Instructions Thyro S 1S H1


Add to my manuals
30 Pages

advertisement

Instructions Thyro S 1S H1 | Manualzz
SVS POWER SUPPLY
S
THYRO-S
T H Y R I S T O R - S C H A LT E R
THYRO-S 1S...H1
THYRISTOR SWITCH
THYRO-S 1S...H1
Betriebsanleitung
Operating Instructions
Y
S
T
E
M
S
S A F E T Y
I N S T R U C T I O N S
The following safety and operating instructions must be carefully
read before assembly, installation and commissioning.
Obligation to give instructions
The following safety and operating instructions must be carefully read before initial
assembly, installation and commissioning of Thyro-A by those persons working with
or on Thyro-A.
These operating instructions are part of the Thyristor switch Thyro-S.
The operator of this device is obliged to provide, without restriction, these operating
instructions to all persons transporting, commissioning, maintaining or performing
other work on this device.
In accordance with the Product Liability Act, the manufacturer of a product has an
obligation to provide explanations and warnings as follows:
• the use of the product other than for the intended use,
• the residual product risk as well as
• operating errors and their consequences.
The information given below must be understood in this respect. It is to warn the
product user and protect him and his systems.
Proper use
• The Thyristor switch is a component which may only be used for control and
regulation of electrical energy.
• The Thyristor switch may at most be operated using the maximum admissible
connected load according to information on the type plate.
• The Thyristor switch may only be operated in connection with a suitable and
series connected power supply disconnecting device.
• As a component, the Thyristor switch is unable to operate alone and must be
projected for its intended use to minimize residual risks.
30
The Thyristor switch may only be operated in the sense of its intended use, otherwise hazards to persons (e.g. electric shocks, burns) and systems (e.g. overload)
may arise.
Residual hazards of the product
• Even in case of proper use, should a fault occur, it is possible that control of
currents, voltages and power is no longer performed in the load circuit by the
Thyristor switch.
In case of destruction of the power components (e.g break-down or high resistance), the following situations are possible: power interruption, half-wave operation, continuous power flow. If such a situation occurs, then load voltages and currents are produced from the physical dimensions of the overall power circuit. It must
be ensured by system design that no uncontrolled large currents, voltages or power
occur.
Maloperation and its results
• With maloperation it is possible that power, voltage or flow levels which are higher than planned reach the Thyristor switch or load. On principle, this can lead
to the Thyristor switch or load being damagad.
Transport
• Thyristor switches are only to be transported in their original packaging (protection against damage e.g. due to jolting, knocking, soiling).
Installation
• If the Thyristor switch is brought into the operation room from a cold environment,
moisture can occur. Prior to it being commissioned, the Thyristor switch must be
absolutely dry. Therefore, wait for a minimum of two hours before commissioning.
Connection
• Prior to connection, it must be ensured that the voltage information on the type
plate corresponds with the mains voltage.
• The electrical connection is carried out at the designated points with the required
cross section and the appropriate screw cross sections.
31
Operation
• The Thyristor switch may only be connected to the mains voltage if it has been
ensured that any hazard to people and system, especially in the load section, has
been eliminated.
• Protect the device from dust and moisture
• Do not block vents.
Maintenance, service, malfunctions
CAUTION
For maintenance and repair work the Thyristor switch must be disconnected from all external voltage sources and protected against restarting. The voltage-free state is to be determined by means of suitable
measuring instruments. This work is only to be carried out by a skilled
electrician. The electrical regulations which are locally valid are to be
adhered to.
CAUTION
The Thyristor switch contains dangerous voltages. Repairs may only
be carried out by qualified and trained maintenance personnel.
CAUTION
Danger of electric shock. Even after disconnection from the mains voltage, capacitators may still contain a dangerously high power level.
CAUTION
Danger of electric shocks. Even when the Thyristor switch is not triggered, the load circuit is not disconnected from the mains.
ATTENTION
Different components in the power section are screwed into place
using exact torques. For safety reasons, power component repairs
must be performed by AEG SVS Power Supply Systems GmbH.
S A F E T Y
32
I N S T R U C T I O N S
Contents
➜
➜
➜
Safety instructions
Safety regulations
Remarks on the present operating instructions and Thyro-S
30
35
38
➜
1.
1.1
1.2
1.3
Introduction
General
Specific characteristics
Type designation
39
39
39
40
➜
2.
2.1
2.1.1
2.2
2.2.1
2.2.2
Functions
Operating modes overview
Digital set point value inputs
Indications
Equipment temperature monitoring
Ventilator monitoring
40
40
41
41
41
41
➜
3.
3.1
3.2
Operation
Configuration switch S1
Diagnosis / status indications
42
42
42
➜
4.
4.1
4.2
4.3
4.4
4.5
External connections
Power supply for Thyro-S
Power supply for the control device
Digital set point input
Block connection diagram
Connections and terminal strips
43
43
43
43
44
45
➜
5.
Interfaces
45
➜
6.
Mains load optimization
46
➜
7.
Connecting diagrams
46
33
➜
8.
8.1
8.2
8.3
8.4
Special remarks
Installation
Commissioning
Service
Checklist
49
49
49
49
50
➜
9.
Type overview
50
➜
10.
Technical data
51
➜
11.
Dimensional drawings
Thyro-S 1S (8H) dimensional drawing 850
Thyro-S 1S (16H, 30H) dimensional drawing 851
Thyro-S 1S (45H, 60H) dimensional drawing 853
Thyro-S 1S (100H) dimensional drawing 854
Thyro-S 1S (130H, 170H) dimensional drawing 856
Thyro-S 1S (280H) dimensional drawing 858
53
53
53
54
54
55
55
➜
12.
Accessories and options
56
➜
13.
Approvals and conformities
56
➜
Addresses
60
List of illustrations and tables
Fig.
Fig.
Fig.
Fig.
Fig.
1
2
3
4
5
Tab 1
34
Block connecting diagram
Terminal plan
Operation
Connecting diagram Thyro-S 1S...H1
Connecting diagram 2x Thyro-S 1S...H1
44
45
45
47
48
Status indications
42
➜
Safety regulations
Important instructions and explanations
The skilled personnel assembling and disassembling the devices, commissioning
them and maintaining them must know and observe these safety regulations.
CAUTION
This instruction indicates work and operating procedures to be observed exactly to exclude hazards to persons.
ATTENTION
This instruction refers to work and operating procedures to be observed exactly to avoid damage or destruction of Thyro-S or parts
thereof.
REMARK
This is where remarks on technical requirements and additional information is given which the user must observe.
Accident prevention rules
It is imperative that the accident prevention rules of the country of application and
the generally applicable safety regulations are observed.
CAUTION
Before commencing any work on Thyro-S, the following safety regulations must be observed:
• switch voltage-free
• secure against switching on
• determine voltage-free state
• ground and short-circuit device
• cover or block neighbouring parts under voltage.
Qualified personnel
Thyro-S may only be transported, installed, connected, commissioned, maintained
and operated by specialists in command of the respective applicable safety and
installation regulations. All work must be monitored by the responsible specialist
personnel.
35
Intended use
CAUTION
The Thyristor switch may only be employed in the sense of its purpose
of use (see the section of the chapter Safety instructions under the
same name), otherwise hazards to persons (e.g. electric shocks,
burns) and systems (e.g. overload) may occur.
Any unauthorized reconstruction and modification of Thyro-S, use of spare and exchange parts not approved by AEG SVS as well as any other use of Thyro-S is not
permitted.
The person responsible for the system must ensure that
- safety and operating instructions are available and observed,
- operating conditions and specifications are observed,
- protective installations are used,
- maintenance personnel are immediately notified or Thyrs-S is immediately put out
of commission if abnormal voltages or noises, higher temperatures, vibrations or
similar occur, to determine the causes.
These operating instructions contain all information required by specialists for the
use of Thyro-S. Additional information and notes for unqualified persons and for the
use of Thyro-S outside of industrial installations are not contained in these operating
instructions.
The warranty given by the manufacturer is only valid if these operating instructions
are observed and adhered to.
Warranty
No liability is assumed for employing applications not provided for by the manufacturer. The responsibility for the necessary measures to avoid hazards to persons and
property is borne by the operator or the user. In case of complaints, please notify us
immediately stating:
Type name
Production number
Complaint
Ambient conditions
Operating mode
Duration of use
36
Guidelines
The CE mark on the device confirms adherence to the general EC guidelines for
72/23 EEC – low voltage and for 89/339 EEC electromagnetic compatibility if the
instructions on installation and commissioning described in the operating instructions
are observed.
37
➜
Remarks on the present operating instructions
and Thyro-S
Validity
These operating instructions refer to the latest technical specification of Thyro-S at the
time of publication. The contents are not subject matter of the contract, but serve
only as information. Modification of information contained in these operating instructions, especially technical data, operation, dimensions and weights, remain reserved
at any time. AEG SVS reserves the right to content modifications and technical changes within the present operating instructions without obligation to notification.
AEG SVS is not obliged to update these operating instructions constantly.
Loss of warranty
Our supplies and services are subject to the general terms and conditions of delivery
of the electrical industry as well as our general sales conditions. Any complaints on
goods delivered are to be submitted, together with the delivery note, within eight
days of receipt.
All guarantees made by AEG SVS and its dealers will be cancelled without prior
notice if other than original AEG SVS spare parts or spare parts purchased by
AEG SVS are used for maintenance and repair.
Copyright
Passing on, duplication and/or takeover of these operating instructions by electronic
or mechanical means, including excerpts, is subject to the express prior written
approval of AEG SVS.
Copyright AEG SVS Power Supply Systems GmbH 2002. All rights reserved.
Additional remark on copyright
Thyro-S is an internationally registered trademark of AEG SVS Power Supply
Systems GmbH.
All other companies and product names are the (registered) trademarks of the
respective owners.
38
➜
1. Introduction
Thyro-S meets the demands for simple assembly, speedy commissioning and safer
operation.
For transport, assembly, installation, commissioning, operation and decommissioning, it is essential that the safety instructions included in these operating instructions
are observed and made available to all persons handling this product.
In case of uncertainties or missing information, please contact your supplier.
1.1 General
Thyro-S is a Thyristor switch with the ability to communicate. It will also be referred
to as Power Controller or simply controller. It can be used wherever voltages or currents need to be controlled in processing technology. With its good coupling ability
to process and automation technology, high control precision and simple handling,
Thyro-S is also future-orientated for new applications. The Thyro-S is suitable for a
direct supply of ohmic loads.
1.2 Specific characteristics
Thyro-S has a wide range of distinguishing features, for instance
• easy handling
• type range 230-500 Volts, 8-280 A, single phase
• ohmic load
• operating modes 1:1, as well as 1:2, 1:3 and 1:5 (e.g. for commissioning)
• control with 24V signal (from 3V) via optional bus module
• series system interface
• electrical separation according to EN 50178 chapt. 3
Options:
• bus connections via bus module (bus adapter) coupling to different bus systems,
e.g. Profibus DP, Modbus RTU, other bus systems on request.
39
1.3 Type designation
The type designation of the Thyristor switch is derived from the construction of its
power section:
Thyro-S 1S
Thyristor switch with single phase power section
suited for single phase loads
Beispiel
...400...280
H
F
1
with 400 Volt type voltage
280 with 280 Amp type current
with integrated semi-conductor fuse
with ventilator (only 280 Amp types)
designation Thyro-S, 2002 series
The complete type range can be found in chapter 9, TYPE OVERVIEW.
➜
2. Functions
2.1 Operating modes
Full wave switch
Depending on the digital set point signal the mains voltage is switched. In the operating mode 1:1 almost no harmonics are created in the mains frequency. Whole
multiples of the mains periods are always switched.
For commissioning etc, a reduced supply can be switched with the S1 switch or via
the optional bus module, the control system thereby either forces the switching of
every 2. wave or an equal number of positive and negative half waves.
In all operation modes d.c. components are avoided:
Operating mode
1:1
1:2
1:3
1:5
40
Load voltage
every mains full wave (nom. oper. mode, default setting)
every 2. mains full wave
every 3. mains full wave (d.c. free)
every 5. mains full wave (d.c. free)
2.1.1 Digital set point inputs
The Thyristor switch Thyro-S is equipped with two set point inputs which are electrically isolated from the mains for triggering signals:
• Set point input 11 logic input 0-24V DC (Ri > 3.3 k)
IN: UIN > 3V
• Set point input 2
via bus module
2.2 Indications
The LEDs on the front signal the following states:
• ON
GREEN
operating indication, power supply controller device
Blinking indications are described in chapter 3.2.
Monitoring of the mains voltage
The limiting values of the voltage are -57% for undervoltage monitoring and +10%
for overvoltage monitoring. This produces the following absolute limiting values:
Type
Undervoltage
Overvoltage
230V
99V
253V
400V
172V
440V
500V
215V
550V
2.2.1 Equipment temperature monitoring
The control board is equipped with a temperature monitor.
If a fault occurs, the LED blinks.
2.2.2 Ventilator monitoring
The separately ventilated power controllers (F) are fitted with thermal monitoring.
The temperature of the heat sink is measured. In case of a temperature overrange
a fault indication (red LED) ensues.
1) see also chapter 4.4 Digital set point input
41
➜
3. Operation
3.1 Configuration switch S1
A 2-pole DIP switch is situated at the front behind the hood. The individual switches
are marked from 1-2 starting from the bottom and must be set before operation.
They are only read in once when switched on (mains recovery). For safety reasons
further operation is carried out with the hood closed.
S1-
1
0
1
0
1
2
0
0
1
1
Operating mode
1:1 operation, nom. Oper. mode (default setting)
1:2 operation
1:3 operation
1:5 operation
For operations where initially no nominal load is possible (e.g.drying ) reduced
power can be controlled by Thyro-S independently.
With 1:2 operation each 2. cycle is switched, with 1:3 and 1:5 operation half
cycles are switched with alternating polarity so that while switched on the load is
supplied with d.c.-free energy.
3.2 Diagnosis / status indications
Faults can occur in the load circuit and in the controller itself or from the mains.
Diagnosis of unexpected operating behaviour is performed by LEDs on the front
panel of the control device.
Description
Frequency fault
Red LED
LED blinks
SYNC fault
LED blinks
Temp. monitoring
LED blinks
Flash values invalid
Corr. values invalid
Undercurrent
LED blinks
LED blinks
LED on
Description
outside 47Hz to 63Hz
when switching on or zero
crossing outside permissible
tolerance range in operation
Temp. monitoring responded
(control board or contr. section)
Controller fault
Parameter fault
Mains fault
Tab. 1 Status indications
Further status indications can be called up via system interface.
42
➜
4. External connections
4.1 Power supply for Thyro-S
Connecting the power supply is carried out as shown in the figures and TECHNICAL
DATA.
4.2 Power supply for the control device
The control device is supplied directly from the power section (terminals U1,
X1:1.2). This voltage also serves as mains synchronization. The mains connection is
equipped for input voltages of Unom -57% to +10% and nominal frequencies of
47Hz to 63Hz. Both terminals (X1:1.2 1.5mm2 grid 3.81) are internally bridged. If
a phase is connected to X1, a fused connection is necessary (figs. 3,7).
4.3 Digital set point input
The set point input is a logic input. Between the terminals X22:1 and 2 it can be
operated with a relay contact.
Between terminals X22:1 (signal), 3 (ground) it can be triggered with up to 24V d.c.
With input voltages 3 Volt it recognises the signal ON.
The signal terminals can be connected with up to 1.5mm2, in grid 3.5.
43
4.4 Block connection diagram
Fig. 1: Block connection diagram and connecting plan
The block connection diagram shows the functions of the H 1 design. Central control
element is a -controller.
44
4.5 Connections and terminal strips
This chapter describes all terminal strips and socket connectors.
System interface
Control ground (5 / 3.3 V)
RxD / connection to bus module
TxD / connection to bus module
Bus module recognition
Ground
Pos. current supply unstabilized (can be used as source for K1.1)
Control signal (ON 3V)
L2/N supply connection – synchr. voltage supply frequency
L2/N supply connection – synchr. voltage supply frequency
RM 3.5
RM 3.81
RM 3.81
Fig. 2 Terminal plan
LED
GREEN ON
Operation mode
Operation mode
Chap. 3.1
Fig. 3 Operation
➜
5. Interfaces
With its system interface the Thyristor switch Thyro-S can be connected via an optional bus module to, for example, Profibus DP or Modbus RTU (other bus modules
available on request). Description and connections can be taken from the instructions of the respective components.
REMARK
The access to set value, actual values and parameters made possible
through bus provides further useful functions for application.
45
➜
6. Mains load optimization
Thyro-S is not suitable for mains load optimization in multiple controller applications.
If mains load optimization is necessary, Thyristor controllers of type Thyro-A or
Thyro-P must be used.
➜
7. Connecting diagrams
Thyro-S can be employed in single phase switch and in three phase switches which
can be transposed to single phase switches, e.g. star connections with MP conductor
or N conductor and in open delta connection.
It is possible to apply 2 identical Thyro-S as a three phase saver circuit (with delta
load or star without N), if the triggering signal for both controllers is set up at the
same time. See Fig. 5.
46
Fig. 4 Connecting diagram Thyro-S 1S...H1
47
Thyro-S No. 1 and No. 2
must be the same type
Fig. 5 Connecting diagram 2x Thyro-S 1S...H1
48
➜
8. Special remarks
8.1 Installation
Thyro-S requires a vertical fitting position. With cabinet mounting sufficient ventilation of the cabinet must be ensured. The distance between the Power Controller and
the cabinet ceiling or other mountings should be at least 150mm. The distance below the Power Controller should be at least 100mm. Heating up of the device by
heat sources must be avoided. The dissipation of the Power Controller is stated in
the Type overview table.
ATTENTION
Grounding must be carried out according to local electricity board
regulations! (grounding screw for protective conductor connection on
fastening adapter is provided).
The grounding also serves EMV devices (Y capacitor 4.7 nF).
For Thyro-S with type currents 8A, 16A or 30A an adapter can be delivered for the
35mm top-hat rail assembly.
8.2 Commissioning
The device must be connected to the mains and the associated load according to the
corresponding connecting plans.
On delivery the device is parameterized and adjusted to the respective power section. If a different operating mode is desired, then it must be set with DIP fix 1 and
2 by the user (commissioning phase).
ATTENTION
Heat sinks and neighbouring plastic parts can become hot during
operation ( 70°C)! Provided sign should be fixed nearby Thyro-S.
8.3 Service
The devices delivered have been produced under quality standard ISO 9001.
Should nevertheless faults or problems occur, our
24-hour service hotline: Tel: 02902 / 763-100.
is at your service.
49
8.4 Checklist
• LED ON greenn
lights up -> mains voltage available
• LED ON green does not light up
Check fuse control 500V 1.6 A, if defective, check external wiring, also applies
to faults of external fusing, check Power Controller fusing. If fuse is defect then
check load and wiring to load. Synchronization voltage is supplied to X1.1.
Check 5 Volt to X22.2. If this voltage is absent or too low, there is a defective
component.
• Supply available but no load current
Check connection signal (digital set point) is present
Check for interruption in load circuit
Check blinking LED signals (chapt. 3.2)
• Load current does not have expected value
Check connection signal (digital set point) for continuous signal ON
With optional bus module
Check bus connection signal (bus set point) for continuous signal ON
Check all parallel load resistances for current conduction
• Load current flows uncontrolled
Check connections in the controller (with initial commissioning)
In rare cases a Thyristor short-circuit can occur
➜
9. Type overview
Thyristor switches with integrated semiconductor and system bus interface.
Type capacity [kW]
Type Current 230V 400V 500V
1S
H1
H1
H1
H1
H1
H1
H1
H1
HF 1
50
8
16
30
45
60
100
130
170
280
1.8
3.7
6.9
10
14
23
30
39
64
3.2
6.4
12
18
24
40
52
68
112
8
15
22.5
30
50
65
85
140
Dissipation
[W]
30
47
48
80
105
150
210
330
Dimens. in mm / kg
W
H
D Weight Dim.
draw.
40
45
45
52
52
75
125
125
125
121
121
121
190
190
190
320
320
370
127
127
127
182
182
190
237
237
237
0.6
0.7
0.7
1.7
1.7
1.9
4
4
5
850
851
851
853
853
854
856
856
858
Current
transf.
Fuse
F1
40
40
100
100
100
150
200
300
12
20
40
63
100
180
200
315
350
➜
10. Technical data
Type voltage
230 Volt -57% +10%
400 Volt -57% +10%
500 Volt -57% +10%
Mains frequency
all models 47Hz bis 63Hz; f=6Hz;
max. frequency change 5% per half wave
Load description
ohmic load
Operating modes
Name
1:1
1:2
1:3
1:5
Load signal, with digital set point = ON
all full wave (default setting)
every 2. mains full wave
every 3. mains half wave (d.c. free)
every 5. mains halve wave (d.c. free)
Digital set point inputs (connection signals)
The Thyro-S has 2 set point inputs. The set point inputs are safely disconnected from
the mains (SELV, PELV).
Set point 1:
Logic input 0-24V
Ri 3,3k
ON 3V
Set point 2:
System interface, connection from superset automation
system via optional bus module.
Ambient temperature
35°C external cooling (F model with integrated ventilator)
45°C self air cooling
At higher temperatures it is possible to operate with reduced type current:
Temperature range up to 55°C: type current –2% / °C
51
Power connections
Type current
Connector U1, U2,
8
16
30
45
60
100
130
170
280
A
A
A
A
A
A
A
A
A
Screw plug-in terminal
Bracket / M4
Bracket / M4
M6
M6
M6
M8
M8
M 10
Earthing
screw
Bracket / M4
Bracket / M4
Bracket / M4
M6
M6
M6
M 10
M 10
M 10
Conductor
cross sect.
4 mm2, max.
6 mm2, max.
6 mm2, max.
50 mm2, max.
50 mm2, max.
50 mm2, max.
95 / 120 mm2
95 / 120 mm2
150 / 185 mm2
With UL applications use only 60°/75° copper conductors!
Torques for connection screws [Nm]
Screw
Min value
Nom. value
M2
0,22
0,25
M4
0,85
1,3
M6
2,95
4,4
M8
11,5
17
M10
22
33
Ventilation 230V, 50-60Hz
Thyro-S
Type current 50 Hz
1S 280 HF
0,13 A
Max value
0,28 (Phönix terminals)
1,7
5,9
22,5
44
Type current 60 Hz
0,13 A
The ventilators must run with Thyro-S switched on, connection to X7.
52
Air volume
120 m3/h
➜
11. Dimensional drawings
Thyro-S 1S (8H)
Dimensional drawing 850
Thyro-S 1S (16H, 30H)
Dimensional drawing 851
53
Thyro-S 1S (45H, 60H)
Dimensional drawing 853
Thyro-S 1S (100H)
Dimensional drawing 854
54
Thyro-S 1S (130H, 170H)
Dimensional drawing 856
Thyro-S 1S (280H)
Dimensional drawing 858
55
➜
12. Accessories and options
Order No. 8000 006 757
Order No. 2000 000 841
Order No. 2000 000 842
➜
Support for 35 mm snap-on assembly
for devices with type current 8A, 16A and 30A
Bus module Profibus DP
Bus module Profibus RTU
13. Approvals and conformities
No product norm exists for Thyristor switches so that a useful norm structure can be
built up based on the corresponding basic norms ensuring reliable application and
comparison potential.
CAUTION
Thyristor switches are not devices for disconnection in the sense of
DIN VDE 0105 T1 and may therefore be operated only in connection
with a suitable mains isolating device (e.g. switch, isolating link).
Approvals and conformities for Thyro-S are available
• Quality standard according to DIN EN ISO 9001
• UL registration, file no. E 135074, under preparation, with consideration to
Canadian National Standard, project no. 02ME08043
• CE conformity
• Low voltage directive 73/23 EEC
• EMV directive 89/336 EEC; 92/31 EEC
In detail
Conditions for usen
Built-in unit (VDE 0160)
General requirements
Design, vertical installation
Operating conditions
Operating location, industry sector
Temperature behaviour
Storage temperature
Transport temperature
Operating temperature
56
DIN EN 50 178
DIN EN 60146-1-1:12.97
DIN EN 60 146-1-1; K. 2.5
CISPR 6
DIN EN 60 146-1-1; K 2.2
-25°C - +55°C
-25°C - +70°C
-10°C - +35°C with external cooling (280A)
-10°C - +45°C with self air cooling
-10°C - +55°C
with reduced type current -2%/°C
Load class
1
DIN EN 60 146-1-1 T.2
Humidity class
F
DIN EN 50 178 Tab. 7
Overvoltage category
ÜIII
DIN EN 50 178 Tab. 3
Degree of pollution
2
DIN EN 50 178 Tab. 2
Air pressure
900 mbar * 1000m above NN
Safe isolation up to 500 V mains voltage: DIN EN 50 178 Chap. 3
Air and creeping distances
casing / mains potential 5.5 mm
casing / control potential 2.5 mm
mains voltage /contr. potent. 8 mm
interface /contr. Potent. -/mains voltages interact 2.5 mm
Test voltage
DIN EN 50 178 Tab 18
Tests according to
DIN EN 60 146-1-1 4.
EMV noise emission
EN 61000-6-4
Noise suppr. control device Class A
DIN EN 55011:3.91 CISPR 11
EMV noise resistance
EN 61000-6-2
Compatibility level
Class 3
EN 61000-2-4:7.95
ESD
8 kV (A)
EN 61000-4-2:3.96
Electromagnetic fields
10 V/m
EN 61000-4-3:3.95
Burst mains lines
2 kV (A
EN 61000-4-4:.95
control lines
2 kV (A)
Surge mains lines
2 kV unsym. EN 61000-4-5:.95
1 kV sym.
EN 61000-4-5:.95
control lines
0.5 kV
Line-conducted
EN 61000-4-6
57
Weltweit ist AEG SVS auf allen wichtigen
Märkten durch Vertriebspartner vertreten.
Die aktuellen regionalen Adressen finden Sie im Internet: http://www.aegsvs.de
You can find the current adresses on the Internet: http://www.aegsvs.de
AEG SVS
Power Supply Systems GmbH
A company of Saft Power
Systems
Emil-Siepmann-Straße 32
D-59 581 Warstein-Belecke
Tel.
+49 (0 ) 29 02 / 7 63 - 5 09
Printed in Germany · Änderungen vorbehalten · Druckerei Hecker, Inh. Andrea Koerdt · Brilon
AEG SVS is represented by sales partners
in all important markets world wide.
Fax
+49 (0 ) 29 02 / 7 63 - 12 01
D 8000008753
http://www.aegsvs.de
08/2002
Phone +49 (0 ) 29 02 / 7 63 - 2 78
http://www.saftpowersystems.com