Trinity

Mk II

WOODBURNING STOVE

SAFETY NOTICE

Please read this entire manual before you install and use your new room heater. Failure to follow instructions may result in property damage, bodily injury or even death.

If this stove is not properly installed, a house fire may result. For your safety, follow the installation directions.

Contact local building or fire officials about restrictions and installation inspection requirements in your area.

This appliance is hot while in operation and retains its heat for a long period of time after use. Children, aged or infirm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled.

This stove must be connected to a UL/U.L.C. listed High Temperature residential chimney, Factory Built,

Residential Type and Building Heating Appliance, UL 103 or a code approved masonry chimney flue liner constructed in accordance with NFPA 211 Chimney Vents and Solid Fuel Burning Appliances

Manufactured by Waterford Stanley (Marketing) Limited, Bilberry, Waterford, Ireland.

INSTALLATION & OPERATING INSTRUCTIONS

TABLE OF CONTENTS

PAGE NO.

1.

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2.

Pre-Installation Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

3.

Top Flue Exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

4.

Rear Flue Exit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

5.

Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

6.

Blower Operation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

7.

Floor Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

8.

Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

9.

Outside Air Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

10.

Mobile Home Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

11.

Minimum Clearances to Combustible Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

12.

Reduced Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

13.

Double Wall Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

14.

Wall Protectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

15.

Chimney . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

16.

Chimney Types: USA Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

17.

Chimney Types: Canada Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

18.

Chimney Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

19.

Connecting to Masonry Chimney . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

20.

Thimbles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

21.

Chimney Connector Systems, Thimbles & Clearances from Combustible Walls . . . . . . 8

22.

Masonry Fireplace. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

23.

Ventilation & Combustion Air Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

24.

Spillage Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

25.

Lighting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

26.

Primary Air Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

27.

Low or Overnight Burn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

28.

Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

29.

De-Ashing (When Fire has Burned Out) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

30.

Disposal of Ashes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

31.

Creosote (Formation & Need for Removal) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

32.

Glass Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

33.

Glass Cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

34.

Vitreous Enamel Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

35.

Fire Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

36.

In the Event of a Chimney Fire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

37.

Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

1

WATERFORD TRINITY MKII WOODBURNING STOVE INSTALLATION AND OPERATING

INSTRUCTIONS

GENERAL

When installing, operating and maintaining your

Waterford Trinity MK II Stove respect basic standards of fire safety. Read these instructions carefully before commencing the installation. Failure to do so may result in damage to persons and property. Consult your local Municipal office, Fire

Department and your insurance representative to determine what regulations are in force. Save these instructions for further reference.

The complete installation must be done in accordance with current Standards and Local

Codes. It should be noted that the requirements and these publications may be superseded during the life of this manual.

Fig.2

PRE-INSTALLATION ASSEMBLY

(a) After removing the stove from its packing, open the ashpit door (item 13 in exploded view) and remove the contents

(b) Open the firedoor (item 8) and remove the contents of the firebox, leaving the bricks in place.

(c) Remove the ashlip (item 12) from the rear of the stove if you have not already done so. Remove the loose fitting hob (item 3) and place on a nonabrasive surface.

Fig.1

(f) Fit the front ashlip (item 12) using two of the ashlip brackets (item 35) and screw together using four

1

/

4

” (6mm) x

1

/

2

” (12mm) hex head bolts provided. Stand the stove upright taking care not to strain the back leg bolts.

Fig.3

(g) Fit the wooden handle (item 28) to the fuelling door (item 8)

Fig.4

(d) Place the plastic packing on the ground at the left hand side of the stove.

NOTE: As the stove is very heavy take care when laying the stove on its side on top of the packing.

(e) Remove the wooden pallet by taking out the 4 retaining screws from the base of the legs (item

2). Discard brackets & woodscrews, replace levelling screws.

2 h) If the side fuelling door (item 21) is to be used, fit the side ash lip (item 24) using two ashlip brackets (item 35) and screw together using four

1/4” (6mm) x 1/2” (12mm) hex head bolts provided.

Take out the chrome locking bolt and fit door latch

(item 73), the door latch spigot (item 40), and the wooden handle (item 28) provided.

Fig.5

Fig. 7

This stove can be connected to either a top or rear exit by simply reversing the orientation of the flue spigot (item 5) on the flue spigot flange.

For either the top or the rear exit option place the ceramic gasket onto the flue spigot flange – located at the top of the back plate (item 31).

TOP FLUE EXIT

Screw the top outlet hob filler piece (item 6) onto the hob (item 3), screw top outer blanking plate (item

29) onto the heat shield (item 30) using the two

1

/

4

(6mm) x

3

/

4

” (19mm) C/S screws provided.

Fig. 6

BLOWER

Caution: Moving parts may cause injury. Do not operate unit with blower housing removed.

Danger: Risk of electric shock. Disconnect power before servicing unit.

Hot parts: Do not operate unit with blower housing removed.

The Listed Waterford Trinity Optional Blower comes assembled, wired, and ready for use.

To fit the Listed Waterford Trinity MK II Optional

Blower take off rear heat shield (item 30) and fit listed blower assembly (item 75) as per illustrations below.

This unit must be connected to a grounded,

Standard 110 volt, 60 Hz electrical outlet, Never route the power cord under or in front of the unit.

Do not, under any circumstances, cut or remove the grounding prong from the power cord.

Do not use an adaptor plug.

Fig. 8

REAR FLUE EXIT

Screw the rear outlet hob filler piece (item 57) to the hob (item 3) using the two screws provided.

Screw the rear outlet heat shield blanking plate (item

58) to the heat shield (item 30) using the two

1

/

4

(6mm) x

3

/

4

” (19mm) C/S screws provided.

3

BLOWER OPERATION INSTRUCTIONS

1. Press switch to ON position (see fig. 9).

2. Fan will power up when stove temperature reaches snap switch operating temperature.

3. Fan operation will cease each time stove temperature drops below snap switch operating temperature.

Fig. 9

Fig. 12

200mm

50mm

50mm

200mm

450mm

Fig. 10

Air inlet duct

FLOOR PROTECTION

When installing this heater on a combustible floor, a floor protector, consisting of a layer of noncombustible material at least

3/8

” (9mm) thick or

1/4

(6mm) thick covered with

1/8

” (3mm) sheet metal is required to cover the area under the heater and to extend to at least 18” (450mm) at the front and 8”

(200mm) to the sides. This will provide protection from sparks and embers which may fall out from the door when stoking or fuelling.

Fig. 11

200mm

200mm 200mm

450mm

LOCATION

There are several conditions to be considered when selecting a location for your Waterford Trinity MK II

Wood Stove.

(a) Distance from a safe chimney.

(b) Position in the area to be heated - central locations are usually best.

(c) Allowances for proper clearances to combustibles.

(d) Obstruction in the ceiling, upper floor or roof, for example, ducting, plumbing, electrical fittings and wiring, overhead fixed furnishings etc.

WARNING:

DO NOT CONNECT TO OR USE IN

CONJUNCTION WITH ANY AIR DISTRIBUTION

DUCTWORK UNLESS SPECIFICALLY

APPROVED FOR SUCH INSTALLATION

DO NOT OBSTRUCT FREE AIR SUPPLY TO THE

AIR INLET DUCT LOCATED AT THE BACK OF

THE STOVE.

Fig. 13

450mm

If the side door is to be used the floor protector must extend at least 18” (450mm) from the right side of the stove when looking from the front.

Air Inlet

Duct

OUTSIDE AIR CONNECTION

This stove may be connected direct to the outside of the house for its combustion air supply.

The primary air inlet (item 55) located at the bottom of the back panel (item 31) may be connected to outside air.

4

To connect this stove to an outside air supply use either 4” (100mm) rigid of flexible stainless steel pipes or non-combustible corrosion-resistant materials not more than 54” (1370mm) in length and having no sharp bends or corners other than the down turn at the terminus. The outside air inlet terminus must be fitted with a

1

/

4

” (6mm) x

1

/

4

” (6mm) corrosion-resistant wire mesh to prevent leaves, and rodents entering from the outside.

Air inlets traversing cavity walls should include a continuous duct across the cavity. The duct should be installed in such a manner as not to impair the weather resistance of the cavity.

Joints between air vents and outside walls should be sealed to prevent ingress of moisture.

Fig.14

elevation of any part of the Mobile Home within

10 ft. (3040mm) of the chimney.

7. The chimney systems shall comply with the standard for Chimneys Factory - Built Residential Type and Building Heating Appliances UL

103.

8. Any openings in a chimney guard if used must not permit the entrance of

3

/

4

” (19mm) diameter rod.

9. CAUTION: THE STRUCTURAL INTEGRITY

OF THE MOBILE HOME ROOF, FLOOR,

WALLS AND CEILING MUST BE

MAINTAINED.

10. Check any other local building code as other local codes may apply.

11. WARNING: DO NOT INSTALL IN A

SLEEPING ROOM.

NOTE: Listed factory built chimney connectors including elbows are acceptable for use in Mobile

Home Installations.

Air Duct

Wire Mesh

MOBILE HOME INSTALLATION

In addition to standard installation instructions the following requirements are mandatory for installation in a mobile home.

CAUTION: Do not obstruct combustion air opening.

1. The stove must be permanently bolted to the floor of the Mobile Home using the floor screws provided.

2. The stove must have a permanent outside air source for combustion.

3. The stove must be grounded to the steel chassis of the Mobile Home.

4. A listed chimney system, roof thimble, spark arrestor and roof flashing kit suitable for use in

Mobile Homes must be used.

5. If the chimney exits the Mobile Home at a location other than through the roof, and exits at a point 7 ft. (2100mm) or less above the ground level on which the Mobile Home is positioned, a guard or method of enclosing the chimney shall be fitted at the point of exit for a height up to 7 ft.

(2100mm).

6. The chimney shall be attached directly to the room heater and shall extend at least 3 ft.

(910mm) above the part of the roof through which it passes. The top of the chimney should project at least 2 ft. (610mm) above the highest

5

MINIMUM CLEARANCES TO COMBUSTIBLE

MATERIALS

From the front of stove 48” (1220mm)

From the side of stove 22” (560mm)

From corner installation 14” (355mm)

From back of stove horizontal installation only 8” (200mm)

If the side door is to be used the right hand side clearances when looking from the front of the stove must be increased to 48” (1220mm)

Mantle clearance

30”Trim Clearance 22” (560mm)

Vertical Single Wall Flue Pipe (USA) 14” (355mm)

Vertical Single Wall Flue Pipe (Canada) 18” (460mm)

USA from back of stove 15” (380mm)

Canada from back of stove 19” (480mm)

This stove has been tested in a combustible alcove measuring 84” high x 72” wide x 48” deep.

Fig.15

560mm 560mm

200mm

Fig.16

(c) When listed pipe shields are used - top exit option only - the clearances may be reduced to

9” (225mm) from the pipe shield and 11 ”

(280mm) from stove back.

Fig.24

Fig.17

(355mm)

(355mm)

Fig.18

(560mm) (1220mm)

Fig.25

(225mm)

Fig.26

Fig.19

(760mm)

Fig.20

(560mm)

(760mm)

(560mm)

(560mm)

(560mm)

Fig.21

(355mm)

USA

DOUBLE WALL CONNECTIONS

Double wall chimney connectors may be substituted for the shielded pipe provided it is UL/ULC listed for a 9” (225mm) clearance or less.

Fig.23

Fig.22

(460mm)

CANADA

2130mm

1830mm

1220mm

REDUCED CLEARANCES

Under certain conditions the minimum clearances may be reduced by means of:

(a) The use of listed pipe shields, installed in accordance with the manufacturer’s instructions.

(b) Shields constructed in accordance with

NFPA211 (USA), Can3-B365 installation code for solid fuel fired appliances.

6

WALL PROTECTORS

Materials and products listed for the purpose of reducing clearance to combustibles shall be installed in accordance with the conditions of the listing and the clearances may be reduced by the percentage reduction as stated in the wall shield manufacturer’s instructions.

For clearance reduction systems using an air space between the combustible wall and the wall protector, adequate air circulation shall be provided by one of the following methods.

1. Adequate air circulation may be provided by leaving all edges of the air protector open with at least a 1” (25mm) air gap.

2. If the wall protector is mounted on a single flat wall, away from corners, an adequate air circulation may be provided by leaving bottom and top edges or only the side and top edges open with at least a 1 ” (25mm) air gap.

3. Wall protectors that cover two walls in a corner shall be open at the bottom and top edges with at least a 1” (25mm) air gap.

4. All clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the Waterford

Trinity MK II Stove disregarding any intervening protection applied to the combustible material.

When using a manufactured wall shield system observe local building codes and by-laws.

Poor draught conditions will result in poor performance.

NOTE: Connection to type “B” gas vents approved for connection to certain gas burning appliance will only result in a fire.

Fig.27

CHIMNEY TYPES: USA ONLY

The stove must be connected to a UL 103 Listed residential type HT and Building Heating Appliance

Chimney installed in accordance with the manufacturer’s instructions or a masonry chimney constructed in accordance with NFPA 211 Chimney

Vents and Solid Fuel Burning Appliances.

(25mm)

CHIMNEY TYPES: CANADA ONLY

The stove must be connected to an Underwriters

Laboratories of Canada Labelled factory built 650 o

C c h i m n e y, installed in accordance with the manufacturer’s instructions or in a lined masonry chimney acceptable to the authority having jurisdiction.

Fig.28

Fig.29

(25mm)

(25mm)

CHIMNEY

The Waterford Trinity MK II Stove is a radiant room heater and must be connected to a chimney of the proper size and type capable of providing an adequate continuous draught or 0.06” wg minimum.

It is best to connect to a chimney of the same size as the stove spigot. Connection to a large size may result in somewhat less draught. DO NOT

CONNECT TO A CHIMNEY SERVING ANOTHER

APPLIANCE.

Minimum chimney height is 15 feet (4570mm) from floor on which stove is installed. An existing masonry chimney should be inspected and, if n e c e s s a r y, repaired by a competent mason or relined using an approved relining system.

7

CHIMNEY CONNECTOR

The chimney connector (smoke pipe) is used to connect the Waterford Trinity MK II Stove to the chimney described above. The chimney connector must be made of Corrosion Resistant Steel, 24 gauge or heavier (black or equivalently treated steel). Be sure to fasten the chimney connectors together and also to the flue outlet of the stove through the two holes provided. Use at least two screws for each joint/connection. Be sure that the joints are tight and fully sealed.

A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, floor or ceiling.

Where passage through a wall or partition of combustible construction is desired, the installation shall conform to NFPA 211 or CAN/CSA - B365.

The connector should maintain a pitch or rise of at least

1/4

” (6mm) per foot from the stove to the chimney. It should be installed so as to avoid sharp turns or other combustion features that would create excessive resistance to the flow of flue gases. It should be securely supported. The entire length of a connector should be readily accessible for inspection, cleaning and replacement.

CONNECTING TO MASONRY CHIMNEY

The connector to a masonry chimney must extend through the wall to the inner face or liner but not beyond, and must be firmly cemented to masonry.

The connector may pass through walls or partitions constructed o combustible material to a masonry chimney provided the connector system selected is installed in accordance with the proper clearances and conditions.

THIMBLES

Thimbles for chimney or vent connector should be fire clay (ASTM C 315, specification for Clay Flue

Linings), galvanised steel of minimum thickness of

24 gauge, or material equivalent durability.

Thimbles should be installed without damage to the liner. The thimble should extend through the wall to, but not beyond, the inner face of the liner and should be firmly cemented to masonry.

Thimbles should be located to provide adequate pitch or rise of chimney or vent connectors and, where the ceiling above the appliance is constructed of combustible material, the location of the thimble should provide minimum clearance required for the connector as specified in section under “Minimum Clearances to Combustibles”.

Insulation material used as part of wall passthrough system should be of non-combustible material and should have a thermal conductivity of

1.0 Btu.in./ft.F (4.88kg.cal/hr.m.C) or less. All clearances and thicknesses are minimums; larger clearances and thicknesses are acceptable. Any material used to close up an opening for the connector should be masonry chimney, except for system 2 (under heading “Chimney Connector

Systems, Thimbles and Clearances”), shall extend to piece through the wall pass-through system and the chimney wall to the inner face of the flue liner, but not beyond.

Fig.30

(230mm)

(50mm)

(305mm) to

(305mm) of brick

(230mm) min.

(50mm)

CHIMNEY CONNECTOR SYSTEMS,

THIMBLES, AND CLEARANCES FROM

COMBUSTIBLE WALLS

1. Minimum 3

1

/

2

” (90mm) thick brick masonry wall framed into combustible wall with a min. of 12”

(305mm) brick separation from clay liner to combustibles, Fire Clay Liner (ASTM C315 or equivalent) min.

5

/

8

” (16mm) wall thickness, should run from outer surface of chimney flue liner and should be firmly cemented in place.

2. Solid insulated listed factory-built chimney length of the same inside diameter as the chimney connector and having 1” (25mm) or more of insulation with a min. 9” (229mm) air space between the outer wall of the chimney length and combustibles. The inner end of the chimney length shall be flush with the inside of the masonry chimney flue and shall be sealed to the flue and to the brick masonry penetration with non-water-soluble refractory cement.

Supports should be securely fastened to wall surfaces on all sides. Fasteners between supports and the chimney length shall not penetrate the chimney liner.

8

3. Sheet steel chimney connector, min. 24 gauge in thickness, with a ventilated thimble, having two

1” (25mm) air channels, separated from combustibles by a min. of 6” (150mm) of glass fibre insulation. Opening should be covered and thimble supported with a sheet steel support, min. 24 gauge in thickness. Supports should be securely fastened to wall surfaces on all sides and should be sized to fit and hold chimney section. Fasteners used to secure chimney sections should not penetrate chimney flue liner.

Fig.31

Minimum 6” (150mm) fibre Insulation

(25mm)

(50mm)

(25mm) constructed of sheet steel

4. Solid insulated listed factory-built chimney length with an inside diameter 2” (50mm) larger than the chimney connector and having 1” (25mm) or more of insulation, serving as a pass-through for a single wall sheet steel chimney connector of min. 24 gauge thickness, with a min. 2” (50mm) air space between the outer wall of chimney section and combustibles. Minimum length of chimney section shall be 12” (305mm). Chimney section concentric with and spaced 1” (25mm) away from connector by means of sheet steel support plates on both ends of chimney section.

Opening shall be covered and chimney section supported on both sides with sheet steel supports of min. 24 gauge thickness.

Supports should be securely fastened to wall surfaces on all sides and shall be sized to fit and hold chimney section. Fasteners used to secure chimney sections should not penetrate chimney flue liner.

Fig. 32 fireplace, no less than 8” (200mm) above the bottom of the first flue tile, by installing a stainless steel or other listed chimney connector from the fireplace damper and smoke chamber, terminating at the first flue tile, or by installing a stainless steel or other listed relining system from the flue outlet up the entire length of the chimney, where necessary.

Fig.33

Air Space 2” (50mm)

(50mm)

Minimum Clearance 2” (50mm)

1” (25mm) air space to chimney length

MASONRY FIRE PLACE

The stove may be installed on the hearth extension of a masonry fireplace. In Canada a continuous line must be provided from the flue collar of the stove to the top of the chimney. In the USA a continuous chimney flue is required. A minimum clearance of

30” (760mm) is required to combustible mantle and a minimum clearance of 22” (560mm) to the side trim, which extends less than 2” (50mm) from the face of the fireplace. (See section under “Minimum

Clearances to Combustibles”).

Before installation, the entire fireplace system should be inspected for condition and code compliance prior to connecting to the the fireplace chimney. Older fireplaces and chimneys may not have been constructed to current relevant codes.

The fireplace and chimney should be in, or brought up to, acceptable conditions and proper clearances should be met before connecting to the fireplace chimney.

The size of the flue must be considered. If the fireplace chimney is too large, reline using the chimney using an approved relining system.

Connection to a masonry chimney may be done by breaching into the chimney from the front of the

9

In Canada when connecting to a masonry fireplace the steel chimney connector must terminate at the top of the masonry chimney or flue liner.

Fig.34

IMPORTANT: BURN WOOD ONLY. DO NOT BURN

COAL, SYNTHETIC LOGS OR OTHER FUELS.

BURN DIRECTLY ON HEARTH, DO NOT USE A

GRATE OR ELEVATE FIRE.

“NEVER USE GASOLINE”, GASOLINE TYPE

LANTERN FUEL, KEROSENE, CHARCOAL

LIGHTER FLUID OR SIMILAR LIQUID TO START

OR “FRESHEN UP” A FIRE IN THIS HEATER.

KEEP ALL SUCH LIQUIDS WELL AWAY FROM

THE HEATER WHILE IT IS IN USE.

OPERATE STOVE ONLY WITH FUELLING DOOR

AND ASHPIT DOOR CLOSED.

THIS HEATER IS HOT WHILST IN OPERATION.

KEEP CHILDREN, CLOTHING AND FURNITURE

A SAFE DISTANCE AWAY.

VENTILATION & COMBUSTION AIR

REQUIREMENTS

Ventilation and adequate air supply is necessary to supply combustion air to the appliance. Refer to your Local Authority for current requirements in your juristriction.

Outside combustion air may be required if:

1.

The solid-fuel-fired appliance does not draw steadily, smoke rollout occurs, fuels burns poorly, or back drafts occur whether or not there is combustion present.

2.

Existing fuel-fired equipment in the house, such as fireplaces or other heating appliances, smell, do not operate properly, suffer smoke roll-out when opened, or back-draft whether or not there is combustion present.

3.

Opening a window slightly on a calm

(windless) day alleviates any of the above symptoms.

4.

The house is equipped with a well-sealed vapour barrier and tight fitting windows and/or has any powered devices that exhaust house air. (e.g extraction hoods and tumble dryers etc.)

5.

There is excessive condensation on windows in the winter.

6.

A ventilation system is installed in the house.

If these or other indications suggest that infiltration air is inadequate, additional combustion air should be provided from the outdoors. Outside combustion air can be provided to the appliance by the following means.

1.

Direct connection: Refer to O.S.A. Hook-up in this manual.

2.

Indirect method: for an appliance not certified for direct connection of outside combustion air, than (12”) 300mm from the appliance, to void affecting the performance of the appliance.

3.

A mechanical ventilation system: if the house has a ventilation system (air change or heat recovery): a. The ventilation system may be able to provide sufficient combustion make-up air for the solid-fuel-fired appliance.

b. The householder should be informed that the ventilation system might need to be re-balanced by a ventilation technician after installation of the appliance.

SPILLAGE TEST

1.

Light/burn appliance under normal conditions in accordance with this installation manual.

2.

Close all doors and windows.

3.

Operate all appliances requiring a full rate

(eg. extraction hoods, tumble dryers etc).

4.

Check for spillage.

LIGHTING

(a) Replace ashpan (item 37), close ashpit door

(item 13), and make sure the ash dump sliding door (item 42) is closed by pushing in ash dump lever (item 54) located at the bottom of the left side panel when looking from the front of stove.

(b) Open fire door (item 8) and open the primary air duct (item 55) by pulling the primary air control lever (item 66) located at the right corner under the ashlip (item 12) all the way towards the front.

(c) Cover hearth with crumpled pieces of paper. Lay dry pieces of kindling approximately

1

/

2

” (12mm) x

1

/

2

” (12mm) x 20” (508mm) long on top of the paper towards the back of the firebox. Ignite and close the fire door (item 8). When the kindling has ignited, open the firedoor (item 8) and add larger pieces of dry wood. Close the firedoor

(item 8). When a hot bed of coals is established add the normal fuel of well seasoned split logs approximately 20” (508mm) long. Once the logs are well lighted, adjust the primary air control lever (item 66) to the required output.

Refuelling – Open the firedoor (item 8) and carefully level the embers and re-load with logs, close the firedoor.

NEVER STORE FUEL WITHIN SPACE HEATER

INSTALLATION CLEARANCES OR WITHIN THE

SPACE REQUIRED FOR CHARGING AND ASH

REMOVAL.

PRIMARY AIR SETTINGS

MAXIMUM – Pull control lever (item 66) all the way towards the front.

LOW (MIN) – Push the control lever (item 66) all the

10

Fig.35

DISPOSAL OF ASHES

Remove ash carefully. Ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be placed on the ground, well away from all combustible materials, pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispersed they should be retained in closed container until all cinders have thoroughly cooled.

Fig.37

LOW OR OVERNIGHT BURN

NOTE: The duration of low or overnight burn is affected by:

Draught conditions: Excessive draught reduces burn time. Quality of fuel load. If the stove and flue temperature at the start of a low or overnight burn are too high it will result in reducing burn time.

1. Allow the fire bed to cool down.

2. Re-load using full length wood (preferably unsplit).

3. Do not pack the fuel load as high as the secondary air tubes (item 47).

4. An air space is necessary between the fuel load and secondary air baffle (item 47) to avoid impingement of the secondary air on the top of the fuel load resulting in speeding up the burn rate.

5. Adjust the primary air control lever (item 66) to the minimum setting by pushing it all the way towards the back.

MAINTENANCE

DO NOT CLEAN STOVE WHEN HOT

DE-ASHING (When the fire has burned out)

When the ash build-up becomes excessive in the fire chamber (3

1

/

2

” (88mm) deep or so) it must be removed by allowing the fire to burn out. When the fire has burned out, open the firedoor (item 8). Pull open the ashpit shutter (item 54). The control knob

(item 45) for this is on the left hand side of the stove.

Rake the ash into the ashpan (item 37) through the grating (item 46) in the centre of the hearth. Push closed the ashpit shutter (item 54) and dispose of the ashes by removing the ashpan (item 37) from the stove.

Fig.36

CREOSOTE (Formation and the need for removal)

When wood is burned slowly, it produces tar and other organic vapours, which combine with expelled moisture to form creosote. The Creosote vapours condense in the relatively cool chimney flue of a slow burning fire. As a result creosote residue accumulates on the flue lining. When ignited this creosote makes an extremely hot fire. The chimney connector and chimney should be inspected at least twice monthly during the heating season to determine if a creosote build-up has occurred. If creosote has accumulated it should be removed to reduce the risk of chimney fire.

Inspect the chimney connector frequently. Tap the connector with your finger when the pipe is cool. If you hear a dull echo, the pipe may need cleaning.

Disassemble the chimney connector and clean the sections. Replace corroded pipe sections. The fitting of a slip-joint in the stove makes the dismantling easy for cleaning and inspection of chimney and stove.Replace the empty ashpan (item 37) in the stove, close the ashpit door (item 13) and re-light the fire.

When inspecting a masonry chimney, start at the cleanout door, normally found in the basement, at the base of the chimney, or on the outside. If your chimney does not have a clean-out door it must be inspected and cleaned by removing stove from chimney.

GLASS REPLACEMENT

(a) Open the firedoor (item 8) fully.

(b) Remove the four corner screws and clips (items

70) and carefully remove the broken glass.

(c) Clean the glass recess in the door.

(d) Attach adhesive thermal tape to the perimeter of the replacement glass.

(e) Place the thermal taped side of the glass into the

11

firedoor recess and replace the four corner clips

(items 70) and screws.

(f) Tighten screws.

(g) Replace glass only with ceramic glass

3

/

16

(5mm) thick.

Fig.38

FIRE SAFETY

To provide reasonable fire safety the following should be given serious consideration.

(1) Do not overfire the stove. If the stove or chimney connector glows, you are overfiring.

(2) Overfiring will also damage painted or enamel finishes on the stove.

(3) The installation of fire detectors.

(4) A conveniently located class “A” fire extinguisher to contend with small fires resulting from burning embers.

(5) A practical evacuation plan.

(6) A plan to deal with a chimney fire as follows:

IN THE EVENT OF A CHIMNEY FIRE

(a) Notify the fire department.

(b) Prepare occupants for immediate evacuation.

(c) Close all openings into the stove.

(d) While awaiting the fire department watch for ignition to adjacent combustibles from overheated stove pipe or from hot embers or sparks from the chimney.

WARNING: DO NOT OPERATE THE STOVE

WITH BROKEN OR CRACKED GLASS. ABUSE

SUCH AS STRIKING, SLAMMING AND USE OF

SUBSTITUTE MATERIALS SHOULD BE

AVOIDED.

GLASS CLEANING

The glass will clean itself when there is sufficient heat generated by the burning fuel. If a build-up of creosote occurs on the glass due to poor draught conditions, poor quality fuel or very low burning for long periods of time, it is best to clean the glass manually when glass is thoroughly cooled.

VITREOUS ENAMEL CLEANING

General cleaning must be carried out when the stove is cool.

If this stove is finished in a high gloss vitreous enamel, to keep the enamel in the best condition observe the following tips:

1.

Wipe over daily with a soapy damp cloth, followed by a polish with a clean dry duster.

2.

For stubborn deposits a soap impregnated pad can be carefully used on the vitreous enamel.

3.

DO NOT USE ABRASIVE PADS OR OVEN

CLEANSERS CONTAINING CITRIC ACID

ON ENAMELLED SURFACES. ENSURE

THAT THE CLEANSER MANUFACTUR

ERS INSTRUCTIONS ARE ADHERED TO.

12

ITEM NO.’S

1.

Leg

2.

Base

3.

Outer Back Panel

4.

Left Hand Side Panel

5.

Right Hand Side Panel

6.

Front

EXPLODED VIEW

28. Fire Fence

29. Fire Fence Spike

30. Heat Exchanger

31 Hob

32. Flue Spigot

33. Hob Extension -

(Horizontal)

34. Hob Extension -

(Vertical)

34A.Knob to Shutter

35. Side Shelf (Optional)

36. Side Shelf Bracket

(Optional)

37. Front ADS Assembly

38. Top Air Duct Assembly

40. Side Filler Plates

41. Mesh Cover for

Ceramic Blanket

42. Lower Air Box

Assembly

43. Left Side Wall Brick

44. Floor Bricks

45. Side Door Insulation

Sheet

46. Ceramic Blanket

47. Heatshield

48. Filler Plate

49. Window Glass

50. Window Clip

51. Rope Channel

52. Ash Pan

53. Ash Pan Lifting Tool

54. Door Latch

55. Door Catch

56. Tension Pin

57. Ash Pit Door Handle

58. Ash Door Latch

59. Door Latch

60. Hinge

61. Door Hinge

62. Door Handle

62A.Side Door Handle

63. Door Handle Axle

7.

Front Door

8.

Door Grille

9.

Side Door

10. Side Door

Protection Plate

11. Ash Pit Door

12. Front Ash Tray

13. Side Ash Tray

14. Combustion Chamber

Base Plate

15. Fire Bed Grate

16. Guide to Ashpit

Sliding Door

16A.Ashpit Sliding Door

17. Inner Back Panel

18. Inner Back Panel RH

Filler Casting

19. Inner Back Panel LH

Filler Casting

21. RH Front Air Duct

(Ramp)

22. LH Front Air Duct

(Ramp)

23. Outer Air Spigot

24. Inner Air Spigot

25. Damper Spacer

26. Damper Flap (ULC

Stoves)

27. Damper Flap (UL

Stoves)

13

64. Spacer to Door

Handle

66. Spacer to Door

Handle Axle

67. Door Stop

69. Damper Handle

70. Primary Air Flap

Axle

71. Primary Air Control

Link Rod

72. Primary Air Control

Lever

73. Primary Air Control

Lever Spacer (Small)

64. Spacer to Door

Handle

66. Spacer to Door

Handle Axle

67. Door Stop

69. Damper Handle

70. Primary Air Flap

Axle

71. Primary Air Control

Link Rod

72. Primary Air Control

Lever

73. Primary Air Control

Lever Spacer (Small)

75. Ashtray Bracket

76. Ashtray Strap

78. Ash Side Shaft

99. Flue Spigot Shield

(Optional)

101.Ducting for Optional

Fan

102.Optional Fan

Assembly

103.Hob Bracket

(Optional)

75. Ashtray Bracket

76. Ashtray Strap

78. Ash Side Shaft

99. Flue Spigot Shield

(Optional)

101.Ducting for Optional

Fan

102.Optional Fan

Assembly

103.Hob Bracket

(Optional)

Manufactured by

WATERFORD STANLEY

Bilberry, Waterford, Ireland.

Tel. 051-302300 Fax 051-302375

14