GX-Series Security System Quick Installation Guide

GX-Series Security System Quick Installation Guide
800-05372 9/10 Rev. B
GX-Series Security System
Quick Installation Guide
General Information
The GX-Series Control Panel offers the following
features:
• On-board PSTN Dialler
• Four RS485 Buses
• 16-520 Zones
• Up to 987 users*
*Excluding Manager, Authorization, Engineer
(Installer) and ATM codes.
Peripheral
Mk7 Keypad
TouchCenter
RIO
Note: The E485-2 Expansion module provides 2 extra Bus
lines (lines 3 and 4).
DCM
Setup
Ethernet
Mount the panel and connect and address all
peripherals as described below, before applying power
to the system.
Peripheral Wiring
The following peripherals can be connected to the panel:
All bus lines: Mk7 LCD Keypad; TouchCenter; Door
Control Module (DCM); Remote Input
Output Module (RIO).
Bus line 1 only: Ethernet
Note: The system must be wired in a daisy-chain configuration.
Spur and star configurations must not be used. The
recommended cable used to connect the RS485 (AB) line
is twisted pair screened cable (Belden 8723 equivalent).
Panel
Keypad
+12V
GND
A
B
+
–
A
B
Touch
Center
+
–
G
Y
RIO &
DCM
Vin
–
A
B
Audio
Interface
+12V
GND
A
B
Note: Do not connect +12V terminals between panels and
remote power supplies
Panel
+12V
GND
A
B
Ethernet
+
A
B
RS485 Peripheral Wiring
Peripheral Addressing
The address on most peripherals is set by either
jumpers or a rotary switch. These must be set before
the system is powered up. See the instructions with
the peripheral for details. The following table
identifies the available peripheral addresses:
1
Line
1
2
3-4
1
2
3-4
1
2
3-4
1
2
3-4
1
VALID
ADDRESSES
0-2, B-F
0-6, F
0-6, F
0-2
0-3
0-3
2
2 -9 & A-F
0-9 & A-F
0-9 & A-F
0-7
0-7
0-7
(B)
Peripheral Addresses
Notes: 1. A single TouchCenter can be installed
on each bus line.
2. The TouchCenter memory card slot not
investigated by UL.
3. If RIO 2 on-board is set to line 0 (Dip
SW 8) then the first external RIO can
use address 1 to give an extra 8 zones
where needed.
AC Power & Wiring
This product is not suitable for installation, maintenance
or connection by the user. A competent, qualified
installer must carry out installation and maintenance.
Install the 1451 Transformer:
1. The 120VAC circuit should provide continuous, 24
hour power, and not be controlled by a wall switch.
2. Remove the front cover and mount the 1451
transformer cover to the wall near the control panel.
3. Identify the circuit breaker or fuse controlling the
circuit furnishing power to the control panel, and
make sure it is in the OFF position.
4. Run 120VAC wiring from the circuit breaker or
fuse to the enclosure in conduit. A dedicated
circuit must be used.
5. Use wire nuts to splice the 120VAC wires to the
transformer’s black and white primary leads.
6. Connect the green wire to a proper earth ground.
7. Run 16 AWG wire in conduit from the enclosure to
the control panel.
8. Route wire through the knockout on the
enclosure’s left side, and tie wrap it to separate it
from other wiring.
FOR DOCUMENTATION AND ONLINE SUPPORT:
(See GX-Series Installation and Setup Guide, P/N 800-05928 or Higher)
9. Use wire nuts to splice the transformer blue
18VAC secondary leads to the 16AWG wire,
and connect the 16AWG wire to the AC
terminals on the control panel.
10. Replace the front cover and secure with screws.
Note:
Ensure that the cabinet is properly grounded.
Zones
Zones are the individual input circuits on GXSeries systems and are fully programmable in
menu 52 = Program Zones.
Outputs
Note: All circuits are power limited except for the output
of the 1451 transformer and standby battery.
Zone Address Format
1 01 5
Bus Line
The configuration for the zones and the resistance
preset values used can be reprogrammed from menu
option 51.46 = Zone Resistance. Each zone on the
system can be further customised to a specific preset
by using menu option 52.9=Resistance Select. The
cable run on each zone should be no more than 1,640
feet (500 meters). For presets 9 and 10 the cable run
should be no more than 328 feet (100 meters).
GX-Series outputs are addressed in the same way as
the zones. However, there are only 4 outputs on each
RIO. The on-board outputs are on RIO 0 and RIO 1.
The addresses are 1001 to 1004 (RIO 0) and 1011 to
1014 (RIO 1).
Note: All individual output programming is done in menu 53.
Zone number
RIO Address
GX-Series zones are given addresses rather than
zone numbers. This is because the zones are
grouped into blocks of 8 called ‘RIOs’. The left
hand digit is the data bus line number. The second
and third digits are the RIO address, which can be
00 to 15. The right hand digit is the individual
zone number on the RIO (1-8). Each zone can also
be given a text descriptor. By default, it is blank.
There are 2 RIOs on board the panel (Line 1). The
first RIO (00) has 8 zones addressed 1001 to 1008
and the second RIO (01) has 8 zones addressed
1011 to 1018.
Note: All individual zone programming is done in menu 52.
Zone Wiring
Output Wiring
With the exception of the 1002, the on-board outputs are
all open-collector switched negative. The load that is to
be controlled by an output should be connected between
+12 V and the output terminal. Output 1002 is a voltagefree relay output. The total maximum load for output
addresses 1001, 1003-1004 and 1011 – 1014 = 400 mA.
The maximum current draw for the +12V AUX outputs is
1A, and for the switched AUX outputs is 400mA (see TB1
– TB6 in the Summary of Connections figure on page 7.)
Dip Switches
The 7 transistorized outputs on the GX-Series can be
configured to open collectors by setting the dip switch
SW3 to the OFF position.
Notes: Wire gauge for field wiring circuits is 22 AWG –
16 AWG (maximum).
Note: Output 2 on RIO 0 (relay output) is not affected. This is a
form C relay that can switch up to 1 amp at 24 volts DC.
The default zone configuration is 1k doublebalanced with fault monitoring via a 3k resistor
(preset 9). In the following configuration a mask
condition is generated if an alarm and fault are
signaled at the same time.
The following table shows which switches control
which outputs.
1k
ZONE
ALARM N/C
3k
TAMPER N/C
FAULT N/C
(SW3)
1
2
3
4
5
6
7
12k
ANTIMASK N/C
1k
RIO
0
0
0
1
1
1
1
Output
1
3
4
1
2
3
4
SW3 Transistorized Output Control
328 FT
GD-001-V0
If no fault output is available, a mask output can
be installed with a 12k resistor as an alternative.
Any unused hardwire zones should always have a
1k resistor wired across the zone terminals to
terminate them.
Note:
Power Wiring
Auxiliary power can be drawn from the terminals
marked +12V. The ‘common’ terminals on the zones
are 0 volts. Terminals marked GND are also 0 volts.
For UL installations, use only the single EOL zone
configurations. Refer to the Installation
Instructions for details.
-2-
Operation
Default User Codes
Default User Code: 12345
Default Engineer (Installer) Code: 112233
Initial Set-up
After all the peripherals have been wired and
addressed remove the card inserted under the
retaining clip on the memory backup.
1. Apply power to the system. About 30 seconds
after power is applied the following display will
appear.
PRESS ANY KEY TO SETUP
2. Press any key to continue. The following
display will appear.
LANGUAGE
1 ENGLISH
3. Press ent to accept English.
DEFAULT
1 UL
4. Press ent to accept UL. The keypads will
configure and show the default banner display.
GX <XXX> <VY.YY>
09:00 SAT 01 JAN
Where: XXX = Panel type, VY.YY = Panel software version.
Memory
The memory backup battery retains the panel
memory for up to 1 year in the event of a complete
power fail. To completely erase the system memory
and return to the default settings, replace a piece
of thin card between the retaining clip and battery
then remove all power to the PCB for one minute.
Re-apply power and remove the card. This is
known as a cold start.
Menu Access Operation/Navigation
Only valid codes can access the GX-Series menu
options. Type the code then press ent to access the
menu. Data entry is via the 0-9 function keys and
the * and # on the keypad.
The A> and <B keys are cursor or scroll keys and are
used to scroll through options in menus.
The ent key is used to enter a PIN code and to accept
screen information.
The esc key is used to cancel or exit from the current
operation.
Note: Users cannot view or access options for which they are
not authorized.
Entering and Exiting Engineer (Installer)
Mode
When the Engineer (Installer) code has been entered
the following will occur:
• All system tampers become isolated.
• The Engineer (Installer) is given access to the full
menu.
• The banner message is changed to indicate
Engineer (Installer) Mode.
To exit Engineer Mode and reinstate all the tampers,
from the banner, enter the Engineer (Installer) code,
but then press the esc key.
Arming and Disarming the System
To Arm (Set) the system in Away mode, the user
enters their code then presses the A> key.
To Arm (Set) the system in Stay mode, the user types
their code then presses the <B key.
To Disarm (Unset) the system, the user types their
code then presses ent. Alternatively, presenting a
valid proximity card at a card reader will also disarm
the system.
Cancelling an Alarm, Tamper or Fault
Alarms, tampers and fault conditions can be cancelled
by entering a user code at a keypad. When the code is
entered, the conditions activated will be displayed. The
scroll keys (A> and <B) can be used to view all the
events. Alarm conditions can also be cancelled by
presenting a valid proximity card at a card reader.
However, a code may need to be entered at a keypad in
order to see and restore the alarms.
Restoring an Alarm
Alarms, tampers and fault conditions will be restored
provided:
• The cause has cleared and
• A user with sufficient authority has viewed the
condition on a keypad.
To reset the system, check first that the condition
itself has actually cleared. Then, from the banner, type
in a valid code and view the condition. Press esc to
finish.
If a user is unable to restore an alarm, then a manager
or engineer (installer) will have to be called, according
to the indication given on the keypad.
-3-
Code Tampers
When enabled (see menu option 51.62 = Lockout),
this parameter controls two things: keypad lockout
and system tamper.
Keypad lockout occurs if a pre-programmed
number of invalid codes (1-10, default 6) are
entered. The lockout lasts for 90 seconds. Each
subsequent invalid attempt causes a further 90
second lockout to occur.
System tamper occurs when a pre-programmed
number of invalid codes (1-21, default 15) are
entered.
Note: The above lockouts also apply to invalid proximity
cards presented to card readers, as well as codes.
Groups (Partitions)
The GX Series has the ability to be split into areas
or subsystems called Groups (Partitions). Each
zone can be assigned to one group (partition).
Users can be assigned to one or many groups. To
enable group mode, turn it on in menu option
63.1.1 = Group (Partition) Mode.
Groups can be assigned to individual users in
menu option 42.1.6 = Modify Groups
(Partitions). This allows users the choice of
which groups to arm and disarm.
Menu Summary
All the functions of the panel are accessible via the
menu. The top level of the menu is summarized
below:
10 = Setting (Arming)
11 = Omit Zones (Bypass Zones)
12 = Timed Set (Timed Arm)
13 = Part Set (Part Arm)
14 = Forced Set (Forced Bypass)
15 = Chime
16 = Instant Set (Away No Delay)
17 = Silent Part
18 = Home Set (Stay)
19 = All Set (All Arm)
40 = Modify
41 = Time/Date
42 = Codes
43 = Dlight Saving
(Daylight Savings)
44 = Trace
45 = Timer Control
46 = Group Omit
(Group Bypass)
47 = Remote Access
48 = Eng. Access
(Installer Access)
20 = Display
21 = Zone Status
22 = Display Log
23 = System (System Version)
24 = Print
25 = Access Doors
30 = Test
31 = Walk Test
32 = Outputs (Output Test)
50 = Engineer
(installer) 1
51 = Parameters
52 = Program Zones
53 = Program O/P
(Program Outputs)
54 = Links
55 = Soak
56 = Communication
60 = Engineer
(Installer) 2
61 = Diagnostics
62 = Full Test
63 = Options
64 = Assemble Zone
65 = Timers
66 = Pre-Check
57 = System Print
58 = Keypad
59 = Quick Menu
67 = Remote Reset
68 = Menu Access
69 = Access Control
70 = Installer
(Installer) 3
71 = SPI Key
(Program Key)
Each of these headings has its own sub options that
can be accessed using the ent, esc and scroll keys (A>
and <B).
The most important menu options are summarized
below:
System Programming
63 = Options
Start with this menu to select Group mode. Group
mode needs to be turned on if the system is to be split
into independent groups.
51 = Parameters
In this menu, all the general parameters are set up,
such as Bell time, entry/exit time, reset levels, and
part set (group arm) signalling parameters. Select
each particular parameter by using the scroll keys (A>
and <B) and press ent to edit the settings for that
parameter. Many parameters will have a separate
setting for each group, if group mode is enabled.
52 = Program Zones
In this menu, the function of each individual zone
input can be customized. Select the zone address using
the scroll keys (A> and <B) and press ent to access the
parameters for that zone.
53 = Program O/P (Outputs)
In this menu, the function of each individual output
can be customized. Select the output address using the
scroll keys (A> and <B) and press ent to access the
parameters for that output.
69 = Access Control
In this menu, door access is controlled by a Door
Control Module (DCM). The Mode needs to be enabled
if proximity cards are to be used with a DCM reader.
56 = Communication
In this menu, Alarm signalling to the ARC can be
configured. First, select the module type from the list
using the scroll keys (A> and <B) then press ent to
access the parameters for that module. The account
number, Telephone no/IP address and format need to
be programmed to enable basic communications.
42 = Codes
In this menu, use the further sub menu called User
Codes to program the attributes of individual users.
Each user on the system can have the following
assigned: PIN code, Proximity card, Type (authority
level) and Group.
To program a Proximity card, first make sure Access
mode is enabled. Next select the user required then
select option 7 Card Number and present the user’s
card to the card reader. The number will enter
automatically.
-4-
Communications
Internal Communications
The GX Series has a built-in telephone dialer. The
incoming telephone line should be wired to the ‘Line A
B’ terminals next to the phone symbol. The alarm panel
should always be the first device on the phone line.
Additional extensions should be connected to the serial
terminals marked ‘PHONE A B’. This will allow the
panel to seize the line when it needs to dial out.
All communications programming is done in menu
56.
Downloading (Remote Servicing)
When using Remote servicing, The System ID field in
menu 51.15.1=System Text should be programmed.
This field is used to identify the panel to the PC
software and is a string up to 16 characters in length.
Typically it can be the installation’s contract number.
The panel is defaulted to only allow connection to
downloading (remote servicing) software, if authorized
via menu 47.1. Set this to Direct access on the
appropriate communication device and dial-in
connection will be authorized for 40 minutes.
Alternatively, a dial out to the downloader (remote
servicing) software can also be initiated from this menu.
Access Control
Door Control Modules (DCMs) can be added onto
the GX-Series bus lines to add fully integrated
access control. Each DCM allows two card readers
to be connected to control two separate doors or
one door with an entry and exit reader.
Group based Access control
Access control works best when Group Mode is
enabled (see above). Each access reader can then
be programmed to control access to a particular
group (or area/subsystem) within the building.
Only users who have access privileges to that
group will be granted access via that reader.
Users and Access Templates
Every user on the system must be allocated an access
template. An access template is a list of groups and
time schedules that will dictate to which groups
and when a user is able to gain access. This method
means that if there are multiple doors leading into
one group or area, then a user will be given access to
all those doors in one move. This reduces
programming time and complexity.
Access Templates are programmed in menu
45.7 = Access Templates. In each Access Template
each group on the system must be allocated a time
schedule as required. If no schedule is allocated to a
particular group (default) in the list then users will
have full access through any doors leading to that
group. When a schedule is allocated, access will be
granted during the OFF periods of the schedule and
denied during the ON periods. Time schedules are
programmed in menu 65 = Timers.
Time schedules
A Time schedule is a weekly list of on and off times and
can be used to control the security of any object to which
it is assigned. When a timer is ON it forces a secure
state (system set (arm), access denied, etc). When a timer
is in the OFF state, it causes an un-secure state
[system unset (disarm) or access allowed, etc]. Up to 28
on or off times can be programmed into each weekly
schedule. Up to 67 schedules are available.
For each time schedule, it is possible to allocate one of
32 Holiday Calendars. A Holiday Calendar is a list of
20 holiday periods, each with a start and end date,
which suspend normal timer operation. During a
holiday period, one of two things can happen.
1. The timer is frozen in its current state (on or off)
and will resume operation from the next event
when the holiday period finishes.
2. An alternate time schedule can be appointed to be
used for the duration of the holiday period.
Panel Specifications
Mechanical
Enclosure
PCB
Width:
17.3 in (440 mm)
10.4 in (265 mm)
Height:
12.8 in (325 mm)
4.7 in (120 mm)
Depth:
3.5 in (88 mm)
Weight:
14.1 lb (6.4 kg)
0.7 lb (0.3 kg)
Operating Temperature: +14°F to +131°F (-10°C to +55°C)
Electrical
AC Input
120 VAC @ 60 Hz
Battery Type
Sealed Lead-Acid (not included)
Max ripple voltage
50.0 mV
Max Current rating*
1.4A
Normal current draw
480 mA
Minimum standby battery capacity required for Max load:
Two 7 Ah batteries required for UL installations.
Aux +12 V outputs
12 V nominal
* Max total +12V output load including Bell output load.
PSTN
V.22 Modem 1200 Baud
RS232
300 – 56k programmable
RS485
9600 Baud, Full Duplex, Asynchronous
The Access Template to be used for each user is
chosen within each user’s options in menu 42.1.11
= Template. There are multiple access templates
available (dependant on panel variant) and each
one is fully customizable.
-5-
Regulatory Agency Statements
FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENT
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS
In the event of telephone operational problems, disconnect the control panel by removing the plug from the RJ31X (CA38A in Canada) wall jack. We recommend that you demonstrate
disconnecting the phones on installation of the system. Do not disconnect the phone connection inside the control panel. Doing so will result in the loss of your phone lines. If the
regular phone works correctly after the control panel has been disconnected from the phone lines, the control panel has a problem and should be returned for repair. If upon
disconnection of the control panel, there is still a problem on the line, notify the telephone company that it has a problem and request prompt repair service. The user may not under any
circumstances (in or out of warranty) attempt any service or repairs to the system. It must be returned to the factory or an authorized service agency for all repairs.
FCC PART 68 NOTICE
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains, among other information, the FCC registration number and
ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company.
This equipment uses the following jacks:
An RJ31X is used to connect this equipment to the telephone network.
The REN is used to determine the quantity of devices that may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in
response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line,
as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
If this equipment causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuance of service may be required. If advance
notice is not practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe
necessary.
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens, the telephone
company will provide advance notice in order for you to make the necessary modifications in order to maintain uninterrupted service.
If trouble is experienced with this equipment, please contact the manufacturer for repair and warranty information. If the trouble is causing harm to the telephone network, the
telephone company may request that you remove the equipment from the network until the problem is resolved.
There are no user serviceable components in this product, and all necessary repairs must be made by the manufacturer. Other repair methods may invalidate the FCC registration
on this product.
This equipment cannot be used on telephone company-provided coin service. Connection to Party Line Service is subject to state tariffs.
This equipment is hearing-aid compatible.
When programming or making test calls to an emergency number, briefly explain to the dispatcher the reason for the call. Perform such activities in the off-peak hours, such as
early morning or late evening.
CANADIAN EMISSIONS STATEMENTS
This Class B digital apparatus complies with Canadian ICES-003
NOTICE
AVIS
The Industry Canada Label identifies certified equipment. This certification means
that the equipment meets telecommunications network protective, operational and
safety requirements as prescribed in the appropriate Terminal Equipment Technical
Requirements document(s). The Department does not guarantee the equipment will
operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be
connected to the facilities of the local telecommunications company. The
equipment must also be installed using an acceptable method of connection. The
customer should be aware that compliance with the above conditions may not
prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative
designated by the supplier. Any repairs or alterations made by the user to this
equipment, or equipment malfunctions, may cause the telecommunications
company to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections
of the power utility, telephone lines, and internal metallic water pipe system, if
present, are connected together. This precaution may be particularly important in
rural areas.
Caution: Users should not attempt to make such connections themselves, but
should contact an appropriate electric inspection authority, or electrician, as
appropriate.
NOTICE: The Ringer Equivalence Number (REN) assigned to each terminal
device provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist of
any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.
L’étiquette d’Industrie Canada identifie le matériel homologué. Cette étiquette
certifie que le matériel est conforme aux normes de protection, d’exploitation et de
sécurité des réseaux de télécommunications, comme le prescrivent les documents
concernant les exigences techniques relatives au matériel terminal. Le Ministère
n’assure toutefois pas que le matériel fonctionnera à la satisfaction de l’utilisateur.
Avant d’installer ce matériel, l’utilisateur doit s’assurer qu’il est permis de le
raccorder aux installations de l’enterprise locale de télécommunication. Le matériel
doit également être installé en suivant une méthode acceptée da raccordement.
L’abonné ne doit pas oublier qu’il est possible que la conformité aux conditions
énoncées ci-dessus n’empêche pas la dégradation du service dans certaines
situations.
Les réparations de matériel nomologué doivent être coordonnées par un
représentant désigné par le fournisseur. L’entreprise de télécommunications peut
demander à l’utilisateur da débrancher un appareil à la suite de réparations ou de
modifications effectuées par l’utilisateur ou à cause de mauvais fonctionnement.
Pour sa propre protection, l’utilisateur doit s’assurer que tous les fils de mise à la
terre de la source d’energie électrique, de lignes téléphoniques et des canalisations
d’eau métalliques, s’il y en a, sont raccordés ensemble. Cette précaution est
particulièrement importante dans les régions rurales.
Avertissement : L’utilisateur ne doit pas tenter de faire ces raccordements luimême; il doit avoir racours à un service d’inspection des installations électriques,
ou à un électricien, selon le cas.
AVIS : L’indice d’équivalence de la sonnerie (IES) assigné à chaque dispositif
terminal indique le nombre maximal de terminaux qui peuvent être raccordés à une
interface. La terminaison d’une interface téléphonique peut consister en une
combinaison de quelques dispositifs, à la seule condition que la somme d’indices
d’équivalence de la sonnerie de tous les dispositifs n’excède pas 5.
WARRANTY INFORMATION
Fort the latest warranty information, please go to:
www.honeywell.com/security/hsc/resources/wa
-6-
RS485
LINE 2
(NOTE 1)
RTS
CTS
RX
TX
+12V
GND
A2
B2
+12V
GND
A1
B1
A
B
A
B
2
12
1
TRIGGER HEAD
(SEE TABLE 1)
ALARM
CONTACT
ZONE WIRING
(FOR ALL ZONE PAIRS)
(TYPICAL)
4
1KΩ
0V
ALARM
CONTACT
3
RIO 0
+12V
5
6
7
0V
8
1
0V
2
3
0V
N/A
N/A
N/A
N/A
N/A
N/A
100 mA
100 mA
100 mA
100 mA
100 mA
100 mA
N/A
N/A
100 mA
4
RIO 1
+12V
5
0V
6
1
ON
2
3
4
0V
8
6
1
7
8
2
RIO 0
3
AUX 3
4
1
SWITCHED 0V OUTPUTS
RIO
SWITCH
3
RIO 1
2
4
** TB6
LOUD SPEAKER
HORN OUTPUT
VOLUME CONTROL
LK4
LK2
GND
+BAT
-BAT
LID
TAMPER 1
LID
TAMPER 2
AC
BLACK
WHITE
INPUT RATING
120VAC, 60 Hz
1.0A MAX
CONNECT TO
A DEDICATED
CIRCUIT
12V 7AH BATTERY
CAPACITY IS
REQUIRED FOR
EMERGENCY
STANDBY FOR AT
LEAST 4 HOURS
FOR UL
INSTALLATIONS
TWO 12V 7AH BATTERIES
ARE REQUIRED
SEE DETAIL
BELOW
BLUE
MODEL 1451
TRANSFORMER
2A
BLUE
ALL CIRCUITS ARE
POWER LIMITED
EXCEPT THE OUTPUT OF
1451 TRANSFORMER
AND THE BATTERY.
DO NOT PLACE JUMPER
OVER 2 PINS.
DEVELOPMENT PURPOSE ONLY
JUMPER MUST BE INSTALLED
SPI
PROGRAM
HEADER
LED 2 Flashes Ethernet Module sending or receiving data
No Communication on RS232 line
Communication between Control Panel and PC
Ethernet Module connected to Ethernet
INDICATION
The on-board Telecom Module monitors the PSTN line
under normal idle state conditions. LED 1 indicates the
communications status.
Line Ringing
Normal indication when
making a call
RELAY
OUTPUT
LID
TAMPER
1
AUX TAMP
GX-SOC-V4
LID
TAMPER
2
DOOR AND REAR TAMPER
(CONNECT AS SHOWN)
TAMPER SWITCH
FOR EXAMPLE
ON EXTERNAL
SIREN
POWERED
12V POWERED LOAD. EG: SIREN,
DETECTOR
WARNING LAMP, ELECTRONIC
LOUND
LOCK, ETC. FOR ALL SWITCHED
SPEAKER
0V OUTPUTS
8-32Ω
NOTE: MAINTAIN
NOTE: MAXIMUM LOAD
1/4" SEPARATION
FOR LOUD SPEAKER IS
OF POWER LIMITED
100 mA DC WITH SPEAKER
AND NON-POWER
IMPEDANCE OF 8Ω
LIMITED CIRCUITS
**NOTE: FOR TB5 AND TB6: TOTAL MAXIMUM CURRENT
DRAW FOR THE SWITCHED AUX OUTPUTS = 400mA.
DETAIL
** TB5
5
No DC supply
Normal Communication
Normal Communication
Failed Communication
Normal Communication
Poor Communication
INDICATION
LED Off
On - 01s, Off- 0.9s
Single pulse at end of call
Flashing at end of alarm call
On during alarm monitoring,
Remote Servicing and SMS
Flickering during alarm monitoring,
Remote servicing and SMS
Flashes in time with ringing signal
Pulses as each digit is dialed
TABLE 3 - COMMUNICATION STATUS
LED (LED 1) STATE
TABLE 4 - LED STATE
ETHERNET LED 1 ON
COMMUNICATION LED 2 ON
2XRS485
STATUS
EXPANSION CARD
LED 2 OFF
PULL-UP (DIP) SWITCHES
RS485 EXPANSION
MODULE STANDOFF
GX SERIES
SUMMARY OF CONNECTIONS
7
SHORT TO PIN 4
PIN 6
INTERFACE
SHORT TO PIN 6
PIN 4
Tx
CTS
PIN 7
Rx
RTS
PIN 8
PIN 2
GROUND
PIN 5
PIN 3
SIGNAL NAME
9W-D
TABLE 2 - RS232 CONNECTIONS
RS-485
EXPANSION
MODULE
GX-520
ONLY
MICRO
PROCESSOR
* TB4
ZONES 1-8 (RIO 0 LINE 1)
ZONES 1-8 (RIO 1 LINE 1
SWITCH SW3-8 OFF)
OR
ZONES 1-8 (RIO 1 LINE 0
SWITCH 3-8 ON)
16 ON-BOARD ZONES
+12V
* NOTES: FOR TB1 - TB4: USE
EOL RESISTOR (1KOHM)
P/N 300-02343 SUPPLIED
IN SAP0166 PACKAGE FOR
UL INSTALLATIONS;
TOTAL MAXIMUM CURRENT
DRAW FOR THE +12V AUX
OUTPUTS = 1A.
0V
* FOR TB1 - TB4: USE
RS232 PORT SOCKET
EOL RESISTOR (1KOHM)
FOR CABLE A234
P/N 300-02343 SUPPLIED
IN SAP0166 PACKAGE
FOR UL INSTALLATIONS.
* TB1
* TB2
* TB3
ENGINEER SOCKET
(RS485 LINE 2)
LED 2 (FOR TELECOMS)
1KΩ
TAMPER
SWITCH
(OPTIONAL)
1
LK5 RS485 LINE 1, 680 Ω TERMINATION
(NOTE 2)
LK3 RS485 LINE 2, 680 Ω TERMINATION
(NOTE 2)
ENGINEER SOCKET
(RS485 LINE 1)
LED 1 (FOR TELECOMS)
0V GND
12
NOT USED
NOT USED
0001
TRIGGER 1
9
10
11
0002
TRIGGER 2
8
0003
TRIGGER 3
7
0004
0005
TRIGGER 4
TRIGGER 5
5
0006
N/A
N/A
6
TRIGGER 6
NOT USED
3
4
NOT USED
2
N/A
MAX. OUTPUT
Memory backup battery replacement:
2. Replace with good battery.
1. Remove memory backup
MEMORY
3. Reconnect mains supply.
battery with a small flat
BACKUP
4. Reconnect 12V battery.
head screwdriver.
BATTERY
BACKUP LITHIUM
BATTERIES ARE TO
BE REPLACED BY
TRAINED SERVICE
PERSONNEL ONLY.
ALTERNATE PHONE
LINE CONNECTION FOR
RJ11 CONNECTORS ‡
1KΩ
1KΩ
UL Applications: Proprietary,
Commercial Central Station,
Local Mercantile Burglar Alarm,
Access Control Unit, Standard
Line Security, Dual Line
Transmission via PSDN and
DACT
9-WAY D-TYPE
CONNECTOR
(FEMALE)
(SEE TABLE 2)
PANEL TERMINALS
TX RX CTS RTS
TIP
RING
TIP
RING
RS485
LINE 1
(NOTE 1)
BROWN
GREY
GREEN
RED
RS232
CONNECTION
TO PC SERIAL
COM PORT
DATA BUS
CONNECTION
FOR PERIPHERAL
MODULES
(MK7 KEYPAD
TOUCHCENTER,
RIO EXPANDER,
ETHERNET MODULE
(LINE 1 ONLY)
DOOR CONTROL
MODULE)
PREMISES
TELEPHONE
(NOTE 5)
INCOMING
TELEPHONE
LINE
WARNING: TO PREVENT RISK
OF SHOCK DISCONNECT
TELEPHONE LINES AT TELCO
JACK BEFORE SERVICING
THIS UNIT.
0V
FOR UL INSTALLATIONS, 26AWG CABLE (MINIMUM) IS REQUIRED FOR TELECO
CONNECTIONS.
NOTE 5:
IC: 573F-GXSERIES
FOR MORE INFORMATION, REFER TO THE FOLLOWING DOCUMENTS:
QUICK INSTALLATION INSTRUCTIONS (P/N 800-05372 REV A)
INSTALLATION INSTRUCTIONS (P/N 800-05928 REV A)
NOTE 4:
NOT EVALUATED BY UL.
WIRING METHOD SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
[ANSI/NFPA70], LOCAL CODES, AND THE AUTHORITIES HAVING JURISDICTION.
NOTE 3:
+12V
OUTPUT ADDRESS
TABLE 1 - TRIGGER HEAD ‡
CONNECTION
1
PIN
SW 3
‡
RS485 DATA BUS LINES MUST USE DAISY CHAIN WIRING BETWEEN MODULES.
EACH END OF THE RS485 DATA BUS MUST BE TERMINATED WITH A 680 OHM
RESISTOR ACROSS THE A&B WIRES. IF THE PANEL DOES NOT FORM ONE END
OF THE BUS, REMOVE THE LINK TO DISABLE THE 680 OHM RESISTOR.
+12V
BATTERY
STARTUP
NOTE 1:
N/0
OFF WALL
TAMPER
NOTE 2:
N/C
-7-
N/C
PHONE
+12V
LINE
GLOSSARY
Term
Meaning
Term
Meaning
DCM
Door Control Module
RIO
Engineer
ent
esc
Prox Reader
Security System Installer
Enter key
Escape key
Proximity card reader
Set / Setting
Unset / Unsetting
User Type
Remote Input Output
Module
Arm(ed) / Arming
Disarm(ed) / Disarming
User (Authority) Level
Prox tag
Proximity card
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
Copyright © 2010 Honeywell International Inc.
www.honeywell.com/security
Ê800-053722Š
800-05372 9/10 Rev. B
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement