Sprecher+Schuh CEP7 DNCT DeviceNet Configuration Terminal User Manual
The CEP7 DNCT is a handheld device used to commission, configure, program, and monitor other devices on a DeviceNet network. The CEP7 DNCT can also upload, store, and later download complete device configurations including DeviceLogix programs via the network. It also presents DeviceNet physical layer diagnostics and network bandwidth statistics to the user.
Advertisement
Advertisement
DeviceNet™ Configuration
Terminal
CEP7-DNCT DeviceNet™
Configuration Terminal
User Manual
ii
Important User
Information
DeviceNet™ Configuration Terminal
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Rockwell Automation publication SGI-1.1, Safety Guidelines for the Application, Installation and
Maintenance of Solid-State Control (available from your local Sprecher + Schuh distributor), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss
Attention statements help you to:
• identify a hazard
• avoid a hazard
• recognize the consequences
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
European
Communities (EC)
Directive
Compliance
If this product has the CE mark, it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
• EMC Directive
• This product is tested per EN61000-6-4:2001 and EN61000-6-2:2005.
Sprecher + Schuh is a trademark of Rockwell Automation. DeviceNet™ is a trademark of the Open
DeviceNet™ Vendors Association (ODVA). All other trademarks and/or registered trademarks are the
DeviceNet™ Configuration Terminal property of their respective owners.
Manual
Objectives
iii
The purpose of this manual is to provide you with the information necessary to apply the DeviceNet™
Configuration Terminal. Described in this manual are methods for installing, configuring, and troubleshooting the DeviceNet™ Configuration Terminal.
Who Should Use
This Manual
Vocabulary
Reference
Manuals
IMPORTANT
Read this manual in its entirety before installing, operating, servicing, or initializing the DeviceNet™ Configuration
Terminal.
This manual is intended for qualified personnel responsible for setting up and servicing DeviceNet™ devices. You must have previous experience with and a basic understanding of communications terminology, configuration procedures, required equipment, and safety precautions.
You should understand DeviceNet™ network operations, including how devices operate on the network.
In this manual we refer to the:
• CEP7 DeviceNet™ Configuration Terminal as CEP7-DNCT, DNCT, terminal, Configuration
Terminal, or HIM (Human Interface Module)
• Programmable Logic Controller as a Programmable Controller, PLC controller, SLC controller,
ControlLogix Controller, or PLC
• DeviceNet™ as DNet or DNET
DeviceNet™ Media Design and Installation Guide
• Publication DNET-UM072_-EN-P
IMPORTANT
Read the DeviceNet™ Media Design and Installation
Guide (Publication DNET-UM072_-EN-P) in its entirety before planning and installing a DeviceNet™ system. If the network is not installed according to this document, unexpected operation and intermittent failures may occur.
If this manual is not available, please contact either the local Rockwell Automation distributor or Sales
Office and request a copy. Copies of this and all other reference publications may also be viewed electronically and downloaded from the Automation Bookstore at http:// www.theautomationbookstore.com.
iv
Notes:
DeviceNet™ Configuration Terminal
Table of Contents
Chapter 1 — Product
Overview
Chapter 2 —Installation and Wiring
Product Overview .................................................................................................. 1-1
Bill of Material ........................................................................................................1-1
Accessories ............................................................................................................1-1
Installation and Wiring ........................................................................................... 2-1
CEP7-CB1 Physical Connections .......................................................................... 2-1
CEP7-CM1 Physical Connections .......................................................................... 2-1
CEP7-DNCT-BZ1 Physical Connections ............................................................... 2-2
Powering the CEP7-DNCT..................................................................................... 2-2
Chapter 3 — Physical
Features 3-1
Chapter 5 — Device
Choices Menu
Chapter 6 — Parameter
Choices Menu
Physical Features .................................................................................................... 3-1
Communication Port ............................................................................................... 3-1
Key Descriptions .....................................................................................................3-2
Shifted Key Descriptions ........................................................................................ 3-2
Chapter 4 — Quick Start
Powerup .................................................................................................................. 4-1
Terminal Setup........................................................................................................ 4-2
Network Who Screen ..............................................................................................4-2
Device Choices Menu .............................................................................................4-2
Parameter Monitoring and Editing ......................................................................... 4-3
DeviceNet™ Configuration Terminal Setup Menus .............................................. 4-4
Device Choices Menu ............................................................................................. 5-1
Version Screen ........................................................................................................ 5-1
Parameter Choices Menu ........................................................................................ 6-1
Groups Screen......................................................................................................... 6-1
Num List Selection ................................................................................................. 6-2
Parameter Edit Screens ........................................................................................... 6-2
Numeric Parameters................................................................................................ 6-2
Accessing a Different Parameter ............................................................................ 6-3
Changing a Parameter Value .................................................................................. 6-3
Enumerated Parameters .......................................................................................... 6-4
Floating Point Parameters ....................................................................................... 6-5
Search for Changed Parameters .............................................................................. 6-6
Chapter 7 — Copy Cat
Menu
Copy Cat ................................................................................................................. 7-1
Copy Cat Uploading ............................................................................................... 7-2
Copy Cat Downloading .......................................................................................... 7-3
Copy Cat Downloading and Product Revisions ..................................................... 7-5
Copy Cat Downloading and Product Current Ratings............................................ 7-6
Deleting Copy Cat Files ..........................................................................................7-7
Copy Cat Memory .................................................................................................. 7-7
Page v
vi
Chapter 8 — Tools Menu
Tools Menu ............................................................................................................. 8-1
Node Commissioning .............................................................................................8-1
Class Instance Attribute Editor ............................................................................... 8-1
Graph Setup Screens ............................................................................................... 8-2
Graph View Screen ................................................................................................. 8-3
Chapter 9 — Advanced
Functions Menu
Chapter 10 — I/O
Message Monitoring
Chapter 11 —
DeviceLogix™
Functionality
Advanced Functions Menu ..................................................................................... 9-1
I/O Message Monitoring ....................................................................................... 10-1
DeviceLogix™ Functionality ...............................................................................11-1
DeviceLogix™ Choices Menu ............................................................................. 11-1
DeviceLogix™ Monitor........................................................................................ 11-1
Boolean Gates: AND, OR, XOR, NAND, NOR, NXOR and NOT .......................11-2
Bistable Latches: RS Latch and SR Latch .............................................................11-2
Counters: Up Counter and Up/Down Counter .......................................................11-2
Timers: On Delay, Off Delay and Pulse Timer ......................................................11-2
Discrete Output Points (DOPs):.............................................................................. 11-3
Produced Network Bits (PNBs):............................................................................. 11-3
DeviceLogix™ Editor........................................................................................... 11-3
Creating a New Function Block............................................................................ 11-4
Assigning Source Bits to Function Block Inputs.................................................. 11-5
Assigning Source Bits for Discrete Outputs Points (DOPs)................................ 11-6
Assigning Source Bits for Produced Network Bits (PNBs) ................................. 11-8
DeviceLogix™ Delete Function ........................................................................... 11-9
DeviceLogix™ Enable/Disable Function ............................................................. 11-9
Forcing Inputs and Outputs................................................................................... 11-9
Chapter 12 — Discrete I/
O Status
Discrete I/O Status ................................................................................................ 12-1
Chapter 13 — Zone
Interlock Protocol (ZIP)
Chapter 14 —
DeviceNet™ Scanner
Menu
Zone Interlock Protocol (ZIP)............................................................................... 13-1
ZIP Consumed ...................................................................................................... 13-1
Mapping Consumed ZIP Data .............................................................................. 13-2
ZIP Produced Data................................................................................................ 13-5
ZIP Data Table Monitor ........................................................................................13-5
DeviceNet™ Scanner Menu .................................................................................14-1
Scanner Setup ....................................................................................................... 14-1
AutoScan Function ............................................................................................... 14-2
ScanList Screen..................................................................................................... 14-2
Node Activation Screen ........................................................................................ 14-2
Chapter 15 — Terminal
Choices Menu
Chapter 16 — Terminal
Setup Menu
vii
Terminal Choices Menu........................................................................................ 15-1
Version Menu ....................................................................................................... 15-1
Offline Connection Set .........................................................................................15-1
Offline Change Address Screen............................................................................ 15-2
DeviceNet™ Error Log......................................................................................... 15-2
Network Statistics Screen ..................................................................................... 15-3
Terminal Setup Menu ........................................................................................... 16-1
Communication Setup Screen (HIM Comm) .......................................................16-1
Password Menu..................................................................................................... 16-2
Password Setup (Primary) ......................................................................................16-2
Password Setup (Secondary) .................................................................................16-3
Entering a Password ...............................................................................................16-3
Resetting Forgotten Passwords ............................................................................... 16-4
Auto Display ......................................................................................................... 16-4
AutoDisplay Setup .................................................................................................. 16-4
AutoDisplay Test .................................................................................................... 16-5
Programmable User Function Key Setup ............................................................. 16-5
Function Key Setup Screen................................................................................... 16-6
LCD Contrast ....................................................................................................... 16-6
Copy and Paste Feature......................................................................................... 17-1
Chapter 17 — Copy and
Paste Feature
Chapter 18 — Menu
Help Feature
Chapter 19 —
Specifications
Appendix A —
DeviceNet™ Objects
Menu Help Feature ............................................................................................... 18-1
Specifications 19-1
Identity Object .......................................................................................................A-1
CLASS CODE 0x0001 ........................................................................................... A-1
Message Router...................................................................................................... A-2
CLASS CODE 0x0002 ........................................................................................... A-2
DeviceNet™ Object............................................................................................... A-2
CLASS CODE 0x0003 ..........................................................................................A-2
Connection Object ................................................................................................A-3
CLASS CODE 0x0005 ........................................................................................... A-3
viii
Chapter
1
Product Overview
Product Overview
The CEP7-DNCT product is a handheld device that can be used to commission, configure, program, and monitor other devices on a DeviceNet™ network. In addition, the CEP7-DNCT can be used to upload, store, and later download complete device configurations for DeviceNet™ devices via the network. The CEP7-DNCT also has the capability to present DeviceNet™ physical layer diagnostics and network bandwidth statistics to the user.
Bill of Material
The CEP7-DNCT product package includes the following items:
Item
CEP7-DNCT
CEP7-CB1
CEP7-QR002_-EN-P
Description
DeviceNet™ Configuration Terminal
1 m DNCT Cable with color-coded bare leads
DeviceNet™ Configuration Terminal Quick Reference
1
1
Quantity
1
Accessories
Description
1 m DNCT Cable with color-coded bare lead
1 m DNCT Cable with microconnector (male)
Door mount bezel kit
Catalog No.
CEP7-CB1
CEP7-CM1
CEP7-DNCT-BZ1
ATTENTION
The CEP7 DeviceNet™ Configuration Terminal should only be used on a DeviceNet™ network.
1-2
Notes:
Chapter
2
Installation and Wiring
Installation and
Wiring
The DNCT ships complete with a 1 m cable (CEP7-CB1) for connection to a DeviceNet™ network. This cable has a plug connection to the terminal on one end, and color coded bare leads on the other end.
Alternately, a 1 m cable (CEP7-CM1) can be ordered that has a plug connection to the terminal on one end, and a DeviceNet™ male micro style connector on the other end. A bezel mounting kit (CEP7-
DNCT-BZ1) is available for mounting the terminal to a panel door.
CEP7-CB1 Physical Connections
The CEP7-CB1 cable that ships with the Configuration Terminal has a plug connection to the terminal on one end, and color coded bare leads on the other end. The cable’s bare leads are wired to a
DeviceNet™ connector according to the following table:
Signal
V-
Can_L
Drain
Can_H
V+
Function
Common
Signal Low
Shield
Signal High
Power Supply
Color
Black
Blue
Non-insulated
White
Red
CEP7-CM1 Physical Connections
The optional Cat. No.CEP7-CM1 has a plug connection to the terminal on one end and a DeviceNet™ male micro-style connector on the other end. The cable’s micro connector pin-out is shown in Figure
2.1
Figure 2.1 Cat. No. CEP7-CM1 Pinout
V+
V-
Drain
Can_L
Can_H
2-2
Powering the
CEP7-DNCT
CEP7-DNCT-BZ1 Physical Connections
ATTENTION
When mounting in a door or panel-mounted bezel kit, only the Cat. No. CEP7-DNCT-BZ1 DeviceNet™ Bezel Kit should be used with the Bulletin CEP7-DNCT
DeviceNet™ Configuration Terminal.
The optional Cat. No. CEP7-DNCT-BZ1 connects to the DeviceNet™ network via an attached cable that has color coded bare leads. The cable’s bare leads are wired to a DeviceNet™ connector according to the following table:
Signal
V-
Can_L
Drain
Can_H
V+
Function
Common
Signal Low
Shield
Signal High
Power Supply
Color
Black
Blue
Non-insulated
White
Red
The DNCT must be powered from an external 24V DC source through the communication cable. The
24V DC connections should be made to the V+ and V- pins/wires in the above cable pinout/wire definitions.
ATTENTION
Before physically connecting the DNCT to a target device, verify that the external power supply has adequate capacity to power all devices on the network.
Chapter
3
Physical Features
Physical Features
Figure 3.1 Cat. No. CEP7-DNCT Physical Features
8-Line, 21-Character, Backlit
LCD Display
Navigation Keys
Communication Port
Function Keys
Numeric Entry Keys
Reset Key
Communication
Port
The communication port is used to connect the DNCT to a DeviceNet™ network through use of a communication cable or bezel mount kit (Cat. No. CEP7-DNCT-BZ1). Additionally, 24V DC power is provided to the DNCT at the communication port.
3-2
Key Descriptions
Shifted Key
Descriptions
…
Escape Key. Exit a menu or cancel a change.
Select key. Select a value, digit, or screen choice.
Increment key. Scroll through options, increase a value, or toggle a bit.
Decrement key. Scroll through options, decrease a value, or toggle a bit.
Enter key. Enter a menu, enter a mode, or enter a value.
Scroll left or right keys. Scroll left or right through a value.
Shift key. Small values (yellow text) on top of keys are entered when pressed after the shift key.
Used to enter numbers.
Used to enter a decimal place for a number.
Used to negate a numeric value. Used to add a sign character when editing a value.
Programmable function keys. See Chapter 16, Function Key Setup Screen.
Programmable Reset key. See Chapter 16, Function Key Setup Screen.
The following table describes the alternate functionality of each key when it is pressed after the shift key.
Key
Combination
The letter A. Used to enter values in hexadecimal.
The letter B. Used to enter values in hexadecimal.
The letter C. Used to enter values in hexadecimal.
The letter D. Used to enter values in hexadecimal.
The letter E. Used to enter values in hexadecimal.
The letter F. Used to enter values in hexadecimal.
Copy function. Used to copy Class, Instance, and/or Attribute data to the clipboard. Available on screens displaying a small “C” in the upper right corner.
Exponential function. Used to enter values in exponential notation.
Paste function. Used to paste Class, Instance, and/or Attribute data from the clipboard. Available on screens displaying a small “P” in the upper right corner.
Help function. Invoke help information for the current screen.
Powerup
Chapter
4
Quick Start
The DeviceNet™ Configuration Terminal is shipped so that when it is placed on the network for the first time, it will automatically set its baud rate to that of the traffic on the network, and then assign itself an unused network address. On power up, the following screen is displayed:
Baud = Fixed baud rate
Auto = AutoBauding
Actual terminal address
Actual baud rate
Adrs = Fixed HIM MacID
Auto = Auto Addressing
Note that there is a 10-second powerup delay programmed at the factory. The above screen will appear for at least 10 seconds on initial powerup. The powerup delay can be modified in the Terminal
Setup screen described in the following section. Once the baud rate is determined and a network address has been set, the terminal will display the Network Who screen, which displays a list of all devices on the network.
IMPORTANT
If the terminal fails to enter the Network Who screen after approximately 20 seconds, it is because it could not determine the network baud rate due to lack of traffic on the network. Pressing the ESC key will allow the user to enter the
Terminal Setup screen so that a fixed baud rate and network address can be set for the terminal.
Note: To go directly to the Terminal Setup screen, press and hold the ESC key during powerup.
4-2
Terminal Setup
Network Who
Screen
Enable = AutoBaud enabled
Disable = Use fixed Baud Rate
Enable = Auto addressing on power up
Disable = Use fixed network address
Fixed Baud Rate setting
Fixed Address setting OR the starting address for auto address determination
Powerup delay in seconds
To scroll through the items on the screen, press the SEL key. To change the value of a selected item, press the Increment or Decrement key. To commit the new value for use, press the Enter (return arrow) key. To exit this screen, press the ESC key.
The terminal searches for all devices on the network and reports the devices it has found on the
Network Who screen. Use the Increment or Decrement key to scroll through devices. Press Enter
(return arrow) to invoke the Device Choices menu.
Device address
Searching at this address
Currently selected device
“-“ = Device is not faulted
“~” = Device is faulted
Device Choices
Menu
This menu allows the user to choose what operation is to be performed for the selected device. The terminal only displays choices that are appropriate for the selected device. The Increment and
Decrement keys allow the operator to scroll through the selections. The Enter key will advance to the selected operation.
Currently selected operation
Version: Displays Version information for the selected device.
Params: Provides access to configuration and status parameters for the selected device. Allows the operator to search for parameters that are not at factory defaults.
Copy Cat: Upload and store complete device configurations, including DeviceLogix™ programs to the programming terminal’s memory. Download stored device configurations from the programming terminal memory to the selected device.
Parameter
Monitoring and
Editing
4-3
Tools: Provides access to Node Commissioning functions, the Class Instance Attribute editor, and the real time graphing function.
Advanced: Provides access to the DeviceLogix™ editor, DeviceNet™ IO message timing information,
ZIP configuration, and local input and output status display.
Scanner: If the selected device is a DeviceNet™ scanner, provides access to simple scanner configuration values and access to the scan list.
Parameters can be accessed as either groups or as a numbered list of all parameters. The Parameter
Screen displays all information for a single parameter. From the Parameter Screen, parameter values can be monitored or edited. Scrolling through a parameter list is accomplished by pressing the
Increment or Decrement keys from the Parameter Screen. Parameters can also be accessed by entering a parameter number with the numeric keys while in the Parameter Screen. The parameter screen has the following format:
Parameter number
Press Shift Copy to copy parameter Class,
Instance, Attribute info to the clipboard
Parameter name
Parameter value
Parameter units
A parameter help string, minimum value, maximum value and default value are scrolled across the screen here
Parameter values are continuously updated.
Change a parameter value by first pressing the SEL key and then modifying the selected value.
1) Press the SEL key to select the value
2) The Increment and Decrement keys increment or decrement the value when it is selected. An edit box will appear when a key is pressed.
OR
Enter a number from the numeric keypad. An edit box will appear when a key is pressed.
Pressing the Enter key will write the new value to the selected device. When a parameter value is selected, pressing the ESC key will deselect the parameter value and allow movement within the parameter list or group.
4-4
Bit-enumerated parameters are displayed and modified as follows:
1) Press the SEL key to select a bit to change.The selected bit name is displayed here
Press < (scroll left) or > (scroll right) to select the next bit
DeviceNet™
Configuration
Terminal Setup
Menus
2) Press the Increment (or 0) or Decrement (or 1) key or to toggle the bit value
Pressing the Enter key will write the new value to the selected device. When a parameter value is selected, pressing the ESC key will deselect the parameter value and allow movement within the parameter list or group. Pressing the ESC key will delete changes and revert to the previous settings for that parameter.
The CEP7 DeviceNet™ Configuration Terminal often refers to itself as a HIM (Human Interface
Module). When “This DNet HIM” is chosen from the Network Who screen, the following HIM Choices
Menu appears:
Displays version information
Displays the HIM Setup Menu
(shown below)
Allows the user to perform
Faulted Node Recovery for nodes that fail the Dup Mac
ID test
Displays a DeviceNet™ communication error log
Displays and latches Network Diagnostic information such as
Baud Rate, Bus Voltages, Bus Loading characteristics and
CAN errors
The HIM Setup menu allows the user to configure many of the programming terminal features.
Invokes the Terminal Setup screen described above
Auto Display setup enables the display of up to 4 parameter values from one or more devices at powerup
Sets up the 5 security passwords:
1 primary and 4 secondary passwords. Primary passwords enable/disable all editing functions Secondary passwords enable/disable editing of the features presented by the terminal
Configures the operation of the User
Keys: F1, F2, F3, F4 and Reset
Adjust the screen contrast
Chapter
5
Device Choices Menu
Device Choices
Menu
The Device Choices menu is entered from the Network Who screen when a device is selected and the
Enter key is pressed. This menu allows the operator to choose what operation is to be performed on the selected device. The choices on this menu are only displayed for features that the selected device supports. The Inc and Dec keys allow the operator to move up and down through the selections. The
Enter key will advance to the selected menu.
Currently selected operation
Version Screen
If the currently selected device is the DeviceNet™ HIM, this menu will be slightly different. See Chapter 15, DeviceNet™
Terminal Choices, for description. Not all choices will be available for all devices.
The Version Screen appears when “Version” is selected from the Device Choices Menu. It displays the major revision, minor revision, and if supported the build number of the selected device. If multiple instances of the Identity Object are supported in the selected device, the revision number for each instance is displayed. Use the Inc/Dec keys to select the different instances of the Identity Objects.
The Esc key will return the user to the Device Choices menu.
Identity Object instance name
Optional build number
Displays vendor ID, device type and product code
5-2
Chapter
6
Parameter Choices Menu
Parameter
Choices Menu
The Parameter Choices Menu is only available if the selected device has built-in parameter support
(DeviceNet™ Parameter Object). This menu allows the operator to go to screens that monitor and change parameters, view/select parameter groups, and search for parameters that are not at their default settings. The Inc and Dec keys allow the operator to move up and down through the selections. The Enter key advances the user to the selected item. The Esc key returns the user to the
Device Choices Menu.
Currently selected function
Groups Screen
This screen allows the operator to select a group of parameters to be monitored/edited. The Inc and
Dec keys allow the operator to move up and down through the selections. The Enter key advances the operator to a Parameter Edit Screen. The Esc key will return the user to the Parameter Choices
Menu. The choices in this menu are only displayed for groups that the selected device supports.
Currently selected parameter group
Parameter group names
6-2
Num List
Selection
Parameter Edit
Screens
Numeric
Parameters
A numerical list (Num List) of Parameter Edit Screens are presented when Num List is selected and the
Enter key is pressed.
The Parameter Edit Screens allow the device’s parameters to be monitored and edited. The parameter screens have slightly different formats for each parameter data type (numeric, value enumerated, bit enumerated Boolean, etc.)
Numeric parameter values are displayed as follows:
Parameter number
Parameter name
Parameter units
Parameter value
Indicates that this parameter is
Read Only and its value cannot be edited.
If the Parameter has a Help string, the string will be scrolled across the bottom line. After the Help String is displayed, the Min value will be display for 3 seconds, followed by the Max value, and then the Default value. After the Default is displayed the string will repeat.
OR
This c indicates that the Class,
Instance, and Attribute data for this parameter can be copied to the clipboard by pressing Shift key then the Copy Key.
Numeric Parameter values have this format
Note: If the parameter is a monitor parameter, the HIM stores the HI and LO values for the parameter during monitoring. The HI:/LO: values are displayed on the same line as the Min, Max, Def and Help string.
Accessing a
Different
Parameter
6-3
Accessing a different parameter from a Parameter Edit Screen is done by entering or changing a new parameter number. Changing the parameter number can be done using the Inc or Dec key to increment through the currently active group of parameters. Entering a new parameter number directly can be done by entering a number with the numeric keypad (only if accessed through the
Num List).
Current parameter number
Pressing a numeric key will displayed an edit box to enter a new parameter number in.
Changing a
Parameter Value
Changing a parameter value is done by pressing the Sel key to highlight the parameter value then using the Inc/Dec keys or numeric keys to enter the value. Pressing the Enter key will write the new
6-4 value to the parameter. When the parameter value is selected, pressing the Esc key will deselect the parameter value and allow the parameter number to be changed.
Press Sel key to select the
Parameter Value
Pressing a numeric key will display an edit box to enter a new parameter value
Enumerated
Parameters
Parameters that display Value Enumerated data values appear as follows:
Enumerated Parameter value
To change a value, press the Sel key to select the Enumerated
Parameter value, then use the
Inc/Dec key to change the value
Parameters with Bit Enumerated data values are displayed as follows:
Bit enumerated parameter value
6-5
Text string associated with the selected bit
Bit selected
Press the left/right arrow key to select the next bit
Floating Point
Parameters
Parameters with Floating Point values will be displayed as follows:
6-6
Entering floating point numbers is performed much the same as regular numeric parameters described earlier. The exponential (displayed as an “E”) is entered as follows:
Use the Shift key then the Exp key to add the E into the value when editing a floating point value
Search for
Changed
Parameters
This function is invoked by selecting the Search option from the Parameter Choices Menu. The function searches through the selected device’s parameters and finds the parameters that are not at their default setting. The following screen is displayed when searching the parameter list for the selected device:
Current parameter being checked for default value
Number of parameters to search through
Number of non-default parameters found
When all the parameters have been checked, a list of parameters that are not at their default value will be displayed. The Inc and Dec keys allow the operator to move up and down through the nondefault parameters. Pressing the Enter key allows the parameter value to be viewed/edited.
Selected parameter
Names of non-default parameters
Parameter number of nondefault parameters
6-7
When accessing parameters found by the Search function, the format of the parameter screen will be similar to a Parameter Edit Screen with a few changes. The title line will say “Non-Default Parameter”, and when Inc or Dec is pressed, only the parameter found in the search will be displayed.
6-8
Copy Cat
Chapter
7
Copy Cat Menu
The copy cat menu allows the operator to upload and download complete device configurations to and from the Configuration Terminal. For DeviceNet™ slave devices, these complete device configurations consist of all configuration parameter values and any DeviceLogix™ program that is programmed in the device. For DeviceNet™ Scanners, device configurations consist of the scan list.
This feature is only available for devices that support the Parameter Object or devices that support the Scanner Object.
The Copy Cat menu uses the acronym HIM in many of its menu selections and screens. HIM stands for
“Human Interface Module” and is used to refer to the Configuration Terminal itself. The HIM acronym is used in this product for historical reasons, as this acronym was used on older hand-held configuration tools and many users are familiar with its use with regard to the Copy Cat function.
The Copy Cat Menu is shown below:
These choices will only be display if one or more Copy Cat files have been stored in the
Configuration Terminal
7-2
Copy Cat
Uploading
To upload the parameters and the DeviceLogix™ program (or scan list) from a device, select Dev-
>HIM at the Copy Cat Menu and press the Enter key. The first screen will allow the operator to select where the data will be stored, either to an existing file or a new file:
Selected file
Existing Copy Cat file names
New unnamed “empty” file
After selecting a file, you will be able to name/rename it:
Selected Character; use the Sel key to move the cursor to the right to select the next character
File name the Copy Cat data will be saved to
Use the Inc/Dec key to move the cursor to change the character. The numeric keypad can be used to enter a number into the file name
When done editing the file name, press the Enter key to start uploading:
Currently uploading parameters.
Note: Will display ScanList for
Copy Cat of a DeviceNet™ Scanner
Upload progress bar
Once the parameters are uploaded, the DeviceLogix™ program will be uploaded (if applicable):
Currently uploading the Logix program
7-3
When the upload is complete, the screen will appear as follows:
Copy Cat
Downloading
To download complete device configuration files that have been stored in the Configuration
Terminal, select HIM->Dev at the Copy Cat Menu. The first screen that appears will allow the operator to select which stored file to download:
Selected file to download
7-4
After selecting the file to download, press the Enter key to start the download. If the device being downloaded to does not match the device the file was uploaded from, an error is displayed before the download continues:
Mismatch type. This could be:
Vendor
ProdType
ProdCode
Revision
IMPORTANT
Pressing the Enter key will cause the Configuration Terminal to ignore the electronic keying errors and continue the download.
The following screen will appear when the downloading starts:
Currently downloading parameters. Note: Will display
“ScanList” for copy cat of a scanner
Currently downloading the
DeviceLogix™ program
Progress bar
After parameters are downloaded, the DeviceLogix™ program is downloaded.
When the download is complete, the screen will appear as follows:
7-5
If there are errors during the download process, the screen will look like this:
Errors may occur in either or both parameters and/or the
DeviceLogix™ program downloading
If parameter errors occur, pressing the Enter key will bring up the following screen, which will allow the operator to choose to view the parameters that had errors during the download. Note: Only the first 32 parameters with errors are stored.
.
If the operator chooses to view the parameters that had errors during the download, a Parameter Edit
Screen will be displayed with minor changes. The title line will say “CopyCat Error Params,” and when
Inc or Dec is pressed, the user will only view the next parameter that had an error during the download.
Copy Cat
Downloading and
Product Revisions
From time to time, new firmware revisions are released in the DeviceNet™ product portfolio. Great care is taken in these product upgrades to ensure backward compatibility with previous revisions when it comes to being able to accept Copy Cat data files. Great care is also taken to ensure that the new revision of the product will behave the same as the older revision after a Copy Cat data file has been downloaded.
7-6
When a Copy Cat data file is downloaded to a different firmware revision of the same product, the user is made aware of the revision difference as follows:
Pressing the Enter key will cause the Configuration
Terminal to ignore the revision difference and continue the download
Pressing ESC will cause the download to be aborted
In some products, new firmware revisions were released in order to add DeviceLogix™ capability to the product. When downloading a Copy Cat data file that was uploaded from a revision of a product without DeviceLogix™ to a revision of the product that contains DeviceLogix™, the status bar on the
Download Status screen will not reach 100%. The “Download Complete” line above the status bar will be the indication that the download was indeed completed.
Copy Cat
Downloading and
Product Current
Ratings
Often times it is useful to download Copy Cat data files to devices within a product family that have different current ranges. This is particularly useful if the user wishes to download a DeviceLogix™ program to multiple members of a product family. When a Copy Cat data file is downloaded to a product whose current range is different from that of the product that the data file was uploaded from, the following screen appears:
Pressing the Enter key will cause the Configuration
Terminal to ignore the product code (current range) difference and continue the download
Pressing ESC will cause the download to be aborted
When downloading to devices in the same product family with different current ranges, the download results will often include Parameter Errors. These errors are the result of downloading
7-7 parameters such as FLA current settings whose min/max range is outside the FLA current setting that was downloaded. When this occurs, the following screen appears:
Pressing the Enter key will bring the operator to the Parameter Edit Screens for the out-of-range parameters. The title line will say “CopyCat Error Params”.
When Inc or Dec are pressed from the
Parameter Edit Screen, the next or previous parameter that had an error during the download will be displayed
Deleting Copy Cat
Files
Deleting a Copy Cat file from the memory of the Configuration Terminal is done by selecting the
Delete option at the Copy Cat Choice menu. Select the file name to delete, and press the Enter key to delete the file. If all the files have been deleted, the screen will again display the Copy Cat Choice menu, but the Delete and HIM -> Dev options will not be displayed.
File to be deleted
Copy Cat Memory
The Copy Cat memory screen displays how many files are stored in the DeviceNet™ HIM and how many blocks of memory are left for copying. The maximum number of files that can be stored in the
Configuration Terminal is 31. Depending on the number of parameters in each file, there may not be
7-8 enough memory to store all 31. Note: Each block of memory is equal to 128 bytes in the memory, and there are 128 blocks of memory reserved for file storage.
Chapter
8
Tools Menu
Tools Menu
The Tools Menu gives the user access to the Node Commissioning screen, a Class Instance Attribute editor, and a graphical parameter chart recorder screen. The Tools Menu is shown below:
Node
Commissioning
Pressing Enter while the NodeComm item is selected in the Tools Menu invokes the Node
Commissioning screen. Node commissioning allows the operator to change the Mac ID and/or the baud rate for the currently selected device.
Currently selected item
This only appears if one of the fields has been changed.
Pressing Enter here will reset the DeviceNet™ HIM after writing any changes to the device
Class Instance
Attribute Editor
The Class Instance Attribute (CIA) Editor allows the operator to perform DeviceNet™ explicit messaging. Get, Set, and Reset services can be sent to any Class, Instance, and Attribute.
8-2
The Get service is outlined in the following screen description:
Highlight and press the
Enter key to perform the service
CIA Copy and Paste is available for this menu
Display size of read data.
Choices: Byte, Word, Dword, or
Multi byte
Selected service
Data that is read when a message is requested
:
The Set service is outlined in the following screen description:
Highlight and press the Enter key to perform the Set service
Display size of data to write.
Choices: Byte, Word, Dword, or
Multi byte
Data to write
The Reset service is outlined in the following screen description:
Highlight and press the Enter key to perform the Reset service
Graph Setup
Screens
The Graph function allows the Configuration Terminal to become a simple graphing device. From the
Graph Setup Screens, the user sets up to four Class, Instance, or Attributes to be monitored and
Graph View
Screen
8-3 displayed as a scrolling graph (similar to an oscilloscope or chart recorder). The first screen allows the operator to configure the four Class, Instance, or Attributes to be monitored.
Class, Instance, Attribute to graph, Note: Traces with the class set to zero will not be graphed.
Offset is the number of pixels from the bottom of the screen the min value for this trace will be displayed at. The range for this field is 0…64, with 32 being the middle of the screen.
Trace number 1-4
Rate the CIA will be polled, in
10 mSec increments
CIA Copy and Paste is available for this menu
Max is the CIA’s value that will be represented as the top of the screen. Min is the CIA’s value that will be represented as the bottom of the screen. (In this example, a
CIA value of 50 would be in the middle of the screen; any CIA value at or above 100 would be displayed on the top pixel of the screen). Note there are only 64 vertical pixels with this LCD.
Press the Enter key after the CIA data is configured to display the Graph Trigger Screen. This screen allows the operator to program a trigger point to stop the graph display from updating. The operator can set which trace will be used as the trigger as well as the slope, value, and position of trigger. The trigger point can be disabled if the operator does not need this feature.
This could be trace 1…4
The value is the trigger point; this is the raw value obtained by reading the CIA for the selected trace.
Position is the location on the screen at which the trigger point will be displayed when the trigger condition is found.
Positive Slope: the raw value
(obtained by reading the CIA for the trace) moving from below the
Programmed Value to equal or above the Programmed Value.
Negative Slope = Above value moving below.
Position value is 0 …128 (128 pixels across the screen) 64 = 50%
Press the Enter key after the trigger data is configured to display the Graph View Screen.
This menu displays the CIA data in graphical form.
This screen show only one trace configured
8-4
Pressing the Enter key while the Graph View Screen is displayed stops the trace and displays a cursor that can be used to view the raw value that was read for that point on the graph.
The Cursor; pressing the Inc/Dec key will move the cursor right or left
The raw data value corresponding to a point on the graph where the cursor intersects. Note: T1: reflexes the trace number that the value corresponds to. To change the trace number, use the Sel key.
HI:/LO: reflect the high and low data values contained in this trace
Chapter
9
Advanced Functions Menu
Advanced
Functions Menu
The Advanced Functions Menu provides access to a DeviceLogix™ editor, Zone Interlocking Protocol
(ZIP) configuration and monitoring screens, an I/O message timing screen that monitors I/O messaging timing between the selected device and a DeviceNet™ scanner, and Discrete I/O statistics.
The Advanced Functions Menu is shown below:
Only available if DeviceLogix™ is supported in the currently selected device
Only available if Zone Interlock
Protocol Object is supported in the currently selected device
Only available if DIP, DOP or
PNB Objects are supported in the currently selected device
9-2
Chapter
10
I/O Message Monitoring
I/O Message
Monitoring
This screen displays I/O message timing information and I/O message data for the currently selected device. It is accessed by selecting I/O Msg and pressing the Enter key at the Advanced Functions
Menu.
Press the INC/DEC key to switch between consumed and produced data
Size of the I/O data in bytes
I/O Message Count
Type of IO connection. Polled or
COS
Most recent produced or consumed I/O data for the currently selected device
Message reception rate
Min, Max and Average
10-2
Chapter
11
DeviceLogix™ Functionality
DeviceLogix™
Functionality
DeviceLogix™
Choices Menu
The Configuration Terminal allows the operator to monitor, edit or delete DeviceLogix™ programs for devices that support DeviceLogix™. DeviceLogix™ can also be enabled or disabled for a device. The
DeviceLogix™ functions can be accessed through the DeviceLogix™ Choices Menu, which is accessed by pressing Enter from the Advanced Functions Menu while the DevLogix menu item is selected.
The DeviceLogix™ Choices Menu is shown below:
Currently selected function
Only available if the DeviceLogix™
DataTable Object is supported in the currently selected device
DeviceLogix™
Monitor
This function allows the operator to view a DeviceLogix™ program, including all programmed function blocks, Discrete Output Points (DOP) and Produced Network Bits (PNB). Text string for inputs, outputs, PNBs, and fault bits are displayed for devices that support the DeviceLogix™ Data
Table Object. The counter and timer preset and accumulator value’s can be modified when selected.
To view each function block, use the INC/DEC keys to move to the next function block. When the last programmed function block is reached, pressing the INC key will advance the screen to the
Programmed DOP screen. Pressing the INC key again will then display the Programmed PNB screen and if the INC key is pressed a third time, the first function block will be displayed again. When viewing Function Blocks, the screen will have the following formats:
11-2
Boolean Gates: AND, OR, XOR, NAND, NOR, NXOR and NOT
Function block number and type
Value of input or output
Negated (Active Low) inputs
IN3 and IN4 may or may not be present
Bistable Latches: RS Latch and SR Latch
Press the SEL key to highlight the function block’s inputs and outputs text strings. (Only available if the device supports the DeviceLogix™ Data Table
Object)
Counters: Up Counter and Up/Down Counter
Down input may or may not be present
Press the Sel key to highlight the preset or count value. To accept new value press the
Enter key
Timers: On Delay, Off Delay and Pulse Timer
Press the Sel key to highlight the preset or count value. To accept a new value press the Enter key
Time base: 1 mSec or
10 mSec
Discrete Output Points (DOPs):
The name of what is driving the
Discrete Output Point in the
Device Logix program
11-3
Discrete Output Point (DOP).
The name text for this comes from the product, so names may vary product to product
Note: The Programmed DOP screen is only available for devices that support the DeviceLogix™ Data
Table Object.
Produced Network Bits (PNBs):
The name of what is driving the
Produced Network Bit in the
DeviceLogix™ program
Produced Network Bit (PNB). The name text for this comes from the product, so names may vary product to product.
DeviceLogix™
Editor
Note: The “Programmed PNB” screen is only available for devices that support the DeviceLogix™ Data
Table Object.
This DeviceLogix™ Editor allows the operator to create or edit a DeviceLogix™ program. Function blocks are displayed in the same format as in the DeviceLogix™ Monitor. To create, edit or delete a program element, use the INC/DEC keys to navigate to the item to create/edit and then press the
Enter key. To edit one of the inputs of a function block, use the SEL key to highlight the input and then press the Enter key. To invoke the DeviceLogix™ Editor, select the Edit item in the DeviceLogix™
Choices Menu and press the Enter key.
11-4
Creating a New
Function Block
Consider the following example of creating a new AND gate function block. First, invoke the Device
Logix editor. One of two displays will appear, either a display of a function block or a screen displaying
“No FB’s programmed”. At this point press the Enter key and the following screen appears:
The Edit and Delete choices are only present if there are function blocks already programmed
Press the Enter key to create a new function block. Now that a new function block has been created, the type of function block must be selected. The following screen will appear:
Use the INC/DEC keys to select the new function block type. Press the Enter key when the desired function block type is selected. The following screen will appear (the Boolean type screen is shown below. Other similar screens appear for other function bock types.)
11-5
Use the INC/DEC keys to assign a type to the new function block. Press the Enter key when the desired type is selected. The screen should now display a new function block of the selected type:
Assigning Source
Bits to Function
Block Inputs
Note: At this time a new function block has been created and assigned a type, but the inputs and outputs are not assigned at this time.
To assign or edit input source bits for a function block, first choose the function block input by pressing the Sel key to scroll through the function block inputs. With each successive Sel key press, a different input will be selected on the screen. Notice that the current source bit assignment for a selected input will be displayed on the screen for three seconds as shown below:
The Assignment text will disappear after three seconds
To edit an input source bit assignment, press the Enter key while the desired input is selected. The following screen appears:
Negating an input makes the input an active low instead of an active high input
Not all inputs of all function block types can be left unassigned, so this option will not be available for all inputs of all function block types
11-6
Press the Enter key when Edit is selected and the following screen appears:
Not all inputs sources may be supported by all products
Use the INC/DEC keys to select the type of the source bit to assign the input. Press the Enter key when the desired type is selected. The following screen will appear (assume “Inputs” was selected above):
The text for this screen is read from the product. Different products will contain a varying number of choices with different text strings
Use the INC/DEC keys to select the source bit to assign the input. Press the Enter key to assign that selection to the function block input.
Assigning Source
Bits for Discrete
Outputs Points
(DOPs)
To assign or edit a source bit for a Discrete Output Point (DOP), first select a DOP. From the function block screens use the INC/DEC keys to get the Programmed DOP’s screen displayed:
OR
11-7
If the “No DOPs Programmed” message appears, press the Enter key to assign a source bit to an unassigned DOP.
To edit, delete, or negate a specific DOP source bit assignment that already exists, use the Sel key to select the DOP on the screen before pressing the Enter key. The following screen will appear:
Only Create will be displayed if no DOPs are currently programmed
To assign a source bit to an unassigned DOP, select Create and press the Enter key. The following screen will appear:
The text for this screen is read from the product. Different products will contain different numbers of DOPs with varying text strings
Use the INC/DEC keys to select which Output to assign a source bit to. Press the Enter key when the desired Output is selected. The following screen will appear:
Not all inputs sources may be supported by all products
11-8
Use the INC/DEC keys to select the type of the source to assign to the Output. Press the Enter key when the desired type is selected. The following screen will appear (assumed “Function Blocks” selected):
Only Function Blocks that have been created are listed here
Use the INC/DEC keys to select the source bit to assign to the Output. Press the Enter key to actually assign the selected source bit. The following screen will appear:
Assigning Source
Bits for Produced
Network Bits
(PNBs)
To assign source bits for Produced Network Bits (PNBs), first select the PNB. From the Programmed
DOPs screens use the INC/DEC keys to get the Programmed PNBs screen displayed:
OR
If the “No PNBs Programmed” message appears, press the Enter key to assign a source bit to an unassigned PNB.
To edit, delete, or negate a specific PNB source bit assignment that already exists, use the Sel key to select the PNB on the screen before pressing the Enter key. The remaining steps and screens to edit
PNBs are very similar to those used to edit DOPs outlined in the preceding section
DeviceLogix™
Delete Function
11-9
This function allows the operator to delete a DeviceLogix™ Program for the currently selected device.
Press the Enter key to delete the current DeviceLogix™ program
DeviceLogix™
Enable/Disable
Function
This function allows the operator to enable or disable the DeviceLogic program in the currently selected device.
Press the Enter key to enable or disable the DeviceLogix™ program in the currently selected device
Forcing Inputs and
Outputs
The Force function allows the user to force the value of a hardware input or output to a specified value to be used by the DeviceLogix™ program. To use the force function, choose "Forces" from the
DeviceLogix™ Choices Menu and press Enter. The following screen will appear:
To force an Input or Output on or off, select Inputs or Outputs and then press the Enter key
The following screen appears for Inputs (a similar screen appears for Outputs):
Use the Inc/Dec keys to select the input to be forced.
Press the Sel key
11-10
The force state will be highlighted as follows:
Use the Inc/Dec keys to choose ON, OFF, or NONE to force the value to the ON (1),
OFF (0) or no force state, respectively. Press Enter to force the value, or ESC to cancel the selection.
Note: Outputs may only be forced if they are bound to another element in a DeviceLogix™ program.
Note: DeviceLogix™ must be enabled for forces to take effect.
Chapter
12
Discrete I/O Status
Discrete I/O
Status
The Discrete I/O Status screen is displayed by selecting I/O Stat and pressing the Enter key at the
Advanced Functions Menu. This screen displays the status of any Discrete Input Points (DIP’s),
Discrete Output Points (DOPs) and Produced Network Bits (PNBs) that are implemented in the currently selected device. This screen will be available if any one of the DIPs, DOPs or PNBs are supported in the currently selected device.
Value of each bit, 1 or 0
The type of bits that are selected and are being displayed. Press the Sel key to select a different bit type
Unused bits
Range of bits displayed on this line
Note: In this example the device supports 4 instances of the Discrete Input Point Object.
12-2
Chapter
13
Zone Interlock Protocol (ZIP)
Zone Interlock
Protocol (ZIP)
The Zone Interlock Protocol (ZIP) menu is available for devices that support the DeviceNet™ Zone
Interlock Protocol Object. The Zone Interlock Protocol provides a way for devices to share I/O message data directly, and the data that is consumed from other devices can then be used in a
DeviceLogix™ program. The ZIP Choices Menu is displayed by selecting ZIP and pressing the Enter key at the Advanced Functions Menu. The following menu choices are available to edit and monitor the ZIP configuration:
ZIP Consumed
This screen allows the operator to configure the ZIP data that the device is going to consume.
Configuring ZIP Consumed data consists of mapping I/O data from other nodes or zones on the network to the device’s internal ZIP Data Table (the ZIP Data Table is where a DeviceLogix™ program accesses ZIP data). Devices that support ZIP can define the number of zones from which they can consume at one time. In this manual it is assumed that the device can consume data from up to four zones at one time. The size of the internal ZIP data table is device specific. In this manual it is also assumed that the internal ZIP data table is eight bytes long.
The following screen shows a device with no ZIP I/O data configured or mapped:
Zone number (1…4) that is associated with data currently highlighted. Note: x = no zone is associated at this time
This is the internal zip data table.
B:00-07 indicates that we are viewing data table bytes 0…7
(B:08-15 would be displayed on the next line if the data table was
16 bytes long). Each XX represents one byte in the data table. The XX will display the Devices Node
Number whose I/O data is mapped to that byte in the ZIP data table.
The Node Number of the device whose I/O data is mapped in this zone
Number of Zones left in this device that are not mapped
13-2
Mapping
Consumed ZIP
Data
This section explains mapping I/O data for a Zone. Assume that the DeviceNet™ Configuration
Terminal is currently configuring Node 11 on the Network. Also assume Node 5 is on the network, and is producing I/O data. Node 11 will be configured to consume the I/O data that Node 5 is producing, which will be done by mapping Node 5 I/O data to Zone 1 in the ZIP data table of Node 11.
First, use the Left/Right arrow keys to select the byte in the ZIP data table where Node 5 I/O data will be mapped to.
The selected byte in the ZIP data table is highlighted. In this case
Byte 0 is selected. Use the
Right/Left arrow keys to select the byte
This is Byte 7 of the ZIP internal data table
Once the desired byte in the internal ZIP data table is selected, enter a Node number using the
numeric keys on the keypad of the node whose I/O is to be mapped (this example maps Node 5 data to byte 0 of the ZIP data table). Press the Enter key after the Node Number has been entered and the following display should appear:
Zone 1 is now configured to Node 5
Node 5 is mapped to byte 0 of the ZIP data table
These are the current ZIP configuration parameters for
Zone 1
Use the Sel key to highlight the various ZIP configuration parameters for this zone. The following screen shows the Node field highlighted:
The node: Field allows the node number associated with this
Zone to be changed
13-3
The following screen shows the EPR (Expected Packet Rate) field highlighted:
EPR (Expected Packet Rate) allows the expected packet rate of the I/O data from node (Node 5) to be changed.
This value is in milliseconds.
The following screen shows the IO Msg field highlighted:
Note: The IO Msg field may also be referred to as the Zone Mask field.
The “IO Msg:” field allows the choice of which bytes of the I/
O data from node 5 are going to be mapped to the ZIP data table. Each bit in the IO Msg field maps or un-maps a byte of the I/O data from node 5.
The value 1 means map this byte of I/O data. In this example, only byte 0 of the I/O data from node 5 is being mapped.
The following screen shows that byte 0 and byte 2 of the I/O data from node 5 are mapped to the ZIP data table. To accomplish this the IO Msg field must be mapped to the value of “00000101”. Press the
Enter key to edit the IO Msg field value. After editing, the value the screen will appear as follows:
This 1 maps byte 0 of the IO data from node 5
Two bytes of I/O data from node
5 are now mapped to the internal ZIP data table
This 1 maps” byte 2 of the IO data from node 5
13-4
Use the Sel key to select the ZIP data table field. Then use the Right/Left arrows to select the second byte (the second “05”) in the data table. The display appears as follows:
When each byte in the ZIP data table is highlighted, the bit of the IO Msg field that is
Mapped to that byte is also highlighted.
As mentioned earlier, use the Sel key to highlight the various ZIP configuration parameters for this zone. The following screen shows the “Security” field highlighted.
This field allows the Security to be enabled or disabled
Note: If Security is disabled, the field for the Key will disappear.
The following screen shows the Zone Security Key field highlighted.
If Security is Enabled, the last 2 bytes of the I/O data from the node (Node 5) must match the
Key value. If not, all the consumed I/O data will be ignored.
When all edits are complete, the ZIP configuration data must be saved to the device (Node 11 for this example). To save the changes, use the Sel key to highlight the Save field and press the Enter key.
When performing a Save, all the configuration data for all
Zones is saved. The Save field will disappear after the save is completed
ZIP Produced
Data
ZIP Data Table
Monitor
13-5
This screen allows the operator to configure the current device to auto-produce I/O data to share with other devices when ZIP is enabled.
Enables or Disables the Auto production of the I/O data for this device. This should be disabled if the device is connected to scanner.
Zip Disabled /Zip Enabled is the
Global Enable for all ZIP functions in the device. This enables or disables ZIP consumption and ZIP production in this device.
Produce Rate is the cyclic rate at which this device will produce data. Inhibit Rate is the minimum time between
Change of State I/O data productions. Both values are in milliseconds.
Security Key is the value of the last 2 bytes of the I/O data produced by this device if security is included in the I/O data.
This function is invoked by selecting Monitor from the ZIP Choices Menu and pressing the Enter key.
The screen allows the operator to monitor the ZIP data table in order to view the I/O data that the device is consuming. The ZIP Data Table Monitor screen functions as following:
Use the Right/Left arrow keys to select individual bytes in the
ZIP data table
This is the actual data in the internal ZIP data table
“Connection Healthy” is displayed if the I/O data is being consumed before the EPR times out.
“Connection Unhealthy” will be displayed if the EPR timer for that zone times out or if security is enabled and the Security Key does not match.
Node Number the I/O data is being consumed from for the selected ZIP data table byte
The highlighted bit represents the byte number in the I/O data that is being consumed for the highlighted ZIP data table byte, in this case it is byte 0
Press the Right/ Left arrow keys to select the various bytes in the ZIP data table. If no Zone has been mapped to the selected byte in the ZIP data table, the display will appear as follows:
No Zone number is associated with this byte of the internal Zip data table
No I/O data being consumed is mapped to this byte (byte 7) in the ZIP data table
13-6
Chapter
14
DeviceNet™ Scanner Menu
DeviceNet™
Scanner Menu
The DeviceNet™ Scanner Menu is available for DeviceNet™ scanners. The scanner menus give the operator some basic information about the scanner’s configuration and the ability to adjust a few of the scanner attributes. The scanner menus do not allow the operator to perform complete configuration of a scanner. RSNetWorx for DeviceNet™ must be used for initial scanner configuration for a system. The DeviceNet™ Scanner Menu is invoked from the Device Choices Menu and is shown below:
Currently selected function
This will appear only if the scanner supports it
Scanner Setup
This function allows the operator to view and set some of the global settings of the scanner.
Press the Sel key to move to the next selection
This line reflects the status of the Processor, IDLE or RUN
Mode.
Select Save and press Enter to save the changes to the scanner.
14-2
AutoScan
Function
The Auto Scan screen allows the operator to enable and disable the Auto Scan feature of some scanners. This menu will only be available if the scanner supports the Auto Scan function.
This line reflects the status of the Processor, IDLE or RUN
Mode.
AutoScan must be
Disabled to set the mapping size.
Select Save and press Enter to save the changes to the scanner
ScanList Screen
The ScanList Screen displays a list of the nodes in the scanner’s ScanList. It displays the node name, and if it is in the active, faulted or idle state. Use the INC/DEC keys to select nodes in the ScanList.
The selected node
Nodes in ScanList with no errors. When these nodes are selected the product name and
“Node Active” will be displayed every other second
A node with errors. The error name and error number will be displayed every other second when these nodes are selected
Node Activation
Screen
This screen allows the operator to enable/disable a node from the scanner’s scanlist without changing the scanner configuration data for that node (i.e.: I/O mapping, keying, and connection type). To enter this screen, select the correct node in the ScanList screen and press the Enter key.
Press Enter to perform this operation, if the node is currently enabled in the scanlist this will be displayed
If the Node is currently Disabled in the scanlist, “Enable in
ScanList” will appear here
Chapter
15
Terminal Choices Menu
Terminal Choices
Menu
The Terminal Choices Menu is only displayed when the device selected in the Who Menu is This
DeviceNet™ HIM. It is displayed instead of the Device Choices Menu.
Version Menu
This screen is displays the revision of the DeviceNet™ Configuration Terminal firmware.
Offline
Connection Set
This function allows the operator to perform Faulted Address Recovery (FAR) for nodes that fail the
Duplicate MAC ID test. To get to this function select Offline from the Terminal Choices Menu. The first screen to appear will be the Offline Who Screen, which will request ownership of the Offline
Connection Set. When ownership is obtained, it will search for faulted nodes. If any faulted nodes are found, they will be displayed.
Once ownership is obtained, this will change to “Checking for
Devices”
15-2
Note: It may take up to 10 seconds for the Faulted Address Recovery process to complete.
If no faulted devices are found, the following screen will appear:
When faulted devices are found, they are reported as follows:
Offline Change
Address Screen
Device’s serial number
Use the Inc/Dec key to select the next device in the list.
Note: The selected device’s network LED will flash red/ green.
Device’s vendor ID number
Device’s port number
Use the Inc/Dec keys in the above screen to select a faulted device. Then pressing the Enter key invokes the Offline Change Address Screen. Simply change the device’s address and press the Enter key while Apply Changes is selected to change the device’s address and reset the device.
New node address number
DeviceNet™ Error
Log
The DeviceNet™ Error Log stores the last five errors the Configuration Terminal received when requesting information from a device. If the terminal receives an error that is the same as the last error, only the first error will be stored. Errors received while in the Who Menu are not entered into the error log. Each error has a time stamp associated with it that indicates the number of days, hours,
Network
Statistics Screen
15-3 minutes, and seconds since the error message was received. The Error Log screen has the following format:
Node Number, Class, Instance, and Attribute of request for which an error was returned
Requested Service:
Get Single
Set Single
Get All
Set All
Reset
Create
Delete
Time Stamp:
DDD:HH:MM:SS
D = Days
H = Hours
M= Minutes
S = Second
This menu supports the
CIA Copy function
Error Buffer Number, use the Inc/Dec keys to scroll through each entry in the log.
The Error code that was returned
This screen displays some DeviceNet™ network statistics such as baud rate, actual bus voltage stats, percentage of bus loading stats, CAN errors per second, and total CAN errors. Latching of statistics for some readings begins when the screen is entered, and stops when exiting the screen. Statistics can be cleared by exiting and re-entering the menu. While displaying this screen, the CEP7-DNCT will not respond to any DeviceNet™ messages directed to it. There will be a short delay when exiting this screen before the Terminal starts producing DeviceNet™ messages, due to the CAN chip being reset and re-initialized. The Network Stats Menu has the following format:
15-4
Chapter
16
Terminal Setup Menu
Terminal Setup
Menu
This menu is used to configure features of the CEP7-DNCT (HIM). The following menu choices are presented:
Communication
Setup Screen
(HIM Comm)
This screen is invoked by pressing Enter while HIM Comm is selected in the Terminal Setup Menu. It configures how the CEP7-DNCT connects to the DeviceNet™ network. Three basic options are configured here: the baud rate, the node address, and the power up delay. When configuring the baud rate, auto baud can be enabled or disabled, and the baud rates 125K, 250K or 500K can be selected. When configuring the Node Address, Auto Addressing can be enabled or disabled, and the node address number can be set. When Auto Addressing is enabled the CEP7-DNCT will operate as follows: the first Dup MacID message will be sent out using the node address that has been configured in the Address Field. If a node is found at that address, the node address is decremented by 1, and the terminal will determine if there is a node at the new address. This will continue until the
CEP7-DNCT finds a node address that is not being used.
The PowerUp Delay field specifies the time waited from initial power up until the first messages are produced by the CEP7-DNCT. This feature allows the operator to set the time before the CEP7-DNCT starts communicating with devices on the network, allowing scanners to connect to any group two devices and start proxying. It also allows all devices to come online before AutoAddressing.
This is the Baud Rate that is used if AutoBaud is disabled
PowerUp Delay (in seconds)
Node Number of the CEP7-DNCT if AutoAddress is disabled. If
AutoAddress is enabled, this is the starting Node Number
16-2
Password Menu
The CEP7-DNCT has five passwords: one primary (master) password and four secondary passwords.
When the primary password has been configured and correctly entered the operator will gain full access to all features in CEP7-DNCT. The secondary passwords can be configured to limit the features that are associated with that password, so when a secondary password is entered, the operator will only gain access to limited features in the CEP7-DNCT. The following choices may appear when the
Password selection is chosen from the HIM Setup Menu:
Must have the primary password set for this selection to appear
Must have at least one password logged in for this selection to appear
Password Setup (Primary)
To activate the primary password, simply set the password to a value other than zero. By logging in using that password value the operator will gain full control of the CEP7-DNCT. The Password Setup
Screen, when set to the Primary Password, has the following format:
Primary Password selected.
Press the Inc/Dec key to get to secondary passwords
This will appear when changes to the password have occurred.
Press the Enter key to save changes to the password
Password value range is
0…999999
16-3
Password Setup (Secondary)
Secondary passwords limit access to certain device features, thus limiting some operator’s ability to change the system configuration. The following menu is used to configure secondary passwords:
Secondary password 1 selected
Password value range is
0…999999
This will appear when changes to the password have occurred.
Press the Enter key to save changes to the password
To associate privileges to a specific secondary password, press the Sel key until the cursor appears on the bit field. Setting a bit to a 1 enables edit privileges for that feature; setting the bit to zero disables editing for that feature. Each of the secondary passwords can be configured to have some or all privileges.
Note: Once the primary password is set, it must be logged in to edit secondary passwords.
Bit Field privileges:
Bit0 = Parameter Edit
Bit1 = CopyCat
Bit2 = Graph Setup
Bit3 = Node Commissioning
Bit4 = CIA Editor
Bit5 = DeviceLogix™
Bit6 = ZIP
Bit7 = Scanner Setup
Bit8 = UserKeys
Bit Field selected. Use the
Left/Right arrow keys to move the cursor to the next bit. This screen shows bit 0 selected.
Entering a Password
When the operator attempts to access a menu that is password protected the following box will appear for password entry:
Password entry box
Password Value
16-4
Auto Display
Resetting Forgotten Passwords
Using RsNetworks for DeviceNet™, find the DNCT on the network, and set parameter 2 - Password
Override to override. This will temporarily override the password in the DNCT. The old password can then be viewed and changed from the DNCT. The password is only overridden until the DNCT is powered down.
The auto display feature allows the CEP7-DNCT to be setup so that on power up, it will connect to one or more devices and display 1…4 values from 1…4 devices. This allows the unit to automatically monitor device values without any intervention at power-up. The following choices appear when
AutoDspl is selected from the Terminal Setup Menu:
AutoDisplay Setup
This screen is used to set up to four Class, Instance Attributes to be auto displayed. This screen allows a different node address to be entered for each CIA value configured, thus up to four different nodes can be monitored at the same time. Setting the node address to 64 for a CIA disables Auto Display for that value. Use the Sel key to select different fields to edit.
CIA Copy and Paste is available for this menu.
Device node number
Class, Instance, Attribute data
This enables or disables the
AutoDisplay on power up. It can be set on the screen for any line number but this value will be the same for all 4 lines.
Display line number (1…4)
16-5
AutoDisplay Test
This function gives the operator an easy way to view and test the AutoDisplay setup data without powering down the CEP7-DNCT after setting up each line. If the CIA data for a line points to the parameter class, the CEP7-DNCT will display the scaled value and units (if any) for that line.
CIA pointing to a parameter object
Note: AutoDisplay can be configured to show 4 lines as shown here or 1, 2, or 3 lines.
CIA NOT pointing to a parameter object
Programmable
User Function Key
Setup
The 5 user programmable function keys (F1, F2, F3, F4 and Reset) can be configured to send
DeviceNet™ explicit messages when they are pressed. The Function Key Setup screen is used to associate DeviceNet™ messages to the various function keys. This screen is accessed by selecting
“UserKeys” in the “Terminal Setup Menu” and pressing the Enter key.
The default operation of these keys is identical to the OutA and OutB start keys, and the OutA and
OutB stop keys on the old Bulletin CEP7-PCT hand-held terminal.
• F1: Default behavior is like that of the green OutA start key on the CEP7-PCT. It sets Discrete
Output Point instance 1 to the ON state. (CIA: 0x09-0x01-0x03 = 1).
• F2: Default behavior is like that of the green OutB start key on the CEP7-PCT. It sets Discrete
Output Point instance 2 to the ON state. (CIA: 0x09-0x02-0x03 = 1).
• F3: Default behavior is like that of the red OutA stop key on the CEP7-PCT. It sets Discrete
Output Point instance 1 to the OFF state. (CIA: 0x09-0x01-0x03 = 0).
• F4: Default behavior is like that of the red OutB stop key on the CEP7-PCT. It sets Discrete
Output Point instance 2 to the OFF state. (CIA: 0x09-0x02-0x03 = 0).
• Reset: Sets Fault Reset to the ON state. (CIA: 0x29-0x01-0x0C = 0).
Each key has the following configuration parameters that can be programmed: Class, Instance,
Attribute, Pressed (Down) Value (ON or OFF) and Mode. The Mode can be programmed to either
Momentary or Maintained operation. The Maintained Mode acts as follows: when key is pressed, the
Press Down Value is sent; when the key is released there is no operation. The Momentary Mode acts as follows: when key is pressed, the Press Down Value is sent; when the key is released, the inverse of the Press Down Value is sent. Since not all screens have an active explicit message connection, the
Function Keys will be active while viewing only some menu screens. The following is a list of screens on which the User Keys will be active:
1. Parameter Screen
2. CIA Editor Screen
3. I/O Message Monitoring Screen
4. Graph View Screen
16-6
Function Key
Setup Screen
LCD Contrast
5. Who Menu (Reset key only)
Table 16.1 Function Key Default Behavior for E3 and ArmorStart
F2
F3
Function Key
F1
F4
Reset
Default E3 Operation
Turns on Output A
Turns on Output B
Turns off Output A
Turns off Output B
Resets Protection Faults
Default ArmorStart Operation
Turns on Run Forward
Turns on Run Reverse
Turns off Run Forward
Turns off Run Reverse
Resets Protection Faults
Class, Instance, Attribute
Information. Values are entered in hexadecimal
Current key (F1) being configured.
Press Inc/Dec to change keys
CIA Copy and Paste is available for this menu
Save will appear after changing the settings for any key, Pressing
Enter will save the information for all the keys
Press Inc/Dec from the F4 setup screen to get to the Reset key setup
Value sent when the key is pressed,
ON (1) or OFF (0)
Mode of key, Momentary or
Maintained
CIA Copy and Paste is available for this menu
Class, Instance, Attribute
Information. Values are entered in Hexadecimal.
The default for the Reset key is the Clear Fault attribute of the
Control Supervisor Object
This screen is used to change the contrast of the CEP7-DNCT LCD. The Inc/Dec keys are used to increase or decrease the contrast of the LCD.
Sample text to view when adjusting the contrast
This bar graph indicates the
LCD’s contrast setting,
0…100%
Chapter
17
Copy and Paste Feature
Copy and Paste
Feature
The CEP7-DNCT has a Copy and Paste feature that allows the operator to copy Class, Instance,
Attribute, Node Number, Min, and Max values from one menu to another menu. Menus that support the Copy and Paste feature will display a small C (copy indication) and P (paste indication) in the upper right hand corner of the screen.
Copy and Paste Support indication for menu
Some screens may only support the copy feature, so only the small “C” in the upper right hand corner will appear. The small “P” in the upper right hand corner will only appear after CIA data has been copied and will only appear on menus that support CIA data paste feature. When a copy or paste is actually performed, the text “Copy” or “Paste” will appear in the upper right hand corner for one second.
To perform a Copy or a Paste use the following key strokes:
To copy the CIA data on a screen:
• Press the Shift key, then
• Press the Copy key (Right Arrow key)
To paste the CIA data to a screen:
• Press the Shift key, then
• Press the Paste key (+/- sign key)
17-2
In the following example, we will copy the Class, Instance, and Attribute data from a parameter screen to the GraphSetup Screen. First go to the Parameter Screen and select the parameter to copy. Press the Shift key and then the Copy key to copy all the parameter data to the clip board.
Displayed for one second at the time of the copying. This indicates the copy is complete.
To paste the data to the Graph Setup Menu, invoke the Graph Setup Screen. Next, press the Shift key and then press the Paste key to paste all the parameter data to the GraphSetup Screen. The screen should appear something like this, depending on the parameter copied:
Class, Instance, Attribute, Min and Max value should change to the settings of the copied parameter
“Paste” is displayed here for 1 second at the time of the paste.
The display disappears when the paste is complete.
The follow table documents which menus support the copy and/or paste feature:
SCREEN
Parameter
CIA Editor
Graph Setup
Error Log
AutoDisplay Setup
Function Key Setup
COPY Support
YES
YES
YES
YES
YES
YES
PASTE Support
NO
YES
YES
NO
YES
YES
Chapter
18
Menu Help Feature
Menu Help
Feature
All of the screens in the DeviceNet™ Configuration Terminal have help text associated with them. To view help text, press the Shift key followed by the Help key (Zero key). Press the ESC or Enter key to close the help screen. Some menus that are complicated, such as graph setup, have help available for each field on the screen. In those cases, select a field and press the Shift key followed by the Help
(Zero) key. The following is an example of a help screen:
18-2
Specifications
Display
Display Type
Viewing Area
128 x 64 LCD with yellow-green backlighting
57 x 30 mm (2.24 x 1.18 in.)
Keypad
Keypad Type
Operation Force
Operational Life
Tactile embossed, domed keys, sealed membrane
453 g (16 oz)
1 million operations
Communications
Communication Protocol DeviceNet™ (125, 250, 500 Kbaud selectable)
Electrical
Input Voltage Range
Input Power, typical
Input current
11…25.0V DC
1.7 W
70 mA @ 24V DC
Environmental
Operating Temperature
Storage Temperature
Humidity
Operating Shock
Non-Operating Shock
Operating Vibration
Non-Operating Vibration
0…50
°
C (32…122
°
F)
-40…85°C (-40…185°F)
5…95% non condensing
30 g
50 g
2.5 g @ 5Hz…2kHz
5 g @ 5Hz…2kHz
Chapter
19
19-2
Dimensions
Height
Width
Depth
Weight
Agency Approvals
UL cUL
CSA
CE
RoHS
116 mm (4.57 in)
70 mm (2.76 in)
15.5 mm (.67 in)
85 g (3 oz)
508
C22.2 No. 14
EN61000-6-2:2005
EN61000-6-4:2001
This product meets the material restrictions of the European Union RoHS Directive
Appendix
A
DeviceNet™ Objects
Identity Object
The following object classes are supported:
Class
0x0001
0x0002
0x0003
0x0005
Object
Identity
Message Router
DeviceNet™
Connection
CLASS CODE 0x0001
The following class attributes are supported for the Identity Object:
Attribute ID
1
Access Rule
Get
Name
Revision
Data Type
UINT
Value
1
Each instance of the Identity Object contains the following attributes:
6
7
3
4
1
2
Attribute
ID
5
Access Rule Name
Get
Get
Get
Get
Get
Vendor
Device Type
Product Code
Revision
Major Revision
Minor Revision
Status
Get
Get
Serial Number
Product Name
String Length
ASCII String
Data Type
UINT
UINT
UINT
Structure of:
USINT
USINT
WORD
Value
1 or 625
115 - Generic Type
208
UDINT
Structure of:
USINT
STRING
Bit 0 - 0=not owned; 1=owned by master
Bit 2 - 0=Factory Defaulted; 1=Configured
Bit 8 - Minor Recoverable fault
Bit 9 - Minor Unrecoverable fault
Bit 10 - Major Recoverable fault
Bit 11 - Major Unrecoverable fault unique number for each device
“DeviceNet™ HIM” or “Boot Code”
A-2
The following common services are implemented for the Identity Object:
Service Code
0x0E
0x05
0x10
Implemented for:
Class
No
No
No
Instance
Yes
Yes
No
Service Name
Get_Attribute_Single
Reset
Set_attribute Single
Message Router CLASS CODE 0x0002
No class or instance attributes are supported. The message router object exists only to rout explicit messages to other objects.
DeviceNet™
Object
CLASS CODE 0x0003
The following class attributes will be supported for the DeviceNet™ Object:
Attribute ID
1
Access Rule
Get
Name
Revision
Data Type
UINT
Value
2
A single instance (instance 1) of the DeviceNet™ Object will be supported. The following instance attributes will be supported.
Attribute ID Access Rule
1 Get
Name Data Type
The following services will be implemented for the DeviceNet™ Object.
Service Code
0x0E
0x10
Implemented for:
Class
Yes
No
Instance
Yes
No
Value
0…63
Service Name
Get_Attribute_Single
Set_Attribute_Single
Connection
Object
CLASS CODE 0x0005
No class attributes are supported for the Connection Object.
Multiple instances of the Connection Object are supported for explicit UCMM connections.
Attribute ID
1
5
8
9
6
7
12
2
3
4
13
14
15
16
Access Rule
Get
Get
Get
Get
Get
Get
Get
Get
Get/Set
Get
Get
Get
Get
Get
Name
State
Instance Type
Transport Class Trigger
Produced Connection ID
Consumed Connection ID
Initial Comm Characteristics
Produced Connection Size
Consumed Connection Size
Expected Packet Rate
Watchdog Action
Produced Connection Path Length
Produced Connection Path
Consumed Connection Path Length
Consumed Connection Path
Data Type Value
USINT 0=nonexistant
1=configuring
3=established
4=timed out
USINT
USINT
UINT
0=Explicit Message
0x83 - Server, Transport Class 3
UINT
Depends on message group and
Message ID
Depends on message group and
Message ID
USINT
UINT
UINT
UINT
USINT
0x33 (Group 3)
0 in milliseconds
01 = auto delete
03 = deferred delete
UINT
UINT
0
Empty
0
Empty
A-3
A-4
Publication CEP7-UM009A-EN-P - January 2007 PN 40754-658-01
Copyright ©2007 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
Advertisement
Key Features
- Device commissioning and configuration
- Program and monitor DeviceNet devices
- Upload and download complete device configurations
- DeviceLogix program support
- DeviceNet physical layer diagnostics
- Network bandwidth statistics
- Handheld design for portability