advertisement
▼
Scroll to page 2
of 32
Quick Start Guide 00825-0100-4075, Rev EC August 2015 Emerson™ Smart Wireless THUM™ Adapter Quick Start Guide August 2015 NOTICE This guide provides basic guidelines for the Emerson Smart Wireless THUM Adapter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installations. Refer to the THUM Adapter Reference Manual (document number 00809-0100-4075) for more instruction. The manual and this guide are also available electronically on www.rosemount.com. This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions. This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. Explosions could result in death or serious injury. Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the Product Certifications section for any restrictions associated with a safe installation. Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices. Electrical shock can result in death or serious injury. Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. This device must be installed to ensure a minimum antenna separation distance of 7.87 in. (20 cm) from all persons. During normal operation, or in fault condition, the THUM Adapter will cause a 2.5 V drop in the connected loop. It is important to ensure that the power supply can provide at least 2.5 V more than the minimum operating voltage of the wired device to make sure it works properly with the THUM Adapter installed. To determine the minimum operating voltage for the wired device, review the wired device operation and installation manual. Contents Wireless considerations . . . . . . . . . page 3 Verify operation . . . . . . . . . . . . . . . page 22 Bench top configuration . . . . . . . . . page 5 Reference information . . . . . . . . . page 24 Physical installation . . . . . . . . . . . . . page 6 Product Certifications . . . . . . . . . . page 25 2 August 2015 Quick Start Guide Wireless considerations Power up sequence Power should not be applied to any wireless device until the Smart Wireless Gateway (“Gateway”) is installed and functioning properly. Wireless devices should also be powered up in order of proximity from the Gateway, beginning with the closest. This will result in a simpler and faster network installation. Enable Active Advertising on the Gateway to ensure that new devices join the network faster. For more information see the Smart Wireless Gateway Manual (document number 00809-0200-4420). THUM Adapter position THUM Adapter should be positioned vertically straight up, and should be approximately 3 ft (1 m) from any large structure, building or conductive surface to allow for clear communication to other devices. If the THUM Adapter is mounted horizontally wireless communication range may be decreased. The THUM Adapter should not be mounted vertically straight down. See THUM Adapter reference manual (document number 00809-0100-4075) for more information. Figure 1. THUM Adapter Position Conduit entry When installing the THUM Adapter into the conduit entry of a wired device, use an approved thread sealant. Thread sealant provides a water tight seal. The thread sealant also provides lubrication to ensure easy removal of the THUM Adapter. M20 Conduit Adapter When using the M20 Conduit Adapter on the THUM Adapter, use an approved thread sealant and tighten wrench tight to the THUM Adapter. When installing the M20 conduit adapter into a conduit, tighten to 32.5 Nm/25 ft-lb. to ensure water tight seal. 3 August 2015 Quick Start Guide Field Communicator connections In order for the Field Communicator to interface with the THUM Adapter, the wired device must be powered. The Field Communicator must be put into poll mode and should use the THUM Adapter address of 63. Power supply Minimum loop load of 250 Ohms. The THUM Adapter communicates via and derives power from a standard 4-20 mA/HART® loop. The THUM Adapter causes a small voltage drop on the loop which is linear from 2.25 V at 3.5 mA to 1.2 V at 25 mA. Under fault conditions, the maximum voltage drop is 2.5 V. The THUM Adapter will not affect the 4-20 mA signal under normal or fault conditions as long as the loop has at least a 2.5 V margin at the maximum loop current (25 mA for a typical 4-20 mA/HART device). Limit the power supply to 0.5 Amps maximum and voltage to 55 Vdc. Loop current THUM Adapter voltage drop 3.5 mA 2.25 V 25 mA 1.2 V Load resistor If required, add a load resistor as shown in Figure 8 on page 10, Figure 12 on page 13, and Figure 16 on page 15. The resistor should be adequately rated for the application (1W minimum) and be compatible with the supplied splice connector which accepts wire sizes from 14 to 22 AWG. Loop To ensure proper operation, the THUM Adapter should not be installed on a HART loop with other active HART masters. HART masters that are active periodically, such as a field communicator can be used on a loop with a THUM Adapter. 4 Quick Start Guide August 2015 Bench top configuration When performing bench top configuration it is suggested that you connect the THUM Adapter to a wired device. If this is not possible, the following wiring diagrams can be used. For bench top configuration, ensure the power supply used is limited to 0.5 Amps maximum. Figure 2. THUM Adapter Only, Powered by a Current Source A Green B Red + - Black White C Yellow D A. THUM Adapter C. 20 mA current source B. Ground D. HART Modem Figure 3. THUM Adapter Only, Powered by a 24 V Power Supply with 1200 Ohm Resistor to Limit Current to 20 mA A Green B Red + Black - White C Yellow D A. THUM Adapter C. 20 V power supply B. Ground D. HART Modem 5 Quick Start Guide August 2015 Step 1: Physical installation The THUM Adapter can be installed in one of two configurations: 1. Direct Mount: The THUM Adapter is connected directly to the conduit entry of the wired device. 2. Remote Mount: The THUM Adapter is mounted separate from the wired device housing and then connected to the wired device using conduit or other suitable means. Figure 4. Direct Mount Direct mount 1. Install the HART device according to standard installation practices and the manufacturer’s instructions, being sure to use an approved thread sealant on all connections. 2. Attach the THUM Adapter to the wired device as shown in Figure 4 on page 6. 3. Connect the THUM Adapter to the HART wired device using the wiring diagrams below. See Figures Figure 21 on page 19, Figure 8 on page 10, Figure 10 on page 11, and Figure 12 on page 13 on the following pages. 4. Close the housing cover on the HART wired device, so that metal touches metal, but do not over tighten to prevent damaging the unit. Note Two splice connectors are included with the THUM Adapter. The first is a two connection splice. The second is a three connection splice for use with a resistor, if there is not enough resistance in the loop. Both of these splice connectors can accept 14 to 22 gauge wire. See wired device reference manual for information on the required loop resistance. 6 August 2015 Quick Start Guide Remote mount Figure 5. Remote Mount 1. Install the HART device according to standard installation practices and the manufacturer’s instructions, being sure to use an approved thread sealant on all connections. 2. The THUM Adapter should be mounted as shown in Figure 5 on page 7. 3. Ground the Remote Mount Kit per local practices. 4. Connect the THUM Adapter to the wired device using standard practices. Wire running from the THUM Adapter to the wired device should be shielded or in conduit when installed in electrically noisy environments. 5. Connect the THUM Adapter to the HART wired device using the wiring diagrams below. See Figure 21 on page 19, Figure 8 on page 10, Figure 10 on page 11, and Figure 12 on page 13 on the following pages. 6. Close the housing cover on the HART wired device, so that metal touches metal, but do not over tighten to prevent damaging the unit. Note Two splice connectors are included with the THUM Adapter. The first is a two connection splice. The second is a three connection splice for use with a resistor, if there is not enough resistance in the loop. Both of these splice connectors can accept 14 to 22 gauge wire. See wired device reference manual for information on the required loop resistance. 7 Quick Start Guide August 2015 Wiring diagrams The following is a list of the figure titles and page numbers for each direct mount and remote mount wiring diagram: Figure 6 - “Direct Mount Wiring Diagram for 2-Wire Device” on page 9 Figure 7 - “Remote Mount Wiring Diagram for 2-Wire Device” on page 10 Figure 8 - “Direct Mount Wiring Diagram for 2-Wire Device with Resistor” on page 10 Figure 9 - “Remote Mount Wiring Diagram for 2-Wire Device with Resistor” on page 11 Figure 10 - “Direct Mount Wiring Diagram for 4-Wire Passive Device” on page 11 Figure 11 - “Remote Mount Wiring Diagram for 4-Wire Passive Device” on page 12 Figure 12 - “Direct Mount Wiring Diagram for 4-Wire Passive Device with Resistor” on page 13 Figure 13 - “Remote Mount Wiring Diagram for 4-Wire Passive Device with Resistor” on page 13 Figure 14 - “Direct Mount Wiring Diagram for 4-Wire Active Device” on page 14 Figure 15 - “Remote Mount Wiring Diagram for 4-Wire Active Device” on page 15 Figure 16 - “Direct Mount Wiring Diagram for 4-Wire Active Device with Resistor” on page 15 Figure 17 - “Remote Mount Wiring Diagram for 4-Wire Active Device with Resistor” on page 16 Figure 18 - “Direct Mount Wiring Diagram for 4-Wire Active Device with No 4-20 mA Loop” on page 17 Figure 19 - “Remote Mount Wiring Diagram for 4-Wire Active Device with No 4-20 mA Loop” on page 18 Figure 20 - “THUM Adapter only, Powered by a 24 V Power Supply with 1200 Ohm resistor to limit current to 20 mA” on page 18 Figure 21 - “THUM Adapter only, Powered by a 24 V Power Supply with 1200 Ohm resistor to limit current to 20 mA” on page 19 8 Quick Start Guide August 2015 Figure 6. Direct Mount Wiring Diagram for 2-Wire Device A Green B C 4 -20 mA Loop + Red Black 4 -20 mA Loop - White F Yellow D - PWR/COMM E + PWR/COMM A. THUM Adapter D. Splice connector B. Wired device E. Load resistor ≥ 250 Ω C. Ground F. Power supply Note In order for the THUM Adapter to function properly there must be at least 250 Ohms resistance in the loop. If the 4–20 mA loop does not have the required resistance, wire a resistor as shown in Figure 8 on page 10, Figure 12 on page 13, or Figure 16 on page 15 as applicable. 9 August 2015 Quick Start Guide Figure 7. Remote Mount Wiring Diagram for 2-Wire Device A B Red Black Green 4 -20 mA Loop + C White 4 -20 mA Loop - Yellow F D + COMM - COMM E To Wired Device A. THUM Adapter D. Shield wire B. Remote mount housing E. Load resistor ≥ 250 Ω C. Ground F. Power supply Figure 8. Direct Mount Wiring Diagram for 2-Wire Device with Resistor A Green B C Red 4 -20 mA Loop + Black 4 -20 mA Loop - White Yellow E - PWR/COMM D + PWR/COMM 10 A. THUM Adapter D. Splice connector B. Wired device E. Load resistor ≥ 250 Ω C. Ground F. Power supply F Quick Start Guide August 2015 Figure 9. Remote Mount Wiring Diagram for 2-Wire Device with Resistor A B Red Green White C E 4 - 20 mA Loop + Black 4 - 20 mA Loop - Yellow + - F D + COMM - COMM To Wired Device A. THUM Adapter D. Shield wire B. Remote mount housing E. Load resistor ≥ 250 Ω C. Ground F. Power supply Figure 10. Direct Mount Wiring Diagram for 4-Wire Passive Device A B Green D 4 - 20 mA Loop + C Red 4 -20 mA Loop - Black F White Yellow Power - Power + COMM - COMM + E A. THUM Adapter D. Splice connector B. Wired device E. Load resistor ≥ 250 Ω C. Ground F. Power supply 11 August 2015 Quick Start Guide Note A passive loop exists when the wired device is not supplying power to the 4–20 mA loop. It is important to verify if the wired device is operating in active or passive mode. Figure 11. Remote Mount Wiring Diagram for 4-Wire Passive Device A B Green 4 -20 mA Loop + C 4 -20 mA Loop - D E + COMM To Wired Device - COMM 12 + - A. THUM Adapter D. Shield wire B. Remote mount housing E. Load resistor ≥ 250 Ω C. Ground F. Power supply F Quick Start Guide August 2015 Figure 12. Direct Mount Wiring Diagram for 4-Wire Passive Device with Resistor A D B Green 4 - 20 mA Loop + C Red 4 -20 mA Loop - Black White + - F E Power - Power + COMM - COMM + Yellow A. THUM Adapter D. Splice connector B. Wired device E. Load resistor ≥ 250 Ω C. Ground F. Power supply Figure 13. Remote Mount Wiring Diagram for 4-Wire Passive Device with Resistor A B Green 4 - 20 mA Loop + C 4 - 20 mA Loop - D + COMM + - F E To Wired Device - COMM A. THUM Adapter D. Shield wire B. Remote mount housing E. Load resistor ≥ 250 Ω C. Ground F. Power supply 13 August 2015 Quick Start Guide Figure 14. Direct Mount Wiring Diagram for 4-Wire Active Device A D B Green C Yellow + - White Black Red Power - Power + COMM - COMM + E A. THUM Adapter D. Splice connector B. Wired device E. Load resistor ≥ 250 Ω C. Ground F. Input card Note An active loop exists when the wired device is supplying the power to the 4-20 mA loop. It is important to verify if the wired device is operating in active or passive mode. 14 F Quick Start Guide August 2015 Figure 15. Remote Mount Wiring Diagram for 4-Wire Active Device A B Green + COMM To Wired Device C - COMM D 4-20 mA Loop + F 4-20 mA Loop - E A. THUM Adapter D. Shield wire B. Remote mount housing E. Load resistor ≥ 250 Ω C. Ground F. Input card Figure 16. Direct Mount Wiring Diagram for 4-Wire Active Device with Resistor A B Green D C Yellow White F Black Red + _ Power - Power + Comm - Comm + E A. THUM Adapter F. Splice connector B. Wired device G. Load resistor ≥ 250 Ω C. Ground H. Input card 15 August 2015 Quick Start Guide Figure 17. Remote Mount Wiring Diagram for 4-Wire Active Device with Resistor A B E COMM + C COMM - G D 4 - 20 mA Loop + F 4 - 20 mA Loop - E A. THUM Adapter E. Load resistor ≥ 250 Ω B. Remote mount housing F. Input card C. Ground G. To wired device D. Shield wire 16 Quick Start Guide August 2015 Figure 18. Direct Mount Wiring Diagram for 4-Wire Active Device with No 4-20 mA Loop A D B Green E C Yellow White Black Power - Power + COMM - COMM + Red A. THUM Adapter D. Splice connector B. Wired device E. Load resistor ≥ 250 Ω C. Ground 17 August 2015 Quick Start Guide Figure 19. Remote Mount Wiring Diagram for 4-Wire Active Device with No 4-20 mA Loop A B Red Green C D Black White Yellow + COMM - COMM To Wired Device A. THUM Adapter C. Ground B. Remote mount housing D. Load Resistor ≥ 250 Ω Figure 20. THUM Adapter Only, Powered by a 24 V Power Supply with 1200 Ohm Resistor to Limit Current to 20 mA A C Green Red + Black - White D E Yellow B 18 A. THUM Adapter D. 250 Ω Resistor B. Junction Box E. 1200 Ohm Resistor Required C. Ground F. 24 V Power Supply F Quick Start Guide August 2015 Figure 21. THUM Adapter Only, Powered by a 24 V Power Supply with 1200 Ohm Resistor to Limit Current to 20 mA A B Red Green C Black + White Yellow E F - D A. THUM Adapter D. 250 Ω Resistor B. Remote Mount Housing E. 1200 Ohm Resistor Required C. Ground F. 24 V Power Supply Device network configuration In order to communicate with the Smart Wireless Gateway, and ultimately the Information System, the transmitter must be configured to communicate with the wireless network. This step is the wireless equivalent of connecting wires from a transmitter to the information system. Using a Field Communicator or AMS® Wireless Configurator, enter the Network ID and Join Key so that they match the Network ID and Join Key of the gateway and other devices in the network. If the Network ID and Join Key are not identical, the THUM Adapter will not communicate with the network. The Network ID and Join Key may be obtained from the Smart Wireless Gateway on the Setup>Network>Settings page on the web server, shown in Figure 22 on page 20. 19 August 2015 Quick Start Guide Figure 22. Gateway Network Settings AMS Wireless Configurator Right click on the THUM Adapter and select Configure. When the menu opens, select Join Device to Network and follow the method to enter the Network ID and Join Key. Field Communicator The Network ID and Join Key may be changed in the wireless device by using the following Fast Key sequence. Set both Network ID and Join Key. Function Wireless Setup 20 Fast Key sequence 1,4 Menu items Smart Power, Network ID, Set Join Key, Radio State Quick Start Guide August 2015 Loop current test To verify the THUM Adapter will work under all conditions, a loop current test should be performed. This test will exercise the loop under the highest possible voltage drop conditions. 1. Place loop in manual control. 2. Drive loop to high alarm level. For details, see wired device instruction manual. When the THUM Adapter is connected to a valve, this will need to be done at the current source and not from the valve. When the THUM Adapter is connected to a transmitter, this will need to be performed at the transmitter. 3. Place the THUM Adapter into fixed voltage drop mode. AMS Wireless Configurator a. Right click on the THUM Adapter and select Configure. b. When the menu opens, select Manual Setup from the window on the left and select the Wired Device tab on the top. c. Make sure the Time drop down menu at the bottom of the page has Current selected. d. Under the Voltage Drop drop down menu in the Smart Power Options box, select Fixed Voltage Drop. e. Select the Apply button to make any changes. See Figure 23 on page 22. Field Communicator a. When communicating to the THUM Adapter select: Configure>Manual setup> Wired Device>Voltage Drop Mode. b. In the method select Fixed Voltage Drop. Function Fast Key sequence Menu items 2,2,2,2 Voltage Drop Voltage Drop 4. Verify the current on the loop reaches the high alarm levels. 5. Place the THUM Adapter into variable voltage drop mode. AMS Wireless Configurator a. Right click on the THUM Adapter and select Configure. b. When the menu opens, select Manual Setup from the window on the left and select the Wired Device tab on the top. c. Make sure the Time drop down menu at the bottom of the page has Current selected. d. Under the Voltage Drop drop down menu in the Smart Power Options box, select Fixed Voltage Drop. e. Select the Apply button to make any changes. See Figure 23 on page 22. 21 August 2015 Quick Start Guide Field Communicator a. When communicating to the THUM Adapter select: Configure>Manual setup>Wired Device>Voltage Drop Mode. b. In the method select Variable Voltage Drop. Function Fast Key sequence Menu items 2,2,2,2 Voltage Drop Voltage Drop 6. Remove loop from high alarm value. Figure 23. AMS Configure Screen Step 2: Verify operation Operation can be verified in three locations: by using the Field Communicator, at the Gateway via the Smart Wireless Gateway’s integrated web server, or via AMS Wireless Configurator. Field Communicator For HART Wireless transmitter communication, a THUM Adapter DD is required.The Field Communicator must be put into poll mode using the THUM Adapter address of 63. Use the wired device documentation to connect the Field Communicator to the THUM Adapter. Function Communications 22 Fast Key sequence 3, 3 Menu items Join Status, Wireless Mode, Join Mode, Number of Available Neighbors, Number of Advertisements Heard, Number of Join Attempts Quick Start Guide August 2015 Smart Wireless Gateway If the THUM Adapter was configured with the Network ID and Join Key, and sufficient time has passed for network polling, the transmitter will be connected to the network. To verify device operation and connection to the network with the Smart Wireless Gateway’s integrated web server, open the Smart Wireless Gateway’s integral web interface and navigate to the Explorer page. Note It may take several minutes for the device to join the network. AMS Wireless Configurator When the device has joined the network, it will appear in the Wireless Configurator as illustrated below. Troubleshooting If the device is not operating properly, refer to the troubleshooting section of the manual. The most common cause of incorrect operation is the Network ID and Join Key. The Network ID and Join Key in the device must match that of the Smart Wireless Gateway. The Network ID and Join Key may be obtained from the Smart Wireless Gateway on the Setup>Network>Settings page on the web server. The Network ID and Join Key may be changed in the wireless device by using the following Fast Key sequence. Function Wireless Setup Fast Key sequence 1, 4 Menu items Smart Power, Network ID, Set Join Key, Radio State 23 August 2015 Quick Start Guide Reference information Note In order to communicate with a Field Communicator, the wired device must be powered. Table 1. THUM Adapter Fast Key Sequence Function Device Info Fast Key sequence 2, 2, 4, 3 Menu items Manufacturer, Model, Final Assembly Number, Universal, Field Device, Software, Hardware, Descriptor, Message, Date, Model Number I, II, III, SI Unit Restriction, Country Guided Setup 2, 1 Configure, Guided Setup, Join Device to Network, Configure Update Rate, Zero Trim, Configure Device Display, Configure Process Alarms Manual Setup 2, 2 Configure, Manual Setup, Wireless, Pressure, Device Temperatures, Device Information, Display, Other Wireless 24 2, 2, 1 Network ID, Join Device to Network, Configure Update Rate, Configure Broadcast Power Level, Power Mode, Power Source August 2015 Quick Start Guide Product Certifications Rev 1.0 European Directive Information A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com. Ordinary Location Certification from FM Approvals As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by FM Approvals, a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA). Telecommunication compliance (for wireless products only) All wireless devices require certification to ensure that they adhere to regulations regarding the use of the RF spectrum. Nearly every country requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage. FCC and IC (for wireless products only) This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons. Installing Equipment in North America The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes. 25 Quick Start Guide August 2015 USA I5 FM Intrinsically Safe (IS) and Non-incendive Certificate: 3036224 Standards: FM Class 3600 - 1998, FM Class 3610 - 2007, FM Class 3611 - 2004, FM Class 3810 - 2005, NEMA 250 - 2003, IEC 60529 - 2004 Markings: IS CL I, DIV 1, GP 1, A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; Class 1, Zone 0 AEx ia IIC T4; NI CL I, DIV 2, GP A, B, C, D T4; T4(-50 °C ≤ Ta ≤ +70 °C) when connected per Rosemount drawing 00775-0010; Type 4X/IP66 Canada I6 CSA Intrinsically Safe Certificate: 2174201 Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA C22.2 No. 94-M91 (R2001), CSA Std C22.2 No. 142-M1987, CAN/CSA C22.2 No.157-92, CSA Std C22.2 No. 213-M1987, C22.2 No. 60529 Markings: Intrinsically Safe Class I, Division 1, Groups A, B, C, and D T3C; Suitable for use in Class I, Division 2, Groups A, B, C, and D T3C; T3C(-50 °C ≤ Ta ≤ +70 °C) when installed per Rosemount drawing 00775-0012; Type 4X/IP66 Europe I1 ATEX Intrinsic Safety Certificate: Baseefa09ATEX0125X Standards: IEC 60079-0:2011; EN60079-11:2012; Markings: II 1G Ex ia IIC T4 Ga, T4(-50 °C ≤ Ta ≤ +70 °C) Special Conditions for Safe Use (X): 1. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or dry cloth. 2. The Model 775 enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in zone 0. N1 ATEX Type n Certificate: Baseefa09ATEX0131 Standards: IEC 60079-0:2011, EN 60079-15:2010; Markings: II 3G nA IIC T4 Gc, T4(-50 °C ≤ Ta ≤ +70 °C) IP66 International I7 IECEx Intrinsic Safety Certificate: IECEx BAS 09.0050X Standards: IEC 60079-0:2011, IEC 60079-11:2011; Markings: Ex ia IIC T4 Ga, T4(-50 °C ≤ Ta ≤ +70 °C) IP66 Special Conditions for Safe Use (X): 1. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or dry cloth. 26 August 2015 Quick Start Guide 2. The Model 775 enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if located in zone 0. N7 IECEx Type n Certificate: IECEx BAS 09.0058 Standards: IEC 60079-0:2011, IEC 60079-15:2010; Markings: Ex nA IIC T4 Gc, T4(-50 °C ≤ Ta ≤ +70 °C) IP66 Brazil I2 INMETRO Intrinsic Safety Certificate: UL-BR 15.0089X Standards: ABNT NBR IEC 60079-0:2008, ABNT NBR IEC 60079-11:2009 Markings: Ex ia IIC T4 Ga (-50 °C ≤ Ta ≤ +70 °C), IP66 Special Condition for Safe Use (X): 1. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic charge build-up, it must not be rubbed or cleaned with solvents or dry cloth. 2. The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish; special care must be taken to minimize the risk of impact or friction of the housing which can cause the generation of sparks. N2 INMETRO Type n Certificate: UL-BR 15.0027 Standards: ABNT NBR IEC 60079-0:2008, IEC 60079-15:2010; Markings: Ex nA IIC T4 Gc (-50 °C ≤ Ta ≤ +70 °C) IP66 China I3 NEPSI Intrinsic Safety Certificate: GYJ14.1094X Standards: GB3836.1 - 2010, GB3836.4 - 2010, GB3836.20-2010 Markings: Ex ia IIC T4 Ga, -50 ~ 70 °C Special Condition for Safe Use (X): 1. See certificate for special conditions. Japan I4 TIIS Intrinsically Safe Certificates: TC20024 Markings: Ex ia IIB T4 EAC – Belarus, Kazakhstan, Russia IM Technical Regulation Customs Union (EAC) Intrinsic Safety Certificate: RU C-US.Gb05.B.00099 Markings: 0Ex ia IIC T4 X Ga; T4 (-50 °C ≤ Ta ≤ +70 °C) IP66 27 Quick Start Guide NM Technical Regulation Customs Union (EAC) Type n Certificate: RU C-US.Gb05.B.00099 Markings: 2Ex nA IIC T4 X Gc T4 (-50 °C ≤ Ta ≤ +70 °C) IP66 Republic of Korea IP Korea (KOSHA) Intrinsic Safety Certificate: 10-KB4BO-0010X Markings: Ex ia IIC T4 Special Condition for Safe Use (X): 1. See certificate for special conditions. India IW India (CCOE) Intrinsic Safety Certificates: A/P/HQ/MH/104/2023(P242867) Markings: Ex ia IIC T4 Combinations KM Combination of IM and NM 28 August 2015 August 2015 Quick Start Guide Figure 24. Emerson THUM Wireless Adapter Declaration of Conformity 29 Quick Start Guide 30 August 2015 August 2015 Quick Start Guide 31 *00825-0100-4075* Quick Start Guide 00825-0100-4075, Rev EC August 2015 Global Headquarters Emerson Process Management 6021 Innovation Blvd. Shakopee, MN 55379, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 [email protected] North America Regional Office Emerson Process Management 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 [email protected] Latin America Regional Office Emerson Process Management 1300 Concord Terrace, Suite 400 Sunrise, Florida, 33323, USA +1 954 846 5030 +1 954 846 5121 [email protected] Europe Regional Office Emerson Process Management Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland +41 (0) 41 768 6111 +41 (0) 41 768 6300 [email protected] Asia Pacific Regional Office Emerson Process Management Asia Pacific Pte Ltd 1 Pandan Crescent Singapore 128461 +65 6777 8211 +65 6777 0947 [email protected] Middle East and Africa Regional Office Emerson Process Management Emerson FZE P.O. Box 17033, Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates +971 4 8118100 +971 4 8865465 [email protected] Standard Terms and Conditions of Sale can be found at: www.rosemount.com\terms_of_sale. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount, and Rosemount logotype are registered trademarks of Rosemount Inc. AMS is a registered trademark Emerson Electrical Co. THUM Adapter is a trademark of Rosemount Inc. HART and WirelessHART are registered trademarks of FieldComm Group. All other marks are the property of their respective owners. © 2015 Emerson Process Management. All rights reserved.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project