E-Series™Rooftop Units 26 to 44 kW (7.5 to 12.5 Ton) Net Cooling

E-Series™Rooftop Units 26 to 44 kW (7.5 to 12.5 Ton) Net Cooling
PA C KA G E D E L E C T R I C / E L E C T R I C
LCH
E-Series™ Rooftop Units
50 HZ
Bulletin No. LCH-092-150-50HZ (4/2016)
P R O D U C T S P E C I F I C AT I O N S
26 to 44 kW (7.5 to 12.5 Ton)
Net Cooling Capacity − 23.7 to 36.7 kW (81 000 to 125 300 Btuh)
Optional Electric Heat − 5.7 to 45.9 kW
MODEL NUMBER IDENTIFICATION
L C H 120 H 4 B N 1 M
Brand/Family
L = E-Series™
Voltage
M = 380/420V-3 phase-50hz
Unit Type
C = Packaged Electric Cooling w/ optional Electric Heat
Major Design Sequence
H = 1st Generation
Nominal Cooling Capacity - Tons
092 = 26 kW
102 = 30 kW
120 = 35 kW
150 = 44 kW
Cooling Efficiency
H = High Efficiency
S = Standard Efficiency
Minor Design Sequence
1 = 1st Revision
2 = 2nd Revision
3 = 3rd Revision
Factory Installed Electric Heat
N = No Heat
C = 5.7 kW Electric Heat
E = 11.5 kW Electric Heat
G = 17.2 kW Electric Heat
J = 23 kW Electric Heat
K = 34.5 kW Electric Heat
L = 45.9 kW Electric Heat
Blower Type
B = Belt Drive
Refrigerant Type
4 = R-410A
FEATURES AND BENEFITS
E
D
K
C
G
J
I
L
H
B
F
Unit shown with
optional
Economizer with
Outdoor Air Hoods
E-Series™ packaged rooftop unit product line was created to save energy with intelligence by offering some
of the highest energy efficiency ratings available with a powerful, easy to use unit controller. This makes
E-Series™ rooftop units perfect for business owners looking for a Heating/Ventilation/Air Conditioning
(HVAC) product with the lowest total cost of ownership. E-Series™ rooftop units feature:
•
•
•
•
•
•
•
•
•
•
•
Hinged Access Panels - Provide quick access to components and protect panels and roof from damage
during servicing.
Isolated Compressor Compartment - Allows performance check during normal compressor operation
without disrupting airflow.
Corrosion-Resistant Removable, Reversible Drain Pan - Provides application flexibility, durability and
improved serviceability.
Thermostatic Expansion Valves - Provide peak cooling performance across the entire application range.
Scroll Compressors - Standard on all units for reliable, long-term operation.
Eco-Last™ Coil System - Smaller, lighter condenser coil.
Dehumidification System - Patented system allows for independent control of temperature and humidity,
providing enhanced comfort control.
Auto-Tensioner for Blower Belt - Factory option ensures blower is delivering the proper airflow for
comfort, while maximizing efficiency and belt life.
MERV 13 (Minimum Efficiency Rating Value) Filters - Available as factory or field option and provides
an enhanced level of indoor air quality.
Foil-Faced Insulation - Insulation on all internal surfaces that have contact with airflow helps minimize
airborne fibers and improve indoor air quality (IAQ).
Common Components - Many maintenance items are standard throughout the entire product line,
reducing the need to carry different parts to the job or maintain in inventory.
Intelli-Guide™ Control System
Standard on every E-Series rooftop unit, the Intelli-Guide™ unit controller is the center of the Intelli-Guide™
Control System. The intuitive user interface makes setup, troubleshooting and service easier than ever.
Each unit tracks the runtime of every major component and records the date and time when service or
maintenance is performed.
WireRight™ System
The WireRight™ System simplifies field sensor or thermostat installation through advanced connectors that are
keyed and color-coded to help prevent miswiring. Not only is the wire coloring scheme standardized across all
models, each connection is intuitively labeled to make troubleshooting and servicing quick and easy.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 2
FEATURES AND BENEFITS
CONTENTS
Blower Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensions - Accessories . . . . . . . . . . . . . . . . . . . . . . . . . 27
Dimensions - Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Electrical/Electric Heat Data . . . . . . . . . . . . . . . . . . . . . . . . 22
Electric Heat Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Features And Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Dehumidification System Ratings . . . . . . . . . . . . . . . . . . . . . 17
Options / Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Outdoor Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Intelli-Guide™ Control System . . . . . . . . . . . . . . . . . . . . . . . .7
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
PERFORMANCE/QUALITY
Components bonded for grounding
to meet safety standards for
servicing required by Underwriters
Laboratories (UL) and the
International Electrotechnical
Commission (IEC).
Cooling performance is rated
at test conditions included in
Air-Conditioning, Heating and
Refrigeration Institute (AHRI)
Standard 340/360-2007 while
operating at rated voltage and air
volumes.
International Organization for
Standardization (ISO) 9001
Registered Manufacturing Quality
System.
CE MARK OPTION
The CE mark has
been added to our
rooftop product line
as a configure to
order (CTO) option. This optional
construction allows units to be sold
into countries requiring CE marking
for rooftop products.
CE marked units meet the
requirements of the Machinery
Directive 2006/42/EC, Low
Voltage Directive 73/23/EEC, EMC
Directive 89/336/EEC, and Gas
Directive 90/396/EEC. Declaration
of conformity certificates will be
provided for each CE marked unit
on demand.
Key features of this option over
and above standard product
features are:
• Touch-proof electrical
components meeting the
requirements of EN 60529.
• B ranch circuits over 0.5
kW load have overcurrent
protection.
• R otary style/finger safe
disconnect switch with locking
handle prevents disconnect
door from being opened with
the power on. Padlock can be
applied to lock the disconnect
switch in the OFF position.
• T he factory wiring has been
redesigned for separation of
high and low voltage circuits.
COOLING SYSTEM
Designed to maximize sensible
and latent cooling performance at
design conditions.
System can operate from -18°C
to 52°C without any additional
controls.
R-410A Refrigerant
Non-chlorine based, ozone
friendly, R-410A.
B Scroll Compressors
Scroll compressors on all models
for high performance, reliability and
quiet operation.
Resiliently mounted on rubber
grommets for quiet operation.
Compressor Crankcase Heaters
Protects against refrigerant
migration that can occur during low
ambient operation.
Thermal Expansion Valve
Assures optimal performance
throughout the application range.
Removable element head.
Filter/Driers
High capacity filter/drier protects
the system from dirt and moisture.
High Pressure Switches
Protects the compressors from
overload conditions such as
dirty condenser coils, blocked
refrigerant flow, or loss of outdoor
fan operation.
Low Pressure Switches
Protects the compressors from
low pressure conditions such as
low refrigerant charge, or low/no
airflow.
Freezestats
Protects the evaporator coil from
damaging ice build-up due to
conditions such as low/no airflow,
or low refrigerant charge.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 3
FEATURES AND BENEFITS
COOLING SYSTEM
(continued)
C Eco-Last™ Coil System
Condenser
coil features
lightweight,
all aluminum
brazed fin
construction.
Constructed
of three
components:
a flat extrusion tube, fins inbetween the flat extrusion tube and
two refrigerant manifolds.
Eco-Last™ Coil System Features:
• Improved heat transfer
performance due to high
primary surface area (flat
tubes) versus secondary
surface (fins).
• Smaller internal volume
(reduced refrigerant charge).
• High durability (all aluminum
construction).
• Fewer brazed joints.
• Compact design (reduces unit
weight).
• Easy maintenance/cleaning.
Face-split design.
Mounting brackets with rubber
inserts secure coil to unit providing
vibration dampening and corrosion
protection.
Evaporator Coil
Copper tube construction,
enhanced rippled-edge aluminum
fins, flared shoulder tubing
connections, silver soldered
construction for improved heat
transfer.
Cross row circuiting with rifled
copper tubing optimizes both
sensible and latent cooling
capacity.
Condensate Drain Pan
Plastic pan with positive slope.
Side or bottom drain connections.
Reversible to allow connection at
back of unit.
D Outdoor Coil Fan Motors
Thermal overload protected, totally
enclosed, permanently lubricated
ball bearings, shaft up, wire basket
mount.
Outdoor Coil Fans
Polyvinyl chloride (PVC) coated
fan guard furnished.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 4
Required Selections
Cooling Capacity
Specify nominal cooling capacity of
the unit
Options/Accessories
Factory Installed
Conventional Fin/Tube
Condenser Coil
(replaces Eco-Last™ Coil
System)
Copper tube construction,
enhanced rippled-edge aluminum
fins, flared shoulder tubing
connections, silver soldered
construction.
NOTE - Required if
Dehumidification System is
ordered.
Service Valves
Fully serviceable brass valves
installed in discharge & liquid lines.
Not available for units equipped
with Eco-Last™ Coil System or
Dehumidification option.
Factory or Field Installed
Condensate Drain Trap
Available in copper or polyvinyl
chloride (PVC).
Field installed only, may be factory
ordered to ship with unit.
Drain Pan Overflow Switch
Monitors condensate level in
drain pan, shuts down unit if drain
becomes clogged.
FEATURES AND BENEFITS
CABINET
E Construction
Heavy-gauge steel panels and full
perimeter heavy-gauge galvanized
steel base rail provides structural
integrity for transportation,
handling, and installation.
Base rails have rigging holes.
Three sides of the base rail have
forklift slots.
Raised edges around duct and
power entry openings in the bottom
of the unit provide additional
protection against water entering
the building.
Airflow Choice
Units are shipped in downflow
(vertical) configuration, can be field
converted to horizontal airflow with
optional Horizontal Discharge Kit.
Duct Flanges
Provided for horizontal duct
attachment.
Power Entry
Electrical lines can be brought
through the unit base or through
horizontal access knock-outs.
Exterior Panels
Constructed of heavy-gauge,
galvanized steel with a two-layer
enamel paint finish.
Required Selections
Airflow Configuration
Specify downflow or horizontal.
Options / Accessories
Return Air Adaptor Plate
For same size LC/LG/LH and TC/
TG/TH unit replacement.
Installs on return air opening in
unit to match return air opening
on existing roof curbs. Also see
Accessory Air Resistance table.
Factory Installed
Corrosion Protection
A completely flexible immersed
coating with an electrodeposited
dry film process. (AST ElectroFin
E-Coat) Meets Mil Spec
MIL-P-53084, ASTM B117
Standard Method Salt Spray
Testing.
Indoor Corrosion Protection:
• Coated coil
• Coated reheat coil
• Painted blower housing
• Painted base
Outdoor Corrosion Protection:
• Coated coil
• Painted base
Field Installed
Combination Coil/Hail Guards
Heavy gauge steel frame painted
to match cabinet with expanded
metal mesh to protect the outdoor
coil from damage.
Horizontal Discharge Kit
Consists of duct covers to block
off downflow supply and return
air openings for horizontal
applications.
Also includes return air duct
flanges for end return air when
economizer is used in horizontal
applications.
NOTE - When configuring unit
for horizontal application with
economizer, a separate Horizontal
Barometric Relief Damper with
Hood must be ordered separately
for installation in the return air duct.
Insulation
All panels adjacent to conditioned
air are fully insulated with nonhygroscopic fiberglass insulation.
Unit base is fully insulated. The
insulation also serves as an air
seal to the roof curb, eliminating
the need to add a seal during
installation.
F Hinged Access Panels
Hinged tool-less access panels
are provided for the filter section,
blower/heating section and
compressor/controls section.
All hinged panels have seals and
quarter-turn latching handles to
provide a tight air and water seal.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 5
FEATURES AND BENEFITS
G BLOWER
A wide selection of supply air
blower options are available
to meet a variety of airflow
requirements.
Motor
Overload protected, equipped with
ball bearings. Belt drive motors
are offered on all models and are
available in several different sizes
to maximize air performance.
Supply Air Blower
Forward curved blades, double
inlet, blower wheel is statically and
dynamically balanced. Equipped
with ball bearings and adjustable
pulley (allows speed change).
Blower assembly slides out of unit
for servicing.
Required Selections
Order blower motor horsepower
and drive kit number required
when base unit is ordered, see
Drive Kit Specifications Table.
Supply Air Blower
Forward curved blades, blower
wheel is statically and dynamically
balanced.
All belt drive motors have
adjustable pulley for speed
change.
Ordering Information
Specify motor horsepower and
drive kit number when base unit is
ordered.
Options/Accessories
ELECTRICAL
WireRight™ System
Advanced wiring connectors are
keyed and color-coded to prevent
miswiring. Wire coloring scheme
is standardized across all models.
Each connection is intuitively
labeled to make troubleshooting
and servicing quick and easy.
Electrical Plugs
Positive connection electrical plugs
are used to connect common
accessories or maintenance parts
for easy removal or installation.
Options / Accessories
Factory or Field Installed
H Electric Heat
Electric heat is CE marked.
Helix wound nichrome elements,
individual element limit controls,
wiring harness. Unit fuse block
is furnished as standard. See
Options / Accessories tables for
ordering information.
INDOOR AIR QUALITY
I Air Filters
Disposable 51 mm filters furnished
as standard.
Options / Accessories
Factory or Field Installed
High Efficiency Air Filters
Disposable MERV 8 or MERV 13
(Minimum Efficiency Reporting
Value based on ASHRAE 52.2)
efficiency 51 mm pleated filters.
Factory Installed
Blower Belt Auto-Tensioner
Provides proper tension to belt
drive blower belt without the need
for regular adjustments. Maintains
airflow and proper performance.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 6
UVC Germicidal Lamps
Germicidal lamps emit ultra-violet
(UV-C) energy, which has been
proven to be effective in reducing
microbes such as viruses, bacteria,
yeasts, and molds. This process
either destroys the organism or
controls its ability to reproduce.
UV-C energy greatly reduces the
growth and proliferation of mold
and other bioaerosols (bacteria
and viruses) on illuminated
surfaces (particularly coil and drain
pan).
Lamps are field installed in the
blower/evaporator coil section.
All necessary hardware for
installation is included.
Lamps operate on 220V singlephase power supply. Step-down
transformer may be ordered
separately for 380/420V primary to
220V secondary units. Alternately,
220V power supply may be used to
directly power the UVC ballast(s).
Magnetic safety interlock
terminates power when access
panels are removed.
Options / Accessories
Field Installed
Indoor Air Quality (CO2) Sensors
Monitors CO2 levels, reports to the
Intelli-Guide™ unit controller which
adjusts economizer dampers as
needed.
Replacement Filter Media Kit
With Frame
Replaces existing pleated filter
media. Includes washable metal
mesh screen and metal frame with
clip for holding replaceable nonpleated filter.
Intelli-Guide™ CONTROL SYSTEM
J INTELLI-GUIDE™
CONTROLLER
UNIT
DDC Compatible
supermarkets.
Dirty Filter Switch Input
On Demand Dehumidification Monitors and controls condenser
hot gas reheat operation with
dehumidfication option.
Discharge Air Temperature
Control
Display/Sensor Readout
The Intelli-Guide™ unit controller is
a microprocessor-based controller
that provides flexible control of all
unit functions.
Economizer Control Options See Economizer / Outdoor Air /
Exhaust Options.
Fresh Air Tempering
Features:
Extensive Unit Diagnostics Over 100 diagnostic and status
messages in English.
LCD Display - Easy to read menu
with buttons for menu navigation.
during setup and diagnostics. 4
lines x 20 character display.
Exhaust Fan Control Modes Fresh air damper position.
Menu LEDs - Four LEDs (Data,
Setup, Service, Settings) aid in
menu navigation.
Permanent Diagnostic Code
Storage
Field Adjustable Control
Parameters - Over 200 different
control settings.
Main Menu and Help Buttons Quick navigation to home screen
and built-in help functions.
Scroll, Value Adjustment Select
and Save Buttons
Simplified Setup Procedure SETUP menu insures proper
installation and setup of the rooftop
unit.
Profile Setup - Copy key settings
between units with the same
configuration greatly reducing
setup time.
USB Port - Allows a
technician to
download and transfer
unit information to
help verify service
was performed.
USB drive will also allow updating
software on the Intelli-Guide™
Control System to obtain enhanced
functionality without the need to
change components.
Unit Controller Software
Unit Self-Test - Unit controller can
perform a rooftop unit self-test to
verify individual critical component
and system performance. Included
is an economizer test function that
helps assure the economizer is
operating correctly.
Time Clock with Run-time
Information
Built-In Functions Include:
Adjustable Blower On/Off Delay
Built-in Control Parameter Defaults
Compressor Time-Off Delay
Indoor Air Quality Input Demand Control Ventilation ready
Low Ambient Controls - Cooling
operation down to 0°F.
Gas Valve Time Delay Between
First and Second Stage
Minimum Compressor Run Time
Network Capable - Can be daisy
chained to other units or controls.
Night Setback Mode
Return Air Temperature Limit
Control
Safety Switch Input - Allows
Controller to respond to a external
safety switch trip.
Service Relay Output
Smoke Alarm Mode - Four
choices (unit off, positive pressure,
negative pressure, purge).
Staging - Up to 2 heat/2 cool
(standard Intelli-Guide™ unit
controller thermostat input). Up to
3 cool with additional relay. Up to 4
cool with room sensor or network
operation.
“Strike Three” Protection
Gas Reheat Control Simultaneous heating and cooling
operation for controlling humidity
for process air applications such as
NOTE - Intelli-Guide™ Control System
features shown vary with the type of
rooftop unit the control is installed in.
NOTE - See separate Intelli-Guide™
Control System Product Specifications
Bulletin for additional information.
Thermostat Bounce Delay
Warm Up Mode Delay
LED Indicators
PC Interface - Connect to the
Intelli-Guide™ unit controller from
a PC with the Allied unit controller
Software.
Room Sensor Operation Controls temperature.
Options / Accessories
Factory or Field Installed
Blower Proving Switch
Monitors blower operation, shuts
down unit if blower fails.
Dirty Filter Switch
Senses static pressure increase
indicating dirty filter condition
Controls Options
Factory or Field Installed
Fresh Air Tempering
Used in applications with high
outside air requirements. The
Controller energizes the first stage
heat as needed to maintain a
minimum supply air temperature
for comfort, regardless of the
thermostat demand. When ordered
as a factory option, the sensor
ships with the unit but must be field
installed.
Smoke Detector
Photoelectric type, installed in
supply air section, return air
section or both sections. Available
with power board and single
sensor (supply or return) or power
board and two sensors (supply and
return). Power board located in unit
control compartment.
Interoperability via BACnet® or
LonTalk® Protocols
Communication compatible with
third-party automation systems that
support the BACnet Application
Specific Controller device
profile, LonMark® Space Comfort
Controller functional profile, or
LonMark Discharge Air Controller
functional profile.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 7
OPTIONS / ACCESSORIES
Controls Options (continued)
Commercial Control Systems
Aftermarket DDC
Novar® ETM module and options.
Thermostats
Control system and thermostat
options. Aftermarket unit controller
options.
Field Installed
General Purpose Control Kit
Plug-in control provides additional
analog and digital inputs/outputs
for field installed options.
Humidity Sensor Kit
Humidity sensor required with
factory installed dehumidification
option or Supermarket reheat field
selectable option.
K ECONOMIZER OPTIONS
Standard and High Performance
Models available.
Economizer operation is set and
controlled by the Intelli-Guide™
unit controller.
Simple plug-in connections from
economizer to unit controller for
easy installation.
Optional sensors may be used
instead of unit sensors to
determine whether outdoor air
is suitable for free cooling. See
Options/Accessories table.
Factory or Field Installed
Economizer
(Standard and High Performance
Common Features)
Downflow or Horizontal with
Outdoor Air Hood.
Outdoor Air Hood is included when
economizer is factory installed and
is furnished with economizer when
ordered for field installation.
L Downflow Barometric Relief
Dampers with Exhaust Hood is
also furnished.
Standard Economizer Features
Gear-driven action, return air
and outdoor air dampers, plugin connections to unit, nylon
bearings, neoprene seals, 24-volt,
fully-modulating spring return
motor.
NOTE: The Free Cooling default
setting for outdoor air temperature
sensor is 13°C.
High Performance
Economizer Features
Gear-driven action, high torque
24-volt fully-modulating spring
return damper motor, return air
and outdoor air dampers, plug-in
connections to unit, stainless steel
bearings, enhanced neoprene
blade edge seals and flexible
stainless steel jamb seals to
minimize air leakage.
Refer to Installation Instructions for
complete setup information.
Differential Sensible Control
Factory setting. Uses outdoor air
and return air sensors that are
furnished with the unit. The IntelliGuide™ unit controller compares
outdoor air temperature with return
air. When the outdoor air is below
the configured setpoint and cooler
than return air, the controller
activates the economizer.
NOTE - Differential Sensible
Control can be configured in the
field to provide Offset Differential
Sensible Control or Single
Sensible Control.
In Offset Differential Sensible
Control mode, the economizer
is enabled if the temperature
differential (offset) between
outdoor air and return air reaches
the configured setpoint.
In Single Sensible Control mode,
the economizer is enabled when
outdoor air temperature falls below
the configured setpoint.
Global Control
The unit controller communicates
with a DDC system with one global
sensor (enthalpy or sensible) to
determine whether outside air is
suitable for free cooling on all units
connected to the control system.
Sensor must be field provided.
Factory or Field Installed
Single Enthalpy Temperature
Control
Outdoor air enthalpy sensor
enables Economizer if the outdoor
enthalpy is less than the setpoint of
the control.
Differential Enthalpy Control
Order two Single Enthalpy
Controls. One is field installed in
the return air section, the other
in the outdoor air section. Allows
the economizer control to select
between outdoor air or return air,
whichever has lower enthalpy.
Field Installed
Outdoor Air CFM Control
Maintains constant outdoor air
volume levels on the supply air
fan and varying unit airflows.
Using information from a velocity
sensor located in the rooftop
unit outdoor air section, the unit
controller changes the economizer
position to help minimize the effect
of supply fan speed changes
on outdoor air volume levels.
Setpoint for outdoor air volume is
established by field testing.
NOTE - Not available with Demand
Control Ventilation (CO2 Sensor)
or Building Pressure Control.
Building Pressure Control
Maintains constant building
pressure level.
Using information from a
differential pressure between
the outdoor air and the building
air, the unit controller changes
the economizer position to help
maintain a constant building
pressure.
NOTE - Not available with Demand
Control Ventilation (CO2 Sensor)
or Outdoor Air CFM Control.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 8
OPTIONS / ACCESSORIES
EXHAUST OPTIONS
Factory or Field Installed
Power Exhaust Fans
Installs internal to unit for downflow
applications only with Economizer
option. Provides exhaust air
pressure relief. Interlocked to
run when supply air blower is
operating, fans run when outdoor
air dampers are 50% open
(adjustable), motor is overload
protected. Requires Economizer
and Downflow Barometric Relief
Dampers. Fan is 508 mm diameter
with 5 blades (K1PWRE10B) with
0.25 kW motor.
Field Installed
Horizontal Low Profile
Barometric Relief Dampers
For use when unit is configured for
horizontal applications requiring an
economizer.
Allows relief of excess air.
Aluminum blade dampers prevent
blow back and outdoor air
infiltration during off cycle.
Field installed in return air duct.
Bird screen and exhaust hood
furnished.
Requires Horizontal Discharge Kit.
OUTDOOR AIR OPTIONS
Factory or Field Installed
Outdoor Air Damper - Downflow
or Horizontal With Air Hood
Linked mechanical dampers, 0 to
25% (fixed) outdoor air adjustable,
installs in unit. Includes outdoor air
hood.
Automatic model features fully
modulating spring return damper
motor with plug-in connection.
Manual model features a slide
damper.
Maximum mixed air temperature in
cooling mode: 38°C.
ROOF CURBS
Nailer strip furnished, mates
to unit, US National Roofing
Contractors Approved, shipped
knocked down.
Hybrid Roof Curbs, Downflow
Roof curb can be assembled using
interlocking tabs to fasten corners
together. No tools required.
Curb can also be fastened together
with furnished hardware.
Available in 203, 356, 457, and
610 mm heights.
See Options/Accessories table.
Adjustable Pitch Curb
Fully adjustable pitch curb provides
a level platform for rooftop units
allowing flexible installations
on roofs with uneven or sloped
angles.
Maximum slope is 19 mm per 300
mm in any direction.
Uses interlocking tabs to fasten
corners together. No tools required.
Hardware is furnished to connect
upper curb with lower curb.
Available in 356 mm height.
CEILING DIFFUSERS
Ceiling Diffusers
(Flush or Step-Down)
Aluminum grilles, large center
grille, insulated diffuser box with
flanges, hanging rings furnished,
interior transition (even air flow),
internally sealed (prevents
recirculation), adapts to T-bar
ceiling grids or plaster ceilings.
Transitions (Supply and Return)
Used with diffusers, installs
in roof curb, galvanized steel
construction, flanges furnished for
duct connection to diffusers, fully
insulated.
Adaptor Curbs (not shown
Curbs are regionally sourced.
Dimensions will vary based
upon the source. Contact your
local sales representative for a
detailed cut sheet with applicable
dimensions.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 9
OPTIONS / ACCESSORIES
DEHUMIDIFICATION SYSTEM
NOTE - Not available with
Eco-Last™ Coil System.
Conventional Fin/Tube
condenser coil must be ordered
as a factory option.
Factory installed option designed
to control humidity.
Provides dehumidification on
demand using American Society
of Heating, Refrigeration and Air
Conditioning Engineers (ASHRAE)
90.1 recommended method for
comfort conditioning humidity
control.
Unit comes equipped with one row
reheat coil, solenoid valve and
humidity controller.
In addition to a thermostat or room
sensor used for conventional
operation, a humidity sensor is
required and must be located
in the occupied space. Remote
Mounted Humidity Sensor Kit is
required for field installation.
The humidity sensor provides
input to the unit controller which
is used to control activation of the
dehumidification operation.
Reheat controls are located in the
compressor control section of the
unit for easy access.
Benefits
Improves indoor air quality.
Helps prevents damage due to
high humidity levels.
Improves comfort levels by
reducing space humidity levels.
OPERATION
No Dehumidification Demand
The unit will operate conventionally
whenever there is a demand
for cooling or heating and no
dehumidification demand.
Free cooling is only permitted
when there is no demand for
dehumidification.
Dehumidification Demand Only
The unit controller is factory set
at 60% relative humidity setpoint
and can be adjusted at the unit
controller or with optional unit
controller software.
Reheat operation will initiate on a
dehumidification demand and does
not require a cooling demand.
The unit will operate in the
dehumidification mode until the
relative humidity of the conditioned
space is below the setpoint.
The reheat coil is sized to provide
20°C to 24°C supply air during
reheat operation.
This reduces sensible cooling
capacity and extends compressor
run time to control humidity when
the cooling load is low.
A solenoid valve diverts hot gas
from the compressor to the reheat
coil.
The cooled and dehumidified air
from the evaporator is reheated as
it passes through the reheat coil.
The de-superheated and partially
condensed refrigerant continues to
the outdoor condenser coil where
condensing is completed. The
unit will continue to operate in this
mode until the dehumidification
demand is satisfied.
See Sequence of Operation for
additional information.
Dehumidification and Cooling
Demand (Thermostat/Room
Sensor Application)
If both a dehumidification and a
full cooling load demand occur, the
system will operate in cooling until
the cooling demand is satisfied.
Then the system will energize the
dehumidification mode.
Options / Accessories
REFRIGERANT SCHEMATIC
EVAPORATOR
COIL
CONDENSER COIL
Humidity Sensor Kit
Remote Mounted Humidity sensor
required with factory installed
Option or Supermarket reheat field
selectable option.
REHEAT
COIL
REFRIGERANT
CIRCUIT 1
REFRIGERANT
CIRCUIT 2
REHEAT
VALVE
CHECK
VALVE
EXPANSION
VALVES
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 10
OPTIONS / ACCESSORIES
Model
Number
Item Description
Unit Model No
Catalog
Number 092 102 120 150
CE MARK
CE Marked Unit
Factory
O
O
O
O
76W26
OX
OX
OX
OX
COOLING SYSTEM
Condensate Drain Trap
Polyvinyl Chloride (PVC) - C1TRAP20AD2
76W27
OX
OX
OX
OX
Conventional Fin/Tube Condenser Coil (replaces Eco-Last™ Coil System)
Factory
O
O
O
O
Corrosion Protection
Factory
O
O
O
O
Copper - C1TRAP10AD2
68W88
OX
OX
OX
OX
Refrigerant Type
R-410A
O
O
O
O
Service valves (not for Eco-Last™ Coil System or equipped units)
Factory
O
O
O
O
Belt Drive - 1.5 kW (2 hp)
Factory
O
O
O
O
Belt Drive - 2.2 kW (3 hp)
Factory
O
O
O
O
Belt Drive - 3.7 kW (5 hp)
Factory
O
O
O
O
Drive Kits
Kit #1 490 - 740 rev/min
Factory
O
O
O
O
See Blower Data Tables for selection
Kit #2 665 - 920 rev/min
Factory
O
O
O
O
Kit #3 660 - 995 rev/min
Factory
O
O
O
O
Drain Pan Overflow Switch
E1SNSR71AD1
BLOWER - SUPPLY AIR
Motors
Kit #7 610 - 810 rev/min
Factory
O
O
O
O
Kit #8 780 - 1000 rev/min
Factory
O
O
O
O
Kit #9 845 - 1085 rev/min
Factory
O
O
O
O
Kit #10 750 - 945 rev/min
Factory
O
O
O
O
Kit #11 865 - 1095 rev/min
Factory
O
O
O
O
Kit #12 940 - 1190 rev/min
Factory
O
O
O
O
Blower Belt Auto-Tensioner
Factory
O
O
O
O
CABINET
Eco-Last™ Coil System - C1GARD52B-1
13T05
X
X
X
X
Conventional Fin/Tube Condenser Coil - E1GARD51B-1
13T04
X
X
X
X
Horizontal Discharge Kit
K1HECK00B-1
51W25
X
X
X
X
Return Air Adaptor Plate (for L Series® and T-Class™ replacement)
C1CONV10B-1
54W96
OX
OX
OX
OX
C1SNSR35FF1
53W65
OX
OX
OX
OX
Intelli-Guide™ System - BACnet® Module - C0CTRL60AE1L
59W51
OX
OX
OX
OX
Intelli-Guide™ System - LonTalk® Module - C0CTRL65FF1
54W27
OX
OX
OX
OX
Combination Coil/Hail Guards
CONTROLS
Blower Proving Switch
Commercial Controls
General Purpose Control Kit
E1GPBK30C1
13J78
X
X
X
X
Dirty Filter Switch
E1SNSR55B-1
53W67
OX
OX
OX
OX
C1SNSR75AD1
58W63
OX
OX
OX
OX
Smoke Detector - Supply or Return (Power board and one sensor)
C1SNSR44B-2
11K76
OX
OX
OX
OX
Smoke Detector - Supply and Return (Power board and two sensors)
C1SNSR43B-2
11K80
OX
OX
OX
OX
Fresh Air Tempering
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 11
OPTIONS / ACCESSORIES
Model
Number
Item Description
Unit Model No
Catalog
Number 092 102 120 150
INDOOR AIR QUALITY
Air Filters
MERV 8 - C1FLTR15B-1
50W61
OX
OX
OX
OX
MERV 13 - C1FLTR40B-1
52W41
OX
OX
OX
OX
C1FLTR30B-1-
Y3063
X
X
X
X
Sensor - Wall-mount, off-white plastic cover with LCD display
C0SNSR50AE1L
77N39
X
X
X
X
Sensor - Wall-mount, off-white plastic cover, no display
C0SNSR52AE1L
87N53
X
X
X
X
Sensor - Black plastic case with LCD display, rated for plenum
mounting
C0SNSR51AE1L
87N52
X
X
X
X
C0MISC19AE1
87N54
X
X
X
X
CO2 Sensor Duct Mounting Kit - for downflow applications
C0MISC19AE1-
85L43
X
X
X
X
Aspiration Box - for duct mounting non-plenum rated CO2 sensors
(87N53 or 77N39)
C0MISC16AE1-
90N43
X
X
X
X
C1UVCL10B-1
54W62
OX
OX
OX
OX
(NOTE - Not available with Eco-Last™ Coil System. Conventional Fin/Tube condenser coil must
be ordered as a factory option)
Factory
O
O
O
O
Humidity Sensor Kit, Remote mounted (required)
COSNSR31AE-1
17M50
X
X
X
X
380/420V - 3 phase
Factory
O
O
O
O
5.7 kW
380/420V-3ph - C1EH0057B-1M
68W04
OX
OX
11.5 kW
380/420V-3ph - C1EH0115B-1M
68W05
OX
OX
OX
OX
17.2 kW
380/420V-3ph - C1EH0172B-1M
68W06
OX
OX
OX
OX
23 kW
380/420V-3ph - C1EH0230B-1M
68W07
OX
OX
OX
OX
34.5 kW
380/420V-3ph - C1EH0345B-1M
68W08
OX
OX
OX
OX
45.9 kW
380/420V-3ph - C1EH0459B-1M
68W09
OX
OX
High Efficiency Air Filters
508 x 635 x 51 mm (Order 4 per unit)
Replacement Media Filter With Metal Mesh
Frame (includes non-pleated filter media)
Indoor Air Quality (CO2) Sensors
Sensor - Wall-mount, black plastic case, no display, rated for
plenum mounting
UVC Germicidal Lamps
1
UVC Light Kit (220V-1ph)
CONDENSER REHEAT OPTION
ELECTRICAL
Voltage 50 hz with neutral (No neutral on CE marked models)
2
ELECTRIC HEAT
amps operate on 220V single-phase power supply. Step-down transformer may be ordered separately for 380/420V primary to 220V secondary units. Alternately,
L
220V power supply may be used to directly power the UVC ballast(s).
2
Nominal kW at 420V-3ph-50hz.
1
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 12
OPTIONS / ACCESSORIES
Model
Number
Item Description
Unit Model No
Catalog
Number 092 102 120 150
ECONOMIZER
Standard Economizer
E1ECON15B-2
13U46
OX
OX
OX
OX
E1ECON17B-1
10U59
OX
OX
OX
OX
LAGEDH03/15
53K04
X
X
X
X
Order 2 - C1SNSR64FF1
53W64
OX
OX
OX
OX
Sensor is Furnished
Factory
O
O
O
O
Standard Economizer
Downflow or Horizontal - Includes Outdoor Air Hood and Downflow
Barometric Relief Dampers with Exhaust Hood
Order Horizontal Barometric Relief Dampers separately
High Performance Economizer
High Performance Economizer
Downflow or Horizontal - Includes Outdoor Air Hood and Downflow
Barometric Relief Dampers with Exhaust Hood
Order Horizontal Barometric Relief Dampers separately
Horizontal Barometric Relief Dampers
Horizontal Low Profile Barometric Relief Dampers (Exhaust hood furnished)
Economizer Controls
Differential Enthalpy
Sensible Control
C1SNSR64FF1
53W64
OX
OX
OX
OX
Building Pressure Control
E1GPBK20C1
13J77
X
X
X
X
Outdoor Air CFM Control
E1GPBK10C1
13J76
X
X
X
X
Sensor Field Provided
Factory
O
O
O
O
LAGEDH03/15
53K04
X
X
X
X
Motorized
C1DAMP20B-1
14G28
OX
OX
OX
OX
Manual
C1DAMP10B-1
14G29
OX
OX
OX
OX
380/420V-3ph - K1PWRE10B-1G
53W45
OX
OX
OX
OX
203 mm height
C1CURB70B-1
11F54
X
X
X
X
356 mm height
C1CURB71B-1
11F55
X
X
X
X
457 mm height
C1CURB72B-1
11F56
X
X
X
X
610 mm height
C1CURB73B-1
11F57
X
X
X
X
C1CURB55B-1
54W50
X
X
X
X
X
X
X
Single Enthalpy
Global Control
Horizontal Barometric Relief Dampers With Hood
Horizontal Barometric Relief Dampers - Hood Furnished
OUTDOOR AIR
Outdoor Air Dampers With Outdoor Air Hood
POWER EXHAUST
Standard Static
ROOF CURBS
Hybrid Roof Curbs, Downflow
Adjustable Pitch Curb, Downflow
356 mm height
CEILING DIFFUSERS
Step-Down - Order one
Flush - Order one
Transitions (Supply and Return) - Order one
RTD11-95
29G04
RTD11-135
29G05
RTD11-185
29G06
FD11-95
29G08
FD11-135
29G09
FD11-185
29G10
C1DIFF30B-1
12X65
C1DIFF31B-1
12X66
C1DIFF32B-1
12X67
X
X
X
X
X
X
X
X
X
NOTE - Catalog and model numbers shown are for ordering field installed accessories.
OX - Configure To Order (Factory Installed) or Field Installed
O = Configure To Order (Factory Installed)
X = Field Installed
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 13
SPECIFICATIONS
General Data
Nominal kW (Tons)
Model Number
Efficiency Type
Blower Type
Cooling
Performance
Gross Cooling Capacity - kW (Btuh)
1
Net Cooling Capacity - kW (Btuh)
AHRI Rated Air Flow - L/s (cfm)
Total Unit Power - kW
1
EER (Btuh/Watt)
2
IEER (Btuh/Watt)
Refrigerant Type
Circuit 1
Eco-Last™ Coil System
Refrigerant
Charge
Circuit 1
26 (7.5)
LCH092H4
High
Constant Air
Volume CAV
24.6 (84 000)
23.7 (81 000)
1416 (3000)
6.6
12.9
12.9
R-410A
3.40 kg
(7 lbs. 8 oz.)
3.40 kg
(7 lbs. 8 oz.)
6.12 kg
30 (8.5)
LCH102H4
High
Constant Air
Volume CAV
27.5 (93 900)
26.4 (90 100)
1605 (3400)
7.2
12.6
12.9
R-410A
3.40 kg
(7 lbs. 8 oz.)
3.40 kg
(7 lbs. 8 oz.)
6.12 kg
35 (10)
LCH120H4
High
Constant Air
Volume CAV
32.9 (112 200)
31.7 (108 200)
1699 (3600)
8.9
12.4
12.7
R-410A
3.30 kg
(7 lbs. 4 oz.)
3.40 kg
(7 lbs. 8 oz.)
6.58 kg
Circuit 2
(13 lbs. 8 oz.)
5.67 kg
(13 lbs. 8 oz.)
5.67 kg
(14 lbs. 8 oz.)
6.12 kg
Circuit 1
(12 lbs. 8 oz.)
7.71 kg
(12 lbs. 8 oz.)
7.71 kg
(13 lbs. 8 oz.)
8.16 kg
Circuit 2
(17 lbs. 0 oz.)
5.67 kg
(17 lbs. 0 oz.)
5.67 kg
(18 lbs. 0 oz.)
6.12 kg
Circuit 2
Conventional Fin/Tube
Coil Option
Conventional Fin/Tube
With Dehumidification Option
Electric Heat Available - See page 13
Compressor Type (number)
Outdoor Coil
Net face area (total) - m2 (sq. ft).
Eco-Last™
(Fin/Tube)
Outdoor
Coil Fans
Indoor
Coils
3
Indoor
Blower and
Drive
Selection
Tube diameter - mm (in.)
Number of rows
Fins per m (Fins per inch)
Motor - (No.) W (hp)
Motor rev/min
Total Motor watts
Diameter - (No.) mm (in.)
Number of blades
Total Air volume - L/s (cfm)
Net face area (total) - m2 (sq. ft.)
Tube diameter - mm (in.)
Number of rows
Fins per m (Fins per inch)
Drain connection - Number and size
Expansion device type
Nominal motor kW (HP)
Maximum usable motor kW (HP)
Kit # (rev/min range)
Nominal motor kW (HP)
Maximum usable motor kW (HP)
Kit # (rev/min range)
Nominal motor kW (HP)
Maximum usable motor kW (HP)
Kit # (rev/min range)
Filters
Blower wheel nominal diameter x
width - mm (in.)
Type of filter
Number and size - mm (in.)
Electrical characteristics
44 (12.5)
LCH150S4
Standard
Constant Air
Volume CAV
38.4 (131 300)
36.7 (125 300)
1935 (4100)
11.4
11.2
11
R-410A
3.30 kg
(7 lbs. 4 oz.)
3.06 kg
(6 lbs. 12 oz.)
7.93 kg
(17 lbs. 8 oz.)
5.78 kg
(12 lbs 12 oz.)
8.39 kg
(18 lbs. 8 oz.)
6.58 kg
(12 lbs. 8 oz.)
(12 lbs. 8 oz.)
(13 lbs. 8 oz.)
(14 lbs 8 oz.)
5.7, 11.5, 17.2, 23, 34.5 kW
11.5, 17.2, 23, 34.5, 45.9 kW
Scroll (2)
Scroll (2)
Scroll (2)
Scroll (2)
2.60 (28.0) /
2.60 (28.0) /
2.60 (28.0) /
2.60 (28.0) /
2.72 (29.33)
2.72 (29.33)
2.72 (29.33)
2.72 (29.33)
18 (0.71) / 9.5 (3/8)
18 (0.71) / 9.5 (3/8)
18 (0.71) / 9.5 (3/8)
18 (0.71) / 9.5 (3/8)
1/3
1/3
1/3
1/3
787 (20)
787 (20)
787 (20)
787 (20)
(2) 249 (1/3)
(2) 249 (1/3)
(2) 249 (1/3)
(2) 373 (1/2)
896
896
896
896
554
554
554
626
(2) 610 (24)
(2) 610 (24)
(2) 610 (24)
(2) 610 (24)
3
3
3
3
3145 (6665)
3145 (6665)
3145 (6665)
3460 (7335)
1.19 (12.78)
1.19 (12.78)
1.26 (13.54)
1.26 (13.54)
9.5 (3/8)
9.5 (3/8)
9.5 (3/8)
9.5 (3/8)
2
2
3
4
551 (14)
551 (14)
551 (14)
787 (20)
(1) 1 in. NPT coupling
Balance port TXV, removable head
1.5 (2)
1.5 (2)
1.5 (2)
1.5 (2)
1.7 (2.3)
1.7 (2.3)
1.7 (2.3)
1.7 (2.3)
#1 (490-740)
#1 (490-740)
#1 (490-740)
#1 (490-740)
#2 (665-920)
#2 (665-920)
#2 (665-920)
#2 (665-920)
#3 (660-995)
#3 (660-995)
#3 (660-995)
#3 (660-995)
2.2 (3)
2.2 (3)
2.2 (3)
2.2 (3)
2.6 (3.45)
2.6 (3.45)
2.6 (3.45)
2.6 (3.45)
#7 (610-810)
#7 (610-810)
#7 (610-810)
#7 (610-810)
#8 (780-1000)
#8 (780-1000)
#8 (780-1000)
#8 (780-1000)
#9 (845-1085)
#9 (845-1085)
#9 (845-1085)
#9 (845-1085)
3.7 (5)
3.7 (5)
3.7 (5)
3.7 (5)
4.3 (5.75)
4.3 (5.75)
4.3 (5.75)
4.3 (5.75)
#10 (750-945)
#10 (750-945)
#10 (750-945)
#10 (750-945)
#11 (865-1095)
#11 (865-1095)
#11 (865-1095)
#11 (865-1095)
#12 (940-1190)
#12 (940-1190)
#12 (940-1190)
#12 (940-1190)
(1) 381 x 381
(1) 381 x 381
(1) 381 x 381
(1) 381 x 381
(15 X 15)
(15 X 15)
(15 X 15)
(15 X 15)
Disposable
(4) 508 x 508 x 51 (20 x 25 x 2)
380/420V - 50 hertz - 3 phase with neutral
(No neutral on CE marked models)
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
Tested at conditions included in the USE certification program, which is based on AHRI Standard 340/360; 35°C (95°F) outdoor air temperature and 27°C (80°F) dry
bulb /19°C (67°F) wet bulb entering evaporator air; minimum external duct static pressure while operating at rated voltage and air volumes.
2
Integrated Energy Efficiency Ratio tested at conditions included in AHRI Standard 340/360 while operating at rated voltage and air volumes.
3
Using total air volume and system static pressure requirements determine from blower performance tables rev/min and motor output required. Maximum usable output
of motors furnished are shown. If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 14
RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
26 kW - LCH092H4 (1ST STAGE)
Entering Total
Wet
Air
Bulb Volume Total
Cool
TemperCap.
ature
L/s
kW
17.2°C
19.4°C
21.7°C
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.8°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
29.4°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cool
Cap.
kW
kW
24°C 27°C 29°C
kW
kW
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
24°C 27°C 29°C
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
kW
kW
24°C
Dry Bulb
27°C
29°C
1135
11.5
1.74
.64
.79
.99
11.0
1.97
.65
.82
1.00
10.6
2.22
.66
.85
1.00
10.1
2.51
.68
.88
1.00
1415
12.0
1.75
.69
.91
1.00
11.6
1.98
.71
.94
1.00
11.1
2.23
.72
.97
1.00
10.6
2.51
.75
1.00
1.00
1700
12.4
1.76
.75
1.00
1.00
12.0
1.98
.77
1.00
1.00
11.6
2.23
.80
1.00
1.00
11.1
2.52
.83
1.00
1.00
1135
12.1
1.75
.51
.62
.74
11.7
1.98
.51
.63
.77
11.2
2.23
.52
.64
.79
10.7
2.51
.54
.66
.82
1415
12.7
1.76
.54
.67
.86
12.2
1.98
.55
.68
.89
11.7
2.23
.56
.70
.92
11.1
2.52
.57
.71
.96
1700
13.1
1.76
.57
.72
.96
12.5
1.99
.57
.74
.99
12.0
2.24
.59
.77
1.00
11.4
2.52
.59
.80
1.00
1135
12.7
1.76
.39
.49
.60
12.3
1.99
.38
.49
.61
11.8
2.23
.39
.49
.62
11.2
2.52
.40
.52
.63
1415
13.3
1.77
.40
.53
.65
12.8
1.99
.40
.54
.67
12.3
2.24
.41
.55
.68
11.7
2.52
.41
.55
.70
1700
13.7
1.77
.41
.56
.70
13.2
1.99
.42
.57
.71
12.6
2.24
.41
.57
.74
12.0
2.52
.43
.59
.77
Total
Cool
Cap.
Comp.
Motor
Input
kW
kW
24°C
26 kW - LCH092H4 (2ND STAGE)
Entering Total
Wet
Air
Bulb Volume Total
Cool
TemperCap.
ature
L/s
kW
17.2°C
19.4°C
21.7°C
Outdoor Air Temperature Entering Outdoor Coil
26.6°C
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
43.3°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cool
Cap.
kW
kW
24°C 27°C 29°C
kW
kW
51.7°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
24°C 27°C 29°C
Sensible To Total
Ratio (S/T)
Dry Bulb
27°C
29°C
1135
24.0
4.31
.71
.86
1.00
22.4
5.17
.73
.90
1.00
20.7
6.24
.76
.96
1.00
18.7
7.58
.80
1.00
1.00
1415
25.1
4.32
.76
.96
1.00
23.4
5.18
.79
1.00
1.00
21.8
6.24
.84
1.00
1.00
19.9
7.57
.91
1.00
1.00
1700
26.1
4.33
.83
1.00
1.00
24.6
5.19
.86
1.00
1.00
22.8
6.24
.93
1.00
1.00
20.8
7.57
.99
1.00
1.00
1135
25.4
4.32
.54
.68
.82
23.7
5.18
.57
.71
.86
21.9
6.24
.59
.74
.92
19.7
7.58
.60
.77
.98
1415
26.5
4.34
.59
.74
.92
24.6
5.18
.61
.77
.97
22.7
6.24
.63
.81
1.00
20.5
7.57
.65
.87
1.00
1700
27.3
4.34
.62
.80
1.00
25.3
5.19
.64
.84
1.00
23.3
6.25
.67
.90
1.00
21.0
7.57
.71
.98
1.00
1135
26.7
4.34
.40
.54
.66
24.9
5.19
.43
.56
.68
23.0
6.24
.43
.58
.72
20.8
7.56
.44
.59
.75
1415
27.9
4.35
.44
.58
.72
26.0
5.20
.44
.60
.75
23.9
6.25
.45
.62
.79
21.5
7.56
.46
.64
.85
1700
28.7
4.36
.45
.61
.77
26.7
5.20
.46
.63
.82
24.5
6.25
.47
.66
.88
22.1
7.56
.49
.70
.95
Total
Cool
Cap.
Comp.
Motor
Input
kW
kW
24°C
30 kW - LCH102H4 (1ST STAGE)
Entering Total
Wet
Air
Bulb Volume Total
Cool
TemperCap.
ature
L/s
kW
17.2°C
19.4°C
21.7°C
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.8°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
29.4°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cool
Cap.
kW
kW
24°C 27°C 29°C
kW
kW
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
24°C 27°C 29°C
Sensible To Total
Ratio (S/T)
Dry Bulb
27°C
29°C
1285
14.1
1.91
.70
.86
1.00
13.6
2.16
.72
.88
1.00
13.1
2.44
.74
.90
1.00
12.5
2.76
.75
.93
1.00
1605
14.8
1.92
.76
.96
1.00
14.2
2.17
.78
.98
1.00
13.6
2.45
.79
1.00
1.00
13.1
2.77
.82
1.00
1.00
1925
15.3
1.93
.81
1.00
1.00
14.8
2.18
.84
1.00
1.00
14.3
2.46
.86
1.00
1.00
13.7
2.77
.90
1.00
1.00
1285
14.9
1.92
.56
.68
.81
14.4
2.17
.56
.70
.84
13.8
2.45
.58
.71
.86
13.2
2.77
.59
.73
.89
1605
15.6
1.93
.60
.74
.92
15.0
2.18
.60
.76
.94
14.3
2.46
.61
.77
.97
13.7
2.77
.62
.79
1.00
1925
16.0
1.94
.62
.79
.99
15.4
2.19
.63
.81
1.00
14.7
2.46
.65
.84
1.00
14.0
2.77
.66
.88
1.00
1285
15.7
1.93
.42
.55
.66
15.2
2.18
.42
.55
.68
14.5
2.46
.43
.56
.69
13.9
2.77
.44
.58
.71
1605
16.4
1.94
.44
.58
.72
15.7
2.19
.44
.59
.74
15.1
2.47
.45
.60
.75
14.3
2.78
.45
.61
.77
1925
16.8
1.95
.45
.62
.77
16.1
2.19
.46
.62
.79
15.4
2.47
.46
.64
.82
14.7
2.78
.46
.65
.85
Total
Cool
Cap.
Comp.
Motor
Input
kW
kW
24°C
30 kW - LCH102H4 (2ND STAGE)
Entering Total
Wet
Air
Bulb Volume Total
Cool
TemperCap.
ature
L/s
kW
17.2°C
19.4°C
21.7°C
Outdoor Air Temperature Entering Outdoor Coil
26.6°C
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
43.3°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cool
Cap.
kW
kW
24°C 27°C 29°C
kW
kW
51.7°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
24°C 27°C 29°C
Sensible To Total
Ratio (S/T)
Dry Bulb
27°C
29°C
1285
26.9
4.60
.73
.89
1.00
25.2
5.53
.75
.93
1.00
23.2
6.68
.78
.98
1.00
21.2
8.12
.82
1.00
1.00
1605
28.1
4.62
.78
.99
1.00
26.3
5.54
.81
1.00
1.00
24.6
6.68
.86
1.00
1.00
22.4
8.12
.94
1.00
1.00
1925
29.3
4.63
.85
1.00
1.00
27.6
5.55
.90
1.00
1.00
25.6
6.69
.96
1.00
1.00
23.4
8.12
1.00
1.00
1.00
1285
28.4
4.62
.57
.70
.85
26.6
5.54
.59
.73
.89
24.5
6.68
.60
.76
.95
22.2
8.12
.62
.80
1.00
1605
29.6
4.63
.61
.76
.96
27.5
5.55
.62
.79
1.00
25.4
6.69
.64
.84
1.00
22.9
8.12
.68
.91
1.00
1925
30.4
4.64
.64
.83
1.00
28.3
5.55
.66
.87
1.00
26.0
6.69
.69
.94
1.00
23.4
8.11
.73
1.00
1.00
1285
29.9
4.64
.43
.56
.68
28.0
5.55
.44
.58
.71
25.8
6.69
.44
.59
.74
23.3
8.11
.45
.61
.77
1605
31.1
4.65
.44
.60
.75
28.9
5.56
.45
.61
.77
26.6
6.69
.46
.63
.82
24.1
8.11
.47
.66
.88
1925
31.9
4.66
.46
.63
.80
29.7
5.57
.47
.65
.85
27.3
6.70
.48
.68
.91
24.6
8.11
.50
.72
.98
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 15
RATINGS
NOTE - For Temperatures and Capacities not shown in tables, see bulletin - Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.
35 kW - LCH120H4 (1ST STAGE)
Entering Total
Wet
Air
Bulb Volume Total
Cool
TemperCap.
ature
L/s
kW
17.2°C
19.4°C
21.7°C
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.8°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
29.4°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cool
Cap.
kW
kW
24°C 27°C 29°C
kW
kW
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
24°C 27°C 29°C
Sensible To Total
Ratio (S/T)
Total
Cool
Cap.
Comp.
Motor
Input
kW
kW
24°C
Dry Bulb
27°C
29°C
1510
16.4
2.32
.66
.81
1.00
15.8
2.62
.67
.83
1.00
15.2
2.96
.69
.86
1.00
14.4
3.34
.70
.90
1.00
1890
17.2
2.34
.71
.92
1.00
16.5
2.65
.73
.96
1.00
15.8
2.99
.74
.99
1.00
15.1
3.37
.77
1.00
1.00
2265
17.8
2.37
.77
1.00
1.00
17.1
2.68
.79
1.00
1.00
16.5
3.02
.82
1.00
1.00
15.8
3.40
.86
1.00
1.00
1510
17.3
2.35
.53
.64
.76
16.7
2.66
.53
.66
.79
16.0
2.99
.53
.66
.82
15.2
3.37
.55
.68
.85
1890
18.1
2.38
.55
.69
.87
17.4
2.69
.56
.71
.91
16.7
3.03
.58
.72
.95
15.9
3.40
.59
.74
.98
2265
18.7
2.40
.59
.74
.98
17.9
2.71
.59
.76
1.00
17.1
3.05
.60
.79
1.00
16.3
3.42
.62
.84
1.00
1510
18.3
2.38
.40
.51
.62
17.6
2.69
.40
.51
.63
16.8
3.03
.41
.52
.65
16.1
3.41
.40
.53
.66
1890
19.0
2.42
.41
.54
.67
18.3
2.73
.42
.55
.69
17.5
3.07
.42
.57
.71
16.7
3.44
.42
.58
.72
2265
19.6
2.44
.43
.58
.72
18.8
2.75
.43
.59
.74
18.0
3.09
.43
.60
.76
17.1
3.46
.44
.61
.80
Total
Cool
Cap.
Comp.
Motor
Input
kW
kW
24°C
35 kW - LCH120H4 (2ND STAGE)
Entering Total
Wet
Air
Bulb Volume Total
Cool
TemperCap.
ature
L/s
kW
17.2°C
19.4°C
21.7°C
Outdoor Air Temperature Entering Outdoor Coil
26.6°C
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
43.3°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cool
Cap.
kW
kW
24°C 27°C 29°C
kW
kW
51.7°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
24°C 27°C 29°C
Sensible To Total
Ratio (S/T)
Dry Bulb
27°C
29°C
1510
32.3
5.92
.69
.86
1.00
30.2
7.10
.71
.91
1.00
27.9
8.53
.74
.98
1.00
25.3
10.26
.79
1.00
1.00
1890
33.7
5.98
.75
.99
1.00
31.5
7.16
.78
1.00
1.00
29.4
8.59
.84
1.00
1.00
26.8
10.33
.91
1.00
1.00
2265
35.1
6.04
.82
1.00
1.00
33.0
7.23
.88
1.00
1.00
30.7
8.65
.94
1.00
1.00
27.9
10.38
1.00
1.00
1.00
1510
34.0
5.99
.54
.67
.82
31.8
7.17
.56
.69
.87
29.3
8.60
.58
.72
.93
26.5
10.31
.60
.76
1.00
1890
35.4
6.06
.58
.73
.94
33.0
7.23
.60
.76
.99
30.4
8.64
.61
.81
1.00
27.3
10.35
.64
.88
1.00
2265
36.4
6.10
.61
.79
1.00
33.8
7.27
.63
.85
1.00
31.1
8.68
.66
.91
1.00
28.0
10.39
.69
.99
1.00
1510
35.8
6.07
.41
.53
.65
33.4
7.25
.42
.55
.67
30.9
8.67
.42
.57
.70
27.8
10.38
.43
.59
.74
1890
37.2
6.13
.42
.57
.71
34.7
7.31
.43
.59
.74
31.9
8.72
.44
.60
.78
28.8
10.42
.45
.64
.85
2265
38.2
6.18
.44
.60
.77
35.5
7.36
.44
.63
.82
32.6
8.76
.46
.65
.89
29.5
10.46
.47
.69
.98
Total
Cool
Cap.
Comp.
Motor
Input
kW
kW
24°C
44 kW - LCH150S4 (1ST STAGE)
Entering Total
Wet
Air
Bulb Volume Total
Cool
TemperCap.
ature
L/s
kW
17.2°C
19.4°C
21.7°C
Outdoor Air Temperature Entering Outdoor Coil
18.3°C
23.8°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
29.4°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cool
Cap.
kW
kW
24°C 27°C 29°C
kW
kW
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
24°C 27°C 29°C
Sensible To Total
Ratio (S/T)
Dry Bulb
27°C
29°C
1795
19.7
3.16
.66
.82
1.00
19.0
3.49
.67
.84
1.00
18.2
3.85
.68
.87
1.00
17.4
4.26
.70
.91
1.00
2075
20.3
3.17
.69
.89
1.00
19.6
3.50
.70
.92
1.00
18.8
3.86
.71
.95
1.00
17.9
4.27
.75
.99
1.00
2360
20.8
3.18
.72
.96
1.00
20.1
3.51
.75
.99
1.00
19.2
3.87
.77
1.00
1.00
18.5
4.28
.80
1.00
1.00
1795
20.8
3.18
.52
.64
.78
20.1
3.51
.53
.65
.80
19.3
3.87
.53
.66
.82
18.4
4.28
.54
.67
.86
2075
21.5
3.19
.54
.67
.84
20.7
3.52
.55
.68
.87
19.8
3.88
.55
.70
.90
18.9
4.29
.57
.71
.94
2360
22.0
3.21
.56
.70
.91
21.2
3.53
.57
.71
.94
20.3
3.89
.57
.74
.97
19.3
4.29
.59
.77
1.00
1795
22.0
3.21
.40
.51
.62
21.3
3.53
.40
.52
.63
20.4
3.89
.40
.52
.64
19.5
4.30
.40
.53
.65
2075
22.6
3.22
.40
.53
.65
21.8
3.54
.41
.53
.66
20.9
3.90
.41
.54
.67
19.9
4.30
.42
.55
.69
2360
23.2
3.23
.41
.55
.68
22.3
3.55
.41
.55
.69
21.4
3.91
.42
.56
.71
20.4
4.31
.42
.58
.74
Total
Cool
Cap.
Comp.
Motor
Input
kW
kW
24°C
44 kW - LCH150S4 (2ND STAGE)
Entering Total
Wet
Air
Bulb Volume Total
Cool
TemperCap.
ature
L/s
kW
17.2°C
19.4°C
21.7°C
Outdoor Air Temperature Entering Outdoor Coil
26.6°C
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
43.3°C
Total
Cool
Cap.
Comp.
Motor
Input
Sensible To Total
Ratio (S/T)
Dry Bulb
Total
Cool
Cap.
kW
kW
24°C 27°C 29°C
kW
kW
51.7°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
Dry Bulb
27°C
29°C
1795
38.2
7.69
.71
.88
1.00
35.6
8.93
.73
.92
1.00
32.6
10.39
.77
.98
1.00
29.5
12.12
.82
1.00
1.00
2075
39.4
7.71
.74
.95
1.00
36.7
8.95
.78
.99
1.00
33.8
10.41
.82
1.00
1.00
30.9
12.15
.89
1.00
1.00
2360
40.4
7.73
.79
1.00
1.00
37.9
8.97
.83
1.00
1.00
35.1
10.44
.87
1.00
1.00
31.9
12.18
.95
1.00
1.00
1795
40.4
7.73
.55
.68
.83
37.7
8.97
.56
.70
.87
34.7
10.43
.59
.74
.93
31.2
12.16
.61
.79
1.00
2075
41.6
7.76
.58
.72
.90
38.8
8.99
.59
.75
.95
35.6
10.45
.61
.79
1.00
31.9
12.18
.64
.85
1.00
2360
42.6
7.78
.60
.76
.96
39.7
9.01
.61
.80
1.00
36.3
10.46
.64
.85
1.00
32.5
12.19
.67
.92
1.00
1795
42.8
7.78
.41
.54
.66
39.9
9.01
.42
.55
.68
36.7
10.47
.43
.58
.71
33.1
12.20
.44
.60
.76
2075
43.9
7.80
.43
.56
.69
40.9
9.03
.43
.58
.72
37.7
10.49
.44
.60
.76
33.8
12.22
.45
.63
.82
2360
44.9
7.82
.43
.58
.73
41.9
9.05
.44
.60
.77
38.5
10.51
.45
.63
.82
34.6
12.24
.47
.66
.88
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 16
24°C 27°C 29°C
Sensible To Total
Ratio (S/T)
DEHUMIDIFICATION SYSTEM RATINGS
26 kW - LCH092H4 with DEHUMIDIFICATION OPERATING (1ST STAGE)
Entering
Total
Wet
Air
Total
Bulb
Volume Cool
TemperCap.
ature
L/s
kW
1135
7.0
17.2°C
19.4°C
21.7°C
18.3°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
1.7
0.47 0.66 0.86
Total
Cool
Cap.
kW
5.9
Outdoor Air Temperature Entering Outdoor Coil
23.8°C
29.4°C
Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Input
Cap. Input
Dry Bulb
Dry Bulb
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
1.9
0.34 0.58 0.81
4.8
2.1
0.22 0.51 0.75
Total
Cool
Cap.
kW
3.7
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
2.3
0.09 0.42 0.69
1415
8.2
1.7
0.52
0.74
0.89
7.0
1.9
0.38
0.63
0.82
5.6
2.1
0.23
0.52
0.74
4.4
2.3
0.09
0.40
0.66
1700
9.4
1.7
0.57
0.80
0.98
8.0
1.9
0.40
0.64
0.86
6.6
2.1
0.25
0.50
0.74
5.0
2.3
0.10
0.36
0.63
1135
9.1
1.7
0.33
0.50
0.67
7.8
1.9
0.20
0.40
0.61
6.5
2.1
0.08
0.31
0.55
5.2
2.3
-0.05
0.21
0.49
1415
10.2
1.7
0.36
0.55
0.75
8.7
1.9
0.21
0.43
0.66
7.4
2.1
0.07
0.32
0.59
5.9
2.4
-0.08
0.20
0.50
1700
11.2
1.7
0.38
0.59
0.81
9.6
1.9
0.21
0.46
0.70
8.2
2.1
0.05
0.33
0.59
6.7
2.3
-0.11
0.19
0.47
1135
11.1
1.8
0.20
0.34
0.48
9.9
2.0
0.06
0.23
0.40
8.1
2.2
-0.06 0.12
0.32
6.6
2.4
-0.20
0.02
0.23
1415
12.0
1.8
0.20
0.36
0.52
10.5
2.0
0.05
0.25
0.45
9.1
2.2
-0.10 0.13
0.37
7.5
2.4
-0.25
0.01
0.29
1700
12.9
1.8
0.21
0.38
0.56
11.4
2.0
0.04
0.26
0.48
10.9
2.2
-0.13 0.13
0.41
8.5
2.4
-0.31
0.01
0.33
26 kW - LCH092H4 with DEHUMIDIFICATION OPERATING (2ND STAGE)
Entering
Total
Wet
Air
Total
Bulb
Volume Cool
TemperCap.
ature
L/s
kW
1135
20.1
17.2°C
19.4°C
21.7°C
18.3°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
3.5
0.66 0.81 0.91
Total
Cool
Cap.
kW
18.2
Outdoor Air Temperature Entering Outdoor Coil
23.8°C
29.4°C
Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Input
Cap. Input
Dry Bulb
Dry Bulb
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
3.9
0.65 0.83 0.92 16.3
4.4
0.63 0.85 0.96
Total
Cool
Cap.
kW
14.4
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
4.8
0.62 0.86 1.00
1415
21.0
3.5
0.71
0.86
0.94
18.9
4.0
0.70
0.86
0.96
16.9
4.4
0.71
0.84
0.98
15.0
4.9
0.70
0.83
1.00
1700
22.1
3.5
0.77
0.90
1.00
19.9
4.0
0.77
0.90
1.00
17.6
4.4
0.79
0.89
1.00
15.4
4.9
0.80
0.88
1.00
1135
22.4
3.5
0.48
0.63
0.77
20.8
4.0
0.47
0.63
0.79
19.2
4.4
0.45
0.64
0.81
17.6
4.9
0.41
0.63
0.82
1415
23.6
3.6
0.53
0.68
0.84
21.6
4.0
0.50
0.68
0.85
19.9
4.5
0.47
0.67
0.85
18.0
4.9
0.46
0.67
0.82
1700
24.6
3.6
0.55
0.75
0.87
22.6
4.0
0.53
0.74
0.85
20.5
4.5
0.52
0.73
0.84
18.4
4.9
0.52
0.73
0.84
1135
24.6
3.6
0.33
0.45
0.60
23.3
4.1
0.30
0.45
0.59
22.1
4.5
0.26
0.43
0.58
20.7
4.9
0.22
0.39
0.57
1415
26.3
3.6
0.34
0.51
0.67
24.5
4.1
0.31
0.48
0.66
22.8
4.5
0.26
0.45
0.65
21.2
5.0
0.23
0.44
0.64
1700
27.6
3.6
0.34
0.53
0.72
25.7
4.1
0.31
0.51
0.73
23.6
4.5
0.27
0.50
0.73
21.7
5.0
0.24
0.49
0.73
Outdoor Air Temperature Entering Outdoor Coil
23.8°C
29.4°C
Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Input
Cap. Input
Dry Bulb
Dry Bulb
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
2.1
0.39 0.58 0.69
6.1
2.3
0.25 0.50 0.68
Total
Cool
Cap.
kW
4.6
30 kW - LCH102H4 with DEHUMIDIFICATION OPERATING (1ST STAGE)
Entering
Total
Wet
Air
Total
Bulb
Volume Cool
TemperCap.
ature
L/s
kW
1285
9.2
17.2°C
19.4°C
21.7°C
18.3°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
1.9
0.53 0.65 0.70
Total
Cool
Cap.
kW
7.7
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
2.6
0.11 0.43 0.69
1605
10.5
1.9
0.57
0.70
0.78
8.8
2.1
0.43
0.64
0.80
6.9
2.3
0.28
0.57
0.82
5.2
2.6
0.13
0.50
0.84
1925
11.9
1.9
0.58
0.72
0.89
9.9
2.1
0.44
0.66
0.93
7.9
2.3
0.30
0.62
0.96
5.8
2.5
0.16
0.57
1.00
1285
11.4
1.9
0.37
0.50
0.63
10.2
2.1
0.22
0.41
0.60
8.9
2.4
0.07
0.31
0.55
7.7
2.6
-0.08
0.22
0.51
1605
12.7
1.9
0.39
0.55
0.70
11.2
2.1
0.23
0.47
0.67
8.5
2.4
0.07
0.37
0.63
8.2
2.6
-0.08
0.28
0.60
1925
13.8
1.9
0.39
0.59
0.74
12.1
2.1
0.23
0.50
0.71
10.4
2.4
0.07
0.42
0.67
8.6
2.6
-0.09
0.33
0.65
1285
13.7
1.9
0.20
0.36
0.50
12.8
2.2
0.05
0.23
0.42
11.7
2.4
-0.10 0.11
0.33
10.9
2.6
-0.27
-0.01
0.24
1605
14.8
1.9
0.20
0.37
0.55
13.6
2.2
0.04
0.25
0.47
12.5
2.4
-0.13 0.12
0.38
11.2
2.6
-0.29
0.00
0.29
1925
15.9
2.0
0.19
0.39
0.58
13.9
2.2
0.02
0.25
0.51
13.0
2.4
-0.16 0.13
0.42
11.6
2.6
-0.33
0.00
0.35
30 kW - LCH102H4 with DEHUMIDIFICATION OPERATING (2ND STAGE)
Entering
Total
Wet
Air
Total
Bulb
Volume Cool
TemperCap.
ature
L/s
kW
1285
22.7
17.2°C
19.4°C
21.7°C
18.3°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
3.8
0.68 0.85 0.97
Total
Cool
Cap.
kW
20.7
Outdoor Air Temperature Entering Outdoor Coil
23.8°C
29.4°C
Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Input
Cap. Input
Dry Bulb
Dry Bulb
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
4.3
0.65 0.87 1.00 18.8
4.8
0.65 0.90 1.00
Total
Cool
Cap.
kW
16.7
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
5.3
0.6
0.9
1.0
1605
23.6
3.8
0.72
0.88
0.98
21.8
4.3
0.72
0.85
1.00
20.0
4.8
0.73
0.84
1.00
18.0
5.3
0.72
0.84
1.00
1925
25.1
3.8
0.78
0.87
0.99
23.0
4.3
0.80
0.88
1.00
20.8
4.8
0.81
0.89
1.00
18.7
5.3
0.82
0.90
1.00
1285
26.8
3.9
0.51
0.65
0.82
24.9
4.4
0.48
0.66
0.82
22.8
4.9
0.45
0.65
0.83
20.8
5.4
0.41
0.65
0.82
1605
27.7
3.9
0.53
0.68
0.86
25.9
4.4
0.50
0.67
0.86
23.6
4.9
0.49
0.67
0.83
21.6
5.4
0.46
0.66
0.81
1925
28.6
3.9
0.57
0.72
0.84
26.7
4.4
0.55
0.72
0.84
24.4
4.9
0.52
0.73
0.84
22.4
5.4
0.51
0.73
0.84
1285
31.0
3.9
0.33
0.47
0.60
30.0
4.4
0.29
0.45
0.60
26.9
4.9
0.24
0.42
0.59
24.9
5.4
0.20
0.39
0.58
1605
31.8
4.0
0.34
0.49
0.65
30.5
4.4
0.29
0.47
0.65
27.6
4.9
0.24
0.45
0.65
25.6
5.4
0.20
0.43
0.66
1925
32.5
4.0
0.34
0.53
0.72
31.2
4.5
0.30
0.51
0.72
28.2
5.0
0.25
0.49
0.73
26.2
5.5
0.21
0.47
0.75
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 17
DEHUMIDIFICATION SYSTEM RATINGS
35 KW - LCH120H4 with DEHUMIDIFICATION OPERATING (1ST STAGE)
Entering
Total
Wet
Air
Total
Bulb
Volume Cool
TemperCap.
ature
L/s
kW
1510
13.2
17.2°C
19.4°C
21.7°C
18.3°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
2.3
0.50 0.73 0.97
Total
Cool
Cap.
kW
11.3
Outdoor Air Temperature Entering Outdoor Coil
23.8°C
29.4°C
Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Input
Cap. Input
Dry Bulb
Dry Bulb
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
2.6
0.40 0.68 0.97
9.4
2.9
0.23 0.63 0.98
Total
Cool
Cap.
kW
7.4
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
3.1
0.01 0.49 1.00
1890
15.7
2.3
0.58
0.88
1.00
13.0
2.6
0.47
0.87
1.00
10.4
2.9
0.32
0.85
0.93
7.8
3.1
-0.01
0.80
0.97
2265
18.3
2.3
0.65
0.97
1.00
14.9
2.6
0.58
0.98
1.00
11.6
2.9
0.43
1.00
1.00
8.2
3.1
-0.02
0.97
0.80
1510
16.3
2.4
0.31
0.51
0.69
14.0
2.6
0.20
0.43
0.67
11.6
2.9
0.01
0.31
0.62
9.2
3.2
-0.06
0.08
0.53
1890
18.1
2.4
0.35
0.58
0.82
15.3
2.6
0.24
0.52
0.81
12.5
2.9
0.05
0.40
0.81
9.7
3.2
-0.12
0.16
0.78
2265
20.0
2.4
0.39
0.66
0.94
16.7
2.7
0.26
0.59
0.95
13.4
2.9
0.06
0.53
0.94
10.1
3.2
-0.18
0.30
0.98
1510
19.5
2.4
0.17
0.33
0.50
16.7
2.7
0.06
0.24
0.43
13.8
2.9
-0.12 0.11
0.36
11.1
3.2
-0.13
0.03
0.20
1890
20.5
2.4
0.17
0.36
0.57
17.6
2.7
0.05
0.29
0.53
14.6
3.0
-0.14 0.16
0.45
11.7
3.2
-0.24
-0.04
0.30
2265
21.7
2.4
0.20
0.41
0.65
18.5
2.7
0.06
0.33
0.60
15.4
3.0
-0.16 0.19
0.53
12.2
3.2
-0.34
-0.09
0.43
35 KW - LCH120H4 with DEHUMIDIFICATION OPERATING (2ND STAGE)
Entering
Total
Wet
Air
Total
Bulb
Volume Cool
TemperCap.
ature
L/s
kW
1510
27.9
17.2°C
19.4°C
21.7°C
18.3°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
4.8
.63
.78
.86
Total
Cool
Cap.
kW
25.4
Outdoor Air Temperature Entering Outdoor Coil
23.8°C
29.4°C
Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Input
Cap. Input
Dry Bulb
Dry Bulb
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
5.4
.61
.79
.91
22.8
6.0
.58
.82
.95
Total
Cool
Cap.
kW
20.1
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
6.6
.55
.82
1.00
1890
30.6
4.9
.66
.83
.93
27.6
5.5
.64
.81
.95
24.6
6.1
.63
.79
.98
21.7
6.7
.62
.79
1.00
2265
33.6
4.9
.69
.82
.99
30.0
5.5
.70
.82
1.00
26.5
6.1
.70
.82
1.00
22.8
6.7
.69
.82
1.00
1510
31.8
4.9
.47
.60
.74
29.0
5.5
.44
.59
.76
26.1
6.1
.41
.59
.79
23.3
6.7
.38
.58
.80
1890
34.2
5.0
.49
.64
.79
31.1
5.6
.46
.63
.80
28.1
6.2
.43
.62
.78
25.0
6.7
.41
.61
.76
2265
36.8
5.0
.50
.67
.80
33.3
5.6
.48
.66
.79
30.1
6.2
.45
.66
.78
26.9
6.8
.44
.65
.78
1510
1890
2265
35.4
38.0
40.3
5.0
5.1
5.1
.30
.31
.32
.42
.45
.47
.55
.59
.62
32.4
34.8
37.2
5.6
5.7
5.7
.26
.27
.27
.41
.43
.45
.54
.58
.61
29.4
31.8
34.1
6.2
6.3
6.3
.23
.23
.24
.38
.39
.41
.52
.56
.61
26.5
28.8
31.2
6.8
6.8
6.8
.21
.20
.20
.35
.38
.39
.51
.56
.60
Outdoor Air Temperature Entering Outdoor Coil
23.8°C
29.4°C
Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Input
Cap. Input
Dry Bulb
Dry Bulb
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
3.3
0.41 0.69 0.96
9.7
3.6
0.26 0.64 0.97
Total
Cool
Cap.
kW
7.3
44 KW - LCH150S4 with DEHUMIDIFICATION OPERATING (1ST STAGE)
Entering
Total
Wet
Air
Total
Bulb
Volume Cool
TemperCap.
ature
L/s
kW
1795
14.9
17.2°C
19.4°C
21.7°C
18.3°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
3.0
0.50 0.74 0.96
Total
Cool
Cap.
kW
12.3
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
3.9
0.35 0.54 0.99
2075
15.6
3.0
0.55
0.82
1.00
12.8
3.3
0.46
0.81
1.00
10.1
3.6
0.32
0.78
1.00
7.3
3.9
0.23
0.73
1.00
2360
16.4
3.1
0.59
0.90
1.00
13.4
3.4
0.53
0.91
1.00
10.4
3.6
0.34
0.76
0.90
7.5
3.9
0.11
0.90
1.00
1795
17.1
3.1
0.30
0.50
0.70
14.5
3.4
0.21
0.42
0.66
11.8
3.7
0.04
0.33
0.62
9.2
4.0
0.03
0.12
0.55
2075
17.9
3.1
0.33
0.53
0.78
15.1
3.4
0.22
0.48
0.76
12.2
3.7
0.05
0.38
0.73
9.4
4.0
-0.04
0.20
0.70
2360
18.7
3.2
0.34
0.57
0.85
15.6
3.4
0.25
0.53
0.84
12.7
3.7
0.08
0.44
0.84
9.7
4.0
-0.10
0.26
0.64
1795
19.4
3.2
0.15
0.32
0.49
16.7
3.5
0.05
0.24
0.44
13.8
3.8
-0.10 0.12
0.37
11.1
4.1
-0.28
-0.07
0.23
2075
20.1
3.2
0.16
0.34
0.53
17.2
3.5
0.05
0.25
0.47
14.4
3.8
-0.11 0.14
0.41
11.5
4.1
-0.30
-0.06
0.28
2360
20.8
3.3
0.16
0.36
0.58
17.9
3.5
0.05
0.29
0.53
15.0
3.8
-0.12 0.17
0.48
12.1
4.1
-0.30
-0.04
0.35
Outdoor Air Temperature Entering Outdoor Coil
23.8°C
29.4°C
Comp. Sensible To Total Total Comp. Sensible To Total
Ratio (S/T)
Ratio (S/T)
Motor
Cool Motor
Input
Cap. Input
Dry Bulb
Dry Bulb
kW
24°C 27°C 29°C
kW
kW
24°C 27°C 29°C
7.1
0.64 0.85 0.99 26.4
7.8
0.63 0.87 1.00
Total
Cool
Cap.
kW
23.1
44 KW - LCH150S4 with DEHUMIDIFICATION OPERATING (2ND STAGE)
Entering
Total
Wet
Air
Total
Bulb
Volume Cool
TemperCap.
ature
L/s
kW
1795
32.8
17.2°C
19.4°C
21.7°C
18.3°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
6.4
0.65 0.83 0.96
Total
Cool
Cap.
kW
29.6
35°C
Comp. Sensible To Total
Ratio (S/T)
Motor
Input
Dry Bulb
kW
24°C 27°C 29°C
8.4
0.62 0.88 1.00
2075
34.0
6.4
0.69
0.87
0.97
30.5
7.1
0.69
0.88
1.00
27.1
7.8
0.69
0.87
1.00
23.8
8.5
0.68
0.85
1.00
2360
35.2
6.5
0.73
0.88
0.99
31.8
7.2
0.74
0.86
1.00
28.1
7.8
0.73
0.87
1.00
24.4
8.5
0.73
0.88
1.00
1795
36.9
6.6
0.49
0.64
0.80
33.4
7.3
0.44
0.63
0.81
29.8
7.9
0.43
0.64
0.83
26.4
8.6
0.42
0.62
0.85
2075
38.0
6.6
0.50
0.67
0.84
34.4
7.3
0.48
0.67
0.85
30.7
8.0
0.46
0.65
0.88
26.9
8.6
0.43
0.65
0.85
2360
39.3
6.7
0.52
0.69
0.87
35.3
7.3
0.50
0.70
0.87
31.4
8.0
0.49
0.69
0.85
27.6
8.7
0.46
0.69
0.85
1795
40.8
6.7
0.32
0.45
0.59
37.0
7.4
0.28
0.43
0.59
33.3
8.1
0.23
0.40
0.58
29.5
8.8
0.20
0.39
0.58
2075
42.0
6.8
0.32
0.47
0.63
37.9
7.5
0.28
0.45
0.62
34.2
8.2
0.24
0.43
0.62
30.4
8.8
0.20
0.40
0.63
2360
43.4
6.9
0.32
0.50
0.67
39.2
7.5
0.28
0.47
0.67
35.2
8.2
0.24
0.45
0.67
31.2
8.8
0.20
0.43
0.66
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 18
BLOWER DATA
BELT DRIVE BLOWER − BASE UNIT
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY (NO HEAT SECTION) WITH DRY INDOOR COIL AND AIR
FILTERS IN PLACE. FOR ALL UNITS ADD:
1 − Wet indoor coil air resistance of selected unit.
2 − Any factory installed options air resistance (heat section, economizer, etc.)
3 − Any field installed accessories air resistance (duct resistance, diffuser, etc.)
Then determine from blower table blower motor output required.
See page 20 for blower motors and drives. See page 19 for wet coil and option/accessory air resistance data.
MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT - Maximum Static Pressure - 500 Pa (2.0 in. w.g.)
5.7 kW, 11.5 kW, 17.2 kW, 23 kW and 34.5 kW - 1320 L/s (2800 cfm)
45.9 kW - 1885 L/s (4000 cfm)
Total
Air
Volume
TOTAL STATIC PRESSURE - Pa (Inches Water Gauge)
100 (0.40)
50 (0.20)
150 (0.60)
200 (0.80)
250 (1.00)
300 (1.20)
350 (1.40)
L/s
cfm
rev/ kW BHP rev/ kW BHP rev/ kW BHP rev/ kW BHP rev/ kW BHP rev/ kW BHP rev/ kW BHP
min
min
min
min
min
min
min
1060
1180
1300
1415
1535
1650
1770
1890
2005
2125
2240
2360
2480
2595
2715
2830
2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
5250
5500
5750
6000
587
601
616
632
649
666
685
706
727
750
775
802
831
862
895
931
Total
Air
Volume
0.06
0.18
0.31
0.43
0.57
0.71
0.87
1.02
1.19
1.37
1.57
1.77
1.99
2.22
2.47
2.73
0.08
0.24
0.41
0.58
0.76
0.95
1.16
1.37
1.60
1.84
2.10
2.37
2.67
2.98
3.31
3.66
637
650
664
679
695
712
730
750
772
795
820
847
876
907
940
976
0.23
0.35
0.46
0.59
0.72
0.85
1.00
1.16
1.32
1.50
1.69
1.89
2.11
2.34
2.60
2.89
0.31
0.47
0.62
0.79
0.96
1.14
1.34
1.55
1.77
2.01
2.26
2.53
2.83
3.14
3.48
3.87
690
703
715
729
744
761
779
798
819
843
868
895
924
955
987
1021
0.42
0.53
0.63
0.75
0.87
1.01
1.14
1.29
1.45
1.63
1.82
2.02
2.24
2.48
2.77
3.10
0.56
0.71
0.85
1.01
1.17
1.35
1.53
1.73
1.95
2.19
2.44
2.71
3.01
3.33
3.71
4.16
746
757
769
782
797
813
830
849
871
894
919
945
973
1002
1032
1064
0.61
0.71
0.81
0.92
1.04
1.16
1.30
1.44
1.60
1.77
1.96
2.17
2.41
2.68
2.99
3.35
0.82
0.95
1.09
1.23
1.39
1.55
1.74
1.93
2.15
2.38
2.63
2.91
3.23
3.59
4.01
4.49
805
815
826
839
853
868
886
905
926
949
972
997
1022
1048
1075
1104
0.79
0.88
0.98
1.08
1.19
1.31
1.45
1.60
1.75
1.93
2.13
2.36
2.61
2.90
3.22
3.56
1.06
1.18
1.31
1.45
1.60
1.76
1.94
2.14
2.35
2.59
2.86
3.16
3.50
3.89
4.32
4.78
865
875
886
899
913
929
946
965
984
1003
1023
1044
1066
1090
1116
1144
0.95
1.04
1.13
1.24
1.35
1.47
1.60
1.75
1.92
2.11
2.32
2.56
2.82
3.11
3.42
3.74
1.28
1.40
1.52
1.66
1.81
1.97
2.15
2.35
2.58
2.83
3.11
3.43
3.78
4.17
4.59
5.02
927
938
950
963
976
990
1005
1019
1034
1050
1067
1087
1108
1132
1158
1185
1.09
1.17
1.27
1.37
1.48
1.62
1.76
1.92
2.09
2.29
2.51
2.75
3.01
3.30
3.59
3.90
1.46
1.57
1.70
1.84
1.99
2.17
2.36
2.57
2.80
3.07
3.36
3.69
4.04
4.42
4.82
5.23
TOTAL STATIC PRESSURE - Pa (Inches Water Gauge)
400 (1.60)
450 (1.80)
500 (2.00)
550 (2.20)
600 (2.40)
650 (2.60)
L/s
cfm
rev/
min
kW
BHP rev/
min
kW
BHP rev/
min
kW
BHP rev/
min
kW
BHP rev/
min
kW
BHP rev/
min
kW
BHP
1060
1180
1300
1415
1535
1650
1770
1890
2005
2125
2240
2360
2480
2595
2715
2830
2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
5250
5500
5750
6000
985
996
1008
1019
1030
1041
1053
1065
1079
1094
1112
1131
1153
1177
1202
1229
1.17
1.27
1.37
1.48
1.61
1.75
1.90
2.07
2.25
2.46
2.68
2.93
3.18
3.46
3.75
4.05
1.57
1.70
1.84
1.99
2.16
2.35
2.55
2.78
3.02
3.30
3.60
3.93
4.27
4.64
5.03
5.43
1.25
1.36
1.48
1.60
1.74
1.89
2.05
2.23
2.42
2.63
2.86
3.10
3.36
3.63
3.91
4.20
1.68
1.82
1.98
2.15
2.33
2.53
2.75
2.99
3.25
3.53
3.84
4.16
4.51
4.87
5.24
5.63
1.34
1.46
1.59
1.73
1.88
2.04
2.21
2.40
2.60
2.81
3.04
3.28
3.53
3.80
4.07
---
1.80
1.96
2.13
2.32
2.52
2.73
2.96
3.22
3.49
3.77
4.08
4.40
4.74
5.09
5.46
---
1.45
1.59
1.72
1.87
2.04
2.20
2.39
2.58
2.78
3.00
3.22
3.46
3.71
3.97
4.24
---
1.95
2.13
2.31
2.51
2.73
2.95
3.20
3.46
3.73
4.02
4.32
4.64
4.98
5.32
5.68
---
1.59
1.72
1.88
2.04
2.20
2.38
2.57
2.76
2.97
3.18
3.41
3.65
3.89
4.15
-----
2.13
2.31
2.52
2.73
2.95
3.19
3.44
3.70
3.98
4.27
4.57
4.89
5.22
5.56
-----
1.73
1.88
2.04
2.21
2.38
2.56
2.75
2.95
3.16
3.38
3.60
3.83
4.08
-------
2.32
2.52
2.73
2.96
3.19
3.43
3.69
3.96
4.24
4.53
4.83
5.14
5.47
-------
1034
1045
1056
1066
1076
1087
1098
1111
1126
1142
1161
1181
1203
1226
1251
1276
1084
1095
1105
1115
1126
1138
1150
1164
1180
1196
1215
1235
1256
1278
1302
---
1136
1147
1158
1169
1181
1193
1207
1221
1236
1253
1271
1291
1312
1333
1356
---
1189
1201
1213
1225
1237
1250
1264
1279
1295
1311
1329
1349
1369
1390
-----
1239
1253
1266
1279
1293
1307
1321
1336
1352
1369
1387
1406
1426
-------
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 19
BLOWER DATA
FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS
Nominal
Maximum
kW
hp
kW
hp
Drive Kit
Number
rev/min
Range
1.5
2
1.7
2.3
1
490 - 740
1.5
2
1.7
2.3
2
665 - 920
1.5
2
1.7
2.3
3
660 - 995
2.2
3
2.6
3.45
7
610 - 810
2.2
3
2.6
3.45
8
780 - 1000
2.2
3
2.6
3.45
9
845 - 1085
3.7
5
4.3
5.75
10
750 - 945
3.7
5
4.3
5.75
11
865 - 1095
3.7
5
4.3
5.75
12
940 - 1190
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rev/min and motor output required. Maximum usable
output of motors furnished are shown If motors of comparable output are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
POWER EXHAUST FAN PERFORMANCE
Return Air System Static Pressure
Pa
Air Volume Exhausted
in. w.g.
L/s
cfm
0
0
1498
3175
12
0.05
1394
2955
25
0.10
1267
2685
37
0.15
1137
2410
50
0.20
1022
2165
62
0.25
906
1920
75
0.30
670
1420
87
0.35
566
1200
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 20
BLOWER DATA
CEILING DIFFUSERS AIR RESISTANCE
RTD11 Step-Down Diffuser
Unit Size
092 Models
102 & 120
Models
150 Models
Air Volume
2 Ends Open
1 Side, 2 Ends
Open
All Ends & Sides
Open
FD11 Flush Diffuser
Pa
in. w.g.
Pa
in. w.g.
Pa
in. w.g.
Pa
in. w.g.
Pa
in. w.g.
1133
2400
52
0.21
45
0.18
37
0.15
35
0.14
1227
2600
60
0.24
52
0.21
45
0.18
42
0.17
1321
2800
67
0.27
60
0.24
52
0.21
50
0.20
1416
3000
80
0.32
72
0.29
62
0.25
62
0.25
1510
3200
102
0.41
92
0.37
80
0.32
77
0.31
1604
3400
124
0.50
112
0.45
97
0.39
92
0.37
1699
3600
152
0.61
134
0.54
119
0.48
109
0.44
1793
3800
182
0.73
157
0.63
142
0.57
127
0.51
1699
3600
90
0.36
70
0.28
57
0.23
37
0.15
1793
3800
99
0.40
80
0.32
65
0.26
45
0.18
1888
4000
109
0.44
90
0.36
72
0.29
52
0.21
1982
4200
122
0.49
99
0.40
82
0.33
60
0.24
2076
4400
134
0.54
109
0.44
92
0.37
67
0.27
2171
4600
149
0.60
122
0.49
104
0.42
77
0.31
2265
4800
162
0.65
132
0.53
114
0.46
87
0.35
2360
5000
172
0.69
144
0.58
124
0.50
97
0.39
2454
5200
186
0.75
154
0.62
134
0.54
107
0.43
1982
4200
55
0.22
47
0.19
40
0.16
25
0.10
2076
4400
70
0.28
60
0.24
50
0.20
30
0.12
2171
4600
85
0.34
72
0.29
60
0.24
37
0.15
2265
4800
99
0.40
85
0.34
72
0.29
47
0.19
2360
5000
114
0.46
97
0.39
85
0.34
57
0.23
2454
5200
129
0.52
109
0.44
97
0.39
67
0.27
2548
5400
144
0.58
122
0.49
107
0.43
77
0.31
2643
5600
159
0.64
134
0.54
117
0.47
87
0.35
2737
5800
174
0.70
147
0.59
127
0.51
97
0.39
CEILING DIFFUSER AIR THROW DATA
Model No.
092 Models
102, 120
Models
150 Models
1
1
Air Volume
Effective Throw Range
RTD11 Step-Down
FD11 Flush
L/s
cfm
m
ft.
m
ft.
1227
2600
7-9
24 - 29
6-7
19 - 24
1321
2800
8-9
25 - 30
6-9
20 - 28
1416
3000
8 - 10
27 - 33
6-9
21 - 29
1510
3200
9 - 11
28 - 35
7-9
22 - 29
1604
3400
9 - 11
30 - 37
7-9
22 - 30
1699
3600
8 - 10
25 - 33
7-9
22 - 29
1793
3800
8 - 11
27 - 35
7-9
22 - 30
1888
4000
9 - 11
29- 37
7 - 10
24 - 33
1982
4200
10 - 12
32 - 40
8 - 11
26 - 35
2076
4400
10 - 13
34 - 42
9 - 11
28 - 37
2643
5600
12 - 15
39 - 49
9 - 11
28 - 37
2737
5800
13 - 16
42 - 51
9 - 12
29 - 38
2831
6000
13 - 17
44 - 54
12 - 15
40 - 50
2926
6200
14 - 17
45 - 55
13 - 16
42 - 51
3020
6400
14 - 17
46 - 55
13 - 16
43 - 52
3115
6600
14 - 17
47 - 56
14 - 17
45 - 56
hrow is the horizontal or vertical distance an air stream travels on leaving the outlet or diffuser before the maximum velocity is reduced to 15 m (50 ft.) per
T
minute. Four sides open.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 21
ELECTRICAL/ELECTRIC HEAT DATA
Voltage - 50hz 3 Phase with neutral
Compressor 1
Rated Load Amps
Locked Rotor Amps
Compressor 2
Rated Load Amps
Locked Rotor Amps
Outdoor Fan
Full Load Amps
Motors (2)
(total)
1
Power Exhaust
Full Load
(1) 0.19 kW (0.25 HP)
Amps
kW
Indoor Blower
Full Load Amps
Motor
2
Maximum
Unit Only
Overcurrent
With 0.25 kW (0.33 HP)
Protection
Power Exhaust
3
Minimum
Unit Only
Circuit
With 0.25 kW (0.33 HP)
Ampacity
Power Exhaust
ELECTRIC HEAT DATA
Electric Heat Voltage
2
Maximum
Unit+
5.7 kW
Overcurrent 4 Electric Heat
11.5 kW
Protection
17.2 kW
23 kW
34.5 kW
45.9 kW
3
Minimum
Circuit
Ampacity
Unit+
4
Electric Heat
2
Maximum
Overcurrent
Protection
Unit+
4
Electric Heat
and 0.25 kW
(0.33 HP)
Power Exhaust
Minimum
Circuit
Ampacity
Unit+
4
Electric Heat
and 0.25 kW
(0.33 HP)
Power Exhaust
3
5.7 kW
11.5 kW
17.2 kW
23 kW
34.5 kW
45.9 kW
5.7 kW
11.5 kW
17.2 kW
23 kW
34.5 kW
45.9 kW
5.7 kW
11.5 kW
17.2 kW
23 kW
34.5 kW
45.9 kW
LCA092H4
380/420V
6.1
41
6.1
41
1.3
(2.6)
LCA102H4
380/420V
6.1
43
6.1
43
1.3
(2.6)
LCA120H4
380/420V
7.8
51.5
7.8
51.5
1.3
(2.6)
LCA150H4
380/420V
9.7
64
9.7
64
1.5
(3)
1.3
1.3
1.3
1.3
1.5
3.4
25
25
2.2
4.8
25
25
3.7
7.6
30
30
1.5
3.5
25
25
2.2
5
25
25
3.7
7.8
30
30
1.5
3.5
30
30
2.2
5
30
30
3.7
7.8
35
35
1.5
3.5
35
35
2.2
5
35
40
3.7
7.8
40
40
20
22
22
23
25
26
20
22
22
23
25
26
24
25
26
27
28
30
29
30
30
32
33
34
420
25
420
25
420
30
420
25
420
25
420
30
420
---
420
---
420
---
420
---
420
---
420
---
25
35
45
70
---
30
40
50
70
---
30
40
50
70
---
25
35
45
70
---
30
40
50
70
---
30
40
50
70
---
30
35
45
70
70
30
40
50
70
70
35
40
50
70
80
35
35
45
70
70
35
40
50
70
70
40
40
50
70
80
20
25
34
44
64
--25
30
40
50
70
--22
26
36
46
66
---
22
26
36
46
66
--25
30
40
50
70
--23
28
38
48
68
---
25
30
40
50
69
--30
35
45
60
80
--26
32
41
51
71
---
20
25
34
44
64
--25
30
40
50
70
--22
26
36
46
66
---
22
26
36
46
66
--25
30
40
50
70
--23
28
38
48
68
---
25
30
40
50
69
--30
35
45
60
80
--26
32
41
51
71
---
--25
34
44
64
68
--30
40
50
70
70
--26
36
46
66
70
--26
36
46
66
70
--30
40
50
70
80
--28
38
48
68
72
--30
40
50
69
73
--35
45
60
80
80
--32
41
51
71
75
--29
34
44
64
68
--35
40
50
70
70
--30
36
46
66
70
--30
36
46
66
70
--40
40
50
70
80
--32
38
48
68
72
--33
40
50
69
73
--40
45
60
80
80
--34
41
51
71
75
Extremes of operating range are plus and minus 10% of line voltage.
Heating Air Conditioning and Refrigeration (HACR) type breaker or fuse.
Refer to local codes to determine wire, fuse and disconnect size requirements.
4
Nominal kW based on 420V-3ph-50hz.
1
2
3
ELECTRIC HEAT CAPACITIES
Volts
Input
5.7 kW
11.5 kW
17.2 kW
23 kW
34.5 kW
45.9 kW
kW Btuh No. of kW Btuh No. of kW Btuh No. of kW
Btuh No. of kW
Btuh No. of kW
Btuh No. of
Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages Input Output Stages
380
4.7
16 000
1
9.4
32 100
1
14.1 48 200
1
18.8 64 200
2
28.2 96 300
2
37.6 128 400
2
400
5.2
17 800
1
10.4 35 500
1
15.6 53 300
1
20.9 71 400
2
31.2 106 600
2
41.6 142 100
2
420
5.7
19 500
1
11.5 39 300
1
17.2 58 700
1
2
34.5 117 500
2
45.9 156 800
2
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 22
23
78 500
UNIT CLEARANCES - MM (INCHES)
C
OPTIONAL
OUTDOOR
AIR HOOD
D
B
D
A
1
A
Unit Clearance
B
C
D
mm
in.
mm
in.
mm
in.
mm
in.
Service Clearance
1524
60
914
36
914
36
1524
60
Minimum Operation Clearance
914
36
914
36
914
36
914
36
Top
Clearance
Unobstructed
NOTE - Entire perimeter of unit base requires support when elevated above the mounting surface.
1
Service Clearance - Required for removal of serviceable parts.
Minimum Operation Clearance - Required clearance for proper unit operation.
OUTDOOR SOUND DATA
Unit
Model Number
Octave Band Sound Power Levels dBA, re 10-12 Watts Center Frequency - HZ
125
250
500
1000
2000
4000
8000
Sound Rating
Number (dB)
092, 102 and 120
76
79
84
83
79
73
66
88
150
77
80
85
84
79
74
66
88
1
Note - The octave sound power data does not include tonal corrections.
1
Sound Rating Number according to AHRI Standard 370-2001.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 23
THIS PAGE INTENTIONALLY BLANK
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 24
WEIGHT DATA
Model Number
092 Base Unit
092 Max. Unit
102 Base Unit
102 Max. Unit
120 Base Unit
120 Max. Unit
150 Base Unit
150 Max. Unit
Outdoor
Coil
Eco-Last
Eco-Last
Eco-Last
Eco-Last
Eco-Last
Eco-Last
Eco-Last
Eco-Last
kg
472
543
475
546
491
565
509
583
Net
lbs.
1040
1197
1047
1204
1082
1246
1122
1286
Shipping
kg
lbs.
510
1125
582
1282
513
1132
585
1289
529
1167
604
1331
547
1207
622
1371
Outdoor
Coil
Fin/Tube
Fin/Tube
Fin/Tube
Fin/Tube
Fin/Tube
Fin/Tube
Fin/Tube
Fin/Tube
kg
508
579
511
582
527
601
545
620
Net
lbs.
1120
1277
1127
1284
1162
1326
1202
1366
Shipping
kg
lbs.
547
1205
618
1362
550
1212
621
1369
566
1247
640
1411
584
1287
658
1451
OPTIONS / ACCESSORIES
Description
CONVENTIONAL FIN/TUBE CONDENSER COIL
Fin/Tube Condenser Coil
ECONOMIZER / OUTDOOR AIR / EXHAUST
Economizer
Economizer Dampers
Outdoor Air Hood (downflow)
Barometric Relief Dampers (downflow)
Barometric Relief Dampers (low profile horizontal)
Outdoor Air Dampers
Outdoor Air Damper Section (downflow) - Automatic
Outdoor Air Damper Section (downflow) - Manual
Outdoor Air Damper Hood (downflow)
Power Exhaust
ELECTRIC HEAT
5.2 kW
10.4 kW
15.6 kW
20.9 kW
31.2 kW
41.6 kW
DEHUMIDIFICATION SYSTEM
Dehumification Option
ROOF CURBS
Hybrid Roof Curbs, Downflow
203 mm height
356 mm height
457 mm height
610 mm height
Adjustable Pitch Curb, Downflow
356 mm height
CEILING DIFFUSERS
Step-Down
RTD11-95
RTD11-135
RTD11-185
Flush
FD11-95
FD11-135
FD11-185
Transitions
C1DIFF30B-1
C1DIFF31B-1
C1DIFF32B-1
PACKAGING
LTL Packaging (less than truck load)
kg
Shipping Weight
lbs.
36
80
27
10
4
9
60
23
8
20
4
1
4
14
9
2
9
31
23
23
26
26
27
31
50
50
57
57
59
68
9
20
27
39
45
57
60
85
100
125
32
191
40
93
178
88
205
392
34
79
131
75
174
289
14
15
16
30
32
36
48
105
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 25
DIMENSIONS - UNIT - MM (INCHES)
Model
No.
092
102
120
150
CORNER WEIGHTS
AA
Base
kg
127
128
133
138
Max.
lbs.
281
282
294
304
kg
148
149
154
159
lbs.
327
329
340
350
BB
Base
kg
114
115
120
124
CC
Max.
lbs.
252
254
264
273
kg
130
130
135
139
lbs.
286
287
297
306
Base
kg
125
125
128
133
lbs.
275
276
283
293
CENTER OF GRAVITY
EE
DD
Max.
kg
139
139
144
148
Base
lbs.
306
308
318
327
kg
142
143
146
151
Max.
lbs.
312
314
321
332
kg
162
163
169
174
Base
lbs.
358
360
372
383
mm
1181
1181
1181
1181
FF
Max.
in.
46.5
46.5
46.5
46.5
mm
1156
1156
1156
1156
in.
45.5
45.5
45.5
45.5
Base
mm
622
622
622
622
Max.
in.
24.5
24.5
24.5
24.5
mm
648
648
648
648
in.
25.5
25.5
25.5
25.5
Base Unit - The unit with NO INTERNAL OPTIONS.
Max. Unit - The unit with ALL INTERNAL OPTIONS Installed. (Economizer, Standard Static Power Exhaust Fans, Controls, etc.). Does not include accessories external to
unit or high static power exhaust.
156
(6-1/8)
143
(5-5/8)
AA
156
(6-1/8)
1527 (60-1/8)
610
(24)
BOTTOM SUPPLY
AIR OPENING
BB
28
(711)
10-3/4
(508)
686
(27)
CENTER OF
GRAVITY
BOTTOM RETURN
AIR OPENING
BOTTOM
POWER ENTRY
140 (5-1/2) Dia.
EE
178 (7)
DD
FF
168
(6-5/8)
CC
BOTTOM
CONDENSATE
178 (7)
886
(34-7/8)
2572
(101-1/4)
BASE
TOP VIEW
2525
(99-1/4)
1476
(58-1/8)
1191
(46-7/8)
1102
(43-3/8)
1527
(60-1/8)
89
(3-1/2)
1191
(46-7/8)
CONDENSATE
DRAIN (FRONT)
25 (1)
ELECTRIC
INLETS
137
(5-3/8)
FORKLIFT SLOTS
LIFTING HOLES
(BOTH SIDES)
(FOR RIGGING)
2572
(101-1/4)
886
(34-7/8)
END VIEW
SIDE VIEW
HORIZONTAL
SUPPLY AIR
OPENING
394
(15-1/2)
394
(15-1/2)
HORIZONTAL
RETURN AIR
OPENING
41
(1-5/8)
762
(30)
308
(12-1/8)
156
(6-1/8)
CONDENSATE
DRAIN (BACK)
800
(31-1/2)
1686
(66-3/8)
762
(30)
137
(5-3/8)
SIDE VIEW
(Horizontal Openings)
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 26
DIMENSIONS - ACCESSORIES - MM (INCHES)
OUTDOOR AIR HOOD DETAIL
543
(21-3/8)
OUTDOOR AIR HOOD
(Furnished with Economizer or
Outdoor Air Damper)
DOWNFLOW BAROMETRIC
RELIEF DAMPERS
EXHAUST AIR HOOD
(Furnished with Economizer, Field Installed)
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 27
DIMESNIONS - ACCESSORIES - MM (INCHES)
HORIZONTAL ECONOMIZER APPLICATION
(With Furnished Barometric Relief Dampers and Optional Horizontal Discharge Kit - Required)
RETURN AIR DUCT INLET
(Field Fabricated - Must be sized to
accommodate Barometric Relief Hood
and Return Air Requirements)
ECONOMIZER
DAMPERS
HORIZONTAL
BAROMETRIC RELIEF
DAMPERS AND HOOD
SUPPLY AIR DUCT
(Field Provided)
RETURN
AIR
INLET
RETURN AIR
DUCT TRANSITION
(Field fabricated and
installed on unit)
SUPPLY
AIR
OUTLET
BAROMETRIC RELIEF HOOD DIMENSIONS
Width - 794 mm (31-1/4 in.)
Height - 572 mm (22-1/2 in.)
TOP VIEW
OUTDOOR AIR HOOD
(Furnished with Economizer)
762
(30)
394
(15-1/2)
984
(38-3/4)
HORIZONTAL
SUPPLY AIR
OPENING
(On Unit)
543
(21-3/8)
BAROMETRIC RELIEF DAMPERS
Furnished with Economizer, detached
from Economizer and field installed on
Field fabricated Return Air Duct
OUTDOOR
AIR
This opening
not used in
Horizontal
Applications
with
Economizer
HORIZONTAL
RETURN AIR
OPENING
914
(36)
156
(6-1/8)
BACK VIEW
RETURN AIR
DUCT TRANSITION
(Field fabricated and
installed on unit)
105
(4-1/8)
660
(26)
EXHAUST
AIR
502
(19-3/4)
152 (6)
RETURN AIR DUCT INLET
(Field Fabricated - Must be sized to
accommodate Barometric Relief Hood
and Return Air Requirements)
OPTIONAL RETURN AIR OPENING
WITH ECONOMIZER AND HORIZONTAL
DISCHARGE KIT (required)
(Field Installed)
NOTE - Return Air Duct and Transition must be supported.
BAROMETRIC RELIEF DAMPERS
(Furnished with Economizer)
(Field installed in horizontal return air duct adjacent to unit)
807 (31-3/4)
1
756 (29-3/4)
368
(14-1/2)
612
(24)
1
587
(23-1/8)
FRONT VIEW
1
SIDE VIEW
NOTE - Opening size required in return air duct.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 28
705
(27-3/4)
END VIEW
DIMENSIONS - ACCESSORIES - MM (INCHES)
HORIZONTAL ECONOMIZER APPLICATION
(with Optional Low Profile Horizontal Barometric Relief Dampers and Horizontal Discharge Kit - Required)
ECONOMIZER
DAMPERS
HORIZONTAL LOW
PROFILE BAROMETRIC RELIEF
DAMPERS AND HOOD
SUPPLY AIR DUCT
(Field Provided)
RETURN AIR
DUCT TRANSITION
(Field fabricated and
installed on unit)
SUPPLY
AIR
OUTLET
RETURN
AIR
INLET
RETURN AIR DUCT INLET
(Field Fabricated - Must be sized to
accommodate Low Profile
Horizontal Barometric
Relief Hood and
Return Air Requirements)
HORIZONTAL RELIEF HOOD DIMENSIONS
Width - 803 mm (31-5/8 in.)
Height - 368 mm (14-1/2 in.)
TOP VIEW
OUTDOOR AIR HOOD
(Furnished with Economizer)
762
(30)
394
(15-1/2)
HORIZONTAL
SUPPLY AIR
OPENING
(On Unit)
543
(21-3/8)
984
(38-3/4)
This opening
not used in
Horizontal
Applications
with
Economizer
156
(6-1/8)
RETURN AIR
DUCT TRANSITION
(Field fabricated and
installed on unit)
BACK VIEW
HORIZONTAL LOW PROFILE
BAROMETRIC RELIEF DAMPERS
(Optional - Must be Ordered Extra and
Field Installed on Field fabricated
Return Air Duct)
105
OUTDOOR
(4-1/8)
AIR
HORIZONTAL
RETURN AIR
OPENING
705
(27-3/4)
502
(19-3/4)
EXHAUST
AIR
RETURN AIR DUCT INLET
(Field Fabricated - Must be sized to
accommodate Low Profile
Horizontal Barometric
Relief Hood and
eturn Air Requirements)
152
(6)
OPTIONAL RETURN AIR OPENING
WITH ECONOMIZER AND HORIZONTAL
DISCHARGE KIT (required)
(Field Installed)
END VIEW
NOTE - Return Air Duct and Transition must be supported.
HORIZONTAL LOW PROFILE BAROMETRIC RELIEF DAMPERS
(Field installed in horizontal return air duct adjacent to unit)
803 (31-5/8)
1
165
(6-1/2)
749 (29-1/2)
368
(14-1/2)
1
300
(13)
FRONT VIEW
1
SIDE VIEW
NOTE - Opening size required in return air duct.
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 29
DIMENSIONS - ACCESSORIES - MM (INCHES)
HYBRID ROOF CURBS - DOUBLE DUCT OPENING
552
(21-3/4)
2423
(95-3/8)
2334
(91-7/8)
1378
(54-1/4)
756
(29-3/4)
216
(8-1/2)
203 (8)
356 (14)
457 (18)
610 (24)
SUPPLY
OPENING
679
(26-3/4)
RETURN
OPENING
756
(29-3/4)
1289
(50-3/4)
NOTE - Roof deck may be omitted within confines of curb.
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
DETAIL ROOF CURB
PACKAGED
UNIT
44
(1-3/4)
13 (1/2)
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
203 (8)
356 (14)
457 (18)
610 (24)
RIGID INSULATION
(Field Supplied)
44
(1-3/4)
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 30
DIMENSIONS - ACCESSORIES - MM (INCHES)
ADJUSTABLE PITCH CURBS - DOUBLE DUCT OPENING
2423
(95-3/8)
2334
(91-7/8)
1378
1289 (54-1/4)
(50-3/4)
552
(21-3/4)
756
(29-3/4)
SUPPLY
OPENING
679
(26-3/4)
356
(14)
RETURN
OPENING
756
(29-3/4)
152 (6)
940
(37)
BOTTOM CURB
ASSEMBLY
NOTE - Maximum slope pitch is 19 mm per 305 mm (3/4 in. per 1 foot)
in any one direction.
TYPICAL FLASHING DETAIL FOR ROOF CURB
BASE BOTTOM
DETAIL ROOF CURB
PACKAGED
UNIT
44
(1-3/4)
13 (1/2)
FIBERGLASS
INSULATION
(Furnished)
COUNTER FLASHING
(Field Supplied)
FACTORY INSTALLED
PERIMETER WOOD
NAILER STRIP
NAILER STRIP
(Furnished)
ROOF CURB
(Extends around entire
perimeter of unit)
CANT STRIP
(Field Supplied)
ROOFING
MATERIAL
356
(14)
RIGID INSULATION
(Field Supplied)
44
(1-3/4)
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 31
DIMENSIONS - ACCESSORIES - MM (INCHES)
ROOF CURBS WITH SUPPLY & RETURN AIR TRANSITIONS FOR CEILING DIFFUSERS
C1DIFF30B-1 ROUND TRANSITIONS
(for 092 models with FD11-95, RTD11-95 Diffusers)
38
(1-1/2)
Typ.
787
(31)
762
(30)
203
(8)
51 (2)
508 mm (20 in.)
Diameter
SUPPLY
AIR
OPENING
RETURN
AIR
OPENING
C1DIFF31B-1 & C1DIFF32B-1 RECTANGULAR TRANSITIONS
(for 102 thru 150 models with FD11-135-185, RTD11-135-185 Diffusers)
Typ.
762
(30)
38
(1-1/2)
787 (31)
C1DIFF31B-1
991 (39)
C1DIFF32B-1
203 (8))
102
(4)
775
(30-1/2)
TOP VIEW
51 (2)
705 (27-3/4)
C1DIFF31B-1
908 (35-3/4)
C1DIFF32B-1
775
(30-1/2)
451
(17-3/4)
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 32
800 (31-1/2)
C1DIFF30B-1
C1DIFF31B-1
1003 (39-1/2)
C1DIFF32B-1
DIMENSIONS - ACCESSORIES - MM (INCHES)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER
E
FLUSH CEILING DIFFUSER
D
H
G
E
H
F
G
H
G
F
G
C
C
51 (2)
L
51 (2)
A
B
D
H
A
B
J
K
Model Number
A
RTD11-95
mm
in.
B
mm
in.
C
mm
in.
D
mm
in.
E
mm
in.
F
mm
in.
G
mm
in.
H
mm
in.
J
mm
in.
K
mm
in.
L
mm
in.
Duct Size
1159
Model Number
A
47-5/8
752
C
D
E
45-1/2
572
G
349
13-3/4
1156
45-1/2
29-5/8
422
16-5/8
27
mm
mm
mm
mm
in.
Duct Size
752
686
in.
H
47-5/8
in.
in.
11-1/2
1159
mm
in.
F
22-1/2
292
mm
in.
27-1/2
1158
mm
in.
14-3/8
699
mm
in.
B
29-5/8
365
FD11-95
1143
45
22-1/2
572
286
11-1/4
343
13-1/2
mm
508 round
in.
20 round
699
27-1/2
206
8-1/8
mm
508 round
in.
20 round
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 33
DIMENSIONS - ACCESSORIES - MM (INCHES)
COMBINATION CEILING SUPPLY AND RETURN DIFFUSERS
STEP-DOWN CEILING DIFFUSER
F
E
H
G
G
FLUSH CEILING DIFFUSER
J
F
E
D
K
H
G
G
D
J
K
C
C
51 (2)
51 (2)
N
B
B
M
Model Number
A
mm
in.
B
mm
in.
C
mm
in.
D
mm
in.
E
mm
in.
F
mm
in.
G
mm
in.
H
mm
in.
J
mm
in.
K
mm
in.
L
mm
in.
M
mm
in.
N
mm
in.
Duct Size
mm
in.
A
A
L
RTD11-135
1210
47-5/8
905
35-5/8
524
20-5/8
851
33-1/2
1156
45-1/2
114
4-1/2
457
18
64
2-1/2
711
28
70
2-3/4
1156
45-1/2
851
33-1/2
232
9-1/8
457 x 711
18 x 28
RTD11-185
1210
47-5/8
1210
47-5/8
625
24-5/8
1156
45-1/2
1156
45-1/2
114
4-1/2
457
18
64
2-1/2
914
36
121
4-3/4
1156
45-1/2
1156
45-1/2
257
10-1/8
457 x 914
18 x 36
E-Series Packaged Electric / Electric 26 to 44 kW 50 hz / Page 34
Model Number
A
FD11-135
mm
in.
B
mm
in.
C
mm
E
F
H
K
1210
35-5/8
47-5/8
743
mm
838
1143
in.
33
45
1143
1143
mm
in.
45
45
mm
112
112
4-1/2
4-1/2
mm
457
457
in.
18
18
mm
57
57
2-1/4
2-1/4
mm
711
914
in.
28
36
mm
64
114
in.
Duct Size
905
29-1/4
in.
J
1210
47-5/8
591
in.
G
1210
47-5/8
23-1/4
in.
D
FD11-185
mm
in.
2-1/2
4-1/2
457 x 711
457 x 914
18 x 28
18 x 36
REVISIONS
Section
Description
Options/Accessories
Added General Purpose Control Kit, Building Pressure Control and Outdoor Air CFM
Control.
Visit us at www.allied-commercial.com
For the latest technical information, visit us at www.allied-commercial.com
Contact us at 1-800-448-5872
NOTE - Due to Allied Commercial ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.