RSLogix 500 Getting Results Guide
Getting Results Guide
Doc ID LG500-GR001A-EN-P
Contacting Technical Support Telephone—1-440-646-7800
Rockwell Software Technical Support Fax—1-440-646-7801
World Wide Web—www.software.rockwell.com
Copyright Notice ©2000, 2001, 2002 Rockwell Software Inc., a Rockwell Automation company. All rights reserved
Printed in the United States of America
Portions copyrighted by Allen-Bradley Company, LLC, a Rockwell Automation company.
This manual and any accompanying Rockwell Software products are copyrighted by Rockwell
Software Inc. Any reproduction and/or distribution without prior written consent from Rockwell
Software Inc. is strictly prohibited. Please refer to the license agreement for details.
Trademark Notices The Rockwell Software logo, RSLogix 500, RSLinx, RSLogix 5, RSTrainer, RSTrend, RSTrendX,
RSView, A.I. Series, Advanced Interface (A.I.) Series, and RSTune are trademarks of Rockwell
Software Inc., a Rockwell Automation company.
DH+, DH 485, MicroLogix, SLC, SLC 5/01, SLC 5/02, SLC 5/03, SLC 5/04, SLC 5/05, and SLC
500 are trademarks of the Allen-Bradley Company, LLC, a Rockwell Automation company.
Microsoft, Windows, Excel, and Visual Basic are registered trademarks, and Windows NT,
Windows 98, Windows 2000, and Windows XP are trademarks of the Microsoft Corporation.
Norton Antivirus is a registered trademark of Symantec Corporation.
Pentium and Pentium II are registered trademarks of the Intel Corporation.
IBM is a registered trademark of International Business Machines Corporation.
All other trademarks are the property of their respective holders and are hereby acknowledged.
Warranty This Rockwell Software product is warranted in accord with the product license. The product's
performance will be affected by system configuration, the application being performed, operator
control and other related factors.
The product's implementation may vary among users.
This manual is as up-to-date as possible at the time of printing; however, the accompanying
software may have changed since that time. Rockwell Software reserves the right to change any
information contained in this manual or the software at anytime without prior notice.
The instructions in this manual do not claim to cover all the details or variations in the equipment,
procedure, or process described, nor to provide directions for meeting every possible contingency
during installation, operation, or maintenance.
Preface
Purpose of this book
This Getting Results book provides you with information on how to install and
navigate the RSLogix 500 software. This guide includes troubleshooting
information and tips on how to use RSLogix 500 effectively. It also explains
how to access and navigate the online help.
Intended audience
We assume that you are a control engineer familiar with:
„ IBM-compliant personal computers
„
„
Microsoft Windows 98®, NT 4.0™, or Microsoft Windows 2000™ or
Windows XP™
Rockwell Automation’s SLC 500™ and MicroLogix™ families of controllers
Document conventions
This manual uses the following typographical conventions:
„ [Bold] characters in brackets represent keystrokes used to execute a
function. When more than one key is to be pressed at a time, the keys are
separated by a plus sign. For example, [Ctrl + v] means hold down the
[Ctrl] key and press the [v] key.
„
Bold characters represent menu choices.
„
TEXT IN THIS FONT represents characters that you should type.
Online help
If you need help while using RSLogix 500, use any of the following methods:
„ choose Help from the menu bar
„
click the Help button on any RSLogix 500 dialog
„
press [F1] on any instruction, dialog box, or window view.
For more information about the online help refer to RSLogix 500 online help on
page 73.
Preface
Q
i
Training
Rockwell Software offers both classroom training and a computer-based
training program for RSLogix 500 software. For more information see RSLogix
500 Training on page 77.
Commonly used terms
The following table defines terms commonly used in this book.
ii
Q
This term:
Represents this concept:
activation files
Hidden files in the root folder that allow the software to run. The
software checks for these files before you have access to offline
or online programming
back up
To make a copy of the current file before replacing that file with
an updated version.
download
Restore a specified file to a specified processor. For example,
when you download the current project file, you copy the file to
a specified processor so the processor can begin running that file.
library
A file into which you store or from which you retrieve portions
of ladder logic.
mnemonic
A term, usually an abbreviation that is easy to remember. SLC
instructions are typically represented by a 3-letter mnemonic.
project
All of the files that make up the SLC 500 logic program including
the documentation files.
upload
Access an SLC processor and save a copy of the project.
verification
An analysis of the ladder program files that results in the display
of any programming errors.
zone
Portion of the ladder logic identified by a marker indicating the
edited state of the file.
Getting Results with RSLogix 500™
Contents
Preface ...................................................................................... i
Purpose of this book .................................................................................................................. i
Intended audience ....................................................................................................................... i
Document conventions.............................................................................................................. i
Online help................................................................................................................................... i
Training........................................................................................................................................ ii
Commonly used terms .............................................................................................................. ii
Chapter 1
Installing RSLogix 500.............................................................. 1
Introduction ................................................................................................................................1
System requirements..................................................................................................................1
Hardware requirements.......................................................................................................................1
Software requirements ........................................................................................................................2
Activation ....................................................................................................................................3
Installing RSLinx Lite software................................................................................................3
Installing and activating RSLogix 500 software.....................................................................4
Installing the source control feature........................................................................................5
Installing the Microsoft SQL Server Desktop Engine...................................................................5
Installing the Archive Module Extended Procedures Component..............................................6
Creating the Archive Module database.............................................................................................6
Installing the Archive Module Administration Utility....................................................................8
Installing the Archive Module client component ...........................................................................9
Starting RSLogix 500 software.................................................................................................9
Troubleshooting installation.....................................................................................................9
Chapter 2
Getting started with RSLogix 500.......................................... 11
Welcome to RSLogix 500 .......................................................................................................11
Exploring RSLogix 500 ...........................................................................................................12
Quick Start Steps......................................................................................................................13
Step 1 • Configure a driver in RSLinx....................................................................................... 14
Table of Contents • iii
Step 2 •
Step 3 •
Step 4 •
Step 5 •
Step 6 •
Step 7 •
Step 8 •
Step 9 •
Step 10 •
Step 11 •
Step 12 •
Configure system communications............................................................................. 16
Create a new project or open an existing project ..................................................... 17
Create program and data table files ............................................................................ 19
Define chassis and modules......................................................................................... 20
Enter a logic program ................................................................................................... 20
Add documentation to your logic instructions ......................................................... 22
Validate your project ..................................................................................................... 23
Configure communication channel, download and go online................................ 24
Monitor data files........................................................................................................... 24
Search and replace instructions ................................................................................... 25
Print a report .................................................................................................................. 26
Chapter 3
Chassis and module setup ......................................................27
Power supply loading .............................................................................................................. 28
Analog and specialty module configuration ........................................................................ 28
Automatic I/O configuration................................................................................................ 28
Chapter 4
Entering ladder logic...............................................................29
Backing up your work............................................................................................................. 29
Crash Recovery.................................................................................................................................. 30
Quick entry of instructions ....................................................................................................31
Addressing ................................................................................................................................ 32
Branching.................................................................................................................................. 33
Add a branch ..................................................................................................................................... 33
Move a branch ................................................................................................................................... 33
Expand a branch ............................................................................................................................... 33
Nested branches ................................................................................................................................ 33
Parallel branches................................................................................................................................ 33
Copy branch leg................................................................................................................................. 34
Copy entire branch structure........................................................................................................... 34
Delete a branch.................................................................................................................................. 34
Branching restrictions....................................................................................................................... 34
Undo operation........................................................................................................................ 34
Online editing........................................................................................................................... 35
Lower case zone markers................................................................................................................. 36
Upper case zone markers................................................................................................................. 36
Online editing example .................................................................................................................... 37
iv • Getting Results with RSLogix 500™
Online editing restrictions ............................................................................................................... 38
ASCII editing ............................................................................................................................38
Configuring interrupts .............................................................................................................38
Selectable Timed Interrupt.............................................................................................................. 39
Discrete Input Interrupt .................................................................................................................. 39
Chapter 5
Importing or exporting the documentation database ........... 41
Introduction ..............................................................................................................................41
Import database........................................................................................................................41
A.I. project documentation database ............................................................................................. 42
APS project documentation database............................................................................................ 42
RSLogix 500 documentation database........................................................................................... 42
CSV (Comma Separated Values) file ............................................................................................. 42
ASCII delimited text file .................................................................................................................. 43
Export database........................................................................................................................43
RS500 ASCII delimited text file examples.................................................................................... 44
A.I. ASCII delimited text file examples......................................................................................... 45
Chapter 6
Monitoring data....................................................................... 47
Introduction ..............................................................................................................................47
Multipoint Monitor..................................................................................................................48
Forces.........................................................................................................................................48
Custom Data Monitor (CDM) ...............................................................................................49
Custom Graphical Monitor ....................................................................................................49
Recipe Monitor.........................................................................................................................50
Trends ........................................................................................................................................51
Histograms ................................................................................................................................51
Data Logging (MicroLogix 1500LRP only) .........................................................................52
Cross Reference........................................................................................................................53
Chapter 7
Saving and loading SLC libraries ........................................... 55
Introduction ..............................................................................................................................55
Exporting libraries....................................................................................................................55
Importing libraries ...................................................................................................................56
Table of Contents • v
Chapter 8
Features in RSLogix 500 Professional....................................59
Microsoft® Visual Basic for Applications® support ........................................................ 59
Source Control ......................................................................................................................... 59
Custom Graphical Monitor.................................................................................................... 59
Editing project databases using Microsoft® Excel®......................................................... 60
Logic Trace ............................................................................................................................... 61
How logic trace works...................................................................................................................... 61
Chapter 9
Source control.........................................................................63
About source control .............................................................................................................. 63
Configuring the source control database ............................................................................. 63
Registering the source control database with the administration utility ................................... 64
Creating database users .................................................................................................................... 64
Assigning folder privileges to users................................................................................................ 65
Registering the source control database with RSLogix 500 .............................................. 66
Adding a project to the archive ............................................................................................. 67
“Getting” and checking out projects.................................................................................... 68
Undoing a check out ............................................................................................................... 70
Checking in projects................................................................................................................ 71
Chapter 10
Getting the information you need...........................................73
Introduction.............................................................................................................................. 73
RSLogix 500 online help ........................................................................................................73
Opening an expandable table of contents..................................................................................... 74
Index
.......................................................................................................................................... 74
Find
.......................................................................................................................................... 74
Learning RSLogix 500 step-by-step...................................................................................... 75
Quick tips about Windows operating systems and RSLogix 500..................................... 76
Keyboard shortcuts ................................................................................................................. 76
User Application help ............................................................................................................. 76
Instruction Set help ................................................................................................................. 77
RSLogix 500 Training ............................................................................................................. 77
Classroom training ............................................................................................................................ 77
Interactive training ............................................................................................................................ 78
vi • Getting Results with RSLogix 500™
Technical support services......................................................................................................78
When you call .................................................................................................................................... 79
Appendix A
Activation................................................................................ 81
Index ....................................................................................... 87
Table of Contents • vii
viii • Getting Results with RSLogix 500™
Installing RSLogix 500
Chapter
Introduction
This chapter explains how to install and start RSLogix 500 software. This
chapter includes information on the following:
„ system requirements
„
installation methods
„
activation overview and methods
„
installation and activation procedures
„
starting procedures
„
troubleshooting installation and activation
After installing the software, we recommend that you read the release note
located in the online help. The release note may contain more up-to-date
information than was available when this document was published. To view the
Release Notes, start the RSLogix 500 software; then choose Help > RSLogix
Release Notes.
Important
If you are installing RSLogix 500 on a computer running Windows
NT®, Windows 2000™, or Windows XP™, you must have
administrator privileges for the computer. For more information,
contact your system administrator.
System requirements
To use RSLogix 500 effectively, your personal computer must meet the
following hardware and software requirements:
Hardware requirements
„
„
an Intel Pentium II® or greater microprocessor
128 MB of RAM for Windows NT, Windows 2000, or Windows XP
installations (64 MB for Windows 98® installations)
Installing RSLogix 500 • 1
„
45 MB of available hard disk space – 115 MB if you are installing the source
control feature (available in the Professional edition)
„
256-color SVGA graphics adapter with 800x600 resolution
„
a CD-ROM drive
„
„
a 3.5-inch, 1.4 MB disk drive (required only for activation, therefore, it is not
required on client machines in a client-server installation)
any Windows-compatible mouse or other pointing device
We recommend a 500-MHz Pentium computer with 128MB RAM or greater
for optimal performance.
Software requirements
„
The operating system must be one of the following:
„
Microsoft Windows 98
„
Microsoft Windows 2000
„
Windows NT 4.0 with Service Pack 6 or greater.
„
Windows XP
RSLogix 500 will not run under Windows 3.1, or Windows for Workgroups
using the 32-bit extensions to these environments, versions of Windows NT
operating systems earlier than 4.0, or Windows 95® operating systems.
„
RSLogix 500 relies on RSLinx™ communication software, version 2.31.00 or
later. One copy of the RSLinx Lite software in included with the RSLogix
500 software.
2 • Getting Results with RSLogix 500™
Activation
Tip
You can find a great deal of information about how software
activation works in Appendix A, starting on page 81.
All Rockwell Software products are copy-protected, allowing only a computer
with access to an activation key the ability to run the software. The activation
key is located in an activation file, which is originally located on the Master disk
supplied with the product. The activation file contains one activation key per
product. Each activation key contains one or more licenses, depending on the
number of copies of the product you have purchased.
Tip
Store your Master disk in a safe place. If your activation becomes
damaged, the Master disk may be the only means to run your
software in an emergency.
During installation, follow the instructions that appear on the screen to move
the activation file from the Master disk to the root folder of the drive on which
you're installing the software.
Important
Do not install activation on RAID or mirrored drives. You could
lose the activation.
Installing RSLinx Lite software
If you have RSLinx
2.10 or later
installed, you do
not need to install
RSLinx Lite.
RSLinx Lite provides communication between the programmable controller
and a personal computer.
To install RSLinx Lite software:
1. Insert the RSLogix 500 CD-ROM into the CD-ROM drive. The
installation program should start automatically. If it does not, open the
installation disk with Windows Explorer and run SETUP.EXE.
2.
Click Install RSLinx Lite.
3.
Follow the directions that appear on the screen.
When the installation is complete either click Exit on the CD-ROM menu or
install RSLogix 500.
Installing RSLogix 500 • 3
Installing and activating RSLogix 500 software
Tip
While installing RSLogix 500 software, you will have the
opportunity to specify the folder into which you want to install the
software. The default folder is:
x:\Program Files\Rockwell Software\RSLogix 500 English
(or RSLogix 500 Pro English)
We recommend that you use the default folder whenever possible.
In procedures that appear throughout this document, we assume
that you used the default name. If you did not use the default name,
substitute the actual name you specified for the default name
shown.
If you intend to use Security Server with RSLogix 500,
you must have a working and configured Security Server before attempting to
run RSLogix 500. Carefully read the warnings that appear on the screen before
continuing with Security Server installation!
Security Server users:
To install and activate RSLogix 500 software, perform the following steps:
1. Insert the RSLogix 500 CD-ROM into the CD-ROM drive. The
installation program should start automatically. If it does not, open the
installation disk with Windows Explorer and run SETUP.EXE.
2.
Click Install RSLogix 500.
3.
Follow the instructions that appear on the screen.
Serial number. When asked for the serial number, you can find this
information on the box your software came in.
The default installation folder is C:\Program
Files\Rockwell Software\RSLogix 500 English. If you wish to install the
software to a different location, choose the Custom setup type. Click
Change to change the drive or folder. Installed features default to those of
the Complete setup. For additional help with the Custom setup, click the
Help button.
Changing the folder.
Activation. When prompted to install activation, insert the Master disk into
the 3.5-inch disk drive. Follow the instructions that appear on the screen
to move the activation file from the Master disk to the computer’s hard
drive.
4.
When you are finished installing and activating the software, remove the
RSLogix 500 CD-ROM and the RSLogix 500 Master disk from the drives.
Store them in a safe place.
4 • Getting Results with RSLogix 500™
Installing the source control feature
Tip
The source control feature of RSLogix 500 requires that you run the
software under Windows 2000 or Windows XP.
The source control feature is a standalone version of the RSMACC
Archive module. Do not install the source control feature if you are
using the RSMACC Archive module.
The source control feature of RSLogix 500 can help you manage your projects.
This feature creates a library of projects. Users can “check out” projects to
work on them, and check them in when their changes are complete. The source
control feature keeps track of these changes, noting who changed the projects.
You can also “roll back” a project to any previously checked-in version.
For information about configuring and using the source control feature, see
Chapter 9, Source control.
Installing the Microsoft SQL Server Desktop Engine
The source control function requires that you install the Microsoft SQL Server
Desktop Engine (MSDE). MSDE is a version of SQL Server 2000 that runs in
a standalone mode.
Important
If you already have an instance of Microsoft SQL Server 2000
installed on the computer, do not install MSDE. The source control
feature will function with SQL Server 2000.
To install MSDE:
1. Insert the RSLogix 500 CD-ROM into the CD-ROM drive. The
installation program should start automatically. If it does not, open the
installation disk with Windows Explorer and run SETUP.EXE.
2.
Click Install Source Control.
3.
Click Install SQL Server Desktop Engine. The MSDE installation
starts.
4.
The MSDE installer shows a dialog showing the progress of the
installation. When the installation completes, this dialog closes.
5.
Reboot your computer (you must reboot to start MSDE).
Installing RSLogix 500 • 5
Installing the Archive Module Extended Procedures
Component
The Archive Module Extended Procedures Component is set of procedures
used with MSDE to properly function with the source control database. To
install the Archive Module Extended Procedures component:
1. Insert the RSLogix 500 CD-ROM into the CD-ROM drive. The
installation program should start automatically. If it does not, open the
installation disk with Windows Explorer and run SETUP.EXE.
2.
Click Install Source Control.
3.
Click Install Archive Module Extended Procedures Component.
4.
Follow the on-screen instructions for installing the component.
Creating the Archive Module database
To create the Archive Module database:
1. Make sure the Archive Module Extended Procedures Component is
installed on the computer on which you want to create the Archive
Module database.
2.
Make sure MSDE is installed and running on the computer on which you
want to create the database(s). Once you have MSDE installed and
running, log on to the computer as a user with administration rights.
3.
Place the RSLogix 500 CD-ROM into the server computer. The
installation program should start automatically. If it does not, open the
installation disk with Windows Explorer and run SETUP.EXE.
4.
Click Install Source Control.
5.
Click Run Archive Module Database Creation Wizard. This starts the
Archive Database Wizard.
6.
Step 1 of the wizard sets the name of the server on which you are going to
install the database and how you will access the database.
a.
Leave the Server field blank (this tells the wizard to create the
database on your computer).
b.
Make sure Use NT authentication is set.
c.
Click Next to continue creating the database.
6 • Getting Results with RSLogix 500™
7.
Step 2 of the wizard defines the name of the database, where the database
is located on disk, and the properties of the database. The following
illustration shows how to set up this window. When you have completed
this window, click Next.
Type the name you
want to give to the
database here
Specify a file path
to where you want
to store the
database
Leave this setting
alone.
Make sure to check
this checkbox!
Set the file growth to be
by 10 percent
Set the maximum
size of the
database to be
unrestricted
Installing RSLogix 500 • 7
8.
Step 3 of the wizard defines the location and size of the database
transaction logs. The following illustration shows how to define these
logs. When you have completed this window, click Next.
Specify a file path
to where you want
to store the
database
transaction logs
Leave this setting
alone.
Make sure to check
this checkbox!
Set the file growth
to be by 10 percent
Set the maximum
size of the log file
to be unrestricted
9.
In Step 4 of the wizard, you need to identify the location of the
RSFREPROC.DLL file. This is a file placed on your computer when you
install the Archive Module Extended Procedures Component. By default,
this file is placed in the \Program Files\Rockwell Software\RSMacSvr
folder. Select the location of this file, then click Next.
10.
Click Finish to complete the wizard. The wizard creates the database.
Installing the Archive Module Administration Utility
To install the Archive Module Administration Utility:
1. Insert the RSLogix 500 CD-ROM into the CD-ROM drive. The
installation program should start automatically. If it does not, open the
installation disk with Windows Explorer and run SETUP.EXE.
2.
Click Install Source Control.
3.
Click Install Archive Module Administration Utility.
4.
Follow the on-screen instructions for installing the utility.
8 • Getting Results with RSLogix 500™
Installing the Archive Module client component
The Archive Module client component provides access to the source control
database. You must install and configure the Archive Module client
component before using the source control feature of RSLogix 500.
For information about configuring the client component, see Configuring the
source control database on page 63.
To install the Archive Module client component:
1. Log onto the computer that will run the Archive Module client
component using an Administrator account (or an account that has
Administrator privileges).
2.
Place the RSLogix 500 CD-ROM into the server computer. The
installation program should start automatically. If it does not, open the
installation disk with Windows Explorer and run SETUP.EXE.
3.
Click Install Source Control.
4.
Click Install Archive Module Client Component.
5.
Follow the on-screen instructions for installing the component.
Starting RSLogix 500 software
To start RSLogix 500 software, click Start > Programs > Rockwell Software
> RSLogix 500 > RSLogix 500.
Troubleshooting installation
If RSLogix 500 does not start up or run properly, keep the following in mind:
„ Do you have the correct version of RSLinx installed? The software requires
RSLinx version 2.31.00 or later.
„
„
Does your computer have enough memory? Check the hardware
requirements on the first page of this chapter for memory requirements.
Is the RSLogix 500 software activated? If upon attempting to run RSLogix
500 you see a message indicating that activation for RSLogix 500 is missing,
you will need to move activation to your local hard drive. Put the RSLogix
500 Master Disk in the floppy drive. Click Start, then Run. In the open field
type x:\evmove, where x is the letter of the drive containing the Master
disk. See Activation on page 81 or the online help in the EVMove utility for
more information about using software activation.
Installing RSLogix 500 • 9
10 • Getting Results with RSLogix 500™
Getting started with
RSLogix 500
Chapter
Welcome to RSLogix 500
RSLogix 500 software is a 32-bit Windows ladder logic programming package
for the SLC 500 and MicroLogix® processors. RSLogix 500 is compatible with
SLC 500 and MicroLogix programs created with any of Rockwell Software’s
programming packages.
RSLogix 500 software includes:
„ a free-form ladder editor that lets you concentrate on the application logic
instead of syntax as you write your program
„
„
„
„
„
„
„
„
„
a powerful project verifier that you use to build a list of errors you can
navigate to make corrections at your convenience
drag-and-drop editing to quickly move data table elements from one data file
to another, rungs from one subroutine or project to another, or instructions
from rung to rung within a project
an address wizard that makes entering addresses easier and reduces keying
errors.
search and replace to quickly change occurrences of a particular address or
symbol
a point-and-click interface called a project tree that lets you access all the
folders and files contained in your project
a custom data monitor to view separate data elements together and observe
interactions
trending and histogram functionality for monitoring and displaying process
data
SLC libraries for storing and retrieving portions of ladder logic for use across
any of Rockwell Software's SLC programming software products.
a compare utility that lets you graphically view project differences.
Getting started with RSLogix 500 • 11
Exploring RSLogix 500
To navigate through the various windows and toolbars in RSLogix 500 more
easily, you should understand what they contain and what functionality each
provides.
When you open a project in RSLogix 500 you can expect to see:.
Menu bar
Icon bar
Online bar
Project tree
Results pane
Status bar
Ladder view
„
„
Instruction toolbar
Menu bar - Select functionality from the menus that appear as you click each
selection on this bar.
Icon bar - The icon bar contains many functions that you will use repeatedly
as you develop and test your logic program. If you want to know what any
of the icons represent, RSLogix 500 can tell you. Move your cursor over the
icon, and floating ToolTip window appears to tell you what the icon is used
for.
„
Online bar - See at a glance the processor mode and whether you have online
edits or forces present. You can also view the communications driver and
node number.
12 • Getting Results with RSLogix 500™
„
Project tree -
„
Status bar -
„
Results pane -
„
„
This view contains all the folders and files contained in your
project. You can usually click an icon in this tree and then click the right
mouse button for a menu that applies only to the icon selected. For example,
if you click the right mouse button on a program file, you see options to
rename the program file, open the program file, hide the program file, or
reveal properties of the program file.
Look here for ongoing status information and prompts as you
use the software.
Displays the results of a Find All search or a verification
procedure. You can hide this pane or place it anywhere on your screen.
Ladder view - This is where you edit your ladder logic. You can view several
program files at the same time.
- Displays instruction mnemonics in tabbed categories.
When you click on a category tab the instruction toolbar just above it
changes to show that category of instructions. Click an instruction to insert
it in your ladder program.
Instruction toolbar
Tip
You may find it more convenient to use a floating instruction palette
from which you can select any instruction available to your
processor. Press [Alt+4] to view the palette. You can resize the
palette by dragging its lower edge.
Quick Start Steps
The following steps explain how to get running quickly with RSLogix 500.
Getting started with RSLogix 500 • 13
Step 1 • Configure a driver in RSLinx
A “light” version of
RSLinx, called “RSLinx
Lite” comes with
RSLogix 500. This
version of RSLinx
provides the
communication drivers
necessary to use
RSLogix 500. RSLinx
Lite will not, however,
provide
communications
through DDE or OPC –
those communication
modes are used with
other software
packages, such as HMI
or data acquisition
packages. To use
DDE or OPC
communication, you
will need to purchase
RSLinx.
Of course, you will want your program to run in an SLC 500 or MicroLogix
controller. That means you will need some way to connect your computer to
your controller – and you will have to tell the software how you are connected.
Communications from RSLogix 500 take place through another software
package, called RSLinx. RSLogix 500 talks to RSLinx, which in turn talks to
your communications devices.
A driver is a small piece of software that allows a computer to talk to other
systems. In this case, RSLinx uses drivers to connect your computer to your
processor. You have to tell RSLinx what driver you want to use to make that
connection.
The driver you use depends on the way your processor is physically connected
to your computer. There is a wide variety of possibile physical connections; it’s
important you know which type of connection your system is using and how
that physical connection is configured. For instance, if your processor is
connected to your network through another computer running RSLinx
Gateway, you need to use an RSLinx Gateway driver. If you are directly
connected to your processor through a 1784-KTX card, you need to use the
driver for that card.
You will also need to know the parameters of the physical connections – for
instance, if you are connecting through a 1784-KTX card, you will need to
know how your KTX card is configured, the station numbers of the processors
on your DH-485 network, and how fast your processors are communicating on
the network.
To configure a driver in RSLinx:
d. Open RSLinx by clicking Start > Programs > Rockwell Software >
RSLinx > RSLinx. RSLinx starts in a minimized mode – you will see
an RSLinx icon in your Windows System Tray. (The System Tray is a
part of the Windows Taskbar – by default, the System Tray is in the
lower right-hand corner of your screen.) Click the RSLinx icon to
open the RSLinx window.
This is the RSLinx icon
that appears in the
System Tray
e.
In RSLinx, click Communications > Configure Drivers. This
opens the Configure Drivers window.
14 • Getting Results with RSLogix 500™
f.
In the Configure Drivers window, select the driver you need to use
based on your physical connection to the processor. For example, if
you are connecting with a 1784-KTX card, select the 1784-KT/
KTX(D)/PKTX(D)/PCMK for DH+/DH-485 devices driver.
Click the down arrow to select a
driver from the Available Driver
Types list
Click Add New to add
the driver
g.
Click Add New to add the driver to the Configured Drivers list.
h.
RSLinx asks you to name the driver. RSLinx uses this name to refer
to the driver. You can use the default name, or enter a name (names
can be up to 15 characters long). Click OK.
i.
The window that appears next depends on the driver you selected.
This window is where you configure the driver. Configure the driver
to match your physical connection to the processor. If you need help
with the parameters for the driver, click the Help button on the
window.
j.
When you have finished configuring the driver, the driver appears in
the Configured Drivers list of the Configure Drivers window. Click
Close.
Getting started with RSLogix 500 • 15
k.
You need to make sure the communications driver you configured is
working properly. To do this, use the RSWho function in RSLinx.
This function shows what processors and other communications
devices are available through the driver. To display an RSWho
window, click Communications > RSWho.
l.
In the RSWho tree, open the driver you configured. You should see
the processor to which you want to connect. If you can see the
processor, the driver is configured correctly and you can proceed to
the next step.
In the RSWho
tree, open the
driver you
configured (a
Remote Devices
via Linx Gateway
driver is shown
here)
If you cannot see the processor, the driver is not configured correctly
(or some other communication problem is preventing you from
accessing the processor). Correct the problem before proceeding. See
the online help in RSLinx for information about the driver you are
using.
Step 2 • Configure system communications
There are two kinds of communications configuration in RSLogix 500.
„ System communications, which are set globally. When you set system
communications parameters, those parameters are the default for all new
projects in RSLogix 500.
„
Controller communications, which are communications parameters
specific to a given project. When you set controller communications for a
project, those settings overwrite the system communications settings for that
project. (Other new projects still use the system communications settings.)
Setting system communications parameters can save you time later. We suggest
you set the system communications parameters before creating your first
project in RSLogix 500.
To set the system communications parameters:
16 • Getting Results with RSLogix 500™
a.
From the Comms menu, click System Comms. This displays the
Communications window. (If RSLinx is not running, it will start.)
The Communications window is very much like the RSWho window
you encountered while configuring your communications driver.
b.
In the Communications window tree, open the driver you configured.
The processor you want to program should be visible. Click the
processor, then click OK.
Open the driver you
configured
Click the processor you
want to program, then
click OK
There is a great deal more that you can do from the Communications window.
See the online help for more information.
Tip
If you want to change the system communications settings, click
Comms > System Comms.
If you want to set different communications parameters for a given
project but leave the system communications settings alone, open
the properties for the project’s controller. See the online help for
RSLogix 500 for more information.
Step 3 • Create a new project or open an existing
project
Create a new project
Projects are the complete set of files associated with your program logic. To
create a new project, click File > New. RSLogix 500 prompts you for the type
of processor you will communicate with and creates a project tree for the
project. The project tree gives you access to program, data table, and database
files.
Getting started with RSLogix 500 • 17
Open an existing project
To open an existing project, click File > Open. The software displays a
window that allows you to choose a project to open.
Using the project tree
When you have opened or created a project, RSLogix 500 display’s the project’s
project tree. The project tree allows you to navigate through the various
program and data table files in your project.
The following illustration shows the parts of the project tree.
This symbol (-) means
that the folder’s contents are already visible.
Click the symbol to collapse the folder and
hide its contents.
This symbol (+) means
that the folder contains
files that are not yet
visible in the project
tree. Click the symbol
to expand the folder and
reveal its contents.
You can rename files.
If you do, the name you
give it will be shown
instead of the default.
Program files 0 and 1
are internal files and
cannot be renamed.
Tip
You can hide any program file (except system files) in the project
tree. This can be useful once you’ve completed editing a program
file and don’t want to risk accidentally selecting it and making
changes. Click on the file in the project tree and then select Hide
from its context (right-mouse) menu.
Tip
Compare project files easily by clicking Tools > Compare. Then
select the projects you want compared. You can print the resulting
graphical display or save it to a report and print it later.
18 • Getting Results with RSLogix 500™
Opening Multiple Files
To open multiple files within the same project you can split the viewing
window.
Split bar
Use your mouse to point to the split bar. The cursor turns into a double bar
with two arrows. Drag the bar up or down to its new position allowing you to
see two views of the window.
You cannot view program files from different projects with only a single
RSLogix 500 application running on your computer. You must open more
than one application to work on multiple projects at the same time. Once you
have the projects opened, you can drag-and-drop instructions and data between
them.
Step 4 • Create program and data table files
The project tree is your entry point for creating new files or accessing existing
files. To create a new file, right-click the program or data file icon and then
select New from the menu. You will be prompted for information about the
file.
Position your cursor over the
folder then click the right
mouse button and choose
New to create a new file.
Program files contain controller information, the main ladder program, and any
subroutine programs. The number of program files you can have in your
ladder project is determined by the type of controller you are using.
Data table files contain the status information associated with external I/O and
all other instructions you use in your main and subroutine ladder program files.
In addition, these files store information concerning controller operation. You
can also use the files to store recipes and look-up tables if needed.
Getting started with RSLogix 500 • 19
Step 5 • Define chassis and modules
After you have opened a project, you need to define your chassis, identify the
I/O cards and their positions in the chassis, and select a power supply for each
chassis in your configuration.
You perform these procedures in the I/O Configuration window. Access this
window by double-clicking the I/O Configuration icon in the project tree.
Then click a module in the list on the right side of the window and drag it into
the slot where you want it to reside.
From the I/O Configuration window, click the Power Supply button to
examine the loading on a rack based on the module configuration that you have
selected.
First, click a module in this list
.
Next, while still holding the mouse button,
drag the module to this side.
For more information about other tasks you can accomplish from the I/O
Configuration window refer to Chassis and module setup on page 27.
Step 6 • Enter a logic program
When you open a program file by double-clicking its icon in the project tree,
the ladder file opens in the right side of the RSLogix 500 window. Usually,
program file #2, the main program file, will open when you open a project. If
you have not entered any ladder logic in a program file, only the end rung will
show.
Click the end rung and then select the New Rung icon from the user toolbar.
To place an instruction on a rung, click the instruction’s button.
20 • Getting Results with RSLogix 500™
If there are too many
instructions on the toolbar
to see them all, use these
arrows (right and left) to
scroll through the list.
This is the “new
rung” icon. Click it
to place a new rung
on your ladder.
Each of these tabs
displays a different
category of instructions in
the toolbar. You can
customize the categories.
You can place several instructions on a rung in sequence by clicking the icons
one after another. RSLogix 500 places instructions from left to right.
RSLogix 500 supports a file-based editor. This means that you can:
„ create and/or edit multiple rungs at a time
„
enter addresses before you actually create data table files for your I/O
„
enter symbols before you have assigned addresses for them in the database
„
enter instructions without having to provide addresses until just before
validating the file
To add addresses, click an instruction then type the address in the empty field
that appears above the instruction. With RSLogix 500 you can also drag and
drop addresses from a data table file onto instructions in your ladder logic.
Tip
As you begin to enter an address (type file letter), a wizard pops up
a list of valid options. You can then make a selection by pressing
[Enter] to select the default item, or navigate the list to make a
different selection. You can also ignore the list and continue entering
your own address.
If you want to close the wizard press the [Esc] key. It can be opened
again by pressing [Insert] when an address/symbol entry field is
open.
Remember to use the right mouse button to access functions whenever
possible. The right mouse button provides you with context menus that list
editing options. And always remember that you can click F1 (or the Help
button when available) on any instruction or within any window to access help.
Keyboard users can press the [Shift + F10] key combination to access a right
mouse menu.
Getting started with RSLogix 500 • 21
Tip
You can select multiple rungs by holding down the [Ctrl] key and
clicking the left mouse button on every rung you want to select. You
can also select a range of rungs by holding down the [Shift] key and
clicking the beginning rung and ending rung.
When you select rungs in this manner, RSLogix 500 remembers the
order in which you made your selections, and pastes the rungs to the
clipboard in that order. When you paste the rungs, the order in
which you copied them is retained. For example if you click rung 11
and then [Shift] click rung 8 to copy a range of rungs, the rungs are
copied to the clipboard from rung 11 to rung 8. Pasting these rungs
will place them in the new location in this same order.
For more detailed information about the steps you follow to enter the ladder
logic including information about branching, addressing, and performing
program edits online, refer to Entering ladder logic on page 29 in this book.
Step 7 • Add documentation to your logic
instructions
You can use several method to add symbols and descriptions to addresses in
the database.
„ Modify symbols and descriptions from within a program file. To do this,
right-click the address in the instruction that you want to document, then
click Edit Symbol or Edit Description.
„
„
„
„
Modify an address’s assigned documentation in the data file. Double-click
the data file in the project tree, and then click on an address within the grid
that appears on the data file dialog. At the bottom of the dialog there are
fields where you can enter the documentation for the address.
Modify the database using the database editor. Double-click an icon in the
database folder located in the project tree.
Enter a symbol while creating new instructions, then assigning an address to
the symbol using the database symbol/description editor.
View and edit the project database using Microsoft Excel (RSLogix 500
Professional version only)
For information about the database import and export options available to you
refer to Importing or exporting the documentation database on page 41 in this book.
22 • Getting Results with RSLogix 500™
Step 8 • Validate your project
Before you can compile and download your project to a processor, you must
validate the project. Validation makes sure your project meets the basic rules
of SLC 500 or MicroLogix programming. You can validate a single program
file or you can validate your entire project at one time. To verify a file, click the
Verify File icon or click Edit > Verify File. To verify your whole project, click
the Verify Project icon or clcik Edit > Verify Project.
After you initiate a verification, the Verify Results output window displays and
gives you information about mistakes or omissions that may have occurred as
you wrote your program logic.
The results of any verification are
displayed at the bottom of the window
under the project tree. To hide this
results window after viewing it, click the
X in the upper left corner of the window.
Click on any result item to navigate to
the location of the error within the logic
program.
Getting started with RSLogix 500 • 23
Step 9 • Configure communication channel,
download and go online
Tip
If you are developing the program offline – for example, if you are
using a computer that is not located where you will use the program
– you may want to override system communication settings made in
step 1of this quick-start guide. You can override the system
communication settings this from the Controller Properties
window, Controller Communications tab. Settings made through
this method will override any driver and node settings established in
step 1, and should be completed before proceeding with step 8.
Before going online you have to define processor communication settings,
such as baud rate, and also decide certain system and protocol controls.
Depending on the type of processor that you are using and the method of
communication (direct vs. networked or modem), the complexity of this
procedure varies.
Double-click the channel configuration icon in the project tree to make these
settings. If you need information about any parameter, click Help on the
channel configuration window.
Finally, click Download > Comms to download the current offline program
into the controller. RSLogix 500 will ask if you want to go online. Click Yes
to go online.
Step 10 • Monitor data files
You can use RSLogix 500 to monitor what is happening in your data table files.
While monitoring these files you can:
„ define how your data file selection grid will display
„
change values in the data table
„
change the display radix
„
show which addresses are used in your ladder logic
„
switch between files
„
quickly jump to another address in another data table file
„
cross reference data
To monitor a data table file, click the data file icon that represents the file you
want to monitor. You can have multiple data table files opened for monitoring
at the same time. Drag each data table window into viewing position by
clicking on the title bar and moving the mouse. Release the mouse button to
place the data table window.
24 • Getting Results with RSLogix 500™
You can also choose to cascade or tile all the windows opened in your RSLogix
project by selecting the Window menu item and clicking Arrange.
Data changes made offline only affect the disk file unless the program is
restored to the processor.
Data changes made online only affect the processor file unless the program is
saved or uploaded while online to update the disk file.
For other tips about how you can create and monitor lists of related addresses
instead of accessing the data table files, refer to Monitoring data on page 47 in
this book.
Step 11 • Search and replace instructions
RSLogix 500’s Find function allows you to quickly locate instructions,
addresses, and symbols in ladder program files. You can even search for edit
zones within your logic program. If you want to automatically replace
instructions and addresses with different ones, you can use the Replace option.
Wildcards may be used in your search.
Begin any Find or Replace operation from the Search menu. Then type the
mnemonic (XIC, TON, etc.), the address (B3/4, etc.) or a combination of both
mnemonic and address (XIC B3/4) or mnemonic and symbol (XIC SYMBOL)
for the instruction you want to locate in the Find What text box.
An alternative method for searching is to click inside this box and type the numeric or symbolic address or the instruction mnemonic you want
searched.
To learn the function of any icon, point to the icon without clicking.
A ToolTip like the one shown here will appear and describe define
the function of the icon.
Tip
You can quickly navigate to a program file, rung, address, symbol or
data table file. Press [Ctrl+G] to display a Goto dialog.
Getting started with RSLogix 500 • 25
Step 12 • Print a report
You can obtain a printout of various elements of your project, such as program
files, data table files, and processor information. Select your report choices
from the File menu by selecting Report Options.
Tip
To preview the way a ladder file will print, click Preview. You can
scale up the image to make the instructions appear larger on the
printed page or scale down the image so that in cases where many
instructions are on a rung of logic, all the instructions can fit on the
printed page.
26 • Getting Results with RSLogix 500™
Chassis and module
setup
Chapter
After you have opened a project, you need to define your chassis, identify the
I/O cards and their positions in the chassis, and select a power supply for each
chassis in your configuration.
You can also display the I/O configuration for your project at any time by
double-clicking the I/O Configuration icon in the project tree.
Click this button to
call a dialog (shown)
allowing you to select
a processor from
which you want to
read the
configuration.
The I/O Configuration dialog lets you do other tasks also.
„ You can learn if the power supply you have planned to use will supply
enough power for the modules you have placed in the rack.
„
„
You can configure your analog and other specialty modules.
You can automatically read the existing I/O configuration of a processor
node on the network.
Chassis and module setup • 27
Power supply loading
These figures
represent the current
power supply loading
based on your
module configuration.
These figures
estimate the power
available before an
overload occurs.
This is where you receive advisory
messages about your power supply
selection.
Access the Power Supply Loading dialog by clicking Power Supply on the I/O
Configuration dialog. The Power Supply Loading dialog is informational only.
You cannot establish any settings on this dialog. Use it to examine the loading
on a rack based on the module configuration that you have selected.
Analog and specialty module configuration
If you have a Specialty I/O Module in your configuration, you have to enter
additional parameters so that the module can function properly in your
program. You enter this information in the Advanced I/O Configuration
window. Go to this dialog by clicking the Adv Config button on the I/O
Configuration dialog.
Remember you can always click the Help button or press [F1] on a dialog if
you are unfamiliar with any of the parameters.
Automatic I/O configuration
If you are programming an SLC 5/03™, SLC 5/04™ or SLC 5/05™
processor offline and have communications configured for the processor, you
can have the processor read the actual I/O configuration for the processor and
reflect that information on the I/O Configuration window. This can save
considerable time. To do this, click the Read I/O Config button on the I/O
Configuration dialog.
28 • Getting Results with RSLogix 500™
Entering ladder logic
Chapter
This chapter provides information that you can use to make editing your ladder
logic easier.
Tip
Shortcut methods exist for most editing functions within RSLogix
500. You can access this list of shortcuts in the online help by
searching the word “shortcuts” in the online help.
Backing up your work
Remember to back up your work as you develop your ladder logic programs.
RSLogix 500 uses two types of backup files that you can access at any time, and
provides you with an auto-recovery file in the case of a power failure. All of
these files contain the entire description database associated with the project.
„ Auto-Backup files are created automatically each time you save a project.
You can preset how many backups should be retained for any project by
entering a Number of Backups on the System Preferences tab of the System
Options dialog. Reach this tab from the Tools menu. Then click Options
and select the System Preference tab. Auto-backup files (saved as .RSS files)
have the letters BAK and a series of numbers (000 to 999) appended to the
filename. For example, an auto-backup created for project TEST.RSS might
be identified as TEST_BAK000.RSS, and a more recent backup might be
identified as TEST_BAK001.RSS.
„
Compressed Format Backup files are typically generated for archiving or
giving to another user. Compressed format backup files include the .RSS
and all database files for the project compressed into a single .RS1 file. From
the File menu click Backup Project to generate a compressed-format backup
file.
Entering ladder logic • 29
Crash Recovery
If you experience a power interruption, RSLogix 500 provides you with a recent
backup file containing current edits.
RSLogix 500 automatically creates file backups while you are working with a
project and when you save the project. This auto-generated recovery file
(internal RSS file) is only available to you the next time you open a project if
you have a system crash or your power is interrupted. After attempting to
open a project after a power failure RSLogix 500 prompts you with choices.
You can open:
„ the auto-saved file, ensuring retention of any edits made before the power
interruption.
„
the last backup that you made, when you selected Save before the power
interruption.
Tip
You must have saved or closed the file you are working on at least
one time for the auto-recovery process to work. Therefore, it is
good practice to save the file immediately after beginning a new
project. This ensures that your auto-recovery process can begin
properly.
You can set the interval time at which auto-recovery saves of your project will
occur. Do this by making a setting in the Preferences dialog. The autorecovery process ensures that you will be able to retain any work that had been
done on the file between the time of the power interruption and the last manual
save.
30 • Getting Results with RSLogix 500™
Quick entry of instructions
To make your programming tasks faster, RSLogix 500 lets you map any
available alphabetic key (A-Z) on your computer keyboard to a ladder logic
programming instruction.
Double-click the word
Free anywhere in this
list.
Then click a
mnemonic from the
drop down list to
assign it to the keyboard key and make it
a quick key.
From the View menu click Properties. Then click Quick Key Mapping to
access the mapping list. Make sure you have a program file window opened
and active or you will not be able to select Properties from the View menu.
Tip
You can jump to any rung in your project by clicking the Search
menu, and then clicking Goto. You can go to a rung in the current
program file or you can go to a rung in another program file within
the same project.Keyboard users can press the [Ctrl + G] key
combination to access the Goto Rung dialog.
Entering ladder logic • 31
Floating instruction palette
As a convenience for selecting instructions RSLogix 500 lets you display a
floating instruction palette. From the View menu click Instruction Palette or
click the palette icon.
icon
palette
You may have to resize the palette for your screen. To do this click on the
lower edge of the palette window and drag to an appropriate size.
Addressing
There are several different methods that you can use to address instructions.
You can enter an address by:
„ manually typing it in
„
dragging addresses from data files or the CDM (Custom Data Monitor)
„
using copy and paste from program to program
Tip
You can drag-and-drop rungs, branches, instructions, and addresses
from file to file or from the database to a file. To drag-and-drop,
position the mouse pointer over a file element, click and hold down
the left mouse button and drag the element to another location, and
then release the mouse button. Red boxes indicate valid locations;
these turn green when properly selected.
32 • Getting Results with RSLogix 500™
Branching
Add a branch
Click this icon on the instruction toolbar to place a branch
in your ladder logic. If your cursor is on an instruction, the
branch is placed immediately to the right of the instruction.
If your cursor is on the rung number, the branch is placed
first on the rung.
Move a branch
Click on the upper left corner of a branch to move the
entire branch structure to another location in your ladder
logic program.
Expand a branch
Click the right leg of the branch, then drag the leg to the
right or left. Valid release points will be visible on the
ladder display.
Nested branches
Place the cursor at the upper left corner of a branch leg,
click the right mouse button, and select Append New
Branch to place another branch structure within the
original branch structure.
Parallel branches
Place the cursor at the bottom left corner of a branch leg
and click the right mouse button to Extend Branch Leg Up
or Extend Branch Leg Down.
Entering ladder logic • 33
Copy branch leg
Click on the left edge of the branch leg you want to copy.
In the picture at the left this is the center leg. Then click
copy in the right mouse menu. Finally click on a rung or
instruction in your logic and click paste from the right
mouse menu to insert the rung leg
Copy entire branch structure
Select the right leg of the branch structure, then click copy
in the right mouse menu. Finally click on a rung or
instruction in your logic and click paste from the right
mouse menu to insert the rung structure.
Delete a branch
Place the cursor at any location on the branch and click the right mouse button.
Then click Delete. If you cut or delete a branch, all instructions on the branch
are also deleted.
Branching restrictions
You are limited to a maximum of 75 parallel branches.
You are limited to a maximum of 4 nested branches. (SLC 5/02 and higher and
MicroLogix).
Undo operation
The undo icon reverses your last action. You can use this icon to walk through
(and undo) your previous actions one at a time. RSLogix 500 remembers up to
200 previous actions.
If you want to undo a move operation, you must click undo two times. This is
because RSLogix 500 considers a move a series of two actions (copy and cut).
You have to let RSLogix know that you want both the copy and the cut undone.
If you click undo only one time when trying to undo a move, the move appears
to be a copy, and you will see the moved element appear at both locations.
34 • Getting Results with RSLogix 500™
Online editing
The online editing function lets you monitor and correct your ladder program
when your programming terminal is connected to a SLC 5/03, SLC 5/04 or
SLC 5/05 processor. Only one programming device at a time can perform
online edits of the program.
Online editing functions consist of inserting, replacing, and deleting rungs in an
existing ladder program while online with the processor.
Within your logic program RSLogix 500 places zone markers in the margin to
the left of the left rail. These letters signify edit zones and they indicate the type
of ladder program edit that exists in the program.
Lower case zone markers indicate edits that exist only in the computer memory.
Upper case zone markers indicate edits that exist in the processor memory.
After successfully assembling the edited rungs, the zone markers disappear.
Tip
You can search for zone markers in your project the same way you
might search for an instruction or an address. To do this, click the
Special button on the Find dialog.
Entering ladder logic • 35
Lower case zone markers
e
(Offline and online, all controllers) These rungs are currently under edit within
the computer RAM. If you are working offline, after a successful program
verification the lower-case e will disappear and the edits will be incorporated
into the program. If you are working online, after accepting the rung, the
lower-case e will be replaced by an upper-case I indicating that the rung is now
in the controller's memory and will be inserted into the program file.
i
(Online Editing, SLC 5/03, 5/04 and 5/05 controllers only) These rungs are
to be inserted into the program. Rungs marked with a lower-case i currently
exist in the computer memory and will not be entered into the controller until
the rung is accepted (right mouse button selection). After the rung is accepted,
the lower-case i is replaced by an upper-case I.
r
(Online Editing, SLC 5/03, 5/04 and 5/05 controllers only) These rungs are
to be replaced in the ladder program. Rungs marked with a lower-case r
currently exist in the computer memory and will not be entered into the
controller until the rung is accepted (right mouse button selection). An r
marked rung is always preceded by an e marked rung. After the rung is
accepted, the lower-case r will be replaced by an upper-case R.
d
(Online Editing, SLC 5/03, 5/04 and 5/05 controllers only) These rungs are
to be deleted from the ladder program. Rungs marked with a lower-case d
indicate a deletion reflected in the computer memory. This deletion will not
be reflected in the controller until the rung is accepted (right mouse button
selection), at which time it will be replaced by an upper-case D.
Upper case zone markers
I
(Online Editing, SLC 5/03, 5/04 and 5/05 controllers only) These rungs have
been inserted in the controller's logic program. You can test the edits by
selecting the Edit menu and clicking Test Edits to see how the rung works in
the online ladder program. Click Assemble Edits to finalize the rung insertion
and complete the editing process.
R
(Online Editing, SLC 5/03, 5/04 and 5/05 controllers only) These rungs have
been replaced in the controller's logic program. Rungs marked with an uppercase R continue to function in the program until you select Test Edits to see
how the new rung works in the online program. Select Assemble Edits to
finalize the replacement and complete the editing process.
D
(Online Editing, SLC 5/03, 5/04 and 5/05 controllers only) These rungs have
been deleted in the controller's logic program. Rungs marked with an uppercase D continue to function in the program until you select Test Edits to see
how the program functions without the rungs in the online program. Select
Assemble Edits to finalize the deletion and complete the editing process.
36 • Getting Results with RSLogix 500™
Online editing example
This example replaces an XIC instruction with an XIO instruction with the
same address while online.
1. Select the rung in the program that requires editing and then from the
Edit menu, select Start Rung Edits from the main menu or choose Start
Rung Edits from the right mouse menu. A duplicate of the selected rung
(preceded by the e edit zone marker) is shown in your program. This is
the rung that all edits will be performed on. The r edit zone marker
precedes the original rung (rung to be replaced). See the example below.
2.
Make the edits to the rung. The lower-case edit markers do not change
since they represent changes that only exist in the computer memory;
these changes are not yet a part of the online program in the controller.
(At this step you can click Cancel Rung Edits to cancel the edits you have
made to the rung.)
3.
Select Accept Rung. This changes the edit zone markers and places both
rungs in the controller memory. The upper-case I represents the rung
that has been inserted into the online program. The upper-case R
represents the online rung that is to be replaced. At this time the R rung
is still operating in the program.
4.
Select Test Edits. The I-marked rung takes precedence. The program in
the controller will operate with the inserted rung, and the R-marked rung
will be ignored. (Alternately you can click Cancel Edits to cancel the
accepted I-marked rung and retain the originally programmed R-marked
rung instead.)
Entering ladder logic • 37
5.
Select Assemble Edits. All edit zone markers disappear and the edits are
incorporated into the online program. There is no Undo option after
online edits have been assembled.
Going from online to offline with rungs under edit removes the RAM
online edits. Make sure you have accepted edits before going offline if you
want any changes retained in the processor.
Online editing restrictions
Your programming terminal must be connected to a SLC 5/03, SLC 5/04 or
SLC 5/05 processor. During an online editing session you cannot:
„ resize data table files
„ create or delete program files
„ change program file protection
„ change index across file boundaries flag
„ reconfigure the I/O
„ select force protection
ASCII editing
ASCII Editing is a function of RSLogix 500 that lets you modify instructions
using ASCII instruction mnemonics instead of having to modify instructions
using the ladder editor.
A quick way to call the ASCII Editor is to double-click a rung number in the
left margin. If you double-click a rung with logic already on it, you will see the
mnemonics for the existing instructions and can modify or add to them. If you
double-click an empty rung, you get an empty editing box into which you can
type the mnemonics that represent the logic you want placed on the rung.
Tip
Another quick method to call the ASCII text editor is to click the
rung number and then press the forward slash key (/) on your
keyboard.
Configuring interrupts
Use interrupts to interrupt the scan of the main program to accomplish a
certain task. Programming requires you to enter essential criteria for the
interrupt to function properly. Depending on the processor you are using, this
criteria is entered into the Status file by accessing it directly (All SLC processors
and MicroLogix 1000 processors) or by entering the appropriate data in the
Function File utility (MicroLogix 1200 and 1500 processors only).
38 • Getting Results with RSLogix 500™
Selectable Timed Interrupt
Use the selectable timed interrupt (STI) function to interrupt the scan of the
main program file automatically, on a periodic basis, in order to scan a specified
subroutine file. You can specify the time interval when your selectable timed
interrupt routine will execute.
Processor Type:
Action:
All SLC and ML
1000
Select a program file for the STI by double-clicking the S2
data file icon in the project tree. Then click the STI tab and
enter the information needed to define the STI. Press the
Help button if you need more information.
ML1200 and
ML1500
Select a program file for the STI by double-clicking the
Function Files icon in the project tree. Then click the STI
tab and enter the information needed to define the STI.
Press the Help button if you need more information.
Discrete Input Interrupt
Use the Discrete Input Interrupt (DII) for high-speed processing applications
or any application that needs to respond to an event quickly. This function
allows the processor to execute a ladder subroutine when the input bit pattern
of a discrete I/O card matches a compare value that you programmed.
Processor Type:
Action:
All SLC
Double-click the S2 data file icon in the project tree. Then
click the DII tab and enter the information needed to define
the DII. Press the Help button if you need more information.
ML1000 ML1200
ML1500
Unavailable with these processors.
Entering ladder logic • 39
40 • Getting Results with RSLogix 500™
Importing or exporting
the documentation
database
Chapter
Introduction
The import and export utilities are available from the Tools menu by clicking
Database. Use the import functionality in RSLogix 500 when you want to apply
documentation that already exists to a project you are currently developing in
RSLogix 500. Use the export functionality in RSLogix 500 to make the
database documentation that is part of your current RSLogix 500 project
available to other projects.
Tip
RSView products can read the documentation database directly
from your RSLogix 500 projects – there is no need to export the
database when using RSView.
Import database
You can apply documentation to newly created logic files by importing existing
database documentation. The existing documentation might come from:
„ projects developed using Rockwell Software's DOS-based AI or APS
programming software
„
another project developed using RSLogix 500
„
a spreadsheet application, like Microsoft Excel™ (saved as a .CSV file)
„
an ASCII text file
Sometimes when you import a documentation database, there may be
conflicting entries in the import file and the database. This is called a collision.
Before you begin any import you can select if you want the imported database
instance or the current database instance discarded if collisions occur.
Importing or exporting the documentation database • 41
A.I. project documentation database
Choose the Native Import option in the Database menu to import database
documentation consisting of:
„ address symbols and descriptions (.DSC files)
„
page title and rung descriptions (.RPD files)
APS project documentation database
Choose the Native Import option in the Database menu to import database
documentation consisting of:
„ address symbols and descriptions
„
page title and rung descriptions
„
instruction comments
By default the file type selected for import is a .OP$ file. The .OP$ file is the
database control file. It references individual database files (for example the
symbol/description file or the page title/rung description file) that reside in the
same folder as the .OP$ file. After an import completes, RSLogix 500 creates
a log file that informs you which database files successfully imported and which
database files contained errors and could not successfully be imported.
RSLogix 500 documentation database
Choose the Native Import option in the Database menu to import database
documentation consisting of:
„ address symbols and descriptions
„
page title and rung descriptions
„
instruction comments
„
symbol groups
By default the file type selected for import is a .CTD file. The .CTD file is the
database control file. It references individual database files (for example the
symbol/description file or the page title/rung description file) that reside in the
same folder as the .CTD file. After an import completes, RSLogix 500 creates
a log file that informs you which database files successfully imported and which
database files contained errors and could not successfully be imported. For a
complete list of RSLogix 500 file extensions for individual database
documentation refer to the online help and search "file extensions."
CSV (Comma Separated Values) file
Choose the ASCII Import option in the Database menu to import database
documentation contained in a .CSV file and consisting of:
42 • Getting Results with RSLogix 500™
„
address symbols and descriptions
„
instruction comments
„
symbol groups
For an example of a .CSV file, refer to the online help and search "CSV format
for import/export."
ASCII delimited text file
You can import documentation files that were created using RSLogix 500
software or AI software and exported and saved as ASCII delimited files.
ASCII delimited means that the fields for each RSLogix 500 database record
are enclosed in quote marks and separated by commas.
Choose the ASCII Import option in the Database menu to import database
documentation contained in an ASCII delimited text file. Choose from:
„ address symbols and descriptions (.EAS files)
„
page title and rung descriptions (.ERP files)
„
instruction comments (.EIC files)
„
symbol groups (.ESG files)
Users can specify any extension instead of the default extension for each file
type (shown above in parenthesis) when using Rockwell Software's AI or
RSLogix 500 software.
An example of each of the above files can be found in the "ASCII Export"
section of this manual.
Export database
Use the export functionality in RSLogix 500 to make the database
documentation that is part of your current RSLogix 500 project available to
other projects.
You can select the display format for descriptions in the exported file. Choose
"treat descriptions as five, 15-character lines of text" if you are exporting a
database that will be used by Rockwell Software's AI or APS programming
packages.
Importing or exporting the documentation database • 43
You can export documentation to the following output formats:
„ ASCII delimited RS500 format
„
ASCII delimited AI format
„
ASCII delimited APS format
„
a comma separated value file (.CSV file)
After it has been exported, you can edit the ASCII file with a text editor, or load
the file into another database.
When you export database documentation to AI or APS ASCII delimited
format, the symbols, descriptions, and instruction comments may be truncated
due to size restrictions imposed by the AI/APS databases. This may result in
conflicts in the exported data.
RS500 ASCII delimited text file examples
The examples in this section show how the documentation would be
represented in an exported ASCII text file, using the RS500 output format.
Each field in a line of ASCII text is enclosed by quotes and separated by a
comma.
Address symbols and descriptions (.EAS files)
"B30","0","SYMBOL","description","","","","","0","","","0","GROUP_NAME"
ASCII Field #
Maximum Length
Contents
1
39 characters
Address
2
--
Scope (0=global, 2-255=local program file #)
3
20 characters
Symbol
4
20 characters
Description line 1
5
20 characters
Description line 2
6
20 characters
Description line 3
7
20 characters
Description line 4
8
20 characters
Description line 5
9
12 characters
Device code (always 0 for addresses that are
not real I/O)
10
9 characters
Device description above
11
9 characters
Device description below
12
--
Disable xref flag, (0=enabled, 1=disabled)
13
20 characters
Symbol group name
44 • Getting Results with RSLogix 500™
Page title and rung descriptions (.ERP files)
"RUNG000002-000002","page title","rung comment\"
ASCII Field #
Maximum Length
Contents
1
39 characters
Data table address or rung identifier
2
--
Page title
3
20 characters
Rung description
Instruction comments (.EIC files)
"B3/0","XIC","ins comment","","","",""
ASCII Field #
Maximum Length
Contents
1
39 characters
Address
2
3 characters
Instruction type
3
20 characters
Comment line 1
4
20 characters
Comment line 2
5
20 characters
Comment line 3
6
20 characters
Comment line 4
7
20 characters
Comment line 5
Symbol groups (.ESG files)
"GROUP_NAME","description"
ASCII Field #
Maximum Length
Contents
1
20 characters
Symbol group name
2
80 characters
Symbol group description
A.I. ASCII delimited text file examples
These examples show how a line might appear in an ASCII text file exported
using the AI output format. Each field in a line of ASCII text is enclosed by
quotes and separated by a comma.
Address symbols and descriptions (.EAS files)
"B3/0","0","SYMBOL","description","","","","","0","","","0"
The field breakdown of AI ASCII delimited text is the same as shown for
RS500 ASCII output format, except the symbol and description fields are
limited to 15 characters and there is no symbol group field.
Importing or exporting the documentation database • 45
Page title and rung descriptions (.ERP files)
"RUNG002-0002","page title","rung comment\"
The field breakdown of AI ASCII delimited text is the same as shown for
RS500 ASCII output format.
APS ASCII delimited text file
APS documentation database files saved to ASCII text format contain
keywords. Keywords tell the software whether the information immediately
following the keyword is a rung comment, an instruction comment, an address
comment, or a symbol. Symbol and address comment examples are shown
below.
SYM
B3/0
SYMBOL
AC
B3/0
“descriptio”
Refer to your APS programming manual for a complete list of keywords and
an explanation of how an APS ASCII text file is built.
CSV format
Search "CSV format for import/export" in the RSLogix 500 online help for
complete details.
46 • Getting Results with RSLogix 500™
Monitoring data
Chapter
Introduction
RSLogix 500 provides you with several customized methods for monitoring
data in your data table files.
„ Multipoint Monitor
„
Custom Data Monitor
„
Custom Graphical Monitor (RSLogix Professional version only)
„
Recipe Monitor
„
Histograms
„
Trending
„
Data Logging (MicroLogix 1500LRP only)
„
Cross Reference Report
The Multipoint Monitor and Custom Data Monitor methods let you compose
lists of addresses that you monitor frequently, or lists of addresses with
interrelated functionality, so that you can view, document, protect or even
force the changing data values from a single source file.
The Custom Graphical Monitor interprets the Custom Data Monitor
graphically with easily customized buttons, sliders, gauges and charts.
The Recipe Monitor is a variation of the Custom Data Monitor used specifically
for monitoring groups of related indirect addresses with a common index.
When you are online, you can use histograms and trends to see how your
program is behaving over time, by examining bits as the program runs in the
SLC controller. A trend logs the data for more than one address (typically
related) over a period of time. A histogram logs the data contained in a single
address over a period of time.
The data logging feature lets you use ladder logic to enable recording data for
predefined sets of addresses. Your data can be date and time stamped.
The Cross Reference report lists every occurrence of all logical addresses in
your project.
Monitoring data • 47
Multipoint Monitor
This is only available with MicroLogix 1000, SLC 5/03 - OS302, SLC 5/04 OS401 and OS410, and SLC 5/05 controllers. The Multipoint Monitor
function can only be used to monitor bit addresses. If you want to monitor
word addresses as well as bit addresses, use the Custom Data Monitor.
Bit addresses in a multipoint list can come from any data table file. They do
not have to be from the same data table file.
You can use a multipoint list to:
„ change the on/off state of bits
„
set and clear forces on I/O points
„
define separate descriptions for on and off state
„
write protect a bit
To access the Multipoint Monitor feature, double-click the Multipoint Monitor
icon located in the project tree.
You can provide
separate
descriptions (up to
16 characters) for
the on- and offstate of a bit.
Use only bit addresses in a multipoint monitor list.
The offline multipoint list is stored in the project file. It is not part of the
processor image. The online multipoint list is stored in the processor memory
and is, therefore, cleared whenever the processor memory is cleared.
When using the MicroLogix controller, descriptions are always stored in
the.RSS file. With the SLC 5/04 and SLC 5/05 controllers the descriptions are
stored in the processor.
Forces
To monitor forces, double-click the input or output force file in the project
tree.
Caution
All force functions can result in sudden machine movement,
possibly injuring personnel or causing equipment damage. USE
EXTREME CAUTION WHEN USING FORCES!
48 • Getting Results with RSLogix 500™
You can also use the Forces dialog to install and enable or disable forces while
you are monitoring your file offline, or in any processor mode while monitoring
your file online. Use the right-click menu on a bit in the Forces dialog to force
the bit on or off. For more information about forcing, refer to the online help.
Custom Data Monitor (CDM)
This is available with all controllers. The Custom Data Monitor function can
be used to monitor bit addresses and word addresses.
Addresses in a custom data monitor list can come from any data table file. They
do not have to be from the same data table file.
Features of the custom data monitor include:
„ CDM lists can contain bit addresses or word addresses.
„
CDM lists can contain ASCII comments to help you clarify bit listings.
„
You can define up to 255 (CDM) lists per project (0-254, inclusive).
„
The CDM name is limited to 20 characters.
„
The CDM description is limited to 59 characters.
„
You can click and drag addresses from the data tables to the CDM file.
„
You can use the [Ctrl] and [Shift] accelerator keys to drag more than one
address at a time from the data tables.
By default an untitled CDM file (#0) is included in your
project. Rename this file when you add your addresses.
To access the Custom Data Monitor feature, double-click the CDM file icon
located in the project tree.
Custom Graphical Monitor
This feature is only available in the RSLogix 500 Professional version.
The Custom Graphical Monitor provides the data monitoring of a Custom
Data Monitor, but in an easy to interpret graphical representation. The Custom
Graphical Monitor is a form on which you can place ActiveX controls for
buttons, sliders, gauges and charts as well as text and imported images. As is
typical of ActiveX controls, you place and configure controls with the form in
Design mode and switch to Run mode to activate the controls.
Monitoring data • 49
To access the Custom Graphical Monitor feature, double-click the CGM folder
located in the project tree.
To create a new Custom Graphical Monitor file, rightclick the Custom Graphical Monitors folder and
select New.
By default an untitled Custom Graphical Monitor file
(#0) is included in your project. Right-click and select
Properties to rename this file.
Drag an address from the ladder or data table to a control.
Click one of these buttons to
add text, buttons, sliders,
gauges, images, or graphs
to the form.
Click here to toggle
between Run and
Design mode.
Displays the
current mode.
Right-click a control and select Properties to change
colors, define ranges, and set other options.
Recipe Monitor
The Recipe Monitor is a variation of the Custom Data Monitor. The Recipe
Monitor is used specifically for monitoring groups of related indirect addresses
with a common index.
Many SLC and MicroLogix projects contain data tables in which each element
is relevant for a different mode of operation. When these data tables are
grouped such that element 1 of each file corresponds to mode 1 of the
assembly line used to make product 1, this is referred to as a “recipe.” The
easiest way to keep track of recipes is to use a common reference address with
indirect addresses to each of the related data files. The Recipe Monitor provides
an easy and intuitive interface for this type of application.
50 • Getting Results with RSLogix 500™
To access the Recipe Monitor feature, double-click the Recipe folder located in
the project tree.
To create a new Recipe Monitor file, right-click the
Recipe Monitors folder and select New.
By default an untitled Recipe Monitor file (#0) is
included in your project. Right-click and select
Properties to rename this file.
Drag a data file from the
project tree to the Recipe
Monitor. Note that an
asterisk (*) represents the
indexed part of the
address. If you type in or
drag an address from the
ladder, be sure to use an
asterisk to indicate the
indexed part.
Trends
A Trend logs the data for more than one address (typically related) over a
period of time. Contrast this with a histogram which logs the data contained in
a single address over a period of time.
This option provides the features of the RSTrendX Viewer plus remote
trending capability. The RSTrendX Viewer is an ActiveX control for displaying
process data in a trend or strip chart recorder format. It is based on the Viewer
display in the RSTrend Data Acquisition and Trending software.
To create a Trend chart right-click the Trends folder in the project tree and
select New. Trends are saved with the project. Logged data is not retained. You
can create a trend configuration while offline or online. You must be online to
trend data.
Histograms
Use the histogram functionality in RSLogix 500 to get information about how
an address's data value changes over time.
You must be online with the SLC controller to access the histogram function.
From the Comms menu, click Histogram to display the Histogram dialog.
Monitoring data • 51
By clicking Start on this dialog, the histogram function sends a message to the
SLC controller to begin logging data. Each time the address value changes, the
controller stores the value for the address in a histogram buffer, logging both
the new value and the time interval between value changes. This data is
represented in the top portion of the histogram display window.
If you frequently log certain data, you can save the configuration and simply
load it without having to enter new parameters each time. Use Save and Load
(accessible from the right mouse menu) for this functionality.
Use this drop-down list box
to select a time base for the
histogram (in seconds).
If you don’t see data values
changing, it is possible that
your time base is incorrect
for the addresses you are
monitoring.
Data Logging (MicroLogix 1500LRP only)
Use the data logging feature to define and edit data sets for later retrieval by a
communication device. The data is retentive in the controller through power
cycles.
52 • Getting Results with RSLogix 500™
Access data logging from the project tree by clicking the Configuration icon in
the Data Logging folder. Then right-click on Data Log Configuration and
select New from the context menu
This is the number of samples
that you would like for each
record retained. When this limit is
reached and a new sample is
recorded the oldest record
is dumped from the record.
By default the separator
character is a space.
Although it may look like
there is nothing in this box,
there is actually a space
character.
Type an address here and then
click Accept or press [Enter] to
place it in the current address list.
Enable data logging for any queue when the DLG instruction in your ladder
logic designating that queue goes from False to True.
Cross Reference
A Cross Reference report lists all logical addresses in your project and gives the
location of every occurrence of each address. The report includes the following
data: address, symbol, instruction mnemonic, file # (and name), and rung #.
You can sort the Cross Reference report by symbol or by address.
As an alternative to a Cross Reference report, you can choose to display cross
reference information right on the ladder view. To use this feature, select View
> Properties, and click the Address Display tab. Make sure either or both
check boxes are checked in the Cross Reference Display area of the dialog.
Tip
You can disable cross references to get online faster. Select Tools >
Options. Click the XRef/Address Wizard tab and uncheck the
Enable Cross Reference Online box.
Monitoring data • 53
54 • Getting Results with RSLogix 500™
Saving and loading SLC
libraries
Chapter
Introduction
SLC library files are ASCII text files of the processor memory that contain the
ladder logic, data table file, and force tables. By exporting (saving to file) and
importing (loading into a new project) these SLC files, you can reuse existing
work. SLC files can be opened in any ASCII text editor and modified for use
in your projects.
Things to remember about library files
„ Only verified project data can be saved to a .SLC file.
„
„
„
„
„
Exported SLC libraries limit symbols to 15 characters. If you have a project
file with database symbols that are 20 characters in length, exporting the
project to a SLC library will truncate the symbols to 15 characters maximum.
Graphics characters are not allowed.
The file name of the ASCII file can contain up to eight characters consisting
of (A-Z, 0-9, or the underscore character).
The file extension of the ASCII processor memory file must be SLC.
The text editor you use with an ASCII text file must produce only printable
ASCII characters, with no control characters or hidden characters.
Tip
You can examine any error messages resulting after an import or
export operation by examining the .LOG file. This file is stored in
the folder named on the Preferences tab accessed by clicking the
Tools menu and selecting Options. You can change this default
folder.
Exporting libraries
You can save entire projects or partial libraries. To save a partial library, select
the rungs you want to save in the library. If you select no rungs a complete save
occurs. Then from the right mouse menu click Copy to SLC Library, and after
supplying the path and filename, click Save.
Saving and loading SLC libraries • 55
If you choose Partial Save, make sure
you selected the rungs before displaying
this window.
Checking Annotate Library places additional information
in the SLC file about the rungs’ position in the original
program. This information is used for troubleshooting a
library file, and can help you if you intend to manually edit
the .SLC file in a text editor.
You can place a description in the SLC file by typing the description in the
Library Description field. This description appears when you import the
library.
Importing libraries
To import a library file, open the project into which you want to load the
library. Then from the right mouse menu click Paste from SLC Library.
If you are loading a complete program image into an existing project, data table
values in the library will overwrite values in the base program, and incoming
rungs will be appended to existing program files.
56 • Getting Results with RSLogix 500™
If you are loading a partial library, select the rung in your program that you want
the library rungs to precede. The library rungs will always be placed before the
rung you select. Data table values from the library will overwrite existing data
table values for those addresses already present in the base project
Choose the indexed mode and then click the Edit Index button if
you want to display a Fixup table from which you can adjust the
addresses in the imported library so that there are no conflicts with
the addresses in the base program.
If you change base address I:000/0 to I:016/00 (in the
Fixup column) and press [Enter], the addresses that
are relative to I:000/00 change to follow the change in
the base. If there were more addresses relative to base
address I:000/0, each one would be offset by the
change applied to the octal base address. Relative
addresses include all the addresses in the list of the
same data file up to the next Base address.
You can change the type address.
Double-click and select Base,
Relative, or Global from the dropdown listbox. An address set to
Global is not affected by indexing
to a preceding base address.
Saving and loading SLC libraries • 57
58 • Getting Results with RSLogix 500™
Chapter
Features in RSLogix 500
Professional
RSLogix 500 comes in two editions: a Standard edition that provides basic
ladder logic editing functions, and a Professional edition that provides
additional functions to expand your automation solutions and make editing
ladder logic simpler. This chapter briefly describes the features included in
RSLogix 500 Professional.
Microsoft® Visual Basic for Applications® support
RSLogix 500 Professional allows you to expand your automation solutions
through Microsoft Visual Basic for Applications (VBA). VBA allows you add
and edit Visual Basic code within the RSLogix 500 development environment.
RSLogix 500 Professional includes an object model that you can access through
VBA. VBA code created through RSLogix 500 Professional is stored in your
projects’ .RSP files.
You can run VBA code with RSLogix 500 Standard – to create or edit VBA
code you must use RSLogix 500 Professional.
See the manual titled RSLogix Automation Interface Reference Manual for more
information about using VBA in your automation solutions. This manual is
included with RSLogix 500 Professional.
Source Control
RSLogix 500 Professional has a source control feature that you can use to help
you maintain version control on your projects.
For information about installing the source control feature, see Installing the
source control feature on page 5.
For information about using source control, see Source control on page 63.
Custom Graphical Monitor
The Custom Graphical Monitor provides graphical data monitoring for your
projects. In the Custom Graphical Monitor, you can place graphical buttons,
sliders, gauges, charts, text, and imported images.
Features in RSLogix 500 Professional • 59
See Custom Graphical Monitor on page 49 for more information about using this
feature.
Editing project databases using Microsoft® Excel®
RSLogix 500 Professional allows you to view and edit project databases with
Microsoft Excel software. Microsoft Excel 97 (and later versions) comes with
an ActiveX control that RSLogix 500 can use. You must have Microsoft Excel
installed on the same computer as RSLogix 500 Professional to use this feature.
The Microsoft Excel ActiveX control gives you the powerful editing features
of Excel, such as search/replace, and modifying multiple records at the same
time. Using this control minimizes or eliminates the need for database import/
export operations.
To access the Excel editor, click Tools > Database > Edit Using Excel. The
Address/Symbol Editor will open using Excel as the editing tool.
Pressing [F1] will access the Microsoft Excel Help system.
When the Excel editor is displayed and has focus, RSLogix 500 displays the
Excel menus and toolbars. You can also access Excel functions by using the
right-mouse button menus while working in the editor.
Keep the following information in mind when using Excel to edit the database:
„ When you open the Excel editor, the entire contents of the Address/Symbol
database is automatically loaded into the control.
„
„
„
„
„
Changes made within the Excel editor will not be applied to the Address/
Symbol database until you click Apply or OK. When you apply changes, the
entire Address/Symbol database will be overwritten with the contents of the
Excel editor.
Empty rows within the Excel editor are be ignored when applying the
contents to the database.
If records are added, removed, or moved within the Excel editor, they will
be sorted when the contents are applied to the Address/Symbol database.
When you click Apply or OK, all legal records will be written to the
Address/Symbol database. Illegal records (records containing illegal
characters, fields with too many characters, duplicate records, etc.) will not
be written to the database.
Any errors or illegal records encountered when applying the contents of the
Excel editor to the database will be logged and displayed in a separate
window. You have the option of saving this information to a file.
60 • Getting Results with RSLogix 500™
„
„
„
If you close the Excel editor without clicking Apply or OK (by clicking
Cancel), the editor closes without overwriting the database. Changes made
in the editor since the last Update Changes operation will be lost.
The Excel editor is limited to approximately 64,000 rows per sheet.
Databases with more than 50,000 records will have their contents spanned
to multiple Excel sheets.
All standard features of the Excel Active X control will be available to
manipulate the database. When the Excel editor has focus, these features are
accessed through the menus or toolbars or from the right-mouse menu.
Remember, you can always get help with the Excel editor by pressing the
[F1] key.
Logic Trace
The Logic Trace feature lets you navigate through your ladder logic like using
a Web browser. As you move your cursor through a ladder logic project, the
Logic Trace feature keeps track of where you have been. You can then use the
Logic Trace toolbar to navigate back to previous positions, or from earlier
positions to later ones.
You can turn the logic trace toolbar on or off by clicking View > Toolbars and
selecting or deselecting the Logic Trace toolbar.
Back button
Back menu
Forward button
Forward menu
How logic trace works
As you move your cursor through the ladder logic, the software records the
positions of your cursor. When no back or forward history is available, the logic
trace arrow buttons are disabled (grayed out).
Features in RSLogix 500 Professional • 61
Actions that create a “back” navigation history include cross reference
navigation, program file display change, clicking your mouse on ladder logic
rung/instruction elements, searching ladder logic, using the Goto Rung
function, using dot commands, etc. Using the keyboard arrow keys will not
generate a navigation history.
Actions that create a “forward” navigation history are limited to clicking an
enabled “back” toolbar button or selecting a location from the “back” pull
down menu.
When you click a “back” button, the cursor will move to the previous location
in the navigation history. Once you have moved backward in the navigation
history, clicking the “forward” button will move the cursor forward through
your navigation history.
The pull down menus are limited to a maximum of 10 entries. Each entry lists
a rung/instruction location. While the menus are limited to showing a
maximum of 10 entries, the arrows allow you to go much farther back.
If you delete an instruction or rung that is in the history, that item is removed
from the logic trace navigation history. If you edit a rung or instruction that is
in the navigation history, it remains in the history.
62 • Getting Results with RSLogix 500™
Chapter
Source control
About source control
Tip
If you are using RSLogix 500 Standard, the source control feature is
not available in the software.
If you are using RSLogix 500 Professional, you can install the source
control features. See Installing the source control feature on page 5 for
information about installing the feature. The source control feature
requires that you run the software under Window 2000 or Windows
XP.
Keeping track of changes to your projects can be a challenge. The source
control system of RSLogix 500 Professional can help you manage changes to
your projects.
The source control system acts as a project library, allowing you to “check out”
and “check in” your project files. Project files are stored in a database. When
you want to work on a project that is stored in the database, you check out the
project. When you are finished working on it, you check it back into the
database. When you check a project in or out of the Archive database, the
database records that you have done so. You can also record comments when
you check out or check in a project.
If you want a copy of the latest version of a project without checking it out (or
if it has been checked out by someone else), you can “get” the project file.
When you get a project, the system places a read-only version of the project
onto your computer.
Configuring the source control database
You must configure the source control database to allow users to access it. Use
the Archive Administration Utility to set permissions for the database.
Source control • 63
Registering the source control database with the
administration utility
Registering the source control database lets the administration utility know
what database it is supposed to administer. To register the source control
database with the administration utility:
1. Click Start > Programs > Rockwell Software > RSMACC Server >
RSMACC Archive Administration Utility. This starts the Archive
Administration Utility.
2.
In the utility’s window, click RSMACC Archive Module Databases.
3.
Click Action > New > New Database Registration. This displays the
New Server Registration window.
4.
In the New Server Registration window, choose your computer from the
Server drop-down list. Type the name of the Archive database in the
Database field.
5.
Click OK. The Archive database appears in the navigation tree. Rightclick the database, then click Connect. If you get an error, it is likely that
you misspelled the name of the Archive database. In this case, right-click
the database, select Properties, and re-enter the database name.
Creating database users
To create a database user with the Archive Administration Utility:
1. Log into the computer using an account that has administrative privileges.
2.
Click Start > Programs > Rockwell Software > RSMACC Server >
RSMACC Archive Administration Utility.
3.
Open the Archive database.
4.
Click the Users folder. The utility displays a list of the currently defined
users for the database.
5.
Right-click the Users folder, then click New Login. The utility displays
the Add new database login window.
6.
In the Username field, enter the name of the user or user group you want
to add. You can browse for the name by clicking the browse button next
to the field.
7.
In the Domain field, enter the domain that authenticates the user or
group (if you browsed for the user name, this field fills automatically).
8.
Select the database role for the user. Normal user means that the user or
group cannot modify folder privileges. User can modify folder rights
means that the user or group can change folder access rights for other
users (the user or group has administrative access to the database).
64 • Getting Results with RSLogix 500™
Assigning folder privileges to users
To assign folder privileges with the Archive Module database utility:
1. Log into the computer using an account that has administrative privileges.
2.
Click Start > Programs > Rockwell Software > RSMACC Server >
RSMACC Archive Administration Utility.
3.
Open the Archive Module database.
4.
Click the Folder Rights folder.
5.
When you click the Folder Rights folder, the display shows the folders
available in the archive (this should be only the File Repository folder at
first). Click the File Repository folder. To the right of this folder, you
will see a set of users and checkboxes. The checkboxes are privilege
settings for the folder.
1. Click the
Folder Rights
folder
2. Click the folder for
which you want to set
privileges
3. Set the
privileges for
the folder
Source control • 65
6.
Click the checkboxes corresponding to the permissions you want to grant
to the users.
This checkbox:
Means:
I
Inherit permissions from the parent folder. The top level
folder (File Repository) cannot have this setting. If you
choose this setting for a folder, no other setting is available
for that folder. By default, any folder you create inherits
its permissions from its parent folder.
R
Read. The user can read files contained in the folder.
C
Check in/Check out. The user can check files into and out
of the folder. This setting implies the R permission.
A
Add/Remove/Delete. The user can add files to and delete
files from the archive. This setting implies the R and C
permissions.
D
Destroy. The user can destroy files (deleting them does
not remove them permanently from the archive). This
setting implies the R, C, and A permissions.
Registering the source control database with
RSLogix 500
Before you can use the source control functions of RSLogix 500 Professional,
you must register the source control database with RSLogix 500. Registration
lets RSLogix 500 know how to access the archive.
To register the database:
1. In RSLogix 500, click Tools > Source Control Utility. This opens the
Archive module tool.
2.
In the Archive tool, click Database > Server Registrations.
3.
The Manage Server Registrations window opens. Click Add New.
4.
In the Server Location field, enter the computer name. You can browse
for the name by clicking the down arrow button next to the field.
5.
In the Database Name field, enter the name of the Archive database.
66 • Getting Results with RSLogix 500™
6.
Click Accept. This registers the server.
1. Click Add New.
2. Enter or select the
database server that
hosts the Archive
database.
4. Click
Accept.
3. Enter the name of the
Archive database.
Adding a project to the archive
When you want to perform source control on an RSLogix 500 project, you
must add it to the source control archive. Once it is added to the archive, you
can then track the modifications people make to it.
To add a project to the archive:
1. Open the project you want to store in the archive.
2.
Click File > Source Control > Add Project to Source Database. The
software logs into the default Archive database and displays the Select
folder in which to add file window. This window allows you to select or
create a folder into which you want to save the project.
3.
If you want to store the project in a previously created folder, double-click
the folder to open it, then click OK. If you want to create a new folder
into which to store the project, click Create New Folder. (If you cannot
create a new folder or store a new project, it is because you do not have
the access rights necessary to do so. See your RSMACC administrator for
more information.)
Source control • 67
“Getting” and checking out projects
There are two ways to open a project that is stored in the Archive database.
You can get the project, which opens a read-only copy of the project for
viewing, or you can check out the project, which opens a writable copy of the
project so you can modify it. Only one user can check out a project at one time.
If you check out a project, no one else can check it out until you check it in.
Other people can get the project while you have a project checked out, but no
one else can modify it.
To get or check out a project:
1. In RSLogix 500, click File > Open. This displays the Open/Import
SLC500 Program window.
2.
In this window, click the Source Control tab. This displays the source
control options for getting or checking out projects.
3.
Select the project you want to check out.
If nothing appears in the Open/Import SLC500 Program window, there
are two possibilities:
a.
The Archive database is not registered. The database much be
registereed before you can use the source control features of RSLogix
500. See See Registering the source control database with RSLogix 500 on
page 66 for more information.
b.
You need to log onto the Archive database. click the Login icon to
select an Archive database. (The Archive database must be registered
before you can select it.) The Login icon looks like this:
The Login icon
4.
Choose whether you want to get or check out the project by clicking the
Get or Check Out buttons.
68 • Getting Results with RSLogix 500™
5.
Click OK.
2. Select the project you want to
get or check out.
4. Click OK.
3. Select whether you want to get
or check out the project.
1. Click the Source
Control tab.
6.
The Get window or Check Out window opens (depending on whether
you chose to get or check out the project).
a.
Enter the path to which you want to get or check out the project in
the To field.
Source control • 69
b.
If you are getting the project, you can make the project writable by
checking the Make Writable box. If you are checking out the
project, you can check it out without copying the project to your
computer by checking the Don’t get local copy box.
Tip
Check the Don’t get local copy box if you want to keep other users
from checking out a project or if you have performed a get on a
project, made changes, and want to save the changes you made in the
archive.
If you choose to check out a project without getting a local copy, and
you do not already have a local copy of the project on your
computer, RSLogix 500 creates a new project with the same name as
the project you checked out.
c.
In the Action comments field, enter a comment regarding what you
intend to do with the project.
d.
Click OK. The project is copied to your computer (unless you
checked out a project without getting a local copy), and the project
opens.
Undoing a check out
Undoing a check out resets the “checked out” flag on the project in the
database, allowing other users to check out the project. Changes you made to
the project while it was checked out are not saved to the database when you
undo the check out.
To undo a check out:
1. Click File > Source Control > Undo Check Out.
2.
The Undo Check Out window appears.
a.
If you want to simply undo the check out, type a description of why
you are undoing the check out in the Action Comments field, then
click OK.
b.
If you would like to undo the check out to a different source control
database, click Change Location. You can then select a different
database into which to undo the check out. (This works only if you
have checked out the project from more than one database.).
70 • Getting Results with RSLogix 500™
Checking in projects
When you check in a project, the project file stored in the database is
overwritten with the project file you have checked out. The changed project is
then available for other users to check out.
To check in a project:
1. Click File > Source Control > Check In.
2.
The Check In window appears.
a.
To simply check in the project, type a description of your changes to
the file in the Action Comments field, then click OK.
b.
To save the project in the database but keep it checked out, check the
Keep Checked Out box before clicking OK.
c.
If you want to change the database into which you are checking in the
project, click Change Destination. You can then select a different
database into which to check in the project. (This works only if you
have checked out the project from more than one database.)
Source control • 71
72 • Getting Results with RSLogix 500™
Getting the information
you need
Chapter
Introduction
Use this chapter to review the sources of additional information on RSLogix
500 software, including online help, RSLogix 500 training, and technical
support.
You can find out more information about RSLogix 500 software by consulting:
„ RSLogix 500 online help
„
RSLogix 500 training
„
Technical support services
RSLogix 500 online help
RSLogix 500 online help provides general overview information, a description
of the fields on every dialog box, and step-by-step procedures for working with
all of the features of RSLogix 500. To open online help while running RSLogix
500 you can:
„ choose Help from the menu on the RSLogix 500 main window
„
click the Help button on any RSLogix 500 dialog box
„
press F1 on any instruction, dialog box, or window view
„
expand the Help folder in the project tree and then double-click on any
informative file listed to launch a help file.
Getting the information you need • 73
Opening an expandable table of contents
To open an outline of the entire RSLogix 500 online help system:
„ click Help on the menu bar and then click Contents
„
click the Help folder in the project tree and then double-click Contents
Double-click any
closed book icon
to reveal the
content.
To collapse the
outline, doubleclick an open
book icon.
To go to a topic
double-click a
page.
Double-click the
procedures book
to see a list of
tasks you can
accomplish using
any function of
the software.
Index
The index tab provides a list of guide words or subjects just like the index of a
book. This is a quick way to find information about a specific topic. Follow the
directions on the Index tab.
Find
If you don’t see what you are looking for in the contents or index, you can
search the entire help file for all occurrences of a word. follow the directions
on the dialog to find a word.
The first time you click the find tab you will see a message about building a
word list. Follow the directions on the screen. The default selection is generally
sufficient. For information refer to Microsoft’s online help (Start > Help).
74 • Getting Results with RSLogix 500™
Learning RSLogix 500 step-by-step
Click this book icon to get more
background reference material
associated with any procedure.
Once you have completed reading the
“How To” window, you can select
another task from this list.
In Help you will find a Step-by-Step topic that asks what you want to do and
lets you select from many of the tasks you might want to perform.
To quickly step through the major tasks associated with creating a project,
going online, and monitoring data, click on the check boxes. If you want more
information about some of the other things that you can do associated with a
major task, click the specific procedure.
Getting the information you need • 75
Quick tips about Windows operating systems and
RSLogix 500
Windows operating systems provide some functionality you may not be
familiar with. The RSLogix 500 online help can point out some shortcuts and
navigational techniques that can make your work easier. Just select
Understanding the Operating Environment from the contents page of the
online help.
Keyboard shortcuts
A list of hot keys (keyboard shortcuts) that enable you to maneuver the
software without a mouse can be found in a help file that you can print out. To
access this file, select Help > Using the Keyboard. To print any of the
keyboard help topics, just click the Print button at the top of the window.
Some of these keyboard shortcuts (sometimes called Ctrl-key accelerators) are
standard to the Windows operating system and work across all Windows-based
products. Other shortcuts will only work with the RSLogix 5 and 500 products.
User Application help
The User Application Help feature allows you to add your own reference
source (document, web page, etc.) to the RSLogix 500 project. You can use
whatever format you want for the source as long as the computer running
RSLogix 500 can open and read that source. For example, you could use a
Microsoft Word .Doc file, provided that you had Word on your computer. Or
you could use an HTML file if you had a browser that could read the file.
Your User Application Help file is saved with the project in RSLogix 500. You
can specify one User Application Help file per project.
To set up your User Application Help file:
1. Create the source file for your User Application Help.
2.
From the project tree in RSLogix 500, right-click User Application Help
(under the Help folder) and select Properties. The User Application
Help dialog appears.
3.
Enter the path and file name (you can Browse for the file), or the URL for
your source file and click OK.
To specify a different source file, go back to the Properties dialog and enter the
new path and name.
To display the User Application Help file, double-click on User Application
Help (under the Help folder in the project tree) or click Help > User
Application Help from the main toolbar menu.
76 • Getting Results with RSLogix 500™
Instruction Set help
All of the instructions available to you in RSLogix 500 have context-sensitive
help. You can click an instruction in your ladder logic for help about the
parameters required or for information about why you might use one type of
instruction instead of another.
Each topic in the instruction set online help also gives you information about
which processors can use the instruction and an example of the instruction with
sample parameters.
RSLogix 500 Training
Rockwell Software offers both classroom and computer-based training for
RSLogix 500.
Classroom training
One of the best ways to increase your proficiency at using Rockwell Software
products is to attend a Rockwell Software training program. Our training
programs can help you master the basics and show you how to unleash the full
potential of our software.
Getting the information you need • 77
We offer a wide range of training programs, from regularly scheduled classes
conducted at Rockwell Software facilities to custom-tailored classes conducted
at your enterprise. The size of each class is kept small intentionally to maximize
student engagement.
For more information about our training programs:
„ visit our web sit at http://www.software.rockwell.com/training/
„
„
view the Support and Training help file either from Help on the menu bar
or from the Help folder in the project tree.
contact the Rockwell software Training Coordinator at 877-724-7864.
Interactive training
Rockwell Software's new RSTrainer 2000 Self-Paced Training programs
provide multimedia lessons and interactive practice exercises designed with
student objectives in mind. Features include animated graphics, professional
audio and content written by Rockwell Training and Tech Support Specialists.
Courses are based on the latest shipping release of the software product and
include links to the software help files.
RSTrainer 2000 for RSLogix 500 contains four lesson modules and over 35
individual multimedia lessons. You’ll learn to install and configure RSLogix 500
and to use it’s powerful features to efficiently develop and maintain ladder logic
programs.
A demo of the training program is included on the RSLogix 500 CD-ROM. To
run the demo, insert the RSLogix 500 CD_ROM into the CD-ROM drive.
When the menu appears, select Try RSTrainer 2000 for RSLogix 500.
If the CD-ROM does not autorun, open the Start menu and select Run. Type
x:\autoplay (where x is your CD-ROM drive), and click OK. Select Try
RSTrainer 2000 for RSLogix 500 from the menu.
Technical support services
If you cannot find answers to your questions in this publication or in the online
help you can call Rockwell Software technical support.
Telephone: 440-646-7800
Fax: 440-646-7801
World Wide Web: http://www.software.rockwell.com/support/
Support staff are available Monday through Friday 8 a.m. to 5 p.m. EST, CST,
MST, and PST, except during U.S. holidays.
78 • Getting Results with RSLogix 500™
When you call
When you call you should be at the computer running the Rockwell Software
product and be prepared to provide the following information:
„ product serial number on the Activation disk labels (You can find the serial
number online. On the RSLogix 500 menu, click Help, and then click
About.)
„
product version number
„
hardware you are using
„
Microsoft Windows operating system and service pack you are using
„
exact wording of any messages that appear on the screen
„
„
description of what happened and what you were doing when the problem
occurred
description of how you tried to solve the problem
Getting the information you need • 79
80 • Getting Results with RSLogix 500™
Appendix
Activation
Rockwell Software’s products are copy-protected. Only a computer with access
to the activation key can run the software. The key is located in an activation
file, which is originally located on the Master disk supplied with the RSLogix
500 product. The activation file contains one activation key per product. Each
key contains one or more licenses depending on how many copies of the
product you have purchased.
Tip
Store your Master disk in a safe place. If your activation becomes
damaged, the Master disk may be the only means to run your
software in an emergency.
During the setup process, the setup program gives you the opportunity to
move the activation file from the Master disk to the root folder of the drive on
which you’re installing the software.
When you launch RSLogix 500, the software first checks your local hard drives,
then network hard drives, and finally local floppy drives for activation. If the
system fails to detect either the activation file or the Master disk, you will
receive an error message stating that activation is required to run the RSLogix
500 software.
Tip
Systems attached to extensive networks can take quite a while to
search for activation files on all available drives. You can use the
CHECKDRIVES environment variable to specify and/or limit
the drives your software checks for activation files and to specify
the order in which they are checked. Refer to the activation
utilities online help file by selecting Help > Copy Protection.
Activation • 81
Protecting your activation files
Caution
Certain anti-virus software packages, such as Norton Anti-virus,
can corrupt the activation files. Configure your anti-virus
software to avoid checking the files EVRSI.SYS and
386SWAP.PAR.
To avoid damaging your activation files, do not perform the following
operations with activation files on the hard drive.
„ Restore from backup
„
Upgrade the operating system
„
Compress or uncompress the hard drive
Defragmentation utilities will not harm activation files.
Before running any type of utility that may modify the structure or organization
of the hard drive, remove activation from the hard drive:
1. Use the Move Activation utility (EvMove) to move activation files from
the hard drive to an activation disk.
Caution
Do not use the the Move Activation utility if Rockwell Software
products are currently running. Ensure all software programs are
closed before initiating the EvMove utility.
Run EVMOVE.EXE from your hard drive (located in C:\Program
Files\Rockwell Software\RSUtil if you accepted the default folder location
during installation).
2.
Perform the hard disk operation.
3.
Move the activation files back to the hard drive.
Caution
You must use the move utility, EvMove, to move activation files.
Attempts to copy, move or e-mail an activation file by other
means will damage the file.
Activating RSLogix 500
Depending on your needs, you can activate RSLogix 500 from any of the
following:
82 • Getting Results with RSLogix 500™
The activation key resides on your computer’s hard disk. Use this
method if you will typically use RSLogix 500 on only one computer. This is the
default method if you activate RSLogix 500 during installation. To run RSLogix
500 on a different computer, move the activation key back to the Master disk,
and then to the hard drive of the new computer.
Hard drive.
Diskette drive. The activation key resides on a floppy disk (activation disk). Use
this method if you will typically use RSLogix 500 on more than one computer,
for example, if you want to run RSLogix 500 on a desktop computer at some
times and a portable computer at others.
Network drive. The activation keys reside on a network drive. Use this method
if you have purchased multiple licenses of the software and want several users
to be able to activate the software over a network. Refer to the online help for
instructions on moving activation to a network drive (refer to the “Finding
more information about activation” section in this chapter to access online
help).
Running the activation utilities
The utilities for moving and resetting activation are called EvMove and Reset
respectively. Reset is used when an activation file has been damaged. The
EVMOVE.EXE and RESET.EXE files are located on your hard drive (located
in C:\Program Files\Rockwell Software\RSUtil if you accepted the default
folder location during installation). To run these programs, select Start >
Progams > Rockwell Software > Utilities > Move Activation or Reset
Activation.
Activation • 83
Finding more information about activation
The online help (COPYPROT.HLP) provides more extensive information on
activation including subjects such as:
Set this environment variable to tell your computer to look for
activation on floppy drives
KEYDISK.
KEYDISK
CHECKDRIVES.
CHECKDRIVES
Specify which drives to search for activation
network activation.
activation Move activation to a network server to allow multiple
users access to the activation
moving activation.
activation
See detailed instructions for moving activation
See detailed instructions for using the Reset utility to
repair a damaged activation file
resetting activation.
activation
troubleshooting.
troubleshooting
Look up error messages, get problem-solving suggestions
You can access online help:
„ from the Help button on one of the EvMove or Reset dialog boxes.
„
„
from RSLogix 500 by selecting Help > Copy Protection from the main
menu.
without running either RSLogix 500 or the activation utilities. From the
Windows Start menu, select Programs > Rockwell Software > Utilities >
Activation Help (if you accepted the default folder location during
installation).
Some common questions
Following are some common problems that people encounter with activation
and their solutions.
My activation files were damaged. What should I
do?
If you have lost the activation because the activation file is damaged, you need
to reset activation. Follow the Reset Codes instructions on the Rockwell
Software Technical Support web page, or call the technical support telephone
number. The web page and telephone number are both listed on the inside
front cover of this guide.
If you cannot obtain a reset code immediately, follow these instructions to use
the Master disk to activate the software as a temporary solution.
To use the Master disk to activate software:
1. Set the KEYDISK environment variable to TRUE. (Please refer to the
online help.)
84 • Getting Results with RSLogix 500™
2.
Insert your Master disk in the floppy drive.
3.
Run your software as usual. Your software will find the activation on the
Master disk.
I accidentally deleted the software folder on my
hard drive. Do I need to call Rockwell Software for
replacement activation files?
No. Deleting the program files does not delete your activation. The activation
files are not stored in the program folder; they are located in the root folder.
Your activation files will not be lost unless you format the hard drive, tamper
with hidden files in the root folder, or perform certain other hard drive
operations (refer to the “Protecting your activation files” section in this chapter
for more information).
To get the software running again, simply reinstall the software, but do not
move the activation when given the opportunity.
Why can’t I move activation to a new floppy disk on
a Windows NT system?
It has to do with a disk modification that NT does not allow. If you have access
to a Windows 95 or 98 machine, you can create a disk that will work under NT.
Format a floppy and move any activation file to it under Windows 95 or 98.
(You can move the activation back off the disk if you want to keep it where it
was.) Then take that disk to your Windows NT machine and move the
activation to it.
Activation • 85
86 • Getting Results with RSLogix 500™
Index
A
about this book • i
Activation • 3
activation • 81
damaged • 84
file • 81
key • 81
moving • 85
network • 84
resetting • 84
troubleshooting • 84
utilities • 83
Activation file
Activation key
License • 3
activation files
definition • ii
addressing • 32
anti-virus software • 82
Archive • 59
Archive Module administration utility
installing • 8
archiving a project • 67
ASCII editing • 38
C
CDM • 49
CGM • 49
chassis • 27
check in • 63, 71
check out • 63, 68
undoing • 70
CHECKDRIVES • 81, 84
communications driver • 14
compare projects • 18
compressing the hard drive • 82
configure communication channel • 24
contents tab in online help • 74
conventions used in this book • i
copy protection • 81
Copy protection, see Activation
crash recovery • 30
creating
data table files • 19
program files • 19
project files • 17
Cross Reference • 53
Custom Data Monitor • 49
Custom Graphical Monitor • 49, 59
B
back up
automatic • 29
compressed format • 29
definition • ii
branching
add a branch • 33
copy branch leg • 34
copy entire branch structure • 34
delete a branch • 34
expand a branch • 33
move a branch • 33
nested branches • 33
parallel branches • 33
restrictions • 34
D
D in rung margin • 36
d in rung margin • 36
Data Logging • 52
data table files
contents of • 19
creating • 19
monitoring • 24
database
source control
installing • 6
defragmentation utilities • 82
deleting the software folder • 85
descriptions
adding to project • 22
Index • 87
DII • 39
disk space required • 2
documentation
adding • 22
documentation database
editing with Excel • 60
export • 43
import • 41
download • 24
definition • ii
drag-and-drop editing • 11
driver • 14
E
e in rung margin • 36
editing
ASCII editor • 38
database with Excel • 60
drag and drop • 11
online example • 37
online restrictions • 38
entering ladder logic • 29
error messages • 81
EvMove • 82
example
custom graphical monitor • 50
data logging • 53
histogram • 52
multipoint monitor • 48
online editing • 37
recipe monitor • 51
Excel
using to edit project databases • 60
export
A.I. ASCII delimited text file • 45
about • 43
RS500 ASCII delimited text file • 44
Extended Procedures Component
installing • 6
F
feature summary • 11
files
back-up files • 29
recovery • 30
find tab in online help • 74
88 • Getting Results with RSLogix 500™
forces • 48
functionality summary • 11
G
get • 63, 68
getting started • 11
go online • 24
goto • 25, 31
H
hardware requirements • 1
help
about instructions • 77
about online help • i, 73
contents • 74
find • 74
glossary • ii
how to use • 74
index • 74
training • ii
hiding program files • 18
Histograms • 51
I
I in rung margin • 36
i in rung margin • 36
I/O chassis • 27
I/O configuration • 20, 27
automatic • 28
I/O modules • 27
icon bar • 12
import
A.I. database • 42
about • 41
APS database • 42
ASCII delimited text file • 43
CSV (Comma Separated Values) file • 42
RSLogix 500 database • 42
index tab in online help • 74
installation
troubleshooting • 9
Installing
RSLinx Lite • 3
RSLogix 500 • 4
installing RSLogix 500 • 1
instruction palette • 13
example of • 32
instruction toolbar • 13
instructions
how to enter • 20
quick entry • 31
quick key mapping • 31
search and replace • 25
interrupts
configuring • 38
DII • 39
STI • 39
K
KEYDISK • 84
L
ladder view • 13
library
definition • ii
Location of program files
standalone workstation • 4
Logic trace • 61
M
master disk • 81
menu bar • 12
mnemonic
definition • ii
module selection • 20
modules
analog and specialty • 28
monitor data files • 24
monitoring data • 47, 59, 63
moving
activation • 85
multiple rungs
selecting • 22
multipoint monitor • 48
N
network
activation • 84
O
online bar • 12
online editing
about • 35
example • 37
restrictions • 38
P
power supply • 20
loading • 28
print a report • 26
program files
contents of • 19
creating • 19
project
definition • ii
project tree • 13
projects
compare • 18
creating • 17
opening • 18
Q
quick start • 13, 75
R
R in rung margin • 36
r in rung margin • 36
rack selection • 20, 27
Recipe Monitor • 50
recovery after power interrupt • 30
reports
previewing • 26
printing • 26
resetting activation • 84
restoring from backup • 82
results pane • 13
RSLinx • 14
version required • 2
RSLinx Lite
installing • 3
RSMACC
using for source control • 59
RSWho • 16
S
search and replace • 25
SLC libraries
exporting • 55
Index • 89
importing • 56
software requirements • 2
source control • 59
adding a project to the archive • 67
Archive Module administration utility
installing • 8
archiving a project • 67
check in • 63
check out • 63
undoing • 70
checking in projects • 71
checking out projects • 68
database • 66
configuring • 63
installing • 6
registering • 66
explained • 63
Extended Procedures Component
installing • 6
get • 63
getting projects • 68
starting RSLogix 500 • 9
status bar • 13
step-by-step guide • 75
steps for getting started • 13
STI • 39
symbols
adding to project • 22
system communications
configuring • 16
T
toolbar
logic trace • 61
toolbars
icon bar • 12
instruction bar • 13
menu bar • 12
online bar • 12
project tree • 13
status bar • 13
tracing logic • 61
training • ii
troubleshooting • 9
activation • 84
90 • Getting Results with RSLogix 500™
U
uncompressing the hard drive • 82
undo • 34
upgrading the operating system • 82
upload
definition • ii
V
VBA • 59
verification
definition • ii
verification results • 23
Visual Basic for Applications support • 59
W
Windows
95 • 85
98 • 85
NT • 85
Z
zone
definition • ii
zone marker
D • 36
d • 36
e • 36
I • 36
i • 36
R • 36
r • 36
Was this manual useful for you? yes no