Intrinsically safe isolation barriers and backplanes with full SIL

Intrinsically safe isolation barriers and backplanes with full SIL
Intrinsically safe isolation barriers and backplanes
with full SIL assessment
We deliver the safest signals by validating our products against the toughest safety standards.
Through our commitment to innovation, we have made pioneering achievements in developing I.S.
interfaces with full SIL assessment that are both efficient and cost-effective.
Our comprehensive range of analog and digital intrinsically safe isolation
barriers offers multifunctional inputs and outputs, making PR an easy-to-implement site standard.
Our backplanes further simplify large installations and provide seamless integration to standard
DCS systems.
I.S. interfaces
I.S. Interface
9106B – HART® transparent repeater
B.2
9107B – HART® transparent driver
B.4
9113B – Temperature / mA converter
B.6
9116B – Universal converter
B.8
9202B – Pulse isolator B.10
9203B – Solenoid / alarm driver B.12
7908 – System 9000 backplane, 8 devices B.14
7916 – System 9000 backplane, 16 devices B.16
5104B – Ex repeater / power supply B.18
5105B – Ex-isolated driver B.20
B
5106B – HART® transparent repeater B.22
5107B – HART® transparent driver B.24
5114B – Programmable transmitter B.26
5115B – Ex signal calculator B.28
5116B – Programmable transmitter B.30
5131B – 2-wire programmable transmitter B.32
5202B – Pulse isolator B.34
5203B – Ex solenoid / alarm driver B.36
5223B – Programmable f/I-f/f converter B.38
5420B – Ex power supply B.40
B.1
HART® transparent repeater
9106B
– 24 VDC supply via power rail or connectors
– Active and passive mA input
– Active or passive output via the same two terminals
– Splitter function - 1 in and 2 out
– SIL2 / SIL3 Full Assessment and certified acc. to IEC 61508
B
Application
• 9106B is a 1- or 2-channel isolated 1:1 repeater barrier for
intrinsic safety applications.
• The device supplies 2-wire SMART transmitters and can also
be used for 2-wire SMART current sources. HART® & BRAIN
protocols are supported and are transferred bi-directionally.
• 9106B can be mounted in the safe area or in zone 2 / Cl. 1,
div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21,
22 including mining / Class I/II/III, Div. 1, Gr. A-G.
• The PR 4501 displays the process value for each channel
and can be used to define high and low limits for detection of
loop current level. If these limits are exceeded, the status
relay will activate.
• In the 1-channel version the status relay can be used as a
simple limit switch.
• I.S. splitter application - 1 input and 2 outputs.
• In the dual channel version the 9106B can be implemented in
a SIL3 loop.
Connections
Advanced features
• The PR 4501 detachable display and the green and red front
LEDs indicate operation status for each channel.
• A tag number can be defined for each channel.
• Monitoring of error events and cable breakage on input via
the individual status relay and/or a collective electronic signal
via the power rail.
Technical characteristics
• High galvanic isolation of 2.6 kVAC.
• Fast response time <5 ms
• High accuracy better than 0.1%.
• 2-wire transmitter supply >16 V.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
B.2
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...13.2 Hz.....................................
Vibration: 13.2...100 Hz.................................
Common specifications
Supply voltage...............................................
Fuse...............................................................
Max. power consumption...............................
Max. internal power dissipation......................
Isolation voltage, test /working:
Input to any....................................................
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
250 g
265 g / 350 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1 mm
±0.7 g
19.2...31.2 VDC
1.25 A SB / 250 VAC
≤ 3 W (2 channels)
≤ 2 W (2 channels)
2.6 kVAC / 300 VAC
reinforced isolation
Analog output to supply................................. 2.6 kVAC / 300 VAC
reinforced isolation
Status relay to supply..................................... 1.5 kVAC / 150 VAC
reinforced isolation
SMART bi-directional communication
frequency range............................................. 0.5...7.5 kHz
Signal / noise ratio......................................... > 60 dB
Response time (0...90%, 100...10%)............. < 5 ms
Accuracy........................................................ Better than 0.1% of selected
range
mA, absolute accuracy................................... ≤ ±16 μA
mA, temperature coefficient........................... ≤ ±1.6 μA / °C
Effect of supply voltage change
on output (nom. 24 VDC)............................... < ±10 μA
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Output specifications
Current output: Signal range.........................
Load (max.)....................................................
Load stability, current output..........................
Current limit....................................................
Effect of external 2-wire
supply voltage variation.................................
Max. load resistance [Ω]................................
Max. external 2-wire supply...........................
Status relay output terminal
33-34: Relay function.....................................
Programmable low setpoint...........................
Programmable high setpoint..........................
Hysteresis for setpoints..................................
Max. voltage, status relay..............................
Max. current, status relay...............................
Max. voltage - hazardous installation.............
Max. current - hazardous installation.............
*of span..........................................................
3.5...23 mA
20 mA/600 Ω/12 VDC
≤0.01% of span / 100 Ω
≤ 28 mA
< 0.005% of span / V
(Vsupply - 3.5) / 0.023 A
26 VDC
B
N.C.
0...29.9 mA
0...29.9 mA
0.1 mA
110 VDC / 125 VAC
0.3 ADC / 0.5 AAC
32 VDC / 32 VAC
1 ADC / 0.5 AAC
= normal measurement range
4...20 mA
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
ATEX 2004/108/EC........................................ DEKRA 11ATEX0244 X
IECEx............................................................. DEK 11.0084X
FM.................................................................. 0003044327-C
INMETRO....................................................... NCC 12.1302 X
UL................................................................... UL 61010-1
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
DNV Marine.................................................... Stand. f. Certific. No. 2.4
CCOE............................................................. P337349/1
SIL.................................................................. SIL 2 / SIL3 certified & fully
assessed acc. to IEC 61508
Input specifications
3,5...23 mA
>16 V / 20 mA
>15 V / 20 mA
< 1 mA
< 4 V @ 23 mA
< 6 V @ 23 mA
9106B-030115
Current input: Measurement
range..............................................................
2-wire transmitter supply
9106B1x (Uo = 28 VDC)................................
2-wire transmitter supply
9106B2x (Uo = 25.6 VDC).............................
Sensor error detection: Loop
break 4...20 mA..............................................
Input voltage drop, supplied
unit.................................................................
Input voltage drop, non-supplied
unit.................................................................
B.3
HART® transparent driver
9107B
– 24 VDC supply via power rail or connectors
– Fast response time
– High active output load 725 Ohm / 20 mA
– Output line fault detection via status relay
– SIL2 certified via Full Assessment according to IEC 61508
B
Application
• 9107B is a 1- or 2-channel isolated 1:1 driver barrier for
intrinsic safety applications.
• Operation and drive control of I/P converters, valves and
indicators mounted in the hazardous area.
• Operation of HART® devices is possible as the unit transmits
HART® communication signals bi-directionally.
• 9107B can be mounted in the safe area or in zone 2 / Cl. 1,
div. 2 and transmit signals to zone 0, 1, 2 and zone 20, 21, 22
including mining / Class I/II/III, Div. 1, Gr. A-G.
• The PR 4501 displays the process value for each channel
and can be used to define high and low limits for detection of
loop current level. If these limits are exceeded, the status
relay will activate.
• Dual channel versions can be used for signal splitter
applications - 1 in and 2 out.
Connections
Advanced features
• The PR 4501 detachable display and the green and red front
LEDs indicate operation status for each channel.
• A tag number can be defined for each channel.
• Output line fault detection.
• In the 1-channel version the status relay can be used as a
simple limit switch.
Technical characteristics
• High galvanic isolation of 2.6 kVAC.
• High accuracy better than 0.1%.
• Continuous check of vital stored data for safety reasons.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
B.4
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...13.2 Hz.....................................
Vibration: 13.2...100 Hz.................................
Common specifications
Supply voltage...............................................
Fuse...............................................................
Max. power consumption...............................
Max. internal power dissipation......................
Isolation voltage, test /working:
Input to any....................................................
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
250 g
265 g / 350 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1 mm
±0.7 g
19.2...31.2 VDC
1.25 A SB / 250 VAC
≤ 2 W (2 channels)
≤ 2 W (2 channels)
2.6 kVAC / 300 VAC
reinforced isolation
Analog output to supply................................. 2.6 kVAC / 300 VAC
reinforced isolation
Status relay to supply..................................... 1.5 kVAC / 150 VAC
reinforced isolation
HART bi-directional communication
frequency range............................................. 0.5...7.5 kHz
Signal / noise ratio......................................... > 60 dB
Response time (0...90%, 100...10%)............. < 5 ms
Accuracy........................................................ Better than 0.1% of selected
range
mA, absolute accuracy................................... ≤ ±16 μA
mA, temperature coefficient........................... ≤ ±1.6 μA / °C
Effect of supply voltage change
on output (nom. 24 VDC)............................... < ±10 μA
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Output specifications
Current output: Signal range.........................
Load (max.)....................................................
Load stability, current output..........................
Current limit....................................................
Status relay output terminal
33-34: Relay function.....................................
Programmable low setpoint...........................
Programmable high setpoint..........................
Hysteresis for setpoints..................................
Max. voltage, status relay..............................
Max. current, status relay...............................
Max. voltage - hazardous installation.............
Max. current - hazardous installation.............
*of span..........................................................
3.5...23 mA
20 mA/725 Ω/14.5 VDC
≤0.01% of span / 100 Ω
≤ 28 mA
N.C.
0...29.9 mA
0...29.9 mA
0.1 mA
110 VDC / 125 VAC
0.3 ADC / 0.5 AAC
32 VDC / 32 VAC
1 ADC / 0.5 AAC
= normal measurement range
4...20 mA
B
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
ATEX 2004/108/EC........................................ DEKRA 11ATEX0247 X
IECEx............................................................. DEK 11.0088X
FM.................................................................. 0003044327-C
INMETRO....................................................... NCC 12.1300 X
UL................................................................... UL 61010-1
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
CCOE............................................................. P337349/2
DNV Marine.................................................... Stand. f. Certific. No. 2.4
SIL.................................................................. SIL 2 certified & fully assessed
acc. to IEC 61508
Input specifications
Current input: Measurement
range..............................................................
Sensor error detection: Loop
break 4...20 mA..............................................
Input voltage drop, supplied
unit.................................................................
Input voltage drop, non-supplied
unit.................................................................
3,5...23 mA
< 1 mA
< 2 V @ 23 mA
< 4 V @ 23 mA
9107B-030115
B.5
Temperature / mA converter
9113B
– Input for RTD, TC and mA
– Active / passive mA output
– 1 or 2 channels
– Can be supplied separately or installed on power rail, PR type 9400
– SIL 2-certified via Full Assessment
B
Advanced features
• Configuration and monitoring by way of detachable display
front (PR 4501); process calibration and signal simulation.
• Copying of the configuration from one device to others of the
same type via the display front.
• TC inputs can use either the internal CJC or a terminal with a
built-in Pt100 sensor (PR 5910Ex, channel 1 / PR 5913Ex,
channel 2) for higher accuracy.
• The device automatically detects whether it must supply an
active or a passive current signal.
• Advanced monitoring of internal communication and stored
data.
• SIL 2 functionality is optional and must be activated in a menu
point.
Connections
Application
• The device can be mounted in the safe area and in zone 2 /
cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20,
21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
• Conversion and scaling of temperature (Pt, Ni and TC) and
active current signals.
• The 9113 has been designed, developed and certified for use
in SIL 2 applications according to the requirements of IEC
61508.
Technical characteristics
• 1 green and 2 red front LEDs indicate operation status and
malfunction.
• 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
B.6
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...13.2 Hz.....................................
Vibration: 13.2...100 Hz.................................
Common specifications
Supply voltage...............................................
Fuse...............................................................
Max. power consumption...............................
Isolation voltage, test /working:
Input to any....................................................
Analog output to supply.................................
Status relay to supply.....................................
Communications interface.............................
Signal / noise ratio.........................................
Accuracy........................................................
Average response time incl.
delay: Temperature input...............................
mA input.........................................................
EMC immunity influence................................
Extended EMC immunity: NAMUR
NE 21, A criterion, burst.................................
Input specifications
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
250 g
265 g / 350 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1 mm
±0.7 g
19.2...31.2 VDC
400 mA SB / 250 VAC
≤ 3.5 W (2 channels)
2.6 kVAC / 300 VAC
reinforced isolation
2.6 kVAC / 300 VAC
reinforced isolation
1.5 kVAC / 150 VAC
reinforced isolation
Communication enabler 4511
/ Programming front 4501
Min. 60 dB (0...100 kHz)
Better than 0.1% of selected
range
≤1s
≤ 0.4 s
< ±0.5% of span
< ±1% of span
B
Output specifications
Current output: Signal range......................... 0...20 mA
Programmable current ranges....................... 0...20 / 4...20 / 20...0 and
20...4 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Sensor error indication, current
output............................................................. 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
Output limitation, on 4...20
and 20...4 mA signals.................................... 3.8...20.5 mA
Output limitation, on 0...20
and 20...0 mA signals.................................... 0...20.5 mA
Current limit.................................................... ≤ 28 mA
2-wire 4…20 mA output: External
2-wire supply range........................................ 3.5...26 VDC
Signal range................................................... 4…20 mA
Max. load resistance [Ω]................................ (Vsupply - 3.5) / 0.023 A
Load stability, 4…20 mA output..................... ≤ 0.01% of span / 100 Ω
Effect of external 2-wire
supply voltage variation................................. < 0.005% of span / V
Max. voltage, status relay.............................. 110 VDC / 125 VAC
Max. current, status relay............................... 0.3 ADC / 0.5 AAC
Max. AC power, status relay.......................... 62.5 VA / 32 W
*of span.......................................................... = of the currently selected
measurement range
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
ATEX 2004/108/EC........................................ KEMA 07ATEX0148 X
IECEx............................................................. KEM 09.0052X
FM.................................................................. 3038279-C
INMETRO....................................................... NCC 12.1310 X
UL................................................................... UL 61010-1
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
DNV Marine.................................................... Stand. f. Certific. No. 2.4
CCOE............................................................. P337349/3
SIL.................................................................. SIL 2 certified & fully assessed
acc. to IEC 61508
9113B-030115
RTD input....................................................... Pt10, Pt20, Pt50, Pt100,
Pt200, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100,
Ni120, Ni1000
Cable resistance per wire
(max.), RTD.................................................... 50 Ω
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
Sensor error detection, RTD.......................... Programmable ON / OFF
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC) via ext. sensor in
connector 5910.............................................. 20...28°C ≤ ±1°C, -20...20°C /
28...70°C ≤ 2°C
CJC via internally mounted
sensor............................................................ ±(2.0°C + 0.4°C * Δt)
Δt =................................................................. Internal temperature-ambient
temperature
Sensor error detection, TC............................. Programmable ON or OFF
(only wire breakage)
Sensor error current: When
detecting / else............................................... Nom. 2 μA / 0 μA
Current input: Measurement
range.............................................................. 0...20 mA
Current input: Programmable
measurement ranges..................................... 0...20 and 4...20 mA
Input resistance, current
input............................................................... Nom. 20 Ω + PTC 50 Ω
Sensor error detection, current
input............................................................... Programmable ON / OFF
B.7
Universal converter
9116B
– Input for RTD, TC, Ohm, potentiometer, mA and V
– Supply for 2-wire transmitters
– Active / passive mA output and relay output
– Can be supplied separately or installed on power rail, PR type 9400
– SIL 2-certified via Full Assessment
B
Advanced features
• Configuration and monitoring by way of detachable display
front (PR 4501); process calibration, signal and relay
simulation.
• Advanced relay configuration, e.g. setpoint, window, delay,
sensor error indication and power monitoring.
• Copying of the configuration from one device to others of the
same type via PR4501.
• Reduced Uo Ex data < 8.3 V for active input signals.
• TC inputs with internal CJC or external CJC for higher
accuracy.
• The device automatically detects whether it must supply an
active or a passive current signal.
Connections
Application
• 9116B can be mounted in the safe area and in zone 2 / cl. 1
div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21,
22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
• Conversion and scaling of temperature, voltage,
potentiometer and linear resistance signals.
• Power supply and signal isolator for 2-wire transmitters.
• Monitoring of error events and cable breakage via the
individual status relay and/or a collective electronic signal via
the power rail.
• The 9116 has been designed, developed and certified for use
in SIL 2 applications according to the requirements of IEC
61508.
Technical characteristics
• 1 green and 1 red front LED indicate operation status and
malfunction. 1 yellow LED indicates relay status.
• 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
B.8
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...13.2 Hz.....................................
Vibration: 13.2...100 Hz.................................
Common specifications
Supply voltage...............................................
Fuse...............................................................
Max. power consumption...............................
Isolation voltage, test /working:
Input to any....................................................
Analog output to supply.................................
Status relay to supply.....................................
Communications interface.............................
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
185 g
200 g / 285 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1 mm
±0.7 g
19.2...31.2 VDC
1.25 A SB / 250 VAC
≤ 3.5 W
2.6 kVAC / 300 VAC
reinforced isolation
2.6 kVAC / 300 VAC
reinforced isolation
1.5 kVAC / 150 VAC
reinforced isolation
Communication enabler 4511
/ Programming front 4501
Min. 60 dB (0...100 kHz)
Signal / noise ratio.........................................
Response time (0...90%, 100...10%):
Temperature input (programmable)............... 1...60 s
mA / V input (programmable)......................... 0.4...60 s
Accuracy........................................................ Better than 0.1% of selected
range
Auxiliary supplies for 9116B1:
2-wire supply (terminal 54...52)...................... 28...16.5 VDC / 0...20 mA
Auxiliary supplies for 9116B2:
2-wire supply (terminal 54...52)...................... 22...16.5 VDC / 0...20 mA
Input specifications
B
Output specifications
Current output: Signal range......................... 0...20 mA
Programmable current ranges....................... 0...20 / 4...20 / 20...0 and
20...4 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Sensor error indication, current
output............................................................. 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
Output limitation, on 4...20
and 20...4 mA signals.................................... 3.8...20.5 mA
Output limitation, on 0...20
and 20...0 mA signals.................................... 0...20.5 mA
Current limit.................................................... ≤ 28 mA
2-wire 4…20 mA output: External
2-wire supply range........................................ 3.5...26 VDC
Signal range................................................... 4…20 mA
Max. load resistance [Ω]................................ (Vsupply - 3.5) / 0.023 A
Load stability, 4…20 mA output..................... ≤ 0.01% of span / 100 Ω
Effect of external 2-wire
supply voltage variation................................. < 0.005% of span / V
Relay output: Relay functions........................ Setpoint, Window, Sensor
error, Power and Off
ON and OFF delay......................................... 0...3600 s
Sensor error reaction..................................... Break / Make / Hold
Max. voltage................................................... 250 VAC / 30 VDC
Max. current................................................... 2 AAC / 2 ADC
Max. AC power.............................................. 500 VA / 60 W
Max. voltage, status relay.............................. 110 VDC / 125 VAC
Max. current, status relay............................... 0.3 ADC / 0.5 AAC
Max. AC power, status relay.......................... 62.5 VA / 32 W
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
ATEX 2004/108/EC........................................ KEMA 10ATEX0053 X
IECEx............................................................. KEM 10.0022X
FM.................................................................. 3038267-C
INMETRO....................................................... NCC 12.1309 X
UL................................................................... UL 61010-1
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
CCOE............................................................. P337349/4
DNV Marine.................................................... Stand. f. Certific. No. 2.4
SIL.................................................................. SIL 2 certified & fully assessed
acc. to IEC 61508
9116B-061515
RTD input....................................................... Pt10, Pt20, Pt50, Pt100,
Pt200, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100,
Ni120, Ni1000
Cable resistance per wire
(max.), RTD.................................................... 50 Ω
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
Sensor error detection, RTD.......................... Programmable ON / OFF
Short circuit detection, RTD........................... Yes
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC) via ext. sensor in
connector 5910.............................................. 20...28°C ≤ ±1°C, -20...20°C /
28...70°C ≤ 2°C
CJC via internally mounted
sensor............................................................ ±(2.0°C + 0.4°C * Δt)
Δt =................................................................. Internal temperature-ambient
temperature
Sensor error detection, TC............................. Programmable ON or OFF
(only wire breakage)
Current input: Measurement
range.............................................................. 0...20 mA
Current input: Programmable
measurement ranges..................................... 0...20 and 4...20 mA
Input resistance, current
input............................................................... Nom. 20 Ω + PTC 50 Ω
Sensor error detection, current
input............................................................... Loop break 4...20 mA
Voltage input: Measurement
range.............................................................. 0...10 VDC
Programmable measurement ranges,
VDC................................................................ 0/0.2...1, 0/1...5, 0/2...10 VDC
Input resistance, voltage
input............................................................... Nom. >10 MΩ
B.9
Pulse isolator
9202B
– Interface for NAMUR sensors and switches
– Extended self-diagnostics and detection of cable fault
– 1 or 2 channels
– Can be supplied separately or installed on power rail, PR type 9400
– SIL 2-certified via Full Assessment
B
Advanced features
• Configuration and monitoring by way of detachable display
front (PR 4501).
• Selection of direct or inverted function for each channel via
PR 4501.
• Advanced monitoring of internal communication and stored
data.
• Optional redundant supply via power rail and/ or separate
supply.
• SIL 2 functionality is optional and must be activated in a menu
point.
Connections
Application
• 9202B can be mounted in the safe area or in zone 2 / Cl. 1
div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21,
22 including mining / Class I/II/III, Div. 1, Gr. A-G.
• Pulse isolator for transmission of signals to the safe area from
NAMUR sensors and mechanical switches installed in the
hazardous area.
• Monitoring of error events and cable breakage via the
individual status relay and/or a collective electronic signal via
the power rail.
• The 9202B has been designed, developed and certified for
use in SIL 2 applications according to the requirements of IEC
61508.
Technical characteristics
• 1 green and 2 yellow/red front LEDs indicate operation status
and malfunction.
• 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
B.10
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...13.2 Hz.....................................
Vibration: 13.2...100 Hz.................................
Common specifications
Supply voltage...............................................
Fuse...............................................................
Max. power consumption...............................
Isolation voltage, test /working:
Input to any....................................................
Analog output to supply.................................
Output 1 to output 2.......................................
Status relay to supply.....................................
Communications interface.............................
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
170 g
185 g / 270 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1 mm
±0.7 g
19.2...31.2 VDC
400 mA SB / 250 VAC
≤ 3 W (2 channels)
2.6 kVAC / 300 VAC
reinforced isolation
2.6 kVAC / 300 VAC
reinforced isolation
1.5 kVAC / 150 VAC
reinforced isolation
1.5 kVAC / 150 VAC
reinforced isolation
Communication enabler 4511
/ Programming front 4501
< 200 ms
Output specifications
Relay output: Max. switching
frequency.......................................................
Max. voltage...................................................
Max. current...................................................
Max. AC power..............................................
Max. voltage, status relay..............................
Max. current, status relay...............................
Max. AC power, status relay..........................
Opto, NPN outputs: Max. switching
frequency.......................................................
Min. pulse length, NPN output.......................
Max. load, current / voltage............................
Voltage drop at 80 mA...................................
20 Hz
250 VAC / 30 VDC
2 AAC / 2 ADC
500 VA / 60 W
110 VDC / 125 VAC
0.3 ADC / 0.5 AAC
62.5 VA / 32 W
B
5 kHz
> 0.1 ms
80 mA / 30 VDC
< 2.5 VDC
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
ATEX 2004/108/EC........................................ KEMA 07ATEX0146 X
IECEx............................................................. KEM 06.0039X
FM.................................................................. 3034430-C
INMETRO....................................................... NCC 12.1307 X
UL................................................................... UL 61010-1
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
CCOE............................................................. P337349/5
DNV Marine.................................................... Stand. f. Certific. No. 2.4
SIL.................................................................. SIL 2 certified & fully assessed
acc. to IEC 61508
Response time for cable fault........................
Auxiliary supplies: NAMUR
supply............................................................. 8 VDC / 8 mA
Input specifications
Sensor types.................................................. NAMUR according to EN
60947-5-6 / mechanical
contact
Frequency range............................................ 0...5 kHz
Min. pulse length............................................ > 0.1 ms
Input resistance.............................................. Nom. 1 kΩ
Trig level, signal............................................. < 1.2 mA, > 2.1 mA
Trig level, cable fault...................................... < 0.1 mA, > 6.5 mA
9202B-030515
B.11
Solenoid / alarm driver
9203B
– Universal Ex driver for solenoids, acoustic alarms and LEDs
– Extended self-diagnostics
– 1 or 2 channels
– Can be supplied separately or installed on power rail, PR 9400
– SIL 2-certified via Full Assessment
B
Advanced features
• Universal I.S. driver for the control of solenoids etc. with
various I.S. data by way of three built-in I.S. barriers.
• Two hardware versions make it possible to choose either Low
(35 mA) or High (60 mA) current output.
• Configuration and monitoring by way of detachable display
front (PR 4501).
• Selection of direct or inverted function for each channel via
PR 4501 and the possibility of reducing the output current to
the hazardous area to suit the application.
• Optional monitoring of the output current to the hazardous
area by way of PR 4501.
• Optional redundant supply via power rail and/or separate
supply.
Connections
Application
• 9203B can be mounted in the safe area or in zone 2 / div. 2
and transmit signals to zone 0, 1, 2 and zone 20, 21, 22
including M1 mining / Class I/II/III, Div. 1, Gr. A-G.
• The 9203B is controlled by an NPN/PNP signal or a switch
signal.
• Monitoring of internal error events via the individual status
relay and/or a collective electronic signal via the power rail.
• The 9203B has been designed, developed and certified for
use in SIL 2 applications according to the requirements of IEC
61508.
Technical characteristics
• 1 green and 2 yellow/red front LEDs indicate operation status
and malfunction.
• 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
B.12
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...13.2 Hz.....................................
Vibration: 13.2...100 Hz.................................
Common specifications
Supply voltage...............................................
Fuse...............................................................
Max. power consumption...............................
Isolation voltage, test /working:
Input to any....................................................
Output 1 to output 2.......................................
Status relay to supply.....................................
Communications interface.............................
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
170 g
185 g / 270 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1 mm
±0.7 g
Output specifications
Output ripple................................................... < 40 mVRMS
Max. voltage, status relay.............................. 110 VDC / 125 VAC
Max. current, status relay............................... 0.3 ADC / 0.5 AAC
Max. AC power, status relay.......................... 62.5 VA / 32 W
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
ATEX 2004/108/EC........................................ KEMA 07ATEX0147 X
IECEx............................................................. KEM 09.0001X
FM.................................................................. 3035277-C
INMETRO....................................................... NCC 12.1306 X
UL................................................................... UL 61010-1
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
DNV Marine.................................................... Stand. f. Certific. No. 2.4
CCOE............................................................. P337349/6
SIL.................................................................. SIL 2 certified & fully assessed
acc. to IEC 61508
B
19.2...31.2 VDC
1.25 A SB / 250 VAC
≤ 3.5 W (2 channels)
2.6 kVAC / 300 VAC
reinforced isolation
1.5 kVAC / 150 VAC
reinforced isolation
1.5 kVAC / 150 VAC
reinforced isolation
Communication enabler 4511
/ Programming front 4501
< ±0.5% of span
EMC immunity influence................................
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Input specifications
Trig level LOW, NPN+switch.......................... ≤ 2.0 VDC
Trig level HIGH, NPN+switch......................... ≥ 4.0 VDC
Max. external voltage, NPN+switch............... 28 VDC
Input impedance, NPN+switch....................... 3.5 kΩ
Trig level LOW, PNP...................................... ≤ 8.0 VDC
Trig level HIGH, PNP..................................... ≥ 10.0 VDC
Max. external voltage, PNP........................... 28 VDC
Input impedance, PNP................................... 3.5 kΩ
9203B-041315
B.13
System 9000 backplane
7908
– Provides safe, easy wiring between the backplane and non I.S.
automation systems using standard prefabricated I/O cables
– Direct, Redundant and Duplicate signalling - including HART I/O
– Robust, compact high-end design solution for 8 system 9000 units
– Digital output and LEDs indicate backplane system status
B
Application
• The 7908 backplane is a compact and robust solution that
enables a safe and easy connection of PR system 9000 IS
device signals into standard automation systems.
• Standard automation system cables and connectors are used
to link the backplane to the I/O cards.
• The backplane can be used for Direct, Redundant, Duplicate
signalling including HART I/O System connectivity (HART
MUX).
• The system 9000 devices isolate and convert AI, AO, DI and
DO signals coming from, or going to the I.S. classified area,
and routes those signals to a system automation I/O card.
• The system 9000 units maintain a SIL2 level of functional
safety, even when mounted in the backplane solution.oop.
Connections
Technical characteristics
• Robust, compact high-end design that holds 8 system 9000
units.
• Digital output indicates status of the 9000 devices and
primary/back-up power supplies.
• Flexible 24 VDC supply voltage and redundant power supply
connection solution.
Mounting / installation / programming
• Flexible horizontal/vertical panel or wall mounting in the Safe
or Zone 2 / Div 2 areas.
• System 9000 devices easily snap ON and OFF using piano
keys, and devices can be hot-swapped.
• Tag number and ID labels are easily mounted and read by
using the dedicated piano key spacer.
• Wide temperature operation range: -20...+60°C.
• Backplane selection guide can be found
at www.prelectronics.com/backplane
B.14
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Relative humidity............................................
Installation in..................................................
-20°C to +60°C
-40°C to +85°C
< 95% RH (non-cond.)
Pollution degree 2 &
measurement / overvoltage
cat. II
Mechanical specifications
Dimensions (HxWxD)..................................... 144 x 247 x 141 mm
Wire size........................................................ 2.5 mm2 / AWG 12
Wire size........................................................ (Supply 1 / 2 and status relay
connectors)
Output specifications
Max. voltage, status relay..............................
Max. voltage, status relay..............................
Max. current, status relay...............................
Max. current, status relay...............................
32 V (Zone 2 / Div. 2 area)
42 V (Safe area)
100 mA (Zone 2 / Div. 2 area)
100 mA (Safe area)
Approvals
EMC............................................................... EN 61326-1
UL................................................................... UL 508
EAC TR-CU 020/2011................................... EN 61326-1
ATEX 2004/108/EC........................................ DEKRA 13ATEX0136X
IECEx............................................................. DEK 13.0044X
FM.................................................................. 0003049918-C
B
Common specifications
Supply voltage............................................... 20...31.2 VDC (24 DC nom.)
Max. power consumption............................... ≤ 30 W
Replaceable fuses......................................... Fuse F1 & F2: 1.6 A SB, 250
V, type TR5
Isolation voltage, test /
working........................................................... 500 VAC / 50 VAC
Isolation voltage, test /
working........................................................... (Basic isolation between
supply 1 & 2 and status relay)
7908-031815
B.15
System 9000 backplane
7916
– Provides safe, easy wiring between the backplane and non I.S.
automation systems using standard prefabricated I/O cables
– Direct, Redundant and Duplicate signalling - including HART I/O
– Robust, compact high-end design solution for 16 system 9000 units
– Digital output and LEDs indicate backplane system status
B
Application
• The 7916 backplane is a compact and robust solution that
enables a safe and easy connection of PR system 9000 IS
device signals into standard automation systems.
• Standard automation system cables and connectors are used
to link the backplane to the I/O cards.
• The backplane can be used for Direct, Redundant, Duplicate
signalling including HART I/O System connectivity (HART
MUX).
• The system 9000 devices isolate and convert AI, AO, DI and
DO signals coming from, or going to the I.S. classified area,
and routes those signals to a system automation I/O card.
• The system 9000 units maintain a SIL2 level of functional
safety, even when mounted in the backplane solution.oop.
Connections
Technical characteristics
• Robust, compact high-end design that holds 16 system 9000
units.
• Digital output indicates status of the 9000 devices and
primary/back-up power supplies.
• Flexible 24 VDC supply voltage and redundant power supply
connection solution.
Mounting / installation / programming
• Flexible horizontal/vertical panel or wall mounting in the Safe
or Zone 2 / Div 2 areas.
• System 9000 devices easily snap ON and OFF using piano
keys, and devices can be hot-swapped.
• Tag number and ID labels are easily mounted and read by
using the dedicated piano key spacer.
• Wide temperature operation range: -20...+60°C.
• Backplane selection guide can be found
at www.prelectronics.com/backplane
B.16
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Relative humidity............................................
Installation in..................................................
-20°C to +60°C
-40°C to +85°C
< 95% RH (non-cond.)
Pollution degree 2 &
measurement / overvoltage
cat. II
Mechanical specifications
Dimensions (HxWxD)..................................... 144 x 443 x 141 mm
Wire size........................................................ 2.5 mm2 / AWG 12
Wire size........................................................ (Supply 1 / 2 and status relay
connectors)
Output specifications
Max. voltage, status relay..............................
Max. voltage, status relay..............................
Max. current, status relay...............................
Max. current, status relay...............................
32 V (Zone 2 / Div. 2 area)
42 V (Safe area)
100 mA (Zone 2 / Div. 2 area)
100 mA (Safe area)
Approvals
EMC............................................................... EN 61326-1
UL................................................................... UL 508
EAC TR-CU 020/2011................................... EN 61326-1
ATEX 2004/108/EC........................................ DEKRA 13ATEX0136X
IECEx............................................................. DEK 13.0044X
FM.................................................................. 0003049918-C
B
Common specifications
Supply voltage............................................... 20...31.2 VDC (24 DC nom.)
Max. power consumption............................... ≤ 60 W
Replaceable fuses......................................... Fuse F1 & F2: 3.15 A SB, 250
V, type TR5
Isolation voltage, test /
working........................................................... 500 VAC / 50 VAC
Isolation voltage, test /
working........................................................... (Basic isolation between
supply 1 & 2 and status relay)
7916-031915
B.17
Ex repeater / power supply
5104B
– 1- or 2-channel version
– 3- / 5-port 3.75 kVAC galvanic isolation
– Loop supply > 17.1 V in hazardous area
– 20 programmable measurement ranges
– Universal supply by AC or DC
B
Application
• Supply voltage and safety barrier for 2-wire transmitters
mounted in a hazardous area.
• Safety barrier for analog current / voltage signals from a
hazardous area.
• 1 : 1 or signal conversion of analog current / voltage signals.
Connections
Technical characteristics
• The 20 factory-calibrated measurement ranges in the 5104B
can be selected by the internal DIP-switches without the need
for recalibration. Special measurement ranges can be
delivered.
• PR5104B is based on microprocessor technology for gain and
offset. The analog signal is transmitted at a response time of
less than 25 ms.
• Inputs, outputs, and supply are floating and galvanically
separated.
• The output can be connected either as an active current /
voltage transmitter or as a 2-wire transmitter.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. By way of the
2-channel version up to 84 channels per meter can be
mounted.
• NB: 5104B is recommended as I.S. barrier for 5331D, 5333D,
5334B, 5343B, 6331B, 6333B, and 6334B.
B.18
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
DIN rail type...................................................
Weight approx................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...25 Hz........................................
Vibration: 25...100 Hz....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
DIN 46277
225 g
1 x 2.5 mm2 stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1.6 mm
±4 g
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 3 W (2 channels)
Internal consumption...................................... ≤ 2 W (2 channels)
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Auxiliary supply: 2-wire supply
(pin 44...42 and 54...52)................................. 28...17.1 VDC / 0...20 mA
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%)............. < 25 ms
Accuracy........................................................ Better than 0.1% of selected
range
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Output specifications
Max. offset...................................................... 20% of max. value
Current output: Signal range......................... 0...20 mA
Min. signal range............................................ 16 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Current limit.................................................... ≤ 28 mA
External loop supply....................................... 29 VDC
Effect of external 2-wire
supply voltage variation................................. < 0.005% of span / V
Voltage output: signal range.......................... 0...1 VDC / 0...10 VDC
Voltage output, min. signal
range.............................................................. 0.8 VDC / 8 VDC
Load (min.)..................................................... 500 kΩ
*of span.......................................................... = of the presently selected
range
B
Approvals
EMC...............................................................
LVD 2006/95/EC............................................
PELV/SELV....................................................
ATEX 2004/108/EC........................................
EN 61326-1
EN 61010-1
IEC 364-4-41 and EN 60742
DEMKO 99ATEX126013, II (1)
GD [EEx ia] IIC
UL................................................................... UL 913, UL 508
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
DNV Marine.................................................... Stand. f. Certific. No. 2.4
Input specifications
Max. offset...................................................... 20% of max. value
Current input: Measurement
range.............................................................. 0...20 mA
Min. measurement range (span),
current input................................................... 16 mA
Input resistance, current
input............................................................... Nom. 10 Ω + PTC 10 Ω
Voltage input: Measurement
range.............................................................. 0...10 VDC
Min. measurement range (span),
voltage input................................................... 8 VDC
Input resistance, voltage
input............................................................... > 2 MΩ
5104B-031915
B.19
Ex-isolated driver
5105B
– 1- or 2-channel version
– 3- / 5-port 3.75 kVAC galvanic isolation
– Driver for Ex / I.S. area
– 20 programmable measurement ranges
– Universal supply by AC or DC
B
Application
• Safety barrier for current signals transmitted to I/P converters
and displays mounted in hazardous area.
• Safety barrier for analog current / voltage signals transmitted
to hazardous area.
• 1 : 1 or signal conversion of analog current / voltage signals.
Connections
Technical characteristics
• The 20 factory-calibrated measurement ranges in the 5105B
can be selected by the internal DIP-switches without the need
for a recalibration. Special measurement ranges can be
delivered.
• PR5105B is based on microprocessor technology for gain and
offset. The analog signal is transmitted at a response time of
less than 25 ms.
• Inputs, outputs, and supply are floating and galvanically
separated.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. By way of the
2-channel version up to 84 channels per meter can be
mounted.
B.20
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...25 Hz........................................
Vibration: 25...100 Hz....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
225 g
DIN 46277
1 x 2.5 mm2 stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1.6 mm
±4 g
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 2 W (2 channels)
Internal consumption...................................... ≤ 2 W (2 channels)
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%)............. < 25 ms
Accuracy........................................................ Better than 0.1% of selected
range
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Output specifications
Max. offset...................................................... 20% of max. value
Current output: Signal range......................... 0...20 mA
Min. signal range............................................ 16 mA
Load (max.).................................................... 20 mA/770 Ω/15.4 VDC
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Current limit.................................................... ≤ 28 mA
Voltage output: signal range.......................... 0...1 VDC / 0...10 VDC
Voltage output, min. signal
range.............................................................. 0.8 VDC / 8 VDC
Load (min.)..................................................... 500 kΩ
*of span.......................................................... = of the presently selected
range
B
Approvals
EMC...............................................................
LVD 2006/95/EC............................................
PELV/SELV....................................................
ATEX 2004/108/EC........................................
EN 61326-1
EN 61010-1
IEC 364-4-41 and EN 60742
DEMKO 99ATEX126014, II (1)
GD [EEx ia] IIC
UL................................................................... UL 913, UL 508
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
DNV Marine.................................................... Stand. f. Certific. No. 2.4
Input specifications
Max. offset...................................................... 20% of max. value
Current input: Measurement
range.............................................................. 0...20 mA
Min. measurement range (span),
current input................................................... 16 mA
Input resistance, current
input............................................................... Nom. 10 Ω + PTC 10 Ω
Voltage input: Measurement
range.............................................................. 0...10 VDC
Min. measurement range (span),
voltage input................................................... 8 VDC
Input resistance, voltage
input............................................................... > 2 MΩ
5105B-031915
B.21
HART® transparent repeater
5106B
– 3- / 5-port 3.75 kVAC galvanic isolation
– Low response time
– 2-wire supply > 17 V in Ex / I.S. area
– 1- or 2-channel version
– Universal supply by AC or DC
B
Application
• Power supply and Ex / I.S. safety barrier with 2-way HART®
communication for 2-wire transmitters installed in the
hazardous area.
• Ex / I.S. safety barrier with 2-way HART® communication for
supplied current transmitters installed in the hazardous area.
• Signal isolator with low response time on analog current
signals from the hazardous area.
Connections
Technical characteristics
• PR5106B primarily processes current signals of 4...20 mA.
• PR5106B is based on microprocessor technology for gain and
offset. The analog signal is transmitted at a response time of
less than 25 ms.
• Inputs, outputs, and supply are floating and galvanically
separated.
• The output can be connected either as an active current
transmitter or as a 2-wire transmitter.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. As the devices
can be mounted without distance between neighboring units,
up to 84 channels can be mounted per meter.
• PR5106B is recommended as Ex / I.S. safety barrier for
5335D and 6335D.
B.22
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
245 g
DIN 46277
1 x 2.5 mm2 stranded wire
0.5 Nm
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 3 W (2 channels)
Internal consumption...................................... ≤ 2 W (2 channels)
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Response time (0...90%, 100...10%)............. < 25 ms
Accuracy........................................................ Better than 0.1% of selected
range
Effect of supply voltage change..................... < ±10 μA
Auxiliary supply: 2-wire supply
(pin 44...42 and 54...52)................................. 25...17 VDC / 0...20 mA
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Output specifications
Current output: Signal range......................... 4…20 mA
2-wire 4...20 mA output: Signal
range.............................................................. 4...20 mA
Min. signal range............................................ 16 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Current limit.................................................... ≤ 28 mA
Max. external 2-wire supply........................... 29 VDC
Effect of external 2-wire
supply voltage variation................................. < 0.005% of span / V
Output ripple................................................... < 3 mVRMS on HART
communication
*of span.......................................................... = of the presently selected
range
B
Approvals
EMC...............................................................
LVD 2006/95/EC............................................
PELV/SELV....................................................
ATEX 2004/108/EC........................................
EN 61326-1
EN 61010-1
IEC 364-4-41 and EN 60742
DEMKO 00ATEX127483, II (1)
G [EEx ia] IIC
UL................................................................... UL 913, UL 508
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
Input specifications
Current input: Measurement
range..............................................................
Min. measurement range (span),
current input...................................................
Input resistance: Supplied
unit.................................................................
Input resistance: Non-supplied
unit.................................................................
4...20 mA
16 mA
Nom. 10 Ω
Rshunt = ∞, Vdrop < 4 V
5106B-031915
B.23
HART® transparent driver
5107B
– 1- or 2-channel version
– 3- / 5-port 3.75 kVAC galvanic isolation
– < 1.3 V voltage drop on input
– 16 V driving voltage on Ex / I.S. output
– Universal supply by AC or DC
B
Application
• Safety barrier for current signals and 2-way HART®
communication transmitted to I/P converters mounted in
hazardous area.
• Safety barrier for 2-way HART® communication and analog
current signals transmitted to hazardous area.
• Signal isolator with low response time on analog current
signals transmitted to hazardous area.
Connections
Technical characteristics
• PR’s HART® transparent driver primarily processes current
signals of 4...20 mA.
• PR5107B is based on microprocessor technology for gain and
offset. The analog signal is transmitted at a response time of
less than 25 ms.
• Inputs, outputs, and supply are floating and galvanically
separated.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. As the devices
can be mounted without distance between neighboring units,
up to 84 channels can be mounted per meter.
B.24
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
260 g
DIN 46277
1 x 2.5 mm2 stranded wire
0.5 Nm
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 2 W (2 channels)
Internal consumption...................................... ≤ 2 W (2 channels)
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Accuracy........................................................ Better than 0.1% of selected
range
Response time (0...90%, 100...10%)............. < 25 ms
Long-term stability, better
than................................................................ ±0.1% of span / Year
Effect of supply voltage change..................... < ±10 μA
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Output specifications
Current output: Signal range.........................
Min. signal range............................................
Load (max.)....................................................
Load stability, current output..........................
Current limit....................................................
*of span..........................................................
4…20 mA
16 mA
20 mA/800 Ω/16 VDC
≤0.01% of span / 100 Ω
≤ 28 mA
= of the presently selected
range
B
Approvals
EMC...............................................................
LVD 2006/95/EC............................................
PELV/SELV....................................................
ATEX 2004/108/EC........................................
EN 61326-1
EN 61010-1
IEC 364-4-41 and EN 60742
DEMKO 01ATEX127484, II (1)
GD [EEx ia] IIC
UL................................................................... UL 913, UL 508
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
Input specifications
Current input: Measurement
range..............................................................
Min. measurement range (span),
current input...................................................
Input resistance: Supplied
unit.................................................................
Input resistance: Non-supplied
unit.................................................................
4...20 mA
16 mA
10 Ω + PTC, Vdrop < 1.3 V
Rshunt = ∞, Vdrop < 3.5 V
5107B-031915
B.25
Programmable transmitter
5114B
– Input for RTD, TC, mV, linear resistance, mA, and V
– 3-port 3.75 kVAC galvanic isolation
– Current and voltage output
– Universal voltage supply
– 1- and 2-channel versions
– Loop supply > 17.1 V in Ex / I.S. zone 0
B
Advanced features
• The 5114 transmitter can be configured, with or without a
power supply, using the PReset software and the Loop Link
communications unit.
Connections
Application
• Jumper selectable inputs for current/voltage or temperature.
• Programmable current (0...100 mA) and voltage (0...250
VDC) inputs.
• Linearized, electronic temperature measurement.
• Conversion of linear resistance variation e.g, from solenoids
and butterfly valves or linear movements with attached
potentiometer.
• 17.1 VDC loop and 2.5 VDC potentiometer supplies.
• Automatic 4- / 3-wire or programmable 2-wire cable
compensation.
• Configurable sensor error detection including NAMUR NE43.
Technical characteristics
• Active or Passive current output and selectable voltage
output.
• Separation of circuits in PELV/SELV installations.
• I.S. barrier for temperature sensors, potentiometers, and
current / voltage signals.
• I.S. barrier with I.S. power supply for 2-wire transmitters in
zone 0, 1, 2, 20, 21 and 2.
B.26
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...25 Hz........................................
Vibration: 25...100 Hz....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
225 g
DIN 46277
1 x 2.5 mm2 stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1.6 mm
±4 g
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 3 W (2 channels)
Internal consumption...................................... ≤ 2 W (2 channels)
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Communications interface............................. Loop Link
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Accuracy........................................................ Better than 0.05% of selected
range
Response time (0...90%, 100...10%):
Temperature input (programmable)............... 400 ms...60 s
mA / V input (programmable)......................... 250 ms...60 s
Updating time................................................. 115 ms (temperature input)
Updating time................................................. 75 ms (mA / V / mV input)
Signal dynamics, input................................... 22 bit
Signal dynamics, output................................. 16 bit
Auxiliary voltages: Reference
voltage............................................................ 2.5 VDC ±0.5% / 15 mA
Auxiliary supply: 2-wire supply
(pin 44...42 and 54...52)................................. 28...17.1 VDC / 0...20 mA
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Input specifications
Output specifications
0...250 VDC
-150...+150 mV
5 mV
Nom. 10 MΩ (≤ 2.5 VDC)
Nom. 5 MΩ (> 2.5 VDC)
B
Nom. 10 MΩ (mV input)
Max. offset...................................................... 50% of selected max. value
Current output: Signal range......................... 0...20 mA
Min. signal range............................................ 10 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Current limit.................................................... ≤ 28 mA
2-wire 4...20 mA output: Signal
range.............................................................. 4...20 mA
Load stability, 4…20 mA output..................... ≤ 0.01% of span / 100 Ω
Max. load resistance [Ω]................................ (Vsupply - 3.5) / 0.023 A
Max. external 2-wire supply........................... 29 VDC
Effect of external 2-wire
supply voltage variation................................. < 0.005% of span / V
Voltage output: signal range.......................... 0...10 VDC
Voltage output, min. signal
range.............................................................. 500 mV
Load (min.)..................................................... 500 kΩ
Sensor error indication, current
output............................................................. Programmable 0...23 mA
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
*of span.......................................................... = of the presently selected
range
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
PELV/SELV.................................................... IEC 364-4-41 and EN 60742
ATEX 2004/108/EC........................................ DEMKO 99ATEX124571
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
DNV Marine.................................................... Stand. f. Certific. No. 2.4
5114B-031915
Max. offset...................................................... 50% of selected max. value
RTD input....................................................... Pt100, Ni100, lin. R
Cable resistance per wire
(max.), RTD.................................................... 10 Ω
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC).............................................................. < ±1.0°C
Sensor error current, TC................................ Nom. 30 μA
Sensor error detection, TC............................. Yes
Current input: Measurement
range.............................................................. 0...100 mA
Min. measurement range (span),
current input................................................... 4 mA
Input resistance: Supplied
unit................................................................. Nom. 10 Ω + PTC 10 Ω
Input resistance: Non-supplied
unit................................................................. RSHUNT = ∞, VDROP < 6 V
Voltage input: Measurement
range..............................................................
Voltage input: Measurement
range..............................................................
Min. measurement range (span),
voltage input...................................................
Input resistance, voltage
input...............................................................
Input resistance, voltage
input...............................................................
Input resistance, voltage
input...............................................................
B.27
Ex signal calculator
5115B
– Redundancy measurement with 2 input signals
– Signal calculator with the four arithmetical operations
– Duplication of the input signal
– Input for RTD, Ohm, TC, mV, mA, and V
– Universal supply by AC or DC
B
Application
• Redundancy measurement of temperature by means of two
sensors, where the secondary sensor takes over the
measurement when a sensor error occurs on the primary
sensor.
• Duplication of the input signal, e.g. from a temperature sensor
or an analog process signal to two separate analog outputs.
• Signal calculator with four arithmetical operations: Addition,
subtraction, multiplication and division.
• Example: Differential measurement: (Input 1 * K1) - (Input 2 *
K2) + K4
• Example: Average measurement: (Input 1 * 0.5) + (Input 2 *
0.5) + K4
• Example: Different functions on the outputs: Output 1 = input
1 - input 2, and Output 2 = input 1 + input 2
• I.S. safety barrier and power supply for 2-wire transmitters.
Connections
Technical characteristics
• Within a few seconds the user can program PR5115B to a
selected application using the configuration program PReset.
• A green front LED indicates normal operation, sensor error on
each sensor, and functional error.
• 5-port 3.75 kVAC galvanic isolation.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. As the devices
can be mounted without any distance between neighboring
units, up to 42 devices can be mounted per meter.
B.28
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...25 Hz........................................
Vibration: 25...100 Hz....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
225 g
1 x 2.5 mm2 stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1.6 mm
±4 g
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 3 W
Internal consumption...................................... ≤ 2.0 W
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Communications interface............................. Loop Link
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Accuracy........................................................ Better than 0.05% of selected
range
Response time (0...90%, 100...10%):
Temperature input (programmable)............... 400 ms...60 s
mA / V input (programmable)......................... 250 ms...60 s
Updating time................................................. 115 ms (temperature input)
Updating time................................................. 75 ms (mA / V / mV input)
Redundancy switch-over time........................
≤ 400 ms
Signal dynamics, input................................... 22 bit
Signal dynamics, output................................. 16 bit
Auxiliary voltages: Reference
voltage............................................................ 2.5 VDC ±0.5% / 15 mA
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
mV input: Measurement range.......................
Min. measurement range (span),
voltage input...................................................
Input resistance, voltage
input...............................................................
Input resistance, voltage
input...............................................................
Input resistance, voltage
input...............................................................
Output specifications
-150...+150 mV
5 mV
Nom. 10 MΩ (≤ 2.5 VDC)
Nom. 5 MΩ (> 2.5 VDC)
Nom. 10 MΩ (mV input)
B
Current output: Signal range......................... 0...20 mA
Min. signal range............................................ 10 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Current limit.................................................... ≤ 28 mA
Voltage output: signal range.......................... 0...10 VDC
Voltage output, min. signal
range.............................................................. 500 mV
Load (min.)..................................................... 500 kΩ
2-wire 4...20 mA output: Signal
range.............................................................. 4...20 mA
Load stability, 4…20 mA output..................... ≤ 0.01% of span / 100 Ω
Effect of external 2-wire
supply voltage variation................................. < 0.005% of span / V
Max. external 2-wire supply........................... 29 VDC
Sensor error indication, current
output............................................................. Programmable 0...23 mA
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
*of span.......................................................... = of the presently selected
range
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
PELV/SELV.................................................... IEC 364-4-41 and EN 60742
ATEX 2004/108/EC........................................ DEMKO 00ATEX128567
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
DNV Marine.................................................... Stand. f. Certific. No. 2.4
Input specifications
5115B-031915
Max. offset...................................................... 50% of selected max. value
RTD input....................................................... Pt100, Ni100, lin. R
Cable resistance per wire
(max.), RTD.................................................... 10 Ω
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
Sensor error detection, RTD.......................... Yes
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC).............................................................. < ±1.0°C
Sensor error current, TC................................ Nom. 30 μA
Current input: Measurement
range.............................................................. 0...100 mA
Min. measurement range (span),
current input................................................... 4 mA
Input resistance: Supplied
unit................................................................. Nom. 10 Ω + PTC 10 Ω
Input resistance: Non-supplied
unit................................................................. RSHUNT = ∞, VDROP < 6 V
Voltage input: Measurement
range.............................................................. 0...250 VDC
B.29
Programmable transmitter
5116B
– Input for RTD, TC, mV, Ohm, potentiometer, mA and V
– 2-wire supply > 16.5 V to Ex zone 0
– Bipolar voltage input
– Output for current, voltage and 2 relays
– Universal supply by AC or DC
B
Application
• Linearized, electronic temperature measurement with RTD or
TC sensor.
• Conversion of linear resistance variation to a standard analog
current / voltage signal, i.e. from solenoids and butterfly
valves or linear movements with attached potentiometer.
• Power supply and signal isolator for 2-wire transmitters.
• Process control with 2 potential-free relay contacts which can
be configured for advanced functions.
• Galvanic separation of analog signals and measurement of
floating signals.
Connections
Technical characteristics
• Within a few seconds the user can program PR5116B to suit
the specific application.
• By way of the front push-button the input can be calibrated to
the exact span of the process. Zero drift on the process signal
can be adjusted by a single press of the front buttton.
• A green front LED indicates normal operation and
malfunction. A yellow LED is ON for each active output relay.
• Continuous check of vital stored data for safety reasons.
• 3-port 3.75 kVAC galvanic isolation.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. As the devices
can be mounted without any distance between neighboring
units, up to 42 devices can be mounted per meter.
B.30
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...25 Hz........................................
Vibration: 25...100 Hz....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
235 g
1 x 2.5 mm2 stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1.6 mm
±4 g
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 3 W
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Communications interface............................. Loop Link
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Accuracy........................................................ Better than 0.05% of selected
range
Response time (0...90%, 100...10%):
Temperature input (programmable)............... 400 ms...60 s
mA / V input (programmable)......................... 250 ms...60 s
Signal dynamics, input................................... 22 bit
Signal dynamics, output................................. 16 bit
Auxiliary voltages: Reference
voltage............................................................ 2.5 VDC ±0.5% / 15 mA
Auxiliary supplies: 2-wire
supply (pin 54...52)........................................ 28...16.5 VDC / 0...20 mA
Input specifications
Output specifications
5 mV
Nom. 10 MΩ (≤ 2.5 VDC)
Nom. 5 MΩ (> 2.5 VDC)
> 5 MΩ (mV input)
170 Ω
B
Current output: Signal range......................... 0...20 mA
Min. signal range............................................ 10 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Current limit.................................................... ≤ 28 mA
Voltage output: signal range.......................... 0...10 VDC
Voltage output, min. signal
range.............................................................. 500 mV
Load (min.)..................................................... 500 kΩ
2-wire 4...20 mA output: Signal
range.............................................................. 4...20 mA
Load stability, 4…20 mA output..................... ≤ 0.01% of span / 100 Ω
Max. external 2-wire supply........................... 29 VDC
Effect of external 2-wire
supply voltage variation................................. < 0.005% of span / V
Sensor error indication, current
output............................................................. Programmable 0...23 mA
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
Relay output: Relay functions........................ Increasing / decreasing
Relay output: Relay functions........................ Window
Max. voltage................................................... 250 VRMS
Max. current................................................... 2 AAC
Max. AC power.............................................. 500 VA
Max. load at 24 VDC...................................... 1 A
Sensor error reaction..................................... Break / Make / Hold / None
*of span.......................................................... = of the currently selected
measurement range
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
PELV/SELV.................................................... IEC 364-4-41 and EN 60742
ATEX 2004/108/EC........................................ KEMA 04ATEX1316 X
FM.................................................................. 3023092
UL................................................................... UL 508
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
DNV Marine.................................................... Stand. f. Certific. No. 2.4
5116B-031915
Max. offset...................................................... 50% of selected max. value
RTD input....................................................... Pt100, Ni100, lin. R
Cable resistance per wire
(max.), RTD.................................................... 10 Ω (max. 50 Ω)
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
Sensor error detection, RTD.......................... Yes
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC).............................................................. < ±1.0°C
Sensor error current, TC................................ Nom. 30 μA
Sensor error detection, TC............................. Yes
Current input: Measurement
range.............................................................. 0...100 mA
Min. measurement range (span),
current input................................................... 4 mA
Input resistance: Supplied
unit................................................................. Nom. 10 Ω + PTC 10 Ω
Input resistance: Non-supplied
unit................................................................. RSHUNT = ∞, VDROP < 6 V
Sensor error detection, current
input............................................................... Loop break 4...20 mA
Voltage input: Measurement
range.............................................................. 0...250 VDC
Voltage input: Measurement
range.............................................................. -2500...+2500 mV
Min. measurement range (span),
voltage input...................................................
Input resistance, voltage
input...............................................................
Input resistance, voltage
input...............................................................
Input resistance, voltage
input...............................................................
Potentiometer via 2.5 V ref............................
B.31
2-wire programmable transmitter
5131B
– Input for RTD, TC, mV, linear resistance, mA, and V
– 3.75 kVAC galvanic isolation
– 4...20 mA loop output
– 1- and 2-channel versions
– ATEX Ex / I.S. version
– DIN rail mounting
B
Advanced features
• The 5131 transmitter can be configured with a standard PC
and the Loop Link communications unit.
Connections
Application
• Independent channel jumper selectable inputs for
current/voltage or temperature.
• Current input programmable in range the 0...100 mA and
voltage inputs in the range 0...250 VDC.
• Linearized, electronic temperature measurement with RTD or
TC sensor.
• Conversion of linear resistance variation to a standard analog
current / voltage signal, for example from solenoids and
butterfly valves or linear movements with attached
potentiometer.
• 4- or 3-wire connection with automatic cable compensation or
2-wire connection with programmable cable compensation.
• Configurable sensor error detection including NAMUR NE43.
Technical characteristics
• Programming can be performed with or without a power
supply.
• The 2-channel version has full galvanic isolation between the
channels.
• Separation of circuits in PELV/SELV installations.
• I.S. barrier for temperature sensors, potentiometers and
current / voltage signals.
B.32
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Common specifications
Supply voltage...............................................
Fuse...............................................................
Isolation voltage, test /
working...........................................................
Communications interface.............................
Signal / noise ratio.........................................
Response time (0...90%, 100...10%):
Temperature input (programmable)...............
mA / V input (programmable).........................
Updating time.................................................
Updating time.................................................
Signal dynamics, input...................................
Signal dynamics, output.................................
Effect of supply voltage change.....................
EMC immunity influence................................
Extended EMC immunity: NAMUR
NE 21, A criterion, burst.................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
195 g
DIN 46277
1 x 2.5 mm2 stranded wire
0.5 Nm
7.5...35 VDC
50 mA SB / 250 VAC
3.75 kVAC / 250 VAC
Loop Link
Min. 60 dB (0...100 kHz)
400 ms...60 s
250 ms...60 s
115 ms (temperature input)
75 ms (mA / V / mV input)
22 bit
16 bit
< 0.005% of span / VDC
< ±0.5% of span
Input resistance, voltage
input............................................................... Nom. 10 MΩ (mV input)
Output specifications
Max. offset...................................................... 50% of selected max. value
Current output: Signal range......................... 4…20 mA
Min. signal range............................................ 10 mA
Load resistance, current output..................... ≤ (Vsupply -7.5)/0.023 [Ω]
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Current limit.................................................... ≤ 28 mA
Sensor error indication, current
output............................................................. Programmable 3.5…23 mA
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
*of span.......................................................... = of the presently selected
range
Approvals
EMC...............................................................
LVD 2006/95/EC............................................
PELV/SELV....................................................
ATEX 2004/108/EC........................................
EAC TR-CU 020/2011...................................
EAC Ex TR-CU 012/2011..............................
B
EN 61326-1
EN 61010-1
IEC 364-4-41 and EN 60742
DEMKO 99ATEX124572
EN 61326-1
RU C-DK.GB08.V.00410
< ±1% of span
Input specifications
5131B-031915
Max. offset...................................................... 50% of selected max. value
RTD input....................................................... Pt100, Ni100, lin. R
Cable resistance per wire
(max.), RTD.................................................... 10 Ω
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
Sensor error detection, RTD.......................... Yes
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC).............................................................. < ±1.0°C
Sensor error current, TC................................ Nom. 30 μA
Sensor error detection, TC............................. Yes
Current input: Measurement
range.............................................................. 0...100 mA
Min. measurement range (span),
current input................................................... 4 mA
Input resistance: Supplied
unit................................................................. Nom. 10 Ω + PTC 10 Ω
Input resistance: Non-supplied
unit................................................................. RSHUNT = ∞, VDROP < 6 V
Voltage input: Measurement
range.............................................................. 0...250 VDC
Voltage input: Measurement
range.............................................................. -150...+150 mV
Min. measurement range (span),
voltage input................................................... 5 mV
Input resistance, voltage
input............................................................... Nom. 10 MΩ (≤ 2.5 VDC)
Input resistance, voltage
input............................................................... Nom. 5 MΩ (> 2.5 VDC)
B.33
Pulse isolator
5202B
– 2 channels - 2 or 4 outputs
– Dual output
– 5-port 3.75 kVAC galvanic isolation
– Cable error detection
– Universal supply by AC or DC
B
Application
• Pulse isolator with safety barrier for the supply of NAMUR
sensors installed in the hazardous area.
• Pulse isolator with safety barrier for the detection of
mechanical contacts installed in the hazardous area.
• One input signal can be used on two separate outputs.
• A cable error alarm can be detected on a separate output.
Connections
Technical characteristics
• PR5202B1 and 5202B2 have relays with change-over
contacts or open NPN collectors available in the safe area.
• PR5202B4 has 4 SPST relays, which are activated
simultaneously two and two, available in the safe area. Each
relay can be programmed to the function N.O. or N.C.
• Inputs, outputs and supply are floating and galvanically
separated.
• 5202B is designed according to strict safety requirements and
is therefore suitable for application in SIL 2 installations.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. Up to 84
channels per meter can be mounted.
B.34
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
Wire size........................................................
Screw terminal torque....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
230 g
1 x 2.5 mm2 stranded wire
0.5 Nm
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 1.5 W (2 channels), 5202B1
and 5202B2
Max. power consumption............................... ≤ 2.0 W (2 channels), 5202B4
Internal consumption...................................... ≤ 1.5 W (2 channels), 5202B1
and 5202B2
Internal consumption...................................... ≤ 2.0 W (2 channels), 5202B4
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Auxiliary supplies: NAMUR
supply............................................................. 8 VDC / 8 mA
EMC immunity influence................................ < ±0.5%
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1%
Output specifications
Relay output: Max. switching
frequency.......................................................
Max. voltage...................................................
Max. current...................................................
Max. AC power..............................................
Max. load at 24 VDC......................................
Opto, NPN outputs: Max. switching
frequency.......................................................
Min. pulse length, NPN output.......................
Max. load, current / voltage............................
Voltage drop at 25 mA / 80
mA..................................................................
20 Hz
250 VRMS
2 AAC
100 VA
1A
5 kHz
> 0.1 ms
80 mA / 30 VDC
B
< 0.75 VDC / < 2.5 VDC
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
PELV/SELV.................................................... IEC 364-4-41 and EN 60742
ATEX 2004/108/EC........................................ DEMKO 99ATEX127186
UL................................................................... UL 913, UL 508
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
Input specifications
Sensor types.................................................. NAMUR according to EN
60947-5-6 / mechanical
contact
Frequency range............................................ 0...5 kHz
Pulse length................................................... > 0.1 ms
Input resistance.............................................. 1 kΩ
Trig level, signal............................................. < 1.2 mA, > 2.1 mA
Trig level, cable fault...................................... < 0.1 mA, > 6.5 mA
5202B-031915
B.35
Ex solenoid / alarm driver
5203B
– 1- or 2-channel version
– Solenoid driver for I.S. area
– 3- / 5-port 3.75 kVAC galvanic isolation
– Digitally controlled voltage supply for I.S. area
– Universal supply by AC or DC
B
Application
• Driver with safety barrier for the control of ON / OFF solenoids
mounted in hazardous area.
• Driver with safety barrier for the supply of LEDs and acoustic
alarms mounted in hazardous area.
• Voltage supply with ON / OFF control of other equipment.
Connections
Technical characteristics
• PR5203B has a digital input per channel for the control of the
I.S. output voltage.
• Supply, inputs, and outputs are floating and galvanically
separated.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. By way of the
2-channel version up to 84 channels per meter can be
mounted.
B.36
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
Wire size........................................................
Screw terminal torque....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
230 g
1 x 2.5 mm2 stranded wire
0.5 Nm
Common specifications
Output specifications
Output voltage................................................ See Ex data in manual
Output current................................................ See Ex data in manual
Output ripple................................................... < 40 mVRMS
Approvals
EMC............................................................... EN 61326-1
LVD 2006/95/EC............................................ EN 61010-1
PELV/SELV.................................................... IEC 364-4-41 and EN 60742
ATEX 2004/108/EC........................................ DEMKO 99ATEX126257
UL................................................................... UL 913, UL 508
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
B
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... ≤ 4 W (2 channels)
Internal consumption...................................... ≤ 2 W (2 channels)
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Max. frequency.............................................. 20 Hz
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Input specifications
Trig level LOW, NPN+switch.......................... ≤ 4.0 VDC
Trig level HIGH, NPN+switch......................... ≥ 7.0 VDC
Max. external voltage, NPN+switch............... 28 VDC
Input impedance, NPN+switch....................... 3.48 kΩ
Trig level LOW, PNP...................................... ≤ 4.0 VDC
Trig level HIGH, PNP..................................... ≥ 7.0 VDC
Max. external voltage, PNP........................... 28 VDC
Input impedance, PNP................................... 3.48 kΩ
5203B-031915
B.37
Programmable f/I-f/f converter
5223B
– Pulse calculator / frequency generator
– Galvanic isolation
– ATEX I.S. version
– Analog current and voltage output
– PNP / NPN output, optional relays
– Universal supply
B
Advanced features
• The 5223 transmitter can be configured with a standard PC
and the Loop Link communications unit, or delivered fully
configured.
Connections
Application
• The f/I function performs frequency to current and voltage
conversion.
• The f/f function can be used for pulse division or multiplication
and as a buffer collecting fast pulse trains.
• A scale factor may be entered in all functions. Using both
digital inputs, pulse addition or subtraction are possible.
• The frequency generator function is used as e.g. a time base
or clock generator.
• Input and supply polarity reversal protection.
• Current and voltage output signals galvanically separated
from the supply and the inputs.
• Programmable digital outputs including NPN, PNP or relay
options.
• ATEX units have input for mechanical contact and NAMUR
inductive proximity sensor.
Technical characteristics
• 5 front LEDs, indicating f1 and f2 active inputs (not NPN),
Dig.out.1 and 2 active outputs, and a programmable error
signal.
• Analog current output can be configured to any current within
0...20 mA range.
• Voltage output range is selectable between 0...10 VDC and
0...1 VDC by use of internal jumpers.
• Programming can be performed with or without a power
supply.
B.38
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
240 g
DIN 46277
1 x 2.5 mm2 stranded wire
0.5 Nm
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Fuse............................................................... 400 mA SB / 250 VAC
Max. power consumption............................... 3.5 W
Internal consumption...................................... 3 W
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Power-up delay.............................................. 0...999 s
Warm-up time................................................. 1 min.
Communications interface............................. Loop Link
Signal / noise ratio......................................... Min. 60 dB
Response time, analog.................................. < 60 ms + period
Response time, digital output......................... < 50 ms + period
Effect of supply voltage change..................... < 0.005% of span / VDC
Temperature coefficient................................. < ±0.01% of span / °C
Linearity error................................................. < 0.1% of span
NAMUR supply I.S. / Ex................................. 8.9 VDC ±0.5 VDC / 8 mA
EMC immunity influence................................ < ±0.5%
Output specifications
Max. offset...................................................... 50% of selected max. value
Current output: Signal range......................... 0...20 mA
Min. signal range............................................ 5 mA
Updating time................................................. 20 ms
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span / 100 Ω
Current limit.................................................... < 23 mA
Voltage output through internal
shunt.............................................................. See manual for details
Voltage output: signal range.......................... 0...10 VDC
Voltage output, min. signal
range.............................................................. 250 mV
Load (min.)..................................................... 500 kΩ
Other output types......................................... Active outputs (NPN / PNP)
Other output types......................................... f/f converter output
Other output types......................................... Frequency generator
Relay output: Max. switching
frequency....................................................... 20 Hz
Max. voltage................................................... 250 VRMS
Max. current................................................... 2 AAC
Max. AC power.............................................. 100 VA (I.S. version 5223B)
Max. load at 24 VDC...................................... 1 A
*of span.......................................................... = of the presently selected
range
Approvals
EMC...............................................................
LVD 2006/95/EC............................................
PELV/SELV....................................................
ATEX 2004/108/EC........................................
EAC TR-CU 020/2011...................................
EAC Ex TR-CU 012/2011..............................
B
EN 61326-1
EN 61010-1
IEC 364-4-41 and EN 60742
KEMA 04ATEX1001
EN 61326-1
RU C-DK.GB08.V.00410
Input specifications
Max. offset...................................................... 90% of selected max.
frequency
Measurement range....................................... 0...20 kHz
Min. measurement range............................... 0.001 Hz
Min. pulse length............................................ 25 μs
Input types...................................................... NAMUR acc. to DIN 19234
5223B-031915
B.39
Ex power supply
5420B
– 2 channels
– 5-port 3.75 kVAC galvanic isolation
– Output voltage > 18 V to I.S. area
– Active current loop detection
– Universal supply by AC or DC
B
Application
• Voltage supply with safety barrier for the supply of equipment
mounted in hazardous area.
• Voltage supply with failsafe detection of active current loop
from 2-wire transmitters mounted in hazardous area.
Connections
Technical characteristics
• PR5420B has a relay with change-over contacts available in
the safe area. When the loop current is within the defined
limit, the relay is ON.
• Supply and outputs are floating and galvanically separated.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. Up to 84
channels per meter can be mounted.
B.40
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Mechanical specifications
Dimensions (HxWxD).....................................
Weight approx................................................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Common specifications
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
109 x 23.5 x 130 mm
215 g
DIN 46277
1 x 2.5 mm2 stranded wire
0.5 Nm
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Max. power consumption............................... ≤ 4 W (2 channels)
Internal consumption...................................... ≤ 2 W (2 channels)
Fuse............................................................... 400 mA SB / 250 VAC
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
EMC immunity influence................................ < ±0.5%
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1%
Output specifications
Output voltage................................................
Output current................................................
Relay outputs: On within limit.........................
Max. voltage...................................................
Max. current...................................................
Max. AC power..............................................
Max. load at 24 VDC......................................
Approvals
EMC...............................................................
LVD 2006/95/EC............................................
PELV/SELV....................................................
ATEX 2004/108/EC........................................
EAC TR-CU 020/2011...................................
EAC Ex TR-CU 012/2011..............................
> 18 VDC at 20 mA
28 mA per channel (max.)
> 3.8...< 20.5 mA
250 VRMS
2 ARMS
100 VA
1A
B
EN 61326-1
EN 61010-1
IEC 364-4-41 and EN 60742
DEMKO 99ATEX126256
EN 61326-1
RU C-DK.GB08.V.00410
5420B-030915