optotronic ot 120/220-240/24 p

optotronic ot 120/220-240/24 p
Product datasheet
OPTOTRONIC OT 120/220-240/24 P
Suitable for outdoor applications
__
Product benefits
High surge protection: up to 3 kV (L-N) / 6 kV (L/N-PE)
High IP protection (IP67)
Slim housing design and flexible mounting concept
Product features
SELV equivalent
July 17, 2012, 13:17:15
OPTOTRONIC OT 120/220-240/24 P
© 2012, OSRAM AG. All rights reserved.
Page 1 of 6
Product datasheet
Technical data
Electrical data
__
Nominal current
0.60 A 1)
Input voltage
198…264 V 2)
Nominal voltage
220…240 V
Mains frequency
50/60 Hz
Output voltage
24 V 3)
Device power loss
13.5 W 4)
Max. no. of ECGs on circuit breaker 10 A
6
Max. no. of ECGs on circuit breaker 16 A
10
Output power
120 W
Power loss in stand-by mode
<1.5 W
Inrush current
60 A 5)
Rated power factor λ
0.95/0.90
Galvanic isolation primary/secondary
3.75 kV 7)
No-load proof
Yes
Surge capability (L-N)
3 kV
Surge capability (L/N-Ground)
6 kV
6)
1) At 230 V
2) Permitted voltage range
3) +1.0/-0.5 V
4) Maximum
5) Maximum / At 250 µs
6) Minimum/Full load at 230 V/Half load at 230 V
7) SELV-equivalent
Dimensions & weight
Maximum cable length – system
10 m
Length
250.0 mm
Width
60.0 mm
Height
39.0 mm
Product weight
1100.00 g
Cable cross-section, output side
1.5 mm² 1)
Cable cross-section, input side
1.0 mm² 1)
1) Flexible
July 17, 2012, 13:17:15
OPTOTRONIC OT 120/220-240/24 P
© 2012, OSRAM AG. All rights reserved.
Page 2 of 6
Product datasheet
Product line drawing with letters
__
Temperatures
Ambient temperature range
-25…+55 °C
Operating temperature
80 °C 1)
Max.housing temperature in case of fault
100 °C
1) Maximum at the Tc-point
Lifespan
ECG lifetime
50000 h 1)
1) At tcase = 70°C at tc point / 10 % failure rate
Additional product data
ECG efficiency
July 17, 2012, 13:17:15
OPTOTRONIC OT 120/220-240/24 P
90 %
© 2012, OSRAM AG. All rights reserved.
Page 3 of 6
Product datasheet
Capabilities
Dimmable
No
Overload protection
Automatic reversible
Overtemperature protection
Automatic reversible
Short-circuit protection
Automatic reversible
Suitable for fixtures with prot. class
I
Certificates & standards
Type of protection
IP67
__
July 17, 2012, 13:17:15
OPTOTRONIC OT 120/220-240/24 P
© 2012, OSRAM AG. All rights reserved.
Page 4 of 6
Product datasheet
Logistical Data
Product code
Packaging unit
(Pieces/Unit)
Dimensions (height x
width x length)
Gross weight
Volume
4008321981707
Folding carton box
1
100 mm x 58 mm x
340 mm
1180.00 g
1.97 dm³
4008321981769
Shipping carton box
10
400 mm x 172 mm x
560 mm
13400.00 g
38.53 dm³
__
July 17, 2012, 13:17:15
OPTOTRONIC OT 120/220-240/24 P
© 2012, OSRAM AG. All rights reserved.
Page 5 of 6
Product datasheet
Disclaimer
Subject to change without notice. Errors and omission excepted. Always make sure to use the most recent release.
__
July 17, 2012, 13:17:15
OPTOTRONIC OT 120/220-240/24 P
© 2012, OSRAM AG. All rights reserved.
Page 6 of 6
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement