Configuring the DL06`s Comm Ports

Configuring the DL06`s Comm Ports
SYSTEM DESIGN AND
CONFIGURATION
CHAPTER
4
In This Chapter
DL06 System Design Strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . .4–2
Module Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4–3
Power Budgeting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4–5
Configuring the DL06’s Comm Ports . . . . . . . . . . . . . . . . . . . . . . . .4–7
Connecting to MODBUS and DirectNET Networks . . . . . . . . . . . . .4–9
Non–Sequence Protocol (ASCII In/Out and PRINT) . . . . . . . . . . . .4–11
Network Slave Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4–12
Network Master Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4–18
Network Master Operation (using MRX and MWX Instructions) . .4–22
Chapter 4: System Design and Configuration
DL06 System Design Strategies
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
I/O System Configurations
The DL06 PLCs offer a number of different I/O configurations. Choose the configuration
that is right for your application, and keep in mind that the DL06 PLCs offer the ability to
add I/O with the use of option cards. Although remote I/O isn’t available, there are many
option cards available. For instance:
• Various A/C and D/C I/O modules
• Combination I/O modules
• Analog I/O modules
• Combination Analog I/O modules
A DL06 system can be developed using several different arrangements using the option
modules. See our DL05/06 Options Modules User Manual (D0-OPTIONS-M) on the
website, www.automationdirect.com for detailed selection information.
Networking Configurations
The DL06 PLCs offers the following ways to add networking:
• Ethernet Communications Module Ҁ connects a DL06 to high-speed peer-to-peer networks. Any
PLC can initiate communications with any other PLC or operator interfaces, such as C-more, when
using the ECOM modules.
• Data Communications Modules Ҁ connects a DL06 to devices using either DeviceNet or Profibus
to link to master controllers, as well as a D0-DCM.
• Communications Port 1 Ҁ The DL06 has a 6-pin RJ12 connector on Port 1 that supports (as
slave) K-sequence, MODBUS RTU or DirectNET protocols.
• Communications Port 2 Ҁ The DL06 has a 15-pin connector on Port 2 that supports either
master/slave MODBUS RTU or DirectNET protocols, or K-sequence protocol as slave. (MRX and
MWX instructions allow you to enter native MODBUS addressing in your ladder program with no
need to perform octal to decimal conversions). Port 2 can also be used for ASCII IN/OUT
communictions.
4–2
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Chapter 4: System Design and Configuration
Module Placement
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Slot Numbering
The DL06 has four slots, which are numbered as follows:
Slot 1
Slot 2
Slot 3
Slot 4
DL06 Micro PLC User Manual; 3rd Edition Rev. A
4–3
Chapter 4: System Design and Configuration
Automatic I/O Configuration
The DL06 CPUs automatically detect any installed I/O modules (including specialty
modules) at powerup, and establish the correct I/O configuration and addresses. This applies
to modules located in the local base. For most applications, you will never have to change the
configuration.
I/O addresses use octal numbering, starting at X100 and Y100 in the slot next to the CPU.
The addresses are assigned in groups of 8, or 16 depending on the number of points for the
I/O module. The discrete input and output modules can be mixed in any order. The
following diagram shows the I/O numbering convention for an example system. Both the
Handheld Programmer and DirectSOFT 5 provide AUX functions that allow you to
automatically configure the I/O. For example, with the Handheld Programmer AUX 46
executes an automatic configuration, which allows the CPU to examine the installed modules
and determine the I/O configuration and addressing.With DirectSOFT 5, the PLC
Configure I/O menu option would be used.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Automatic
Manual
Slot 1
Slot 2
Slot 3
8pt. Input 16pt. Output 16pt. Input
X100–X107 Y100–Y117 X110–X127
Slot 4
8pt. Input
X130–X137
Slot 1
Slot 2
Slot 3
8pt. Input 16pt. Output 16pt. Input
X100–X107 Y100–Y117 X200–X217
Slot 4
8pt. Input
X120–X127
Manual I/O Configuration
It may never become necessary, but DL06 CPUs allow manual I/O address assignments for
any I/O slot(s) . You can manually modify an auto configuration to match arbitrary I/O
numbering. For example, two adjacent input modules can have starting addresses at X100
and X200.Use DirectSOFT 5 PLC Configure I/O menu option to assign manual I/O
address. In automatic configuration, the addresses are assigned on 8-point boundaries.
Manual configuration, however, assumes that all modules are at least 16 points, so you can
only assign addresses that are a multiple of 20 (octal). You can still use 8 point modules, but
16 addresses will be assigned and the upper eight addresses will be unused.
WARNING: If you manually configure an I/O slot, the I/O addressing for the other modules may
change. This is because the DL06 CPUs do not allow you to assign duplicate I/O addresses. You
must always correct any I/O configuration errors before you place the CPU in RUN mode.
Uncorrected errors can cause unpredictable machine operation that can result in a risk of personal
injury or damage to equipment.
4–4
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Chapter 4: System Design and Configuration
Power Budgeting
The DL06 has four option card slots. To determine whether the combination of cards you
select will have sufficient power, you will need to perform a power budget calculation.
Power supplied
Power is supplied from two sources, the internal base unit power supply and, if required, an
external supply (customer furnished). The D0-06xx (AC powered) PLCs supply a limited
amount of 24VDC power. The 24VDC output can be used to power external devices.
For power budgeting, start by considering the power supplied by the base unit. All DL06
PLCs supply the same amount of 5VDC power. Only the AC units offer 24VDC auxiliary
power. Be aware of the trade-off between 5VDC power and 24VDC power. The amount of
5VDC power available depends on the amount of 24VDC power being used, and the
amount of 24VDC power available depends on the amount of 5VDC power consumed.
Determine the amount of internally supplied power from the table on the following page.
Power required by base unit
Because of the different I/O configurations available in the DL06 family, the power
consumed by the base unit itself varies from model to model. Subtract the amount of power
required by the base unit from the amount of power supplied by the base unit. Be sure to
subtract 5VDC and 24VDC amounts.
Power required by option cards
Next, subtract the amount of power required by the option cards you are planning to use.
Again, remember to subtract both 5VDC and 24VDC. If your power budget analysis shows
surplus power available, you should have a workable configuration.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
4–5
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Chapter 4: System Design and Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
DL06 Power Consumed
by Option Cards
DL06 Power Supplied by Base Units
Part Number
5 VDC (mA)
24 VDC (mA)
<1500mA
<2000mA
1500mA
300mA
200mA
none
D0-06xx
D0-06xx-D
If the 5VDC loading is less than 2000mA, but more than
1500mA, then available 24VDC supply current is 200mA.
If the 5VDC loading is less than 1500mA, then the
available 24VDC current is 300mA.
DL06 Base Unit Power Required
Part Number
D0-06AA
D0-06AR
D0-06DA
D0-06DD1
D0-06DD2
D0-06DR
D0-06DD1-D
D0-06DD2-D
D0-06DR-D
5 VDC (mA)
24 VDC (mA)
800mA
900mA
800mA
600mA
600mA
950mA
600mA
600mA
950mA
none
none
none
280mA, note 1
none
none
280mA, note 1
none
none
Power Budgeting Example
Power Source
D0-06DD1
(select row
A or row B)
A
1500mA
300mA
B
2000mA
200mA
Current Required
D0-06DD1
D0-16ND3
D0-10TD1
D0-08TR
F0-4AD2DA-2
D0-06LCD
Total Used
Remaining
5VDC
24VDC
power (mA) power (mA)
A
B
Part Number
D0-07CDR
D0-08CDD1
D0-08TR
D0-10ND3
D0-10ND3F
D0-10TD1
D0-10TD2
D0-16ND3
D0-16TD1
D0-16TD2
D0-DCM
D0-DEVNETS
F0-04TRS
F0-08NA-1
F0-04AD-1
F0-04AD-2
F0-2AD2DA-2
F0-4AD2DA-1
F0-4AD2DA-2
F0-04RTD
F0-04THM
F0-CP128
H0-PSCM
H0-ECOM
H0-CTRIO
5 VDC (mA)
130mA
100mA
280mA
35mA
35mA
150mA
150mA
35mA
200mA
200mA
250mA
45mA
250mA
5mA
50mA
75mA
50mA
100mA
100mA
70mA
30mA
150mA
530mA
250mA
250mA
24 VDC (mA)
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
30mA
40mA
none
none
none
none
none
none
none
5VDC
24VDC
power (mA) power (mA)
600mA
35mA
150mA
280mA
100mA
50mA
1215mA
285mA
785mA
280mA, note 1
0
0
0
0
0
280mA
20mA
note 2
NOTE: See the DL05/DL06 OPTIONS
manual
DL06 Power Consumed by Other Devices
Part Number
D0-06LCD
D2-HPP
DV1000
5 VDC (mA)
24 VDC (mA)
50mA
200mA
150mA
none
none
none
NOTE 1: Auxiliary 24VDC used to power V+ terminal of D0-06DD1/-D sinking outputs.
NOTE 2: If the PLC’s auxiliary 24VDC power source is used to power the sinking outputs, use power
choice A, above.
4–6
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Chapter 4: System Design and Configuration
Configuring the DL06’s Comm Ports
This section describes how to configure the CPU’s built-in networking ports for either
MODBUS or DirectNET. This will allow you to connect the DL06 PLC system directly to
MODBUS networks using the RTU protocol, or to other devices on a DirectNET network.
MODBUS masters on the network must be capable of issuing the MODBUS commands to
read or write the appropriate data. For details on the MODBUS protocol, please refer to the
Gould MODBUS Protocol reference Guide (P1–MBUS–300 Rev. B). In the event a more
recent version is available, check with your MODBUS supplier before ordering the
documentation. For more details on DirectNET, order our DirectNET manual, part number
DA–DNET–M.
NOTE: For information about the MODBUS protocol see the Group Schneider Web site at:
www.schneiderautomation.com. At the main menu, select Support/Services, Modbus, Modbus Technical
Manuals, PI-MBUS-300 Modbus Protocol Reference Guide or search for PIMBUS300. For more
information about the DirectNET protocol, order our DirectNET user manual, part number
DA–DNET–M, or download it free from our Web site: www.automationdirect.com. Select
Documentation/Misc./DA-DNET-M.
DL06 Port Specifications
Communications Port 2
Communications Port 1
Connects to HPP, DirectSOFT 5, operator
interfaces, etc.
6-pin, RS232C
Communication speed (baud): 9600 (fixed)
Parity: odd (fixed)
Port 1 Station Address: 1 (fixed)
8 data bits
1 start, 1 stop bit
Asynchronous, half-duplex, DTE
Protocol (auto-select): K-sequence (slave only),
DirectNET (slave only), MODBUS (slave only)
Connects to HPP, DirectSOFT 5, operator
interfaces, etc.
15-pin, multifunction port, RS232C, RS422, RS485
Communication speed (baud): 300, 600, 1200,
2400, 4800, 9600, 19200, 38400
Parity: odd (default), even, none
Port 2 Station Address: 1 (default)
8 data bits
1 start, 1 stop bit
Asynchronous, half-duplex, DTE
Protocol (auto-select): K-sequence (slave only),
DirectNET (master/slave), MODBUS (master/slave),
non-sequence/print/ASCII in/out
Port 2 Pin Descriptions
DL06 Port Pinouts
Port 1 Pin Descriptions
TERM
PORT1
PORT2
R
RUN STOP
5 4 3 2
6
1
5
1
10
6
15
PORT1
11
PORT2
1
2
3
4
5
6
0V
5V
RXD
TXD
5V
0V
Power (-) connection (GND)
Power (+) connection
Receive data (RS-232C)
Transmit data (RS-232C)
Power (+) connection
Power (-) connection (GND)
1 5V
2 TXD
3 RXD
4 RTS
5 CTS
6 RXD7 0V
8 0V
9 TXD+
10 TXD11 RTS+
12 RTS13 RXD+
14 CTS+
15 CTS-
Power (+) connection
Transmit data (RS-232C)
Receive data (RS-232C)
Ready to send (RS-232C)
Clear to send (RS232C)
Receive data (-) (RS-422/485)
Power (-) connection (GND)
Power (-) connection (GND)
Transmit data (+) (RS-422/485)
Transmit data (-) (RS-422/485)
Ready to send (+) (RS-422/485)
Ready to send (-) (RS-422/485)
Receive data (+) (RS-422/485)
Clear to send (+) (RS-422/485)
Clear to send (-) (RS-422/485)
DL06 Micro PLC User Manual; 3rd Edition Rev. A
4–7
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Chapter 4: System Design and Configuration
Choosing a Network Specification
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
The DL06 PLC’s multi-function port gives you the option of using RS-232C, RS-422, or
RS-485 specifications. First, determine whether the network will be a 2-wire RS–232C type,
a 4-wire RS–422 type, or a 2-wire/4-wire RS-485 type.
The RS–232C specification is simple to implement for networks of shorter distances (15
meters max) and where communication is only required between two devices. The RS–422
and RS-485 signals are for networks that cover longer distances (1000 meters max.) and for
multi-drop networks (from 2 to 247 devices).
NOTE: Termination resistors are required at both ends of RS–422 and RS-485 networks. It is necessary to
select resistors that match the impedance rating of the cable (between 100 and 500 ohms).
11
1
Signal GND
GND
RXD
0V
3
RXD
RXD
4
TXD
TXD
TXD
TXD
RXD
CTS
PORT1
6P6C
Phone Jack
RTS
RTS
Connections on Port 1
CTS
Connections on Port 2
10
Signal GND
1
15
Point-to-point
DTE Device
5
Normally, the RS-232
signals are used for
shorter distances (15
meters maximum), for
communications
between two devices.
6
RS-232 Network
RTS
OR
Loop
Back
CTS
RS-422 Network
RS-422 signals are for
long distances ( 1000
meters maximum). Use
terminator resistors at
both ends of RS-422
network wiring,
matching the impedence
rating of the cable
(between 100 and 500
ohms).
RXD+
RXD–
TXD+
TXD–
Signal GND
RS-485 Network
TXD– / RXD–
Signal GND
Signal GND
Signal GND
RXD–
1
11
0V
RTS+
RXD+
TXD–
DL06 Micro PLC User Manual; 3rd Edition Rev. A
RTS–
CTS+
recommended for
RS-485 networks.
15
10
CTS–
Belden 9841, or
Cable: Use Belden
equivalent,
is
9841
or equivalent
CTS–
15
CTS+
RTS+
TXD+
10
RTS–
5
RXD+
11
6
RXD–
6
1
0V
5
TXD– / RXD–
Connect shield
to signal ground
DL06 CPU Port 2
4–8
PORT 2
Master
TXD+ / RXD+
TXD+ / RXD+
TXD– / RXD–
TXD+
Termination
Resistor at
both ends of
network
Termination
Resistor
TXD+ / RXD+
RS-485 signals are for
longer distances (1000
meters max) and for
multi-drop networks.
Use termination
resistors at both ends
of RS-485 network
wiring, matching the
impedance rating of
the cable (between
100 and 500 ohms).
9 TXD+
10 TXD–
13 RXD+
6 RXD–
11 RTS+
12 RTS–
14 CTS+
15 CTS–
7 0V
We recommend Belden 8102
The recommended cable
shielded
twisted
cable, or
for RS422
is pair
Belden
equivalent,
used for RS-422
9729 orbe
equivalent.
networks.
TXD–
DL06 CPU Port 2
Chapter 4: System Design and Configuration
Connecting to MODBUS and DirectNET Networks
MODBUS Port Configuration
In DirectSOFT 5, choose the PLC menu, then Setup, then “Secondary Comm Port”.
• Port: From the port number list box at the top, choose “Port 2”.
• Protocol: Check the box to the left of “MODBUS” (use AUX 56 on the HPP, and select
“MBUS”), and then you’ll see the box below.
• Timeout: amount of time the port will wait after it sends a message to get a response before logging
an error.
• RTS ON / OFF Delay Time: The RTS ON Delay Time specifies the time the DL06 waits to send
the data after it has raised the RTS signal line. The RTS OFF Delay Time specifies the time the
DL06 waits to release the RTS signal line after the data has been sent. When using the DL06 on a
multi-drop network, the RTS ON Delay time must be set to 5ms or more and the RTS OFF Delay time
must be set to 2ms or more. If you encounter problems, the time can be increased.
• Station Number: For making the CPU port a MODBUS master, choose “1”. The possible range
for MODBUS slave numbers is from 1 to 247, but the DL06 network instructions used in Master
mode will access only slaves 1 to 99. Each slave must have a unique number. At powerup, the port
is automatically a slave, unless and until the DL06 executes ladder logic network instructions which
use the port as a master. Thereafter, the port reverts back to slave mode until ladder logic uses the
port again.
• Baud Rate: The available baud rates include 300, 600, 1200, 2400, 4800, 9600, 19200, and 38400
baud. Choose a higher baud rate initially, reverting to lower baud rates if you experience data errors
or noise problems on the network. Important: You must configure the baud rates of all devices on
the network to the same value. Refer to the appropriate product manual for details.
• Stop Bits: Choose 1 or 2 stop bits for use in the protocol.
• Parity: Choose none, even, or odd parity for error checking.
•Echo Suppression: Select the appropriate wiring configuration used on Port 2.
Then click the button indicated to send the Port configuration to the CPU, and click
Close.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
4–9
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
Chapter 4: System Design and Configuration
DirectNET Port Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–10
In DirectSOFT 5, choose the PLC menu, then Setup, then “Secondary Comm Port”.
• Port: From the port number list box, choose “Port 2 ”.
• Protocol: Check the box to the left of “DirectNET” (use AUX 56 on the HPP, then select
“DNET”), and then you’ll see the dialog below.
• Timeout: Amount of time the port will wait after it sends a message to get a response before logging
an error.
• RTS ON / OFF Delay Time: The RTS ON Delay Time specifies the time the DL06 waits to send
the data after it has raised the RTS signal line. The RTS OFF Delay Time specifies the time the
DL06 waits to release the RTS signal line after the data has been sent. When using the DL06 on a
multi-drop network, the RTS ON Delay time must be set to 5ms or more and the RTS OFF Delay time
must be set to 2ms or more. If you encounter problems, the time can be increased.
• Station Number: For making the CPU port a DirectNET master, choose “1”. The allowable range
for DirectNET slaves is from 1 to 90 (each slave must have a unique number). At powerup, the port
is automatically a slave, unless and until the DL06 executes ladder logic instructions which attempt
to use the port as a master. Thereafter, the port reverts back to slave mode until ladder logic uses the
port again.
• Baud Rate: The available baud rates include 300, 600, 1200, 2400, 4800, 9600, 19200, and 38400
baud. Choose a higher baud rate initially, reverting to lower baud rates if you experience data errors
or noise problems on the network. Important: You must configure the baud rates of all devices on
the network to the same value.
• Stop Bits: Choose 1 or 2 stop bits for use in the protocol.
• Parity: Choose none, even, or odd parity for error checking.
• Format: Choose between hex or ASCII formats.
Then click the button indicated to send the Port configuration to the CPU, and click
Close.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Chapter 4: System Design and Configuration
Non–Sequence Protocol (ASCII In/Out and PRINT)
Non-Sequence Port Configuration
Configuring port 2 on the DL06 for Non–Sequence allows the CPU to use port 2 to either
read or write raw ASCII strings using the ASCII instructions. See the ASCII In/Out
instructions and the PRINT instruction in chapter 5.
In DirectSOFT 5, choose the PLC menu, then Setup, then “Secondary Comm Port”.
• Port: From the port number list box at the top, choose “Port 2”.
• Protocol: Check the box to the left of “Non–Sequence”.
• Timeout: Amount of time the port will wait after it sends a message to get a response before logging
an error.
• RTS On Delay Time: The amount of time between raising the RTS line and sending the data.
• RTS Off Delay Time: The amount of time between resetting the RTS line after sending the data.
• Data Bits: Select either 7–bits or 8–bits to match the number of data bits specified for the
connected devices.
• Baud Rate: The available baud rates include 300, 600, 900, 2400, 4800, 9600, 19200, and 38400
baud. Choose a higher baud rate initially, reverting to lower baud rates if you experience data errors
or noise problems on the network. Important: You must configure the baud rates of all devices on
the network to the same value. Refer to the appropriate product manual for details.
• Stop Bits: Choose 1 or 2 stop bits to match the number of stop bits specified for the connected
devices.
• Parity: Choose none, even, or odd parity for error checking. Be sure to match the parity specified
for the connected devices.
• Echo Suppression: Select the appropriate radio button based on the wiring configuration used on
port 2.
• Xon/Xoff Flow Control: Choose this selection if you have Port 2 wired for Hardware Flow Control
(Xon/Xoff ) with RTS and CTS signal connected between all devices.
• RTS Flow Control: Choose this selection if you have Port 2 RTS signal wired between all devices.
Click the button indicated to send the port configuration to the CPU, and click Close.
• Memory Address: Starting V-memory address for ASCII IN data storage, 128 byte maximum
(see AIN instruction).
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–11
Chapter 4: System Design and Configuration
Network Slave Operation
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
This section describes how other devices on a network can communicate with a CPU port
that you have configured as a DirectNET slave or MODBUS slave (DL06). A MODBUS
host must use the MODBUS RTU protocol to communicate with the DL06 as a slave. The
host software must send a MODBUS function code and MODBUS address to specify a PLC
memory location the DL06 comprehends. The DirectNET host uses normal I/O addresses to
access applicable DL06 CPU and system. No CPU ladder logic is required to support either
MODBUS slave or DirectNET slave operation.
NOTE: For more intformation on DirectNET proprietary protocol, see the DirectNET reference
manual, DA-DNET-M, available on our website.
MODBUS Function Codes Supported
MODBUS Function Code
Function
DL06 Data Types Available
01
02
05
15
03, 04
06
16
Read a group of coils
Read a group of inputs
Set / Reset a single coil
Set / Reset a group of coils Y,
Read a value from one or more registers
Write a value into a single register
Write a value into a group of registers
Y, CR, T, CT
X, SP
Y, CR, T, CT
CR, T, CT
V
V
V
The MODBUS function code determines whether the access is a read or a write, and whether
to access a single data point or a group of them. The DL06 supports the MODBUS function
codes described below.
Determining the MODBUS Address
4–12
There are typically two ways that most host software conventions allow you to specify a PLC
memory location. These are:
• By specifying the MODBUS data type and address
• By specifying a MODBUS address only
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Chapter 4: System Design and Configuration
If Your Host Software Requires the Data Type and Address
Many host software packages allow you to specify the MODBUS data type and the
MODBUS address that corresponds to the PLC memory location. This is the easiest method,
but not all packages allow you to do it this way.
The actual equation used to calculate the address depends on the type of PLC data you are
using. The PLC memory types are split into two categories for this purpose.
• Discrete – X, SP, Y, CR, S, T, C (contacts)
• Word – V, Timer current value, Counter current value
In either case, you basically convert the PLC octal address to decimal and add the appropriate
MODBUS address (if required). The table below shows the exact equation used for each
group of data.
DL06 Memory Type
QTY
(Decimal)
PLC Range
(Octal)
MODBUS Address
Range
MODBUS Data Type
(Decimal)
For Discrete Data Types .... Convert PLC Addr. to Dec. + Start of Range + Data Type
512
X0 – X777
2048 – 2559
Input
Inputs (X)
512
SP0 – SP777
3072 – 3583
Input
Special Relays(SP)
512
Y0 – Y777
2048 – 2559
Coil
Outputs (Y)
1024
C0 – C1777
3072 – 4095
Coil
Control Relays (CR)
256
T0 – T377
6144 – 6399
Coil
Timer Contacts (T)
128
CT0 – CT177
6400 – 6527
Coil
Counter Contacts (CT)
1024
S0 – S1777
5120 – 6143
Coil
Stage Status Bits(S)
For Word Data Types .... Convert PLC Addr. to Dec. + Data Type
256
V0 – V377
0 – 255
Input Register
Timer Current Values (V)
128
V1000 – V1177
512 – 639
Input Register
Counter Current Values (V)
V-Memory, user data (V)
V-Memory, non-volatile (V)
3200
4096
128
V1200 – V7377
V10000 - V17777
V7400 – V7577
640 – 3839
4096 - 8191
3840 – 3967
Holding Register
Holding Register
Holding Register
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–13
Chapter 4: System Design and Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
The following examples show how to generate the MODBUS address and data type for hosts
which require this format.
Example 1: V2100
Find the MODBUS address for User V location V2100.
Holding Reg 1088
1. Find V-memory in the table.
2. Convert V2100 into decimal (1088).
3. Use the MODBUS data type from the table.
V-memory, user data (V)
3200
V1200 – V7377
640 – 3839
Holding Register
Example 2: Y20
Find the MODBUS address for output Y20.
1. Find Y outputs in the table.
Coil 2064
2. Convert Y20 into decimal (16).
3. Add the starting address for the range (2048).
4. Use the MODBUS data type from the table.
Outputs (V)
256
Y0 – Y377
2048 - 2303
Coil
Example 3: T10 Current Value
Find the MODBUS address to obtain the current value from Timer T10.
1. Find Timer Current Values in the table.
Input Reg. 8
2. Convert T10 into decimal (8).
3. Use the MODBUS data type from the table.
Timer Current Values (V)
128
V0 – V177
0 - 127
Input Register
Example 4: C54
4–14
Find the MODBUS address for Control Relay C54.
1. Find Control Relays in the table.
Coil 3116
2. Convert C54 into decimal (44).
3. Add the starting address for the range (3072).
4. Use the MODBUS data type from the table.
Control Relays (CR)
512
C0 – C77
3072 – 3583
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Coil
Chapter 4: System Design and Configuration
If Your MODBUS Host Software Requires an Address ONLY
Some host software does not allow you to specify the MODBUS data type and address.
Instead, you specify an address only. This method requires another step to determine the
address, but it’s still fairly simple. Basically, MODBUS also separates the data types by address
ranges as well. So this means an address alone can actually describe the type of data and
location. This is often referred to as “adding the offset”. One important thing to remember
here is that two different addressing modes may be available in your host software package.
These are:
• 484 Mode
• 584/984 Mode
We recommend that you use the 584/984 addressing mode if your host software allows you
to choose. This is because the 584/984 mode allows access to a higher number of memory
locations within each data type. If your software only supports 484 mode, then there may be
some PLC memory locations that will be unavailable. The actual equation used to calculate
the address depends on the type of PLC data you are using. The PLC memory types are split
into two categories for this purpose.
• Discrete – X, SP, Y, CR, S, T (contacts), C (contacts)
• Word – V, Timer current value, Counter current value
In either case, you basically convert the PLC octal address to decimal and add the appropriate
MODBUS addresses (as required). The table below shows the exact equation used for each
group of data.
Discrete Data Types
DL06 Memory Type
Global Inputs (GX)
Inputs (X)
Special Relays (SP)
Global Outputs (GY)
Outputs (Y)
Control Relays (CR)
Timer Contacts (T)
Counter Contacts (CT)
Stage Status Bits (S)
PLC Range
(Octal)
GX0-GX1746
GX1747-GX3777
X0 – X1777
SP0 – SP777
GY0 - GY3777
Y0 – Y1777
C0 – C3777
T0 – T377
CT0 – CT377
S0 – S1777
Address (484 Address (584/984 MODBUS Data
Mode)
Mode)
Type
1001 - 1999
------1 - 2048
2049 - 3072
3073 - 5120
6145 - 6400
6401 - 6656
5121 - 6144
10001 - 10999
11000 - 12048
12049 - 13072
13073 - 13584
1 - 2048
2049 - 3072
3073 - 5120
6145 - 6400
6401 - 6656
5121 - 6144
Input
Input
Input
Input
Output
Output
Output
Output
Output
Output
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–15
Chapter 4: System Design and Configuration
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–16
Registers
V-memory (Timers)
V-memory (Counters)
V-memory (Data Words)
Word Data Types
PLC Range Input/Holding Input/Holding
(Octal)
(484 Mode)* (584/984 Mode)*
V0 - V377
V1000 - V1177
V1200 - V1377
V1400 - V1746
V1747 - V1777
V2000 - V7377
V10000 - V17777
3001/4001
3513/4513
3641/4641
3769/4769
-------
30001/40001
30513/40513
30641/40641
30769/40769
31000/41000
41025
44097
* MODBUS: Function 04
The DL05/06, DL250-1/260, DL350 and DL450 will support function 04, read input
register (Address 30001). To use function 04, put the number ‘4’ into the most significant
position (4xxx). Four digits must be entered for the intruction to work properly with this
mode.
LD
K101
LD
K4128
LDA
O4000
The Maximum constant possible is 4128. This
is due to the 128 maximum number of Bytes
that the RX/WX instruction can allow. The
value of 4 in the most significant position of the
word will cause the RX to use function 04
(30001 range).
RX
Y0
1. Refer to your PLC user manual for the correct memory mapping size of your PLC. Some of
the addresses shown above might not pertain to your particular CPU.
2. For an automated MODBUS/Koyo address conversion utility, go to our website,
www.automationdirect.com, and down load download the EXCEL file
modbus_conversion.xls located at: Tech Support > Technical Support Home page.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Chapter 4: System Design and Configuration
Example 1: V2100 584/984 Mode
Find the MODBUS address for User V location V2100.
PLC Address (Dec.) + Mode Address
1. Find V-memory in the table.
V2100 = 1088 decimal
2. Convert V2100 into decimal (1088).
1088 + 40001 =
41089
3. Add the MODBUS starting address for the
mode (40001).
For Word Data Types....
Timer Current Values (V)
Counter Current Values (V)
V-memory, user data (V)
PLC Address (Dec.)
128
128
1024
V0 – V177
V1200 – V7377
V2000 – V3777
+
Appropriate Mode Address
0 – 127
512 – 639
1024 – 2047
3001
3001
4001
30001
30001
40001
Input Register
Input Register
Holding Register
Example 2: Y20 584/984 Mode
Find the MODBUS address for output Y20.
PLC Addr. (Dec.) + Start Address + Mode
1. Find Y outputs in the table.
Y20 = 16 decimal
2. Convert Y20 into decimal (16).
16 + 2048 + 1 =
2065
3. Add the starting address for the range (2048).
4. Add the MODBUS address for the mode (1).
Outputs (Y)
Control Relays (CR)
Timer Contacts (T)
320
256
128
Y0 - Y477
C0 - C377
T0 - T177
2048 - 2367
3072 - 3551
6144 - 6271
1
1
1
1
1
1
Coil
Coil
Coil
Example 3: T10 Current Value 484 Mode
Find the MODBUS address to obtain the
current value from Timer T10.
PLC Address (Dec.) + Mode Address
TA10 = 8 decimal
1. Find Timer Current Values in the table.
8 + 3001 =
3009
2. Convert T10 into decimal (8).
3. Add the MODBUS starting address for the mode (3001).
For Word Data Types....
Timer Current Values (V)
Counter Current Values (V)
V-memory, user data (V)
PLC Address (Dec.)
128
128
1024
V0 – V177
V1200 – V7377
V2000 – V3777
+
0 – 127
512 – 639
1024 – 2047
Appropriate Mode Address
3001
3001
4001
30001
30001
40001
Input Register
Input Register
Holding Register
Example 4: C54 584/984 Mode
Find the MODBUS address for Control Relay C54. PLC Addr. (Dec.) + Start Address + Mode
1. Find Control Relays in the table.
C54 = 44 decimal
2. Convert C54 into decimal (44).
44 + 3072 + 1 =
3117
3. Add the starting address for the range (3072).
4. Add the MODBUS address for the mode (1).
Outputs (Y)
Control Relays (CR)
Timer Contacts (T)
320
256
128
Y0 - Y477
C0 - C377
T0 - T177
2048 - 2367
3072 - 3551
6144 - 6271
1
1
1
1
1
1
Coil
Coil
Coil
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–17
Chapter 4: System Design and Configuration
Network Master Operation
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–18
This section describes how the DL06 can communicate on a MODBUS or DirectNET
network as a master. For MODBUS networks, it uses the MODBUS RTU protocol, which
must be interpreted by all the slaves on the network. Both MODBUS and DirectNet are
single master/multiple slave networks. The master is the only member of the network that can
initiate requests on the network. This section teaches you how to design the required ladder
logic for network master operation.
0V
G
LG
Y0
Y2
C1
Y5
Y7 Y10 Y12
C3 Y15 Y17
AC(L) AC(N) 24V C0
Y1
Y3
Y4
Y6
C2
Y11 Y13 Y14 Y16 N.C.
OUTPUT: 6-240V
Y
0
X
1
2
50 - 60Hz
3
INPUT: 12 - 24V
4
2.0A, 6 - 27V
5
6
7
10
2.0A
11
12
PWR: 100-240V
13
14
15
16
PWR
RUN
CPU
TX1
RX1
TX2
RX2
50-60Hz 40VA
17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC
C0
06
K oyo
X1
X0
X3
X2
X4
C1
X6
X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C.
X15 X17 X20 X22 N.C.
X10 X12 C3
TERM
PORT1
PORT2
RUN STOP
Master
MODBUS RTU Protocol,, or DirectNET
Slave #1
Slave #2
Slave #3
When using the DL06 PLC as the master station, simple RLL instructions are used to initiate
the requests. The WX instruction initiates network write operations, and the RX instruction
initiates network read operations. Before executing either the WX or RX commands, we will
need to load data related to the read or write operation onto the CPU’s accumulator stack.
When the WX or RX instruction executes, it uses the information on the stack combined
with data in the instruction box to completely define the task, which goes to the port.
LG
Y0
Y2
C1
Y5
Y7 Y10 Y12
C3 Y15 Y17
G
0V
AC(L) AC(N) 24V C0
Y1
Y3
Y4
Y6
C2
Y11 Y13 Y14 Y16 N.C.
OUTPUT: 6-240V
Y
X
0
1
2
50 - 60Hz
3
INPUT: 12 - 24V
4
5
2.0A, 6 - 27V
6
7
10
2.0A
11
12
PWR: 100-240V
13
14
15
16
PWR
RUN
CPU
TX1
RX1
TX2
RX2
50-60Hz 40VA
17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC
C0
06
K oyo
X1
X0
X3
X2
X4
C1
X6
X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C.
X10 X12 C3
X15 X17 X20 X22 N.C.
TERM
PORT1
PORT2
RUN STOP
Master
Network
WX (write)
RX (read)
Slave
The following step-by-step procedure will provide you the information necessary to set up
your ladder program to receive data from a network slave.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Chapter 4: System Design and Configuration
Step 1: Identify Master Port # and Slave #
The first Load (LD) instruction identifies the
communications port number on the network
master (DL06) and the address of the slave
station. This instruction can address up to 99
MODBUS slaves, or 90 DirectNET slaves.
The format of the word is shown to the right.
The “F2” in the upper byte indicates the use of
the right port of the DL06 PLC, port number
2. The lower byte contains the slave address
number in BCD (01 to 99).
Step 2: Load Number of Bytes to Transfer
F
2
0
1
Slave address (BCD)
Port number (BCD)
Internal port (hex)
LD
KF201
6
4
(BCD)
The second Load (LD) instruction determines
the number of bytes which will be transferred
# of bytes to transfer
between the master and slave in the subsequent
WX or RX instruction. The value to be loaded
LD
is in BCD format (decimal), from 1 to 128
K64
bytes.
The number of bytes specified also depends on the type of data you want to obtain. For
example, the DL06 Input points can be accessed by V-memory locations or as X input
locations. However, if you only want X0 – X27, you’ll have to use the X input data type
because the V-memory locations can only be accessed in 2-byte increments. The following
table shows the byte ranges for the various types of DirectLOGIC products.
DL05 / 06 / 205 / 350 / 405 Memory
Bits per unit
Bytes
V-memory
T / C current value
Inputs (X, SP)
Outputs
(Y, C, Stage, T/C bits)
Scratch Pad Memory
Diagnostic Status
16
16
8
2
2
1
8
1
8
8
1
1
DL330 / 340 Memory
Bits per unit
Bytes
Data registers
T / C accumulator
I/O, internal relays, shift register bits, T/C
bits, stage bits
Scratch Pad Memory
Diagnostic Status(5 word R/W)
8
16
1
2
1
1
8
16
1
10
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–19
Chapter 4: System Design and Configuration
Step 3: Specify Master Memory Area
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4
The third instruction in the RX or WX sequence is a
Load Address (LDA) instruction. Its purpose is to
load the starting address of the memory area to be
transferred. Entered as an octal number, the LDA
instruction converts it to hex and places the result in
the accumulator.
For a WX instruction, the DL06 CPU sends the
number of bytes previously specified from its memory
area beginning at the LDA address specified.
For an RX instruction, the DL06 CPU reads the
number of bytes previously specified from the slave,
placing the received data into its memory area
beginning at the LDA address specified.
0
6
0
0
(octal)
Starting address of
master transfer area
LDA
O40600
MSB
V40600
LSB
15
MSB
0
V40601
LSB
15
0
NOTE: Since V-memory words are always 16 bits, you may not always use the whole word. For example, if
you only specify 3 bytes and you are reading Y outputs from the slave, you will only get 24 bits of data. In
this case, only the 8 least significant bits of the last word location will be modified. The remaining 8 bits are
not affected.
Step 4: Specify Slave Memory Area
The last instruction in our sequence is the WX or RX
instruction itself. Use WX to write to the slave, and RX
to read from the slave. All four of our instructions are
shown to the right. In the last instruction, you must
specify the starting address and a valid data type for the
slave.
SP116
LD
KF201
LD
K64
• DirectNET slaves – specify the same address in the WX
and RX instruction as the slave’s native I/O address
LDA
O40600
• MODBUS DL405, DL205, or DL06 slaves – specify the
same address in the WX and RX instruction as the slave’s
native I/O address
Y0
RX
• MODBUS 305 slaves – use the following table to convert
DL305 addresses to MODBUS addresses
DL305 Series CPU Memory Type–to–MODBUS Cross Reference (excluding 350 CPU)
PLC Memory Type
PLC Base
Address
TMR/CNT Current Values
R600
V0
I/O Points
Data Registers
Stage Status Bits (D3-330P only)
IO 000
R401,R400
S0
GY0
V100
GY200
4–20
MODBUS PLC Memory
Base Address
Type
TMR/CNT Status
Bits
Control Relays
Shift Registers
DL06 Micro PLC User Manual; 3rd Edition Rev. A
PLC Base
Address
MODBUS
Base Address
CT600
GY600
CR160
SR400
GY160
GY400
Chapter 4: System Design and Configuration
Communications from a Ladder Program
Typically network communications
SP117
Y1
will last longer than 1 scan. The
SET
program must wait for the
SP116
communications to finish before
LD
KF201
starting the next transaction.
Port Communication Error
Port 2, which can be a master, has two
LD
Port Busy
K0003
Special Relay contacts associated with
it (see Appendix D for comm port
LDA
O40600
special relays).One indicates “Port
busy”(SP116), and the other indicates
RX
Y0
”Port Communication Error”(SP117).
The example above shows the use of
these contacts for a network master that only reads a device (RX). The “Port Busy” bit is on
while the PLC communicates with the slave. When the bit is off the program can initiate the
next network request.
The “Port Communication Error” bit turns on when the
Interlocking Relay
PLC has detected an error. Use of this bit is optional.
SP116 C100
LD
When used, it should be ahead of any network instruction
KF201
boxes since the error bit is reset when an RX or WX
instruction is executed.
LD
K0003
Multiple Read and Write Interlocks
If you are using multiple reads and writes in the RLL
program, you have to interlock the routines to make sure
all the routines are executed. If you don’t use the
interlocks, then the CPU will only execute the first
routine. This is because each port can only handle one
transaction at a time.
In the example to the right, after the RX instruction is
executed, C100 is set. When the port has finished the
communication task, the second routine is executed and
C100 is reset.
If you’re using RLLPLUS Stage Programming, you can put
each routine in a separate program stage to ensure proper
execution and switch from stage to stage allowing only one
of them to be active at a time.
LDA
O40600
Interlocking
Relay
SP116
C100
RX
VY0
C100
SET
LD
KF201
LD
K0003
LDA
O40400
WX
VY0
C100
RST
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–21
Chapter 4: System Design and Configuration
Network Master Operation (using MRX and MWX
1 Instructions)
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
This section describes how the DL06 can communicate on a MODBUS RTU network as a
master using the MRX and MWX read/write instructions. These instructions allow you to
enter native MODBUS addressing in your ladder logic program with no need to perform
octal to decimal conversions. MODBUS is a single master/multiple slave network. The
master is the only member of the network that can initiate requests on the network. This
section teaches you how to design the required ladder logic for network master operation.
G
LG
Y0
Y2
C1
Y5
Y7 Y10 Y12
C3 Y15 Y17
0V
Y1
Y3
Y4
Y6
C2
Y11 Y13 Y14 Y16 N.C.
AC(L) AC(N) 24V C0
OUTPUT: 6-240V
Y
X
0
1
2
50 - 60Hz
3
INPUT: 12 - 24V
4
5
2.0A, 6 - 27V
6
7
10
2.0A
11
12
PWR: 100-240V
13
14
15
16
PWR
RUN
CPU
TX1
RX1
TX2
RX2
50-60Hz 40VA
17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC
C0
06
K oyo
X1
X0
X3
X2
X4
C1
X6
X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C.
X15 X17 X20 X22 N.C.
X10 X12 C3
TERM
PORT1
PORT2
RUN STOP
Master
MODBUS RTU Protocol,, or DirectNET
Slave #1
Slave #2
Slave #3
MODBUS Function Codes Supported
The MODBUS function code determines whether the access is a read or a write, and whether
to access a single data point or a group of them. The DL06 supports the MODBUS function
codes described below.
MODBUS Function Code
4–22
01
02
05
15
03, 04
06
07
08
16
Function
Read a group of coils
Read a group of inputs
Set / Reset a single coil (slave only)
Set / Reset a group of coils
Read a value from one or more registers
Write a value into a single register (slave only)
Read Exception Status
Diagnostics
Write a value into a group of registers
DL06 Micro PLC User Manual; 3rd Edition Rev. A
DL06 Data Types Available
Y, CR, T, CT
X, SP
Y, CR, T, CT
Y, CR, T, CT
V
V
V
V
V
Chapter 4: System Design and Configuration
MODBUS Read from Network(MRX)
The MODBUS Read from Network (MRX) instruction is used by the DL06 network master
to read a block of data from a connected slave device and to write the data into V–memory
addresses within the master. The instruction allows the user the to specify the MODBUS
Function Code, slave station address, starting master and slave memory addresses, number of
elements to transfer, MODBUS data format and the Exception Response Buffer.
• Port Number: must be DL06 Port 2 (K2)
• Slave Address: specify a slave station address (0–247)
• Function Code: The following MODBUS function codes are supported by the MRX
instruction:
01 – Read a group of coils
02 – Read a group of inputs
03 – Read holding registers
04 – Read input registers
07 – Read Exception status
08 – Diagnostics
• Start Slave Memory Address: specifies the starting slave memory address of the data to be
read. See the table on the following page.
• Start Master Memory Address: specifies the starting memory address in the master where
the data will be placed. See the table on the following page.
• Number of Elements: specifies how many coils, input, holding registers or input register
will be read. See the table on the following page.
• MODBUS Data Format: specifies MODBUS 584/984 or 484 data format to be used
• Exception Response Buffer: specifies the master memory address where the Exception
Response will be placed. See the table on the following page.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–23
Chapter 4: System Design and Configuration
MRX Slave Memory Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
MRX Slave Address Ranges
Function Code
MODBUS Data Format
Slave Address Range(s)
01 – Read Coil
01 – Read Coil
02 – Read Input Status
484 Mode
584/984 Mode
484 Mode
02 – Read Input Status
584/984 Mode
03 – Read Holding Register
484 Mode
03 – Read Holding Register
584/984
04 – Read Input Register
484 Mode
04 – Read Input Register
584/984 Mode
07 – Read Exception Status
08 – Diagnostics
484 and 584/984 Mode
484 and 584/984 Mode
1–999
1–65535
1001–1999
10001–19999 (5 digit) or 100001–165535
(6 digit)
4001–4999
40001–49999 (5 digit) or 4000001–465535
(6 digit)
3001–3999
30001–39999 (5 digit) or 3000001–365535
(6 digit)
n/a
0–65535
MRX Master Memory Addresses
MRX Master Memory Address Ranges
Operand Data Type
DL06 Range
Inputs X
Outputs Y
Control Relays C
Stage Bits S
Timer Bits T
Counter Bits CT
Special Relays SP
V–memory V
Global Inputs GX
Global Outputs GY
0–1777
0–1777
0–3777
0–1777
0–377
0–377
0–777
All
0–3777
0–3777
MRX Number of Elements
Number of Elements
DL06 Range
Operand Data Type
V–memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K
All
1–2000
MRX Exception Response Buffer
Exception Response Buffer
Operand Data Type
V–memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . V
4–24
DL06 Range
All
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Chapter 4: System Design and Configuration
MODBUS Write to Network (MWX)
The MODBUS Write to Network (MWX) instruction is used to write a block of data from
the network masters’s (DL06) memory to MODBUS memory addresses within a slave device
on the network. The instruction allows the user to specify the MODBUS Function Code,
slave station address, starting master and slave memory addresses, number of elements to
transfer, MODBUS data format and the Exception Response Buffer.
• Port Number: must be DL06 Port 2 (K2)
• Slave Address: specify a slave station address (0–247)
• Function Code: The following MODBUS function codes are supported by the MWX
instruction:
05 – Force Single coil
06 – Preset Single Register
08 – Diagnostics
15 – Force Multiple Coils
16 – Preset Multiple Registers
• Start Slave Memory Address: specifies the starting slave memory address where the data will
be written.
• Start Master Memory Address: specifies the starting address of the data in the master that is
to written to the slave.
• Number of Elements: specifies how many consecutive coils or registers will be written to.
This field is only active when either function code 15 or 16 is selected.
• MODBUS Data Format: specifies MODBUS 584/984 or 484 data format to be used.
• Exception Response Buffer: specifies the master memory address where the Exception
Response will be placed.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–25
Chapter 4: System Design and Configuration
Chapter 4: CPU Specifications and Operation
MWX Slave Memory Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
MWX Slave Address Ranges
Function Code
MODBUS Data Format
05 – Force Single Coil
05 – Force Single Coil
06 – Preset Single Register
484 Mode
584/984 Mode
484 Mode
06 – Preset Single Register
84/984 Mode
08 – Diagnostics
15 – Force Multiple Coils
15 – Force Multiple Coils
16 – Preset Multiple Registers
484 and 584/984 Mode
484
585/984 Mode
484 Mode
16 – Preset Multiple Registers
584/984 Mode
Slave Address Range(s)
1–999
1–65535
4001–4999
40001–49999 (5 digit) or
400001–465535 (6 digit)
0–65535
1–999
1–65535
4001–4999
40001–49999 (5 digit) or
4000001–465535 (6 digit)
MWX Master Memory Addresses
MRX Master Memory Address Ranges
Operand Data Type
DL06 Range
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stage Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Timer Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Counter Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Relays. . . . . . . . . . . . . . . . . . . . . . . . . . . .
V–memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Global Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Global Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .
X
Y
C
S
T
CT
SP
V
GX
GY
0–777
0–777
0–1777
0–1777
0–377
0–177
0–777
All
0–3777
0–3777
MWX Number of Elements
Number of Elements
Operand Data Type
DL06 Range
V–memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V
K
All
1–2000
MWX Exception Response Buffer
Exception Response Buffer
Operand Data Type
V–memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4–26
V
DL06 Range
All
DL06 Micro PLC User Manual; 3rd Edition Rev. A
Chapter 4: System Design and Configuration
MRX/MWX Example in DirectSOFT 5
DL06 port 2 has two Special Relay contacts associated with it (see Appendix D for comm
port special relays). One indicates “Port busy”(SP116), and the other indicates ”Port
Communication Error”(SP117). The “Port Busy” bit is on while the PLC communicates with
the slave. When the bit is off the program can initiate the next network request. The “Port
Communication Error” bit turns on when the PLC has detected an error and use of this bit is
optional. When used, it should be ahead of any network instruction boxes since the error bit
is reset when an MRX or MWX instruction is executed. Typically network communications
will last longer than 1 CPU scan. The program must wait for the communications to finish
before starting the next transaction.
The “Port Communication Error” bit turns on when the PLC has detected an error. Use of
this bit is optional. When used, it should be ahead of any network instruction boxes since the
error bit is reset when an RX or WX instruction is executed.
Multiple Read and Write Interlocks
If you are using multiple reads and writes in the RLL program, you have to interlock the
routines to make sure all the routines are executed. If you don’t use the interlocks, then the
CPU will only execute the first routine. This is because each port can only handle one
transaction at a time. In the example below, after the MRX instruction is executed, C100 is
set. When the port has finished the communication task, the second routine is executed and
C100 is reset. If you’re using RLLPLUS Stage Programming, you can put each routine in a
separate program stage to ensure proper execution and switch from stage to stage allowing
only one of them to be active at a time.
See example on the next page.
DL06 Micro PLC User Manual; 3rd Edition Rev. A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–27
Chapter 4: System Design and Configuration
Pulse/Minute
_1Minute
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
4–28
C20
( PD )
SP3
Calculation of communication transfer quantity per minute between PLC and device.
Pulse/Minute
2
LD
C20
CTA1
OUT
Transactions/Min
V3600
LD
CTA2
OUT
Errors/Minute
V3601
SP116 pulses on every transaction - CT1 counts the transactions per minute.
The counter is reset every minute.
Port 2 busy bit
3
CNT
SP116
Number of
transactions per
minute
Pulse/Minute
C20
CT1
K9999
SP117 pulses on every transaction - CT2 counts the errors per minute.
The counter is reset every minute.
Port 2 error bit
4
CNT
SP117
Number of errors
per minute
Pulse/Minute
C20
CT2
K9999
This rung does a MODBUS write to the first holding register 40001 of slave address number one.
It writes the values over that reside in V2000. This particular function code only writes to one
register. Use function code 16 to write to multiple registers. Only one Network Instruction
(WX, RX, MWX, MRX) can be enabled in one scan. That is the reason for the interlock bits. For using
many network instructions on the same port, use the Shift Register instruction.
Port 2 busy bit
SP116
C100
MWX
Port Number:
K2
Slave Address:
K1
Function Code: 06 - Preset Single Register
Start Slave Memory Address:
40001
Number of Elements:
n/a
Modbus Data Type:
584/984 Mode
Exception Response Buffer:
V400
3
Instruction interlock bit
C100
( SET )
This rung does a MODBUS read from the first 32 coils of slave address number one.
It will place the values into 32 bits of the master starting at C0.
Port 2 busy bit
4
SP116
C100
MRX
Port Number:
K2
Slave Address:
K1
Function Code:
01 - Read Coil Status
Start Slave Memory Address:
1
Start Master Memory Address:
C0
Number of Elements:
32
Modbus Data Type:
584/984 Mode
Exception Response Buffer:
V400
Instruction interlock bit
C100
( RST )
DL06 Micro PLC User Manual; 3rd Edition Rev. A