SF1000000X1FX - Schneider Electric

SF1000000X1FX - Schneider Electric
SF1000000X1FX
Product data sheet
Characteristics
SF1 A1-B1-C1 fixed / up to 36kV / 12,5 to 25kA /
630-1250A / 220 to 380mm / IEC
Range of product
SF
Product or component type
Circuit-breaker
Device short name
SF1
Network type
AC
Network frequency
50/60 Hz
Rated voltage
36 kV
[Ui] rated insulation voltage
70 kV 50 Hz for 1 min
[In] rated current
1250 A
630 A
Short-circuit current
25 kA
[Icw] rated short-time withstand current
25 kA for 3 s
Rated switching sequence
O - 0.3 sec - CO - 15 sec - CO
O - 0.3 sec - CO - 3 min - CO
O - 3 min - CO - 3 min - CO
[Iu] rated interrupted current
50 A : C2 cable charging
400 A : C2 single capacitor bank
400 A : C2 back to back capacitor bank
Type of operator
Spring return RI type
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Complementary
Poles description
3P
Control type
Push-button
Mounting mode
Fixed
Rolling frame
Protection type
Without protection
Charging time
<= 15 s
Operating time
<= 50 ms
Maximum breaking time
<= 65 ms
Closing response time
<= 70 ms
Mechanical durability
M2 : 10000 cycles
Electrical endurance class
E2
Technology type
SF6 gas
Nov 13, 2017
1
Environment
Creepage distance
470 mm input to output
400 mm phase to earth
Pole distance
220...380 mm phase to phase
380 mm input to output
230 mm phase to earth
Height
750 mm A1
750 mm B1
745 mm C1
Width
365 mm A1
365 mm B1
1260 mm C1
Depth
1560 mm A1
1560 mm B1
565 mm C1
Product weight
88 kg
Standards
IEC 62271-100 2012
GOST-R 52565 2006
Ambient air temperature for storage
-40...70 °C
Ambient air temperature for operation
-5...40 °C
2
Was this manual useful for you? yes no