Level FA Series 10 - 100 kVA 208 Vac 3ph/3ph
ONLINE UPS
Level FA Series 10 - 100 kVA
208 Vac 3ph/3ph
True three level rectifier and
inverter technology. On-line
double conversion Class
VFI-SS-111 performance with
multi-language LCD screen
display.
3ph/1ph version available
(10-15kVA)
FEATURES
Low energy consumption and cost of ownership
Low energy consumption with max efficiency of 96%
Input power factor of 0.99% minimizes energy consumption and hardware installation costs
Clean power
True on-line double conversion with sine wave output and a power factor of 1kVA = 1kW
Power factor corrected IGBT rectifier minimizes input current THD to less than 3%
Advanced battery management
Maximizes battery life with intelligent temperature compensated charging
Displays estimated battery backup and tests for battery capacity
Flexible and reliable
Dual input connects UPS to backup generator and mains
Parallel operation with current sharing of up to 8 units
Reverse energy tolerant of regenerative loads
Static and manual (maintenance) bypass
Power Options
Isolation transformer
Internal battery configurations
External battery cabinets
Parallel cable
Management Options
UPS management PC software
SNMP card
Dry contact card
RS485 serial port
Modbus card
External battery temperature sensor
keatecenergy.com
[email protected]
ONLINE UPS
Level FA Series 10 - 100 kVA
208 Vac 3ph/3ph
SPECIFICATIONS
Model
Capacity kVA
10
Power kW (PF 1.0)
10
Internal battery (option)
Weight Kg (w/o battery)
15
20
30
40
50
60
80
100
15
20
30
40
50
60
80
100
450
485
34 x 9Ah
107
Dimensions
W x D x H mm
external battery cabinet
118
125
490 x 805 x 1190
260
270
763 x 771 x 1555
350
355
810 x 820 x 1705
830 x 870
x 1800
AC Input
Input voltage
110/200V or 120/208V or 127/220V +20% [(L-N)/(L-L)] 3P+N+PE
Input power factor
>0.99% at full load
input frequency
45 - 65 Hz (selectable)
THD
<3%
AC Output
Output voltage
110/200V or 120/208V or 127/220V +1% [(L-N)/(L-L)] 3 Phase+N
Recovery
0% - 100% - 0% load, maximum output tolerance 5%, 1% back to band <40ms
Efficiency
Up to 96% (Eco Mode 98%)
Output frequency
+0.5% synchronous with the network / 50/60 Hz + 0.2% battery mode
THD
<2% linear load, <5% non-linear load
Crest factor
3:1
Overload capacity
125% 10 min, 150% 1 min
External Battery Requirements
DC nominal
+/- 102 Vdc
Series configuration
17 x 12 Vdc (VRLA)
Charge value
nominal 0.1 C (adjustable)
Battery power
25% of UPS power
Communication
Communication
RS232, parallel port (2), parallel cable (1), (expansion slots (2)
Protocol
SEC, TELNET, MODBUS (optional)
General Specifications
Parallel operation
Up to 8 units, active current sharing
Temperature
Operating 0 to +40° C (32 to +104° F), Storage -15 to +45° C (5 to +113° F)
Altitude
<1000 m correction factor 1.0. <2000 m correction factor 0.92, <3000 m correction factor 0.84
Humidity
≤95% non‑condensing
Standards
Performance
EN 62040-3 (VFI-SS-111)
EMC/LVD
EN 62040-2 / EN 62040-1 / EN 60950
© Keatec Energy. All rights reserved. Keatec Energy reserves the right to change specifications without notice.