- No category
advertisement
▼
Scroll to page 2
of 52
Operating instructions for system users Heating system with weather−compensated, digital boiler and heating circuit control unit VITOTRONIC 300 5592492GB2/2005 Please keep safe Safety instructions For your safety Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions explained If you notice a smell of gas ¨ Danger ¨ Danger This symbol warns against the Escaping gas can lead to risk of injury. ! Please note This symbol warns against the risk of material losses and environmental pollution. Note Details identified by the word "Note" contain additional information. Target group These operating instructions are designed for heating system users. ¨ Danger Incorrect work on the heating If you smell flue gas ¨ Danger Flue gas can lead to life−threatening poisoning. H Shut down your heating system. H Ventilate the boiler room. H Close all doors leading to the living space. 5592492GB system can lead to life−threatening accidents. H Work on gas equipment must only be carried out by a registered gas fitter. H Electrical work must only be carried out by a qualified electrician. explosions which may lead to serious injury. H Do not smoke! Prevent naked flames and sparks. Never switch electrical lights or equipment. H Open windows and doors. H Close the gas shut−off valve. H Remove all people from the danger zone. H Observe the safety regulations of your local gas supplier found on the gas meter. H Notify your heating contractor from outside the building. 2 Safety instructions For your safety (cont.) In case of fire ¨ Danger With fire there is a risk of burning and explosion. H Shut down your heating system. H Close the shut−off valves of the main fuel lines. H Use a tested fire extinguisher, class ABC. Ancillary components, spare and wearing parts ! Please note Components which are not tested with the heating system may lead to damage to the heating system, or may affect their various functions. Installation or replacement must only be carried out by qualified personnel. Boiler room requirements ! Please note Incorrect ambient conditions can lead to damage to the heating system and put safe operation at risk. H Ensure ambient temperatures above 0ºC and below 35ºC. H Prevent air contamination by halogenated hydrocarbons (e.g. as contained in paints, solvents or cleaning fluids) and excessive dust (e.g. through grinding/polishing work). H Avoid continuously high humidity levels (e.g. through frequent drying of washing). H Never close existing ventilation apertures. 5592492GB 3 Index Index Introductory information Initial start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Your heating system is preset at the factory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 6 Where to find the controls Summary of controls and indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 H Opening the control unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 H Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 H Symbols in the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 H Heating circuit selectionbefore any adjustment and scanning . . . . . . . . . . . . . . . . . . 10 11 12 13 14 14 15 Room temperature setting Setting a permanent room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H Setting a standard room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H Setting a reduced room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H Setting a time program (switching times) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changing the room temperature for a few days only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H Setting a holiday program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changing the room temperature for a few hours only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H Setting economy mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H Setting party mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 17 17 18 20 20 22 22 23 Setting up DHW Setting up constant DHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H Setting the DHW temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H Setting a time program (switching times) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting up DHW for a few hours only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting up DHW once only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 25 26 30 31 5592492GB Start−up/shutdown Heating system start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heating system shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starting DHW and heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switching OFF DHW and heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starting DHW only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switching OFF DHW only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Index Index (cont.) Further settings Setting date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Language selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Modifying the boiler heating characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H Changing slope and level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H For technically−minded system users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjusting the display contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reinstating standard settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 32 33 33 35 36 36 Scanning options Temperature scanning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time program scanning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Scanning party or economy mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Scanning fault display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 38 39 39 What to do if...? Rooms are too cold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rooms are too hot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No DHW is available . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The DHW is too hot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The display flashes "Fault" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The display shows "Service" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The display shows "Remote control" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The display shows "External control" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The display shows "Central control" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The display shows "Slab curing program" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The display shows "Without function" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 43 44 45 45 45 45 46 46 46 46 Ordering fuel oil Fuel oil additives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Combustion improvers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Bio−fuels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Repairs Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Inspection and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 5592492GB Keyword index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 5 Introductory information Initial start−up The initial start−up and matching of the control unit to local conditions and the structural characteristics of the building must be carried out by your heating contractor. As the user of new combustion equipment, you are obliged to notify the installation to your local flue gas inspector (check local regulations). Your local flue gas inspector will also inform you (where appropriate) about work he may be required to carry out on your combustion equipment (e.g. regular checks, cleaning). Your heating system is preset at the factory You may change the factory settings in accordance with individual requirements. Note All data is saved in case of power failure. 5592492GB The control unit is preset at the factory. Your heating system is therefore ready for use: H Between 06:00 and 22:00h, central heating operates with standard room temperature. H Between 05:30 and 22.00h, DHW is heated (if a DHW cylinder is installed, DHW will be reheated to the set temperature), and the DHW circulation pump is ON (if connected to the control unit). H Between 22:00 and 06:00h, central heating operates with reduced room temperature (set to 3 ºC, frost protection). H Between 22:00 and 05:30h, DHW cylinder will not be reheated. H Weekday and time (CET), summer/winter time changeover is automatic. 6 Where to find the controls Summary of controls and indicators You can change all settings for your heating system, centrally, at the programming unit. You may also make such changes on the remote control units, if your system is equipped with such units. Separate operating instructions Opening the control unit A The programming unit is located behind the hinged cover. To open, pull the hinged cover from top edge down to the front. 5592492GB A Hinged cover 7 Where to find the controls Summary of controls and indicators (cont.) Functions C D E F G H Boiler temperature Mo N A ON/OFF indicator (green) (page11 and 12) B Fault indicator (red) (page39) C Emissions test switch (only for service) D Heating circuit selection keys (page10) E Control panel A Central heating time program (page18) B DHW heating time program (page26) C Circulation pump time program (page27) H Holiday program (page20) F DHW temperature (page 25) E Reduced room temperature (page 17) I Heating curve slope (page33) J Heating curve level (page33) D Time/date (page32) K Standby mode 8 M LK L DHW only G Heating and DHW N Economy mode (page22) M Party mode (page23) a/b Adjusting values d Confirmation c Information (page32 and 37) e Standard setting (page36) F Rotary selector"ts" for "Standard room temperature" (page17)) G Control thermostat H Excess temperature reset K ON/OFF switch (page11 and 12) L Fuses M Test switch (only for service) N Open flap 5592492GB BA Where to find the controls Summary of controls and indicators (cont.) Symbols in the display These symbols are not permanently displayed, but appear subject to the system version and the operating state. Flashing displays indicate that modifications can be made. e s 5592492GB if frost is possible for central heating with standard room temperature m for central heating with reduced room temperature e p, s p, m p Heating circuit pump running | Mixer "open" ~ Mixer "close" w DHW heating enabled w p Cylinder primary pump running, DHW is being heated p DHW heating via solar heating system A Burner "ON" u Time adjustment and display S Emissions test function "ON" Q Radio clock reception (only with radio clock module, accessory) 9 Where to find the controls Summary of controls and indicators (cont.) Heating circuit selectionbefore any adjustment and scanning Your building may be heated by several interdependent heating circuits (e.g. underfloor heating circuits or radiator circuits). These are selected at the control unit using keys!, ? or §. Your heating contractor will label the keys individually. Heating system with only one heating circuit Key ! or ? and one of the keysG, L or K are illuminated, and you can begin your adjustments. Heating system with two or three heating circuits Choose the required heating circuit before every adjustment and scanning. Heating circuit A1 1r Press ! or ? or §. The following keys will be illuminated: H Key!, ? or § H KeyG, L or K H KeyM or N (if active) 5592492GB Note If you make no adjustments, the key illumination will extinguish after a short time. 10 Start−up/shutdown Heating system start−up 1. Check the pressure of your heating system on the pressure gauge. The system pressure is too low if the indicator points to the area below the red field. In that case, top up with water or notify your local heating contractor. 2. Open the shut−off valves in the oil supply lines (at the oil tank and filter) or open the gas shut−off valve. 3. Switch ON the mains power supply, e.g. at a separate fuse or a mains electrical isolator. 5592492GB 0 4. Switch mains ON/OFF switch"8" ON (see page8). Standby mode is signalled by the green lamp (ON indicator); a short while later the boiler temperature will be displayed. Your heating system and, if installed, your remote control unit are now ready to operate. 11 Start−up/shutdown Heating system shutdown If you want to shut down your heating system temporarily, e.g. during a summer holiday, set the heating circuit to "Standby mode" K (see page14). Note The circulation pumps are briefly started every 24hours to prevent them from seizing up. Switch your heating system OFF if you do not intend using it. Before and after you shut down your heating system for longer periods, it would be advisable to contact your local heating contractor. Where necessary, your contractor can take certain steps, e.g. protecting the system against frost. 1. Switch ON/OFF switch"8" OFF (see page8). The green lamp (ON indicator) extinguishes. 2. Close the shut−off valves in the oil supply lines (at the oil tank and filter) or close the gas shut−off valve. 0 3. Switch the mains power supply OFF, e.g. at a separate fuse or a mains electrical isolator. As the system is now voltage free, the heating system has no frost protection. 5592492GB Note All control settings remain intact. 12 Start−up/shutdown Starting DHW and heating circuit You want to heat your rooms and have DHW available. Press the following keys: 1. !, ? or §, the selected key will be illuminated. 5592492GB 2. Gfor"Heating and DHW". H Central heating will be implemented with standard or reduced room temperature (frost protection) according to the set time program. Standard setting: from 06:00 to 22:00h standard room temperature, otherwise reduced room temperature. H DHW heating (if a DHW cylinder is installed) is active, and the DHW circulation pump (if installed) is ON according to the set time program. Standard setting: from 05:30 to 22:00h, DHW is reheated to the selected set temperature, and the DHW circulation pump is switched ON. Observe the information on page26. H Frost protection for the boiler and the DHW cylinder is active. Please note If keyG is illuminated, the following appears: H Symbol "s" is displayed when central heating with standard room temperature is active (see page9). H Symbol "m" is displayed when central heating with reduced room temperature above 3ºC is active (see page9). 13 Start−up/shutdown Switching OFF DHW and heating circuit You do not want to heat your rooms or have DHW available. Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. K for "Standby mode". H Central heating is inactive for that heating circuit. H No DHW heating. H Frost protection for the boiler and the DHW cylinder is active. Note The pumps are briefly started every 24hours to prevent them from seizing up. Starting DHW only You want to have DHW available but not heat your rooms. Press the following keys: 1. !, ? or §, the selected key will be illuminated. Note The heating circuit pumps are briefly started every 24hours to prevent them from seizing up. 5592492GB 2. L for "DHW only". H Central heating is inactive for that heating circuit. H DHW heating (if a DHW cylinder is installed) is active, and the DHW circulation pump (if installed) is ON according to the set time program. Standard setting: from 05:30 to 22:00h, DHW is reheated to the selected set temperature, and the DHW circulation pump is switched ON. H Frost protection for the boiler and the DHW cylinder is active. 14 Start−up/shutdown Switching OFF DHW only You want to heat your rooms but not have DHW available. Please observe the information on page26. Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. G for"Heating and DHW". Note The cylinder primary pump is briefly started every 24hours to prevent it from seizing up. 3. Delete time phases for DHW heating (see page29). or Set the DHW set temperature to 10ºC (see page25). 5592492GB H Central heating will be implemented with standard or reduced room temperature (frost protection) according to the set time program. Standard setting: from 06:00 to 22:00h standard room temperature, otherwise reduced room temperature. H No DHW heating. H Frost protection for the boiler and DHW cylinder is active. 15 Room temperature setting Setting a permanent room temperature Observe the following points if your heating circuit should provide central heating. 1. "Heating and DHW"G must be selected for respective heating circuit!, ? or §. Check: Press !, ? or §; G must be illuminated, otherwise press G. 2. For the respective heating circuit!, ? or §, select the "Standard room temperature" (for day)with rotary selector"ts" and "Reduced room temperature" (for night)with keyE(see page17). 3. The timing of when your heating circuit operates with standard or reduced room temperature depends on the settings of the time program (four possible time phases) for the respective day. H If no time phases are selected, central heating will be active for the whole day at reduced room temperature. H If one or more time phases are selected, central heating will be active for those times with standard room temperature. Check: H Press !, ? or §. H Press and hold down A/c simultaneously, a time slot graphic shows the set time phases. 0 3 6 9 12 15 18 21 24 1−7 5592492GB For changing the time program, see page18. 16 Room temperature setting Setting a permanent room temperature (cont.) Setting a standard room temperature 1. Press !, ? or §, the selected key will be illuminated. 2. Set the required temperature for the "Standard room temperature" with rotary selector"ts". Normal room temp. 20 s ºC Setting a reduced room temperature Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. E for "Reduced room temperature"; the current set temperature will flash. 3. a/b for the required temperature. 4. d to confirm; the temperature no longer flashes and is now saved. Red.room temp. ºC 5592492GB m 14 17 Room temperature setting Setting a permanent room temperature (cont.) Setting a time program (switching times) For central heating, up to four changes between standard and reduced room temperature can be programmed (fourtime phases). At the factory, time phase 1 is set for all weekdays from 06:00 to 22:00 h, i.e. during that time, all rooms are heated to the standard room temperature. You can select identical time programs for all weekdays or individual programs for each weekday. When setting time programs, please note that your heating system requires some time to heat the rooms to the required temperature. 5592492GB For time program setting steps, see page19. For a sequence of steps to delete a time phase, see page20. 18 Room temperature setting Setting a permanent room temperature (cont.) Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. A for "Heating time program". Note If you want to terminate the time program prematurely, pressA again and confirm with d. 3. a/b until "17" is displayed, if you want to set up the same time phases for all days Note If different time phases are set for the individual days of the week, and you want to set up identical time phases for all weekdays again, press d when the display shows "17". All time phases are returned to their original condition. 4. d to confirm: "Htg.timer1" is displayed. Note Pressa if you want to skip a time phase. Htg.time program 1−7 or "Mo", "Tu" etc., is displayed if you want to set different time phases for the displayed weekday. Htg.time program Mo 5. d to confirm; "Htg.cycle1 On" is displayed. 6. a/b for the start of the heating phase. 7. d to confirm; "Htg.cycle1 Off" is displayed. 8. a/b for the end of the heating phase. 9. d to confirm; "Htg.cycle2 On" is displayed. 5592492GB 10. Proceed for setting up the start and end of heating phases2 to 4 as described under points6 to 9. 19 Room temperature setting Setting a permanent room temperature (cont.) Press the following keys if you want to delete a time phase: 1. !, ? or §, the selected key will be illuminated. 2. A for "Heating time program". 3. d until the required "Htg.cycle OFF" is displayed. 4. b until ":" is displayed for the end time. Htg.cycle 2 OFF 1−7 5. d to confirm, until the boiler temperature is displayed. Changing the room temperature for a few days only For when you are away, the following energy saving options are available: H You can switch OFF central heating completely (see "Switching OFF heating circuit" on page14) or H You can set central heating to minimum energy consumption (e.g. to prevent your houseplants from freezing). For this, select "Holiday program"H. When "Heating and DHW" G is selected, all heating circuits are heated during the holiday program with the set reduced room temperature (see page17), but there will be no DHW heating. With the selection "DHW only" L during the holiday program, all heating circuits operate only to provide frost protection for the boilers and the DHW cylinder. Setting a holiday program The holiday program starts at 00:00 h following your day of departure and ends at 00:00 h on the return day, i.e. the permanently set time program is active on the day of departure and on the return day. 5592492GB Note The control unit is set so that the holiday program applies to all heating circuits. If you want to make changes, contact your local heating contractor. 20 Room temperature setting Changing the room temperature for a few days only (cont.) Press the following keys: 1. H for "Holiday program". Note PressH again if you want to prematurely exit the setting of the holiday program. 2. d for "Departure date" (the current date is displayed). 3. a for the date of the required departure day. Departure date Fr 18;02;05 4. d to confirm; "Return date" (a date after the departure day) is displayed. 7. The room temperature during the holiday program is the selected reduced room temperature (see page17). Should you want to change this temperature: H Press E. H Set the required value with a or b. H Press d to confirm; the temperature no longer flashes and is now saved. Note This change generally applies for the reduced room temperature and must be modified again, if required, after the holiday program ends. 5. a for the date of the required departure day. Return date Fr 25;02;05 6. d to confirm. 5592492GB Ending a holiday program H The holiday program ends automatically with the return date. H Press H again, if you want to prematurely terminate the holiday program, and confirm "Delete? Yes" with d. 21 Room temperature setting Changing the room temperature for a few hours only The following functions enable you to change the room temperature for a few hours, without permanently altering your control settings. H To save energy, you can reduce the standard room temperature with "Economy mode"N (see below). H You want to heat spontaneously at standard room temperature and provide DHW. For this, select "Party mode"M (see page23). Setting economy mode In economy mode, the standard room temperature will be reduced automatically. Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. N for "Economy mode". Economy mode 5592492GB Ending economy mode H Economy mode ends automatically with the next change to central heating with reduced room temperature. H If you want to prematurely terminate economy mode, press keys !, ? or § and N again; the key illumination extinguishes. 22 Room temperature setting Changing room temperature for a few hours only (cont.) Setting party mode H Central heating will be activated at any temperature you select (party temperature) H DHW will be reheated to the set temperature H The DHW circulation pump is switched ON Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. M for "Party mode"; the party temperature flashes. 3. a/b for the required temperature, if you want to change the room temperature. 4. d Party mode 20 ºC to confirm; the temperature no longer flashes and is now saved. 5592492GB Ending party mode H Party mode ends automatically with the next change to central heating with standard room temperature, after 8 hours at the latest. H If you want to prematurely terminate party mode, press keys !, ? or § and M again; the key illumination extinguishes. 23 Setting up DHW Setting up constant DHW Note The control unit is set so that the settings for DHW heating apply to all heating circuits. If you want to make changes, contact your local heating contractor. Observe the following points if you want to activate DHW heating. 1. "Heating and DHW"G or "DHW only"L must be selected for respective heating circuit!, ? or §. Check: Press !, ? or §; G or L must be illuminated; otherwise press G or L. Note You can select the DHW temperature (see page25). 0 3 6 9 12 15 18 21 24 1−7 For changing the time program, see page26. 5592492GB 2. The timing of when DHW heating with the selected temperature is enabled for your heating circuit, and when the DHW circulation pump (if installed) runs, depends on the settings of both time programs B or C (each with four time phases) for the respective day. Check: H Press !, ? or §, H Press and hold down B/c or C/c simultaneously; a time slot graphic shows the set time phases. 24 Setting up DHW Setting up constant DHW (cont.) Setting the DHW temperature Press the following keys: 1. F for "Set DHW temperature"; the current set temperature will flash. 2. a/b for the required temperature. 3. d to confirm; the temperature no longer flashes and is now saved. DHW temp.setpt. ºC 5592492GB w 50 25 Setting up DHW Setting up constant DHW (cont.) Setting a time program (switching times) Heating system without DHW circulation pump Note The control unit is set so that the settings for DHW heating apply to all heating circuits. If you want to make changes, contact your local heating contractor. Should you not wish to operate in automatic mode, you can also set up individual time programs. You can select identical time programs for every weekday or individual ones for each weekday. When setting time programs, please note that your heating system requires some time to heat the DHW cylinder to the required temperature. 5592492GB DHW heating can be activated/deactivated up to four times per day (four time phases). At the factory, automatic mode is set up in the time program, i.e. DHW heating is activated parallel to the central heating time program for the first available heating circuit. However, it begins 30minutes earlier (from 05:30 to 22:00h). 26 Setting up DHW Setting up constant DHW (cont.) Heating system with DHW circulation pump Note The control unit is set so that the settings for DHW heating apply to all heating circuits. If you want to make changes, contact your local heating contractor. The DHW circulation pump pumps hot water through a circuit between the DHW cylinder and the taps to deliver DHW to the taps as quickly as possible. DHW heating and the DHW circulation pump can be activated/deactivated up to four times per day (four time phases). At the factory, automatic mode is set up in the time program, i.e. DHW heating is activated parallel to the central heating time program for the first available heating circuit. However, it begins 30minutes earlier (from 05:30 to 22:00h). Should you not wish to operate in automatic mode, you can also set up individual time programs. You can select identical time programs for every weekday or individual ones for each weekday. When setting time programs, please note that your heating system requires some time to heat the DHW cylinder to the required temperature. Also, activating the DHW circulation pump is only sensible for those times when DHW is actually drawn. The following explains the setting up of a time program using DHW heatingB as an example. Set up a time program for DHW circulation pumpC in the same way. 5592492GB For time program setting steps, see page28. For a sequence of steps to delete a time phase, see page29. 27 Setting up DHW Setting up constant DHW (cont.) Selecting automatic mode (if required) Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. B 3. a/b for "Automatic?", if "Automatic?" is not yet displayed. for "DHW time program". 4. d to confirm. Setting up an individual time program Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. B for "DHW time program". Note If you want to terminate the time program prematurely, pressB again and confirm with d. 3. a/b for "Individual?", if "Individual?" is not yet displayed. 4. d to confirm. 5. a/b until "17" is displayed, if you want to set up the same time phases for all days DHW time program 1−7 or "Mo", "Tu" etc., is displayed if you want to set different time phases for the displayed weekday. DHW time program 5592492GB Mo 28 Setting up DHW Setting up constant DHW (cont.) Note If different time phases are set for the individual days of the week, and you want to set up identical time phases for all weekdays again, press d when the display shows "17". All time phases are returned to their original condition. 6. d 9. d to confirm; "DHW phase1 Off" is displayed. 10. a/b for the end of the DHW phase. 11. d to confirm; "DHW time phase1" is displayed. Note Pressa if you want to skip a time phase. 7. d 8. a/b for the starting point of the DHW heating phase. to confirm; "DHW phase2 On" is displayed. 12. Proceed for setting the start and end of DHW heating phases2 to 4 as described under points 8 to 11. to confirm; "DHW phase1 On" is displayed. Press the following keys if you want to delete a time phase: 1. !, ? or §, the selected key will be illuminated. 2. B for "DHW time program". 3. d until the required "DHW phase OFF" is displayed. 4. b until ":" is displayed for the end time. DHW cycle 2 Off 1−7 5592492GB 5. d to confirm, until the boiler temperature is displayed. 29 Setting up DHW Setting up DHW for a few hours only The following functions enable you to heat DHW for a few hours, without permanently altering your control settings. For this, select "Party mode"M. During party mode, the DHW circulation pump is active, and central heating operates at "Party temperature". Set the party temperature to 4ºC (see page23), if you require no central heating (e.g. in summer). Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. M for "Party mode"; the party temperature flashes. 3. a/b for the required temperature, if you want to change the room temperature. 4. d Party mode 20 ºC to confirm; the temperature no longer flashes and is now saved. 5592492GB Ending party mode H Party mode ends automatically with the next change to central heating with standard room temperature, after 8 hours at the latest. H If you want to prematurely terminate party mode, press keys !, ? or § and M again; the key illumination extinguishes. 30 Setting up DHW Setting up DHW once only The following functions enable you to heat DHW once, without permanently altering your control settings. For this, select "Party mode"M. Preconditions: H Not in "Standby mode" K, and not in "Holiday program" H H The DHW temperature must be below the set value (see page 25) Press the following keys: 3. d to confirm; DHW heating begins. 2. M for "Party mode". 4. After approx. 10s, press M again; the key illumination extinguishes. 5592492GB 1. !, ? or §, the selected key will be illuminated. 31 Further settings Setting date and time Date and time are factory−set and may be changed manually. Press the following keys: 1. D 4. a/b for the required date. for "Time". 2. a/b for the required time. Date We Time 09:05 u 5. d 3. d 16;02;05 to confirm. to confirm. "Date" is displayed. Language selection Press the following keys: 1. !, ? or §, the selected key will be illuminated. 3. b for the required language. German 2. c for "Outside temp.". i Outdoor temp. 13 ºC 4. d to confirm. 5592492GB i 32 Further settings Modifying the boiler heating characteristics You can alter the heating characteristics if the room temperature does not meet your requirements for some time. You alter the heating characteristics by changing the slope and level of the heating curve. For more information regarding the heating curve, see page35. Please observe the modified heating characteristics over several days (if possible await a major change in the weather), before making further adjustments. Make short−term adjustments of the room temperature using rotary selector"ts" or key E (see page17). Changing slope and level For assistance, use the table on page34. Press the following keys: 1. !, ? or §, the selected key will be illuminated. 2. I 4. d to confirm. for "Slope" Slope 1;4 J 3. a/b for the required value. Note Setting the slope or level of the heating curve too high or too low will not result in damage to your heating system. or for "Shift". Shift 5592492GB 0 33 Further settings Changing the boiler heating characteristics (cont.) Heating characteristics Remedy The living space is too cold during the heating season Adjust heating curve slope to next higher value (e.g.1.5) Slope The living space is too hot during the heating season Adjust heating curve slope to next lower value (e.g.1.3) Slope The living space is too Adjust the heating cold during transitional curve level to a higher periods (spring/autumn) value (e.g. +3K) and during the heating season The living space is too hot during the transitional periods (spring/autumn) and during the heating season Adjust the heating curve level to a lower value (e.g. 3K) The living space is too cold during the transitional periods (spring/autumn), but warm enough during the heating season Adjust the heating curve slope to the next lower value, and the level to a higher value (e g +3K) (e.g. +3 K) Example Shift Shift Slope Shift The living space is too hot during the transitional periods (spring/autumn), but warm enough during the heating season Adjust the heating curve slope to the next higher value, and the level to a lower value (e g 3 (e.g. 3K) K) Slope 5592492GB Shift 34 Further settings Changing the boiler heating characteristics (cont.) For technically−minded system users Heating curves illustrate the relationship between the outside temperature and the boiler water or the flow temperature. To put it simply: The lower the outside temperature, the higher the boiler water or flow temperature. The illustrated heating curves apply subject to the following settings: H Heating curve level = 0 Different level settings shift the curves parallel in a vertical direction. H Standard room temperature = approx. 20ºC. In the factory, the following settings are made: slope=1.4, level=0. 2.4 3.4 3.2 3.0 2.8 2.6 Slope Boiler water temperature or flow temperautre in °C 2.2 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 Outside temperature in °C 5592492GB A Underfloor heating B Low temperature heating system C Heating system with a boiler water temperature in excess of 75ºC Examples H Well insulated house in a sheltered position (with radiator heating system): Slope=1.2 H Home in exposed position or with an older heating system (with radiator heating system): Slope=1.6 35 Further settings Adjusting the display contrast Press keyd and simultaneously set the contrast with keysa or b. Reinstating standard settings For this, presse. 5592492GB It is possible to simultaneously reset all changed values for the heating circuit to the factory settings. 36 Scanning options Temperature scanning Subject to connected components and settings made, you can scan current temperatures and operating conditions. Press the following keys: 1. !, ? or §, the selected key will be illuminated. 3. a/b for further scanning of the list. 2. c 4. c for "Outdoor temp.". to end scanning. Outdoor temp. 5592492GB i 9 ºC Order in which temperatures and operating conditions may be scanned: H Solar DHW temp. DHW H User no., in connection with temperature in conjunction with a heating circuit control unit solar heating system Vitotronic050 H Collector temp. in conjunction with H Holiday program with departure a solar heating system and return date, if programmed H Burner burner hours run H Outside temperature H Burner stage 1 hours run, burner H Boiler water temperature stage 1 H Flue gas temperature, H Burner stage 2 hours run, burner if a sensor is installed stage 2 H Sensor 17A, H Number of burner start−ups if a sensor is installed H Consumption fuel consumption H Sensor 17B subject to appropriate settings if a sensor is installed having been made by the heating H DHW temperature domestic hot contractor water temperature H Solar energy display in kWh, in H DHW temperature 1 or 2 DHW conjunction with a solar heating temperature, if 2 cylinder system temperature sensors are available H Time H Flow temperature H Date for heating circuit with mixer H Burner ON/OFF H Standard room temp. (set value) H Burner stage 1 ON/OFF H Room temperature (actual value), H Burner stage 2 ON/OFF if a Vitotrol remote control is installed 37 Scanning options Temperature scanning (cont.) H Output 20 ON/OFF H Output 29 ON/OFF H Output 52 OPEN/CLOSE 0 ¢ Close 1 to 99 (%) 100 ¢ Open H Cylinder primary pump ON/OFF H DHW circulation pump ON/OFF H Heating circuit pump ON/OFF H Mixer open/closed 0 ¢ Closed 1 to 99 (%) 100 ¢ Open H Solar pump ON/OFF H Solar pump hours run H Language Time program scanning Press the following keys: 1. !, ? or §, the selected key will be illuminated. 3. For changing the time programs, see page18 and 26. 2. A/c for central heating time program or B/c for DHW time program or C/c for DHW circulation pump time program press and hold down simultaneously; a time slot graphic shows the set time phases. 0 3 6 9 12 15 18 21 24 5592492GB 1−7 38 Scanning options Scanning party or economy mode Press the keys !, ? or §, the selected key and the key of the active program will be illuminated (see page 10). Scanning fault display A B CD Boiler sensor A Fault display B Fault symbol C Fault number D Fault code 5592492GB If your heating system has developed a fault, it will be displayed and indicated by the flashing red fault indicator. You can check the fault code on the display and then notify your heating contractor accordingly. This allows the heating contractor to better prepare for the service call and may save additional travelling costs. 39 Scanning options Scanning fault display (cont.) Press the following keys: 1. c for troubleshooting. 2. a/b to display further fault codes, if several faults are active. 3. d To recall fault codes press the following keys: 1. d for approx. 2s. 2. a/b to acknowledge the fault codes. to "Acknowledge" all fault codes. 4. a/b for "Yes" or "No". With "Acknowledge? Yes" you confirm that you have noted the fault. 5. d to confirm. 5592492GB Note If the fault has not been rectified, the fault message will be redisplayed at 07.00h the following day. The red fault indicator flashes until the fault has been rectified. 40 What to do if...? Rooms are too cold Remedy The heating system is switched OFF H Switch ON/OFF switch"8" ON (see page11) H Switch ON mains electrical isolator, if installed (outside the boiler room) H Check the fuse in the power distribution (main domestic fuse) Control unit incorrectly adjusted Check and correct settings, if required: H Heating circuit must be switched ON (see page13) H Room temperature (see page17) H Time (see page32) H Boiler heating characteristics (see page34) Only when operating with DHW cylinder: DHW priority (wp in the display) Wait until the DHW cylinder has been heated up (p extinguishes from the display) No fuel With oil/LPG: Check the fuel reserves and re−order, if required With natural gas: Open the gas shut−off valve or enquire with your gas supply company if required Control unit fault: "Fault" is displayed and the red fault indicator flashes Check the type of fault (see page39) and notify your local heating contractor 5592492GB Cause 41 What to do if...? Rooms are too cold (cont.) Remedy False burner start: "Fault" is displayed, the red fault indicator at the control unit flashes, and the fault indicator on the burner lights up in red H With a pressure jet burner: Press the reset button on the burner hood. H With an atmospheric boiler: Press the reset button on the boiler front panel. Contact your local heating contractor if the burner still fails to start. Vitoair draught stabiliser faulty Contact your local heating contractor. Reset Vitoair to manual: Press the rotary selector on the motor and turn it to the limit stop beyond position"3". Mixer motor faulty Adjusting the mixer manually 5592492GB Cause 42 What to do if...? Rooms are too hot Remedy Control unit incorrectly adjusted Check and correct settings, if required: H Room temperature (see page17) H Time (see page32) H Boiler heating characteristics (see page34) Control unit fault or outside temperature sensor/boiler temperature sensor faulty: "Fault" is displayed and the red fault indicator flashes Check the type of fault (see page39) and notify your local heating contractor Emissions test switch"S" shows "h" Set emissions test switch"S" to "a" (see page8) 5592492GB Cause 43 What to do if...? No DHW is available Remedy The heating system is switched OFF H Switch ON/OFF switch"8" ON (see page11) H Switch ON mains electrical isolator, if installed (outside the boiler room) H Check the fuse in the power distribution (main domestic fuse) Control unit incorrectly adjusted Check and correct settings, if required: H DHW heating must be switched ON (see page13 and 14) H DHW temperature (see page25) H Time (see page32) No fuel See page41 Control unit fault: "Fault" is displayed and the red fault indicator flashes Check the type of fault (see page39) and notify your local heating contractor False burner start: "Fault" is displayed, the red fault indicator at the control unit flashes, and the fault indicator on the burner lights up in red See page42 Vitoair draught stabiliser faulty See page42 Cylinder primary pump is faulty Contact your local heating contractor 5592492GB Cause 44 What to do if...? The DHW is too hot Cause Remedy Control unit incorrectly adjusted Check and correct the DHW temperature, if required (see page25) Sensor fault Contact your local heating contractor Emissions test switch"S" shows "h" Set emissions test switch"S" to "a" (see page8) The display flashes "Fault" Cause Remedy Heating system fault Check the type of fault (see page39) and notify your local heating contractor The display shows "Service" Cause Remedy Maintenance time has been reached Arrange for your local heating contractor to service your heating system The display shows "Remote control" Remedy A remote control is connected to the heating circuit Make adjustments or carry out scanning at the remote control (see separate operating instructions) 5592492GB Cause 45 What to do if...? The display shows "External control" Cause Remedy The heating program set at the control unit was changed over by an external device No action required. The heating program changeover was manually selected. The display shows "Central control" Cause Remedy The settings or the holiday and day programs will be taken from the heating circuit, as "Central control" is set The display shows "Slab curing program" Cause Remedy The screed function has been set up Wait until this function has terminated The display shows "Without function" Remedy No function has been allocated to the key you pressed, or the function can only be adjusted on your remote control 5592492GB Cause 46 Ordering fuel oil Ordering fuel oil Fuel oil additives Fuel oil additives are materials that can be used to H improve fuel stability during storage, H improve thermal stability of fuel and H reduce odour during filling. ! Bio−fuels Bio−fuel is made from vegetable oil, e.g. sunflower or rapeseed oil. ! Please note Bio−fuels can lead to damage on Viessmann oil burners. Their use is not permissible. Please note Fuel oil additives can create residues and impair the safe operation of your heating system. The use of fuel oil additives which leave residues is not acceptable. Combustion improvers Combustion improvers are additives for optimising fuel oil combustion. Viessmann oil burners do not require combustion improvers, as these burners operate with clean and efficient combustion. ! Please note Combustion improvers can create residues and impair the safe operation of your heating system. The use of combustion improvers which leave residues is not acceptable. 5592492GB If in doubt ask your local fuel oil supplier. 47 Repairs Cleaning All devices may be cleaned with a commercially available domestic cleaning agent (non−scouring). Inspection and maintenance Inspection and maintenance of your heating system is prescribed by the Energy Savings Order [Germany] and the standards DIN4755, DIN4756, DIN19888 and EN806 and/or local regulations. Regular maintenance ensures trouble−free, energy−efficient and environmentally responsible heating operation. For this, we strongly advise you to arrange an inspection and maintenance contract with your local heating contractor. Boiler Increasing boiler contamination raises the flue gas temperature and thereby increases energy losses. For that reason, all boilers should be cleaned annually. checked annually by a heating contractor. The anode function can be checked without interrupting system operation. The heating contractor will check the earth current with an anode tester. DHW cylinder DIN 1988−8 and EN806 prescribe that maintenance and cleaning should be carried out no later than two years after commissioning and thereafter as necessary. Only a recognised heating contractor should clean the inside of a DHW cylinder and the DHW connections. Refill any water treatment equipment (e.g. a lock or injection equipment) in good time, if such equipment is installed in the cold water supply of the DHW cylinder. Observe the manufacturer’s details. Safety valve (DHW cylinder) Check the safety valve function every six months by venting, or have it checked by your heating contractor. The valve seat may become contaminated (see the valve manufacturer’s instructions). 48 5592492GB In addition for Vitocell 100: We recommend that the correct function of the sacrificial anode is DHW filter (where installed) To maintain high hygienic standards H on non−back−flushing filters, replace filter element every 6 months (visual check every 2 months); H on back−flushing filters, back−flush every 2 months. Keyword index Keyword index A Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Automatic mode . . . . . . . . . . . . . . . . . . . . . 26, 27, 28 B Boiler room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Boiler room requirements . . . . . . . . . . . . . . . . . . 3 Burner, hours run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 C Cleaning tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Collector temperature . . . . . . . . . . . . . . . . . . . . . . . 37 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 11 Contrast settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Control unit commissioning . . . . . . . . . . . 11 Control unit shutdown . . . . . . . . . . . . . . . . . . . . . . 12 Cylinder primary pump . . . . . . . . . . . . . . . 8, 38 F Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 8, 36 Factory settings, heating system . . . . . 6 Fault display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,39 Fault message acknowledgement 40 Fault message call−up . . . . . . . . . . . . . . . . . . . . . . . . 40 Faults (errors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Fault messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Flue gas smell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Frost protection . . . . . . . . . . . . . . . . . . . . . . . . 6, 13, 14 Fuel consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 G Gas shut−off valve . . . . . . . . . . . . . . . . . . . 2, 11, 12 Gas smell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 H Heating and DHW . . . . . . . . . . . . . . . . . . . . . . 6, 8, 13 Heating characteristics . . . . . . . . . . . . . . . . . . . . . . 34 Heating circuit selection . . . . . . . . . . . . . . . . . . . 10 Heating circuit shutdown . . . . . . . . . . . . . . . . . 14 Heating circuit start−up . . . . . . . . . . . . . . . . . . . . . 13 Heating circuit pump . . . . . . . . . . . . . . . . . . . . 9, 38 Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 33 Heating system shutdown . . . . . . . . . . . . . . 12 Heating system start−up . . . . . . . . . . . . . . . . . . . 11 Heating times, changing . . . . . . . . . . . . . . . . . . 19 Heating program changeover . . . . . . . . 46 Holiday . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Holiday program setting . . . . . . . . . . . . . . . . . . 20 5592492GB D Danger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Date, changing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 32 Day temperature (standard room temperature) . . . . . . . . 17 DHW cylinder (inspection and maintenance) . . . . . . . 48 DHW circulation pump . . . . . . . . . . 8, 27, 38 DHW heating once . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 DHW heating shutdown . . . . . . . . . . . . . . 14,15 DHW heating start−up . . . . . . . . . . . . . . . . . 13, 14 DHW production (automatic mode) . . . . . . . . . . . . . . . . . . . . . . . . . 26, 27 DHW temperature setting . . . . . . . . . . . . . . . . 25 Domestic hot water . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 8 Drinking water filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 E Economy mode "û" . . . . . . . . . . . . 8, 22, 39 Emissions test switch . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Energy saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20, 22 Equipment shutdown . . . . . . . . . . . . . . . . . . . . . . . . 12 Equipment start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 49 Keyword index Keyword index (cont.) K Key illumination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 L Lamps (diodes) . . . . . . . . . . . . . . . . . . . 8, 11,12, 39 Language selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Level of heating curve, changing . 33 M Mains ON/OFF switch . . . . . . . . . . . . 8, 11, 12 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Maintenance contract . . . . . . . . . . . . . . . . . . . . . . . . 48 Maintenance display . . . . . . . . . . . . . . . . . . . . . . . . . . 45 N Night temperature (reduced room temperature) . . . . . 8, 17 Notice of completion . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 O Operating display . . . . . . . . . . . . . . . . . . . . 8, 11, 12 P Party mode"g" . . . . . . . 8, 23, 30, 31, 39 Party temperature setting . . . . . . . . . . . . . . . . 23 Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Programming unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Programs, setting . . . . . . . . . . . . . . . . . . . . . . . . . 18, 26 50 R Radio clock reception . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Radio clock receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Reduced room temperature (night temperature) . . . . . . . . . . . . . . . . . . 6, 8, 17 Remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 45 Renewed start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Requirements for boiler room . . . . . . . . . . 3 Room temperature changing . . . . . . . . . 17 S Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Safety valve (DHW cylinder) . . . . . . . . . . . . 48 Scanning actual temperature . . . . . . . . . 37 Scanning DHW temperature . . . . . . . . . . 37 Scanning holiday program . . . . . . . . . . . . . . 37 Scanning information . . . . . . . . . . . . . . . . . . . . . . . . 37 Scanning operating conditions . . . . . 37 Scanning solar energy . . . . . . . . . . . . . . . . . . . . . . 37 Scanning temperatures and operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Scanning time program . . . . . . . . . . . . . . . . . . . 38 Screed drying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Slope of heating curve, changing 33 Spring/autumn (heating and DHW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Standard factory settings . . . . . . . 6, 8, 36 Standard room temperature (day temperature) . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 17 Standard settings . . . . . . . . . . . . . . . . . . . . . . 6, 8, 36 Standby mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14, 20 Summer mode (DHW only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Switching OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Switching times, setting . . . . . . . . . . . . . 18,26 Symbols in the display . . . . . . . . . . . . . . . . . . . . . . . . 9 System shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 System start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Solar circuit pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 5592492GB I Illuminated keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Indicators (diodes) . . . . . . . . . . . . 8, 11,12, 39 Individual time programs . . . . . . . . . 18, 19 26, 27, 28 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Initial start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Instructions on safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Keyword index Keyword index (cont.) W What to do if...? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Where to find the controls . . . . . . . . . . . . . . . . . 7 Winter operation (heating and DHW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Work on the equipment/heating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 5592492GB T Temperature scanning . . . . . . . . . . . . . . . . . . . . . . 37 Temperature setting . . . . . . . . . . . . . . . . . . . . 17, 25 Time phases, deleting (DHW only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Time phases, deleting (heating and DHW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Time programs H central heating . . . . . . . . . . . . . . . . . . . . . . . . 6, 8, 18 H DHW circulation pump . . . . . . . . 6, 8, 27 H DHW heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 8, 26 Time setting (changing) . . . . . . . . . . . . . . . 8, 32 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 51 Applicability For heating systems with boiler, DHW cylinder and Vitotronic300, typeGW2, part no.7187099 Printed on environmentally friendly, chlorine−free bleached paper Certification Contact your local heating contractor if you have any questions regarding the maintenance and repair of your heating system. You may, for example, find local heating contractors under www.viessmann.de on the internet. Viessmann Werke GmbH&Co KG D35107 Allendorf Tel: +49 6452 700 Fax: +49 6452 702780 www.viessmann.de Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Tel: +44 1952 675000 Fax: +44 1952 675040 E−mail: info−[email protected] 52 5592492GBSubject to technical modifications. Your contact
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project