Emerson Smart Wireless THUM Adapter

Add to my manuals
32 Pages

advertisement

Emerson Smart Wireless THUM Adapter | Manualzz
Quick Start Guide
00825-0100-4075, Rev EC
August 2015
Emerson™ Smart Wireless THUM™
Adapter
Quick Start Guide
August 2015
NOTICE
This guide provides basic guidelines for the Emerson Smart Wireless THUM Adapter. It does not provide
instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installations.
Refer to the THUM Adapter Reference Manual (document number 00809-0100-4075) for more instruction.
The manual and this guide are also available electronically on www.rosemount.com.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions. This
device may not cause harmful interference. This device must accept any interference received, including
interference that may cause undesired operation.
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local,
national, and international standards, codes, and practices. Review the Product Certifications section for any
restrictions associated with a safe installation.
 Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments are installed
in accordance with intrinsically safe or non-incendive field wiring practices.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical
shock.

This device must be installed to ensure a minimum antenna separation distance of 7.87 in. (20 cm) from all
persons.
During normal operation, or in fault condition, the THUM Adapter will cause a 2.5 V drop in the connected
loop. It is important to ensure that the power supply can provide at least 2.5 V more than the minimum
operating voltage of the wired device to make sure it works properly with the THUM Adapter installed. To
determine the minimum operating voltage for the wired device, review the wired device operation and
installation manual.
Contents
Wireless considerations . . . . . . . . . page 3 Verify operation . . . . . . . . . . . . . . . page 22
Bench top configuration . . . . . . . . . page 5 Reference information . . . . . . . . . page 24
Physical installation . . . . . . . . . . . . . page 6 Product Certifications . . . . . . . . . . page 25
2
August 2015
Quick Start Guide
Wireless considerations
Power up sequence
Power should not be applied to any wireless device until the Smart Wireless
Gateway (“Gateway”) is installed and functioning properly. Wireless devices
should also be powered up in order of proximity from the Gateway, beginning
with the closest. This will result in a simpler and faster network installation. Enable
Active Advertising on the Gateway to ensure that new devices join the network
faster. For more information see the Smart Wireless Gateway Manual (document
number 00809-0200-4420).
THUM Adapter position
THUM Adapter should be positioned vertically straight up, and should be
approximately 3 ft (1 m) from any large structure, building or conductive surface
to allow for clear communication to other devices. If the THUM Adapter is
mounted horizontally wireless communication range may be decreased. The
THUM Adapter should not be mounted vertically straight down. See THUM
Adapter reference manual (document number 00809-0100-4075) for more
information.
Figure 1. THUM Adapter Position
Conduit entry
When installing the THUM Adapter into the conduit entry of a wired device, use
an approved thread sealant. Thread sealant provides a water tight seal. The
thread sealant also provides lubrication to ensure easy removal of the THUM
Adapter.
M20 Conduit Adapter
When using the M20 Conduit Adapter on the THUM Adapter, use an approved
thread sealant and tighten wrench tight to the THUM Adapter. When installing
the M20 conduit adapter into a conduit, tighten to 32.5 Nm/25 ft-lb. to ensure
water tight seal.
3
August 2015
Quick Start Guide
Field Communicator connections
In order for the Field Communicator to interface with the THUM Adapter, the
wired device must be powered. The Field Communicator must be put into poll
mode and should use the THUM Adapter address of 63.
Power supply



Minimum loop load of 250 Ohms.
The THUM Adapter communicates via and derives power from a standard 4-20
mA/HART® loop. The THUM Adapter causes a small voltage drop on the loop
which is linear from 2.25 V at 3.5 mA to 1.2 V at 25 mA. Under fault
conditions, the maximum voltage drop is 2.5 V. The THUM Adapter will not
affect the 4-20 mA signal under normal or fault conditions as long as the loop
has at least a 2.5 V margin at the maximum loop current (25 mA for a typical
4-20 mA/HART device).
Limit the power supply to 0.5 Amps maximum and voltage to 55 Vdc.
Loop current
THUM Adapter voltage drop
3.5 mA
2.25 V
25 mA
1.2 V
Load resistor
If required, add a load resistor as shown in Figure 8 on page 10, Figure 12 on
page 13, and Figure 16 on page 15. The resistor should be adequately rated for
the application (1W minimum) and be compatible with the supplied splice
connector which accepts wire sizes from 14 to 22 AWG.
Loop
To ensure proper operation, the THUM Adapter should not be installed on a HART
loop with other active HART masters. HART masters that are active periodically,
such as a field communicator can be used on a loop with a THUM Adapter.
4
Quick Start Guide
August 2015
Bench top configuration
When performing bench top configuration it is suggested that you connect the
THUM Adapter to a wired device. If this is not possible, the following wiring
diagrams can be used. For bench top configuration, ensure the power supply
used is limited to 0.5 Amps maximum.
Figure 2. THUM Adapter Only, Powered by a Current Source
A
Green
B
Red
+
-
Black
White
C
Yellow
D
A. THUM Adapter
C. 20 mA current source
B. Ground
D. HART Modem
Figure 3. THUM Adapter Only, Powered by a 24 V Power Supply with 1200
Ohm Resistor to Limit Current to 20 mA
A
Green
B
Red
+
Black
-
White
C
Yellow
D
A. THUM Adapter
C. 20 V power supply
B. Ground
D. HART Modem
5
Quick Start Guide
August 2015
Step 1: Physical installation
The THUM Adapter can be installed in one of two configurations:
1. Direct Mount: The THUM Adapter is connected directly to the conduit entry of
the wired device.
2. Remote Mount: The THUM Adapter is mounted separate from the wired
device housing and then connected to the wired device using conduit or other
suitable means.
Figure 4. Direct Mount
Direct mount
1. Install the HART device according to standard installation practices and the
manufacturer’s instructions, being sure to use an approved thread sealant on
all connections.
2. Attach the THUM Adapter to the wired device as shown in Figure 4 on page 6.
3. Connect the THUM Adapter to the HART wired device using the wiring
diagrams below. See Figures Figure 21 on page 19, Figure 8 on page 10, Figure
10 on page 11, and Figure 12 on page 13 on the following pages.
4. Close the housing cover on the HART wired device, so that metal touches
metal, but do not over tighten to prevent damaging the unit.
Note
Two splice connectors are included with the THUM Adapter. The first is a two connection splice.
The second is a three connection splice for use with a resistor, if there is not enough resistance in
the loop. Both of these splice connectors can accept 14 to 22 gauge wire. See wired device
reference manual for information on the required loop resistance.
6
August 2015
Quick Start Guide
Remote mount
Figure 5. Remote Mount
1. Install the HART device according to standard installation practices and the
manufacturer’s instructions, being sure to use an approved thread sealant on
all connections.
2. The THUM Adapter should be mounted as shown in Figure 5 on page 7.
3. Ground the Remote Mount Kit per local practices.
4. Connect the THUM Adapter to the wired device using standard practices. Wire
running from the THUM Adapter to the wired device should be shielded or in
conduit when installed in electrically noisy environments.
5. Connect the THUM Adapter to the HART wired device using the wiring
diagrams below. See Figure 21 on page 19, Figure 8 on page 10, Figure 10 on
page 11, and Figure 12 on page 13 on the following pages.
6. Close the housing cover on the HART wired device, so that metal touches
metal, but do not over tighten to prevent damaging the unit.
Note
Two splice connectors are included with the THUM Adapter. The first is a two connection splice.
The second is a three connection splice for use with a resistor, if there is not enough resistance in
the loop. Both of these splice connectors can accept 14 to 22 gauge wire. See wired device
reference manual for information on the required loop resistance.
7
Quick Start Guide
August 2015
Wiring diagrams
The following is a list of the figure titles and page numbers for each direct mount
and remote mount wiring diagram:
Figure 6 - “Direct Mount Wiring Diagram for 2-Wire Device” on page 9
Figure 7 - “Remote Mount Wiring Diagram for 2-Wire Device” on page 10
Figure 8 - “Direct Mount Wiring Diagram for 2-Wire Device with Resistor” on
page 10
Figure 9 - “Remote Mount Wiring Diagram for 2-Wire Device with Resistor” on
page 11
Figure 10 - “Direct Mount Wiring Diagram for 4-Wire Passive Device” on page 11
Figure 11 - “Remote Mount Wiring Diagram for 4-Wire Passive Device” on page 12
Figure 12 - “Direct Mount Wiring Diagram for 4-Wire Passive Device with Resistor”
on page 13
Figure 13 - “Remote Mount Wiring Diagram for 4-Wire Passive Device with
Resistor” on page 13
Figure 14 - “Direct Mount Wiring Diagram for 4-Wire Active Device” on page 14
Figure 15 - “Remote Mount Wiring Diagram for 4-Wire Active Device” on page 15
Figure 16 - “Direct Mount Wiring Diagram for 4-Wire Active Device with Resistor”
on page 15
Figure 17 - “Remote Mount Wiring Diagram for 4-Wire Active Device with
Resistor” on page 16
Figure 18 - “Direct Mount Wiring Diagram for 4-Wire Active Device with No 4-20
mA Loop” on page 17
Figure 19 - “Remote Mount Wiring Diagram for 4-Wire Active Device with No 4-20
mA Loop” on page 18
Figure 20 - “THUM Adapter only, Powered by a 24 V Power Supply with 1200 Ohm
resistor to limit current to 20 mA” on page 18
Figure 21 - “THUM Adapter only, Powered by a 24 V Power Supply with 1200 Ohm
resistor to limit current to 20 mA” on page 19
8
Quick Start Guide
August 2015
Figure 6. Direct Mount Wiring Diagram for 2-Wire Device
A
Green
B
C
4 -20 mA Loop +
Red
Black
4 -20 mA Loop -
White
F
Yellow
D
- PWR/COMM
E
+ PWR/COMM
A. THUM Adapter
D. Splice connector
B. Wired device
E. Load resistor ≥ 250 Ω
C. Ground
F. Power supply
Note
In order for the THUM Adapter to function properly there must be at least 250 Ohms resistance in
the loop. If the 4–20 mA loop does not have the required resistance, wire a resistor as shown in
Figure 8 on page 10, Figure 12 on page 13, or Figure 16 on page 15 as applicable.
9
August 2015
Quick Start Guide
Figure 7. Remote Mount Wiring Diagram for 2-Wire Device
A
B
Red
Black
Green
4 -20 mA Loop +
C
White
4 -20 mA Loop -
Yellow
F
D
+ COMM
- COMM
E
To Wired Device
A. THUM Adapter
D. Shield wire
B. Remote mount housing
E. Load resistor ≥ 250 Ω
C. Ground
F. Power supply
Figure 8. Direct Mount Wiring Diagram for 2-Wire Device with Resistor
A
Green
B
C
Red
4 -20 mA Loop +
Black
4 -20 mA Loop -
White
Yellow
E
- PWR/COMM
D
+ PWR/COMM
10
A. THUM Adapter
D. Splice connector
B. Wired device
E. Load resistor ≥ 250 Ω
C. Ground
F. Power supply
F
Quick Start Guide
August 2015
Figure 9. Remote Mount Wiring Diagram for 2-Wire Device with Resistor
A
B
Red
Green
White
C
E
4 - 20 mA Loop +
Black
4 - 20 mA Loop -
Yellow
+
-
F
D
+ COMM
- COMM
To Wired Device
A. THUM Adapter
D. Shield wire
B. Remote mount housing
E. Load resistor ≥ 250 Ω
C. Ground
F. Power supply
Figure 10. Direct Mount Wiring Diagram for 4-Wire Passive Device
A
B
Green
D
4 - 20 mA Loop +
C
Red
4 -20 mA Loop -
Black
F
White
Yellow
Power -
Power +
COMM -
COMM +
E
A. THUM Adapter
D. Splice connector
B. Wired device
E. Load resistor ≥ 250 Ω
C. Ground
F. Power supply
11
August 2015
Quick Start Guide
Note
A passive loop exists when the wired device is not supplying power to the 4–20 mA loop. It is
important to verify if the wired device is operating in active or passive mode.
Figure 11. Remote Mount Wiring Diagram for 4-Wire Passive Device
A
B
Green
4 -20 mA Loop +
C
4 -20 mA Loop -
D
E
+ COMM
To Wired Device
- COMM
12
+
-
A. THUM Adapter
D. Shield wire
B. Remote mount housing
E. Load resistor ≥ 250 Ω
C. Ground
F. Power supply
F
Quick Start Guide
August 2015
Figure 12. Direct Mount Wiring Diagram for 4-Wire Passive Device with
Resistor
A
D
B
Green
4 - 20 mA Loop +
C
Red
4 -20 mA Loop -
Black
White
+
-
F
E
Power -
Power +
COMM -
COMM +
Yellow
A. THUM Adapter
D. Splice connector
B. Wired device
E. Load resistor ≥ 250 Ω
C. Ground
F. Power supply
Figure 13. Remote Mount Wiring Diagram for 4-Wire Passive Device with
Resistor
A
B
Green
4 - 20 mA Loop +
C
4 - 20 mA Loop -
D
+ COMM
+
-
F
E
To Wired Device
- COMM
A. THUM Adapter
D. Shield wire
B. Remote mount housing
E. Load resistor ≥ 250 Ω
C. Ground
F. Power supply
13
August 2015
Quick Start Guide
Figure 14. Direct Mount Wiring Diagram for 4-Wire Active Device
A
D
B
Green
C
Yellow
+
-
White
Black
Red
Power -
Power +
COMM -
COMM +
E
A. THUM Adapter
D. Splice connector
B. Wired device
E. Load resistor ≥ 250 Ω
C. Ground
F. Input card
Note
An active loop exists when the wired device is supplying the power to the 4-20 mA loop. It is
important to verify if the wired device is operating in active or passive mode.
14
F
Quick Start Guide
August 2015
Figure 15. Remote Mount Wiring Diagram for 4-Wire Active Device
A
B
Green
+ COMM
To Wired Device
C
- COMM
D
4-20 mA Loop +
F
4-20 mA Loop -
E
A. THUM Adapter
D. Shield wire
B. Remote mount housing
E. Load resistor ≥ 250 Ω
C. Ground
F. Input card
Figure 16. Direct Mount Wiring Diagram for 4-Wire Active Device with
Resistor
A
B
Green
D
C
Yellow
White
F
Black
Red
+
_
Power -
Power +
Comm -
Comm +
E
A. THUM Adapter
F. Splice connector
B. Wired device
G. Load resistor ≥ 250 Ω
C. Ground
H. Input card
15
August 2015
Quick Start Guide
Figure 17. Remote Mount Wiring Diagram for 4-Wire Active Device with
Resistor
A
B
E
COMM +
C
COMM -
G
D
4 - 20 mA Loop +
F
4 - 20 mA Loop -
E
A. THUM Adapter
E. Load resistor ≥ 250 Ω
B. Remote mount housing
F. Input card
C. Ground
G. To wired device
D. Shield wire
16
Quick Start Guide
August 2015
Figure 18. Direct Mount Wiring Diagram for 4-Wire Active Device with No
4-20 mA Loop
A
D
B
Green
E
C
Yellow
White
Black
Power -
Power +
COMM -
COMM +
Red
A. THUM Adapter
D. Splice connector
B. Wired device
E. Load resistor ≥ 250 Ω
C. Ground
17
August 2015
Quick Start Guide
Figure 19. Remote Mount Wiring Diagram for 4-Wire Active Device with No
4-20 mA Loop
A
B
Red
Green
C
D
Black
White
Yellow
+ COMM
- COMM
To Wired Device
A. THUM Adapter
C. Ground
B. Remote mount housing
D. Load Resistor ≥ 250 Ω
Figure 20. THUM Adapter Only, Powered by a 24 V Power Supply with 1200
Ohm Resistor to Limit Current to 20 mA
A
C
Green
Red
+
Black
-
White
D
E
Yellow
B
18
A. THUM Adapter
D. 250 Ω Resistor
B. Junction Box
E. 1200 Ohm Resistor Required
C. Ground
F. 24 V Power Supply
F
Quick Start Guide
August 2015
Figure 21. THUM Adapter Only, Powered by a 24 V Power Supply with 1200
Ohm Resistor to Limit Current to 20 mA
A
B
Red
Green
C
Black
+
White
Yellow
E
F
-
D
A. THUM Adapter
D. 250 Ω Resistor
B. Remote Mount Housing
E. 1200 Ohm Resistor Required
C. Ground
F. 24 V Power Supply
Device network configuration
In order to communicate with the Smart Wireless Gateway, and ultimately the
Information System, the transmitter must be configured to communicate with
the wireless network. This step is the wireless equivalent of connecting wires from
a transmitter to the information system. Using a Field Communicator or AMS®
Wireless Configurator, enter the Network ID and Join Key so that they match the
Network ID and Join Key of the gateway and other devices in the network. If the
Network ID and Join Key are not identical, the THUM Adapter will not
communicate with the network. The Network ID and Join Key may be obtained
from the Smart Wireless Gateway on the Setup>Network>Settings page on the
web server, shown in Figure 22 on page 20.
19
August 2015
Quick Start Guide
Figure 22. Gateway Network Settings
AMS Wireless Configurator
Right click on the THUM Adapter and select Configure. When the menu opens,
select Join Device to Network and follow the method to enter the Network ID and
Join Key.
Field Communicator
The Network ID and Join Key may be changed in the wireless device by using the
following Fast Key sequence. Set both Network ID and Join Key.
Function
Wireless Setup
20
Fast Key sequence
1,4
Menu items
Smart Power, Network ID, Set Join Key, Radio State
Quick Start Guide
August 2015
Loop current test
To verify the THUM Adapter will work under all conditions, a loop current test
should be performed. This test will exercise the loop under the highest possible
voltage drop conditions.
1. Place loop in manual control.
2. Drive loop to high alarm level. For details, see wired device instruction manual.

When the THUM Adapter is connected to a valve, this will need to be done
at the current source and not from the valve.

When the THUM Adapter is connected to a transmitter, this will need to be
performed at the transmitter.
3. Place the THUM Adapter into fixed voltage drop mode.
AMS Wireless Configurator
a. Right click on the THUM Adapter and select Configure.
b. When the menu opens, select Manual Setup from the window on the left
and select the Wired Device tab on the top.
c. Make sure the Time drop down menu at the bottom of the page has
Current selected.
d. Under the Voltage Drop drop down menu in the Smart Power Options box,
select Fixed Voltage Drop.
e. Select the Apply button to make any changes. See Figure 23 on page 22.
Field Communicator
a. When communicating to the THUM Adapter select: Configure>Manual
setup> Wired Device>Voltage Drop Mode.
b. In the method select Fixed Voltage Drop.
Function
Fast Key sequence
Menu items
2,2,2,2
Voltage Drop
Voltage Drop
4. Verify the current on the loop reaches the high alarm levels.
5. Place the THUM Adapter into variable voltage drop mode.
AMS Wireless Configurator
a. Right click on the THUM Adapter and select Configure.
b. When the menu opens, select Manual Setup from the window on the left
and select the Wired Device tab on the top.
c. Make sure the Time drop down menu at the bottom of the page has
Current selected.
d. Under the Voltage Drop drop down menu in the Smart Power Options box,
select Fixed Voltage Drop.
e. Select the Apply button to make any changes. See Figure 23 on page 22.
21
August 2015
Quick Start Guide
Field Communicator
a. When communicating to the THUM Adapter select: Configure>Manual
setup>Wired Device>Voltage Drop Mode.
b. In the method select Variable Voltage Drop.
Function
Fast Key sequence
Menu items
2,2,2,2
Voltage Drop
Voltage Drop
6. Remove loop from high alarm value.
Figure 23. AMS Configure Screen
Step 2: Verify operation
Operation can be verified in three locations: by using the Field Communicator, at
the Gateway via the Smart Wireless Gateway’s integrated web server, or via AMS
Wireless Configurator.
Field Communicator
For HART Wireless transmitter communication, a THUM Adapter DD is
required.The Field Communicator must be put into poll mode using the THUM
Adapter address of 63. Use the wired device documentation to connect the Field
Communicator to the THUM Adapter.
Function
Communications
22
Fast Key sequence
3, 3
Menu items
Join Status, Wireless Mode, Join Mode, Number of Available
Neighbors, Number of Advertisements Heard, Number of Join
Attempts
Quick Start Guide
August 2015
Smart Wireless Gateway
If the THUM Adapter was configured with the Network ID and Join Key, and
sufficient time has passed for network polling, the transmitter will be connected
to the network. To verify device operation and connection to the network with
the Smart Wireless Gateway’s integrated web server, open the Smart Wireless
Gateway’s integral web interface and navigate to the Explorer page.
Note
It may take several minutes for the device to join the network.
AMS Wireless Configurator
When the device has joined the network, it will appear in the Wireless
Configurator as illustrated below.
Troubleshooting
If the device is not operating properly, refer to the troubleshooting section of the
manual. The most common cause of incorrect operation is the Network ID and
Join Key. The Network ID and Join Key in the device must match that of the Smart
Wireless Gateway.
The Network ID and Join Key may be obtained from the Smart Wireless Gateway
on the Setup>Network>Settings page on the web server. The Network ID and Join
Key may be changed in the wireless device by using the following Fast Key
sequence.
Function
Wireless Setup
Fast Key sequence
1, 4
Menu items
Smart Power, Network ID, Set Join Key, Radio State
23
August 2015
Quick Start Guide
Reference information
Note
In order to communicate with a Field Communicator, the wired device must be powered.
Table 1. THUM Adapter Fast Key Sequence
Function
Device Info
Fast Key sequence
2, 2, 4, 3
Menu items
Manufacturer, Model, Final Assembly Number, Universal, Field
Device, Software, Hardware, Descriptor, Message, Date, Model
Number I, II, III, SI Unit Restriction, Country
Guided Setup
2, 1
Configure, Guided Setup, Join Device to Network, Configure
Update Rate, Zero Trim, Configure Device Display, Configure
Process Alarms
Manual Setup
2, 2
Configure, Manual Setup, Wireless, Pressure, Device
Temperatures, Device Information, Display, Other
Wireless
24
2, 2, 1
Network ID, Join Device to Network, Configure Update Rate,
Configure Broadcast Power Level, Power Mode, Power Source
August 2015
Quick Start Guide
Product Certifications
Rev 1.0
European Directive Information
A copy of the EC Declaration of Conformity can be found at the end of the Quick
Start Guide. The most recent revision of the EC Declaration of Conformity can be
found at www.rosemount.com.
Ordinary Location Certification from FM Approvals
As standard, the transmitter has been examined and tested to determine that the
design meets the basic electrical, mechanical, and fire protection requirements
by FM Approvals, a nationally recognized test laboratory (NRTL) as accredited by
the Federal Occupational Safety and Health Administration (OSHA).
Telecommunication compliance (for wireless
products only)
All wireless devices require certification to ensure that they adhere to regulations
regarding the use of the RF spectrum. Nearly every country requires this type of
product certification.
Emerson is working with governmental agencies around the world to supply fully
compliant products and remove the risk of violating country directives or laws
governing wireless device usage.
FCC and IC (for wireless products only)
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following conditions: This device may not cause harmful interference. This device
must accept any interference received, including interference that may cause
undesired operation. This device must be installed to ensure a minimum antenna
separation distance of 20 cm from all persons.
Installing Equipment in North America
The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area classification,
gas, and temperature class. This information is clearly defined in the respective
codes.
25
Quick Start Guide
August 2015
USA
I5 FM Intrinsically Safe (IS) and Non-incendive
Certificate: 3036224
Standards: FM Class 3600 - 1998, FM Class 3610 - 2007, FM Class 3611 - 2004, FM
Class 3810 - 2005, NEMA 250 - 2003, IEC 60529 - 2004
Markings: IS CL I, DIV 1, GP 1, A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; Class 1, Zone 0
AEx ia IIC T4; NI CL I, DIV 2, GP A, B, C, D T4; T4(-50 °C ≤ Ta ≤ +70 °C)
when connected per Rosemount drawing 00775-0010; Type 4X/IP66
Canada
I6 CSA Intrinsically Safe
Certificate: 2174201
Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA C22.2 No. 94-M91 (R2001),
CSA Std C22.2 No. 142-M1987, CAN/CSA C22.2 No.157-92, CSA Std C22.2
No. 213-M1987, C22.2 No. 60529
Markings: Intrinsically Safe Class I, Division 1, Groups A, B, C, and D T3C; Suitable for
use in Class I, Division 2, Groups A, B, C, and D T3C; T3C(-50 °C ≤ Ta ≤ +70 °C)
when installed per Rosemount drawing 00775-0012; Type 4X/IP66
Europe
I1 ATEX Intrinsic Safety
Certificate: Baseefa09ATEX0125X
Standards: IEC 60079-0:2011; EN60079-11:2012;
Markings:
II 1G Ex ia IIC T4 Ga, T4(-50 °C ≤ Ta ≤ +70 °C)
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1GΩ. To avoid
electrostatic charge build-up, it must not be rubbed or cleaned with solvents
or dry cloth.
2. The Model 775 enclosure may be made of aluminum alloy and given a
protective polyurethane paint finish; however, care should be taken to protect
it from impact or abrasion if located in zone 0.
N1 ATEX Type n
Certificate: Baseefa09ATEX0131
Standards: IEC 60079-0:2011, EN 60079-15:2010;
Markings:
II 3G nA IIC T4 Gc, T4(-50 °C ≤ Ta ≤ +70 °C) IP66
International
I7 IECEx Intrinsic Safety
Certificate: IECEx BAS 09.0050X
Standards: IEC 60079-0:2011, IEC 60079-11:2011;
Markings: Ex ia IIC T4 Ga, T4(-50 °C ≤ Ta ≤ +70 °C) IP66
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1GΩ. To avoid
electrostatic charge build-up, it must not be rubbed or cleaned with solvents
or dry cloth.
26
August 2015
Quick Start Guide
2. The Model 775 enclosure may be made of aluminum alloy and given a
protective polyurethane paint finish; however, care should be taken to protect
it from impact or abrasion if located in zone 0.
N7 IECEx Type n
Certificate: IECEx BAS 09.0058
Standards: IEC 60079-0:2011, IEC 60079-15:2010;
Markings: Ex nA IIC T4 Gc, T4(-50 °C ≤ Ta ≤ +70 °C) IP66
Brazil
I2 INMETRO Intrinsic Safety
Certificate: UL-BR 15.0089X
Standards: ABNT NBR IEC 60079-0:2008, ABNT NBR IEC 60079-11:2009
Markings: Ex ia IIC T4 Ga (-50 °C ≤ Ta ≤ +70 °C), IP66
Special Condition for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1GΩ. To avoid
electrostatic charge build-up, it must not be rubbed or cleaned with solvents
or dry cloth.
2. The enclosure may be made of aluminum alloy and given a protective
polyurethane paint finish; special care must be taken to minimize the risk of
impact or friction of the housing which can cause the generation of sparks.
N2 INMETRO Type n
Certificate: UL-BR 15.0027
Standards: ABNT NBR IEC 60079-0:2008, IEC 60079-15:2010;
Markings: Ex nA IIC T4 Gc (-50 °C ≤ Ta ≤ +70 °C) IP66
China
I3 NEPSI Intrinsic Safety
Certificate: GYJ14.1094X
Standards: GB3836.1 - 2010, GB3836.4 - 2010, GB3836.20-2010
Markings: Ex ia IIC T4 Ga, -50 ~ 70 °C
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Japan
I4 TIIS Intrinsically Safe
Certificates: TC20024
Markings: Ex ia IIB T4
EAC – Belarus, Kazakhstan, Russia
IM Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate: RU C-US.Gb05.B.00099
Markings: 0Ex ia IIC T4 X Ga; T4 (-50 °C ≤ Ta ≤ +70 °C) IP66
27
Quick Start Guide
NM
Technical Regulation Customs Union (EAC) Type n
Certificate: RU C-US.Gb05.B.00099
Markings: 2Ex nA IIC T4 X Gc T4 (-50 °C ≤ Ta ≤ +70 °C) IP66
Republic of Korea
IP Korea (KOSHA) Intrinsic Safety
Certificate: 10-KB4BO-0010X
Markings: Ex ia IIC T4
Special Condition for Safe Use (X):
1. See certificate for special conditions.
India
IW India (CCOE) Intrinsic Safety
Certificates: A/P/HQ/MH/104/2023(P242867)
Markings: Ex ia IIC T4
Combinations
KM Combination of IM and NM
28
August 2015
August 2015
Quick Start Guide
Figure 24. Emerson THUM Wireless Adapter Declaration of Conformity
29
Quick Start Guide
30
August 2015
August 2015
Quick Start Guide
31
*00825-0100-4075*
Quick Start Guide
00825-0100-4075, Rev EC
August 2015
Global Headquarters
Emerson Process Management
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
[email protected]
North America Regional Office
Emerson Process Management
8200 Market Blvd.
Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
[email protected]
Latin America Regional Office
Emerson Process Management
1300 Concord Terrace, Suite 400
Sunrise, Florida, 33323, USA
+1 954 846 5030
+1 954 846 5121
[email protected]
Europe Regional Office
Emerson Process Management Europe GmbH
Neuhofstrasse 19a P.O. Box 1046
CH 6340 Baar
Switzerland
+41 (0) 41 768 6111
+41 (0) 41 768 6300
[email protected]
Asia Pacific Regional Office
Emerson Process Management Asia Pacific Pte Ltd
1 Pandan Crescent
Singapore 128461
+65 6777 8211
+65 6777 0947
[email protected]
Middle East and Africa Regional Office
Emerson Process Management
Emerson FZE P.O. Box 17033,
Jebel Ali Free Zone - South 2
Dubai, United Arab Emirates
+971 4 8118100
+971 4 8865465
[email protected]
Standard Terms and Conditions of Sale can be found at:
www.rosemount.com\terms_of_sale.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Rosemount, and Rosemount logotype are registered trademarks of
Rosemount Inc.
AMS is a registered trademark Emerson Electrical Co.
THUM Adapter is a trademark of Rosemount Inc.
HART and WirelessHART are registered trademarks of FieldComm Group.
All other marks are the property of their respective owners.
© 2015 Emerson Process Management. All rights reserved.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement