5-digit digital panel meter in 96x24 mm (BxH) AC voltage

5-digit digital panel meter in 96x24 mm (BxH) AC voltage
M3 – 5-digit digital panel meter in 96x24 mm (BxH)
AC voltage signals / AC current signals – rms-value (TRMS)
300 VAC, 5 AAC
• red display from -19999…99999 digits (optional green, orange, blue or tricolour display)
• installation depth: 120 mm without plug-in screw terminal
• multi voltage power supply unit 100-240 VAC
• adjustment via factory setting or directly on the sensor signal
• min/max-memory with adjustable permanent display
• 30 additional adjustable support points
• display flashing at threshold value exceedance / undercut
• navigation keys for the triggering of Hold, Tara, display change, setpoint setting, alarm actuation
• flexible alarm system with adjustable delay times
• flexible power measurement and energy measurement at constant voltage
• mathematical functions like reciprocal value, square root, square and rounding
• constant setting / setpoint setting
• sliding averaging
• brightness control via parameter or front keys
• programming interlock via access code
• protection class IP65 at the front
• plug-in screw terminal
• optional: 1 or 2 relay outputs
• optional: 1 independently scalable analog output
• accessories: pc-based configuration-kit PM-TOOL with CD & USB adapter
• on demand: devices for working temperatures of -20°C…60°C or -40°C…70°C
Update 08/09/2016- m3_ac voltage_h_96x24.gb.doc
Errors and omissions excepted.
Page 1
96x24
ORDER NUMBER
EUR
(without options)
• AC current, ac voltage (true RMS value) – special measuring inputs H
Supply 100-240 VAC, DC ± 10%
M3-3VR5B.0H04.S70BD
345,00
• Product key options
M
3-
3
V
R
5
B.
0
H
0
4.
S
7
0
B
D
EUR
1
1 relay output (with option analog output only 1 switching point is possible)
20,00
2
2 relay outputs
30,00
1
without keypad, operation via PM-TOOL
10,00
X
Analog output 0/4-20 mA, 0-10 VDC
90,00
B
Blue
44,00
G
Green
10,00
Y
Orange
T
Tricolour (Red-Green-Orange)
4,00
30,00
On demand state dimension unit on order, e.g. V.
• Parameterisation software
PC based configuration software PM-Tool for devices without keypad,
for a simple adjustment of standard devices, incl. CD & USB-adapter.
Programming happens via an interface on the back.
Update 08/09/2016- m3_ac voltage_h_96x24.gb.doc
Errors and omissions excepted.
PM-TOOL-MUSB4
Page 2
89,00
• Technical data
Dimensions
Housing
Panel cut-out
Fixing
Housing material
Sealing material
Protection class
Weight
Connection
B96 x H24 x D120 mm, (incl. plug-in terminal D= 145 mm cable outlet at the back)
92.0+0.8 x 22.2+0.3 mm
screw elements for a wall thickness up to 10 mm
PC Polycarbonate, black
EPDM, 65 Shore, black
at the front IP65 standard, at the back IP00
approx. 250 g
plug-in terminal; wire cross section up to 2.5 mm2
Display
Display
Digit height
Segment colour
Range of display
Threshold value
Overflow
Underflow
Display time
5-digit
14 mm
red (Standard), optional in green, orange, blue or tricolour (red/green/orange)
-19999 to 99999
optical display flashing
horizontal bars at the top
horizontal bars at the bottom
0.1 to 10.0 seconds
Measuring input
Measuring range
Input resistance
Measuring fault
300 VAC
/ 5 AAC
Ri at ~ 1 MΩ
/ Ri at ~ 0.02 MΩ
0.5 % of final value with 50 Hz…1 kHz to crest factor 4, ± 1 digit
for input signals from 1%...100% of final value
100 ppm/K
0.1 … 10.0 seconds
U/F-conversion
approx. 18 bit at 1s measuring time
Temperature drift
Measuring time
Measuring principle
Resolution
Analog output
with change-over contact 250 V / 2 AAC, 30 V / 2 ADC
30 * 103 at 2 AAC, 2 ADC ohm resistive burden, 10 * 106 mechanically
Separation according to DIN EN50178 / Specific values according to DIN EN 60255
0-10 VDC / burden ≥ 10 kΩ, 0/4-20 mA / burden ≤ 500 Ω, 16 bit
Power pack
Supply
100-240 VAC 50/60 Hz, DC ±10 % (max. 10 VA)
Memory
EEPROM
Data preservation ≥ 100 years at 25°C
Ambient condition
Working temperature
Storing temperature
Climatic density
0 to +50°C
-20 to +80°C
relative humidity 0-85% on years average without dew
CE-sign
Conformity to directive 2014/30/EU
EMV
EN 61326, EN 55011
Safety standard
According to low voltage directive 2014/35/EU, EN 61010; EN 60664-1
Output
Relay
Switching cycle
Housing:
24,0
3,0
Se
alin
g
l
ina
rm
e
t
)
-in s)
4,0
(15 . plug ption
0
,
l
o
5
c
14 th in s on
d
p
n
e
n d epe
atio pth d
l
l
a
t
e
Ins (D
96
,0
Gap for physical unit
Update 08/09/2016- m3_ac voltage_h_96x24.gb.doc
Errors and omissions excepted.
Page 3
• Order key
M 3- 3 V R 5 B. 0 H 0 4. S 7 0 B D
Standard type M-Line
Dimension
D physical unit (on demand)
Installation depth
145 mm incl. plug-in terminal (154 mm)
3
Version
B B
Housing size
96x24x120 mm (BxHxT)
3
Switching points
0 without
1 1 relay output
Display type
V, A
V
2 2 relay outputs
Blue
B
1 without keypad, operation via PM-TOOL
Green
G
7 IP65 / plug-in terminal
Red
R
Red/Green/Orange
T
Orange
Y
Display colours
Protection class
Supply voltage
S 100-240 VAC
Number of digits
5-digits
Measuring input
5
4 AC, TRUE RMS
Digit height
14 mm
Analog output
B
0 without
X 1x 0-10 VDC, 0/4-20 mA
Digital input
without
0
Special measuring input
H 300 VAC, 5 AAC
Update 08/09/2016- m3_ac voltage_h_96x24.gb.doc
Errors and omissions excepted.
Page 4