VITOTRONIC 300 Operating instructions

Add to my manuals
52 Pages

advertisement

VITOTRONIC 300 Operating instructions | Manualzz
Operating instructions
for system users
Heating system with
weather−compensated, digital boiler and heating circuit control unit
VITOTRONIC 300
5592492GB2/2005
Please keep safe
Safety instructions
For your safety
Please follow these safety instructions closely to prevent accidents and
material losses.
Safety instructions explained
If you notice a smell of gas
¨ Danger
¨ Danger
This symbol warns against the
Escaping gas can lead to
risk of injury.
!
Please note
This symbol warns against the
risk of material losses and
environmental pollution.
Note
Details identified by the word "Note"
contain additional information.
Target group
These operating instructions are
designed for heating system users.
¨ Danger
Incorrect work on the heating
If you smell flue gas
¨ Danger
Flue gas can lead to
life−threatening poisoning.
H Shut down your heating
system.
H Ventilate the boiler room.
H Close all doors leading to the
living space.
5592492GB
system can lead to
life−threatening accidents.
H Work on gas equipment must
only be carried out by a
registered gas fitter.
H Electrical work must only be
carried out by a qualified
electrician.
explosions which may lead to
serious injury.
H Do not smoke! Prevent
naked flames and sparks.
Never switch electrical lights
or equipment.
H Open windows and doors.
H Close the gas shut−off valve.
H Remove all people from the
danger zone.
H Observe the safety
regulations of your local gas
supplier found on the gas
meter.
H Notify your heating
contractor from outside the
building.
2
Safety instructions
For your safety (cont.)
In case of fire
¨ Danger
With fire there is a risk of
burning and explosion.
H Shut down your heating
system.
H Close the shut−off valves of
the main fuel lines.
H Use a tested fire
extinguisher, class ABC.
Ancillary components, spare and
wearing parts
!
Please note
Components which are not
tested with the heating system
may lead to damage to the
heating system, or may affect
their various functions.
Installation or replacement
must only be carried out by
qualified personnel.
Boiler room requirements
!
Please note
Incorrect ambient conditions
can lead to damage to the
heating system and put safe
operation at risk.
H Ensure ambient
temperatures above 0ºC and
below 35ºC.
H Prevent air contamination by
halogenated hydrocarbons
(e.g. as contained in paints,
solvents or cleaning fluids)
and excessive dust (e.g.
through grinding/polishing
work).
H Avoid continuously high
humidity levels (e.g. through
frequent drying of washing).
H Never close existing
ventilation apertures.
5592492GB
3
Index
Index
Introductory information
Initial start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Your heating system is preset at the factory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
6
Where to find the controls
Summary of controls and indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
H Opening the control unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
H Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
H Symbols in the display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
H Heating circuit selectionbefore any adjustment and scanning . . . . . . . . . . . . . . . . . . 10
11
12
13
14
14
15
Room temperature setting
Setting a permanent room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Setting a standard room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Setting a reduced room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Setting a time program (switching times) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing the room temperature for a few days only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Setting a holiday program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Changing the room temperature for a few hours only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Setting economy mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Setting party mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
17
17
18
20
20
22
22
23
Setting up DHW
Setting up constant DHW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Setting the DHW temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Setting a time program (switching times) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting up DHW for a few hours only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting up DHW once only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
24
25
26
30
31
5592492GB
Start−up/shutdown
Heating system start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heating system shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting DHW and heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching OFF DHW and heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting DHW only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching OFF DHW only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Index
Index (cont.)
Further settings
Setting date and time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Language selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modifying the boiler heating characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H Changing slope and level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H For technically−minded system users . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjusting the display contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reinstating standard settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
32
33
33
35
36
36
Scanning options
Temperature scanning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time program scanning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanning party or economy mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanning fault display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
37
38
39
39
What to do if...?
Rooms are too cold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rooms are too hot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
No DHW is available . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The DHW is too hot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The display flashes "Fault" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The display shows "Service" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The display shows "Remote control" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The display shows "External control" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The display shows "Central control" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The display shows "Slab curing program" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The display shows "Without function" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
41
43
44
45
45
45
45
46
46
46
46
Ordering fuel oil
Fuel oil additives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Combustion improvers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Bio−fuels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Repairs
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Inspection and maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
5592492GB
Keyword index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
5
Introductory information
Initial start−up
The initial start−up and matching of
the control unit to local conditions
and the structural characteristics of
the building must be carried out by
your heating contractor.
As the user of new combustion
equipment, you are obliged to notify
the installation to your local flue gas
inspector (check local regulations).
Your local flue gas inspector will also
inform you (where appropriate)
about work he may be required to
carry out on your combustion
equipment (e.g. regular checks,
cleaning).
Your heating system is preset at the factory
You may change the factory settings
in accordance with individual
requirements.
Note
All data is saved in case of power
failure.
5592492GB
The control unit is preset at the
factory. Your heating system is
therefore ready for use:
H Between 06:00 and 22:00h, central
heating operates with standard
room temperature.
H Between 05:30 and 22.00h, DHW is
heated (if a DHW cylinder is
installed, DHW will be reheated to
the set temperature), and the DHW
circulation pump is ON (if
connected to the control unit).
H Between 22:00 and 06:00h, central
heating operates with reduced
room temperature (set to 3 ºC,
frost protection).
H Between 22:00 and 05:30h, DHW
cylinder will not be reheated.
H Weekday and time (CET),
summer/winter time changeover is
automatic.
6
Where to find the controls
Summary of controls and indicators
You can change all settings for your heating system, centrally, at the
programming unit.
You may also make such changes on the remote control units, if your system
is equipped with such units.
Separate operating instructions
Opening the control unit
A
The programming unit is located
behind the hinged cover.
To open, pull the hinged cover from
top edge down to the front.
5592492GB
A Hinged cover
7
Where to find the controls
Summary of controls and indicators (cont.)
Functions
C
D
E
F
G
H
Boiler temperature
Mo
N
A ON/OFF indicator (green)
(page11 and 12)
B Fault indicator (red) (page39)
C Emissions test switch
(only for service)
D Heating circuit selection keys
(page10)
E Control panel
A Central heating time
program (page18)
B DHW heating time
program (page26)
C Circulation pump time
program (page27)
H
Holiday program (page20)
F DHW temperature
(page 25)
E Reduced room
temperature (page 17)
I
Heating curve slope
(page33)
J
Heating curve level
(page33)
D Time/date (page32)
K
Standby mode
8
M
LK
L
DHW only
G Heating and DHW
N
Economy mode (page22)
M
Party mode (page23)
a/b Adjusting values
d
Confirmation
c
Information
(page32 and 37)
e
Standard setting
(page36)
F Rotary selector"ts" for
"Standard room temperature"
(page17))
G Control thermostat
H Excess temperature reset
K ON/OFF switch (page11 and 12)
L Fuses
M Test switch
(only for service)
N Open flap
5592492GB
BA
Where to find the controls
Summary of controls and indicators (cont.)
Symbols in the display
These symbols are not permanently displayed, but appear subject to the
system version and the operating state.
Flashing displays indicate that modifications can be made.
e
s
5592492GB
if frost is possible
for central heating with
standard room temperature
m
for central heating with
reduced room temperature
e p,
s p,
m p Heating circuit pump running
| Mixer "open"
~ Mixer "close"
w DHW heating enabled
w p Cylinder primary pump
running, DHW is being heated
p DHW heating via solar heating
system
A Burner "ON"
u Time adjustment and display
S Emissions test function "ON"
Q
Radio clock reception (only with
radio clock module, accessory)
9
Where to find the controls
Summary of controls and indicators (cont.)
Heating circuit selectionbefore any adjustment and scanning
Your building may be heated by several interdependent heating circuits (e.g.
underfloor heating circuits or radiator circuits).
These are selected at the control unit using keys!, ? or §. Your heating
contractor will label the keys individually.
Heating system with only one heating circuit
Key ! or ? and one of the keysG, L or K are illuminated, and you can
begin your adjustments.
Heating system with two or three heating circuits
Choose the required heating circuit before every adjustment and scanning.
Heating circuit A1
1r
Press ! or ? or §.
The following keys will be
illuminated:
H Key!, ? or §
H KeyG, L or K
H KeyM or N (if active)
5592492GB
Note
If you make no adjustments, the key
illumination will extinguish after a
short time.
10
Start−up/shutdown
Heating system start−up
1. Check the pressure of your heating
system on the pressure gauge.
The system pressure is too low if
the indicator points to the area
below the red field. In that case,
top up with water or notify your
local heating contractor.
2. Open the shut−off valves in the oil
supply lines (at the oil tank and
filter) or open the gas shut−off
valve.
3. Switch ON the mains power
supply, e.g. at a separate fuse or a
mains electrical isolator.
5592492GB
0
4. Switch mains ON/OFF switch"8"
ON (see page8). Standby mode
is signalled by the green lamp (ON
indicator); a short while later the
boiler temperature will be
displayed.
Your heating system and, if
installed, your remote control unit
are now ready to operate.
11
Start−up/shutdown
Heating system shutdown
If you want to shut down your heating system temporarily, e.g. during a
summer holiday, set the heating circuit to "Standby mode" K (see page14).
Note
The circulation pumps are briefly started every 24hours to prevent them from
seizing up.
Switch your heating system OFF if you do not intend using it.
Before and after you shut down your heating system for longer periods, it
would be advisable to contact your local heating contractor.
Where necessary, your contractor can take certain steps, e.g. protecting the
system against frost.
1. Switch ON/OFF switch"8" OFF
(see page8).
The green lamp (ON indicator)
extinguishes.
2. Close the shut−off valves in the oil
supply lines (at the oil tank and
filter) or close the gas shut−off
valve.
0
3. Switch the mains power supply
OFF, e.g. at a separate fuse or a
mains electrical isolator.
As the system is now voltage free,
the heating system has no frost
protection.
5592492GB
Note
All control settings remain intact.
12
Start−up/shutdown
Starting DHW and heating circuit
You want to heat your rooms and have DHW available.
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
5592492GB
2. Gfor"Heating and DHW".
H Central heating will be
implemented with standard or
reduced room temperature (frost
protection) according to the set
time program.
Standard setting:
from 06:00 to 22:00h standard
room temperature, otherwise
reduced room temperature.
H DHW heating (if a DHW cylinder
is installed) is active, and the
DHW circulation pump (if
installed) is ON according to the
set time program.
Standard setting:
from 05:30 to 22:00h, DHW is
reheated to the selected set
temperature, and the DHW
circulation pump is switched
ON. Observe the information on
page26.
H Frost protection for the boiler
and the DHW cylinder is active.
Please note
If keyG is illuminated, the
following appears:
H Symbol "s" is displayed when
central heating with standard room
temperature is active (see page9).
H Symbol "m" is displayed when
central heating with reduced room
temperature above 3ºC is active
(see page9).
13
Start−up/shutdown
Switching OFF DHW and heating circuit
You do not want to heat your rooms or have DHW available.
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. K for "Standby mode".
H Central heating is inactive for
that heating circuit.
H No DHW heating.
H Frost protection for the boiler
and the DHW cylinder is active.
Note
The pumps are briefly started every
24hours to prevent them from
seizing up.
Starting DHW only
You want to have DHW available but not heat your rooms.
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
Note
The heating circuit pumps are briefly
started every 24hours to prevent
them from seizing up.
5592492GB
2. L for "DHW only".
H Central heating is inactive for
that heating circuit.
H DHW heating (if a DHW cylinder
is installed) is active, and the
DHW circulation pump (if
installed) is ON according to the
set time program.
Standard setting:
from 05:30 to 22:00h, DHW is
reheated to the selected set
temperature, and the DHW
circulation pump is switched
ON.
H Frost protection for the boiler
and the DHW cylinder is active.
14
Start−up/shutdown
Switching OFF DHW only
You want to heat your rooms but not have DHW available.
Please observe the information on page26.
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. G for"Heating and DHW".
Note
The cylinder primary pump is briefly
started every 24hours to prevent it
from seizing up.
3. Delete time phases for DHW
heating (see page29).
or
Set the DHW set temperature to
10ºC (see page25).
5592492GB
H Central heating will be
implemented with standard or
reduced room temperature (frost
protection) according to the set
time program.
Standard setting:
from 06:00 to 22:00h standard
room temperature, otherwise
reduced room temperature.
H No DHW heating.
H Frost protection for the boiler and
DHW cylinder is active.
15
Room temperature setting
Setting a permanent room temperature
Observe the following points if your heating circuit should provide central
heating.
1. "Heating and DHW"G must be
selected for respective heating
circuit!, ? or §.
Check:
Press !, ? or §; G must be
illuminated, otherwise press G.
2. For the respective heating
circuit!, ? or §, select the
"Standard room temperature" (for
day)with rotary selector"ts"
and "Reduced room temperature"
(for night)with keyE(see
page17).
3. The timing of when your heating
circuit operates with standard or
reduced room temperature
depends on the settings of the
time program (four possible time
phases) for the respective day.
H If no time phases are selected,
central heating will be active for
the whole day at reduced room
temperature.
H If one or more time phases are
selected, central heating will be
active for those times with
standard room temperature.
Check:
H Press !, ? or §.
H Press and hold down A/c
simultaneously, a time slot
graphic shows the set time
phases.
0 3 6 9 12 15 18 21 24
1−7
5592492GB
For changing the time program,
see page18.
16
Room temperature setting
Setting a permanent room temperature (cont.)
Setting a standard room temperature
1. Press !, ? or §, the selected
key will be illuminated.
2. Set the required temperature for
the "Standard room temperature"
with rotary selector"ts".
Normal room temp.
20
s
ºC
Setting a reduced room temperature
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. E
for "Reduced room
temperature"; the current
set temperature will flash.
3. a/b for the required
temperature.
4. d
to confirm; the temperature
no longer flashes and is
now saved.
Red.room temp.
ºC
5592492GB
m
14
17
Room temperature setting
Setting a permanent room temperature (cont.)
Setting a time program (switching times)
For central heating, up to four
changes between standard and
reduced room temperature can be
programmed (fourtime phases).
At the factory, time phase 1 is set for
all weekdays from 06:00 to 22:00 h,
i.e. during that time, all rooms are
heated to the standard room
temperature.
You can select identical time
programs for all weekdays or
individual programs for each
weekday.
When setting time programs, please
note that your heating system
requires some time to heat the
rooms to the required temperature.
5592492GB
For time program setting steps, see
page19.
For a sequence of steps to delete a
time phase, see page20.
18
Room temperature setting
Setting a permanent room temperature (cont.)
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. A
for "Heating time
program".
Note
If you want to terminate the time
program prematurely, pressA
again and confirm with d.
3. a/b until
"17" is displayed, if you
want to set up the same
time phases for all days
Note
If different time phases are set
for the individual days of the
week, and you want to set up
identical time phases for all
weekdays again, press d when
the display shows "17". All time
phases are returned to their
original condition.
4. d
to confirm: "Htg.timer1"
is displayed.
Note
Pressa if you want to skip a
time phase.
Htg.time program
1−7
or
"Mo", "Tu" etc., is
displayed if you want to set
different time phases for
the displayed weekday.
Htg.time program
Mo
5. d
to confirm; "Htg.cycle1
On" is displayed.
6. a/b for the start of the heating
phase.
7. d
to confirm; "Htg.cycle1
Off" is displayed.
8. a/b for the end of the heating
phase.
9. d
to confirm; "Htg.cycle2
On" is displayed.
5592492GB
10. Proceed for setting up the start
and end of heating phases2 to 4
as described under points6 to 9.
19
Room temperature setting
Setting a permanent room temperature (cont.)
Press the following keys if you want to delete a time phase:
1. !, ? or §, the selected key will
be illuminated.
2. A for "Heating time program".
3. d until the required "Htg.cycle
OFF" is displayed.
4. b until ":" is displayed for
the end time.
Htg.cycle 2 OFF
1−7
5. d to confirm, until the boiler
temperature is displayed.
Changing the room temperature for a few days only
For when you are away, the following energy saving options are available:
H You can switch OFF central heating completely (see "Switching OFF heating
circuit" on page14)
or
H You can set central heating to minimum energy consumption (e.g. to
prevent your houseplants from freezing).
For this, select "Holiday program"H.
When "Heating and DHW" G is selected, all heating circuits are heated
during the holiday program with the set reduced room temperature (see
page17), but there will be no DHW heating.
With the selection "DHW only" L during the holiday program, all heating
circuits operate only to provide frost protection for the boilers and the
DHW cylinder.
Setting a holiday program
The holiday program starts at 00:00 h following your day of departure and
ends at 00:00 h on the return day, i.e. the permanently set time program is
active on the day of departure and on the return day.
5592492GB
Note
The control unit is set so that the holiday program applies to all heating
circuits. If you want to make changes, contact your local heating contractor.
20
Room temperature setting
Changing the room temperature for a few days only (cont.)
Press the following keys:
1. H for "Holiday program".
Note
PressH again if you want to
prematurely exit the setting of the
holiday program.
2. d for "Departure date" (the
current date is displayed).
3. a for the date of the required
departure day.
Departure date
Fr
18;02;05
4. d to confirm; "Return date" (a
date after the departure day)
is displayed.
7. The room temperature during the
holiday program is the selected
reduced room temperature
(see page17).
Should you want to change this
temperature:
H Press E.
H Set the required value
with a or b.
H Press d to confirm; the
temperature no longer flashes
and is now saved.
Note
This change generally applies for
the reduced room temperature
and must be modified again, if
required, after the holiday
program ends.
5. a for the date of the required
departure day.
Return date
Fr
25;02;05
6. d to confirm.
5592492GB
Ending a holiday program
H The holiday program ends
automatically with the return date.
H Press H again, if you want to
prematurely terminate the holiday
program, and confirm
"Delete? Yes" with d.
21
Room temperature setting
Changing the room temperature for a few hours only
The following functions enable you to change the room temperature for a few
hours, without permanently altering your control settings.
H To save energy, you can reduce the standard room temperature with
"Economy mode"N (see below).
H You want to heat spontaneously at standard room temperature and provide
DHW. For this, select "Party mode"M (see page23).
Setting economy mode
In economy mode, the standard room temperature will be reduced
automatically.
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. N for "Economy mode".
Economy mode
5592492GB
Ending economy mode
H Economy mode ends automatically
with the next change to central
heating with reduced room
temperature.
H If you want to prematurely
terminate economy mode, press
keys !, ? or § and N again;
the key illumination extinguishes.
22
Room temperature setting
Changing room temperature for a few hours only (cont.)
Setting party mode
H Central heating will be activated at any temperature you select
(party temperature)
H DHW will be reheated to the set temperature
H The DHW circulation pump is switched ON
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. M
for "Party mode"; the party
temperature flashes.
3. a/b for the required
temperature, if you want to
change the room
temperature.
4. d
Party mode
20
ºC
to confirm; the temperature
no longer flashes and is
now saved.
5592492GB
Ending party mode
H Party mode ends automatically
with the next change to central
heating with standard room
temperature, after 8 hours at the
latest.
H If you want to prematurely
terminate party mode, press keys
!, ? or § and M again; the key
illumination extinguishes.
23
Setting up DHW
Setting up constant DHW
Note
The control unit is set so that the settings for DHW heating apply to all
heating circuits. If you want to make changes, contact your local heating
contractor.
Observe the following points if you want to activate DHW heating.
1. "Heating and DHW"G or "DHW
only"L must be selected for
respective heating circuit!, ?
or §.
Check:
Press !, ? or §; G or L
must be illuminated; otherwise
press G or L.
Note
You can select the DHW
temperature (see page25).
0 3 6 9 12 15 18 21 24
1−7
For changing the time program,
see page26.
5592492GB
2. The timing of when DHW heating
with the selected temperature is
enabled for your heating circuit,
and when the DHW circulation
pump (if installed) runs, depends
on the settings of both time
programs B or C (each with
four time phases) for the
respective day.
Check:
H Press !, ? or §,
H Press and hold down B/c or
C/c simultaneously; a time
slot graphic shows the set time
phases.
24
Setting up DHW
Setting up constant DHW (cont.)
Setting the DHW temperature
Press the following keys:
1. F
for "Set DHW
temperature"; the current
set temperature will flash.
2. a/b for the required
temperature.
3. d
to confirm; the temperature
no longer flashes and is
now saved.
DHW temp.setpt.
ºC
5592492GB
w
50
25
Setting up DHW
Setting up constant DHW (cont.)
Setting a time program (switching times)
Heating system without DHW circulation pump
Note
The control unit is set so that the settings for DHW heating apply to all
heating circuits. If you want to make changes, contact your local heating
contractor.
Should you not wish to operate in
automatic mode, you can also set up
individual time programs.
You can select identical time
programs for every weekday or
individual ones for each weekday.
When setting time programs, please
note that your heating system
requires some time to heat the DHW
cylinder to the required temperature.
5592492GB
DHW heating can be
activated/deactivated up to four
times per day (four time phases).
At the factory, automatic mode is set
up in the time program, i.e. DHW
heating is activated parallel to the
central heating time program for the
first available heating circuit.
However, it begins 30minutes earlier
(from 05:30 to 22:00h).
26
Setting up DHW
Setting up constant DHW (cont.)
Heating system with DHW circulation pump
Note
The control unit is set so that the settings for DHW heating apply to all
heating circuits. If you want to make changes, contact your local heating
contractor.
The DHW circulation pump pumps
hot water through a circuit between
the DHW cylinder and the taps to
deliver DHW to the taps as quickly as
possible.
DHW heating and the DHW
circulation pump can be
activated/deactivated up to four
times per day (four time phases).
At the factory, automatic mode is set
up in the time program, i.e. DHW
heating is activated parallel to the
central heating time program for the
first available heating circuit.
However, it begins 30minutes earlier
(from 05:30 to 22:00h).
Should you not wish to operate in
automatic mode, you can also set up
individual time programs.
You can select identical time
programs for every weekday or
individual ones for each weekday.
When setting time programs, please
note that your heating system
requires some time to heat the DHW
cylinder to the required temperature.
Also, activating the DHW circulation
pump is only sensible for those
times when DHW is actually drawn.
The following explains the setting up
of a time program using DHW
heatingB as an example. Set up a
time program for DHW circulation
pumpC in the same way.
5592492GB
For time program setting steps, see
page28.
For a sequence of steps to delete a
time phase, see page29.
27
Setting up DHW
Setting up constant DHW (cont.)
Selecting automatic mode (if required)
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. B
3. a/b for "Automatic?", if
"Automatic?" is not yet
displayed.
for "DHW time program".
4. d
to confirm.
Setting up an individual time program
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. B
for "DHW time program".
Note
If you want to terminate the time
program prematurely, pressB
again and confirm with d.
3. a/b for "Individual?", if
"Individual?" is not yet
displayed.
4. d
to confirm.
5. a/b until
"17" is displayed, if you
want to set up the same
time phases for all days
DHW time program
1−7
or
"Mo", "Tu" etc., is
displayed if you want to set
different time phases for
the displayed weekday.
DHW time program
5592492GB
Mo
28
Setting up DHW
Setting up constant DHW (cont.)
Note
If different time phases are set
for the individual days of the
week, and you want to set up
identical time phases for all
weekdays again, press d when
the display shows "17". All time
phases are returned to their
original condition.
6. d
9. d
to confirm; "DHW phase1
Off" is displayed.
10. a/b for the end of the DHW
phase.
11. d
to confirm; "DHW time
phase1" is displayed.
Note
Pressa if you want to skip a
time phase.
7. d
8. a/b for the starting point of
the DHW heating phase.
to confirm; "DHW phase2
On" is displayed.
12. Proceed for setting the start and
end of DHW heating phases2 to
4 as described under points 8 to
11.
to confirm; "DHW phase1
On" is displayed.
Press the following keys if you want to delete a time phase:
1. !, ? or §, the selected key will
be illuminated.
2. B for "DHW time program".
3. d until the required "DHW
phase OFF" is displayed.
4. b until ":" is displayed for
the end time.
DHW cycle 2 Off
1−7
5592492GB
5. d to confirm, until the boiler
temperature is displayed.
29
Setting up DHW
Setting up DHW for a few hours only
The following functions enable you to heat DHW for a few hours, without
permanently altering your control settings. For this, select "Party mode"M.
During party mode, the DHW circulation pump is active, and central heating
operates at "Party temperature". Set the party temperature to 4ºC (see
page23), if you require no central heating (e.g. in summer).
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. M
for "Party mode"; the party
temperature flashes.
3. a/b for the required
temperature, if you want to
change the room
temperature.
4. d
Party mode
20
ºC
to confirm; the temperature
no longer flashes and is
now saved.
5592492GB
Ending party mode
H Party mode ends automatically
with the next change to central
heating with standard room
temperature, after 8 hours at the
latest.
H If you want to prematurely
terminate party mode, press keys
!, ? or § and M again; the key
illumination extinguishes.
30
Setting up DHW
Setting up DHW once only
The following functions enable you to heat DHW once, without permanently
altering your control settings. For this, select "Party mode"M.
Preconditions:
H Not in "Standby mode" K, and not in "Holiday program" H
H The DHW temperature must be below the set value (see page 25)
Press the following keys:
3. d to confirm; DHW heating
begins.
2. M for "Party mode".
4. After approx. 10s, press M again;
the key illumination extinguishes.
5592492GB
1. !, ? or §, the selected key will
be illuminated.
31
Further settings
Setting date and time
Date and time are factory−set and may be changed manually.
Press the following keys:
1. D
4. a/b for the required date.
for "Time".
2. a/b for the required time.
Date
We
Time
09:05
u
5. d
3. d
16;02;05
to confirm.
to confirm.
"Date" is displayed.
Language selection
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
3. b for the required language.
German
2. c for "Outside temp.".
i
Outdoor temp.
13
ºC
4. d to confirm.
5592492GB
i
32
Further settings
Modifying the boiler heating characteristics
You can alter the heating characteristics if the room temperature does not
meet your requirements for some time.
You alter the heating characteristics by changing the slope and level of the
heating curve. For more information regarding the heating curve, see
page35.
Please observe the modified heating characteristics over several days (if
possible await a major change in the weather), before making further
adjustments.
Make short−term adjustments of the room temperature using rotary
selector"ts" or key E (see page17).
Changing slope and level
For assistance, use the table on page34.
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
2. I
4. d
to confirm.
for "Slope"
Slope
1;4
J
3. a/b for the required value.
Note
Setting the slope or level of the
heating curve too high or too low
will not result in damage to your
heating system.
or
for "Shift".
Shift
5592492GB
0
33
Further settings
Changing the boiler heating characteristics (cont.)
Heating characteristics
Remedy
The living space is too
cold during the heating
season
Adjust heating curve
slope to next higher
value (e.g.1.5)
Slope
The living space is too
hot during the heating
season
Adjust heating curve
slope to next lower
value (e.g.1.3)
Slope
The living space is too
Adjust the heating
cold during transitional curve level to a higher
periods (spring/autumn) value (e.g. +3K)
and during the heating
season
The living space is too
hot during the
transitional periods
(spring/autumn) and
during the heating
season
Adjust the heating
curve level to a lower
value (e.g. 3K)
The living space is too
cold during the
transitional periods
(spring/autumn), but
warm enough during
the heating season
Adjust the heating
curve slope to the next
lower value, and the
level to a higher value
(e g +3K)
(e.g.
+3 K)
Example
Shift
Shift
Slope
Shift
The living space is too
hot during the
transitional periods
(spring/autumn), but
warm enough during
the heating season
Adjust the heating
curve slope to the next
higher value, and the
level to a lower value
(e g 3
(e.g.
3K)
K)
Slope
5592492GB
Shift
34
Further settings
Changing the boiler heating characteristics (cont.)
For technically−minded system users
Heating curves illustrate the relationship between the outside temperature
and the boiler water or the flow temperature. To put it simply: The lower the
outside temperature, the higher the boiler water or flow temperature.
The illustrated heating curves apply subject to the following settings:
H Heating curve level = 0
Different level settings shift the curves parallel in
a vertical direction.
H Standard room temperature = approx. 20ºC.
In the factory, the following settings are made: slope=1.4, level=0.
2.4
3.4
3.2
3.0
2.8
2.6
Slope
Boiler water temperature or
flow temperautre in °C
2.2
2.0
1.8
1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
Outside temperature in °C
5592492GB
A Underfloor heating
B Low temperature heating system
C Heating system with a boiler
water temperature in excess of
75ºC
Examples
H Well insulated house in a sheltered
position (with radiator heating
system): Slope=1.2
H Home in exposed position or with
an older heating system (with
radiator heating system):
Slope=1.6
35
Further settings
Adjusting the display contrast
Press keyd and simultaneously set
the contrast with keysa or b.
Reinstating standard settings
For this, presse.
5592492GB
It is possible to simultaneously reset
all changed values for the heating
circuit to the factory settings.
36
Scanning options
Temperature scanning
Subject to connected components and settings made, you can scan current
temperatures and operating conditions.
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
3. a/b for further scanning of the
list.
2. c
4. c
for "Outdoor temp.".
to end scanning.
Outdoor temp.
5592492GB
i
9
ºC
Order in which temperatures and operating conditions may be scanned:
H Solar DHW temp. DHW
H User no., in connection with
temperature in conjunction with a
heating circuit control unit
solar heating system
Vitotronic050
H Collector temp. in conjunction with
H Holiday program with departure
a solar heating system
and return date, if programmed
H Burner burner hours run
H Outside temperature
H Burner stage 1 hours run, burner
H Boiler water temperature
stage 1
H Flue gas temperature,
H Burner stage 2 hours run, burner
if a sensor is installed
stage 2
H Sensor 17A,
H Number of burner start−ups
if a sensor is installed
H Consumption fuel consumption
H Sensor 17B
subject to appropriate settings
if a sensor is installed
having been made by the heating
H DHW temperature domestic hot
contractor
water temperature
H Solar energy display in kWh, in
H DHW temperature 1 or 2 DHW
conjunction with a solar heating
temperature, if 2 cylinder
system
temperature sensors are available
H Time
H Flow temperature
H Date
for heating circuit with mixer
H Burner ON/OFF
H Standard room temp. (set value)
H Burner stage 1 ON/OFF
H Room temperature (actual value),
H Burner stage 2 ON/OFF
if a Vitotrol remote control is
installed
37
Scanning options
Temperature scanning (cont.)
H Output 20 ON/OFF
H Output 29 ON/OFF
H Output 52 OPEN/CLOSE
0 ¢ Close
1 to 99 (%)
100 ¢ Open
H Cylinder primary pump ON/OFF
H DHW circulation pump ON/OFF
H Heating circuit pump ON/OFF
H Mixer open/closed
0 ¢ Closed
1 to 99 (%)
100 ¢ Open
H Solar pump ON/OFF
H Solar pump hours run
H Language
Time program scanning
Press the following keys:
1. !, ? or §, the selected key will
be illuminated.
3. For changing the time programs,
see page18 and 26.
2. A/c for central heating time
program
or
B/c for DHW time program
or
C/c for DHW circulation pump
time program
press and hold down
simultaneously; a time slot
graphic shows the set time
phases.
0 3 6 9 12 15 18 21 24
5592492GB
1−7
38
Scanning options
Scanning party or economy mode
Press the keys !, ? or §, the
selected key and the key of the active
program will be illuminated (see
page 10).
Scanning fault display
A
B
CD
Boiler sensor
A Fault display
B Fault symbol
C Fault number
D Fault code
5592492GB
If your heating system has developed a fault, it will be displayed and
indicated by the flashing red fault indicator.
You can check the fault code on the display and then notify your heating
contractor accordingly. This allows the heating contractor to better prepare
for the service call and may save additional travelling costs.
39
Scanning options
Scanning fault display (cont.)
Press the following keys:
1. c
for troubleshooting.
2. a/b to display further fault
codes, if several faults are
active.
3. d
To recall fault codes press the
following keys:
1. d
for approx. 2s.
2. a/b to acknowledge the fault
codes.
to "Acknowledge" all fault
codes.
4. a/b for "Yes" or "No".
With "Acknowledge? Yes"
you confirm that you have
noted the fault.
5. d
to confirm.
5592492GB
Note
If the fault has not been rectified, the fault message will be redisplayed at
07.00h the following day.
The red fault indicator flashes until the fault has been rectified.
40
What to do if...?
Rooms are too cold
Remedy
The heating system is switched OFF
H Switch ON/OFF switch"8" ON
(see page11)
H Switch ON mains electrical
isolator, if installed (outside the
boiler room)
H Check the fuse in the power
distribution (main domestic fuse)
Control unit incorrectly adjusted
Check and correct settings, if
required:
H Heating circuit must be switched
ON (see page13)
H Room temperature
(see page17)
H Time
(see page32)
H Boiler heating characteristics
(see page34)
Only when operating with DHW
cylinder:
DHW priority
(wp in the display)
Wait until the DHW cylinder has
been heated up
(p extinguishes from the display)
No fuel
With oil/LPG:
Check the fuel reserves and re−order,
if required
With natural gas:
Open the gas shut−off valve or
enquire with your gas supply
company if required
Control unit fault:
"Fault" is displayed and the red fault
indicator flashes
Check the type of fault (see page39)
and notify your local heating
contractor
5592492GB
Cause
41
What to do if...?
Rooms are too cold (cont.)
Remedy
False burner start:
"Fault" is displayed, the red fault
indicator at the control unit flashes,
and the fault indicator on the burner
lights up in red
H With a pressure jet burner:
Press the reset button on the
burner hood.
H With an atmospheric boiler:
Press the reset button on the boiler
front panel.
Contact your local heating
contractor if the burner still fails to
start.
Vitoair draught stabiliser faulty
Contact your local heating
contractor.
Reset Vitoair to manual:
Press the rotary selector on the
motor and turn it to the limit stop
beyond position"3".
Mixer motor faulty
Adjusting the mixer manually
5592492GB
Cause
42
What to do if...?
Rooms are too hot
Remedy
Control unit incorrectly adjusted
Check and correct settings, if
required:
H Room temperature
(see page17)
H Time
(see page32)
H Boiler heating characteristics
(see page34)
Control unit fault or outside
temperature sensor/boiler
temperature sensor faulty:
"Fault" is displayed and the red fault
indicator flashes
Check the type of fault (see page39)
and notify your local heating
contractor
Emissions test switch"S" shows
"h"
Set emissions test switch"S" to
"a" (see page8)
5592492GB
Cause
43
What to do if...?
No DHW is available
Remedy
The heating system is switched OFF
H Switch ON/OFF switch"8" ON
(see page11)
H Switch ON mains electrical
isolator, if installed (outside the
boiler room)
H Check the fuse in the power
distribution (main domestic fuse)
Control unit incorrectly adjusted
Check and correct settings, if
required:
H DHW heating must be switched
ON (see page13 and 14)
H DHW temperature
(see page25)
H Time
(see page32)
No fuel
See page41
Control unit fault:
"Fault" is displayed and the red fault
indicator flashes
Check the type of fault (see page39)
and notify your local heating
contractor
False burner start:
"Fault" is displayed, the red fault
indicator at the control unit flashes,
and the fault indicator on the burner
lights up in red
See page42
Vitoair draught stabiliser faulty
See page42
Cylinder primary pump is faulty
Contact your local heating contractor
5592492GB
Cause
44
What to do if...?
The DHW is too hot
Cause
Remedy
Control unit incorrectly adjusted
Check and correct the DHW
temperature, if required (see
page25)
Sensor fault
Contact your local heating
contractor
Emissions test switch"S" shows
"h"
Set emissions test switch"S" to
"a" (see page8)
The display flashes "Fault"
Cause
Remedy
Heating system fault
Check the type of fault (see page39)
and notify your local heating
contractor
The display shows "Service"
Cause
Remedy
Maintenance time has been reached
Arrange for your local heating
contractor to service your heating
system
The display shows "Remote control"
Remedy
A remote control is connected to the
heating circuit
Make adjustments or carry out
scanning at the remote control (see
separate operating instructions)
5592492GB
Cause
45
What to do if...?
The display shows "External control"
Cause
Remedy
The heating program set at the
control unit was changed over by an
external device
No action required. The heating
program changeover was manually
selected.
The display shows "Central control"
Cause
Remedy
The settings or the holiday and day
programs will be taken from the
heating circuit, as "Central control" is
set
The display shows "Slab curing program"
Cause
Remedy
The screed function has been set up
Wait until this function has
terminated
The display shows "Without function"
Remedy
No function has been allocated to the
key you pressed, or the function can
only be adjusted on your remote
control
5592492GB
Cause
46
Ordering fuel oil
Ordering fuel oil
Fuel oil additives
Fuel oil additives are materials that
can be used to
H improve fuel stability during
storage,
H improve thermal stability of fuel
and
H reduce odour during filling.
!
Bio−fuels
Bio−fuel is made from vegetable oil,
e.g. sunflower or rapeseed oil.
!
Please note
Bio−fuels can lead to damage
on Viessmann oil burners.
Their use is not permissible.
Please note
Fuel oil additives can create
residues and impair the safe
operation of your heating
system.
The use of fuel oil additives
which leave residues is not
acceptable.
Combustion improvers
Combustion improvers are additives
for optimising fuel oil combustion.
Viessmann oil burners do not require
combustion improvers, as these
burners operate with clean and
efficient combustion.
!
Please note
Combustion improvers can
create residues and impair the
safe operation of your heating
system.
The use of combustion
improvers which leave
residues is not acceptable.
5592492GB
If in doubt ask your local fuel oil supplier.
47
Repairs
Cleaning
All devices may be cleaned with a
commercially available domestic
cleaning agent (non−scouring).
Inspection and maintenance
Inspection and maintenance of your heating system is prescribed by the
Energy Savings Order [Germany] and the standards DIN4755, DIN4756,
DIN19888 and EN806 and/or local regulations.
Regular maintenance ensures trouble−free, energy−efficient and
environmentally responsible heating operation. For this, we strongly advise
you to arrange an inspection and maintenance contract with your local
heating contractor.
Boiler
Increasing boiler contamination
raises the flue gas temperature and
thereby increases energy losses. For
that reason, all boilers should be
cleaned annually.
checked annually by a heating
contractor. The anode function can
be checked without interrupting
system operation. The heating
contractor will check the earth
current with an anode tester.
DHW cylinder
DIN 1988−8 and EN806 prescribe that
maintenance and cleaning should be
carried out no later than two years
after commissioning and thereafter
as necessary.
Only a recognised heating contractor
should clean the inside of a DHW
cylinder and the DHW connections.
Refill any water treatment equipment
(e.g. a lock or injection equipment) in
good time, if such equipment is
installed in the cold water supply of
the DHW cylinder. Observe the
manufacturer’s details.
Safety valve (DHW cylinder)
Check the safety valve function every
six months by venting, or have it
checked by your heating contractor.
The valve seat may become
contaminated (see the valve
manufacturer’s instructions).
48
5592492GB
In addition for Vitocell 100:
We recommend that the correct
function of the sacrificial anode is
DHW filter (where installed)
To maintain high hygienic standards
H on non−back−flushing filters,
replace filter element every
6 months (visual check every
2 months);
H on back−flushing filters, back−flush
every 2 months.
Keyword index
Keyword index
A
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Automatic mode . . . . . . . . . . . . . . . . . . . . . 26, 27, 28
B
Boiler room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Boiler room requirements . . . . . . . . . . . . . . . . . . 3
Burner, hours run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
C
Cleaning tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Collector temperature . . . . . . . . . . . . . . . . . . . . . . . 37
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 11
Contrast settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Control unit commissioning . . . . . . . . . . . 11
Control unit shutdown . . . . . . . . . . . . . . . . . . . . . . 12
Cylinder primary pump . . . . . . . . . . . . . . . 8, 38
F
Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 8, 36
Factory settings, heating system . . . . . 6
Fault display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8,39
Fault message acknowledgement 40
Fault message call−up . . . . . . . . . . . . . . . . . . . . . . . . 40
Faults (errors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Fault messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Flue gas smell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Frost protection . . . . . . . . . . . . . . . . . . . . . . . . 6, 13, 14
Fuel consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
G
Gas shut−off valve . . . . . . . . . . . . . . . . . . . 2, 11, 12
Gas smell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
H
Heating and DHW . . . . . . . . . . . . . . . . . . . . . . 6, 8, 13
Heating characteristics . . . . . . . . . . . . . . . . . . . . . . 34
Heating circuit selection . . . . . . . . . . . . . . . . . . . 10
Heating circuit shutdown . . . . . . . . . . . . . . . . . 14
Heating circuit start−up . . . . . . . . . . . . . . . . . . . . . 13
Heating circuit pump . . . . . . . . . . . . . . . . . . . . 9, 38
Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 33
Heating system shutdown . . . . . . . . . . . . . . 12
Heating system start−up . . . . . . . . . . . . . . . . . . . 11
Heating times, changing . . . . . . . . . . . . . . . . . . 19
Heating program changeover . . . . . . . . 46
Holiday . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Holiday program setting . . . . . . . . . . . . . . . . . . 20
5592492GB
D
Danger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Date, changing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 32
Day temperature
(standard room temperature) . . . . . . . . 17
DHW cylinder
(inspection and maintenance) . . . . . . . 48
DHW circulation pump . . . . . . . . . . 8, 27, 38
DHW heating once . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
DHW heating shutdown . . . . . . . . . . . . . . 14,15
DHW heating start−up . . . . . . . . . . . . . . . . . 13, 14
DHW production
(automatic mode) . . . . . . . . . . . . . . . . . . . . . . . . . 26, 27
DHW temperature setting . . . . . . . . . . . . . . . . 25
Domestic hot water . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 8
Drinking water filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
E
Economy mode "û" . . . . . . . . . . . . 8, 22, 39
Emissions test switch . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Energy saving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20, 22
Equipment shutdown . . . . . . . . . . . . . . . . . . . . . . . . 12
Equipment start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
49
Keyword index
Keyword index (cont.)
K
Key illumination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
L
Lamps (diodes) . . . . . . . . . . . . . . . . . . . 8, 11,12, 39
Language selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Level of heating curve, changing . 33
M
Mains ON/OFF switch . . . . . . . . . . . . 8, 11, 12
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Maintenance contract . . . . . . . . . . . . . . . . . . . . . . . . 48
Maintenance display . . . . . . . . . . . . . . . . . . . . . . . . . . 45
N
Night temperature
(reduced room temperature) . . . . . 8, 17
Notice of completion . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
O
Operating display . . . . . . . . . . . . . . . . . . . . 8, 11, 12
P
Party mode"g" . . . . . . . 8, 23, 30, 31, 39
Party temperature setting . . . . . . . . . . . . . . . . 23
Pressure gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Programming unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Programs, setting . . . . . . . . . . . . . . . . . . . . . . . . . 18, 26
50
R
Radio clock reception . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Radio clock receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Reduced room temperature
(night temperature) . . . . . . . . . . . . . . . . . . 6, 8, 17
Remote control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7, 45
Renewed start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Requirements for boiler room . . . . . . . . . . 3
Room temperature changing . . . . . . . . . 17
S
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Safety valve (DHW cylinder) . . . . . . . . . . . . 48
Scanning actual temperature . . . . . . . . . 37
Scanning DHW temperature . . . . . . . . . . 37
Scanning holiday program . . . . . . . . . . . . . . 37
Scanning information . . . . . . . . . . . . . . . . . . . . . . . . 37
Scanning operating conditions . . . . . 37
Scanning solar energy . . . . . . . . . . . . . . . . . . . . . . 37
Scanning temperatures and
operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Scanning time program . . . . . . . . . . . . . . . . . . . 38
Screed drying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Slope of heating curve, changing 33
Spring/autumn
(heating and DHW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Standard factory settings . . . . . . . 6, 8, 36
Standard room temperature
(day temperature) . . . . . . . . . . . . . . . . . . . . . . . . . . 8, 17
Standard settings . . . . . . . . . . . . . . . . . . . . . . 6, 8, 36
Standby mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14, 20
Summer mode
(DHW only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Switching OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Switching times, setting . . . . . . . . . . . . . 18,26
Symbols in the display . . . . . . . . . . . . . . . . . . . . . . . . 9
System shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
System start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Solar circuit pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5592492GB
I
Illuminated keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Indicators (diodes) . . . . . . . . . . . . 8, 11,12, 39
Individual time programs . . . . . . . . . 18, 19
26, 27, 28
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Initial start−up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Instructions on safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Keyword index
Keyword index (cont.)
W
What to do if...? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Where to find the controls . . . . . . . . . . . . . . . . . 7
Winter operation
(heating and DHW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Work on the equipment/heating
system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5592492GB
T
Temperature scanning . . . . . . . . . . . . . . . . . . . . . . 37
Temperature setting . . . . . . . . . . . . . . . . . . . . 17, 25
Time phases, deleting
(DHW only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Time phases, deleting
(heating and DHW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Time programs
H central heating . . . . . . . . . . . . . . . . . . . . . . . . 6, 8, 18
H DHW circulation pump . . . . . . . . 6, 8, 27
H DHW heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 6, 8, 26
Time setting (changing) . . . . . . . . . . . . . . . 8, 32
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
51
Applicability
For heating systems with boiler, DHW cylinder and Vitotronic300, typeGW2,
part no.7187099
Printed on environmentally friendly,
chlorine−free bleached paper
Certification
Contact your local heating contractor if you have any questions regarding the
maintenance and repair of your heating system.
You may, for example, find local heating contractors under
www.viessmann.de on the internet.
Viessmann Werke GmbH&Co KG
D35107 Allendorf
Tel:
+49 6452 700
Fax: +49 6452 702780
www.viessmann.de
Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Tel:
+44 1952 675000
Fax: +44 1952 675040
E−mail: info−[email protected]
52
5592492GBSubject to technical modifications.
Your contact

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement