EPS 2404 INPUT Input Frequency Protection Isolation Safety EMI-EMC Standard Input Connection MECHANICAL Case Dimension Casing Material Automatic Switch-Mode Battery Charger GENERAL FEATURES ! 2 Stage charging cycle ! Suitable for batteries up to 34 AH in cyclic application ! Suitable for up to 50 AH in a standby or float application ! Fully Automatic Operation ! Compact and Light weight ! Fully overload protected (auto recovery) ! Simple LED charging indicator Weight Cooling Warranty 90-260 VAC 47-63Hz Internal Primary Input-Output 3000VAC Input-Case 2500 VAC Output-Case 500 VAC Designed to IEC 950 FCC Class B, CE, C-Tick AS 3193 3 Core SAA Cable IEC 105L X 207W X 60H Extruded Anodized Aluminum 1. Kg. Convection cooled 12 Months ELECTRICAL Topology Efficiency Boost Charge Voltage Float Charge Voltage Output Charge Current Ripple & Noise Line Regulation Short Circuit Protection Over Current Protection Reverse Polarity Protection Switching DC Power 85% 29.4VDC 27.6VDC 4 Amps 150 mV +/- 0.5% Over Input Range +/- 1% 0-100% Load 500 mS 20 [email protected] Output Output Shutdown Primary Power Limit Internal Relay ENVIRONMENTAL Operating Temp. Range Storage Temperature Relative Humidity Altitude -5O to 50OC O O -30 C to +85 C 10% to 90% 0-3000m Load regulation Rise Time Hold-up Time INVENSYS ENERGY SYSTEMS PTY LTD Melb (03) 9590 0555 , Syd (02) 9878 5000, Perth (08) 9240 4666, Brisb (07) 3217 2090