UMG 104 UMG 104 – Energy measurement device for DIN rails

UMG 104 UMG 104 – Energy measurement device for DIN rails
UMG 104
Harmonics
Temperature input
Measurement accuracy 0.5
Memory 4 MByte
UMG 104 – Energy measurement device for DIN rails
Communication
• Profibus (DP / V0 – optional)
• Modbus RTU
Interfaces
• RS232
• RS485
Accuracy of measurement
• Energy: Class 0.5S (… / 5 A)
• Current: 0.2 %
• Voltage: 0.2 %
Power quality
• Harmonics up to 40th harmonic
• Unbalance, rotary field indication
• Distortion factor THD-U / THD-I
Networks
• IT, TN, TT networks
• 3 and 4-phase networks
• Up to 4 single-phase networks
Temperature measurement
• PT100, PT1000, KTY83, KTY84
2 digital inputs
• Pulse input
• Signalling input logic
• State monitoring
2 digital outputs
• Pulse output kWh / kvarh
• Switch output
• Threshold value output
• Logic output
Measured data memory
• 4 MByte Flash (156,000 measured
values)
Network visualisation software
• GridVis®-Basic (in the scope of supply)
1
UMG 104
Areas of application
• Consumption data acquisition and evaluation (load profiles,
load curves)
• Continuous power quality monitoring
• Cost centre accounting of energy costs
• Network protection
• Measured value transducer for building management systems
or PLC
Main features
Power quality
• Harmonics analysis up to 40th harmonic
• Unbalance
• Rotary field indication
• Distortion factor THD-U / THD-I
• Measurement of positive, negative and zero sequence component
High-speed Modbus
Fig.: GridVis® – Phasor diagram
• Fast and reliable data exchange via
RS485 interface
• Speed up to 921.6 kB/s
Secure and rapid communication via
Modbus and Profibus
• Rapid, cost-optimised and reliable communication in existing
Fieldbus architectures
• Integration in PLC systems and building management systems
• High flexibility due to the use of open standards
High-speed
Modbus
Large measurement data memory
• 4 MByte
• 156,000 saved values
• Recording range dependent on the user-defined measurement
data memory configuration over a few months
• Recording freely configurable
2
Fig.: High-speed Modbus
UMG 104
Added value through additional functions
UMG 104
he UMG 104 goes far beyond the limits of digital multifunction
T
measurement devices thanks to the integration of additional
functions:
• Multifunction measurement device
• State monitoring
• Data logger
• Meters (kWh, kvarh)
• Temperature monitoring
• Harmonics analyser
Fig.: Large measurement data memory
Due to the four current and voltage inputs there are also
particular advantages with the monitoring of up to four singlephase outputs, e.g. in data centres, offices or single-phase motor
outputs.
Dimension diagrams
44 mm
35 mm
107,5 mm
90 mm
90 mm
73 mm
10 mm
All dimensions in mm
50 mm
76 mm
82 mm
Front view
Side view
3
UMG 104
Typical connection
UMG104
Profibus connector
Terminating resistors
D-sub,
9 pin,
connector
Load
D-sub,
9 pin,
socket
Other
profibus
sations
Screw-type terminals
Device overview and technical data
UMG 104
Item number
UMG 104P
52.20.003
Item number (UL)
52.20.201
-
52.20.205
52.20.202
Supply voltage AC
95 ... 240 V AC
50 ... 110 V AC
20 ... 50 V AC
95 ... 240 V AC
Supply voltage DC
135 … 340 V DC
50 … 155 V DC
20 … 70 V DC
135 … 340 V DC
RS485: 9.6 – 921.6 kbps
(Screw-type terminal)
•
•
•
•
RS232: 9.6 – 115.2 kbps
(Screw-type terminal)
•
•
•
•
Profibus DP: Up to 12 Mbps
(DSUB-9-socket)
-
-
-
•
Communication
Interfaces
General
Use in low and medium voltage networks
Accuracy voltage measurement
Accuracy current measurement
Accuracy active energy (kWh, …/5 A)
Number of measurement points per period
Uninterrupted measurement
•
0.2 %
0.25 %
Class 0.5S
400
•
Comment: For detailed technical information please refer
to the operation manual and the Modbus address list.
Current, voltage, frequency
•
• = included - = not included
Active, reactive and apparent power / total and per phase
•
Power factor / total and per phase
•
RMS - momentary value
4
An RS232 connecting cable is not included in the delivery
and must be ordered separately as item no. 08.02.427.
UMG 104
Energy measurement
Active, reactive and apparent energy [L1,L2,L3, L4, ∑ L1–L3, ∑ L1–L4]
•
Recording of the mean values
Voltage, current / actual and maximum
•
Active, reactive and apparent power / actual and maximum
•
Frequency / actual and maximum
•
Demand calculation mode (bi-metallic function) / thermal
•
Other measurements
Clock
•
Power quality measurements
UMG104
1st – 40th
Harmonics per order / active and reactive power
1st – 40th
Distortion factor THD-U in %
•
Distortion factor THD-I in %
•
Voltage unbalance
•
Rotary field indication
•
Current and voltage, positive, zero and negative sequence component
•
Measured data recording
Profibus connector
Memory (Flash)
Terminating resistors
D-sub,
9 pin,
socket
Harmonics per order / current and voltage
D-sub,
9 pin,
connector
Other
profibus
sations
4 MB
Average, minimum, maximum values
•
Measured data channels
4
Alarm messages
•
Time stamp
Screw-type terminals
Fig.: Profibus connector, contact allocation
•
Time basis average value
freely user-defined
RMS averaging, arithmetic
•
Displays and inputs / outputs
LCD display
•
Digital inputs
2
Digital outputs (as switch or pulse output)
2
Thermistor input (PT100, PT1000, KTY83, KTY84)
•
Voltage and current inputs
every 4
Password protection
•
Communication
Protocols
Modbus RTU
•/•
-/•
Profibus DP V0
Software GridVis®-Basic*1
kWh, °C, kW
UMG 104
Online graphs
•
Databases (Janitza DB, Derby DB); MySQL, MS SQL with higher GridVis® versions)
•
Manual reports (energy, power quality)
•
Topology views
•
Manual read-out of the measuring devices
•
Graph sets
•
Programming / threshold values / alarm management
UMG 511
Ethernet
Modbus
Internet
Comparator (2 Groups with 4 comparators each)
•
Technical data
Type of measurement
Constant true RMS
Up to 40th harmonic
Nominal voltage, three-phase, 4-conductor (L-N, L-L)
277 / 480 V AC
Nominal voltage, three-phase, 3-conductor (L-L)
480 V AC
Measurement in quadrants
4
Networks
TN, TT, IT
Measurement in single-phase / multi-phase networks
1 ph, 2 ph, 3 ph, 4 ph and up to 4 times 1 ph
Measured voltage input
Fig.: Word-wide remote monitoring of the energy
consumption and temperature for various different
locations
Comment: For detailed technical information please refer
to the operation manual and the Modbus address list.
• = included - = not included
*1 Optional additional functions with the packages
GridVis®-Professional, GridVis®-Service and
GridVis®-Ultimate.
Overvoltage category
300 V CAT III
Measured range, voltage L-N, AC
(without potential transformer)
10 … 600 Vrms
Measured range, voltage L-L, AC
(without potential transformer)
18 … 1,000 Vrms
Resolution
0.01 V
Impedance
4 MOhm / phase
Frequency measuring range
45 ... 65 Hz
Power consumption
approx. 0.1 VA
Sampling frequency
20 kHz / phase
5
UMG 104
Measured current input
Rated current
1/5A
Resolution
1 mA
Measurement range
0.001 … 8.5 Amps
Overvoltage category
300 V CAT III
Measurement surge voltage
4 kV
Power consumption
approx. 0.2 VA (Ri = 5 MOhm)
Overload for 1 sec.
100 A (sinusoidal)
Sampling frequency
20 kHz
Digital inputs and outputs
Number of digital inputs
2
Maximum counting frequency
20 Hz
Input signal present
18 ... 28 V DC (typical 4 mA)
Input signal not present
0 ... 5 V DC, current < 0.5 mA
Number of digital outputs
2
Switching voltage
max. 60 V DC, 30 V AC
Switching current
max. 50 mA Eff AC / DC
Pulse output (energy pulse)
max. 20 Hz
Maximum cable length
up to 30 m unscreened,
from 30 m screened
Mechanical properties
Weight
350 g
Device dimensions in mm (H x W x D)
90 x 107.5 x approx. 82
Battery
Type Lithium CR2032, 3 V
Protection class per EN 60529
IP20
Assembly per IEC EN 60999-1 / DIN EN 50022
35-mm DIN rail
Connecting phase (U / I),
Single core, multi-core, fine-stranded
Terminal pins, core end sheath
0.08 to 2.5 mm²
1.5 mm²
Environmental conditions
Temperature range
Operation: K55 (-10 ... +55 °C)
Relative humidity
Operation: 5 to 95 % (at 25 °C)
Operating height
0 ... 2,000 m above sea level
Degree of pollution
2
Installation position
user-defined
Electromagnetic compatibility
Electromagnetic compatibility of
electrical equipment
Directive 2004/108/EC
Electrical appliances for application within
particular voltage limits
Directive 2006/95/EC
Equipment safety
Safety requirements for electrical
equipment for measurement, regulation, control
and laboratory use –
Part 1: General requirements
IEC/EN 61010-1
Part 2-030: Particular requirements for
testing and measuring circuits
IEC/EN 61010-2-030
Noise immunity
Industrial environment
IEC/EN 61326-1
Electrostatic discharge
IEC/EN 61000-4-2
Voltage dips
IEC/EN 61000-4-11
Emissions
Class B: Residential environment
IEC/EN 61326-1
Radio disturbanc voltage strength 30 – 1000 MHz
IEC/CISPR11/EN 55011
Radiated interference voltage 0.15 – 30 MHz
IEC/CISPR11/EN 55011
Safety
Europe
CE labelling
USA and Canada
UL variants available
Firmware
Firmware update
Update via GridVis® software.
Firmware download (free of charge)
from the website:
http://www.janitza.com
Comment:
For detailed technical information please refer to the operation manual and the Modbus address list.
• = included - = not included
6
Was this manual useful for you? yes no