advance
FREE Advance
FREE Studio
(3.5 or greater)
FREE Advance
RJ45
RJ45
USB cable
Micro
SD
OK
USB A
OK
RS485
Data downloading
direction
Parameters map
IEC application
HMI application
Data files
BIOS
14
Î
Í
-
9
-
-
Data downloading
direction
Parameters map
IEC application
HMI application
Data files
BIOS
Î
Í
9
9
9
9
9
9
9
9
9
-
Data downloading
direction
Parameters map
IEC application
HMI application
Data files
BIOS
USB mini-B
OK
RS485
Î
Í
9
9
9
9
9
9
9
9
9
-
AVD8400, AVD8400 SSR, AVC8400
AVD8400
AVD8400 SSR
AVC8400
Technical Data
format
display
power supply
digital outputs
analogue outputs
digital inputs
analogue inputs
connectivity
operating temperature
AVD8400
AVD8400 SSR
AVC8400
8DIN
128x64 pixel graphic LCD backlit
+24V~ not insulated
+20...+38VC not insulated
8: 7 x 3A, 1 x 1A 250V~
4: 2 x 0-10V, 2 x 0-10V /
4...20mA / ON-OFF / PWM /
O.C. 24VC 30mA max
6 x safety extra low voltage SELV
2 x pulse / frequency counter up to
2 kHz
8 x NTC 103AT / NTC NK103 / D.I. /
PTC KTY81 / Pt1000 / 0...20 mA /
4...20 mA / 0-10V / 0-5V
USB; 1 x plug-in EVS
ETHERNET: BACnet IP
CANBus: CANopen
2 x RS485: Modbus RTU
(including 1 x RS485: also BACnet
MS/TP)
-20...+60°C
8DIN
128x64 pixel graphic LCD backlit
+24V~ not insulated
+20...+38VC not insulated
6: 5 x 3A, 1 x 1A 250V~
SSR: 2 x 0.5A 240V~
4: 2 x 0-10V, 2 x 0-10V /
4...20mA / ON-OFF / PWM /
O.C. 24VC 30mA max
6 x safety extra low voltage SELV
2 x pulse / frequency counter up to
2 kHz
8 x NTC 103AT / NTC NK103 / D.I. /
PTC KTY81 / Pt1000 / 0...20 mA /
4...20 mA / 0-10V / 0-5V
USB; 1 x plug-in EVS
ETHERNET: BACnet IP
CANBus: CANopen
2 x RS485: Modbus RTU
(including 1 x RS485: also BACnet
MS/TP)
-20...+60°C
8DIN
+24V~ not insulated
+20...+38VC not insulated
8: 7 x 3A, 1 x 1A 250V~
4: 2 x 0-10V, 2 x 0-10V /
4...20mA / ON-OFF / PWM /
O.C. 24VC 30mA max
6 x safety extra low voltage SELV
2 x pulse / frequency counter up to
2 kHz
8 x NTC 103AT / NTC NK103 / D.I. /
PTC KTY81 / Pt1000 / 0...20 mA /
4...20 mA / 0-10V / 0-5V
USB; 1 x plug-in EVS
ETHERNET: BACnet IP
CANBus: CANopen
2 x RS485: Modbus RTU
(including 1 x RS485: also BACnet
MS/TP)
-20...+60°C
Wiring and assembly diagrams
mm
in
A
110
4.33
AC
VDC
POWER
+
SUPPLY
24 Va/c
DO1
C1
DO2
C2
C34
DO3
DO4
C567
DO5
DO7
DO8
DO8-
C8
AC
VDC
POWER
+
SUPPLY
24 Va/c
DO1
C1
DO2
C2
C34
DO3
DO4
C567
DO5
DO6
DO7
DO8
C8
DO8-
AVD8400 SSR:
SSR Outputs
FREE ADVANCE
144
5.67
49
1.93
11
0.43
76
2.99
45
1.77
3
DO6
2
75
2.95
1
A
A
A
CN6
CN9
CN8
CN7
CN10
CN6
CN7
CN9
CN8
CN10
OK
AI8
24Vdc
5Vdc
AI7
GND
AI6
AI5
AI4
AI3
AI2
AI1
DI8
DI7
DI6
DI5
DI4
DI3
AO4
AO3
AO2
AO1
GND
+
GND
GND
+
-
GND
H
L
24Vdc
AI8
5Vdc
AI7
GND
AI6
AI5
AI4
AI3
AI2
AI1
DI8
DI7
DI6
DI5
DI4
CN5
AVD8400 - AVD8400 SSR
+5V
+24V
24 Va/c +
24 Va/c +-
RS485-2
RS485-1
CAN
+5V
+24V
24 Va/c +
24 Va/c +-
RS485-2
RS485-1
B
CAN
B
CN4
COM-DI
CN3
CN2
DI2
CN1
DI1
CN19
COM-DI
CN18
CN5
B
DI3
AO4
AO3
AO2
AO1
GND
+
GND
GND
+
-
GND
H
L
CN4
COM-DI
CN3
CN2
DI2
CN1
DI1
CN19
COM-DI
CN18
B
AVC8400
15
AVD12600, AVD12600 SSR, AVC12600
AVD12600
AVD12600 SSR
AVC12600
Technical Data
format
display
power supply
digital outputs
analogue outputs
digital inputs
analogue inputs
connectivity
operating temperature
AVD12600
AVD12600 SSR
AVC12600
8DIN
128x64 pixel graphic LCD backlit
+24V~ not insulated
8DIN
128x64 pixel graphic LCD backlit
+24V~ not insulated
8DIN
+24V~ not insulated
+20...+38VC not insulated
12: 10 x 3A, 2 x 1A 250V~
6: 4 x 0-10V, 2 x 0-10V / 4...20mA /
ON-OFF / PWM / O.C. 24VC 30mA max
10 x safety extra low voltage SELV
2 x pulse / frequency counter up to
2 kHz
12 x NTC 103AT / NTC NK103 /
D.I. / PTC KTY81 / Pt1000 / 0...20 mA /
4...20 mA / 0-10V / 0-5V
USB; 1 x plug-in EVS
ETHERNET: BACnet IP
CANBus: CANopen
2 x RS485: Modbus RTU
(including 1 x RS485: also BACnet
MS/TP)
-20...+60°C
+20...+38VC not insulated
10: 8 x 3A, 2 x 1A 250V~
SSR: 2 x 0.5A 240V~
6: 4 x 0-10V, 2 x 0-10V / 4...20mA /
ON-OFF / PWM / O.C. 24VC 30mA max
10 x safety extra low voltage SELV
2 x pulse / frequency counter up to
2 kHz
12 x NTC 103AT / NTC NK103 /
D.I. / PTC KTY81 / Pt1000 / 0...20 mA /
4...20 mA / 0-10V / 0-5V
USB; 1 x plug-in EVS
ETHERNET: BACnet IP
CANBus: CANopen
2 x RS485: Modbus RTU
(including 1 x RS485: also BACnet
MS/TP)
-20...+60°C
+20...+38VC not insulated
10: 8 x 3A, 2 x 1A 250V~
6: 4 x 0-10V, 2 x 0-10V / 4...20mA /
ON-OFF / PWM / O.C. 24VC 30mA max
10 x safety extra low voltage SELV
2 x pulse / frequency counter up to
2 kHz
12 x NTC 103AT / NTC NK103 /
D.I. / PTC KTY81 / Pt1000 / 0...20 mA /
4...20 mA / 0-10V / 0-5V
USB; 1 x plug-in EVS
ETHERNET: BACnet IP
CANBus: CANopen
2 x RS485: Modbus RTU
(including 1 x RS485: also BACnet
MS/TP)
-20...+60°C
Wiring and assembly diagrams
mm
in
2
110
4.33
AC
VDC
POWER
+
SUPPLY
24 Va/c
DO1
C1
DO2
C2
C34
DO3
DO4
C567
DO5
DO6
CN10
24Vdc
+24V
AI12
AI11
5Vdc
GND
AI10
AI9
CN13
DI12
DI11
DI10
DI9
D
COM-DI
GND
AO5
AO6
CN12
+5V
CN11
C
CN9
CN8
C91011
DO9
C12
C
24Vdc
AI12
AI11
5Vdc
GND
AI10
AI9
DI12
DI11
DI10
DI9
COM-DI
GND
AO5
AO6
D
C
CN7
DO10
CN6
A
CN13
DO11
CN12
DO12-
CN11
CN10
DO12
CN9
CN8
C91011
DO9
DO10
CN7
DO11
DO12-
C12
DO12
CN6
D
B
24 Va/c
24 Va/c +
24Vdc
AI8
+5V
+24V
AI7
5Vdc
GND
AI6
AI5
AI4
AI3
AI2
AI1
DI8
DI7
CN5
DI6
DI5
DI4
DI3
COM-DI
CN4
DI2
AO4
AO3
DI1
24 Va/c +-
AO2
AO1
COM-DI
CN3
CN2
GND
+
GND
GND
CN1
RS485-2
RS485-1
+
-
CN19
GND
B
H
AI8
24Vdc
AI7
5Vdc
+5V
+24V
AI6
GND
AI5
AI4
AI3
AI2
AI1
DI8
DI7
24 Va/c +
AVD12600 - AVD12600 SSR
CN15
CN18
CN5
DI6
DI5
DI4
DI3
COM-DI
CN4
DI2
AO4
AO3
DI1
24 Va/c +-
AO2
AO1
COM-DI
CN3
CN2
GND
+
GND
GND
CN1
RS485-2
RS485-1
+
-
CN19
GND
H
CAN
B
L
CN18
CN14
L
+ 24 Va/c
CAN
CN15
+24V
CN14
+ -
B
+5V
D
16
DO7
A
A
OK
DO8
C8
A
C
DO8-
AC
VDC
POWER
+
SUPPLY
24 Va/c
DO1
C1
DO2
C2
C34
DO3
DO4
C567
DO5
DO6
DO7
DO8
C8
DO8-
AVD12600 SSR:
SSR Outputs
FREE ADVANCE
144
5.67
49
1.93
11
0.43
76
2.99
45
1.77
3
75
2.95
1
AVC12600 SSR
FREE Evolution models
FREE Evolution models (EVD with display, EVC without display) are
available in the 8 DIN rail-mounted version, with removable screw terminals
to make installation easier and faster.
Each EVD or EVC can be expanded by CANbus (field) up to 12 expansion
modules and 2 terminals (EVK). By CANbus (network) it is also possible to
connect up to 10 controllers to one another.
Up to 127 devices can be managed with the Modbus Master, by RS485.
FREE Evolution
FREE Evolution with or without display /C indicates the presence of the RTC – Real Time Clock; RS485 and CANbus
integrated as standard
Model
Code
Relay
outputs
SSR
Outputs
Analogue outputs
dangerous
voltage
EVD7500/C/U EVD7500060B00 7
EVD75SS/C/U EVD75SS060B00 5
EVC7500/C/U EVC7500060B00 7
*Fast counter 1KHz
2
-
Digital
inputs
Digital
inputs
Analogue
inputs
safety extra low
voltage SELV
no
voltage
safety extra low
voltage SELV
8
8
8
1*
1*
1*
6
6
6
Digital
inputs
Digital
inputs
Inputs
inputs
safety extra low
voltage SELV
no
voltage
safety extra low
voltage SELV
8
4
1*
-
6
4
safety extra low voltage SELV
A04/A05 configurable as Open
Collector 12VC 100mA max each
5
5
5
Expansion modules RS485 (only EVE7500) and CANbus integrated as standard
Model
Code
Relay
outputs
SSR
Outputs
Analogue outputs
safety extra low voltage SELV
A04/A05 configurable as Open
Collector 12VC 100mA max each
dangerous
voltage
EVE7500
EVE7500000B00 7
EVE4200
EVE4200000500 4
*Fast counter 1KHz
-
5
2
Terminals
Model
Code
Installation
EVK1000
Panel
EVK1000000B00 (for wall-mounting see
Dimensions
Display
Serial
160x96x10mm
Backlit LCD
CANBus
Accessories page)
Plug-in 2DIN models; power supply from the base EVD / EVC
Output
Model
Code
EVS RS232
EVS10R2000000 1 x SPDT 5A 250V~
Modbus ASCII
EVS RS485
EVS00R4000000 -
Modbus RTU
EVS CAN
EVS00CA000000 -
CANopen
EVS ETH
EVS00ET000000 -
Modbus TCP - BACnet IP - HTTP
EVS Profibus
EVS00PB000000 -
Profibus DP Slave-V0
EVS Bacnet
EVS00BM000000 -
Modbus RTU - BACnet MSTP
dangerous voltage
Connectivity protocol
EVS ETH/RS485 EVS00EB000000 -
Modbus RTU - BACnet MSTP - Modbus TCP - BACnet IP - HTTP
EVS LONWORKS EVS0LON000000 -
LON
KEY: SSR = Solid State Relay; SELV = Safety Extra Low Voltage
Resources available - FREE Panel, FREE Evolution
Minimum kit for the developer - FREE Evolution
The IEC programmer includes the following resources:
•
FREE Studio installation setup.
CPU
72 MHz, 32MB RAM
•
1 FREE Evolution EVD7500/C/U
1 MByte
•
USB/RS485 converter or Ethernet plug-in for PC
connection
•
FREE Evolution power transformer
Available memory for Application
Available memory for User Interface
1.5 MByte
FLASH memory data
128 MByte
RAM memory - automatic mapping
512 KByte
RAM memory - Modbus mapping
EEPROM variables
5000 word
4000 word (application)
+ 10000 word (BACnet objects)
17
FREE Evolution connectivity
FREE Evolution models have RS-485 and CANbus serials integrated as standard. They can be integrated into
industrial systems, BMS and Ethernet networks through the range of plug-ins and 2DIN modules that connect
quickly and intuitively to the main EVD/EVC module.
http:
http
ftp:
RS 232
RS 485 Modbus
Ethernet Modbus TCP
Webserver
Profibus
BACnet
bridge
RS 485 Modbus
CANopen®
CANopen®
Ethernet Modbus TCP
RS 485 Modbus
LAN
WEB functionalities
FREE Evolution and FREE Panel are WEB-enabled, giving machine manufacturers and system integrators
integral remote access.
Having a web-based connection in machines significantly reduces support and maintenance costs.
This is also beneficial for end users, who can control their system from multiple devices.
• Web-based access.
• Remote reading and support.
• Local and remote system control, including alarms management.
• Preventive and predictive maintenance.
• Email alarm alerts.
• Next generation system interface on PC, Tablet and Smartphone
USB Host
USB ÎÍFREE
Data downloading
direction
Parameters map
IEC application
HMI application
Data files
BIOS
Commissioning
18
Î
Í
9
9
9
9
9
-
9
9
9
9
-
USB Device
PC ÎÍFREE
Data downloading
direction
Parameters map
IEC application
HMI application
Data files
BIOS
Commissioning
USB-RS485 / Ethernet + Plugin
PC ÎÍFREE
Î
Í
9
9
9
9
9
9
9
9
Data downloading
direction
Parameters map
IEC application
HMI application
Data files
BIOS
Commissioning
Î
Í
9
9
9
9
9
9
9
9
9
EVD7500, EVD75SS, EVC7500
EVD7500
EVD75SS
EVC7500
Technical Data
format
display
power supply
digital outputs
analogue outputs
digital inputs
analogue inputs
connectivity
operating temperature
EVD7500
EVD75SS
EVC7500
8DIN
128x64 pixel graphic LCD backlit
24V~/C - 48VC
7: 2 x 8A, 5 x 5A 250V~
5 x 0-10V / 4...20mA /
(switch 0..20mA)
A04/A05 configurable as O.C.
12VC 100mA max each
8 safety extra low voltage SELV
1 x Fast voltage-free counter 1KHz
2 x NTC 103AT / NTC NK103 / DI
8DIN
128x64 pixel graphic LCD backlit
24V~/C - 48VC
5: 2 x 8A, 3 x 5A 250V~
SSR: 2 x 1A 250V~
5 x 0-10V / 4...20mA /
(switch 0..20mA)
A04/A05 configurable as O.C.
12VC 100mA max each
8 safety extra low voltage SELV
1 x Fast voltage-free counter 1KHz
2 x NTC 103AT / NTC NK103 / DI
8DIN
24V~/C - 48VC
7: 2 x 8A, 5 x 5A 250V~
5 x 0-10V / 4...20mA /
(switch 0..20mA)
A04/A05 configurable as O.C.
12VC 100mA max each
8 safety extra low voltage SELV
1 x Fast voltage-free counter 1KHz
2 x NTC 103AT / NTC NK103 / DI
4 x NTC 103AT / NTC NK103 / DI /
Pt1000 / 4...20 mA / 0-10V / 0-5V
4 x NTC 103AT / NTC NK103 / DI /
Pt1000 / 4...20 mA / 0-10V / 0-5V
4 x NTC 103AT / NTC NK103 / DI /
Pt1000 / 4...20 mA / 0-10V / 0-5V
USB; 1 x Plug-in EVS
CANBus: CANopen
RS485: Modbus RTU
-10...+55°C
USB; 1 x Plug-in EVS
CANBus: CANopen
RS485: Modbus RTU
-10...+55°C
USB; 1 x Plug-in EVS
CANBus: CANopen
RS485: Modbus RTU
-10...+55°C
Wiring and assembly diagrams
DIGITAL INPUTS
12.55mm
RS485
RS485
H L
CAN
DI 1 DI2 DI3 DI4 C1-4 DI5 DI6 DI7 DI8 C5-8
DIGITAL INPUT
POWER
OUT
+
4 3 2 1
ON
ON
5Vout 12Vout
G AI1 AI2 AI3 AI4 AI5 AI6
ANALOGUE INPUT
4 DIP SWITCH
G
5Vout 12Vout
10 9 8 7 6 5 4 3 2 1
EVS
Plugin
PLUG-IN
Connector
PLUG-IN
Connector
6 5 4 3 2 1
ON
ON
10 DIP SWITCH
6 DIP SWITCH
mini
USB
mini
USB
FDI G
FDI G
ANALOGUE
OUTPUTS
4 DIP SWITCH
USB
USB
EVS
Plugin
POWER
OUT
+
4 3 2 1
G
H L
CAN
+
+
+
G AI1 AI2 AI3 AI4 AI5 AI6
ANALOGUE INPUT
GS
+5V +12V
+5V +12V
+
+
- +
RS485
ANALOGUE INPUTS
ANALOGUE INPUTS
+
GS
R TERM
GS
CAN
R TERM
- +
RS485
R TERM
GS
POWER
[Ext. Keyboard EVK]
+ 24 Va/c
48 Vc
-
CAN
R TERM
DI 1 DI2 DI3 DI4 C1-4 DI5 DI6 DI7 DI8 C5-8
DIGITAL INPUT
EVS
DIGITAL INPUTS
24 Va/c 48 Vc +
[Ext. Keyboard EVK]
+ 24 Va/c
48 Vc
-
EVD/EVC
140mm
POWER
24 Va/c 48 Vc +
76mm
45mm
41.8mm
110mm
71.2mm
24.25mm
FAST DIGITAL INPUT
AO1 G
AO1
AO2 G AO3 G
AO2
AO3
AO4 G AO5 G
AO4
AO5
ANALOGUE
OUTPUTS
FAST DIGITAL INPUT
AO1 G
AO1
AO2 G AO3 G
AO2
AO3
AO4 G AO5 G
AO4
12Amax
12Amax
C1 DO1 DO1 C2 DO2 DO2 DO3 DO4 C34 DO5 DO6 DO7 C567
DIGITAL OUTPUTS
AO5
24 Va/c
48 Vc
POWER IN
EVD7500 - EVD75SS
C1 DO1 DO1 C2 DO2 DO2 DO3 DO4 C34 DO5 DO6 DO7 C567
DIGITAL OUTPUTS
24 Va/c
48 Vc
POWER IN
EVC7500
19
Expansion modules EVE, Terminal EVK,
Plugin EVS
EVE7500
EVE4200
EVK1000
EVS
Technical Data
EVE7500
EVE4200
EVK1000
EVS
format
8DIN
4DIN
160x96x10mm
mounting
on DIN rail
on DIN rail
panel-mounted (for wall-mounting
see Accessories page)
display
power supply
24V~/c - 48Vc
2 x 8A 250V~
5 x 5A 250V~
5 x 0-10V / 4..20mA / switch 0..20mA
8 safety extra low voltage SELV
1 x Fast voltage-free counter 1KHz
24V~/c not insulated
1 x 5A 250V~
3 x 3A 250V~
2 x 0-10V
Backlit LCD
12...24V~ / 24Vc
see
table
pg. 13
(FREE
Advance)
pg. 17
(FREE
Evolution)
4 safety extra low voltage SELV
-
2 x NTC 103AT / NTC NK103 / DI
4 x NTC 103AT / NTC NK103 /
DI / Pt1000 / PTC / 4...20 mA /
0-10V / 0-5V
-
CANBus*: CANopen
-
CANBus: CANopen
-
*CANbus / TTL not insulated
-
-10...+55°C
-5...+55°C
digital outputs
analogue outputs
digital inputs
analogue inputs
connectivity
operating temperature
4 x NTC 103AT / NTC NK103 / DI /
Pt1000 / 4...20 mA / 0-10V / 0-5V
CANBus: CANopen
RS485: Modbus RTU
1 x EVS Plugin
(solo EVS RS485, EVS CAN)
-10...+55°C
-
Wiring, assembly and dimensional diagrams
2
1
DIGITAL INPUTS
3
POWER
24 Va/c 48 Vc +
1
[Ext. Keyboard EVK]
+ 24 Va/c
48 Vc
-
RS485
4
6 .6
CAN
70.2mm
GS
H L
CAN
POWER
OUT
87mm
- +
RS485
R TERM
GS
R TERM
DI 1 DI2 DI3 DI4 C1-4 DI5 DI6 DI7 DI8 C5-8
DIGITAL INPUT
ANALOGUE INPUTS
+5V +12V
+
+
4 3 2 1
ON
G AI1 AI2 AI3 AI4 AI5 AI6
ANALOGUE INPUT
G
5Vout 12Vout
4 DIP SWITCH
ON
GS
EVS Plugin
(Supported
models:
EVS RS485,
EVS CAN)
PLUG-IN
Connector
4
6 5 4 3 2 1
10 9 8 7 6 5 4 3 2 1
10 DIP SWITCH
3
2
H
L
7
6
5
4
DO4
DO3
DO2
3
2
1
1
4 DIP SWITCH
ON
ON
5.2mm
43.6mm
56.4mm
+
6 DIP SWITCH
CAN
MAX. 10A
+
N
DO1
FDI G
ANALOGUE
OUTPUTS
FAST DIGITAL INPUT
AO1 G
AO1
AO2 G AO3 G
AO2
AO3
AO4 G AO5 G
AO4
AO5
12Amax
Power Out
c 5V: 20 mA
c 24V: 50 mA
Power Supply
z 24V
C1 DO1 DO1 C2 DO2 DO2 DO3 DO4 C34 DO5 DO6 DO7 C567
DIGITAL OUTPUTS
EVE7500
20
24 Va/c
48 Vc
POWER IN
+
—
GND AI1 AI2 AI3 AI4
c
c
GND AO1 AO2 DI1 DI2 DI3 DI4 Com
+5V +24V
EVE4200
Accessories
In association with FREE Smart, FREE Panel and FREE Evolution Eliwell
supplies a wide range of accessories, from the protected transformer to
IP68 temperature probes, pressure/ratiometric transducers and pressure
switches.
EVP / EVK backplates
Single-phase (with a current from 2 to 9A) and three-phase fan modules are
also available.
The connection of ratiometric pressure sensors, external modules
(e.g. fan modules) and terminals does not require the use of any other
serial interfaces.
Pressure
transducers
Converter
USB/RS485
DMI
Code
Description
Details
USB/485 MINI KIT converter
USB/CAN converter
Interface module DMI100-3 Manufacturer
MFK: programming key for uploading/downloading parameters,
applications
FREE Evolution / FREE Advance
FREE Smart only
COLV0000E0100
COLV000035100
COLV000042100
Wiring for I/O connection - safety extra low voltage SELV - 1 m cable
Wiring RS485
Wiring AO3-4-5 - cable 1m
FREE Smart only 12...24V
FREE Smart only 12...24V
FREE Smart only 12...24V
BA10000R3700
BusAdapter 150 TTL-RS485
FREE Smart only
Converters, interfaces, programming keys
SAR0RA00X701
EVA00USCA0000
DMI1003002000
MFK100T000000
FREE Smart only
Wiring
Connectivity
Backplates
EVA00WMRC0000 White backplate kit (4 pcs) for wall mounting.
For EVP/EVK
EVA00WMRC0001 Black backplate kit (4 pcs) for wall mounting.
For EVP/EVK
KP100000
%RH Humidity module
For SKW terminal
VAL00031K
Demo Case for FREE Smart
-
VAL00033K
Demo Case for FREE Evolution
-
SN8DED11502C0
SN8DAE11502C0
SN9DAE11502C6
SN9DED11502C6
NTC 103AT 5X20 1.5m TPE IP68
NTC 103AT 6X20 1.5m TPE IP68
Pt1000 6X20 1.5m IP68
Pt1000 5X20 1.5m IP68
FREE Smart 4500 / FREE
Evolution / FREE Advance
TF411205
230V~/12V 6VA transformer (protected)
FREE Smart only
TF411210
230V~/12V 11VA transformer (protected)
FREE Smart only
TF111211
220V~/24V-24V 16VA transformer
FREE Smart only
TF111202
230V~/24V 25VA transformer
FREE Evolution only
TF111205
230V~/24V 35VA transformer. Mounting on DIN rail
FREE Evolution / FREE Advance
TD220050
TD220007
TD320050
TD320007
EWPA050 4…20mA / 0...667 psi / 0..50bar IP54** 2m cable
EWPA007 4…20mA / -7...101.5 psi /-0.5..7bar IP54** 2m cable
EWPA050 4…20mA / 0...667 psi / 0..50bar IP54** 2m cable
EWPA007 4…20mA / -7...101.5 psi / -0.5..7bar IP54** 2m cable
1/4 SAE MALE
1/4 SAE MALE
1/4 SAE FEMALE
1/4 SAE FEMALE
TD420010
TD420030
TD420050
EWPA 010 R 0...145 psi / 0...10bar IP67 2m cable (Packard connector)
EWPA 030 R 0...508 psi / 0...30bar IP67 2m cable (Packard connector)
EWPA 050 R 0...667 psi / 0...50bar IP67 2m cable (Packard connector)
Female connector
Female connector
Female connector
EXP11 250V 10A expansion module with DIN rail-mounted base
CFS05 TANDEM TRIAC 5+5A 250V
CFS - Single-phase speed regulators for currents from 2A to 9A
Open Collector Output
Various codes available
Humidity module
Demo Case
Temperature probes*
Transformers
Pressure transducers
Ratiometric transducers
Expansion modules, fan modules
MW320100
MW991012
CFS modules
KEY: SELV = Safety Extra Low Voltage
*different cable lengths available on request **version IP67 with optional Packard connector
21
Eliwell Controls Srl
Via dell’Industria, 15 Z. I. Paludi
32010 Pieve d’Alpago (BL) - ITALY
+39 0437 986 111
Sales
+39 0437 986 100 (Italy)
+39 0437 986 200 (other countries)
[email protected]
Technical support
+39 0437 986 250
[email protected]
CT123302 - EN - rel. 02/16
© Copyright Eliwell Controls s.r.l. 2016 - All rights reserved
Follow us on
www.eliwell.com
For more than 35 years, Eliwell has been offering control systems and services for refrigeration and air conditioning units, both
commercial and industrial, with highly innovative and technologically advanced products. Eliwell is part of Schneider Electric.
Subscribe to our newsletter on the site www.eliwell.com.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project