Vicinity Map Project Team Architectural Symbols Abbreviations

Vicinity Map Project Team Architectural Symbols Abbreviations
Project Team
100% Construction Documents - May 14, 2012
CLIENT
CLIENT
ARCHITECT
MECHANICAL
ELECTRICAL
Utah DFCM
4110 State Office Building
Salt Lake City, UT 84114
Ph: 801.538.3018
Fx: 801.538.3267
Contact:
Utah Valley University Facilities Planning
800 West University Parkway
Orem, UT 84058
Ph: 801.863.7534
Fx: 801.863.8473
Contact:
Method Studio, Inc.
925 South West Temple
Salt Lake City, UT 84101
Ph: 801.532.4422
Fx: 801.328.4187
Contact: Joe Smith
WHW Engineering, Inc.
8619 South Sandy Parkway #101
Sandy, UT 84070
Ph: 801.466.4021
Fx: 801.466.8536
Contact: Win Packer
Ken Garner Engineering, Inc.
102 West 500 South, Suite 225
Salt Lake City, UT 84101
Ph: 801.328.8800
Fx: 801.328.8802
Contact: Sullivan Watson, Jr.
Abbreviations
A
A/C
AB
ABV
AC or ACOUS
ACC
ACFL
ACPL
ACT
ACU
AD
AD
ADD
ADDL
ADH
ADJ
ADJT
AFF
AGG
AHU
ALLOW
ALT
ALUM
ANC
ANG
ANOD
AP or AC PNL
APC
APPROX
APT
ARCH
ASC
ASPH
AUTO
AVE
AVG
AWT
Air Conditioning
Anchor Bolt
Above
Acoustical
Access
Access Floor
Acoustical Plaster
Acoustical Tile
Air Conditioning Unit
Access Door
Area Drain
Addendum
Additional
Adhesive
Adjacent
Adjustable
Above Finish Floor
Aggregate
Air Handling Unit
Allowance
Alternate
Aluminum
Anchor, Anchorage
Angle
Anodized
Access Panel
Architectural Precast Concrete
Approximate
Apartment
Architect(ural)
Above Suspended Ceiling
Asphalt
Automatic
Avenue
Average
Acoustical Wall Treatment
C
C
C
C to C
C of O
CAB
CANTL
CB
CCTV
CEM
CER
CF
CFM
CG
CH
CHAM
CHBD
CHEM
CI
CIPC
CIR
CJ
CKT
CL
CLG
CLG HT
CLL
CLO
CLR
CLRM
CM
CM
CMP
CMU
CND
CO
CO
COL
COMM
CONC
COND
CONF
CONN
CONST
CONT
CONTR
COORD
CORR
CORR
CPT
CRS
CRT
CSMT
CST
CSWK
CT
CT
CTR
CUH
CW
CY
CYL
Celsius, Degree
Channel
Center to Center
Certificate Of Occupancy
Cabinet
Cantilever
Catch Basin
Closed Circuit Television
Cement
Ceramic
Cubic Foot
Cubic Feet Per Minute
Corner Guard
Coat Hook
Chamfer
Chalkboard
Chemical, Chemistry
Cubic Inch
Cast-In-Place Concrete
Circle
Control Joint
Circuit
Center Line
Ceiling
Ceiling Height
Contract Limit Line
Closet
Clear(ance)
Classroom
Centimeter(s)
Construction Manager
Corrugated Metal Pipe
Conc. Masonry Unit
Conduit
Change Order
Clean Out
Column
Communication Outlet
Concrete
Condenser or Condensate
Conference
Connect(ed)(ion)
Construction
Continuous
Contractor
Coordinate
Corridor
Corrugated
Carpet(ed)
Course(s)
Computer Terminal
Casement
Cast Stone
Casework
Ceramic Tile
Cooling Tower
Center
Cabinet Unit Heater
Cold Water
Cubic Yard
Cylinder
D
D
DB
DBL
DBL ACT
DC
Depth
Decibel
Double
Double Acting
Direct Current
East
Each
Each End
Each Face
Exhaust Fan
Exhaust Grille
Exterior Insulation & Finish System
Expansion Joint
Elevation
Electrical
Elevator
Emergency
Enclosure
Engineer
Entrance
Equal
Equipment
Escalator
Estimate
Establish
Electric Water Cooler
Exhaust
Existing
Expansion
Exterior
Extrusion
F
FA
FAS
FB
FBO
FCO
FD
FDTN
FE
FEC
FF
FF&E
FFE
FFL
FH
FHC
FHMS
FHWS
FIN
FIX
FL
FLASH
FLR
FLUOR
FOC
FOF
FOM
FOS
FOW
FP
FR
FRM
FS
FSP
FT'
FTG
FUR
FURN
FUT
FV
FVC
Fire Alarm
Fasten, Fastener
Face Brick
Furnished By Others
Floor Cleanout
Floor Drain
Foundation
Fire Extinguisher
Fire Extinguisher Cabinet
Finished Floor
Fixtures, Furniture & Equipment
Finished Floor Elevation
Finished Floor Line
Fire Hydrant/Hose
Fire Hose Cabinet
Flat Head Machine Screws
Flat Head Wood Screws
Finish
Fixture
Flow Line
Flashing
Floor
Fluorescent
Face of Concrete
Face Of Finish
Face of Masonry
Face of Stud
Face of Wall
Fireproof
Fire Rated, Fire Retardant
Frame
Full Size
Fire Stand Pipe
Foot, Feet
Footing
Furring
Furnish
Future
Field Verify
Fire Valve Cabinet
G
G
GA
GAL
GALV
GB
GC
GEN
GFRC
GFRG
GL
GLU LAM
GR
GR BM
GRND
GSF
GU
GWB
GYP BD
GYP
Gas
Gage or Gauge
Gallon
Galvanized
Grab Bar
General Contract(or)
Generator
Glass Fiber Reinforced Concrete
Glass Fiber Reinforced Gypsum
Glass
Glue Laminated
Grade
Grade Beam
Ground
Gross Square Feet
Gutter
Gypsum Wallboard
Gypsum Wallboard
Gypsum
H
H
H PT
HB
HC
HD
HDBD
HDR
HDWR
HDWD
HJT
HM
HNDRL
HORIZ
HP
HR
HT
HTG
HTR
High
High Point
Hose Bibb
Hollow Core
Head
Hardboard
Header
Hardware
Hardwood
Head Joint
Hollow Metal
Handrail
Horizontal
Horsepower
Hour
Height
Heating
Heater
HVAC
HW
HWH
HWY
HYD
I
ID
IF
ILLUM
IN"
INC
INFO
INSUL
INSUL PNL
INT
INVT
INVT EL
Heating, Ventilating, Air Conditioning
Hot Water
Hot Water Heater
Highway
Hydrant
Inside Diameter
Inside Face
Illumination
Inches
Include(d) (ing)
Information
Insulation
Insulated Panel
Interior
Invert
Invert Elevation
Q
QT
QT
QTY
QTR
QUAL
J
JAN
JB
JC
JST
JST BR
JT
Janitor
Junction Box
Janitor's Closet
Joist
Joist Bearing
Joint
K
KD
KIT
KO
KPL
KW
Knocked Down
Kitchen
Knockout
Kick Plate
Kilowatts
Length
Laboratory
Laminated
Lavatory
Large
Left Hand
Linear
Live Load
Locate, Location
Longitudinal
Low Point
Light
Lighting
Lintel
Louver
Lightweight
Lightweight Concrete
S
S
SA
SAN
SC
SCD JT
SCHED
SE
SECT
SHT
SIM
SPEC
SPKR
SQ
SQ FT or SF
ST STL or SS
STAG
STC
South
Supply Air
Sanitary
Solid Core
Scored Joint
Schedule
Southeast
Section
Sheet
Similar
Specification
Speaker
Square
Square Foot
Stainless Steel
Staggered
Sound Transmission Coefficient
STD
STL
STOR
STRUCT
STRUCT STL
SUSP
SW
SW
SYS
Standard
Steel
Storage
Structural
Structural Steel
Suspended
Southwest
Switch
System
T
T
T&G
TB
TEL
TEMP
TEMP
TEMP GL
TEX FIN
THERM
THK
TKBD
TOB
TOC
TOD
TOF
TOP
TOPAR
TOS
TOW
TPD
TR
TV
TYP
Tread
Tongue and Groove
Towel Bar
Telephone
Temperature
Temporary
Tempered GlassL
Textured Finish
Thermal
Thick(ness)
Tackboard
Top of Beam
Top of Curb (Concrete)
Top of Deck
Top of Footing
Top of Pier
Top of Parapet
Top of Steel
Top of Wall
Toilet Paper Dispenser
Transom
Television
Typical
U
UNFIN
UNO
Unfinished
Unless Noted Otherwise
UR
USG
UTIL
Urinal
United States Gage
Utility
V
V
VAL
VAR
VB
VCT
VEN
VENT
VERT
VEST
VIF
VIT
VOL
VWC
Volt
Value
Varnish
Vapor Barrier
Vinyl Composition Tile
Veneer
Ventilating
Vertical
Vestibule
Verify In Field
Vitreous
Volume
Vinyl Wall Covering
W
W
W
W/
W/O
WC
WD
WDW
WF
WG
WH
WPT
WSCT
WT
WTW
WWF
West
Wide, Width
With
Without
Water Closet
Wood
Window
Wide Flange
Wired Glass
Water Heater
Working Point
Wainscot
Weight
Wall to Wall
Welded Wire Fabric
Y
YD
Yard
SYMBOLS:
&
@
#
Ø
AND
AT
POUND OR NUMBER
DIAMETER OR ROUND
M
M
MAINT
MAN
MANF
MAS
MATL
MAX
MBR
MDF
MECH
MED
MEMB
MEZZ
MFR
MH
MIN
MIN
MIR
MISC
MIX
MLDG
MLWK
MM
MO
MOD
MS
MTD
MTL
MTR
MULL
Meter
Maintenance
Manual
Manufacturer
Masonry
Material
Maximum
Member
Medium Density Fiberboard
Mechanical
Medium
Membrane
Mezzanine
Manufacturer
Manhole
Minimum
Minute
Mirror
Miscellaneous
Mixture
Molding
Millwork
Millimeter
Masonry Opening
Modified, Modular
Machine Screw
Mounted
Metal
Mortar
Mullion
N
N
NA
NE
NIC
NO, Num, #
NOM
NORM
NRC
NTS
NW
North
Not Applicable
Northeast
Not In Contract
Number
Nominal
Normal
Noise Reduction Coefficient
Not to Scale
Northwest
O
OA
OB
OB GL
OC
OD
OFF
OFOI
OH
OPNG
OPP
ORD
ORIG
OTO
OZ
Overall
Obscure
Obscure Glass
On Center
Outside Diameter
Office
Owner Furnished Owner Installed
Overhead
Opening
Opposite
Overflow Roof Drain
Original
Out to Out
Ounce
P
PC
PCF
PERF
PERP
PL
PL
PLAM
PLAS
PLUMB
PLYWD
PNL
PR
PREFAB
PRELIM
PROJ
PROP
PSF
PSI
PT
PT
PTD
PTD
PTN
PVC
PVMT
PWD
Precast Concrete
Pounds per Cubic Foot
Perforated
Perpendicular
Plate
Property Line
Plastic Laminate
Plaster
Plumbing
Plywood
Panel
Pair
Prefabricated
Preliminary
Projection
Property
Pounds per Square Foot
Pounds per Square Inch
Paint
Point, Point of Tangent
Painted
Paper Towel Dispenser
Partition
Polyvinyl Chloride
Pavement
Plywood
Cover Sheet / General Information
Code Analysis
Radius
Riser
Return Air
Rubber Base
Reinforced Concrete Pipe
Roof Drain
Reference
Reinforcing Bar
Recessed
Receptacle
Rectangular
Refrigerator
Regular
Reinforcing (ed)
Required
Return
Revision
Roofing
Right Hand
Relief
Room
Round
Rough Opening
Right-of-Way
Railroad
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
CAST-IN-PLACE CONCRETE
PRECAST CONCRETE
ARCHITECTURAL
R
R, RAD
R
RA
RB
RCP
RD
RE or REF
REBAR
REC
RECP
RECT
REFR
REG
REINF
REQD
RET
REV
RFG
RH
RLF
RM
RND
RO
ROW
RR
L
L
LAB
LAM
LAV
LG
LH
LIN
LL
LOC
LONG
LP
LT
LTG
LTL
LVR
LWT
LWT CONC
GI001
GI002
studio inc.
03 CONCRETE
GENERAL
Quarry Tile
Quart
Quantity
Quarter
Quality
method
Architectural Symbols
AD101
AD102
AE101
AE102
AE103
AE110
AE301
AE302
AE501
AE601
NEW WALL
REVISION CLOUD
Demolition Floor Plan - Classroom Area
Demolition Ceiling Plan - Classroom Area
Floor Plan - Classroom Area
Floor Framing Plan - Classroom Area
Finish Plan - Classroom Area
Reflected Ceiling Plan - Classroom Area
Sections
Section Details
Details
Door Schedule / Interior Elevations
EXISTING WALL TO BE
REMOVED
1
A101
PG001
PD101
Mechanical General Notes & Legend
Mechanical Classroom Demo Floor Plan
Mechanical Classroom Floor Plan
Mechanical Details
Mechanical Schedules
1
A101
DOOR TAG
CONCRETE MASONRY UNITS
FLOOR LEVEL SYMBOL
GLASS BLOCK
CEILING HEIGHT SYMBOL
STONE
1i
KEYNOTE SYMBOL
CAST STONE
1i
WALL TYPE SYMBOL
GROUT
Name
Elevation
C1 10' - 0"
SIM
BUILDING/DETAIL SECTION
MECHANICAL
MG001
MD101
ME101
ME501
ME601
BRICK
101
EXISTING WALL TO
REMAIN
SIM
DETAIL REFERENCE
0' - 1 1/2"
DIMENSION
1
A101
Plumbing Legend and General Notes
Plumbing Classroom Demo Floor Plan
SIM
04 MASONRY
REVISION INDICATOR
1
05 METALS
STEEL
LOCATION ON SHEET
SHEET NUMBER
ALUMINUM
06 WOODS AND PLASTICS
BREAK LINE
PROJECT NORTH
ARROW
ELECTRICAL
EG001
EDL101
ED101
EL102
EP102
EY102
EX501
Symbols, Abbreviations, & Sheet Index
Lighting Demolition Plan
Electrical Demolition Plan
Lighting Floor Plan
Power Floor Plan
System Floor Plan
Electrical Details & Schedules
Room name
101
150 SF
CONTINUOUS WOOD
FOR TRUE NORTH
SEE CIVIL
DRAWINGS
ROOM NAME
ROOM NUMBER
AREA
INTERMITTENT WOOD
PLYWOOD
FINISH WOOD
1i
INTERIOR PARTITION TYPE SYMBOL
HARDBOARD
A101
PARTICLE BOARD
SHEET NUMBER SEQUENCE
1t
SOLID SURFACE MATERIAL
SHEET TYPE
WINDOW TYPE SYMBOL
DISCIPLINE
BENCHMARK/SPOT ELEV.
SYMBOL
1
0
BATT INSULATION
LOOSE FILL INSULATION
View Name
1/8" = 1'-0"
RIGID INSULATION
R101
08 DOORS & WINDOWS
COLUMN LINE/GRID INDICATOR
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
UVU Admin Building
Classroom Remodel
STEEL
09 FINISHES
GYPSUM BOARD
Vicinity Map
Utah Valley University Campus
800 W University Parkway
Orem, UT 84058
DFCM PROJECT # 1 2 0 3 5 7 9 0
BA
project#:
date:
12.0250
05 / 14 / 2012
revisions :
Cover Sheet /
General Info
15
Balance
Bulletin Board
Back of Curb
Board
Bottom Face
Bottom Footing Elevation
Bumper Guard
Bed Joint
Building Line
Building
Block
Blocking
Boiler
Below
Beam
By Others/Owner
Bottom of Curb
Bottom Of Steel
Bottom
Bearing Plate
Bedroom
Bearing
Bridging
Brick
Bracket
Bronze
Both Sides
Basement
Between
Built-up Roofing
Bevel(ed)
Both Ways
Beyond
E
E
EA
EE
EF
EF
EG
EIFS
EJT
EL or ELEV
ELEC
ELEV
EMER
ENCL
ENGR
ENTR
EQ
EQUIP
ESC
EST
ESTB
EWC
EXH
EXIST'G
EXP
EXT
EXTRU
Degree
Demolish, Demolition
Department
Drinking Fountain
Double Hung
Diameter
Diagonal
Diffuser
Dimension
Direction, Director
Dispenser
Distribution
Division
Dark
Dead Load
Demountable
Down
Door Opening
Dampproofing
Deep
Door
Downspout
Design
Detail
Duplicate
Dishwasher
Drawing
Dowel(s)
Drawer
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
consultants:
TE
TA
RS
TE
IN
B
BAL
BBD
BC
BD
BF
BFE
BG
BJT
BL
BLDG
BLK
BLKG
BLR
BLW
BM
BO
BOC
BOS
BOT
BPL
BR
BRG
BRIDG
BRK
BRKT
BRZ
BS
BSMT
BTWN
BUR
BVL
BW
BYND
DEG
DEMO
DEPT
DF
DH
DIA
DIAG
DIFF
DIM
DIR
DISP
DIST
DIV
DK
DL
DMT
DN
DO
DP
DP
DR
DS
DSGN
DTL
DUP
DW
DWG
DWL(S)
DWR
Sheet Index
05 / 14 / 2012
1200 SOUTH
UNI
VER
SIT
Y
BROWNING ADMINISTRATION BUILDING
PAR
KW
AY
sheet:
GI001
100% Construction Documents
A
CODE ANALYSIS
A
APPLICABLE CODES
International Building Code
International Mechanical Code
International Plumbing Code
International Fire Code
International Energy
Conservation Code
MISCELLANEOUS GENERAL NOTES
1.
2.
THE PROJECT MANUAL, UNDER SEPARATE COVER, IS AN INTEGRAL PART OF THESE CONSTRUCTION DRAWINGS.
PLANS, SECTIONS, ELEVATIONS, DETAILS AND DIMENSIONS LABELED "TYPICAL" SHALL APPLY TO ALL SITUATION OCCURRING THAT ARE THE SAME OR SIMILAR TO THOSE
SPECIFICALLY KEYED ON THE DRAWINGS.
ALL WORK, MATERIALS, AND METHODS SHALL BE IN CONFORMANCE WITH THE CODES, ORDINANCES AND REGULATIONS OF ALL GOVERNMENTAL AGENCIES HAVING
JURISDICTION AT THE PROJECT LOCATION.
UNLESS OTHERWISE INDICATED IN THE CONSTRUCTION DOCUMENTS AS BEING NOT IN CONTRACT (N.I.C.) OR EXISTING, ALL ITEMS, MATERIALS AND INSTALLATION OF SAME
ARE PART OF THE CONTRACT AS DEFINED BY THE CONSTRUCTION DOCUMENTS. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL ACCESSORIES, COMPONENTS AND
ASSEMBLIES REQUIRED FOR THE WORK DEPICTED OR SPECIFIED.
CONTRACTORS ARE RESPONSIBLE FOR ALL WORK REGARDLESS OF THE LOCATION OF THE INFORMATION ON THE DOCUMENTS.
KEEP SITE CLEAN AND CLEAR OF DEBRIS AND IN ORDERLY CONDITION THAT DOES NOT DETRACT FROM THE SURROUNDING SITE AND REPAIR ANY DAMAGE CAUSED BY
WORK OF THE CONTRACT.
DIMENSIONS ARE TO THE FACE OF EXISTING WALL TO CENTER OF NEW WALL UNLESS NOTED OTHERWISE.
INSTALL SEALANT AT EXTERIOR SIDE OF ALL JOINTS, SEAMS, CONNECTIONS OR OPENINGS WHICH WOULD ALLOW WATER OR AIR INFILTRATION EXCEPT AS NOTED
OTHERWISE. SEALANT COLOR TO MATCH ADJACENT SURFACE. COLOR REQUIRES ARCHITECTS APPROVAL.
DOOR OPENINGS IN FRAME CONSTRUCTION WHICH ARE NOT DIMENSIONED ARE EITHER CENTERED IN THE WALL, FACE OF JAMB OR LOCATED 4" FROM THE FACE OF STUD
TO THE FINISHED JAMB.
ALL SPECIAL ACCESSIBLE FACILITIES SHALL BE IDENTIFIED WITH APPROVED SIGNAGE.
THE CONTRACTOR IS RESPONSIBLE FOR PRODUCING A WEATHER TIGHT BUILDING, DETAILS AND OMISSIONS TO DRAWINGS NOTWITHSTANDING. ALL DRAWING CONFLICTS
WHICH MAY NOT ALLOW A WEATHERTIGHT CONDITION SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT.
DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND PLANS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT. CONTRACTOR SHALL SUBMIT SPECIFIC
DISCREPANCIES FOR ARCHITECT REVIEW.
PROVIDE FULL METAL BACKING PLATE (16 GAUGE X 6" HIGH SECURED TO 3 STUDS MIN.) OR WOOD BLOCKING AS REQUIRED TO SECURELY ANCHOR ALL WALL MOUNTED
EQUIPMENT (CABINETS, TOILET ROOM ACCESSORIES, HARDWARE, ETC.). BLOCKING SHALL PROVIDE A RIGID CONNECTION CAPABLE OF SUPPORTING DESIGN LOADS.
PROVIDE A 16 GAUGE X 6" STL. STUD/TRACK SECURED TO 2 STUDS TO SECURELY SUPPORT ALL WALL STOPS (DOOR BUMPER).
COORDINATE WITH ALL TRADES, SIZES AND LOCATIONS OF ALL OPENINGS FOR MECHANICAL, PLUMBING AND ELECTRICAL EQUIPMENT, EQUIPMENT PADS OR BASES, AS
WELL AS ELECTRIC POWER, WATER, AND DRAIN INSTALLATIONS, BEFORE PROCEEDING WITH WORK. CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS FOR
PROPER PLACEMENT OF ALL TRADES' WORK. ANY CONCERNS, SPACE LIMITATIONS OR STRUCTURAL CONFLICTS, SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT. A REASONABLE RESPONSE TIME SHALL BE ALLOWED AS NOTED IN THE SPECIFICATIONS.
ALL FLOOR OR WALL OPENINGS REQUIRED FOR PIPES, DUCTS, CONDUITS,ETC. SHALL BE SEALED IN AN APPROVED MANNER.
FIRE SPRINKLER DESIGN TO BE DONE BY A CERTIFIED SUB-CONTRACTOR AND WILL REQUIRE APPROVALS BY THE CITY AND STATE FIRE MARSHAL. APPROVALS BY THE FIRE
MARSHAL ARE TO BE OBTAINED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO ARCHITECT. SUBMITTAL TO THE ARCHITECT ALSO INDICATES THAT THE CONTRACTOR HAS
REVIEWED AND COORDINATED FIRE-SPRINKLER PIPING LOCATIONS WITH ALL TRADES.
ROOMS ENCLOSED WITH RATED WALLS REQUIRE RATED DOORS. ANY DUCTS PASSING THROUGH WALLS REQUIRE FIRE DAMPERS AND OR FIRE/SMOKE DAMPERS. ANY
CONDUIT OR PIPING REQUIRES RATED SEALANT AT JOINTS.
GENERAL STRUCTURAL NOTES GOVERN TYPICAL CONDITIONS WHETHER OR NOT SPECIFICALLY DETAILED OR NOTED.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE AND LOCATE ELECTRICAL, DATA AND PHONE RECEPTACLES, SWITCHES, ETC. TO AVOID CASEWORK, DOORS,
ETC.
THE DRAWINGS AND SPECIFICATIONS INDICATE THE GENERAL SCOPE OF THE PROJECT IN TERMS OF THE ARCHITECTURAL AND STRUCTURAL DESIGN CONCEPT. THE
DIMENSIONS OF THE BUILDING, THE TYPE OF STRUCTURAL, MECHANICAL, ELECTICAL AND UTILITY SYSTEMS AND MAJOR ARCHITECTURAL ELEMENTS OF CONSTRUCTION AS
"SCOPE" DOCUMENTS.
THE DRAWINGS AND SPECIFICATIONS DO NOT NECESSARILY INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE FULL PERFORMANCE AND COMPLETION OF THE WORK.
CONTRACTS SHALL BE LET ON THE BASIS OF SUCH DOCUMENTS, WITH THE UNDERSTANDING THAT THE CONTRACTOR IS TO FURNISH ALL ITEMS REQUIRED FOR PROPER
COMPLETION OF THE WORK WITH OUT ADJUSTMENT TO CONTRACT PRICE. IT IS INTENDED THAT THE WORK TO BE OF SOUND AND QUALITY CONSTRUCTION AND THE
CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR THE INCLUSION OF ADEQUATE AMOUNTS TO COVER INSTALLATION OF ALL ITEMS INDICATED, DESCRIBED OR
REASONABLY IMPLIED.
DN
3.
4.
5.
6.
7.
8.
9.
2
GI002
DN
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
1
OVERALL CODE PLAN
1" = 30'-0"
LEGEND
DN
HATCH
OCCUPANCIES
IBC chapter 3
WALL TO DECK AE101, AE102
X
A.
Year
2009
2009
2009
2009
National Electrical Code
Uniform Code for
Building Conservation
ADA Accessibility
Guildelines
Year
2008
2006
ANSI
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
2009
B
Occupancy and Group: ________
A3
________
________
________
________
x
x
Change in Use: Yes ______ No _____
Mixed Occupancy: Yes ______
No ______
NO
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
B.
D
Seismic Design Category: ______
05 / 14 / 2012
method
studio inc.
N/A (interior remodel)
Design Wind Speed: __________________
925 south west temple
C.
salt lake city, utah 84101
Type of Construction (circle one):
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
A
D.
B
A
B
A
B
HT
A
B
Fire Resistance Rating Requirements for the Exterior Walls based on the fire
separation distance (in hours): N/A (existing bldg)
E.
Mixed Occupancies: ___________
Nonseparated Uses: _______________
Yes
No
F:
Sprinklers: Fully sprinkled. Area Increase = 200%
Yes
Required: ______
consultants:
x
NFPA 13
Provided: ______
Type of Sprinkler System: ____________
Area Increase : N/A (not increasing building area)
G:
2 total only 1 high @
N/A (not increasing bldg height,
remodeled
area
existing building 37'-6")
Number of Stories: _______________ Building Height: __________________________
H:
1,347 sq. ft. (area remodeled)
Actual Area per Floor (square feet): __________________________
I:
_______________________________
Actual area per occupancy type NET sf:
B Second Floor Remodel
94 sq. ft.
A3 Second Floor Remodel
1,253 sq. ft.
___________________________________________
J:
Area Modifications (IBC section 506): N/A (Not changing bldg occupancy type)
K.
Fire Resistance Rating Requirements for Building Elements (hours). None per
IBC table 601
X
X
A3
15 SF / OCC
X
202B
1
68
L.
X
AE501
X
B
100 SF / OCC
100
Design Occupant Load: ___________________
81
X
1' - 5"
Exit Width Required: ________
X
9' - 0"
Exit Width Provided: ______
X
X
EXISTING 1 HR FIRE
SEPARATION
M.
X
Minimum Number of Required Plumbing Facilities: (N/A: Not increasing bldg size)
project:
X
COMMON PATH OF EGRESS 100' MAX.
- PER IBC 1014.3.1 (exception #1)
FOOTNOTES:
X
1)
In case of conflict with the U.S. Department of Justice Federal Registers Parts
through - ADA Guidelines and specific reference to the International Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
2)
Additional Code Information shall be provided at the discretion of the Building
Official for Complex Buildings. Including, but not limited to:
FEC - FIRE EXTINGUISHING CABINET
EXIT
40 OCC
8" R
36" P
202
79
1185
15
X
INTENDED PATH OF EGRESS
OCCUPANT LOADS
X
ROOM NUMBER
ROOM SQUARE
FOOTAGE
XXX
1
0
0
OCCUPANT LOAD
X
X
LOAD FACTOR FROM
TABLE 1004.1.1 IBC 2009
X
X
FEC
EXIT
1 OCC
1" R
36" P
100
X
EXIT
39 OCC
8" R
36" P
CODE DATA PLAN - CLASSROOM AREA
1/8" = 1'-0"
High Rise Requirements.
Atriums.
Performance Based Criteria.
Means or Egress Analysis.
Fire Assembly Locator Sheet.
f)
g)
Exterior and Interior Accessibility Route.
Fire Stopping, Including Tested Design Number.
800 W University Parkway
Orem, UT 84058
X
DFCM PROJECT # 1 2 0 3 5 7 9 0
project#:
date:
REQUIREMENTS
FOR OCCUPANCY
2
a)
b)
c)
d)
e)
UVU Admin Building
Classroom Remodel
X
O
PE
N
94
X
TO
1
EE501
X
BE
LO
W
202A
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
1. A CODE INSPECTION REPORT RECOMMENDING THAT A
CERTIFICATE OF OCCUPANCY BE ISSUED.
2. FINAL REPORT FROM THE SPECIAL INSPECTION AGENCY.
3. CERTIFICATE OF FIRE CLEARANCE FROM THE STATE FIRE
MARSHALL.
4. FINAL APPROVAL FROM THE STATE ELEVATOR INSPECTOR, IF
APPLICABLE.
5. FINAL APPROVAL FROM THE STATE BOILER INSPECTOR, IF
APPLICABLE.
6. REPORT OF THE DISINFECTION OF THE POTABLE WATER
SYSTEM. IPC 610.
7. A CERTIFICATE OF COMPLIANCE FROM THE APPROVED
FABRICATOR, IF APPLICABLE. IBC 1704.2.2.
8. A STAMPED AND SIGNED FINAL REPORT FROM THE
STRUCTURAL ENGINEER WHEN STRUCTURAL OBSERVATION IS
REQUIRED BY IBC 1710.
9. FINAL REPORT FROM THE SPECIAL INSPECTOR AND THE
MECHANICAL ENGINEER WHEN SMOKE CONTROL IS REQUIRED.
THE REPORTS MUST COMPLY WITH IBC 909.18.8.3.
10. THE NFRC CERTIFICATE TO SHOW COMPLIANCE WITH THE
FENESTRATION REQUIREMENTS OF THE INTERNATIONAL
ENERGY.
revisions :
DEFERRED SUBMITTALS
SUBMITTAL CONTRACTOR TO PROVIDE DEFERRED SUBMITTALS FOR THE
DEADLINE FOLLOWING ITEMS:
5/21/2012
FIRE SPRINKLER SYSTEM PLANS
5/21/2012
FIRE ALARM PLANS
5/21/2012
SEE NONSTRUCTURAL COMPONENT CHECKLIST - GI003
ROOM SCHEDULE
ROOM NUMBER
ROOM NAME
200
202
202A
202B
12.0250
05 / 14 / 2012
Code
Analysis
sheet:
CORRIDOR
CLASSROOM
OFFICE
CONTROL
Note:
1. The deferred submittal must include all necessary details and specific information relating to the materials, type, size, etc. as
necessary to fabricate and install the deferred submittal item.
2. Work related to the deferred submittal is not to commence until the Building official has approved the submittal.
3. See notes on nonstructural component checklist for more instructions.
GI002
100% Construction Documents
DEMOLITION FLOOR
PLAN GENERAL NOTES
1
CONTRACTOR SHALL PROTECT EXISTING STRUCTURE /
ASSEMBLIES / EQUIPMENT AS REQUIRED FROM DEMOLITION
WORK. REPAIR, PATCH, REPLACE EXISTING CONSTRUCTED
ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED
FOR NEW CONSTRUCTION.
2
REFER TO ROOM FINISH SCHEDULE, INTERIOR PLANS, AND
FINISH DETAILS FOR ADDITIONAL INFORMATION FOR AREAS
THAT MAY REQUIRE MATERIAL DEMOLITION / REMOVAL NOT
NECESSARILY SHOWN ON DEMOLITION PLANS.
THE CONTRACTOR SHALL PATCH TO MATCH EXISTING
FINISHES, WALLS, FLOORS, CEILINGS, ETC, AS REQUIRED IN
THOSE AREAS NOT SPECIFICALLY CALLED OUT ON THE ROOM
FINISH SCEDULE, BUT THAT ARE EFFECTED BY
CONSTRUCTION.
3
4
GENERAL CONTRACTOR TO PATCH / REPAIR ALL AREAS
RESULTING FROM DEMOLITION AND PREPARE SUCH
SURFACES TO RECEIVE SCHEDULED FINISHES.
GENERAL CONTRACTOR SHALL REVIEW ALL DOORS, FRAMES,
AND HARDWARE TO BE DEMOLISHED WITH OWNER, DELIVER
SELECTED DOORS TO OWNER'S STORAGE AND DISPOSE OF
ANY REMAINING ITEMS PROPERLY.
REFER TO MECHANICAL, PLUMBING, ELECTRICAL &
STRUCTURAL DRAWINGS FOR ADDITIONAL DEMOLITION
COORDINATION.
5
6
05 / 14 / 2012
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
DN
consultants:
4
8
8
3
3
8
5
8
DEMOLITION KEY NOTES
4
4
6
1
7
EXISTING WALL TO REMAIN.
12
2
8
EXISTING CARPET TO BE REMOVED WHERE NEW
WALLS OCCUR. EXISTING CARPET TO REMAIN, PATCH
& REPAIR @ NEW WALLS. PROTECT FROM DAMAGE
DURING CONSTRUCTION.
8
7
8
3
SALVAGE TO OWNER
4
REMOVE FLOORING IN ITS ENTIRETY (INCLUDING
GLUES, MORTARS AND CAULKING) AND PREP SURFACE
(S) TO RECEIVE NEW FINISH(S).
5
REMOVE ELECTRICAL ITEM / EQUIPMENT (ELECTRICAL
BOXES, TELE / DATA CONNECTION COMMUNICATION
EQUIPMENT, TV'S ETC.) COORDINATE WITH OWNER,
RE: ELECTRICAL. REFER TO ELECTRICAL DRAWINGS
FOR RELOCATED ELCTRICAL PANELS.
CLASSROOM
202
6
8
8
7
8
9
REMOVE / RELOCATE MECHANICAL ITEM / EQUIPMENT
(EXHAUST FAN, AIR CURTAINS, MECH. EQUIPMENT,
LOUVERS, ETC.) COORDINATE WITH OWNER. RE:
MECHANICAL
REMOVE PLUMBING ITEM / FIXTURE (SINKS,
LAVATORIES, WATER COOLERS, ETC.) COORDINATE
WITH OWNER AND WITH ACM CONTRACTOR PRIOR TO
DEMOLITION. RE: PLUMBING.
REMOVE CASEWORK (COUNTERTOPS, SHELVING,
UPPER CABINETS, LOWER CABINETS, BUILT-INS,
PLUMBING FIXTURES, ELECTRICAL DEVICES, GAS
FIXTURES, ETC.) AND ANY ASSOCIATED FURR-DOWNS.
RE: ELECTRICAL, PLUMBING.
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
UVU Admin Building
Classroom Remodel
CUT HOLE AND RE-FRAME FOR NEW DOOR, RELOCATE
EXISTING MECHANICAL, ELECTRICAL, AND PLUMBING
AS NECESSARY.
10
STOREFRONT TO BE REMOVED
11
DEMOLISH GYP BOARD ONE SIDE FOR NEW
CONSTRUCTION.
12
DEMOLISH EXISTING CASEWORK - PREP FOR NEW
WALL.
13
REMOVE / DISPOSE OF EXISTING BLINDS.
800 W University Parkway
Orem, UT 84058
4
9
3
DEMOLITION LEGEND
DFCM PROJECT # 1 2 0 3 5 7 9 0
ITEMS TO BE REMOVED
project#:
date:
EXISTING WALL TO REMAIN
revisions :
12.0250
05 / 14 / 2012
DEMOLISH DOOR FRAME SALVAGE DOOR & HARDWARE
TO OWNER
KEY PLAN
Demolition
Floor Plan
Classroom
sheet:
1
DEMOLITION FLOOR PLAN - CLASSROOM AREA
1/4" = 1'-0"
AD101
100% Construction Documents
DEMOLITION CEILING
PLAN GENERAL NOTES
1
CONTRACTOR SHALL PROTECT EXISTING
STRUCTURE / ASSEMBLIES / EQUIPMENT AS
REQUIRED FROM DEMOLITION WORK. REPAIR,
PATCH, REPLACE EXISTING CONSTRUCTED
ITEMS AND EQUIPMENT THAT ARE TO REMAIN
AS REQUIRED FOR NEW CONSTRUCTION.
2
REFER TO ROOM FINISH SCHEDULE, INTERIOR
PLANS, AND FINISH DETAILS FOR ADDITIONAL
INFORMATION FOR AREAS THAT MAY REQUIRE
MATERIAL DEMOLITION / REMOVAL NOT
NECESSARILY SHOWN ON DEMOLITION PLANS.
THE CONTRACTOR SHALL PATCH TO MATCH
EXISTING FINISHES, WALLS, FLOORS,
CEILINGS, ETC, AS REQUIRED IN THOSE AREAS
NOT SPECIFICALLY CALLED OUT ON THE ROOM
FINISH SCEDULE, BUT THAT ARE EFFECTED BY
CONSTRUCTION.
3
4
GENERAL CONTRACTOR TO PATCH / REPAIR
ALL AREAS RESULTING FROM DEMOLITION
AND PREPARE SUCH SURFACES TO RECEIVE
SCHEDULED FINISHES.
GENERAL CONTRACTOR SHALL REVIEW ALL
DOORS, FRAMES, AND HARDWARE TO BE
DEMOLISHED WITH OWNER, DELIVER
SELECTED DOORS TO OWNER'S STORAGE AND
DISPOSE OF ANY REMAINING ITEMS
PROPERLY.
5
6
05 / 14 / 2012
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
REFER TO MECHANICAL, PLUMBING,
ELECTRICAL & STRUCTURAL DRAWINGS FOR
ADDITIONAL DEMOLITION COORDINATION.
1
1
1
DEMOLITION KEY NOTES
3
1
CLASSROOM
202
2
DEMOLISH EXISTING CEILING, SOFFIT,
AND ATTACHED ELECTRICAL ITEMS.
EXISTING LIGHTS TO BE SALVAGED TO
OWNER. PROTECT ADJACENT
REMAINING WALLS.
EXISTING CEILING, SOFFITS, AND LIGHTS
TO REMAIN, COORDINATE EXTENT WITH
NEW CONSTRUCTION.
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
UVU Admin Building
Classroom Remodel
3
3
EXISTING LIGHTS TO BE REMOVED.
REFER TO ELECTRICAL.
9
2
AE501
800 W University Parkway
Orem, UT 84058
DFCM PROJECT # 1 2 0 3 5 7 9 0
9
project#:
date:
AE501
12.0250
05 / 14 / 2012
revisions :
1
KEY PLAN
Demolition
Ceiling Plan
Classroom
sheet:
1
DEMOLITION CEILING PLAN - CLASSROOM AREA
1/4" = 1'-0"
AD102
100% Construction Documents
5/8" TYPE-X GYP. BD
TO DECK
GENERAL FINISH FLOOR
PLAN NOTES
5/8" TYPE-X GYP. BD
TO DECK
1
3 5/8" MTL STUD
FRAMING @ 18" O.C.
TO DECK
GENERAL CONTRACTOR SHALL FIELD VERIFY
ALL EXISTING CONDITIONS, MATERIALS,
FINISHES, AND DIMENSIONS BEFORE &
AFTER DEMOLITION.
CONTRACTOR TO ENSURE THAT ALL
CORRIDORS OUTSIDE OF CONSTRUCTION
AREA ARE KEPT CLEAN & CLEAR OF DEBRIS
& OBSTRUCTIONS AT ALL TIMES.
GENERAL CONTRACTOR SHALL PROVIDE A 6
MIL POLYETHYLENE DUST BARRIER FROM
FLOOR TO CONCRETE DECK ABOVE. DUST
BARRIER SHALL BE SEALED AIR TIGHT IN ALL
AREAS OF CONSTRUCTION.
UPON COMPLETION OF CONSTRUCITON IT IS
THE GENERAL CONTRACTOR'S
RESPONSIBILITY TO THOROUGHLY CLEAN
ALL AREAS IN WHICH CONSTRUCTION TOOK
PLACE AND AREAS AFFECTED BY THE
CONSTRUCTION. THE GENERAL
CONTRACTOR SHALL CLEAN ALL CARPET,
REMOVE ALL DUST, CLEAN DOORS AND
FRAMES, LIGHT FIXTURES, CEILING
SYSTEMS, MECHANICAL GRILLS, ELECTRICAL
PANELS, WINDOW SYSTEMS AND GLAZING,
ETC...
SOUND BATT
INSULATION
TO DECK
2
SOUND BATT
INSULATION
TO DECK
3
3-5/8" MTL STUD
FRAMING @ 18" O.C.
TO DECK
4
A1
A2
2 WALL TYPES
3" = 1'-0"
5
6
7
DN
8
9
2
10
AE301
4' - 0 1/4"
1
11
AE301
4' - 0"
"
-0
ELEVATION
3'-0"
4
ALLIGN
5'
A1
4' - 4"
5
12
6
10
202B
3'
"
-4
ELEVATION
2'-6"
202B
ELEVATION
1'-0"
6
5
4' - 4"
5"
AE601
ELEVATION
1'-6"
4
14
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
CONTRACTOR TO PATCH/REPAIR EXISTING
WALLS, CEILINGS, AND FINISHED SURFACES
ADJACENT TO WORK PERFORMED.
PROTECT FROM DAMAGE ALL ITEMS TO
REMAIN.
PROVIDE DEFLECTION TRACKS @ ALL STUD
WALLS, SEE DETAIL 2/AE501
ALL MATERIALS TO BE INSTALLED PER
SPECIFIC MANUFACTURER'S INSTALLATION
RECOMMENDATIONS
FLOORING MATERIAL TRANSITIONS TO
OCCUR AT CENTER LINE OF DOOR
THRESHOLDS, U.N.O.
PREPARE FLOORS/WALLS TO RECIEVE
FINISH MATERIAL. REFER TO
MANUFACTURERS RECOMMENDATIONS FOR
SURFACE PREPERATION. NOTIFY
ARCHITECT IF CONDITIONS ARE INADEQUATE
ALL METAL STUD WALLS TO DECK ABOVE,
SEE WALL TYPES. COPE GYP BOARD &
STUDS @ ALL MECHANICAL, PLUMBING AND
ELECTRICAL CONDITIONS
CONTRACTOR TO PROVIDE SOLID BLOCKING
AT ALL CASE WORK, FIXED FURNISHINGS
AND EQUIPMENT. COORDINATE WITH
ELEVATIONS, SECTIONS AND FURNITURE
AND FIXTURE SHEETS AND SPECIFICATION
WRAP GYP. BD. AT EXPOSED FURRING ENDS
U.N.O.
DIMENSIONS ARE FROM FACE OF EXISTING
WALL TO CENTER OF NEW WALL.
CONTRACTOR TO FIELD VERIFY EXISTING
CONDITIONS & NOTIFY ARCHITECT OF ANY
DISCREPANCIES
4' - 0"
ELEVATION
0'-0"
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
AL
LI
GN
11
"
CLASSROOM
UVU Admin Building
Classroom Remodel
202
12
AE601
6
method
A2
ELEVATION
0'-6"
11
AE601
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
202C
11
"
11
AE601
13
A2
11
"
1' - 0"
A2
6
6
AE501
A1
AE601
11"
2
CONTROL
4' - 0 1/4"
ELEVATION
2'-0"
4' - 4"
AE601
7
ALLIGN
A1
ALLIGN
2
05 / 14 / 2012
1185 SF
AE601
6
6
1
FLOOR PLAN KEY NOTES
1
4' - 4"
4' - 4"
1
OWNER PROVIDED TEACHER STATION PROVIDE POWER & DATA ON COLUMN
ADJACENT- SEE ELECTRICAL
2
PLASTIC LAMINATE COUNTER TOP WITH
CONCEALED SUPPORTS, SEE DETAIL
13/AE501
4' - 4"
11"
5
AE501
3
4
EQ
1 1/2"
4' - 0"
AE601
3
4
BE
LO
W
TO
EQ
ALLIGN
4
1 1/2 DIA. PIPE HANDRAIL (PNT-2) ATTACHED EVERY 5' O.C. W/ SOLID
BLOCKING - PATCH AND REPAIR EXISTING
GYP. BOARD AS NECESSESARY
5
O
PE
N
9' - 2"
202A
A1
SEMI-RECESSED FIRE EXTINGUISHER
CABINET SEE ELEVATION & DETAIL 9/AE501
AE601
A1
OFFICE
3
202A
30" x 30" FLOOR ACCESS PANEL - PROVIDE
ADEQUATE METAL STUD FRAMING AT
OPENING - COORDINATE WITH MANUF.
RECOMMENDATIONS
6
FIXED FURNITURE PROVIDED BY OTHERS
7
SEAM IN WOOD FLOOR BASE TO MATCH
ADJACENT EXISTING BASE
KEY PLAN
800 W University Parkway
Orem, UT 84058
DFCM PROJECT # 1 2 0 3 5 7 9 0
project#:
date:
12.0250
05 / 14 / 2012
revisions :
Floor Plan
Classroom
sheet:
AE101
1
FLOOR PLAN - CLASSROOM AREA
1/4" = 1'-0"
100% Construction Documents
05 / 14 / 2012
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
DN
2
AE301
STEEL STUD
JOIST @ 24" O.C.
MAX, TYP.
1
CONTROL
AE302
202B
1
AE301
3
1
AE302
AE302
1
AE302
1
3
AE302
AE302
4
AE302
3
AE302
1
AE302
3
3
SIM.
AE302
3
UVU Admin Building
Classroom Remodel
2
AE302
AE302
1
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
SIM.
AE302
2
AE302
AE302
2
SIM.
AE302
CLASSROOM
202
3
3
AE302
AE302
SIM.
800 W University Parkway
Orem, UT 84058
3
AE302
O
PE
N
TO
BE
LO
W
DFCM PROJECT # 1 2 0 3 5 7 9 0
project#:
date:
12.0250
05 / 14 / 2012
revisions :
Floor Framing
Plan
Classroom
sheet:
1
FLOOR FRAMING PLAN
1/4" = 1'-0"
AE102
100% Construction Documents
GENERAL FINISH FLOOR
PLAN NOTES
FINISHES
1
CODE
CARPET
CPT-1
MATERIAL
Carpet Tile
BASE
RB-1
Rubber Base
PAINT
PNT-1
Paint
PNT-2
Paint
PNT-3
Paint
PLASTIC LAMINATE
PL-1
Plastic Laminate
ACOUSTICAL CEILING TILE
ACT-1
Acoustical Ceiling Tile
MANUFACTURER
Interface Flor
PRODUCT NAME / NUMBER
Tonal
COLOR / FINISH
SIZE
Barley
COMMENTS
50cm x 50cm
2
Johnsonite Wall Base
100% Vulcanized Rubber
40 - Black
Columbia
Oyster White
Black / 2132-10
Satin
Satin
Paint to match existing adjacent wall finish
Wilsonart Laminate
North Sea / D90-60
USG
Radar
4" High
Straight Profile. Provide in 120 ft Coils.
3
2' X 2'
Straight
4
202
202A
202B
Name
CLASSROOM
OFFICE
CONTROL
CPT-1
CPT-1
CPT-1
RB-1
RB-1
RB-1
PNT-1
PNT-1
PNT-1
PNT-1
PNT-1
PNT-1
PNT-1
PNT-1
PNT-1
5
Comments
DN
PNT-1
PNT-1
PNT-1
6
7
8
9
10
11
CONTROL
12
202B
13
14
PN
T3
Number
PNT-3
ROOMS
ROOM FINISH SCHEDULE - CLASSROOM
FLOORS
WALL
Floor Base North East South West
Finish Finish Wall
Wall
Wall
Wall
GENERAL CONTRACTOR SHALL FIELD VERIFY
ALL EXISTING CONDITIONS, MATERIALS,
FINISHES, AND DIMENSIONS BEFORE &
AFTER DEMOLITION.
CONTRACTOR TO ENSURE THAT ALL
CORRIDORS OUTSIDE OF CONSTRUCTION
AREA ARE KEPT CLEAN & CLEAR OF DEBRIS
& OBSTRUCTIONS AT ALL TIMES.
GENERAL CONTRACTOR SHALL PROVIDE A 6
MIL POLYETHYLENE DUST BARRIER FROM
FLOOR TO CONCRETE DECK ABOVE. DUST
BARRIER SHALL BE SEALED AIR TIGHT IN ALL
AREAS OF CONSTRUCTION.
UPON COMPLETION OF CONSTRUCITON IT IS
THE GENERAL CONTRACTOR'S
RESPONSIBILITY TO THOROUGHLY CLEAN
ALL AREAS IN WHICH CONSTRUCTION TOOK
PLACE AND AREAS AFFECTED BY THE
CONSTRUCTION. THE GENERAL
CONTRACTOR SHALL CLEAN ALL CARPET,
REMOVE ALL DUST, CLEAN DOORS AND
FRAMES, LIGHT FIXTURES, CEILING
SYSTEMS, MECHANICAL GRILLS, ELECTRICAL
PANELS, WINDOW SYSTEMS AND GLAZING,
ETC...
05 / 14 / 2012
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
CONTRACTOR TO PATCH/REPAIR EXISTING
WALLS, CEILINGS, AND FINISHED SURFACES
ADJACENT TO WORK PERFORMED.
PROTECT FROM DAMAGE ALL ITEMS TO
REMAIN.
PROVIDE DEFLECTION TRACKS @ ALL STUD
WALLS, SEE DETAIL 2/AE501
ALL MATERIALS TO BE INSTALLED PER
SPECIFIC MANUFACTURER'S INSTALLATION
RECOMMENDATIONS
FLOORING MATERIAL TRANSITIONS TO
OCCUR AT CENTER LINE OF DOOR
THRESHOLDS, U.N.O.
PREPARE FLOORS/WALLS TO RECIEVE
FINISH MATERIAL. REFER TO
MANUFACTURERS RECOMMENDATIONS FOR
SURFACE PREPERATION. NOTIFY
ARCHITECT IF CONDITIONS ARE INADEQUATE
ALL METAL STUD WALLS TO DECK ABOVE,
SEE WALL TYPES. COPE GYP BOARD &
STUDS @ ALL MECHANICAL, PLUMBING AND
ELECTRICAL CONDITIONS
CONTRACTOR TO PROVIDE SOLID BLOCKING
AT ALL CASE WORK, FIXED FURNISHINGS
AND EQUIPMENT. COORDINATE WITH
ELEVATIONS, SECTIONS AND FURNITURE
AND FIXTURE SHEETS AND SPECIFICATION
WRAP GYP. BD. AT EXPOSED FURRING ENDS
U.N.O.
DIMENSIONS ARE FROM FACE OF EXISTING
WALL TO CENTER OF NEW WALL.
CONTRACTOR TO FIELD VERIFY EXISTING
CONDITIONS & NOTIFY ARCHITECT OF ANY
DISCREPANCIES
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
CLASSROOM
202
FLOOR FINISH LEGEND
CODE
MATERIAL
CPT-1
CARPET
project:
UVU Admin Building
Classroom Remodel
WALL / BASE FINISH LEGEND:
B-1
MATERIAL
TYPE
MATERIAL
TRANSITION
800 W University Parkway
Orem, UT 84058
OFFICE
202A
DFCM PROJECT # 1 2 0 3 5 7 9 0
94 SF
project#:
date:
12.0250
05 / 14 / 2012
revisions :
KEY PLAN
Finish Plan
Classroom
sheet:
1
FINISH PLAN - CLASSROOM AREA
AE103
1/4" = 1'-0"
100% Construction Documents
REFLECTED CEILING
PLAN GENERAL NOTES
1
THIS PLAN SHALL BE USED TO COORDINATE
THE CEILING LAYOUT WITH MECHANICAL &
ELECTRICAL. REFER TO MECHANICAL
DRAWINGS FOR SIZES & TYPES OF CEILING
DIFFUSERS & GRILLES. REFER TO ELECTRICAL
DRAWINGS FOR SIZES & TYPES OF LIGHTING
FIXTURES.
2
COORDINATE THE LOCATIONS OF STRUCTURAL
SUPPORTS FOR EXHAUST, DUCTS, ETC. WITH
MECHANICAL DUCTWORK, LIGHTING FIXTURES,
& ALL CONDUITS.
ALL CEILING HEIGHTS INDICATED ARE RELATIVE
TO THE FLOOR LINE AT WHICH THEY OCCUR.
ALL LAY-IN CEILING GRIDS TO BE CENTERED
AND EQUALLY SPACED IN THE ROOM UNLESS
SHOWN OTHERWISE.
SPRINKLER PIPING TO BE HELD TIGHT TO THE
BOTTOM OF BEAMS OR JOISTS WHERE
POSSIBLE. HEADS TO BE DIRECTED UP IN
EXPOSED CONDITIONS & DIRECTED DOWN AT
CEILING LOCATIONS.
3
4
5
6
FIRE SPRINKLER HEADS TO BE LOCATED IN THE
CENTER OF ACOUSTIC LAY-IN PANELS.
7 ALL CEILING HEIGHTS ARE FROM FINISHED
FLOOR OF ROOM (U.N.O.)
8 VERIFY ALL LIGHTS, SMOKE DETECTORS, & EXIT
SIGNS, WITH ELECTRICAL DRAWINGS.
9 VERIFY ALL MECHANICAL DUCTS, GRILLES,
DIFFUSERS, & VENTS WITH MECHANICAL
DRAWINGS.
10 VERIFY ALL SPRINKLER LINES, SPRINKLER
HEADS, & PIPING WITH PLUMBING DRAWINGS.
11 FOR TYPICAL CEILING DETAILS, SEE SHEET
AE501.
12 SEE AE104 & AE105 FOR FINISH SCHEDULE.
B 11'8'-- 4"
4"
A.F.F.
05 / 14 / 2012
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
A 13' - 6"
4
AE501
SIM
RCP KEY NOTES
4
AE501
4
A
8' - 0"
1
RECESSED FLAT SCREEN WALL MOUNTED
TV's
2
EXISTING GYP. BOARD SOFFIT
TYP
AE501
4
AE501
B 13' - 6"
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
1
project:
UVU Admin Building
Classroom Remodel
9
AE501
RCP PLAN LEGEND
2
TYPE A
5/8" PTD. GYPSUM BOARD SOFFIT
ON SUSPENDED MTL. STUDS
1
4
AE501
TYP
TYPE B
2' x 2' (ACT-1) ACOUSTICAL TILE IN
SUSPENDED GRID
9
800 W University Parkway
Orem, UT 84058
AE501
MECHANICAL SUPPLY DIFUSER
B 10' - 0"
DFCM PROJECT # 1 2 0 3 5 7 9 0
MECHANICAL RETURN AIR
project#:
date:
12.0250
05 / 14 / 2012
revisions :
KEY PLAN
Reflected
Ceiling Plan
Classroom
sheet:
AE110
1
REFLECTED CEILING PLAN - CLASSROOM AREA
1/4" = 1'-0"
100% Construction Documents
05 / 14 / 2012
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
10
AE501
9
AE501
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
CONTROL
13' - 6"
CLASSROOM
202B
202
5
AE302
FINISHED FLOOR
LEVEL 2
1
SECTION 1
1/2" = 1'-0"
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
UVU Admin Building
Classroom Remodel
800 W University Parkway
Orem, UT 84058
DFCM PROJECT # 1 2 0 3 5 7 9 0
project#:
date:
12.0250
05 / 14 / 2012
revisions :
CLASSROOM
202
6
AE302
Sections
FINISHED FLOOR
LEVEL 2
sheet:
2
SECTION 2
1/2" = 1'-0"
AE301
100% Construction Documents
EXISTING STEEL STUD WALL
VARIES
11"
3' - 5"
11"
3' - 5"
11"
600T125-33 STEEL TRACK TOP & BOTTOM
TWO (2) #8 SCREWS TO TOP TRACK
6"
6"
TWO (2) LAYERS FIRE TREATED 23/32" TONGUE &
GROVE OSB W/ #8 SCREWS @ 6" O.C. EDGE &
12" O.C. FIELD
05 / 14 / 2012
6"
600S162-33 STEEL STUD JOIST @ 24" O.C.
MAX.
6"
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
6"
7/16" FIRE TREATED OSB W/ #8 SCREWS @ 6"
O.C. EDGE AND 12" O.C. FIELD
6"
600S162-33 STEEL STUD @ 24" O.C.
1/4" DIAM. SIMPSON TITEN HD MINI SCREW
ANCHOR TO EXISTING CONCRETE (1"
EMBED) @ 48" O.C. & AT EACH END OF WALL
SIM.
1
AE302
3
AE302
4
AE302
EXISTING CONCRETE SLAB
5
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
3
AE302
3
AE302
method
consultants:
TIERED SEATING SECTION 1
1" = 1'-0"
AT JOISTS
4' - 4"
4' - 4"
600S162-33 STEEL STUD BLOCKING
1' - 0"
4' - 4"
1' - 0"
1' - 0"
#8 SCREW @ 6" O.C. TO TOP TRACK
SIM.
1
AE302
6
2
AE302
2
AE302
2
AE302
IN BETWEEN JOISTS
TIERED SEATING SECTION 2
1
1" = 1'-0"
TYPICAL STEEL STUD WALL @ EXISTING STEEL STUD WALL
1 1/2" = 1'-0"
11" MIN.
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
TWO (2) LAYERS FIRE TREATED 23/32" TONGUE &
GROVE OSB W/ #8 SCREWS @ 6" O.C. EDGE &
12" O.C. FIELD
7/16" FIRE TREATED OSB W/ #8 SCREWS @ 6"
O.C. EDGE AND 12" O.C. FIELD
project:
TWO (2) LAYERS FIRE TREATED 23/32" TONGUE &
GROVE OSB W/ #8 SCREWS @ 6" O.C. EDGE &
12" O.C. FIELD
TWO (2) LAYERS FIRE TREATED 23/32" TONGUE &
GROVE OSB W/ #8 SCREWS @ 6" O.C. EDGE &
12" O.C. FIELD
362T125-33 STEEL TRACK TOP & BOTTOM
7/16" FIRE TREATED OSB W/ #8 SCREWS @ 6"
O.C. EDGE AND 12" O.C. FIELD
600S162-33 STEEL STUD JOIST @ 24" O.C.
MAX.
7/16" FIRE TREATED OSB W/ #8 SCREWS @ 6"
O.C. EDGE AND 12" O.C. FIELD
600T125-33 STEEL TRACK TOP & BOTTOM
TWO (2) #8 SCREWS TO TOP TRACK
600T125-33 STEEL TRACK TOP & BOTTOM
TWO (2) LAYERS FIRE TREATED 23/32" TONGUE &
GROVE OSB W/ #8 SCREWS @ 6" O.C. EDGE &
12" O.C. FIELD
TWO (2) #8 SCREWS TO TOP TRACK
TWO (2) #8 SCREWS TO TOP TRACK
600T125-33 STEEL TRACK TOP & BOTTOM
TWO (2) LAYERS FIRE TREATED 23/32" TONGUE &
GROVE OSB W/ #8 SCREWS @ 6" O.C. EDGE &
12" O.C. FIELD
600S162-33 STEEL STUD JOIST @ 24" O.C.
MAX.
600S162-33 STEEL STUD JOIST @ 24" O.C.
MAX. TYP.
#8 SCREW @ 6" O.C. FROM OSB TO STEEL TOP
TRACK
600S162-33 STEEL STUD JOIST @ 24" O.C.
MAX. TYP.
TWO (2) #8 SCREWS TO TOP TRACK
600S162-33 STEEL STUD @ 24" O.C. MAX.
362S162-33 STEEL STUD @ 24" O.C.
1/4" DIAM. SIMPSON TITEN HD MINI SCREW
ANCHOR TO EXISTING CONCRETE (1"
EMBED) @ 48" O.C. & AT EACH END OF WALL
600S162-33 STEEL STUD @ 24" O.C. TYP.
600T125-33 STEEL TRACK TOP & BOTTOM
1/4" DIAM. SIMPSON TITEN HD MINI SCREW
ANCHOR TO EXISTING CONCRETE (1"
EMBED) @ 48" O.C. & AT EACH END OF WALL
600S162-33 STEEL STUD @ 24" O.C. MAX.
800 W University Parkway
Orem, UT 84058
600S162-33 STEEL STUD @ 24" O.C. TYP.
1/4" DIAM. SIMPSON TITEN HD MINI SCREW
ANCHOR TO EXISTING CONCRETE (1"
EMBED) @ 48" O.C. & AT EACH END OF WALL
EXISTING CONCRETE SLAB
EXISTING CONCRETE SLAB
AT STEP
3
UVU Admin Building
Classroom Remodel
DFCM PROJECT # 1 2 0 3 5 7 9 0
project#:
date:
12.0250
05 / 14 / 2012
revisions :
TYPICAL STEEL STUD WALL @ STEP
1 1/2" = 1'-0"
AT JOISTS
TWO (2) LAYERS FIRE TREATED 23/32" TONGUE &
GROVE OSB W/ #8 SCREWS @ 6" O.C. EDGE &
12" O.C. FIELD
600S162-33 STEEL STUD BLOCKING, TYP.
600S162-33 STEEL STUD BLOCKING W/ #8
SCREW @ 6" O.C. TO TRACK, TYP.
#8 SCREW @ 6" O.C. TO TOP TRACK
Section
Details
600S162-33 STEEL STUD JOIST @ 24" O.C.
MAX.
TWO (2) #8 SCREWS TO TOP TRACK
600T125-33 STEEL TRACK TOP & BOTTOM
sheet:
600S162-33 STEEL STUD @ 24" O.C. MAX.
1/4" DIAM. SIMPSON TITEN HD MINI SCREW
ANCHOR TO EXISTING CONCRETE (1" EMBED)
@ 48"
IN BETWEEN JOISTS
EXISTING CONCRETE SLAB
4
STEEL STUD JOIST @ STEEL STUD WALL
1 1/2" = 1'-0"
2
TYPICAL STEEL STUD WALL @ DIAPHRAGM STEP
1 1/2" = 1'-0"
AE302
100% Construction Documents
ELEV. A.F.F.
13' - 6"
AIN
RU
NN
ER
3 5/8" STL. STUD CONTINUOUS
- RETURN @ MECHANICAL
LOUVER & END OF
COORRIDOR
3 5/8" STL. STUD
3"
MA
X.,
E
TE
SS
O
CR
TY
P.
2"
LAYER(S) OF
GYPSUM BOARD
AND WHERE
OCCURS RESILIENT
CHANNEL OVER
METAL FRAMING
- SEE FRAMING
PLAN
2" CONTINUOUS 18 GA.
METAL STRAP
3' - 10"
DEMOLISH EXISTING STUD
FRAMING & GYP. BOARD TO
ACCOMMODATE NEW RECESSED
TV ALCOVE - COORDINATE WITH
ELEVATIONS 1/AE601
5/8" TYPE-X GYP. BOARD
3
TYP. FIXTURE SUPPORT
2
1/64" = 1'-0"
DEFLECTION TRACK
AE501
NOTE 1 - ALL HANGER WIRES TO BE IN LINE WITH
ATTACHED COMPONENT OR SHALL BE COUNTERSLOPED NOT
GREATER THAN 1/6
8 1/2"
B.O. CEILING
PER RCP PLAN
HANGER 12 GA. @ 4'-0"
O.C. MAX.
7/8" HAT CHANNEL
LAY IN CEILING
EXISTING CONCRETE
COLUMN
EXISTING STUD
FRAMEING
8" MAX
8" MAX
GRID PERPENDICULAR TO
CEILING NOT ATTACHED TO
CLOSURE ANGLE (TWO
ADJACENT WALLS)
5/8" GYP. BD. TYP. 4
SIDES
CEILING GRID MAIN
RUNNER OR CROSS TEE
7/8" HAT CHANNEL
LAY IN CEILING ACT-1,
SEE FINISH SCEDULE
GYP. BOARD
B.O. SOFFIT
PER RCP PLAN
NEW CONSTRUCTION
SOFFIT & RECESSED TV
SCHED. CEILING TILE
B.O. CEILING
PER RCP PLAN
FASTENER ON ALL
MEMBERS @ TWO
ADJACENT WALLS ONLY
PER MFG REQ.
METAL STUD
FRAMING
6
3/4" = 1'-0"
GYP SOFFIT W/ ACT LAY-IN
5
1 1/2" = 1'-0"
CONCRETE COLUMN FURRING
CLIP ANGLE CEILING DETAIL
4
1" = 1'-0"
7/8" SEISMIC CLIP BY
MANUFACTURER
1 1/2" = 1'-0"
3 5/8" METAL FRAMING W/
INSULATION - SEE WALL
TYPES
LAY-IN CEILING
SEMI-RECESSED FIRE
EXTINGUISHER
CABINET - REFER TO
SHOP DRAWINGS
PER SHOP DWGS
2'-0" ±
5' - 0"
A.F.F.
PROVIDE RECESS FOR
F.E. CABINET AS REQ'D REFER TO WALL TYPES
FOR WALL
CONSTRUCTION
3" MAX
PROVIDE 3/4" CONTINUOUS
BACKING AS REQUIRED TO
BRACE TV MOUNTS
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
SECTION
SEE ELEVATION
OWNER PROVIDED TV
project:
1'-2" ±
1' - 0"
PER SHOP
DWGS
ELEV. A.F.F.
7' - 10"
PLAN
7
FIRE EXTINGUISHER - SEMI-RECESSED
3/4" = 1'-0"
NOTE 1- ALL SPLAY WIRES TO BE IN LINE WITH ATTACHED
COMPONENT
1' - 0"
RECESS TO ACCOMODATE
OWNER PROVIDED CAMERA.
SEE ELEVATIONS &
ELECTRICAL
UVU Admin Building
Classroom Remodel
LAY-IN CEILING
4 7/8"
5/8" GYP. BOARD
1' - 0"
NOTE 2- ALL SPLAY WIRES TO BE TAUT AND TIED BOTH ENDS WITH MINIMUM OF
THREE TURNS IN 1" OF RUN.
NOTE 3- COMPLY WITH IBC 2009
NOTE 4- SPLAY WIRES SHALL ATTACH TO STRUCTURAL GIRDER OR JOIST ONLY,
DO NOT ATTACH TO ROOF DECK.
NOTE 5- METAL COMPRESSION POST (STRUT) FASTENED TO THE MAIN RUNNER
SHALL BE EXTENDED TO AND FASTENED TO THE STRUCTURAL MEMBERS
SUPPORTING THE ROOF OR FLOOR ABOVE. COMPRESSION POSTS & SPLAY
WIRES TO BE INSTALLED EVERY 12' O.C. BOTH DIRECTIONS STARTING 6' FROM
WALL. SEE COMPRESSION POST ALLOWABLE LENGTHS TABLE FOR SIZES. SEE
DETAILS 3 & 4 FOR TYPICAL BRACING.
3/4" PLYWOOD BACKING
CONTINUOUS 41" ABOVE
TOP OF COUNTER &
CENTERED 96" WIDE
NOTE 6- ALL LIGHT FIXTURES SHALL BE POSITIVELY ATTACHED TO THE
SUSPENDED CEILING SYSTEM. WHEN INTERMEDIATE SYSTEMS ARE USED, ATTACH
NO. 12 GAGE HANGERS TO THE GRID MEMBERS WITHIN 3" OF EACH CORNER OF
EACH FIXTURE. LIGHT FIXTURES WEIGHING LESS THAN 56 LBS. SHALL HAVE TWO
NO. 12 GAGE HANGERS CONNECTED FROM THE FIXTURE HOUSING TO THE
STRUCTURE ABOVE. COMPLY WITH IBC 2009
VERTICAL HANGER
WIRE ADJACENT
TO POST
3/4" PLYWOOD BACKING
CONTINUOUS 41" ABOVE
TOP OF COUNTER &
CENTERED 96" WIDE
STRUT ASSEMBLY TOP CLIP
MECHANICALLY FASTENED TO
DECK PER MANUFACTURERS
RECOMMENDATIONS
STRUCTURE
6' - 0"
SPRING CLIP INSERTS IN
HOLE IN POST
SPLAY WIRE - SECURE
TO STRUCTURE
COMPRESSION POST - INSTALL
WITHIN 2" OF CROSS TEE
INTERSECTION
1' - 6"
2" DIA GROMMET TO
MATCH (PL-1) @ 36" O.C.
2' - 6"
45° OR
LESS
BULB CLIP ATTACHING
COMPRESSION POST AND MAIN
RUNNER MECHANICALLY
FASTENED PER MANUFACTURERS
RECOMMENDATIONS
PROVIDE BLOCKING
AS REQ'D
FULLY CONCEALED
WORKSURFACE SUPPORTS
SPACED AT 3'-0" OC - PAINT
EXPOSED SURFACE TO
MATCH ADJACENT WALL
FINISH
MAIN TEE
COMPRESSION POST ALLOWABLE
LENGTHS TABLE
MATERIAL
CROSS TEE
13/16" x 13/32" STRUT 19 GA
24"
1 5/8" x 13/16" STRUT 12 GA
48"
13/16" x 13/16" STRUT 19 GA
54"
1 5/8" x 1" STRUT 12 GA
60"
3 5/8" x 1 1/4" STRUT 16 GA
82"
1 1/4" x 1 1/4" STRUT 14 GA
84"
1 5/8" x 1 3/8" STRUT 12 GA
96"
1 5/8" x 1 5/8" STRUT 12 GA
108"
1 5/8" x 2 7/16" STRUT 12 GA
120"
2. WALL MOLDING SHOULD NOT BE USED AS STRUTS.
3. A STRUCTURAL ENGINEER SHOULD BE CONSULTED FOR LENGTHS
GREATER THAT 14'.
1 1/2" = 1'-0"
8
SEISMIC BRACING DETAIL 1
1 1/2" = 1'-0"
12.0250
05 / 14 / 2012
revisions :
TYP. ALLOWABLE
LENGTH
1. THE INFORMATION PROVIDED IS FOR QUICK REFERENCE ONLY.
OTHER RESTRICTIONS AND EXEMPTIONS MAY APPLY.
RECESSED AV EQUIPMENT
project#:
date:
Details
45° OR LESS
NOTES
BASE AS SPECIFIED
DFCM PROJECT # 1 2 0 3 5 7 9 0
NOTE 7- ALL LIGHT FIXTURES SHALL BE POSITIVELY ATTACHED 20 LBS. SHALL BE
POSITIVELY ATTACHED TO THE CEILING SUSPENSION MAIN RUNNERS. TERMINALS
OR SERVICES WEIGHING 20 LBS., BUT NOT MORE THAT 56 LBS., SHALL IN ADDITION
HAVE TWO NO. 12 GAGE HANGERS CONNECTED TO THE CEILING SYSTEM
HANGERS OR TO THE STRUCTURE ABOVE. TERMINALS OR SERVICES WEIGHING
MORE THAN 56 LBS. SHALL BE SUPPORTED DIRECTLY FROM THE STRUCTURE
ABOVE BY APPROVED HANGERS. COMPLY WITH IBC 2009
45° OR
LESS
A FASTENER OR SPLAY WIRES
MAYBE INSERTED INTO THE TAB
OF THE POST AND THROUGH A
CONVENIENCE HOLE IN THE MAIN
TEE BULB
COUNTERTOP: 1 1/2" CORE
FACED W/ (PL-1) - SCRIBE
TIGHTLY TO WALL, SEAL
SEAM WITH CLEAR
SILICONE
800 W University Parkway
Orem, UT 84058
NOTE 8- ALL GRID SYSTEM IN SEISMIC ZONE D OR GREATER ARE REQUIRED TO BE
HEAVY DUTY. REFER REQUIREMENTS TO ASCE 7REQUIREMENTS.
45° OR LESS
10
consultants:
NOTE 2 - ALL HANGER WIRES TO BE TAUT AND TIED BOTH
ENDS W/ MIN. OF 4 TURNS IN 1" OF RUN.
2X KICKER @4'-0"
O.C. (TYP.)
ELEV. A.F.F.
10' - 6"
925 south west temple
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
3 5/8" METAL STUD
FRAMING
9
studio inc.
12" = 1'-0"
3 5/8" STL. STUD
1' - 0"
DEMOLITION DETAIL
method
salt lake city, utah 84101
SEISMIC BRACING DETAIL 2
1
3" = 1'-0"
COMPRESSION POST
NOTE:
AREAS SMALLER THAN 144 SQ. FT. AND WITH WALLS ON
FOUR SIDES EXTENDING TO THE STRUCTURE
NEED NOT BE BRACED. BOUNDARY WALLS
MUST BE BRACED TOP AND BOTTOM INDEPENDENT
OF CEILING TO QUALIFY.
8
EXISTING STUD FRAMEING
& GYP. BOARD
5/8" TYPE-X
GYP. BOARD
ELEV. A.F.F.
8' - 0
.)
AX
M
(
"
2'-0
TYP.
PROVIDE 3/4" CONTINUOUS
BACKING AS REQUIRED TO
BRACE TV MOUNTS
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
SPLAY WIRE
x;1
3 1/2" SOUND BATT INSULATION
RECESSED FLAT
SCREEN TV &
MOUNT - SEE
ELECTRICAL
DISTANCE TO FIRST
SCREW IN GYPSUM
BOARD
'-0
x;6
05 / 14 / 2012
.
AX
"M
90°
HE
"T
AV
YP
YD
ICA
UT
L
YM
AIN
RU
NN
ER
20 GA. MTL. SLIP
DEFLECTION
TRACK. SEE
STRUCT. FOR MAX.
DEFLECTION.
4"
ACT CEILING
4'-0
AX.)
0" (M
x;12'-
HE
AV
YD
UT
YM
WALL
CONCRETE FLOOR
SLAB OVER METAL
DECK - SEE
STRUCTURAL
2"
12 GA. METAL
HANGER WIRES
EXISTING STUD
FRAMEING
CEILING SUSPENSION
SYSTEM
3"
SLACK
WIRES
EXISTING CONC. BEAM
FIRST LINE OF BRACING
6'-0" OR LESS FROM
WALL BOUNDARY
#12 WIRE HANGER AT
EACH CORNER OF
FIXTURE (TYP.)
INDEPENDENT OF
CEILING SUPPORT
SYSTEM
sheet:
AE501
100% Construction Documents
6' - 1"
6' - 0"
1
3' - 10"
3' - 10"
6
CONTRACTOR TO FIELD VERIFY ALL WALLS PRIOR TO
INSTALLATION & FABRICATION OF GLAZING.
3' - 0"
10
1' - 6"
9
10
7
8 1/2"
1' - 0"
8
GENERAL DOOR & WINDOW
SCHEDULE NOTES
7' - 8"
8 1/2"
AE501
OPEN
AE501
9
TYP
1' - 6"
2
AE501
6
10
2
9
6' - 0"
3' - 0"
OPEN
9
05 / 14 / 2012
2
3' - 0"
3' - 0"
1' - 0"
3' - 0"
7
2
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
2
1
method
3
3
ELEVATION KEY NOTES
3
7
3
202 EAST CLASSROOM
1
1/4" = 1'-0"
1/4" = 1'-0"
7
925 south west temple
2
PAINTED GYP. BOARD WALL. SEE FINISH
PLANS.
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
3
BASE AS SPECIFIED. SEE FINISH PLANS.
4
EXISTING CONCRETE COLUMN
5
ALUMINUM MINI BLINDS - FIELD VERIFY
DIMENSIONS
6
FLAT SCREEN TV - OWNER PROVIDED
7
HANDRAIL PAINTED (PNT-2), PARALLEL TO NOSING
OF TIERS.
8
SEMI-RECESSED FIRE EXTINGUISHER
CABINET
9
POWER, DATA, AUDIO VISUAL - SEE
ELECTRICAL.
10
CAMERA - SEE ELECTRICAL - PROVIDE 1" x
12" x 12" PLASTIC LAMINATE SHELF WITH
CONCEALED WALL SUPPORTS
11
12" x 12" x 12" RECESS TO ACCOMODATE
CAMERA
AE501
4 7/8"
2
3' - 1"
4' - 10"
2
4' - 10"
6
12
HANDRAILS SHOULD EXTEND TO EXISTING
CONCRETE FLOOR - PROVIDE BASE PLATE W/
(4) EPOXY ANCHORED DOWELS. BRACE AT
SUB-FLOOR W/ SOLID BLOCKING.
consultants:
6
2
1' - 0"
1 1/2"
1' - 0"
1 1/2"
11
7
2
1' - 0"
6' - 0"
7' - 5"
1' - 0"
3' - 0"
2
3' - 0"
12
3
12
3
11
salt lake city, utah 84101
10
3' - 0"
CENTER ISLE HANDRAIL 1
6
3/4" = 1'-0"
202 CLASSROOM (HANDRAIL)
5
1/4" = 1'-0"
202 WEST CLASSROOM
1/4" = 1'-0"
7
SEALANT BOTH
SIDES TYP.
1 1/2"
METAL STUDS
DOOR AS SCHEDULED
SEALANT BOTH
SIDES TYP.
METAL STUDS
HOLLOW METAL FRAME
HOLLOW METAL FRAME
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
1 1/2"
12
MARK
WINDOW SCHEDULE1
DESCRIPTION
COMMENTS
DOOR AS SCHEDULED
SEALANT BOTH
SIDES TYP.
W1
W2
13
AE601
12
CENTER ISLE HANDRAIL 2
8
3/4" = 1'-0"
HM DOOR HEAD W/ MTL STUD & GYP
7
3" = 1'-0"
STOREFRONT SYSTEM
STOREFRONT SYSTEM
13
HANDRAIL BASE DETIAL
10
3" = 1'-0"
DOOR TYPE D1 ELEVATION - WOOD
9
1/4" = 1'-0"
DOOR
3' - 0"
2' - 8"
1' - 6"
7' - 0"
7' - 0"
7' - 0"
0' - 1 3/4"
0' - 1 3/4"
0' - 1 3/4"
D1
D1
D1
01
03
04
STN
STN
STN
WD
WD
WD
COMMENTS
1/4" CLEAR TEMPERED
1/4" CLEAR GLASS
DFCM PROJECT # 1 2 0 3 5 7 9 0
OPEN
project#:
date:
12.0250
05 / 14 / 2012
DOOR FRAME TYPE F1 - HM W/ 2IN HEAD
1/4" = 1'-0"
Door Sched. /
Int.
Elevations
FRAME
HARDWARE
SET
NUMBER WIDTH HEIGHT THICKNESS TYPE
FINISH MATERIAL
HOLLOW METAL
GL1
GL2
TYPE
800 W University Parkway
Orem, UT 84058
revisions :
DOOR SCHEDULE
202A
202B
202C
MARK
2"
3/8" x 4" x 4" BASE PLATE
RECESSED INTO EXISTING
CONCRETE
WOOD FINISH TO
MATCH EXISTING
OAK VENEER
SEE SCHED.
EXISTING
CONCRETE FLOOR
GLAZING SCHEDULE
2"
C.L. OF HARDWARE
1 1/2" HANDRAIL
UVU Admin Building
Classroom Remodel
3" = 1'-0"
SEE SCHED.
PROVIDE (4) 3/8" x 3"
TAPERED EXPANSION
ANCHOR FLUSH W/ TOP
OF BASE PLATE
SEE 4/AE601
SEE 3/AE601
project:
HM DOOR JAMB W/ MTL STUD & GYP
SEE SCHED.
3'-4"
1/4" = 1'-0"
202B EAST CONTROL
2
SEE SCHED.
202 CLASSROOM (HANDRAIL)
3' - 0"
1/4" = 1'-0"
3
3' - 0"
202 CLASSROOM (HANDRAIL)
3' - 0"
4
PLASTIC LAMINATE COUNTERTOP WITH WALL
MOUNTED STEEL SUPPORTS.
1
AE501
studio inc.
FIRE
RATING
45 min.
-
TYPE
F1
F1
F1
MATERIAL FINISH
HM
HM
HM
PNT-2
PNT-2
PNT-2
COMMENTS
sheet:
AE601
100% Construction Documents
05/08/2012
GENERAL NOTES:
MECHANICAL LEGEND
SYMBOL
ABR.
DESCRIPTION
SYMBOL
ABR.
MA
1
D!1
CFM
R!1
SYMBOL
ABR.
DESCRIPTION
AIR SIDE
GENERAL TERMINOLOGY
A2
DESCRIPTION
WET SIDE
DETAIL NUMBER DESIGNATION
CORRESPONDING WITH GRID LOCATION
EXISTING AIR DUCT TO BE REMOVED
MECHANICAL EQUIPMENT DESIGNATION
NEW AIR DUCT
UNION
NEW SPIRAL DUCT
BUTTERFLY VALVE
NEW MEDIUM PRESSURE DUCT
GATE VALVE
EXISTING AIR DUCT TO REMAIN
EQUIPMENT ITEM DESIGNATION
REGISTER, GRILL OR DIFFUSER
DESIGNATION WITH BALANCING CFM
LISTED
BELOW
REGULATOR
R
BV
LINED DUCT
REVISION DESIGNATOR AND NUMBER
VANED ELBOW
1
KEY NOTE DESIGNATOR AND NUMBER
RADIUS ELBOW
POC POINT OF CONNECTION
BALL VALVE
PRESSURE GAUGE AND GAUGE COCK !
WATER
PRESSURE GAUGE AND GAUGE COCK !
STEAM
FLEXIBLE AIR DUCT CONNECTION
VD
VOLUME DAMPER
THERMOMETER AND THERMOWELL
GC
GENERAL CONTRACTOR
MC
MECHANICAL CONTRACTOR
ATC
CONTROL CONTRACTOR
SUPPLY AIR DIFFUSER
RETURN AIR, FRESH AIR, AND TRANSFER
AIR
CEILING MOUNTED EXHAUST FAN OR
EXHAUST GRILLE
DIRECTION OF FLOW
ELBOW UP
ELECTRICAL CONTRACTOR
RETURN OR OUTSIDE AIR DUCT UP
ELBOW DOWN
FPC
FIRE PROTECTION CONTROL
SUPPLY DUCT UP
TEE UP
NIC
NOT IN CONTRACT
EXHAUST AIR INTAKE UP
TEE DOWN
NTS
NOT TO SCALE
RETURN OR OUTSIDE AIR DUCT DOWN
EXISTING PIPING TO BE REMOVED
COMMON
SUPPLY DUCT DOWN
EXISTING PIPING TO REMAIN
NC
NORMALLY CLOSED
EXHAUST DUCT DOWN
NEW PIPING
NO
NORMALLY OPEN
ROUND DUCT UP
PIPE CAP OR PLUG
ROUND DUCT DOWN
FLEXIBLE CONNECTION
EC
C
AP
ACCESS PANEL
CW
CULINARY COLD WATER
EXISTING EQUIPMENT TO BE REMOVED
HW
CULINARY HOT WATER
EXISTING EQUIPMENT TO REMAIN
T
RTU!1
T!STAT
A ! EACH DRAWING SHEET AND THE SPECIFICATIONS HAVE BEEN
PREPARED TO SUPPLEMENT EACH OTHER AND THEY SHALL BE
INTERPRETED AS AN INTEGRAL UNIT WITH ITEMS SHOWN AND NOTED
ON ONE AND NOT THE OTHER BEING FURNISHED AND INSTALLED AS
THOUGH SHOWN AND CALLED OUT IN ALL PLACES. ITEMS IN
SPECIFICATIONS OR DRAWINGS LISTED WHICH ARE DIFFERING IN
EFFICIENCY OR QUALITY SHALL BE HELD TO THE GREATEST OF:
EFFICIENCY, QUALITY OR GOVERNING CODE.
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 ! 4 4 2 2
consultants:
CBV CIRCUIT BALANCING VALVE
FLEXIBLE AIR DUCT
1
POR POINT OF REMOVAL
PUMP
BURIED OR UNDER FLOOR DUCT
GRILLE, OR LOUVER DESIGNATION WHERE
BALANCING NOT REQUIRE
G!1 MECHANICAL INFORMATION IS NOT LIMITED TO THE MECHANICAL
DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR INFORMATION
OF THE EXISTING BUILDING AND SITE CONDITIONS, EXISTING PIPING,
EXISTING ELECTRICAL, AND EXISTING SUPPORTS.
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
RECIRCULATED CULINARY HOT WATER
NEW EQUIPMENT
HWS
HEATING WATER SUPPLY
WALL MOUNTED THERMOSTAT
MECHANICAL EQUIPMENT CONTROLLED
HWR
HEATING WATER RETURN
CHWS
CHILLED WATER SUPPLY
CHWR
CHILLED WATER RETURN
B ! THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR THE
INSTALLATION OF THE SYSTEMS ACCORDING TO THE TRUE INTENT
AND MEANING OF THE CONTRACT DOCUMENTS.
C ! THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT WITH PROPER
SERVICE ACCESS AND CLEARANCES ACCORDING TO
MANUFACTURERS RECOMMENDATIONS. THE CONTRACTOR SHALL
REVIEW SUPPLIERS BID PACKAGES FOR COMPLETENESS AND
COMPLIANCE TO THE SPECIFICATIONS, SCHEDULES, AND DESIGN
INTENT (ALL EQUIPMENT AND METHODS). THE CONTRACTOR SHALL
REMOVE AND REINSTALL CORRECTLY AT HIS OWN EXPENSE ANY
EQUIPMENT NOT IN COMPLIANCE.
D ! THE CONTRACTOR SHALL CONSULT MANUFACTURERS
INSTALLATION INSTRUCTIONS FOR SIZES, METHODS, ACCESSORIES,
AND CLEARANCES IN SPACE AVAILABLE PRIOR TO BIDDING PROJECT.
E ! ANYTHING NOT CLEAR OR IN CONFLICT WILL BE EXPLAINED BY
MAKING APPLICATION TO THE ENGINEER IN WRITING.
G!2 ANY AND ALL ALTERATIONS TO THE SYSTEM SHOWN SHALL BE
SUBMITTED TO THE ENGINEER PRIOR TO CHANGES FOR APPROVAL.
CONTRACTOR SHALL NOT START ANY CHANGES UNTIL NOTIFIED IN
WRITING. IF CHANGES ARE MADE PRIOR TO APPROVAL CONTRACTOR
SHALL TAKE ALL RESPONSIBILITY FOR THE CHANGES MADE AND ALL
COSTS RELATING TO FAILURE OR REPLACEMENT OF ALTERATIONS.
G!3 CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND LOCATIONS.
G!4 THE WORKING DRAWINGS ARE DIAGRAMMATIC. THEY DO NOT SHOW
EVERY OFFSET, BEND, OR ELBOW NECESSARY FOR THE COMPLETE
INSTALLATION IN THE SPACE PROVIDED. ALL LOCATIONS FOR
MECHANICAL EQUIPMENT SHALL BE FIELD VERIFIED AND
COORDINATED WITH ALL DRAWINGS. THE CONTRACTOR SHALL
PROVIDE OR COORDINATE WITH THE GENERAL CONTRACTOR
PROVISIONS FOR BLOCKOUTS OR CORE DRILLS THROUGH
STRUCTURE.
G!5 THE INSTRUCTION TO "PROVIDE" ALSO INCLUDES INSTALLATION.
G!6 MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL SMOKE AND
FIRE DAMPERS AS REQUIRED BY LOCAL CODES AND AUTHORITIES.
G!7 SHEET METAL DUCT SIZES SHOWN ON DRAWINGS ARE FREE AREA
DIMENSIONS.
SA
SUPPLY AIR
RA
RETURN AIR
EA
EXHAUST AIR
G!8 PROVIDE AND INSTALL BALANCING DAMPERS IN ALL SUPPLY AND
EXHAUST AIR BRANCH DUCTS. BALANCE TO CFM SHOWN ON PLAN.
OA
OUTSIDE AIR
G!9 SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT
LOCATION OF DIFFUSERS AND GRILLES.
MA
MIXED AIR
G!10 PROVIDE TURNING VANES IN ALL ELBOWS OF RECTANGULAR DUCT.
FA
FRESH AIR
RF
RELIEF AIR
G!11 THE CONTRACTOR SHALL ASSUME ALL RESPONSIBILITY IN HANDLING
AND DISPOSING OF REFRIGERANTS, OILS, ETC. ALL SUCH MATERIALS
SHALL BE HANDLED, DISPOSED, AND USED IN ACCORDANCE WITH ALL
LOCAL, STATE, AND FEDERAL LAWS.
G!12 THE MECHANICAL CONTRACTOR SHALL VERIFY MOTOR VOLTAGES
WITH THE ELECTRICAL DRAWING BEFORE ORDERING MOTORIZED
EQUIPMENT AND CONTROLS.
G!13 C.F.M. LISTED IS ACTUAL AIR.
G!14 SUPPLIERS SHALL REVIEW ALL DRAWINGS AND THE SPECIFICATIONS
PRIOR TO SUBMITTING PRICES TO THE CONTRACTOR. ALL QUESTIONS
AND DISCREPANCIES SHALL BE BROUGHT TO THE ENGINEERS
ATTENTION PRIOR TO BIDDING.
G!15 CONTRACTOR SHALL THOROUGHLY REVIEW AND SIGN SUBMITTALS
FOR COMPLETENESS AND COMPLIANCE TO THE SPECIFICATIONS
PRIOR TO ENGINEERS REVIEW. SUPPLIERS SHALL HIGHLIGHT OR
MARK ALL INFORMATION REQUIRED TO SHOW COMPLIANCE TO THE
SPECIFICATIONS. ALL REQUESTED EXCEPTIONS TO THE
SPECIFICATIONS, OR SCHEDULES SHALL BE CLEARLY NOTED AND
EXPLAINED. SUBMITTAL REVIEW AND ACCEPTANCE IS FOR DESIGN
CONCEPT ONLY, AND DOES NOT AT ANY TIME RELIEVE THE
CONTRACTOR OF RESPONSIBILITY TO MEET SPECIFICATIONS,
CAPACITIES, OR DESIGN INTENT.
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
UVU Admin Building
Classroom Remodel
800 W. University Parkway
Orem, UT 84058
DFCM PROJECT #11064280
project#:
date:
12.0250
05 / 14 / 2012
revisions :
G!16 ALL MECHANICAL SHALL BE INSTALLED AND CONFORM TO THE 2009
EDITION OF THE IMC AND IPC WITH UTAH ANNOTATIONS AND LOCAL
AUTHORITY REQUIREMENTS.
G!17 THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE DRAINING DOWN
AND RE!FILLING OF ALL SYSTEMS NECESSARY TO COMPLETE THE
WORK OUTLINED BY THIS PROJECT. THIS INCLUDES PROVIDING THE
REQUIRED CHEMICAL TREATMENT WHEN RE!FILLING THE SYSTEM.
G!18 ALL PIPING, MATERIALS, ETC. SHALL BE NEW AND DOMESTIC MADE
UNLESS SPECIFICALLY AUTHORIZED IN WRITING PRIOR TO BID.
MECHANICAL
GENERAL NOTES
AND LEGEND
sheet:
MG001
100% Construction Documents
SHEET NOTES
1
2
3
4
1
4
5
6
7
8
REMOVE EXISTING DIFFUSER/GRILLE AND
ASSOCIATED DUCTWORK.
REMOVE EXISTING FAN COIL AND ASSOCIATED
SUPPLY AND RETURN DUCTWORK.
REMOVE EXISTING CHWS, CHWR, HWS, & HWR
PIPING AND ALL ACCESORIES, VALVES, FITTINGS,
ETC.
REMOVE EXISTING EXHAUST FAN AND ASSOCIATED
GRILLE AND DUCTWORK. PATCH AND REPAIR ROOF.
ROOF WORK TO MAINTAIN ANY EXISITNG
WARRANTIES.
EXISTING FRESH AIR DUCT TO REMAIN.
EXISTING FRESH AIR LOUVER TO REMAIN.
REMOVE EXISTING THERMOSTAT.
COORDINATE WITH GC TO PATCH AND REPAIR FIRE
RATED WALL.
05/08/2012
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
T
925 south west temple
7
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 ! 4 4 2 2
8
1
consultants:
1
1
8
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
3
UVU Admin Building
Classroom Remodel
2
800 W. University Parkway
Orem, UT 84058
5
DFCM PROJECT #11064280
project#:
date:
6
12.0250
05 / 14 / 2012
revisions :
MECHANICAL
CLASSROOM DEMO
FLOOR PLAN
1
MECHANICAL CLASSROOM DEMO FLOOR PLAN
1/2" = 1' 0"
sheet:
MD101
100% Construction Documents
SHEET NOTES
05/08/2012
1
2
AC
1
6
3
4
5
6
R!3
CONTROL
202B
RECONNECT TO EXISTING PIPING MAINS. SEE
2!WAY PIPING DETAIL FOR NEW PIPING
CONFIGURATION.
EXISTING FRESH AIR INTAKE AND DUCTWORK TO
REMAIN.
PROVIDE NEW THERMOSTAT IN THIS APPROXIMATE
LOCATION. COORDINATE EXACT LOCATION AND
HEIGHT WITH FURNITURE LAYOUT AND OWNER.
PROVIDE NEW FIRE SMOKE DAMPER IN RATED
WALL.
CONNECT NEW RETURN DUCTWORK INTO EXISTING
FRESH AIR DUCT.
SPLIT SYSTEM TO BE MOUNTED ON WALL IN
CONTROL ROOM. OUTDOOR UNIT TO BE MOUNTED
ON ROOF ABOVE (SEE ROOF SUPPORT DETAIL).
FLASH AND SEAL AROUND PIPING THROUGH ROOF.
ROUTE CONDENSATE PIPING TO NEAREST WASTE
PIPING. SEE CONDENSATE RECIEVER DETAIL.
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 ! 4 4 2 2
consultants:
10
"ø
SA
D!3
360
10
"ø
SA
1
"S
2
x1
4"
A
D!3
360
GENERAL NOTES
_
1. PROVIDE RETURN AIR BOOT ON ALL RETURN GRILLES.
SEE DETAIL.
2. FIRE SPRINKLER CONTRACTOR TO RELOCATE ANY
EXPOSED PIPING. ALL PIPING TO BE CONCEALED.
10
D!3
360
"ø
SA
1
4
"S
2
x1
8"
A
10
CLASSROOM
1
S
4"
1
x
8"
A
202
"ø
3. FLUSH AND CLEAN PIPING PRIOR TO RECONNECTING TO
EXISTING PER SPECIFICATIONS.
SA
D!3
360
FS
22"x14" SA
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
FC
1
8"ø SA
10
1
"ø
project:
UVU Admin Building
Classroom Remodel
SA
4
D!3
360
R!3
FS
5
22"x14" RA
800 W. University Parkway
Orem, UT 84058
2
DFCM PROJECT #11064280
project#:
date:
R!2
12.0250
05 / 14 / 2012
revisions :
OFFICE
202A
D!2
100
3
T
FC!7
1
MECHANICAL CLASSROOM FLOOR PLAN
1/2" = 1' 0"
MECHANICAL
CLASSROOM FLOOR
PLAN
sheet:
ME101
100% Construction Documents
PROVIDE HANGER STRAP TO
STABILIZE AND BALANCE
BOOT
SHEET METAL
W/ 1" LINER
ATTACH HANGER STRAPS
TO STRUCTURE
MAIN AIR
DUCT
SOUND SHALL NOT HAVE
A
DIRECT PATH TO PLENUM
Y
PL
P
SU
NOTE:
DUCT BOARD NOT
ACCEPTABLE ALTERNATE
ATTACH TO STRUCTURE
NOTE: MAXIMUM
SPACING OF 10'!0"
L
NOTE:
PROVIDE ADEQUATE
CLEARANCE TO ALLOW
ACCESS TO MOTOR PANEL
AND FILTER PANEL.
HANGERS MUST NOT
DEFORM DUCT SHAPE
NOTE:
L=1/4 W (4" MINIMUM.)
N
UR
T
RE
3/8" BOLT
45°
1" x 16 GA.
HANGER STRAP
SIZE PER
SMACNA
3/8" ROD.
(FOUR REQUIRED)
SHEET METAL SCREW
FLEX CONNECTION
FLAT FILTER SECTION
ACCESS REQUIRED
CHANNEL
(TYPICAL)
1" x 16 GA.
HANGER STRAP
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
HEATING COIL
!
W
SA
DUCT
CEILING
RETURN GRILLE
1
SCALE: NONE
1" THICK
DUCT LINER
12
2"
.
"C
12
METAL FASTENERS
INSULATED PINS, FASTENERS
OR GRIP NAILS.
GRIP NAILS SHALL BE
INSTALLED BY AIR
HAMMER OR BY
AUTOMATIC FASTENER
EQUIPMENT.
"C
.C
.M
AX
.
BRANCH DUCT TAKE!OFF
& DAMPER DETAIL
2
1" X 18 GAGE STRAP
HANGERS AT 8'!0"
SPACING.
#10 X 3/4" SELF
TAPPING
CADMIUM
PLATED
SHEET METAL
SCREWS TO
ANCHOR STRAPS
TO DUCT. ALL
STRAPS TO BE
TIGHT AGAINST
DUCT AND
SUPPORT
MEMBERS. (TYP.)
NO POP RIVETS ALLOWED
NOT MORE THAN 2"
FROM EDGE OF LINER.
6
SHEET METAL ROUND
TO ROUND DUCT TAKE!
OFF SEE DETAIL ME5!
04.
45°
MANUAL VOLUME DAMPER
W/ LOCKING QUADRANT ON
ALL SUPPLY AIR DUCTS,
AND WHERE SHOWN FOR
RETURN AIR DUCTS.
FASTEN RIGID DUCT
TO FITTING w/ #10x3/4"
SHEET METAL
SCREWS.
DO NOT INTERFERE W/
VOLUME DAMPER
OPERATION.
DUCT STRAP HANGER DETAIL
SCALE: NONE
7
ROUND!TO!ROUND
DUCT CONSTRUCTION DETAIL
DUCT
consultants:
SIDE VIEW
TRANSVERSE REINFORCING (1)
AT JOINTS
MIN.
H.
PLAIN
IN.
S SLIP
1
1
1
1
1"X1"X1/8" @ 60 IN
H
H
DRIVE
SLIP
RECOM!
MENDED
GAGE
26
24
!
!
HEMMED
S SLIP
REIN!
ALTER'NT FORCED
BAR SLIP BAR SLIP
RECOM!
MENDED
GAGE
26
24
24
!
RECOM!
MENDED
GAGE
24
24
24
22
RECOM!
MENDED
GAGE
24
24
24
22
DUCT CONSTRUCTION DETAIL
SCALE: NONE
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
LOW PRESSURE ROUND DUCT
CONSTRUCTION SCHEDULE
2" VENT UP THRU
ROOF. OFFSET TO
MISS TOP PLATE
OF WALL CONSTRUCTION.
3 thru 8
9 thru 14
15 thru 26
27 thru 36
37 thru 50
2"X1 1/2"
BUSHING
1 1/2"
NIPPLE
project:
MAXIMUM 2" W.G.
MAXIMUM 2" W.G.
STATIC POSITIVE
STATIC NEGATIVE
SPIRAL
LONGITUDINAL SPIRAL
LONGITUDINAL
SEAM GAUGE SEAM GAUGE SEAM GAUGE SEAM GAUGE
28
28
28
24
DUCT
DIAMETER
IN INCHES
SANITARY
"Y" FITTING
1" x 16 G.A.
HANGER STRAP
3/4" DRAIN.
ROUTE TO DRAIN AS
SHOWN
ON MECHANICAL PLAN.
1. TRANSVERSE REINFORCING SIZE IS DETERMINED BY
DIMENSION OF SIDE TO WHICH ANGLE IS APPLIED.
THERMOPLASTIC
2"X4" DIA.
ADAPTOR
STAINLESS
STEEL
SCREW DRIVER
OPERATED BAND
(TYPICAL)
p h o n e : (8 0 1) 5 3 2 ! 4 4 2 2
NONE REQUIRED
NONE REQUIRED
1"X1"X1/8" @ 60 IN
26
24
24
22
SCALE: NONE
CR
MINIMUM
REINFORCING
ANGLE SIZE
AND MAXIMUM
LONGITUDINAL
SPACING
BETWEEN
TRANSVERSE
JOINTS &/OR
INTERMEDIATE
REINFORCING
SHEET
METAL
GAGE
(ALL
FOUR
SIDES)
8
1" x 16 G.A.
HANGER STRAP
salt lake city, utah 84101
SCALE: NONE
UP THRU 12
13 ! 18
19 ! 30
31 ! 36
AIR BRANCH
DUCT (TYPICAL).
925 south west temple
FAN COIL UNIT DETAIL
DIMENSION
OF
LONGEST
SIDE,
INCHES
D
1" x 1" x 1/8" ANGLE
(TYPICAL).
1" x18 GA.
GALVANIZED
STEEL STRAPS.
(FOUR
REQUIRED).
4
INSULATION NOT
SHOWN.
SEE SPECIFICATIONS.
NOTE:
PROVIDE SUPPORT ON ALL
BRANCH DUCT RUNOUTS.
MINIMUM OF TWO SUPPORTS
ON BRANCH DUCT SECTIONS
OVER 6'!0" IN LENGTH.
WRAP ALL BRANCH DUCTS
AND COVER CONNECTIONS
WITH DUCT WRAP. SEE
SPECIFICATIONS
CT
U
D
IR OW
A
IN FL
MA AIR
Y
W
PL
LO
P
F
U
S
AIR
N
UR
T
RE
SIZE CUT OUT
ACCORDING
TO
MANUFACTURERS
RECOMMENDATIONS
1"
SCALE: NONE
NOTE:
DUCT SHALL BE WRAPPED EXTERNALLY
AS PER THE SPECIFICATIONS.
16 GAGE GALVANIZED
STEEL AUXILLIARY
DRIP
PAN.
SCALE: NONE
#10x3/4" SHEET
METAL
SCREWS
DUCT LINER DETAIL
5
ROUND DUCT SUPPORT DETAIL
SEAL SEAM WITH
HARD!CAST
DUCT SEALER.
ALL ENDS OF LINER TO
BE COATED W/ ADHESIVE
ENDS OF LINER SHALL BE
BUTTED FIRMLY TOGETHER.
ALL JOINTS, SEAMS, AND
TEARS
SHALL BE COATED W/
ADHESIVE
DURING INSTALLATION.
3/4" DRAIN.
ROUTE TO DRAIN AS
SHOWN
ON MECHANICAL PLAN.
1" x 1" x 1/8" ANGLE
(TYPICAL).
END VIEW
SHEET METAL DUCT
!
RETURN AIR DUCT
SCALE: NONE
DUCTLINER
ONE INCH THICK 1!1/2 LB
DENSITY FIBERGLASS.
2"
3
!
20" DIA TO 36" DIA.
DUCTS > 36"∅
AIR BRANCH
DUCT (TYPICAL)
studio inc.
C
DUCTS < 20"∅
TOP AND BOTTOM
SECTIONS OF LINER
SHALL OVERLAP THE
SIDES
X.
A
C.M
2"
MANUAL VOLUME DAMPER
W/ LOCKING QUADRANT ON
ALL SUPPLY AIR DUCTS, AND
WHERE SHOWN FOR RETURN
AIR DUCTS.
method
!
DUCT
TYPICAL RETURN AIR BOOT DETAIL
TRANSIZE TO DUCT.
SIZE SHOWN ON
DRAWINGS.
COOLING COIL
TRANSIZE TO DUCT.
SIZE SHOWN ON
DRAWINGS.
VIBRATION
ISOLATORS
05/08/2012
28
26
24
22
26
24
22
20
26
24
22
20
UVU Admin Building
Classroom Remodel
24
22
20
18
DRAIN PAN
ROUND RIGID DUCT
SHEET METAL
SUPPORT STRAP
2" X 24 GAGE
3'!0"
UL 181 LABELED INSULATED FLEX DUCT
SEE SPECS. NO SAGS OR SHARP TURNS
ALLOWED. MAXIMUM RUN LIMITED TO 3'!0"
STRETCH DUCT RUN FOR SMOOTH
INTERIOR.
T!BAR FOR LAY!IN
CEILINGS
9
CRIMP JOINT BEAD
(TYPICAL)
2" WASTE DOWN.
RUN IN WALL TO
BELOW FLOOR SLAB.
CEILING
11
LOW PRESSURE ROUND
DUCT CONSTRUCTION DETAIL
SCALE: NONE
1 1/2" P!TRAP AND TAIL PIECE
USE THERMOPLASTIC PIPE
AND FITTINGS.
DIFFUSER
10
LAY!IN CEILING
800 W. University Parkway
Orem, UT 84058
CONDENSATE RECEIVER DETAIL
HIGH EFFICIENCY TYPE PRE!
MANUFACTURED
TAKE!OFF WITH DAMPER.
SCALE: NONE
TYPICAL DIFFUSER CONNECTION DETAIL
NOTE: TAKE!OFFS SHOULD NOT BE
INSTALLED CLOSER THAN TWO WIDTHS
TO ELBOWS OR INTERSECTIONS
SCALE: NONE
A
VACUUM BREAKER OPEN
TO ATMOSPHERE
3/4"
G.I. CAP
4x6 REDWOOD
RAILS
G.I. FLASHING
1/2" AIR VENT AND
COIL DRAINS
(TYP.)
SCREWED
CAPPED
CLEANOUT
(TYP.)
TO DRAIN.
SLOPE AT
1/4"/FT.
SPRING TYPE VIBRATION
ISOLATORS WITH SEISMIC
SNUBBERS
REDWOOD RAILS SHALL BE
A MINIMUM OF 4' IN LENGTH
AND BE ORIENTED TO DIST!
RIBUTE LOAD BETWEEN TWO
ROOF TRUSSES.
M
R
S OS
W
H HW
C
LOCKING QUADRANT HANDLE OR
REMOTE CEILING OPERATOR WHERE
DAMPER IS INACCESSIBLE.
RIGID ROUND
DUCT OR
DIFFUSER
COLLAR
3/4"
R
HW R
O R
W
CH
INSULATED
FLEX DUCT.
MAX LENGTH
6'!0".
24 GA.
1/2"
PROVIDE ISOLATION
VALVES AS SHOWN
(TYP.)
revisions :
B
FLOW
3" MIN.
REMOVE GRAVEL & SET
REDWOOD RAILS & CANT
STRIP IN ASPHALT ROOFING.
FLASH AND COUNTER FLASH,
PER ROOFING SYSTEM
MANUFACTURERS
RECOMMENDATIONS.
ANCHOR RAILS TO ROOF
STRUCTURE,
12.0250
05 / 14 / 2012
SEE DETAIL
DRAIN PAN
AIR
SIZE CONTROL VALVE FOR 3 PSI
PRESSURE DROP.
project#:
date:
45°
CANT STRIP
CONDENSING
UNIT
NOTE: AREA OF A x B SHALL
BE EQUAL TO 1.5 x AREA BRANCH DUCT
DFCM PROJECT #11064280
NYLON CLAMP OVER INSULATION
NYLON CLAMP OVER FLEX DUCT
SEE
DETAIL
MECHANICAL
DETAILS
INSULATION
FLEX DUCT
TO DRAIN
PROVIDE VENTED P!TRAP
CEILING DIFFUSER
12
ROOF SUPPORT DETAIL
SCALE: NONE
13
2!WAY COIL PIPING DETAIL
SCALE: NONE
14
COOLING COIL
CONDENSATE DRAIN DETAIL
sheet:
DETAIL
SCALE: NONE
SCALE: NONE
15
SQUARE!TO!ROUND TAKE!OFF DETAIL
ME501
SCALE: NONE
100% Construction Documents
Fan Coil Schedule
Symbol
Mark
Rooms Served
CFM
O.A.
CFM
FC
1
202
1995
400
ESP
HP (W)
MCA
0.25
0.75
15
Cooling
Heating
Entering Leaving
Entering Leaving
Water
Water
Water
Water
Temp
Temp
Temp
Heating Heating Temp
Cooling Cooling
GPM (Heating) (Heating)
MBH
GPM (Cooling) (Cooling) MBH
48.8
10.25
48
58
28.2
6.5
105
05/08/2012
97
Make
Notes
Trane BCHC054
1,2,3
1. Provide with integral condensate pump.
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
2. Siesmicly brace equipment per specifications.
method
3. Fluid to be 30% glycol. Coordinate with owner.
studio inc.
925 south west temple
salt lake city, utah 84101
Diffuser Schedule
Max
Ceiling
Flow
Type
Blow Max NC
Mark
Face
Size
Neck
Size
D!1
D!2
D!3
24x24
24x24
24x24
6" DIA
150 CFM
8" DIA 300 CFM
10" DIA500 CFM
LAY!IN
LAY!IN
LAY!IN
4!WAY
4!WAY
4!WAY
25
25
25
p h o n e : (8 0 1) 5 3 2 ! 4 4 2 2
Make &
Model
Schedule
Notes
Price SMD
Price SMD
Price SMD
1,2,3,4,5
1,2,3,4,5
1,2,3,4,5
consultants:
1. PROVIDE LAY!IN CEILING AND BORDER / MODULE AS REQUIRED. SEE ARCHITECTURAL CEILING PLANS.
2. MAXIMUM NC 25 AT CFM LISTED.
3. PROVIDE TRANSITION TO DIFFUSER NECK SIZE AS REQUIRED TO DUCT WORK SHOWN ON PLAN.
4. DIFFUSER SHALL BE PRICE MODEL SMD OR EQUAL BY APPROVED MANUFACTURER IN SPECIFICATIONS.
5. FINISH SHALL BE STANDARD WHITE.
Mark Count
R!2
R!3
1
2
Face
Size
Neck
Size
24x24
24x24
10/10
12/12
Grille Schedule
Ceiling
Type Max NC
CFM
Make &
Model
Schedule
Notes
LAY!IN
LAY!IN
Price 535
Price 535
1,2
1,2
180 CFM
250 CFM
25
25
1. PROVIDE LAY!IN CEILING AND BORDER / MODULE AS REQUIRED. SEE ARCHITECTURAL CEILING PLANS.
2. . FINISH SHALL BE STANDARD WHITE.
Symbol
Mark
Rooms
Served
AC
1
Control 202B
Cooling Compressor
MBH
Count
18
1
Split System Schedule
LRA
RLA
(Each) (Each) MOCP V/Ø/Hz
14
12
20
208/1/60
Weight
(Indoor/Outdoo)
Make & Model
50/100
Mitsubishi PKA!A18HA4 & PUZ!A18NHA4
1. PROVIDE INDOOR AND OUTDOOR UNIT. OUTDOOR UNIT TO BE INSTALLED ON ROOF ABOVE.
2. R!410A REFRIGERANT
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
3. PROVIDE WITH INTEGRAL CONDENSATE PUMP, WIRELESS REMOTE, WIND BAFFLE, PACKAGED THERMOSTAT AND BAS SENSOR.
project:
4. INTERIOR UNIT POWERED OFF OF EXTERIOR. PROVIDE WITH EXTERNAL DISCONNNECT.
UVU Admin Building
Classroom Remodel
5. COORDINATE REFRIGERANT CHARGE WITH PIPE RUN AND MANUFACTURER'S RECOMMENDATIONS.
800 W. University Parkway
Orem, UT 84058
DFCM PROJECT #11064280
project#:
date:
12.0250
05 / 14 / 2012
revisions :
MECHANICAL
SCHEDULES
sheet:
ME601
100% Construction Documents
05/08/2012
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
PLUMBING LEGEND
MEANING
SYMBOL OR
ABBREVIATION
HOT WATER LINE
MEANING
WALL CLEANOUT
COLD WATER LINE
CLEANOUT
HOT WATER
RECIRCULATING LINE
CLEANOUT TO GRADE
VENT LINE
FLOOR CLEANOUT
WASTE LINE
BALL VALVE
GAS LINE
VENT THRU ROOF
UNDER FLOOR
SANITARY SEWER
PLUMBING GENERAL NOTES:
SYMBOL OR
ABBREVIATION
WCO
G!1
ALL PLUMBING SHALL BE INSTALLED AND CONFORM TO THE 2009
EDITION OF THE INTERNATIONAL PLUMBING CODE (IPC) WITH
UTAH ANNOTATIONS AND LOCAL AUTHORITY REQUIREMENTS.
G!2
ALL PIPING MATERIALS SHALL MEET ALL REQUIREMENTS OF IPC
AND LOCAL AUTHORITY. PLASTIC PIPING SHALL BE ALLOWED
ONLY WHERE ALLOWED BY CODE. PLASTIC PIPING SHALL NOT BE
ROUTED THROUGH RETURN AIR PLENUMS OR OTHER AREAS
PROHIBITED BY THE IMC, IPC OR NFPA CODES OR BY LOCAL
AUTHORITY
CO
COTG
FCO
G!3
GAS PIPING INSTALLATION SHALL BE IN STRICT ACCORDANCE
WITH GAS COMPANY REGULATIONS, NFPA CODE REQUIREMENTS,
AND LOCAL AUTHORITY.
G!4
ALL MATERIALS SHALL BE NEW AND SHALL BE DOMESTIC MADE
UNLESS SPECIFICALLY APPROVED OTHERWISE IN WRITING BY
ARCHITECT OR OWNER.
G!5
PROVIDE VACUUM BREAKERS AND BACK FLOW PREVENTERS
WHERE REQUIRED BY CODE OR WHERE THERE MAY BE ANY
POSSIBLE CHANCE FOR CROSS CONTAMINATION. PREVENTERS
SHALL BE INSTALLED IN ACCORDANCE WITH UTAH CODE.
G!6
ALL PLUMBING INFORMATION IS NOT LIMITED TO THE PLUMBING
DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR
INFORMATION ON ALL OTHER CONSTRUCTION DOCUMENTS
INCLUDING SPECIFICATIONS, ARCHITECTURAL DRAWING,
STRUCTURAL DRAWINGS, MECHANICAL DRAWINGS, AND
ELECTRICAL DRAWINGS.
G!7
THE WORKING DRAWINGS ARE DIAGRAMMATIC. BECAUSE OF THE
SMALL SCALE OF THE DRAWING, THEY DO NOT SHOW EVERY
OFFSET, BEND OR ELBOW NECESSARY FOR THE COMPLETE
INSTALLATION IN THE SPACE PROVIDED. ALL PIPING SHALL BE
CHECKED AND COORDINATED WITH THE SPECIFICATIONS,
ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL
DRAWINGS.
G!8
COORDINATE ALL PIPING AND PLUMBING EQUIPMENT WITH ALL
OTHER TRADES AND/OR CONTRACTORS PRIOR TO INSTALLATION.
UNION
VTR
UF
SS
CONNECTION TO
EXISTING PIPING
REGULATOR
SOFT WATER
R
SW
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 ! 4 4 2 2
consultants:
ANY AND ALL ALTERATIONS TO THE SYSTEM SHOWN SHALL BE
THE RESPONSIBILITY OF THIS CONTRACTOR AND
ARCHITECT/ENGINEER SHALL BE NOTIFIED IN WRITING PRIOR TO
CHANGES.
G!10 GAS LINE FITTINGS SHALL BE STANDARD WELD FITTINGS WITH
TAPERED REDUCERS. DO NOT USE VALVES, UNIONS, OR AUTO
CONTROLS IN GAS LINES ROUTED IN INACCESSIBLE CONCEALED
SPACES.
G!9
G!11 ALL WATER SYSTEMS SHALL MEET THE REQUIREMENTS OF
ANSI/NSF STANDARD 61 SECTION 9 (1998), CONCERNING METAL
CONTAMINANTS IN THE WATER SYSTEM.
G!12 WATER PIPING SHALL NOT BE ROUTED IN OUTSIDE WALLS OR ON
EXTERIOR SIDE OF BUILDING INSULATION ENVELOPE.
G!13 WATER HAMMER ARRESTORS SHALL BE INSTALLED IN ALL WATER
LINES WITH QUICK OPEN OR QUICK CLOSE VALVES.
WATER HAMMER ARRESTOR SCHEDULE:
TYPE A 1!11 FIXTURE UNITS
TYPE B 12!32 FIXTURE UNITS
TYPE C 33!60 FIXTURE UNITS
TYPE D 61!113 FIXTURE UNITS
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
UVU Admin Building
Classroom Remodel
800 W. University Parkway
Orem, UT 84058
DFCM PROJECT #11064280
project#:
date:
12.0250
05 / 14 / 2012
revisions :
PLUMBING LEGEND
AND GENERAL
NOTES
sheet:
PG001
100% Construction Documents
SHEET NOTES
05/08/2012
1
9
9
10
1
2
T
3
11
4
9
5
6
REMOVE EXISTING EYE WASH AND ALL
ASSOCIATED PIPING. FIELD VERIFY EXACT PIPING
ROUTING.
2 REMOVE EXISTING GAS TURRET AND ASSOCIATED
PIPING. FIELD VERIFY EXACT PIPING ROUTING.
3 REMOVE EXISTING LAB SINK AND ASSOCIATED
PIPING. FIELD VERIFY EXACT PIPING ROUTING.
4 REMOVE EXISTING DISHWASHER AND ASSOCIATED
PIPING. FIELD VERIFY EXACT PIPING ROUTING.
5 REMOVE EXISTING DISTILLER AND ASSOCIATED
PIPING. SALVAGE TO OWNER. FIELD VERIFY EXACT
PIPING ROUTING.
6 REMOVE EXISTING AUTOCLAVE AND ASSOCIATED
PIPING. SALVAGE TO OWNER. FIELD VERIFY EXACT
PIPING ROUTING.
7 REMOVE EXISTING ACID WASTE VENT PIPING UP
THROUGH ROOF. SEAL ROOF OPENING WATER
TIGHT. FIELD VERIFY EXACT PIPING ROUTING.
8 REMOVE EXISTING EYEWASH SHOWER COMBO AND
ASSOCIATED PIPING. FIELD VERIFY EXACT PIPING
ROUTING.
9 REMOVE EXISTING LAB SINK, FAUCET AND GAS
TURRETS AND ASSOCIATED PIPING. FIELD VERIFY
EXACT PIPING ROUTING.
10 REMOVE EXISTING CW, HW, AND GAS PIPING BACK
TO RISERS IN THIS APPROXIMATE LOCATION AND
INSTALL SHUTOFF AND CAP. RISERS TO REMAIN
OPERATIONAL FOR SERVICE TO OTHER PORTIONS
OF BUILDING. FIELD VERIFY EXACT PIPING
ROUTING.
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 ! 4 4 2 2
consultants:
11 REMOVE ACID WASTE AND VENT PIPING BACK TO
RISERS IN THIS APPROXIMATE LOCATION. PROVIDE
WALL CLEANOUT AT WASTE DROP. CAP VENT
PIPING BEFORE RISER. RISERS TO REMAIN
OPERATIONAL FOR SERVICE TO OTHER PORTIONS
OF BUILDING
9
7
9
GENERAL NOTES
9
1. PIPING SHOWN IS RUN UNDER FLOOR AND WILL
NEED TO BE ACCESSED FROM THE FLOOR BELOW.
COORDINATE WITH OWNER FOR HOURS OF
ACCESS OF FLOOR BELOW. WORK MAY NEED TO BE
PERFOMRED AFTER HOURS OR OVER A WEEKEND.
2. REMOVE ACID WASTE & VENT PIPING PER OSHA
AND HAZARDOUS WASTE MANAGEMENT
STANDARDS.
8
9
3. COORDINATE SHUTDOWN OF PIPING SYSTEMS
WITH OWNER. WORK MAY NEED TO BE DONE AFTER
HOURS OR OVER A WEEKEND.
9
9
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
9
project:
9
9
UVU Admin Building
Classroom Remodel
9
800 W. University Parkway
Orem, UT 84058
9
DFCM PROJECT #11064280
project#:
date:
12.0250
05 / 14 / 2012
revisions :
PLUMBING
CLASSROOM DEMO
FLOOR PLAN
sheet:
1
PLUMBING CLASSROOM DEMO FLOOR PLAN
1/2" = 1' 0"
PD101
100% Construction Documents
No. 271888
G I NEER
EN
L I CENSED
SS I ON
AL
OFE
PR
KENNETH D.
GARNER
ST
AT
E O F UT
AH
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
SYMBOL LIST
M
ABBREVIATIONS
SURFACE/PENDANT LIGHT FIXTURE
T
TIMER
S
SECURITY SYSTEM AUDIO SENSOR
AFF
ABOVE FINISHED FLOOR
RECESSED DOWNLIGHT
PC
PHOTO CONTROL
M
SECURITY MONITOR, WALL MOUNTED
AIC
AMP INTERRUPTING CURRENT (SYMMETRICAL)
RECESSED ADJUSTABLE LIGHT FIXTURE
PS
STATION POWER SUPPLY
K
SECURITY SYSTEM KEYPAD
AL
ALUMINUM
WALL MOUNTED LIGHT FIXTURE
T
TRANSFORMER
WL
SECURITY WARNING LIGHT
BG
BELOW GRADE
MOTION SENSOR CONTROLLED WALL MOUNTED LIGHT FIXTURE
T
THERMOSTAT
MS
MOTION SENSOR, CEILING MOUNTED
WALL MOUNTED FLOODLIGHT
SL
SOLENOID
MS
MOTION SENSOR, WALL MOUNTED
CFCI
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
EXIT LIGHT
U
UNIT HEATER
FACP
FIRE ALARM CONTROL PANEL
CKT
CIRCUIT
WALL MOUNTED EXIT LIGHT
U
GAS UNIT HEATER
FAVE
FIRE ALARM VOICE EVACUATION PANEL
CO
CONDUIT ONLY
WALL MOUNTED RECESSED LIGHT FIXTURE
M
METER BASE
INDICATOR LAMP FOR CONCEALED DETECTOR
CU
COPPER
FV
FIRE ALARM VISUAL SIGNAL
EM
EMERGENCY
FUSED DISCONNECT SWITCH
F
FIRE ALARM HORN
(E)
EXISTING
DUAL POLE MOUNTED LIGHT FIXTURE
MANUAL STARTER
FV
FIRE ALARM VISUAL SIGNAL WITH HORN
EWC
ELECTRIC WATER COOLER
POLE TOP MOUNTED LIGHT FIXTURE
MAGNETIC STARTER
SS
FIRE ALARM VISUAL SIGNAL WITH SPEAKER
EWH
ELECTRIC WATER HEATER
CONTACTOR
F
FIRE ALARM REMOTE ANNUNCIATOR
(F)
FUTURE
COMBINATION STARTER/NON-FUSED DISCONNECT SWITCH
F
FIRE ALARM MANUAL PULL STATION
FA
FIRE ALARM
COMBINATION STARTER/FUSED DISCONNECT SWITCH
Z
FIRE ALARM FSD CONTROL RELAY
WALL MOUNTED FLUORESCENT LIGHT FIXTURE
MOTOR CONNECTION
FZ
FIRE ALARM ZONE MODULE
FLA
FULL LOAD AMPS
WALL MOUNTED LIGHT FIXTURE (EMERGENCY POWER)
PUSH BUTTON
F
FIRE ALARM CHIME
GFI
GROUND FAULT INTERRUPTER
EMERGENCY BATTERY LIGHT FIXTURE
EMERGENCY POWER OFF BUTTON, 46" AFF
FV
FIRE ALARM CHIME / VISUAL
GFP
GROUND FAULT PROTECTOR
SURFACE FLUORESCENT LIGHT FIXTURE
START-STOP BUTTON
F
FIRE ALARM BELL
GRD
GROUND
SURFACE FLUORESCENT LIGHT FIXTURE ON EMERGENCY
UP-DOWN-STOP BUTTON
F
REMOTE TROUBLE BUZZER
GRC
GALVANIZED RIGID CONDUIT
DATA OUTLET:
# INDICATES QTY.; NO DESIGNATION =(2) DATA OUTLET
DD
DUCT DETECTOR
P
PHOTO ELECTRIC SMOKE DETECTOR
LTG
LIGHTING
R
RATE OF RISE/THERMAL DETECTOR
MCB
MAIN CIRCUIT BREAKER
H
HEAT DETECTOR
MCC
MOTOR CONTROL CENTER
FS
FLOW SWITCH
MLO
MAIN LUGS ONLY
PS
FIRE ALARM PRESSURE SWITCH
(N)
NEW
TS
O.S. & Y. VALVE TAMPER SWITCH
NAC
NOTIFICATION APPLIANCE CIRCUIT
CM
FIRE ALARM CONTROL MODULE
NIC
NOT IN CONTRACT
MM
FIRE ALARM MONITOR MODULE
NL
FSD
FIRE SMOKE DAMPER
NTS
NOT TO SCALE
DC
DOOR CONTACT
OFCI
OWNER FURNISHED CONTRACTOR INSTALLED
ES
ELECTRIC STRIKE
OFOI
OWNER FURNISHED OWNER INSTALLED
GA
GENERATOR ANNUNCIATOR
PNL
PANEL
NAC
NOTIFICATION APPLIANCE CIRCUIT EXTENDER
(R)
RELOCATE
RFCC
REMOTE FIRE COMMAND CENTER
ST
SHUNT TRIP
TRAN
FIRE ALARM TRANSPONDER PANEL
F
POLE MOUNTED LIGHT FIXTURE
C
RECESSED FLUORESCENT LIGHT FIXTURE
RECESSED FLUORESCENT LIGHT FIXTURE ON EMERGENCY
F
FLUORESCENT STRIP LIGHT FIXTURE
3
LIGHT TRACK WITH LIGHT FIXTURES
SINGLE POLE SWITCH
3
A
AUTOMATIC SWITCH
K
KEY SWITCH
3
MOMENTARY CONTACT SWITCH
MK
MOMENTARY CONTACT KEY SWITCH
3K
3 - WAY KEY SWITCH
3
3 - WAY SWITCH
PP
PUSHPLATE SWITCH
D
LV
LOW VOLTAGE SWITCH
L
LINE VOLTAGE SENTRY SWITCH
TS
DIGITAL TIME SWITCH
VR
SWITCH WITH VANDAL RESISTANT COVER PLATE
D
DIMMER
OS
OCCUPANCY SENSOR, CEILING MOUNT
OCCUPANCY SENSOR, WALL MOUNT
PP
POWER PACK
3
TELEPHONE OUTLET:
# INDICATES QTY.; NO DESIGNATION =(1) TELEPHONE OUTLET
3
TELEPHONE OUTLET - ABOVE COUNTER:
# INDICATES QTY.; NO DESIGNATION =(1) TELEPHONE OUTLET
3
TELEPHONE OUTLET - FLUSH IN FLOOR:
# INDICATES QTY.; NO DESIGNATION =(1) TELEPHONE OUTLET
3
TELEPHONE OUTLET - PEDESTAL MOUNTED:
# INDICATES QTY.; NO DESIGNATION =(1) TELEPHONE OUTLET
3D,1P
3D,1P
SLAVE POWER PACK
ECU
DATA OUTLET - FLUSH IN FLOOR:
# INDICATES QTY.; NO DESIGNATION =(2) DATA OUTLET
DATA OUTLET - PEDESTAL MOUNTED:
# INDICATES QTY.; NO DESIGNATION =(2) DATA OUTLET
3D,1P
OS
DATA OUTLET - ABOVE COUNTER:
# INDICATES QTY.; NO DESIGNATION =(2) DATA OUTLET
3
DOOR SWITCH
SP
EMERGENCY CONTROL RELAY UNIT
3D,1P
DUPLEX RECEPTACLE
COMMUNICATIONS OUTLET:
D=DATA, P=TELEPHONE, F=FIBER, # INDICATES QTY.
NO DESIGNATION=(2) DATA OUTLET, (1) TELEPHONE OUTLET
COMMUNICATIONS OUTLET - ABOVE COUNTER
D=DATA, P=TELEPHONE, F=FIBER, # INDICATES QTY.
NO DESIGNATION=(2) DATA OUTLET, (1) TELEPHONE OUTLET
COMMUNICATIONS OUTLET - FLUSH IN FLOOR
D=DATA, P=TELEPHONE, F=FIBER, # INDICATES QTY.
NO DESIGNATION=(2) DATA OUTLET, (1) TELEPHONE OUTLET
RESCUE ANNUNCIATOR STATION
UNO
UNLESS NOTED OTHERWISE
RC
RESCUE CALL STATION
WG
WIRE GUARD
RX
SECURITY REQUEST TO EXIT
WP
WEATHER PROOF
MAGNETIC DOOR HOLDER (WALL OR FLOOR MOUNTED)
(X)
DEMOLISH/DELETE
#
DRAWING NOTE DESIGNATION
#
LIGHT FIXTURE DESIGNATION
W
WIRELESS DATA STATION AND RECEPTACLE, 84" AFF
VR
DUPLEX RECEPTACLE WITH VANDAL RESISTANT COVER PLATE
C
WIRELESS DATA STATION AND RECEPTACLE
FLEXIBLE CONDUIT
WIRELESS LAN TRANSMITTER
CONDUIT CONCEALED IN WALLS, CEILING OR FLOOR
19" TELECOM EQUIPMENT RACK WITH VERTICAL WIRE MGMT.
FOUR PLEX RECEPTACLE
STUB UP
FOUR PLEX RECEPTACLE ABOVE COUNTER
STUB DOWN
DUPLEX RECEPTACLE, FLUSH CEILING
FLOOR BOX WITH DUP. RECEPT. AND DATA
S
CEILING SPEAKER, RECESSED
DUPLEX RECEPTACLE, PEDESTAL MOUNTED
S
WALL SPEAKER
FOUR PLEX RECEPTACLE, PEDESTAL MOUNTED
V
SPEAKER VOLUME CONTROL
FOUR PLEX RECEPTACLE WITH COMMUNICATIONS OUTLET,
PEDESTAL MOUNTED
M
MICROPHONE RECEPTACLE, WALL
M
MICROPHONE RECEPTACLE, FLUSH FLOOR
TV
T.V. OUTLET
TVC
T.V. CAMERA
TVM
T.V. MONITOR
SPECIAL OUTLET TO MATCH EQUIPMENT PLUG, FLUSH IN FLOOR
CLOCK
SPECIAL OUTLET TO MATCH EQUIPMENT PLUG, PEDESTAL MOUNTED
MASTER CLOCK
SPECIAL OUTLET WITH NEMA CONFIGURATION, FLUSH IN FLOOR
BUZZER
EQUIPMENT CONNECTION
MULTI OUTLET ASSEMBLY
SURFACE EQUIPMENT CABINET AS NOTED
RECESSED EQUIPMENT CABINET AS NOTED
SURFACE ELECTRICAL PANELBOARD
PHASE CONDUCTOR
NEUTRAL CONDUCTOR
PHASE CONDUCTOR
NEUTRAL CONDUCTOR
PROVIDE GREEN GROUND WIRE
SIZED PER NEC IN ALL RACEWAYS
AHU-1
BELL
CHIME
IC
INTERCOM HORN, SECURITY
IC
INTERCOM STATION, SECURITY
CR
CARD READER
E
SECURITY EMERGENCY OVERRIDE
Enter address here
SHEET INDEX
MECHANICAL EQUIPMENT DESIGNATION
CABLE TRAY FOR DATA TELEPHONE AND
SOUND/PAGING ONLY (NO CONTROL WIRING)
TRANSFORMER
BREAKER
PROGRAM HORN
SPECIAL OUTLET WITH NEMA CONFIGURATION, PEDESTAL MOUNTED
BLANK BOX FOR FUTURE DATA
ISOLATED GROUND CONDUCTOR
EQUIPMENT GROUND CONDUCTOR
WALL MOUNTED CLOCK
SPECIAL OUTLET WITH NEMA CONFIGURATION
J B
STUB OUT
FLOOR BOX W/ FLEX TO LANDSCAPE PARTITION
SAME CODES AS RECESSED FLOOR BOX
DUPLEX RECEPTACLE, FLUSH IN FLOOR
JUNCTION BOX, FLUSH FLOOR MOUNTED
UVU Classroom
GROUND WIRE
19" TELECOM EQUIPMENT RACK
FOUR PLEX FLUSH IN FLOOR WITH INTERCOM
J
project:
EXISTING CONDUIT
FLOOR BOX WITH FOUR PLEX RECEPT. AND DATA
JUNCTION BOX
TRANSFORMER
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDERFLOOR
HALF SWITCHED DUPLEX RECEPTACLE
J
XFMR
consultants:
TYPICAL
RA
COMMUNICATIONS OUTLET - PEDESTAL MOUNT
D=DATA, P=TELEPHONE, F=FIBER, # INDICATES QTY.
NO DESIGNATION=(2) DATA OUTLET, (1) TELEPHONE OUTLET
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
NIGHT LIGHT
TRANSIENT VOLTAGE SURGE SUPPRESSOR
DUPLEX RECEPTACLE SAFETY TYPE
SPECIAL OUTLET TO MATCH EQUIPMENT PLUG
TYP
salt lake city, utah 84101
ISOLATED GROUND
TVSS
S
RANGE RECEPTACLE
IG
925 south west temple
FIRE ALARM CONTROL PANEL
MAGNETIC LOCK
DUPLEX RECEPTACLE WITH VANDAL RESIST COVERPLATE
POKE-THRU DEVICE
FACP
ML
VR
DUPLEX RECEPTACLE ABOVE COUNTER
J
CONDUIT
NON-FUSED DISCONNECT SWITCH
GROUND MOUNTED LIGHT FIXTURE
M
F
C
studio inc.
MANHOLE
EG001
SYMBOLS, ABBREVIATIONS AND SHEET INDEX
EDL101
LIGHTING DEMOLITION PLAN
ED101
ELECTRICAL DEMOLITION PLAN
EL102
LIGHTING FLOOR PLAN
EP102
POWER FLOOR PLAN
EY102
SYSTEM FLOOR PLAN
EX501
ELECTRICAL DETAILS AND SCHEDULES
DFCM PROJECT #11064280
project#:
date:
12.0250
05 / 07 / 2012
revisions :
600A DEADBREAK MOLDED
PRODUCT TERMINATION (15KV)
600A DEADBREAK MOLDED
PRODUCT SPLICE (15KV)
G&W UNIVERSAL CE
TERMINATION (15KV)
G&W UNIVERSAL CE
SPLICE (15KV)
RECESSED ELECTRICAL PANELBOARD
R
RELAY
200A LOADBREAK MOLDED
PRODUCT TERMINATION (15KV)
MEDIUM VOLTAGE
SPLICE (15KV HEATSHRINK
OR LOADSHRINK)
SYMBOLS,
ABBREVIATIONS,
& SHEET INDEX
sheet:
EG001
100% Construction Documents
3.
4.
5.
A.
B.
C.
D.
E.
GENERAL NOTES - SHEET EDL101
ALL DRAWINGS ARE BASED ON INFORMATION
PROVIDED ON EXISTING AS-BUILT DRAWINGS AND
FIELD SURVEY, CONTRACTOR TO FIELD VERIFY ALL
EXISTING CONDITIONS, MATERIALS, FINISHES AND
DIMENSIONS BEFORE AND AFTER DEMOLITION/
CONSTRUCTION.
CONTRACTOR TO ENSURE THAT ALL AREAS
OUTSIDE OF CONSTRUCTION AREA ARE KEPT
CLEAN AND CLEAR OF DEBRIS AND OBSTRUCTIONS
AT ALL TIMES.
PROTECT ALL ITEMS TO REMAIN FROM DAMAGE.
MAINTAIN CIRCUIT INTEGRITY OF POWER, LIGHTING,
TELECOM, SOUND, SECURITY AND ALL OTHER
CIRCUITS IN THE AREAS WHERE CIRCUIT CONTINUITY
IS INTERRUPTED BECAUSE OF THE REMODELING.
MAKE NECESSARY MODIFICATIONS TO MAINTAIN
CIRCUIT INTEGRITY.
ALL DEMOLISHED DEVICES AND EQUIPMENT ARE
THE PROPERTY OF THE OWNER AND SHALL BE
DISPOSED OF OR SALVAGED AND DELIVERED TO
THE OWNER AT THEIR DISCRETION.
SS I ON
AL
OFE
PR
No. 271888
G I NEER
EN
2.
KEYEN NOTES - SHEET EDL101
DISCONNECT AND REMOVE EXISTING PENDANT MOUNTED
FLUORESCENT STRIP LIGHT. ROOM LIGHT SWITCHES AND
ALL ASSOCIATED CONDUIT AND WIRE TO ABOVE CELLING.
TO BE RECONNECTED TO NEW LIGHTS.
DISCONNECT AND REMOVE EXISTING PENDANT MOUNTED 120V
INCANDESCENT DOWN LIGHTS AND ALL ASSOCIATED CONDUIT
AND WIRE BACK TO PANEL. LABEL PANEL AS SPARE.
NO WORK REQUIRED IN THIS ROOM.
EXISTING PANEL TO REMAIN.
EXISTING TELEPHONE BACKBOARD TO REMAIN.
L I CENSED
1.
KENNETH D.
GARNER
ST
AT
E O F UT
AH
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
2
S
O
1
OS
2
S
O
2
1
1
(TYP)
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
UVU Classroom
1
1
1
5
'HF'
3
4
'F'
4
Enter address here
2
DFCM PROJECT #11064280
Lighting Demo Ceiling Plan Classroom Area
project#:
date:
1/8" = 1'-0"
12.0250
05 / 07 / 2012
revisions :
KEY PLAN
LIGHTING
DEMOLITION
PLAN
sheet:
EDL101
100% Construction Documents
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
A.
B.
C.
D.
E.
GENERAL NOTES - SHEET ED101
ALL DRAWINGS ARE BASED ON INFORMATION
PROVIDED ON EXISTING AS-BUILT DRAWINGS AND
FIELD SURVEY, CONTRACTOR TO FIELD VERIFY ALL
EXISTING CONDITIONS, MATERIALS, FINISHES AND
DIMENSIONS BEFORE AND AFTER DEMOLITION/
CONSTRUCTION.
CONTRACTOR TO ENSURE THAT ALL AREAS
OUTSIDE OF CONSTRUCTION AREA ARE KEPT
CLEAN AND CLEAR OF DEBRIS AND OBSTRUCTIONS
AT ALL TIMES.
PROTECT ALL ITEMS TO REMAIN FROM DAMAGE.
MAINTAIN CIRCUIT INTEGRITY OF POWER, LIGHTING,
TELECOM, SOUND, SECURITY AND ALL OTHER
CIRCUITS IN THE AREAS WHERE CIRCUIT CONTINUITY
IS INTERRUPTED BECAUSE OF THE REMODELING.
MAKE NECESSARY MODIFICATIONS TO MAINTAIN
CIRCUIT INTEGRITY.
ALL DEMOLISHED DEVICES AND EQUIPMENT ARE
THE PROPERTY OF THE OWNER AND SHALL BE
DISPOSED OF OR SALVAGED AND DELIVERED TO
THE OWNER AT THEIR DISCRETION.
SS I ON
AL
OFE
PR
No. 271888
G I NEER
EN
2.
KEYED NOTES - SHEET ED101
DISCONNECT AND REMOVE EXISTING PEDESTAL
OUTLETS AND ALL ASSOCIATED CONDUIT AND
WIRE BACK TO SERVING PANEL. TYPICAL ALL
STUDENTS LAB TABLES.
DISCONNECT AND REMOVE EXISTING COUNTER
TOP OUTLET AND ALL ASSOCIATED CONDUIT AND
WIRE.
EXISTING TTB TO REMAIN.
DISCONNECT AND REMOVE EXISTING WIRING
DEVICES IN THIS ROOM (U.O.N) AND ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE
EXISTING FIRE ALARM DEVICE TO BE DISCONNECTED,
REMOVE AND RELOCATE.
DISCONNECT AND REMOVE ALL CONDUIT AND WIRE.
SERVING EXISTING FAN COIL UNIT TO BE REMOVED
DISCONNECT AND REMOVE EXISTING CEILING MOUNTED
PROJECTOR AND ALL ASSOCIATED CONDUIT AND WIRE
BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING MOTORIZED
PROJECTION SCREEN AND ALL ASSOCIATED CONDUIT
AND WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING PEDESTAL OUTLETS
AND ALL ASSOCIATED CONDUIT AND WIRE BANK TO
SOURCE.
DISCONNECT AND REMOVE EXISTING EXHAUST FAN AND
ALL ASSOCIATED CONDUIT AND WIRE BACK TO NEAREST
SOURCE.
REMOVE CONDUIT WIRE TO EXISTING DISHWASHER TO
BE REMOVED.
REMOVE CONDUIT AND WIRE TO EXISTING AUTO CLAVE
AND DISTILLER TO BE REMOVED.
L I CENSED
1.
KENNETH D.
GARNER
ST
AT
E O F UT
AH
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
DN
1
CTR
CTR
J
4
ABOVE DOOR
J
10
11
4
12
8
5
4
MOUNTED +80" AFF
FOR MOTORIZED
PROJECTOR SCREEN
C
7
TR
9
1
(TYP.)
5
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
FV
C
TR
1
project:
C
TR
J
1
C
UVU Classroom
TR
6
1
4
2
'HF'
3
Enter address here
2
Power Demo Floor Plan Classroom Area
1/8" = 1'-0"
DFCM PROJECT #11064280
project#:
date:
12.0250
05 / 07 / 2012
revisions :
KEY PLAN
ELECTRICAL
DEMOLITION
PLAN
sheet:
ED101
100% Construction Documents
2.
3.
A.
B.
C.
D.
KEYED NOTES - SHEET EL102
PROVIDE CONDUIT AND WIRE TO RECONNECT LIGHTS
TO EXISTING NORMAL POWER. LIGHTING CIRCUIT IN
THIS ROOM.
NO WORK REQUIRED IN THIS ROOM.
CONNECT TO EXISTING EMERGENCY LIGHTING
CIRCUIT IN THIS ROOM. LIGHT FIXTURE SHALL BE
NIGHT LIGHT.
GENERAL NOTES - SHEET EL102
CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS,
MATERIALS, FINISHES AND DIMENSIONS BEFORE AND
AFTER DEMOLITION/CONSTRUCTION.
CONTRACTOR TO ENSURE THAT ALL CORRIDORS
OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN
AND CLEAR OF DEBRIS AND OBSTRUCTIONS AT ALL
TIMES.
PROTECTOR FROM DAMAGE. ALL ITEMS TO REMAIN.
VERIFY EXACT LOCATION OF ALL CEILING MOUNTED
LIGHT FIXTURES WITH ARCHITECTURAL REFLECTED
CEILING PLAN.
No. 271888
G I NEER
EN
1.
L I CENSED
SS I ON
AL
OFE
PR
KENNETH D.
GARNER
ST
AT
E O F UT
AH
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
C
OS
A
1
b
C
b
OS
PP
b
OS
a
b
A
b
A
b
b
3
FS
3
NL
E
PP
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
a3b3
b
b
a
A
A
b
project:
b
OS
UVU Classroom
a
b
J
3
NL
CLASSROOM
202
OFFICE
1
OS
202A
A
2
E
3
a3b3
'HF'
Enter address here
DFCM PROJECT #11064280
2
Lighting New Ceiling Plan Classroom Area
project#:
date:
1/8" = 1'-0"
12.0250
05 / 07 / 2012
revisions :
KEY PLAN
LIGHTING
FLOOR PLAN
sheet:
EL102
100% Construction Documents
DESCRIPTION
FAN COIL UNIT
WALL MTD AC UNIT
PH
HP
KW
AMPS
MCA
120
208
1
1
0.65
-
-
12.0
14.0
15.0
17.5
DISCONNECT
SIZE
FUSE SIZE
NA
30
25.00
FURN. BY
ELEC
STARTER
TYPE
SIZE
MAN.
20A
MAN.
20A
WIRES
FURN. BY
ELEC.
ELEC.
2#12, 1#12 GND
2#10,1#10GND
CONDUIT
0.75
0.75
REMARKS
LOCATION
ABOVE CLG.
CONTROL B.
CONDENSING UNIT ON ROOF
120 VOLT LOAD CALCULATION
3.
CALCULATION
LOAD TOTAL
EXISTING DUPLEX RECEPTACLES REMOVED = 30
30 X 180 VA EA. =
5,400 VA
NEW DUPLEX RECEPTACLES ADDED = 25
25 x 180 VA EA. =
4,500 VA
LOAD DESCRIPTION
NET LOAD REMOVED =
2.
4.
900 VA
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
A.
B.
C.
D.
KEYED NOTES - SHEET EP102
24"X24"X4" FLUSH MOUNTED MEDIA J-BOX IN CEILING
WITH (1) 2"C.O. ROUTED TO A/V RACK
IN PROJECTION ROOM AND TO TEACHER STATION.
VERIFY EXACT LOCATION WITH OWNERS
REPRESENTATIVE.
PROVIDE TWO (2) 40AMP 1 POLE 120V CIRCUITS
TO A/V RACK. VERIFY EXACT RECEPTACLE/
TERMINATION REQUIREMENTS WITH OWNER.
ROUTE (2) 1"C 2#8 +1# C.O. GROUND TO CIRCUIT
INDICATED.
PROVIDE WALL MOUNTED OUTLET FOR CLASSROOM VIDEO
CAMERA. VERIFY EXACT LOCATION PRIOR TO ROUGH-IN.
PROVIDE RECESSED WALL BOX ADJACENT TO OUTLET WITH
2" CONDUIT UP TO CEILING SPACE.
FLUSH MOUNTED ROUND FLOOR BOX FOR POWER
ADDITIONAL REQUIRED. PROVIDE POWER AND DATA CABLE
FROM FLOOR BOX THRU TABLE LEGS TO CONNECT TO
POP-UP OUTLETS. COORDINATE EXACT LOCATION OF
BOXES WITH FURNITURE INSTALLED PRIOR TO
ROUGH-IN. FLOOR BOX SHALL BE FSR-FL-500-6 SERIES
OR EQUIVALENT (TRIPLE GANG). PROVIDE 2"C FOR
MICROPHONE BACK TO A/V RACK.
PROVIDE TELE/DATA OUTLET SURFACE MTD TO
CONCRETE COLUMN FOR UVU MEDIA A/V CONTROL
CABINET CONNECTION. SEE SYSTEMS PLAN FOR
ADDITIONAL REQUIRED.
PROVIDE WALL MTD. OUTLET FOR CLASSROOM VIDEO CAMERA
VERIFY EXACT LOCATION PRIOR TO ROUGH-IN. PROVIDE
RECESSED WALL BOX (IN BOOTH) BEHIND CAMERA
LOCATION WITH 3" CONDUIT UP TO CEILING SPACE.
SEE ARCHITECT'S ELEVATION SHEETS. AE601 FOR MORE
INFORMATION.
COORDINATE FINAL LOCATION OF RECEPTACLE
TO 70" LCD FLAT SCREEN TV PRIOR TO ROUGH-IN.
PROVIDE FLOOR BOX SAME AS NOTE 4 ABOVE
BUT FOR DATA ONLY AND NOT POWER. FIELD
VERIFY EXACT LOCATION. PROVIDE 1" CONDUIT FOR
MICROPHONE TO A/V RACK.
PROVIDE MINIMUM 1"C FOR EACH TELL/DATA
OUTLET TO EXIST TTB.
VERIFY EXACT LOCATION FOR 55" FLAT SCREEN TV'S
MONITOR (BY OWNER) PROVIDE 1"C TO A/V RACK.
EXISTING RELOCATED PANEL, EXTEND EXISTING
FEEDER CONDUIT, WIRE AND RECONNECT. INTERCEPT
EXISTING
BRANCH CIRCUITS TO REMAIN WITH WIRE
GUTTER. SPLICE IN NEW CONDUIT, WIRE AND RECONNECT
TO EXISTING BRANCH CIRCUIT BREAKERS.
PROVIDE CONDUIT AND WIRE TO CONNECT
RECEPTACLE TO CIRCUIT DEMOLITION IN THE ROOM.
MAKE FINAL CONNECTION TO AC-1 (WALL MOUNTED)
ROUTE CONDUIT AND WIRE UP TO ROOF MOUNTED.
CONDENCER UNIT AND PROVIDE NEMA 3R 30A 2P FUSE
DISCONNECT SWITCH.
NEW FIRE/SMOKE DAMPER, PROVIDE NEW CONDUIT AND
LOW VOLTAGE WIRE TO CONNECT TO EXISTING BUILDING
FACP. COORDINATE WITH MECHANICAL.
SS I ON
AL
OFE
PR
No. 271888
G I NEER
EN
FC-7
AC-1
V
1.
L I CENSED
EQUIPMENT SCHEDULE
KENNETH D.
GARNER
ST
AT
E O F UT
AH
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
GENERAL NOTES - SHEET EP102
CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS,
MATERIALS, FINISHES AND DIMENSIONS BEFORE AND
AFTER DEMOLITION/CONSTRUCTION.
CONTRACTOR TO ENSURE THAT ALL CORRIDORS
OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN
AND CLEAR OF DEBRIS AND OBSTRUCTIONS AT ALL
TIMES.
PROJECTOR ALL ITEMS TO REMAIN FROM DAMAGE.
CONTACTOR SHALL MEASURE ALL LOADS EXCEED 80%
OF OCP. INFORM ENGINEER IMMEDIATELY FOR CORRECTIVE
ACTION.
DN
2
FF-2
FF-4
J
F-4,6
F-28
F-36
F-36
4
8
F-28
J
13
9
F-32 F-26
F-32
F-36
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
10
F-26
CLASSROOM
6
4
F-32
202
F-3
project:
8
FS
F-32
UVU Classroom
+80"
F-3
3
F-31
7
F-8
F-32
4
8
F-26
F-26
FC-7
8
F-31
F-2
F-36
F-19
7
4
J
F-32
3
9
CONNECT WITH 2#10, 1#10 GROUND.
+80"
F-3
IN 3/4C BACK TO PANEL.
5
12
OFFICE
202A
Enter address here
12
EXISTING TTB
'HF'
'F'
DFCM PROJECT #11064280
project#:
date:
12.0250
05 / 07 / 2012
revisions :
2
Power Floor Plan Classroom Area
1/8" = 1'-0"
KEY PLAN
POWER FLOOR
PLAN
sheet:
EP102
100% Construction Documents
1"C TO CEILING SPACE
2"C TO CEILING SPACE
J
J
POWER J-BOX
J
2.
3.
4.
5.
J-BOX FOR AUDIO
J-BOX FOR VIDEO
6.
7.
FRONT CAMERA
TYPICAL WALL ELEVATION
1
EY102
SCALE: NTS
8.
9.
10.
11.
12.
A.
B.
C.
GENERAL NOTES - SHEET EY102
CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS,
MATERIALS, FINISHES AND DIMENSIONS BEFORE AND
AFTER DEMOLITION/CONSTRUCTION.
CONTRACTOR TO ENSURE THAT ALL CORRIDORS
OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN
AND CLEAR OF DEBRIS AND OBSTRUCTIONS AT ALL
TIMES.
PROJECTOR ALL ITEMS TO REMAIN FROM DAMAGE.
No. 271888
G I NEER
EN
1.
KEYED NOTES - SHEET EY102
OWNER FURNISHED CONTRACTOR CEILING MOUNTED
SPEAKER. OWNER SHALL PROVIDE CABLE AND MAKE ALL
TERMINATIONS.
NOT USED
NOT USED
NOT USED
PROVIDE (2) 2"C 2(1)1"C FROM TEACHER STATION
TO CEILING SPACE. CONDUITS SHALL BE SURFACE
MOUNTED VERTICALLY DOWN COLUMN AND TERMINATED
WITH BUSED ENDS, ABOVE ACCESSIBLE CEILING.
DOCUMENT ID CAMERA LOCATION (FIELD VERIFY EXACT
LOCATION PRIOR TO ROUGH-IN) PROVIDE 1"C TO
MEDIA J-BOX.
PROVIDE 1"C FROM WALL MOUNTED SPEAKER LOCATION
TO A/V RACK. SPEAKERS SHALL BE " DAISY CHAINED".
CABLE TRAY SHALL BE ZINC PLATED STEEL WIRE BASKET,
SUPPORTEDMIN. EVERY EIGHT FEET.
70"C.O. FLAT SCREEN TV (FIELD VERIFY EXACT MOUNTED
HEIGHT LOCATION WITH OWNER), OFCI. PROVIDE 1"C TO
CABLE TRAY.
55" TV MONITOR (FIELD VERIFY EXACT MOUNTED HEIGHT AND
LOCATION WITH OWNER), OFCI. PROVIDE 1"C TO A/V RACK
PROVIDE NEW FIRE ALARM SYSTEM DEVICE AND PROVIDE
CONDUIT AND WIRE TO CONNECT TO EXISTING BUILDING
FIRE ALARM SYSTEM.
EXISTING RELOCATED FIRE ALARM VISUAL/STROBE DEVICE
RECONNECT TO BUILDING FIRE ALARM SYSTEM.
L I CENSED
SS I ON
AL
OFE
PR
KENNETH D.
GARNER
ST
AT
E O F UT
AH
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
consultants:
DN
A/V RACK
12"X4" CABLE TRAY
8
S
10
S
10
1
(TYP)
CC
TV
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
6 +80"
S
S
S
6
7
202
FV
+80"
project:
S
UVU Classroom
TV
CC
CLASSROOM
(TYP)
S
12
FS
S
11
9
7
S
TV
CC
6
+80"
5
OFFICE
202A
Enter address here
EXISTING TTB
'HF'
DFCM PROJECT #11064280
project#:
date:
12.0250
05 / 07 / 2012
revisions :
2
Systems Floor Plan Classroom Area
1/8" = 1'-0"
KEY PLAN
SYSTEMS
FLOOR PLAN
sheet:
EY102
100% Construction Documents
LAY-IN 2' X 4' FLAT CENTER ANGLED SIDES
24 IN. X 48 IN.
STEEL
PROGRAM START BALLAST
BAKED WHITE ENAMEL
ACRYLIC
.77 BALLAST FACTOR
HIGH (80%-85% FIXTURE EFFIENCY)
RECESSED LAY-IN
MUST SUBMIT PHOTOMETRIC REPORT FOR APPROVAL
C
(2) F32T8 SP35K
PENDANT 4' LONG FLUORESCENT LIGHT
10 IN. X 3 IN. X 48 IN.
GE PROLINE
COLD ROLLED STEEL
INSTANT START BALLAST
.87 BALLAST FACTOR
BAKED WHITE ENAMEL
WRAP AROUND PRSIMATIC LENS
72275-GE-232-MV-N
OR EQUAL
SURFACE /PENDANT
FUSE
E
UNIVERSAL L.E.D. EDGE LIT EXIT SIGN
GREEN L.E.D.
120/277 VOLT *
8 IN. X 12 IN. X 2 IN. NOMINAL
POLYCARBONATE
WHITE HOUSING.
DIRECTIONAL ARROWS (SEE DRAWINGS)
UNIVERSAL (SEE DRAWINGS)
CVD SERIES DIECAST ALUMINUM LED EXIT SIGN,
AC ONLY, GREEN LETTERS, WHITE STENCIL &
HOUSING, SINGLE OR DOUBLE FACE.
* CONTRACTOR SHALL FIELD VERIFY OPERATING VOLTAGE. EXIT SIGNS SHALL BE 120VOLT TO MATCH EXISTING, ALL OTHER LIGHT FIXTURES
DESCRIPTION:
SIZE:
HOUSING:
FINISH:
LENS:
PERFORMANCE:
MOUNTING:
REMARKS:
DESCRIPTION:
SIZE:
HOUSING:
FINISH:
REFLECTOR:
MOUNTING:
ACCESSORIES:
DESCRIPTION:
SIZE:
HOUSING:
FINISH:
ACCESSORIES:
MOUNTING:
OTHER:
LIGHTOLIER #SKS2GPK332UNV-PS
FINELITE # HPR12X4DCO3T8UNVPS
LEDALITE # 3324D1STT332S UNVPS
AXIS #DIA24VLT83UNVETB
OR APPROVED
METALUX # R3WL3 T81 UNV T1 2X4
54
METALUX # WSA 232 A UNV T81
OR EQUAL APPROVED:
COLUMBIA
LITHONIA
LIGHTOLIER
COOPER/SURE-LITES
#LPX-7
4
OR EQUAL APPROVED:
LITHONIA
DUAL LITE
COLUMBIA
3/8" ALL THREAD ROD (TYP)
PHONE BOARD
*PROJECTOR RM 202 CLG.
PLUGS FLOOR & WALL 205
PLUG ADJ CORD + RM 206
PLUG 206
PLUG 206
PLUG MEN & WOMEN BATHROOMS
PLUG 216F
PLUGS 214 + 216G
PLUG ADJ CORD + RM 207
PLUG 207
LIGHTING 205A
EXH. FAN 209
EXH. FANS (2) BATHS
LIGHTING CORRIDOR
*FLAT SCREEN TV'S
SIMPLEX RELAY FOR FANS
PLUG 216
NORTH OFF.LTS. PLUGS 217F
NORTH OFF.HEAT & COOL.FANS
NORTH OFFICE PLUGS
180
360
3
BKR
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
P
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PH
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
4
W
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
AIC
225 A BUS
BKR
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
100
-
CONNECTED LOAD
4.3 KVA
12.0
Amps
NEC DEMAND LOAD
0.0 KVA
0.0
Amps
P
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
-
DESCRIPTION
LOAD
720 FLOOR RECP CLASSRM 204*
720 FLOOR RECP CLASSRM 204*
900 RECEPTACLES *
PLUGS
PLUGS 205 C,D
PLUGS 205 E,F
PLUGS 205 A,P
PLUGS 205 G,H
PLUGS 205 J,K
PLUGS 216 B,C
PLUGS 216 C,D
PLUGS 216 D,E
360 OFFICE RECEPTS *
540 TEACH'S STAT./DOC CAM.*
FRIDGE 216F
180 PROJECTION SCREEN *
PLUGS 216C
360 * A/V RACK
SUB FEED PANEL FF
SUB FEED PANEL FF
SUB FEED PANEL FF
No. 271888
KENNETH D.
GARNER
ST
AT
E O F UT
AH
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS
AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED FOR
CONSTRUCTION, RECORDING PURPOSES OR IMPLEMENTATION
method
studio inc.
925 south west temple
salt lake city, utah 84101
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
* CONNECT NEW CONDUCTORS TO EXISTING SPARE CIRCUIT BREAKERS
consultants:
6" MAX.
SLOTTED METAL
FRAMING CHANNEL
1-5/8" x 1-5/8"
(TYP)
STIFFENER
CLIP
AIRCRAFT
CABLE SUPPORT
(TYP)
TYPICAL WALL
OUTLET
BAR
STRAPS
6" MAX.
PROVIDE CONDUIT SUPPORTS IN
ACCORDANCE WITH NEC SPACING
REQUIREMENTS FOR TYPE OF
RACEWAY REQUIRED.
AS REQUIRED FOR TYPE
OF CONSTRUCTION
STEEL CITY
NO. 7501
BOX SUPPORT
BAR
STRAPS
TYPICAL
OUTLET BOX
NOTES:
45° +15%
45° +15%
FRONT VIEW
SIDE VIEW
TOP VIEW
1
EX501
TYPICAL S
OUTLET BOX
1.
TYPICAL FOR WOOD AND
METAL STUD ROUGH-IN.
2.
PLASTER RINGS NOT SHOWN.
3.
LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH
ARCHITECTURAL AND MECHANICAL DRAWINGS, AND
WITH ALL APPLICABLE SHOP DRAWINGS.
4.
IN ACCORDANCE WITH UBC 4303 OUTLETS ON OPPOSITE SIDES OF WALLS OR
PARTITIONS IN THE SAME STUD SPACE MUST BE SEPARATED BY A MINIMUM
OF 24" HORIZONTAL DISTANCE.
TYPICAL SUSPENDED LIGHT FIXTURE
SEISMIC BRACING DETAIL
TYPICAL ROUGH IN REQUIREMENTS
2
SCALE: NTS
EX501
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL
TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR
COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE
AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
BAR
STRAPS
UVU Classroom
Enter address here
SCALE: NTS
DFCM PROJECT #11064280
LOCAL
OFF
SWITCH
NEUTRAL
RED
WHT
POWER
PACK
BLK
RED
HOT
WHT
L
O
A
D
project#:
date:
Neutral
RED
L
o
a
d
3-Way
Switches
BLU
BLU
BLK
RED
BLK
CAP-OFF
UNUSED
CONTROL OUTPUT
ANY
24VDC
CEILING/WALL
SENSOR
+24VDC
COMMON
Blk
Hot
Red
+24VDC
ANY
24VDC
CEILING/WALL
SENSOR
Power
Pack
NOTE:
USE THIS SCHEMATIC WHEN
CURRENT CONSUMPTION OF
MULTIPLE SENSORS EXCEEDS
CURRENT OUTPUT OF A SINGLE
POWER PACK.
MULTIPLE OCCUPANCY
SENSORS WITH MULTIPLE
POWER PACKS
Red
Blu
CONTROL OUTPUT
Control Output
Common
+24VDC
MULTIPLE OCCUPANCY SENSORS
WITH MULTIPLE POWER PACKS
SCALE: NTS
ELECTRICAL
DETAILS AND
SCHEDULES
Red
Wht
EX501
revisions :
Travelers
RED
COMMON
3
12.0250
05 / 07 / 2012
RED
POWER
PACK
Blk
A
MANUFACTURER(S)
INPUT
(VA)
77
LAMP(S) AND
BALLASTS
(3) F32T8 SP35K
DESCRIPTION
BLK
TYPE
LOAD
L I CENSED
120 208
DESCRIPTION
G I NEER
EN
PANEL: F (EXIST.)
LUMINAIRE SCHEDULE - SHEET EX501
SS I ON
AL
OFE
PR
4
EX501
Any
24VDC
Ceiling/Wall
Sensor
3-WAY SWITCHING WITH SENSOR
SCALE: NTS
sheet:
EX501
100% Construction Documents