Super compact version on/off control

Super compact version on/off control
Super compact version
on/off control
Model: HC005S
Antenna module
Daylight sensor
Led indication
Detection area
Hold-time
Daylight threshold
Power supply
220-240V out control
The smallest HF motion sensor on the planet, worldwide patented!!!
This sensor is a motion switch, turn on the light on detection of people movement, and turn off after a pre-selected holdtime when there is no
people around. A daylight sensor is also built-in to switch off the light when there is sufficient natural light.
Function and options
1
On-off Function
With sufficient natural light, the light does
not switch on when presence detected
With insufficient natural light,the sensor
switches on the light automatically when
person enters the room
After the hold time,then switch off
automatically when no movement is
detected.
Wiring Diagram
HC005S
2
3-steps dimming control
with Tridonic switchDIM ballast / driver ( Excel ballast/driver, corridor function) , this sensor can also achieve 3-steps dimming control...
Wiring Diagram
switchDIM
switchDIM
HC005S
switchDIM
10%
30%
50%
75%
ceiling mounting pattern (m)
wall mounting height
ceiling mounting height(m)
Detection Pattern
10%
30%
50%
75%
wall mounting pattern (m)
Zero-cross relay operation
zero-cross point
Designed in the software, sensor switches
on/off the load right on the zero-cross point,
to ensure the min. current passing through the
relay contact point, and enbale the max. load
and life-time of the relay.
alternating current
Settings
1
1
Detection area
2
3
100%
75%
Detection area can be reduced by selecting the combination on
the DIP switches to fit precisely for each specific application.
50%
30%
10%
2
I – 5s
II – 30s
III – 1minutes
IV – 5minutes
V – 20minutes
VI – 30minutes
Hold-time
Hold-time means the time period you would like to keep the
lamp on 100% after the person has left the detection area.
3
I – Detection range 100%
II – Detection range 75%
III – Detection range 50%
IV – Detection range 30%
V – Detection range 10%
Daylight sensor
I – disabled
II – 50 lux
III – 20 lux
IV – 5 lux
V – 2 lux
The daylight threshold can be set on DIP switches, to fit for
particular application.
“daylight” : The lamp works always,even during daylight.
“twilight” : The lamp works only in twilight .
“darkness” : The lamp works only in darkness.
Technical Data
Operating voltage
220-240V
Switched power
Max.400W (capacitive)
Standby power
Max.1200w(resistive)
0.5w
Warmming-up time
20s
Detection area
10/25/50/75/100%, can be customized
Hold time
5S/30S/1min/5min/15min/30min, can be customized
Daylight threshold
2~50lux daylight/twilight/darkness, can be customized
Microwave frequency
5.8GHz+/-75MHz
Microwave power
0.2mw
Detection range
Max. (oxH): 12m x 6m
Detection angle
30 ~150
Mounting height
Max.6m
Operating temperature
-35 C ~ +70 C
IP rating
IP20
certificate
Semko, EMC, CE, R&TTE
o
o
o
o
IP65(mounting in Hytronik special box)
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF