Universal Interface Module UIM

Universal Interface Module UIM
esserbus communication transponder for ECP 8010
Part-No. 808615
•
•
•
•
•
2 relays transponder. The detector states prealarm or
detector malfunction may also be displayed.
Variable reset delay of the detector zone (0 to 15
seconds)
The detector zones can be operated in 2-zone
dependency
Two relays with programmable operating modes
Programmable with the programming software tools
8000; Panel software Version V2.40 or higher required
Programmable surveillance of the external DC power
supply
Current consumption
Quiescent current @ FACP battery
Ambient temperature
Storage temperature
Type of protection
Air humidity
Weight
Dimensions
max. 28 mA
approx. 150 µA
-10 °C ... 50 °C
-25 °C ... 75 °C
IP 40 (with housing)
< 95 %
approx. 28 g
W: 72 mm H: 65 mm D: 20 mm
Subject to change without notice!
Mounting: in the housing of the 8010 extinguishing relay output
Including loop isolator PCB (Part No. 788612)
Novar GmbH a Honeywell Company
Dieselstr. 2 41469 Neuss
Phone: +49 2131 40615 600
Faximile: +49 2131 40615 606
© Honeywell International Inc.
With this esserbus transponder the extinguishing relay output 8010 can be
integrated on the bus of panel 8000, IQ8Control and FlexES, thus enabling
several extinguishing zones to be networked with each other. On each bus, a
maximum of eight 8010 extinguishing relay outputs can be operated and a
maximum of 16 communication transponders for each FACP8000 C/M,
IQ8Control and FlexES. All indicators and controls can be activated from the fire
alarm panel. The communication transponder occupies one address on the
esserbus. Integrated loop isolator on board. Maximum 8 transponders per loop
and max. 16 transponders per FACP. The RZT 8000 third-party detector
connecting module has four inputs for detector zones and two relay outputs. It
Features:
may be used for connecting four additional standard detector zones with
non-addressable third-party detectors to the analog loop. The two relay outputs
• Output current max. 125 mA per detector zone
• Optional use of the extended functionality of the 4 zone / are available for general control purposes.