DualLite SlimLite SL1 Installation, Operation And Service Instructions

Add to my manuals
2 Pages

advertisement

DualLite SlimLite SL1 Installation, Operation And Service Instructions | Manualzz

SERVICE

Replacing An Emergency Lamp

1. Remove lens, and remove lamp. Replace with part number shown on replacement

label. Replace lens and push "Test" button to check lamp operation.

Battery Replacement

1. De-energize the Ac supply to the unit. Failure to do so could result

in an unsafe operating condition.

2. Remove the unit from the back plate.

3. Disconnect the RED (+, positive) and

BLACK (—, negative) leads from the

battery terminals.

4. Remove the battery. Recycle

responsibly.

5. Replace battery with part number

shown on model label.

6. Reconnect the RED (+, positive)

and BLACK (—, negative) leads to

the battery terminals.

7. Reinstall the unit. Energize the AC

supply and test the unit by pressing

the "Test" button.

RECYCLING INFORMATION

All steel, aluminum and thermoplastic parts

are recyclable.

NOTICE: Emergency units contain

rechargeable batteries which must be

recycled or disposed of properly.

1300737

5100730

Hubbell Lighting, Inc. Life Safety Products • www.dual-lite.com

Copyright © Hubbell Lighting, Inc., All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A. 0603229 12/09

Slimlite

®

Sl1

Contemporary Twin Lamp Emergency Lighting Unit

Installation, Operation and Service Instructions

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOllOw All SAFETy INSTRUcTIONS

1. Do not use outdoors.

2. Do not mount near heaters or hot surfaces.

3. Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel.

4. The use of accessory equipment not authorized by the manufacturer may cause an unsafe condition.

Caution: Halogen cycle lamps may be used in this equipment. Halogen cycle lamps operate at high temperatures. Do not store or place flammable materials near lamp.

To avoid shattering: Do not operate lamp in excess of rated voltage.

Protect lamp against abrasion and scratches and against liquids when operating. Dispose of lamp with care.

5. Do not use this equipment for other than its intended use.

6. Servicing of this equipment should be performed by qualified personnel.

7. Caution: Energize AC only after installation has been completed.

Failure to do so could result in an unsafe operating condition.

8. Test cycling: the Life Safety Code (NFPA 101) requires testing of emergency lighting units once a month for a minimum of 30 seconds, and once a year for a minimum of 90 minutes.

INSTALLER:

•SEE UNIT LABEL FOR ADDITIONAL MODEL SPECIFICATIONS

•SAVE THESE INSTRUCTIONS FOR USE BY OWNER/OCCUPANT

WARNING – This product contains chemicals known to the State of California to cause cancer, birth defects and/or other reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product.

INSTALLATION

1.

Make sure the Ac supply is off before starting installation!

wiring Diagram

5100730

CONNECTOR

(MOUNTING PLATE)

B

L

L

BROWN 277V

BLACK 120V

WHITE NEUTRAL

EMERGENCY LAMPS

YEL YEL

BLUE BLUE

3.

Connect the RED positive battery lead to the B+ terminal on the PC board (see wiring diagram).

1300737

DO NOT cONNEcT

RIGID cONDUIT TO

ANy K.O. ON

BAcK PlATE

4.

Snap housing onto backplate.

B

+

BLACK

RED

BLUE

2.

Remove appropriate KO's on back plate. Make electrical connections (see wiring diagram).

Insulate unused lead. Secure backplate to outlet box or conduit end.

RED (+)

BATTERY

LEAD

TEST

SWITCH

CHARGER PCB

VOLTMETER

+

CONNECTIONS

FOR VOLTMETER

OPTION

OPERATION

+

BATTERY

Placing The Unit In Service

Energize the AC supply. Push the "Test" button; both lamps should light.

Routine Test Cycling

1. Once a month: Press and hold the "Test" button for at least thirty (30) seconds. Both lamps should light.

2. Once a year: Perform a full battery conditioning cycle by turning off the unit AC supply circuit, and allow the unit to operate for 90 minutes in emergency mode.