HARRINGTON EARLY CHILD
DEVELOPMENT CENTER
2501 GISLER AVENUE
Oxnard, CA 93033
BY
DOUGHERTY + DOUGHERTY ARCHITECTS LLP
3194 AIRPORT LOOP
COSTA MESA, CA 92626-3405
(714) 427-0277
FAX (714) 427-0288
D+D Project # 21336.00
Cut Sheets
November 1, 2015
Table of Contents
1.0
Mechanical Equipment
2.0
Plumbing Fixtures
3.0
Restroom Accessories
58PHB/PHY PERFORMANCE™ BOOST 80
4---WAY MULTIPOISE
INDUCED---COMBUSTION GAS FURNACE
Input Capacities: 45,000 thru 135,000 Btuh
Series 100
Product Data
multipoise design, through--the--furnace downflow venting, 13
different venting options, and a design for easy service access. An
inner blower door is provided for tighter sealing in sensitive
applications. The 58PHB/PHY furnaces are approved for use with
natural or propane gas, and the 58PHY is approved for use in Low
NOx Air Quality Management Districts.
STANDARD FEATURES
S ECM Blower Motor included
S QuieTecht noise reduction system
S Microprocessor based control center
Enhanced diagnostics with LED and reflective sight glass.
Stores fault codes during power outages
Adjustable heating air temperature rise
Adjustable cooling airflow
S 4--way Multipoise furnace, 13 vent applications
S Compact design -- only 33--1/3 in. (847 mm) tall
S Power Heat SiNt Igniter
S Draft safeguard switch to ensure proper furnace venting
S Insulated blower compartment
S Inner door for tighter sealing
A10251
THE CARRIER PERFORMANCEt BOOST 80
GAS FURNACE
The 58PHB/PHY 4--way Multipoise Gas Furnaces offer features
not found in other single--stage 80% gas furnaces. The ECM
motor and Carrier’s control logic combine to provide a SEER
BOOST of up to 1.5 points.* Carrier’s QuieTecht noise reduction
system makes the Performancet Boost 80 an incredibly quiet
induced--draft gas furnace.
The gas furnace control system provides fault code storage in the
event of power outages. Applications are easy with 4--way
S Certified to leak 2 percent or less of its nominal air
conditioning CFM delivered when pressurized to 1--In.
Water Gauge with all present air inlets and air outlet sealed.
S HYBRID HEAT Dual Fuel System compatible
S All models are chimney friendly when used with accessory
vent kit
S Residential installations eligible for consumer financing
through the Retail Credit Program
*as compared to the Air Conditioning Heating and Refrigeration Institute’s standard coil ---only rating when paired with selected Carrier evaporator coils.
1
FURNACE COMPONENTS
INDUCER MOTOR
ASSEMBLY
VENT
ELBOW
MAIN LIMIT SWITCH
(BEHIND GAS VALVE)
PRESSURE
SWITCH
BLOCKED VENT
SWITCH
FLUE COLLECTOR
BOX
FLAME
SENSOR
58PHB
GAS VALVE
GAS MANIFOLD
MANUAL RESET
LIMIT SWITCHES
HOT SURFACE
IGNITOR
GAS BURNER
BLOWER
DOOR SAFETY
SWITCH
FURNACE
CONTROL
BOARD
BLOWER AND
MOTOR
CAPACITOR/
POWER CHOKE
A10314
NOTE: The 58PHB/PHY Furnaces are factory shipped for use with natural gas. These furnaces can be field--converted for propane gas with
a factory--authorized and listed accessory conversion kit.
2
MODEL NUMBER NOMENCLATURE
58PHB
045
100
08
Nominal Cooling Size
(Airflow at .5 e.s.p.)
400 CFM per 12,000 Btuh)
08 --- 800 CFM
12 --- 1200 CFM
20--- 2000 CFM
100
Series Number
58PHB 4--- Way Multipoise
58PHY Low NOx Version
Input Rates
045 --- 44,000 Btuh
070 --- 66,000 Btuh
090 --- 88,000 Btuh
110 --- 110,000 Btuh
135 --- 132,000 Btuh
58PHB
DIMENSIONS
5.1
[130.5]
2 1/16
[51.6]
1.7
[43.5]
5 15/16
[150.7]
5 1/2
[140.3]
8 7/16
[213.5]
9 7/8
[250.7]
Ø7/8
[22.2]
ACCESSORY
Ø1/2
[12.7]
THERMOSTAT WIRE ENTRY
27 3/4
[704.7]
Ø7/8
[22.2]
ACCESSORY (2)
1 15/16
[49.2]
2 5/16
3 7/16 [59]
[86.8]
5 7/8
[148.5]
TOP OF CASING
Ø7/8
[22.2]
JUNCTION BOX
LOCATION
AIR FLOW
FRONT OF CASING
FRONT OF CASING
C
5 7/8
[148.5]
AIR FLOW
5 7/16
[138.5]
A
B
TOP OF CASING
6 13/16
[172.3]
8 5/8
[219]
5 5/8
[143.3]
AIR FLOW
1 15/16
[49.2]
19
[481.7]
OUTLET
Ø1/2
[12.7]
THERMOSTAT WIRE ENTRY
Ø1 3/4
[44.5]
GAS ENTRY
4 13/16
[122.2]
9 9/16
[243.3]
27 3/4
[704.7]
Ø1 3/4
[44.5]
GAS ENTRY
29 9/16
[750.7]
33 1/4
[843.9]
Ø7/8
[22.2]
ACCESSORY
6.1
[155.7]
D
BOTTOM RETURN
WIDTH
3/4
[19.1]
11 7/16
[290.7]
Ø7/8
[22.2]
J.BOX PROVISION
Ø7/8
[22.2]
ACCESSORY
Ø7/8
[22.2]
ACCESSORY
21.6
[549.5]
BOTTOM INLET
28.39
[721.2]
29
[736.9]
7 13/16
9 11/16
[197.8]
[245.4]
KNOCK OUTS FOR
VENTING(5
PLACES)
22 1/16
[560]
SIDE INLET
(BOTH SIDES)
14 7/8
[337.3]
(BOTH SIDES)
1 1/4
[31.8]
1
[25.4]
NOTES:
1. Two additional 7/8 ---in. (22 mm) diameter holes are located in the top plate.
2. Minimum return ---air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
3. Minimum return ---air opening at furnace.
a. For 800 CFM ---16 ---in. (406 mm) round or 14 1/2 x 12 ---in. (368 x 305 mm) rectangle.
b. For 1200 CFM ---20 ---in. (508 mm) round or 14 1/2 x 19 1/2 ---in. (368 x 495 mm) rectangle.
c. For 1600 CFM ---22 ---in. (559 mm) round or 14 1/2 x 22 1/16 ---in. (368 x 560mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets,
a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
FC-2, FC-3,
FC-8
FURNACE SIZE
045--- 12
070--- 12
070--- 16
090--- 14
090--- 16
110--- 20
135--- 20
A
CABINET
WIDTH
B
OUTLET
WIDTH
C
TOP AND
BOTTOM FLUE
COLLAR
D
BOTTOM
INLET WIDTH
14--- 3/16 (360)
17--- 1/2 (445)
17--- 1/2 (445)
17--- 1/2 (445)
21 (533)
21 (533)
24--- 1/2 (622)
12--- 9/16 (319)
15--- 7/8 (403)
15--- 7/8 (403)
15--- 7/8 (403)
19--- 3/8 (492)
19--- 3/8 (492)
22--- 7/8 (581)
9--- 5/16 (237)
11--- 9/16 (294)
11--- 9/16 (294)
11--- 9/16 (294)
13--- 5/16 (338)
13--- 5/16 (338)
15--- 1/16 (383)
12--- 11/16 (322)
16 (406)
16 (406)
16 (406)
19--- 1/2 (495)
19--- 1/2 (495)
23 (584)
VENT
CONNECTION
SIZE
SHIP WT.
LB. (KG)
ACCESSORY
FILTER
MEDIA
CABINET SIZE
IN. (MM)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)*
104 (47)
126 (57)
126 (57)
126 (57)
140 (64)
152 (69)
163 (74)
16 (406)
16 (406)
16 (406)
16 (406)
20 (508)
20 (508)
24 (610)
*135 size furnace requires a 5 or 6 ---in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions for complete
installation requirements.
FC-1, FC-4,
FC-5, FC-6,
FC-7, FC-9
3
FC-1, FC-4,
FC-5, FC-6,
FC-7, FC-9
FC-2, FC-3,
FC-8
SPECIFICATIONS
UNIT SIZE
045 -- 12
070 -- 12
070 -- 16
090 -- 14
090 -- 16
110 -- 20
135 -- 20
RATINGS AND PERFORMANCE
Input Btuh*
58PHY Upflow; all 58PHB
44,000
66,000
66,000
88,000
88,000
110,000
132,000
Nonweatherized ICS
58PHY Downflow/Horizontal
42,000
63,000
63,000
84,000
84,000
105,000
126,000
Output Capacity (Btuh)†
58PHY Upflow; all 58PHB
36,000
54,000
54,000
71,000
72,000
90.000
107.000
Nonweatherized ICS
58PHY Downflow/Horizontal
34,000
51,000
51,000
68,000
68,000
85,000
102,000
80.0
80.0
80.0
80.0
80.0
80.0
80.0
30-60
(17--- 33)
35--- 65
(19--- 36)
25--- 55
(14--- 31)
40-70
(22--- 39)
35--- 65
(19--- 36)
30-60
(17--- 33)
40-70
(22--- 39)
Heating
0.10
0.12
0.12
0.15
0.15
0.20
0.20
Cooling
0.50
0.50
0.50
0.50
0.50
0.50
0.50
AFUE†
Certified Temperature Rise Range --- ° F (° C)
58PHB
External Static Pressure
Airflow CFM‡
Heating
710
982
1205
1203
1418
1890
1760
Cooling
1080
1005
1435
1210
1445
2040
1810
ELECTRICAL
Unit Volts--- Hertz--- Phase
115-60-1
Operating Voltage Range
Min-Max
104-127
Maximum Unit Amps
5.6
5.6
10.0
8.2
8.2
13.4
10.7
Unit Ampacity
7.8
7.8
13.3
11.0
11.0
17.4
14.0
47 (14.3)
47 (14.3)
27 (8.2)
33 (10.1)
33 (10.1)
33 (10.1)
26.0 (7.9)
Maximum Wire Length (Measure one way in Ft (M)
Minimum Wire Size
14
12
14
Maximum Fuse or Ckt Bkr Size (Amps)**
15
20
15
5
6
Transformer (24v)
40va
External Control
Heating
12va
Power Available
Cooling
35va
Air Conditioning Blower Relay
Standard
CONTROLS
Limit Control
SPST
Heating Blower Control
Solid-State Time Operation
Burners (Monoport)
2
3
3
4
Gas Connection Size
4
1/2-in. NPT
GAS CONTROLS
Gas Valve (Redundant)
Mfr.
White-Rodgers
Min. inlet pressure (In. W.C.)
4.5/1.21 (Natural Gas)
Max. inlet pressure (In. W.C.)
13.6/3.386 (Natural Gas)
Ignition Device
Hot Surface
Factory-installed orifice
Size 43
BLOWER DATA
Direct-Drive Motor HP (ECM)
1/3
1/3
3/4
1/2
1/2
1
3/4
Motor Full Load Amps
4.4
4.4
8.8
6.8
6.8
11.5
8.8
10 x 6
(254 x
152)
11 x 8
(279 x
203)
11 x 8
(279 x
203)
10 x 10
(254 x
254)
11 x 11
(279 x
279)
11 x 11
(279 x
279)
RPM (Nominal)-Speeds
Blower Wheel Diameter x Width --- In. (mm)
1050--- 5
*
11 x 8
(279 x
203)
Gas input ratings are certified for elevations to 2000 ft. (610 M). In USA, for elevations above 2000 ft. (610 M), reduce ratings 4 percent for each 1000 ft. (305
M) above sea level. Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1 ---2012 Table F.4 or furnace installation instructions.
†
Capacity in accordance with U.S. Government DOE test procedures.
‡
Airflow shown is for bottom only return-air supply for the as-shipped speed tap. For air delivery above 1800 CFM, see Air Delivery table for other options. A
filter is required for each return-air supply. An airflow reduction of up to 7 percent may occur when using the factory-specified 4-5/16 in. wide, high efficiency
media filter.
** Time ---delay type is recommended.
ICS Isolated Combustion System
4
CARRIER ACCESSORIES
Media Filter Cabinet
Cartridge Media Filter
EZ Flex Media Filter with End Caps
Replacement EZ Flex Filter Media
Filter Rack Bottom Return
External Side Return Filter Rack
Unframed Filter 3/4---in. (19 mm)
Flue Extension
Combustible Floor Base
Downflow Vent Guard
Vent Extension Kit
Chimney Adapter Kit
Chimney Adapter Kit
Natural---to---Propane Conversion
Kit*
Propane---to---Natural Conversion
Kit*
Gas Orifice
PART NO.
045 -- 12
070 -- 12
070 -- 16
090 -- 14
FILCABXL0016
FILCABXL0020
FILCABXL0024
FILCCCAR0016
FILCCCAR0020
FILCCCAR0024
EXPXXUNV0016
EXPXXUNV0020
EXPXXUNV0024
EXPXXFIL0016
EXPXXFIL0020
EXPXXFIL0024
KGBFR0401B14
KGBFR0501B17
KGBFR0601B21
KGBFR0701B24
KGAFR0201ALL
KGAWF1306UFR {
KGAWF1406UFR
KGAWF1506UFR
KGAFE0112UPH
KGASB0201ALL
KGBVG0101DFG
KGAVE0101DNH
KGACA02014FC
KGACA02015FC
X
X
X
X
090 -- 16
110 -- 20
X
X
135 -- 20
KGBNP50011SP
X
X
X
X
X
X
X
KGBPN42011SP
X
X
X
X
X
X
X
LH32DB207
LH32DB202
LH32DB200
LH32DB205
LH32DB208
LH32DB078
LH32DB076
LH32DB203
LH32DB201
LH32DB206
LH32DB209
LH32DB210
See Installation Instructions for model, altitude, and heat value usages.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
*Factory ---authorized and field---installed. Gas conversion kits are CSA (AGA/CGA) recognized.
{Suitable for Side Return Filter Rack
X --- Accessory
S --- Standard
5
58PHB
DESCRIPTION
CARRIER ACCESSORIES
58PHB
ACCESSORIES
ELECTRONIC AIR
CLEANER (EAC)
AIR PURIFIER
MECHANICAL AIR
CLEANER
HUMIDIFIER
HEAT RECOVERY
VENTILATOR
ENERGY
RECOVERY
VENTILATOR
UV LIGHTS
THERMOSTAT --NON--PROGRAMMABLE
Model EACB
Models GAPAAXCC1625, GAPAAXCC2025
Models EZXCAB, FILCAB
Model HUM
Model HRV
Model ERV
Model UVL
For use with 1---speed Air Conditioner --- deg. F/C, Auto Changeover --- TP---NAC, TC ---NAC
For use with 1---speed Heat Pump --- deg. F/C, Auto Changeover --- TP---NHP, TC ---NHP*
For use with 1---speed Air Conditioner --- deg. F/C, Auto Changeover, 7---Day Programmable --- TP---PAC
For use with 1---speed Heat Pump --- deg. F/C, Auto Changeover, 7---Day Programmable --TP---PHP*
For use with 1---speed Air Conditioner --- deg. F/C, 5---2 Day Programmable --- TP---PAC
Comfort Series™ Three---Zone Kit --- ZONECC3ZAC01, ZONECC3ZHP01
2---Performance™ Series ComfortZone™ Zoning/Temperature and Humidity Control --- ZONECC2KIT01---B
4---Performance™ Series ComfortZone™ Zoning/Temperature and Humidity Control --- ZONECC4KIT01---B
8---Performance™ Series ComfortZone™ Zoning/Temperature and Humidity Control --- ZONECC8KIT01---B
THERMOSTAT --PROGRAMMABLE
ZONING CONTROL
TYPICAL WIRING SCHEMATIC
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
NOTE 2
FIVE WIRE
THREE-WIRE
HEATING-ONLY
W
C
R
G
Y
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE
PHASE
BLOWER DOOR SWITCH
BLK
BLK
WHT
WHT
GND
115-V FIELDSUPPLIED
DISCONNECT
W
GND
AUXILIARY
J-BOX
C
O
N
T
R
O
L
R
208/230-V
SINGLE
PHASE
G
COM
GND
NOTE 1
CONDENSING
UNIT
Y/Y2
24-V
TERMINAL
BLOCK
FURNACE
TWO
WIRE
NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
*Model HP and 2S thermostat must be field converted to air conditioner operation.
{Thermidistatt Control control can be configured for multiple use and staging. It must be configured for each specific application.
}Dual Fuel thermostat is used with furnace and heat pump application.
A99440
6
SEE NOTES: 1,2,3,4,7,8,9
UPFLOW
SEE NOTES: 1,2,4,5,7,8,9
DOWNFLOW
A02059
A02061
A02058
SEE NOTES:1,2,3,4,5,7,8,9
DOWNFLOW
SEE NOTES: 1,2,3,4,7,8,9
DOWNFLOW
SEE NOTES: 1,2,4,5,6,7,8,9
DOWNFLOW
A02060
A02063
A02062
Venting Notes
1. For common vent, vent connector sizing and vent material: United States, latest edition of the National Fuel Gas Code (NFGC),
NFPA54/ANSI Z223.1.
2. Immediately increase to 5--in. (127 mm) vent connector outside furnace casing when 5--in. (127 mm) vent connector required, refer to
Note 1.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when
Downflow Vent Guard is used in downflow position.
4. Type B vent where required, refer to Note 1.
5. 4--in. (102 mm) single wall vent must be used inside furnace casing and the Downflow Vent Guard Kit.
6. Accessory Downflow Vent Guard Kit required in downflow installations with bottom vent configuration.
7. Chimney Adapter Kit required for exterior masonry chimney applications. Refer to Chimney Adapter Kits for sizing and complete
application details.
8. Secure vent connector to furnace elbow with (2) corrosion--resistant sheet metal screws, space approximately 180_ apart.
9. Secure all other single wall vent connector joints with (3) corrosion--resistant screws spaced approximately 120_ apart. Secure Type B
vent connectors per vent connector manufacturer’s recommendations.
7
58PHB
SEE NOTES: 1,2,4,7,8,9
UPFLOW
58PHB
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL RIGHT
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL RIGHT
A02068
A02070
SEE NOTES: 1,2,4,7,8,9
HORIZONTAL RIGHT
SEE NOTES: 1,2,4,7,8,9
HORIZONTAL LEFT
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02069
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02064
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02066
8
A02065
A02067
AIR DELIVERY - CFM (WITH FILTER)*
045-12
070-12
070-16
090-14
090-16
110-20
135-20
Wire
Lead
Color
Gray
Yellow
Orange
Blue
Red
Gray
Yellow
Blue
Orange
Red
Gray
Yellow
Blue
Orange
Red
Gray
Yellow
Blue
Orange
Red
Gray
Blue
Yellow
Orange
Red
Gray
Blue
Yellow
Orange
Red
Gray
Blue
Yellow
Orange
Red
Speed
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
13
5
4
3
2
13
5
4
3
2
1
5
4
3
2
13
Test Airflow Delivery @ Various External Static Pressures
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1230
980
770
710
600
1185
1000
990
855
860
1610
1385
1215
1175
1080
1355
1295
1220
1030
945
1625
1440
1425
1260
1095
2255
1945
1600
1420
1280
2065
1825
1760
1620
1325
1190
945
720
660
540
1140
940
935
775
685
1565
1335
1165
1130
1015
1320
1255
1185
985
905
1580
1395
1380
1210
1040
2205
1890
1525
1340
1205
2005
1760
1690
1550
1260
1155
920
685
620
500
1095
895
895
720
515
1525
1290
1120
1085
955
1285
1220
1150
940
855
1535
1350
1335
1160
980
2150
1830
1465
1280
1140
1940
1695
1625
1480
1185
1120
890
640
580
455
1055
850
845
660
445
1475
1250
1075
1035
920
1245
1185
1105
900
800
1490
1305
1290
1105
905
2100
1770
1400
1200
1055
1875
1630
1555
1405
1100
1080
855
600
540
415
1005
800
790
605
385
1435
1205
1035
990
875
1210
1140
1065
845
750
1445
1255
1235
1050
845
2040
1715
1335
1140
990
1810
1560
1485
1335
1025
1045
815
560
490
385
960
750
740
560
340
1395
1165
985
945
820
1165
1100
1025
790
670
1395
1200
1185
990
780
1985
1655
1275
1065
910
1740
1490
1415
1260
955
1010
770
520
455
345
915
695
690
495
275
1350
1125
940
900
780
1125
1055
975
715
600
1340
1145
1125
935
720
1920
1600
1210
1005
840
1670
1420
1345
1195
885
975
735
475
415
305
865
650
640
435
205
1305
1075
895
855
725
1080
1005
915
655
540
1260
1090
1075
880
650
1835
1545
1150
925
760
1600
1350
1275
1130
805
935
690
430
375
235
820
600
590
385
-1260
1025
845
805
670
1025
955
840
590
490
1135
1040
1020
820
585
1735
1480
1080
865
695
1530
1275
1200
1065
735
895
645
385
335
-780
555
535
335
-1215
980
840
760
620
815
815
740
535
435
995
950
940
755
520
1615
1430
1015
790
630
1470
1205
1130
995
670
1. A filter is required for each return ---air inlet. Airflow performance included 3/4 ---in. (19 mm) washable filter media such as contained in factory ---authorized
accessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure.
2. Adjust the blower speed tabs as necessary for the proper air temperature rise for each installation.
3. Highlighted areas indicate airflow range is beyond the range allowed for heating. THESE AIRFLOW RANGES MAY ONLY BE USED FOR COOLING.
4. --- --- Indicates unstable operating conditions.
9
58PHB
Furnace
58PHB
A10269
Always Ask For
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
10
GUIDE SPECIFICATIONS
Casing
Casing shall be of .030--in. (.76 mm) thickness minimum,
pre--painted steel.
GENERAL
System Description
Furnish a _________________ fixed capacity gas--fired furnace
for use with natural gas or propane (factory authorized conversion
kit required for propane); furnish cold air return plenum; furnish
external accessory media cabinet for use with accessory media filter
or standard filter.
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be 3rd party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will carry the CSA Blue Star label.
Unit efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest AHRI Consumer’s Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Inducer Motor
Inducer motor shall be soft mounted to reduce vibration
transmission.
Draft Safeguard Switch
Draft Safeguard Switch (blocked vent safeguard) shall be factory
installed to reduce the possibility of vent gas infiltration due to a
blocked or restricted vent pipe.
Heat Exchangers
Heat exchangers shall be a 4--Pass 20 gage aluminized steel of
fold--and--crimp sectional design when applied operating under
negative pressure.
Controls
Control shall include a micro--processor based integrated electronic
control board with at least 11 service troubleshooting codes
displayed via enhanced flashing LED diagnostic light on the
control, a self--test feature that checks all major functions of the
furnace within one minute, and a replaceable automotive--type
circuit protection fuse. Multiple operational settings available
including, separate blower speeds for heating, cooling and
continuous fan.
Delivery, Storage and Handling
Operating Characteristics
Unit shall be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Heating Capacity shall be ________ Btuh input; ________ Btuh
output capacity.
Fuel Gas Efficiency shall be 80% AFUE.
Air delivery shall be ___________ CFM minimum at 0.50 In.
W.C. external static pressure.
Dimensions shall be: depth __________ in. (mm); width
_________ in. (mm); height_________in. (mm) (casing only).
Height shall be_________in. (mm) with A/C coil and
____________ in. (mm) overall with plenum.
Warranty (for inclusion by specifying engineer)
U.S. only. Warranty certificate available upon request.
PRODUCTS
Equipment
Components shall include: slow--opening gas valve to reduce
ignition noise, regulate gas flow, with electric switch gas shut--off;
flame proving sensor, hot surface igniter, pressure switch assembly;
flame rollout switch, blower and inducer assembly, 40va
transformer; low--voltage (heating) (heating/ cooling) thermostat.
Blower Wheel and Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed bearings, of _______hp, and
shall be multiple--speed direct drive. shall be soft mounted to the
blower scroll to reduce vibration transmission.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal).
Minimum wire size shall be_________AWG; maximum fuse size
or circuit breaker shall be __________Amps.
Special Features
Refer to section of the product data sheet identifying accessories
and descriptions for specific features and available enhancements.
Filters
Furnace may have reusable--type filters. Filter shall be _______ in
(x) _______in. (mm). An accessory high efficiency Media Filter is
available as an option. _______________ Media Filter.
11
58PHB
Gas Furnace
58PHB/PHY
58PHB
Copyright 2015 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Edition Date: 01/15
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
12
Catalog No: 58PHB---01PD
Replaces: New
Floor Drains_08.qxd
3/27/08
9:31 AM
Page 98
FLOOR DRAINS
SUPER-FLO® Features
The two-piece Floor Drain bodies which are designed to be combined with any adjustable strainers offered by JOSAM have proven features which
make them the easiest and quickest drains of this type to install. The clean fine thread which is on all types of adjustable strainers provides uninterrupted adjustment at any time during construction up to and including the time the floor is being poured. Exclusive features are described and shown
below. For further details and specifications, refer to the specific series in this section.
ADJUSTABLE STRAINERS FOR ALL APPLICATIONS
All adjustable Strainers and Accessories shown in the
Strainer Section can be used with the 30000, 30000-PD,
30000-TSO, 30002-ST, 30304-Z and 30500 Series Drain
Bodies. Strainers are offered for all types of floor finishes
and applications. Adjustable strainer and body combinations are shown so that dimensional data can be obtained
for installation and specification purposes.
FLOOR DRAINS
COLLAR
Invertible collar provides extra
vertical adjustment for strainer.
KEYHOLE
Keyhole slots assure quick assembly
without removal of bolts.
PRIMER TAP
1/2” Primer Tap Connection with
plug, standard on some series,
optional (-50) on others.
JIFFEE-SET
JOSAM Floor Drains feature JIFFEE-SET connections with MULTI-TITE® service
weight (SV) soil pipe gaskets, conforming to ASTM Standard C564 in 2, 3, and 4
inch sizes for labor-saving assembly to service weight cast iron, no-hub cast iron,
PVC and ABS pipe. Merely lubricate gasket and pipe, set drain in place, push
down until top of pipe contacts built-in stop and the joint is complete.
98
WEEPHOLES
Weepholes around double
drainage flange for seepage.
THREADS
Heavy collar designed to accept
all JOSAM exclusively threaded
strainers.
WEJLOC®
Exclusive compression "wedge lock"
provides positive non-puncturing bond of
waterproofing membrane to drain.
Floor Drains_08.qxd
3/27/08
9:32 AM
Page 110
FLOOR DRAINS • Strainers
A SERIES
ROUND NIKALOY SUPER-FLO® STRAINER
APPLICATION
For use in finished areas with pedestrian traffic such as toilet and shower rooms.
Available Options
-SS
-2
-80
-CP
-J
-VP
Stainless Steel, 5A, 6A, 7A, 8A
Satin Finish Bronze
Perforated Stainless Steel Basket
Chrome Plated, 5A, 6A
Backwater Valve
Secured Grate, Vandal-Proof Screws
TYPE NO.
5A
6A
7A
8A
9A•
10A•
A
5
6
7
8
9
10
B
1-15/16
2-1/4
2-11/16
2-1/2
2-1/4
2-1/4
C
1-1/8
15/16
1-1/2
7/8
1
1-1/8
D
4-5/8
5-1/4
6-7/16
7-1/8
8-1/8
9
AD SERIES
FREE AREA
7.8
11.0
13.2
16.2
21.1
28.0
LBS.
2
3
4
5
7
9
•Not SUPER-FLO® Design
ROUND NIKALOY STRAINER with Clamp Device
APPLICATION
For use in finished areas with pedestrian traffic such as supermarkets or kitchens.
FLOOR DRAINS
Available Options
-2 Satin Bronze Top
-VP Secured Grate, Vandal-Proof Screws
TYPE NO.
6AD
FREE AREA
10.4
LBS.
4
AF SERIES
ROUND NIKALOY STRAINER with Tile Flange
APPLICATION
For use in areas where a vinyl tile, liquid or trowel applied floor covering is to be
adhered to the strainer flange and pedestrian traffic is expected.
Available Options
-2
-80
-J
-VP
Satin Finish Bronze
Perforated Stainless Steel Basket
Backwater Valve
Secured Grate, Vandal-Proof Screws
TYPE NO.
6AF
110
FREE AREA
10.4
LBS.
5
MVP FAUCETS
3500-8E2805ABCP
Manual Faucets
Product Type
___________________________________________________
Deck Mounted 8" Fixed Centers Single Supply Metering Sink Faucet
Job Name ________________________________________________
Features & Specifications
___________________________________________________
• 8" Fixed Centers
• 0.5 GPM (1.9 L/min) Vandal Proof Non-Aerating Spray
• MVP Metering Adjustable Cycle Time Closure Cartridge
• Single Supply for Tempered Water
• Stainless Steel Hose Included
• 4" Center to Center Integral Cast Brass Spout
• ECAST® design provides durable construction with total lead content
equal to or less than 0.25% by weighted average
• CFNow! Item Ships in 3 Days
Item Number _____________________________________________
Section/Tag ______________________________________________
Model Specified ___________________________________________
Architect _________________________________________________
Engineer _________________________________________________
Contractor ________________________________________________
Performance Specification
___________________________________________________
• Rated Operating Pressure: 20-125 PSI
• Rated Operating Temperature: 40-140ºF
[ ] Submitted as Shown
[ ] Submitted with Variations
Date _____________________________________________________
Warranty
___________________________________________________
• Lifetime Limited Faucet Warranty
• 5-Year Limited Cartridge Warranty
• 1-Year Limited Finish Warranty
Codes & Standards
___________________________________________________
• ASME A112.18.1/CSA B125.1
• Certified to NSF/ANSI 61, Section 9 by CSA
• California Health and Safety Code 116875 (AB1953-2006)
• Vermont Bill S.152
• NSF/ANSI 372 Low Lead Content
• ADA ANSI/ICC A117.1
• CALGreen
ECAST products are intended for installation where state laws and local
codes mandate lead content levels or in any location where lead content
is a concern.
Last Revision: 04/30/2013 • Date Printed: 10/26/2015 • Product specifications subject to change without notice
2100 South Clearwater Drive
Des Plaines, IL
P: 847/803-5000
F: 847/803-5454
Technical: 800/TEC-TRUE
www.chicagofaucets.com
3500-8E2805ABCP
Manual Faucets
Architect/Engineer Specification
________________________________________________________________________________________________________
Chicago Faucets No. 3500-8E2805ABCP, Sink Faucet, metering, single-supply, deck-mounted with 8" fixed centers, chrome plated. Integral, cast
brass spout, 4" center-to-center. 0.5 GPM (1.9 L/min) vandal-proof, pressure compensating, Econo-Flo, non-aerating spray. MVP self-closing,
auto-timed metering cartridge, adjustable run time from 2 to 15 seconds, opens with push, 0.20 max gallon/cycle. Single supply for tempered water.
Stainless steel hose included. ECAST® construction with less than 0.25% lead content by weighted average. CALGreen compliant. This product
meets ADA ANSI/ICC A117.1 requirements and is tested and certified to industry standards: ASME A112.18.1/CSA B125.1, Certified to NSF/ANSI
61, Section 9 by CSA, California Health and Safety Code 116875 (AB1953-2006), Vermont Bill S.152, NSF/ANSI 372 Low Lead Content, and
California Green Building Standards Code (CALGreen). This product meets ADA ANSI/ICC A117.1 requirements and is tested and certified to
industry standards: ASME A112.18.1/CSA B125.1, Certified to NSF/ANSI 61, Section 9 by CSA, California Health and Safety Code 116875
(AB1953-2006), Vermont Bill S.152, NSF/ANSI 372 Low Lead Content, and California Green Building Standards Code (CALGreen).
Operation and Maintenance
________________________________________________________________________________________________________
Installation should be in accordance with local plumbing codes. Flush all pipes thoroughly before installation. After installation, remove spout outlet or
flow control and flush faucet thoroughly to clear any debris. Care should be taken when cleaning the product. Do not use abrasive cleaners,
chemicals or solvents as they can result in surface damage. Use mild soap and warm water for cleaning and protecting the life of Chicago Faucet
products. For specific operation and maintenance refer to the installation instructions and repair parts documents that are located at
www.chicagofaucets.com.
Chicago Faucets, member of the Geberit Group, is the leading brand of commercial faucets and fittings in the United States, offering a complete
range of products for schools, laboratories, hospitals, office buildings, food service, airports and sport facilities. Call 1.800.TECTRUE or
1.847.803.5000 Option 1 for installation or other technical assistance.
Last Revision: 04/30/2013 • Date Printed: 10/26/2015 • Product specifications subject to change without notice
2100 South Clearwater Drive
Des Plaines, IL
P: 847/803-5000
F: 847/803-5454
Technical: 800/TEC-TRUE
www.chicagofaucets.com
LUCERNE™
WALL-HUNG LAVATORY
VITREOUS CHINA
BARRIER FREE
LUCERNE™ WALL-HUNG LAVATORY
• Wall-hung sink
• Vitreous china
• Front overflow
• D-shaped bowl
• Self-draining deck area with contoured
back and side splash shields
• Faucet ledge
• Compliant with Texas accessibility standard
(TAS) for children age group 13 and up
Faucet holes on 203mm (8") centers (Illus.):
❏ 0356.028 For exposed bracket support
Shown with 4801.862 Amarilis Heritage faucet with Triune Cross handles (not included)
❏ 0356.015 For wall hanger (included) or
concealed arms support
❏ 0356.915 For wall hanger (included) or
concealed arms support
• Less overflow
0356.028
Faucet holes on 102mm (4") centers:
❏ 0355.027 For exposed bracket support
❏ 0355.012 For wall hanger (included) or
concealed arms support
concealed arms support
• Less overflow
❏ 0355.912 For wall hanger (included) or
Single center faucet hole (Illus.):
❏ 0356.041 For exposed bracket support
❏
❏
❏
❏
Shown with 1340.000 metering faucet
(not included)
0356.421 For wall hanger (included) or
concealed arms support
0356.921 For wall hanger (included) or
concealed arms support
• Less overflow
0356.439 For wall hanger (included) or
concealed arms support
• Single faucet hole on right
0356.066 For exposed bracket support
• Single faucet hole on right
Nominal Dimensions:
521 x 464mm
(20-1/2" x 18-1/4")
Bowl sizes:
381mm (15") wide
254mm (10") front to back
165mm (6-1/2") deep
Compliance Certifications Meets or Exceeds the Following Specifications:
• ASME A112.19.2 / CSA B45.1 for Vitreous
China Fixtures
© 2014 AS America Inc.
0356.041
SEE FOLLOWING PAGES FOR ROUGHING-IN DIMENSIONS
To Be Specified:
❏ Color: ❏ White
❏ Faucet*:
❏ Faucet Finish:
❏ Supplies:
❏ 1-1/4" Trap:
❏ Nipple:
❏ Bracket Support (by others):
❏ Concealed Arms Support (by others):
* See faucet section for additional models available
MEETS THE AMERICANS WITH DISABILITIES ACT GUIDELINES AND ANSI A117.1 ACCESSIBLE AND USABLE
BUILDINGS AND FACILITIES - CHECK LOCAL CODES.
Top of front rim mounted 864mm (34") from finished floor.
M31
Revised 3/14
LUCERNE™
WALL-HUNG LAVATORY
VITREOUS CHINA
BARRIER FREE
0356.028 8" CTRS FOR EXPOSED BRACKET SUPPORT
0356.015 8" CTRS FOR WALL HANGER OR CONCEALED ARMS
0356.915 LESS OVERFLOW
86mm
(3-3/8")
102mm
(4")
203mm
(8")
152mm
(6")
464mm
(18-1/4")
203mm
(8")
425mm
(16-3/4")
267mm
(10-1/2")
114mm
(4-1/2")
206mm
(8-1/8")
286mm
*(11-1/4")
203mm
(8")
38mm
(1-1/2")
1-1/4" O.D. WASTE
OUTLET FOR
POP-UP DRAIN
18-1/4"
(464mm)
10mm
(3/8")
DIA. ANCHOR
SCREW HOLES
352mm
*(13-7/8")
27mm X 14mm
(1-1/16" x 5/16") SLOTS
SUPPLIES
AS REQUIRED
1-1/4" O.D. WASTE
OUTLET FOR
DRAIN PLUG
79mm
(3-1/8")
298mm
*(11-3/8")
FINISHED
FLOOR
787mm (31")
864mm (34")
203mm
(8")
1-1/4" O.D. WASTE
OUTLET FOR
POP-UP DRAIN
1-1/4" O.D. WASTE
OUTLET FOR
DRAIN PLUG
18-1/4"
(464mm)
FINISHED
WALL
8" MIN.
(203mm)
34"
(864mm)
S-9 HANGER
27mm x 14mm
(1-1/16 x 5/16")
SLOTS
SUPPLIES
AS REQUIRED
6" MAX.
(152mm)
6" MAX.
(152mm)
BARRIER FREE
CLEARANCE
9" MIN.
(229mm)
BARRIER FREE
CLEARANCE
11"
(279mm)
FINISHED
WALL
8" MIN.
(203mm)
34"
(864mm)
27" MIN.
(686mm)
27" MIN.
(686mm)
FINISHED
FLOOR
787mm (31)
864mm (34)
79mm
(3-1/8")
54mm (2-1/8") DIA.
HOLES FOR
CONCEALED ARMS
298mm
*(11-3/8")
102mm
(4")
25mm
(1")
44mm
(1-3/4")
25mm
(1")
352mm
*(13-7/8")
54mm (2-1/8") DIA.
HOLES FOR
CONCEALED ARMS
114mm
(4-1/2")
S-9 HANGER
13mm
(1/2")
521mm
(20-1/2")
425mm
(16-3/4")
267mm
(10-1/2")
10mm (3/8")
DIA. ANCHOR
SCREW HOLES
8mm
(5/16")
(6) 25mm
(1") DIA.
ACCESS
HOLES
FOR
CONC.
ARMS
13mm
(1/2")
521mm
(20-1/2")
464mm
(18-1/4")
102mm
(4")
152mm
(6")
8mm
(5/16")
(6) 25mm
(1") DIA.
ACCESS
HOLES FOR
CONC. ARMS
38mm
(1-1/2")
FINISHED
WALL
203mm
(8")
152mm
(6")
152 mm
(6")
102mm 44mm
(4") (1-3/4")
86mm
(3-3/8")
102mm
FINISHED (4")
WALL
206mm
(8-1/8")
FINISHED
WALL
260mm
*(10-1/4")
0355.021 4" CTRS FOR EXPOSED BRACKET SUPPORT
0355.012 4" CTRS FOR WALL HANGER OR CONCEALED ARMS
0355.912 LESS OVERFLOW
9" MIN.
(229mm)
11"
(279mm)
NOTES:
DIMENSIONS SHOWN FOR LOCATION OF SUPPLIES AND “P” TRAP ARE SUGGESTED.
*PROVIDE
SUITABLE REINFORCEMENT FOR ALL WALL SUPPORTS.
FITTINGS NOT INCLUDED AND MUST BE ORDERED SEPARATELY.
CONCEALED ARM SUPPORT AS REQUIRED TO BE FURNISHED BY OTHERS.
IMPORTANT: Dimensions of fixtures are nominal and may vary within the range of tolerances established
by ANSI Standard A112.19.2. These measurements are subject to change or cancellation. No responsibility
is assumed for use of superseded or voided pages.
© 2014 AS America Inc.
LAVATORY DESIGNED TO MEET ADA HANDICAPPED GUIDELINES WITH MOUNTING HEIGHT SET AT 864MM (34") ABOVE FINISHED FLOOR.
M32
Revised 3/14
LUCERNE™
WALL-HUNG LAVATORY
VITREOUS CHINA
BARRIER FREE
0356.041
SINGLE CENTER HOLE FOR EXPOSED BRACKET SUPPORT
0356.421 SINGLE CENTER HOLE FOR WALL HANGER OR CONCEALED ARMS
0356.921 LESS OVERFLOW
44mm (1-3/4") DIA.
STD. OUTLET
0356.439
SINGLE CENTER HOLE ON RIGHT FOR WALL HANGER OR CONCEALED ARMS
0356.066 SINGLE CENTER HOLE ON RIGHT FOR EXPOSED BRACKET SUPPORT
25mm (1-3/8") DIA.
PUNCHING
86mm
(3-3/8")
102mm
(4")
86mm
(3-3/8")
114mm
(4-1/2")
203mm
(8")
FINISHED
WALL
152mm
(6")
203mm
(8")
FINISHED
WALL
13mm x 51mm BRACKET
(1/2" x 2") SLOTS
464mm
(18-1/4")
44mm (1-3/4") DIA.
STD. OUTLET
464mm
(18-1/4")
152mm
(6")
102mm
(4")
8mm
(5/16")
(6) 25mm (1") DIA.
ACCESS HOLES
FOR CONC. ARMS
25mm (1") DIA.
HOLES
8mm
(5/16")
57mm
(2-1/4")
13mm
(1/2")
425mm
(16-3/4")
521mm
(20-1/2")
13mm
(1/2")
521mm
(20-1/2")
425mm
(16-3/4")
425mm
(16-3/4")
267mm
(10-1/2")
267mm
(10-1/2")
114mm
(4-1/2")
102mm 44mm
(4") (1-3/4")
35mm (1-3/8") DIA.
PUNCHING
349mm
(13-3/4")
114mm
(4-1/2")
54mm (2-1/8") DIA.
HOLES FOR
CONCEALED ARMS
25mm
(1")
102mm 44mm
(4") (1-3/4")
79mm
(3-1/8")
25mm
(1")
79mm
(3-1/8")
206mm
(8-1/8")
38mm
(1-1/2")
54mm (2-1/8") DIA.
HOLES FOR
CONCEALED ARMS
10mm (3/8")
DIA. ANCHOR
SCREW HOLES
206mm
(8-1/8")
10mm (3/8")
38mm
DIA. ANCHOR
(1-1/2")
SCREW HOLES
787mm (31")
864mm (34")
S-9 HANGER
FINISHED
FLOOR
27mm X 14mm
(1-1/16" x 5/16") SLOTS
18-1/4"
(464mm)
27" MIN.
(686mm)
18-1/4"
(464mm)
FINISHED
WALL
27" MIN.
(686mm)
9" MIN.
(229mm)
FINISHED
WALL
8" MIN.
(203mm)
34"
(864mm)
6" MAX.
(152mm)
BARRIER FREE
CLEARANCE
FINISHED
FLOOR
27mm X 14mm
(1-1/16" x 5/16") SLOTS
8" MIN.
(203mm)
34"
(864mm)
787mm (31")
864mm (34")
S-9 HANGER
6" MAX.
(152mm)
BARRIER FREE
CLEARANCE
9" MIN.
(229mm)
11"
(279mm)
11"
(279mm)
NOTES:
DIMENSIONS SHOWN FOR LOCATION OF SUPPLIES AND “P” TRAP ARE SUGGESTED.
*PROVIDE
SUITABLE REINFORCEMENT FOR ALL WALL SUPPORTS.
FITTINGS NOT INCLUDED AND MUST BE ORDERED SEPARATELY.
CONCEALED ARM SUPPORT AS REQUIRED TO BE FURNISHED BY OTHERS.
IMPORTANT: Dimensions of fixtures are nominal and may vary within the range of tolerances established
by ANSI Standard A112.19.2. These measurements are subject to change or cancellation. No responsibility
is assumed for use of superseded or voided pages.
© 2014 AS America Inc.
LAVATORY DESIGNED TO MEET ADA HANDICAPPED GUIDELINES WITH MOUNTING HEIGHT SET AT 864MM (34") ABOVE FINISHED FLOOR.
M33
Revised 3/14
Celebrity® Classroom Sink and Sink Packages
ModelsCDKR2517, CDKAD2517, and
CDKRC2517Series
®
SP E C I F I C AT I O N S
GENERAL
Good quality sink formed of #20 gauge, type 304 (18-8) nickel
bearing stainless steel.Top Mount.
DESIGN FEATURES
Sink Bowl Depth: 6-7/8"(175mm) (CDKR2517series), 6-1/2"(165mm)
(CDKAD251765 series).
Coved Corners: 3"(76mm) vertical and 2-1/4"(57mm) horizontal radius.
Bowl and Faucet Deck Recess: 3/16"(5mm) below outside edge of
sink.
Finish: Exposed surfaces are polished to a highlighted
Celebrity bright finish.
Underside: Fully undercoated to dampen sound and reduce
condensation.
Model CDKAD251765
OTHER
Drain Opening: 3-1/2"(89mm).
Select faucet and bubbler holes are slotted to allow for
vandal-resistant faucet and bubbler. See side 2 for illustration.
NOTE: Unless otherwise specified, sink is furnished with 2
faucet holes as illustrated.
Package model numbers include all components shipped in
a single carton. VRC suffix represents packages that have
vandal-resistant components.
Sink complies with ASME A112.19.3/ CSA B45.4
Sinks are listed by IAPMO as meeting the applicable
requirements of the Uniform Plumbing Code , International
Plumbing Code , and National Plumbing Code of Canada.
C
LKD208513LC
SINK DIMENSIONS (INCHES)*
Model
Number
Inside Bowl
Overall
L
W
L
W
D
No. of
Faucet
Holes
Minimum
Cabinet
Size
†
CDKR2517
14
67⁄8
163⁄8
25
17
153⁄4
243⁄8
(635mm) (431mm) (400mm) (356mm) (175mm) (619mm)(416mm) 2, 2LM or 4
30
CDKAD251765
25
17
153⁄4
14
243⁄8
163⁄8
6 1⁄ 2
(635mm) (431mm) (400mm) (356mm) (165mm) (619mm)(416mm) 2, 2LM or 4
30
*Length is left to right. Width is front to back.
Sink
Model Number
17"
(432mm)
14"
(356mm)
3" R
(76mm)
PACKAGE DETAILS
Package
Model Number
LKJ35
LKVR18
Cutout in
Countertop
(1-1/2"Radius
Corners)
L
W
LK1141A
LK35
Faucet
Model Number
Bubbler
Model Number
Drain
Model Number
CDKAD2517C
CDKAD2517652
LKD208513LC
LK1141A
LK35
CDKAD2517VRC
CDKAD2517652
LKDVR208513LC
LKVR1141A
LKVR18
CDKR2517C
CDKR25172
LKD208513LC
LK1141A
LK35
CDKR2517VRC
CDKR25172
LKDVR208513LC
LKVR1141A
LKVR18
CDKRC2517C
CDKR25172
LKD20858C
LK1141A
LKJ35
CDKRC2517VRC
CDKR25172
LKD20858LC
LKVR1141A
LKVR18
THIS PRODUCT, AS CONSTRUCTED IS SUBJECT TO
INTERPRETATION OF A.D.A. REQUIREMENTES. THE
UNOBSTRUCTED KNEE SPACE REQUIRED TO SATISY
A.D.A. STANDARDS MAY NOT BE DESIRABLE.
15-3/4"
(400mm)
25"
(635mm)
6-7/8"
(175mm)
2-1/4" R
(57mm)
Model CDKR2517 Illustrated
6-1/2"
(165mm)
2-1/4" R
(57mm)
Model CDKAD251765 Illustrated
In keeping with our policy of continuing product improvement, Elkay reserves the right to change
product specifications without notice. Please visit elkay.com for the most current version of Elkay
product specification sheets.
Elkay
elkay.com
This specification describes an Elkay product with design, quality, and functional benefits to the
user. When making a comparison of others producers offerings, be certain these featrues are
not overlooked.
2222 Camden Court
Oak Brook, IL 60523
© 2014 Elkay
(Rev. 04/14) 1-8H
Celebrity® Classroom Sink and Sink Packages
ModelsCDKR2517, CDKAD2517, and
CDKRC2517Series
®
SP E C I F I C AT I O N S
HOLE DRILLING CONFIGURATIONS
2 HOLE CONFIGURATION
2 LM (LEFT MIDDLE) HOLE CONFIGURATION
2-1/4"
(57mm)
2-1/4"
(57mm)
3"
(76mm)
8-1/2"
(216mm)
3"
(76mm)
SLOTTED
HOLE
(2 PLACES)
3"
(76mm)
2-1/4"
(57mm)
SLOTTED
HOLE
(1 PLACE)
MODELS CDKR25172LM
CDKAD2517652LM
MODELS CDKR25172
CDKAD2517652
4 HOLE CONFIGURATION
2-1/4"
(57mm)
4"
(102mm)
4"
(102mm)
4-1/2"
(114mm)
14"
(356mm)
SLOTTED
HOLE
(1 PLACE)
2-1/4"
(57mm)
MODELS CDKR25174
CDKAD2517654
Slotted Hole Detail
1-1/2”
(38mm)
In keeping with our policy of continuing product improvement, Elkay reserves the right to change
product specifications without notice. Please visit elkay.com for the most current version of Elkay
product specification sheets.
Elkay
elkay.com
1-1/8
(29mm)
DIA.
This specification describes an Elkay product with design, quality, and functional benefits to the
user. When making a comparison of others producers offerings, be certain these featrues are
not overlooked.
2222 Camden Court
Oak Brook, IL 60523
© 2014 Elkay
(Rev. 04/14) 1-8H
COMMERCIAL
S p e c ­i ­f i ­c a ­t i o n s
COMMERCIAL
SINK DESCRIPTION
•
•
•
Manufactured of 20 gauge stainless steel
The large bowl is a minimum of 14" wide by 16" and is 5 1/2" deep
The sink ledge has four fixture mounting holes, 1-1/2" in diameter
and 4" on center
Has two 3-1/2" diameter recessed drain openings located at rear of bowl
Soundshield undercoating maximizes sound deadening
and inhibits condensation
Made in USA
Includes all necessary mounting hardware
•
•
•
•
CUT OUT DIMENSIONS
•
Cut out dimensions are 32-3/8" x 21-3/8", with a 3/8" corner radius.
A tolerance of plus or minus 1/16" is acceptable
STANDARDS
•
Third party certified to meet ASME A112.18.1/CSA B-125.1
and all applicable specifications referenced therein
Certified to NSF 61/9
Complies with California Proposition 65 and with the
Federal Safe Drinking Water Act
•
•
ADA
•
Double Bowl Kitchen Sink
Mode:l 22129
(CDE-3322-4H)
for lever handles
WARRANTY
•
Warranted for five years against material or manufacturing defects
SINK OVERALL DIMENSION
CL
16-1/2"
(419mm)
4"
(102mm)
4"
1-1/2"(38mm)
DIA. TYP.
3/8" (10mm)
R. TYP.
SEALANT MATERIAL
COUNTERTOP
COUNTERTOP CUT-OUT
BOWL
DIMENSION
4-1/8"
(105mm)
CONTINUOUS
"V" CHANNEL
4-1/2
(114mm)
22"
(559mm)
WIDTH
3-1/2"(89mm)
DIA. TYP.
3-1/2"(89mm)
DIA. TYP.
16"
(406mm)
BOWL
SINK
CLAMP
UNDERCOAT
SINK OVERALL DIMENSION
SEALANT MATERIAL
COUNTERTOP
COUNTERTOP CUT-OUT
BOWL
DIMENSION
CONTINUOUS
"V" CHANNEL
SINK
CLAMP
UNDERCOAT
Installation Detail
2-3/4"(70mm)
R. TYP.
1-7/8"(48mm)
8-7/8"
(225mm)
1-1/4"(32mm)
8-7/8"
(225mm)
33"(838mm) LENGTH
1-7/8"
(48mm)
14" (356mm)
BOWL
14" (356mm)
BOWL
1-7/8"(48mm)
5-1/2"(140mm)
BOWL DEPTH
CL
16-1/2"
(419mm)
4"
(102mm)
4"
1-1/2"(38mm)
DIA. TYP.
3/8" (10mm)
R. TYP.
4-1/8"
(105mm)
4-1/2
(114mm)
22"
(559mm)
WIDTH
3-1/2"(89mm)
DIA. TYP.
3-1/2"(89mm)
DIA. TYP.
16"
(406mm)
BOWL
2-3/4"(70mm)
R. TYP.
1-7/8"(48mm)
8-7/8"
(225mm)
1-1/4"(32mm)
8-7/8"
(225mm)
33"(838mm) LENGTH
1-7/8"
(48mm)
14" (356mm)
BOWL
14" (356mm)
BOWL
1-7/8"(48mm)
5-1/2"(140mm)
BOWL DEPTH
CRITICAL DIMENSIONS
(DO NOT SCALE)
Rev. 11/11
FOR MORE INFORMATION CALL: 1-800-BUY-MOEN
www.moen.com
_____________________________________
KITCHEN SINK FAUCET
Z871C4
TAG _______
®
Engineering Specifications: Zurn AquaSpec Z871C4
Polished chrome-plated 8" [203mm] brass deck faucet with an 8"
[203mm] centerline rigid or swing gooseneck spout and quarter turn
ceramic disc cartridges. Unit is furnished with a 2.2 GPM [8.3 L]
pressure compensating aerator (complying with ANSI A112.18.1
Standard for flow), 4" [102mm] vandal-resistant color-coded metal wrist
blade handles, mounting hardware and 1/2" NPSM coupling nuts for
standard lavatory risers.
Note: All dimensions are for reference only. Do not use for pre-plumbing
OPTIONAL ACCESSORIES
Suffix
__ -FC
__ -HCT
__ -HS
__ -PT
__ -2F
__ -3F
__ -4F
__ -7F
__ -16F
__ -17F
__ -18F
Description
2.0 GPM [7.6L] Laminar Flow Control in Base of Spout
Hot/Cold Text Indexes
Hose and Spray
1-1/4” [32mm] Cast Brass P-Trap with a 7-1/2” [191mm] Long 17-Gauge Wall Bend
2.2 GPM [8.3 L] Vandal-Resistant Pressure Compensating Female Aerator
0.5 GPM [1.9 L] Vandal-Resistant Pressure Compensating Female Aerator
2.2 GPM [8.3 L] Vandal-Resistant Pressure Compensating Female Laminar Flow
1.0 GPM [3.8 L] Pressure Compensating Female Spray Outlet
1.0 GPM [3.8 L] Vandal-Resistant Pressure Compensating Female Spray Outlet
1.5 GPM [5.7 L] Vandal-Resistant Pressure Compensating Female Aerator
1.5 GPM [5.7 L] Vandal-Resistant Pressure Compensating Female Laminar Flow
ZURN INDUSTRIES, INC. ♦ COMMERCIAL BRASS OPERATION ♦ 2640 SOUTH WORK STREET ♦ FALCONER NY 14733
Phone: 1-716-665-1132 ♦ Fax: 1-716-665-1135 ♦ World Wide Web: www.zurn.com
In Canada: ZURN INDUSTRIES LIMITED ♦ 3544 Nashua Drive ♦ Mississauga, Ontario L4V1L2 ♦ Phone: 905/405-8272 Fax: 905/405-1292
AquaSpec® is a registered trademark of Zurn Industries, Inc.
©2006 Zurn Industries, Inc.
Rev. H
Date: 7/21/06
Dwg. No. 60540
C.N. No. 104674
Product No. Z871C4
Celebrity® Classroom Sink and Sink Packages
ModelsCDKR2517, CDKAD2517, and
CDKRC2517Series
®
SP E C I F I C AT I O N S
GENERAL
Good quality sink formed of #20 gauge, type 304 (18-8) nickel
bearing stainless steel.Top Mount.
DESIGN FEATURES
Sink Bowl Depth: 6-7/8"(175mm) (CDKR2517series), 6-1/2"(165mm)
(CDKAD251765 series).
Coved Corners: 3"(76mm) vertical and 2-1/4"(57mm) horizontal radius.
Bowl and Faucet Deck Recess: 3/16"(5mm) below outside edge of
sink.
Finish: Exposed surfaces are polished to a highlighted
Celebrity bright finish.
Underside: Fully undercoated to dampen sound and reduce
condensation.
Model CDKAD251765
OTHER
Drain Opening: 3-1/2"(89mm).
Select faucet and bubbler holes are slotted to allow for
vandal-resistant faucet and bubbler. See side 2 for illustration.
NOTE: Unless otherwise specified, sink is furnished with 2
faucet holes as illustrated.
Package model numbers include all components shipped in
a single carton. VRC suffix represents packages that have
vandal-resistant components.
Sink complies with ASME A112.19.3/ CSA B45.4
Sinks are listed by IAPMO as meeting the applicable
requirements of the Uniform Plumbing Code , International
Plumbing Code , and National Plumbing Code of Canada.
C
LKD208513LC
SINK DIMENSIONS (INCHES)*
Model
Number
Inside Bowl
Overall
L
W
L
W
D
No. of
Faucet
Holes
Minimum
Cabinet
Size
†
CDKR2517
14
67⁄8
163⁄8
25
17
153⁄4
243⁄8
(635mm) (431mm) (400mm) (356mm) (175mm) (619mm)(416mm) 2, 2LM or 4
30
CDKAD251765
25
17
153⁄4
14
243⁄8
163⁄8
6 1⁄ 2
(635mm) (431mm) (400mm) (356mm) (165mm) (619mm)(416mm) 2, 2LM or 4
30
*Length is left to right. Width is front to back.
Sink
Model Number
17"
(432mm)
14"
(356mm)
3" R
(76mm)
PACKAGE DETAILS
Package
Model Number
LKJ35
LKVR18
Cutout in
Countertop
(1-1/2"Radius
Corners)
L
W
LK1141A
LK35
Faucet
Model Number
Bubbler
Model Number
Drain
Model Number
CDKAD2517C
CDKAD2517652
LKD208513LC
LK1141A
LK35
CDKAD2517VRC
CDKAD2517652
LKDVR208513LC
LKVR1141A
LKVR18
CDKR2517C
CDKR25172
LKD208513LC
LK1141A
LK35
CDKR2517VRC
CDKR25172
LKDVR208513LC
LKVR1141A
LKVR18
CDKRC2517C
CDKR25172
LKD20858C
LK1141A
LKJ35
CDKRC2517VRC
CDKR25172
LKD20858LC
LKVR1141A
LKVR18
THIS PRODUCT, AS CONSTRUCTED IS SUBJECT TO
INTERPRETATION OF A.D.A. REQUIREMENTES. THE
UNOBSTRUCTED KNEE SPACE REQUIRED TO SATISY
A.D.A. STANDARDS MAY NOT BE DESIRABLE.
15-3/4"
(400mm)
25"
(635mm)
6-7/8"
(175mm)
2-1/4" R
(57mm)
Model CDKR2517 Illustrated
6-1/2"
(165mm)
2-1/4" R
(57mm)
Model CDKAD251765 Illustrated
In keeping with our policy of continuing product improvement, Elkay reserves the right to change
product specifications without notice. Please visit elkay.com for the most current version of Elkay
product specification sheets.
Elkay
elkay.com
This specification describes an Elkay product with design, quality, and functional benefits to the
user. When making a comparison of others producers offerings, be certain these featrues are
not overlooked.
2222 Camden Court
Oak Brook, IL 60523
© 2014 Elkay
(Rev. 04/14) 1-8H
Celebrity® Classroom Sink and Sink Packages
ModelsCDKR2517, CDKAD2517, and
CDKRC2517Series
®
SP E C I F I C AT I O N S
HOLE DRILLING CONFIGURATIONS
2 HOLE CONFIGURATION
2 LM (LEFT MIDDLE) HOLE CONFIGURATION
2-1/4"
(57mm)
2-1/4"
(57mm)
3"
(76mm)
8-1/2"
(216mm)
3"
(76mm)
SLOTTED
HOLE
(2 PLACES)
3"
(76mm)
2-1/4"
(57mm)
SLOTTED
HOLE
(1 PLACE)
MODELS CDKR25172LM
CDKAD2517652LM
MODELS CDKR25172
CDKAD2517652
4 HOLE CONFIGURATION
2-1/4"
(57mm)
4"
(102mm)
4"
(102mm)
4-1/2"
(114mm)
14"
(356mm)
SLOTTED
HOLE
(1 PLACE)
2-1/4"
(57mm)
MODELS CDKR25174
CDKAD2517654
Slotted Hole Detail
1-1/2”
(38mm)
In keeping with our policy of continuing product improvement, Elkay reserves the right to change
product specifications without notice. Please visit elkay.com for the most current version of Elkay
product specification sheets.
Elkay
elkay.com
1-1/8
(29mm)
DIA.
This specification describes an Elkay product with design, quality, and functional benefits to the
user. When making a comparison of others producers offerings, be certain these featrues are
not overlooked.
2222 Camden Court
Oak Brook, IL 60523
© 2014 Elkay
(Rev. 04/14) 1-8H
M-500
PRESSURE DROP ACTIVATED
TRAP SEAL PRIMER
Internet address: www.mifab.com
Toll Free: 1-800-465-2736
Canada Toll Free: 1-800-387-3880
SPECIFICATION: MIFAB model MR-500 pressure drop activated brass trap
seal primer, with inlet opening of 1/2” (13) male N.P.T. and outlet opening of
female 1/2” (13) N.P.T. Complete with four view holes and removable filter
screen. Serves up to 6 floor drain traps and requires no adjustments and no air
pre-charge.
®
Plumbing and Drainage
Mechanical Section
REMOVABLE
FILTER SCREEN
SPECIFICATION: MIFAB® model M1-500 pressure drop activated brass trap
seal primer, with inlet opening of 1/2” (13) male N.P.T. and outlet opening of
female 1/2” (13) N.P.T. Complete with four view holes and removable filter
screen. Serves up to 10 floor drain traps and requires no adjustments and no
air pre-charge.
B
A
SPECIFICATION: MIFAB® model M2-500 pressure drop activated brass trap
seal primer, with inlet opening of 1/2” (13) male N.P.T. and outlet opening of
female 1/2” (13) N.P.T. Complete with four view holes and removable filter
screen. Serves up to 3 floor drain traps and requires no adjustments and no air
pre-charge.
MODEL
NO.
C
MR-500
M1-500
M2-500
A
B
C
D
E
IN
IN
IN
IN
IN
4 1/8” (105) 3 1/4” (82)
4 1/8” (105) 3 1/4” (82)
4 1/8” (105) 3 1/4” (82)
7/8” (22)
7/8” (22)
7/8” (22)
NUMBER
OF DRAINS
SERVED
1 1/4” (32) 1 1/8” (29)
1 1/4” (32) 1 1/8” (29)
1 1/4” (32) 1 1/8” (29)
6
10
3
E
D
FUNCTION AND DESCRIPTION: MIFAB's M-500 Series of pressure activated trap seal primers (MR-500, M1-500 and M2500) can be connected to any cold water line, and will be automatically activated when a valve or faucet, that is on the line,
is opened. A pressure drop of three p.s.i. will activate all of the trap seal primers. MIFAB's M-500 Series of trap seal primers
can be disassembled in the field. Their unique design permits filter replacement without affecting the performance of the
primer. The ''O'' ring seals are tested for reliability at a temperature range of -40 degrees to 450 degrees F. The M-500 Series
of trap seal primers do not require adjustment. The operating range for all of MIFAB's M-500 Series of trap seal primers is 20
to 125 p.s.i. All three models are listed with I.A.P.M.O. and C.S.A. and are tested and certified to the A.S.S.E. Standard 1018
and are so marked. U.S. Patent # 6,152,164.
(Dimension) Denotes Millimetres
MIFAB’s factory is cer tified to the ISO 9001-94 Design and Manufacturing Standard. Design and dimensions are subject to modification.
Page P1
C
INSTALLATION INSTRUCTIONS
FOR M-500 TRAP SEAL PRIMERS
Internet address: www.mifab.com
Toll Free: 1-800-465-2736
Canada Toll Free: 1-800-387-3880
INSTALLATION INSTRUCTIONS: An 1 1/8'' open end wrench should be used to install the M-500 Series of trap seal primers to the line by
using the flats on the top of the trap seal primer. Water lines must be flushed before installing MIFAB's M-500 Series of trap seal primers. The
trap seal primers should be cycled at least six times to ensure optimum performance. Ensure that all flux and other debris is removed. Use
only teflon tape around threads. Do not use pipe dope. Do not solder fittings directly onto the inlet or outlet of the primer. Failure to follow
these instructions will negatively affect performance of the product. MIFAB’s primers have a unique design which allows the primer to be taken
apart and cleaned before re-assembly. Do this in the event of excess water discharge. Do not install the trap seal primers closer than forty feet
apart when using the same potable water supply line. The device should be located within 20’ of the valve or faucet for optimal discharge. Trap
seal primers should be mounted one foot above the finished floor for every twenty feet of floor drain trap make-up water line. For easy access
to the trap seal primer, install a union connection above it. Install a line shut off valve upstream of the trap seal primer in order to shut off the
water supply when performing maintenance on the trap seal primer.
Plumbing and Drainage
Mechanical Section
INSPECTION INSTRUCTIONS: After installing and pre-cycling the trap seal primer, use any of the four holes to view water discharge from
the orifice. A light can be placed opposite the observed view hole to improve clarity in this inspection.
MAINTENANCE INSTRUCTIONS: In order to replace the filter screen, remove the trap seal primer by using an open end wrench on the top
set of flats. Grasp the top of the filter screen with fingers, squeeze and remove the filter. Insert the new filter screen by squeezing and pushing
it firmly down into the top of the trap seal primer. Re-install the trap seal primer using the top set of flats. In regions that experience heavy
residual deposits such as calcium in the water supply, MIFAB's M-500 Series of trap seal primers can be field refurbished by removing the
bottom end of the primer, and replacing the cartridge.
LINE SHUT OFF
VALVE
FILTER
SCREEN
AVOID DIRECT INSTALLATION
TO PREVENT FOREIGN
MATERIAL FROM ENTERING
DIRECTLY INTO PRIMER
UNION
CONNECTION
TRAP PRIMER
VALVE
MI-GAP
AIR GAP FITTING
FOUR VIEW
HOLES
TRAP PRIMER VALVE
SHOULD BE MOUNTED
ONE FOOT ABOVE THE
FINISHED FLOOR FOR
EVERY 20 FEET OF
PRIMER LINE.
WATER TRAP
SEWER GAS
(Dimension) Denotes Millimetres
MIFAB’s factory is cer tified to the ISO 9001-94 Design and Manufacturing Standard. Design and dimensions are subject to modification.
Page P2
C
MANUAL FloWise®
EXPOSED TOILET FLUSH VALVE
1.1 GPF
MODEL NUMBER:
❑ 6047.111.002 Flush Valve for 11-1/2" Supply C\L to top of bowl, 1.1 gpf
NOTICE:
To ensure proper performance, this 1.1 gpf (4.2 Lpf)
Toilet Flush Valve must be installed on a flushometer bowl that is certified (per ASME A112.19.2/CSA
B45.1) to operate at 1.1 gpf (4.2 Lpf).
OPERATING PRESSURE:
Overall Range: 20-125 psi**
Recommended: 25 psi (flowing)-80 psi (static)
** Water pressure over 80 psi is not recommended
for most plumbing fixtures.
FLOW REQUIREMENT:
25gpm (94.6 L/min.)
GENERAL DESCRIPTION:
Manual Piston-Type Water Closet Flush Valve for
floor-mounted or wall-hung 1-1/2" top spud bowls.
MaP* Score
• 1,000 grams of miso @ 1.1 gpf (when used with
an American Standard Afwall Millenium or Madera
universal flushometer bowl)
INCLUDES:
• 1" I.P.S. angle stop with back-flow prevention and
vandal-resistant cap
• Sweat solder kit including cover tube and wall flange
• High back pressure vacuum breaker with down tube
• Spud coupling & flange for 1-1/2” top spud
PRODUCT FEATURES:
• Self-cleaning brass piston with integral wiper spring
prevents clogging and reduces maintenance
• Piston operation delivers superior flush accuracy and
repeatability
• Piston valve remains closed and does not need to be
reset after loss of water pressure
• Non-hold open handle provides automatic shut-off
after every flush
• Fail-Safe Operation: Valve automatically closes and
does not need to be reset, on loss of water pressure
• Positive seal ensures leak-free performance
• No external volume adjustment
• Durable chrome-plated cast brass construction
is ideal for commercial applications
• Chemical-resistant EPDM seals for long life
• Adjustable tailpiece for rough-in flexibility
*Maximum Performance (MaP) testing performed by IAPMO R&T Lab.
MaP Report conducted by Veritec Consulting, Inc. and Koeller and
Company.
TYPICAL WATER CLOSET INSTALLATION:
AFWALL™ TOILET SHOWN
FINISHED WALL
73mm
(2-7/8")
343mm
(13-1/2")
295mm
(11-1/2")
-C-L-
SUPPLY
DN 25mm
(1" I.P.S.)
CRITICAL
LEVEL
121mm, +/-13mm
(4-3/4")(+/-1/2")
SEE ROUGH-IN
ON BACK
FINISHED
FLOOR
RECOMMENDED SPECIFICATION:
Manual toilet flush valve shall feature self-cleaning brass piston valve with integral wiper spring in refill orifice to prevent clogging. Valve
remains closed and does not need to be reset after loss of water pressure. Includes cast brass valve body and cover with chrome finish and
vandal resistant stop cap. Includes sweat solder kit with wall flange and cover tube. High back pressure vacuum breaker and angle stop with back-flow
protection and vacuum breaker included. 1.1 gpf / 4.2 Lpf Flush valve shall be American Standard Model # 6047.111.002.
© 2014 AS America Inc.
L221
Revised
MANUAL FloWise®
EXPOSED TOILET FLUSH VALVE
1.1 GPF
FINISHED WALL
Roughing-in Dimensions
38mm-127mm
(1-1/2"-5")
SUPPLY
DN 25mm
(1" I.P.S.)
108mm-133mm
(4-1/4" to 5-1/4")
6047.122
ROUGH-IN
DIMENSION
687mm
(27")
-C-L-
*CRITICAL
LEVEL
6047.122
735mm
(29")
6047.121
ROUGH-IN
DIMENSION
295mm
(11-1/2")
6047.121
343mm
(13-1/2")
FOR 1-1/2" TOP
SPUD FIXTURES
*Note: The Critical Line (-C-L-) on Vacuum Breaker
must typically be a minimum of 6 " (152mm) above
fixture. Consult Codes for details.
Left or Right Hand Installation
MEETS THE AMERICANS WITH DISABILITIES ACT GUIDELINES
AND ANSI A117.1 REQUIREMENTS FOR ACCESSIBLE AND
USABLE BUILDING FACILITIES-CHECK LOCAL CODES
© 2014 AS America Inc.
L222
Revised
Z5675-BWL
TAG
HET Children’s Floor Mounted
EcoVantage® Flush Valve Toilet
Z5675 HET Series
• Zurn High Efficiency Toilets and paired performance flush
valve systems are designed to exceed industry standards,
while using as little as 1.1 gallons of water per flush.
• Universal high efficiency toilet can be specified with 1.28
gpf [4.8 lpf], 1.6 gpf [6.0 lpf] or dual flush valves.
• Vitreous china
• Elongated front rim
• 2" fully glazed trapway
• High efficiency siphon jet flush action
• Zurn product system component compatibility and
quality assurance
• Shipping Weight: 42 lbs
Z5675 Series
Recommended Trim:
 Z5959SS-JUV White, open front juvenile toilet
seat less cover with stainless steel check
hinge.
 Z5972-COMB Closet bolt/wax ring kit
Engineering Specification:
Recommended Trim:
 Z5675-BWL
Vitreous china, 1.1 gpf [4.16 lpf] or greater high
efficiency, floor mounted, children’s toilet with
siphon jet flushing action, 10” high elongated front
rim, with 1-1/2” top spud. This bowl is designed to
perform to industry standards with as little as 1.1
gallons per flush, engineered to provide optimal
performance.
Note: To ensure system performance:
Minimum Running Water Pressure = 25 psi.
These dimensions and specifications are subject to change without
notice.
Fixture dimensions meet ANSI/ASME standard A112.19.2 and CAN/
CSA B45 requirements.
Architectural/Engineering Approval
ZURN INDUSTRIES, LLC. ♦ COMMERCIAL BRASS OPERATION
5900 ELWIN BUCHANAN DRIVE ♦ SANFORD NC 27330
Phone: 1-800-997-3876 ♦ Fax: 919-775-3541
www.zurn.com
In Canada: ZURN INDUSTRIES LIMITED
3544 Nashua Drive ♦ Mississauga, Ontario L4V1L2
Phone: 905-405-8272 Fax: 905-405-1292
EcoVantage® is a registered trademark of Zurn Industries, LLC.
See Zurn One Systems for suggested packages.
The information contained in this document is subject to change without notice.
Please contact Zurn for most up to date information.
Rev. A
Dwg. No. 84389
Date: 5/31/12
Product No. Z5675-BWL
Z5675-BWL
TAG
HET Children’s Floor Mounted
EcoVantage® Flush Valve Toilet
Rough-in dimensions for Z5675 Series
1 [64]
22
1 [394]
152
1 [140] 131 [343]
52
2
25 [635]
43
4 [121]
FINISHED WALL
1 [25]
I.P.S. SUPPLY
7 [87]
316
1 [292]
112
5 [127]
10 [254]
7 [181]
10 [254]
C/L OUTLET
FINISHED FLOOR
These dimensions and specifications are subject to change without
notice.
Fixture dimensions meet ANSI/ASME standard A112.19.2 and CAN/
CSA B45 requirements.
ZURN INDUSTRIES, LLC. ♦ COMMERCIAL BRASS OPERATION
5900 ELWIN BUCHANAN DRIVE ♦ SANFORD NC 27330
Phone: 1-800-997-3876 ♦ Fax: 919-775-3541
www.zurn.com
In Canada: ZURN INDUSTRIES LIMITED
3544 Nashua Drive ♦ Mississauga, Ontario L4V1L2
Phone: 905-405-8272 Fax: 905-405-1292
EcoVantage® is a registered trademark of Zurn Industries, LLC.
MANUAL FloWise®
EXPOSED TOILET FLUSH VALVE
1.1 GPF
MODEL NUMBER:
❑ 6047.111.002 Flush Valve for 11-1/2" Supply C\L to top of bowl, 1.1 gpf
NOTICE:
To ensure proper performance, this 1.1 gpf (4.2 Lpf)
Toilet Flush Valve must be installed on a flushometer bowl that is certified (per ASME A112.19.2/CSA
B45.1) to operate at 1.1 gpf (4.2 Lpf).
OPERATING PRESSURE:
Overall Range: 20-125 psi**
Recommended: 25 psi (flowing)-80 psi (static)
** Water pressure over 80 psi is not recommended
for most plumbing fixtures.
FLOW REQUIREMENT:
25gpm (94.6 L/min.)
GENERAL DESCRIPTION:
Manual Piston-Type Water Closet Flush Valve for
floor-mounted or wall-hung 1-1/2" top spud bowls.
MaP* Score
• 1,000 grams of miso @ 1.1 gpf (when used with
an American Standard Afwall Millenium or Madera
universal flushometer bowl)
INCLUDES:
• 1" I.P.S. angle stop with back-flow prevention and
vandal-resistant cap
• Sweat solder kit including cover tube and wall flange
• High back pressure vacuum breaker with down tube
• Spud coupling & flange for 1-1/2” top spud
PRODUCT FEATURES:
• Self-cleaning brass piston with integral wiper spring
prevents clogging and reduces maintenance
• Piston operation delivers superior flush accuracy and
repeatability
• Piston valve remains closed and does not need to be
reset after loss of water pressure
• Non-hold open handle provides automatic shut-off
after every flush
• Fail-Safe Operation: Valve automatically closes and
does not need to be reset, on loss of water pressure
• Positive seal ensures leak-free performance
• No external volume adjustment
• Durable chrome-plated cast brass construction
is ideal for commercial applications
• Chemical-resistant EPDM seals for long life
• Adjustable tailpiece for rough-in flexibility
*Maximum Performance (MaP) testing performed by IAPMO R&T Lab.
MaP Report conducted by Veritec Consulting, Inc. and Koeller and
Company.
TYPICAL WATER CLOSET INSTALLATION:
AFWALL™ TOILET SHOWN
FINISHED WALL
73mm
(2-7/8")
343mm
(13-1/2")
295mm
(11-1/2")
-C-L-
SUPPLY
DN 25mm
(1" I.P.S.)
CRITICAL
LEVEL
121mm, +/-13mm
(4-3/4")(+/-1/2")
SEE ROUGH-IN
ON BACK
FINISHED
FLOOR
RECOMMENDED SPECIFICATION:
Manual toilet flush valve shall feature self-cleaning brass piston valve with integral wiper spring in refill orifice to prevent clogging. Valve
remains closed and does not need to be reset after loss of water pressure. Includes cast brass valve body and cover with chrome finish and
vandal resistant stop cap. Includes sweat solder kit with wall flange and cover tube. High back pressure vacuum breaker and angle stop with back-flow
protection and vacuum breaker included. 1.1 gpf / 4.2 Lpf Flush valve shall be American Standard Model # 6047.111.002.
© 2014 AS America Inc.
L221
Revised
MANUAL FloWise®
EXPOSED TOILET FLUSH VALVE
1.1 GPF
FINISHED WALL
Roughing-in Dimensions
38mm-127mm
(1-1/2"-5")
SUPPLY
DN 25mm
(1" I.P.S.)
108mm-133mm
(4-1/4" to 5-1/4")
6047.122
ROUGH-IN
DIMENSION
687mm
(27")
-C-L-
*CRITICAL
LEVEL
6047.122
735mm
(29")
6047.121
ROUGH-IN
DIMENSION
295mm
(11-1/2")
6047.121
343mm
(13-1/2")
FOR 1-1/2" TOP
SPUD FIXTURES
*Note: The Critical Line (-C-L-) on Vacuum Breaker
must typically be a minimum of 6 " (152mm) above
fixture. Consult Codes for details.
Left or Right Hand Installation
MEETS THE AMERICANS WITH DISABILITIES ACT GUIDELINES
AND ANSI A117.1 REQUIREMENTS FOR ACCESSIBLE AND
USABLE BUILDING FACILITIES-CHECK LOCAL CODES
© 2014 AS America Inc.
L222
Revised
MADERA™ FloWise® 15" HEIGHT
1.1 GPF FLUSHOMETER TOILET SYSTEM
with EVERCLEAN®
MANUAL FLUSH VALVE
MADERA™ FloWise® 15" HEIGHT 1.1 GPF
FlushOmeter toilet system with EVERCLEAN®
❏2855.111 1.1 gpf 15" Height Top Spud Bowl and
Manual Flush Valve
BOWL:
• Floor mount elongated flushometer valve toilet
• Vitreous china
• High Efficiency. Operates in the range of 1.1 gpf to
1.6 gpf (4.2 Lpf to 6.0 Lpf)
• Permanent EverClean® anti-microbial surface inhibits
the growth of stain- and odor-causing bacteria, mold,
and mildew on the surface
• Fully glazed 2-1/8" trapway
• 10" or 12" roughing-in
• 15" rim height
• Condensation channel
• Powerful direct-fed siphon jet action
• 10" x 12" water surface area
• 1-1/2" inlet spud
• 100% factory flush tested
• Less toilet seat
• Model 3451.001
MANUAL FLUSH VALVE:
• Self-cleaning brass piston with integral wiper spring
prevents clogging and reduces maintenance
• Piston operation delivers superior flush accuracy
and repeatability
• Piston valve remains closed and does not need
to be reset after loss of water pressure
• ADA compliant non-hold open handle provides
automatic shut-off after every flush
• Positive seal ensures leak-free performance
• No external volume adjustment
• Durable chrome-plated cast brass construction
is ideal for commercial applications
• Chloramine-resistant EPDM seals
• Adjustable tailpiece for rough-in flexibility
• Can be installed left or right hand
• Model 6047.111
Includes:
• 047007-0070A Inlet Spud (furnished with bowl)
• 481310-100 2 Bolt caps with retainers
(furnished with bowl)
• 1" I.P.S. angle stop with back-flow prevention and
vandal-resistant cap
• Sweat solder kit including cover tube and wall flange
• High back pressure vacuum breaker with down tube
• Spud coupling & flange for 1-1/2” top spud
SEE REVERSE FOR ROUGHING-IN DIMENSIONS
High-Efficiency Toilet Systems:
• 31.3% water savings when compared to a 1.6 gpf
toilet system
System MaP* Score:
• 1,000 grams of miso @ 1.1 gpf
* Maximum Performance (MaP) testing performed by
IAPMO R&T Lab. MaP Report conducted by Veritec
Consulting, Inc. and Koeller and Company.
Operating Pressure:
Overall Range: 20-125 psi**
Recommended: 25 psi (flowing)-80 psi (static)
** Water pressure over 80 psi is not recommended
for most plumbing fixtures.
Flow Requirement:
25gpm (94.6 L/min.)
Nominal Fixture Dimensions:
718 x 356 x 381mm (28-1/4" x 14" x 15")
To Be Specified:
❏ Color: ❏ White
❏ Seat:
❏ American Standard #5901.100
Heavy duty open front less cover
❏ American Standard #5905.100
Extra heavy duty open front less cover
© 2014 AS America Inc.
N33
6/14
MADERA™ FloWise® 15" HEIGHT
1.1 GPF FLUSHOMETER TOILET SYSTEM
with EVERCLEAN®
MANUAL FLUSH VALVE
FINISHED WALL
356mm
(14 " )
718mm
(28-1/4 " )
102mm
(4")
SUPPLY
DN 25mm
(1" I.P.S.)
343mm
(13-1/2")
108 -133mm
(4-1/4" to 5-1/4")
292mm
(11-1/2")
-C-L-
470mm
(18-1/2 " )
25mm
(1")
*CRITICAL
LEVEL
C/L OF SEAT POST HOLES
140mm (5-1/2 " ) CENTERS
724mm
(28-1/2 " )
381mm
(15 " )
FINISHED
FLOOR
13mm
(1/2 " )
254mm
(10 " )
150mm
(5-7/8")
338mm
(13-5/16 " )
238mm
(9-3/8 " )
*Note: The Critical Line (-C-L-) on Vacuum Breaker
must typically be a minimum of 6" (152mm) above
fixture. Consult Codes for details.
C/L OF OUTLET
Valve Left or Right Hand Installation
Fixture Compliance Certifications Meets or Exceeds the Following Specifications:
• ASME A112.19.2-2008 / CSA B45.1-08 for
Vitreous China Fixtures
Valve Listings:
• ASSE 1037
• ANSI/ASME A112.19.2
• ADA Compliant
© 2014 AS America Inc.
NOTES:
TO COMPLY WITH AREA CODE GOVERNING THE HEIGHT OF VACUUM
BREAKER ON THE FLUSHOMETER VALVE, THE PLUMBER MUST
VERIFY DIMENSIONS SHOWN FOR SUPPLY ROUGHING.
THIS TOILET DESIGNED TO ROUGH-IN AT A MINIMUM DIMENSION
OF 254MM (10") AND A MAXIMUM DIMENSION OF 305MM (12") FROM
FINISHED WALL TO C/L OF OUTLET.
IMPORTANT: Dimensions of fixtures are nominal and may vary within
the range of tolerances established by ANSI Standard A112.19.2. These
measurements are subject to change or cancellation. No responsibility is
assumed for use of superseded or voided pages.
N34
6/14
®
PISTON OPERATED
WATER HAMMER ARRESTOR
MWH
Specification: MIFAB® MWH Series (specify size) piston operated water hammer arrestor with hard drawn seamless “K” copper
body, RYTON PPS piston with double o-rings (Parco # 5778-80) and CDA 360 brass M.P.T. connection. Certified to the A.S.S.E.
1010-1996 and ANSI A112.26.1M Standards. Engineered to limit the system surge pressure up to 1,500 P.S.I.G.
Functions: Used in commercial, institutional and residential applications on water supply lines to reduce water hammer caused
by the quick opening and closing of valves within the piping system. To be installed as close as possible to quick closing valves.
The resulting hydraulic shock waves can lead to broken pipes and affect valves in appliances if not reduced with the use of a water
hammer arrestor. An access door is not required to provide access to MIFAB’s water hammer arrestors.
®
MIFAB® HAMMERGARD Series Features
SEAMLESS COPPER BODY. Hard
drawn seamless “K” copper body
ensures maximum integrity and
guarantees free movement of the piston
for maximum performance
Plumbing and Drainage
Mechanical Section
B
DRAWN SEAMLESS
“K” COPPER BODY
WITH FACTORY
AIR CHARGE
A
RYTON PPS piston. Assembled with
two Parco # 5778-80 o-rings and
lubricated with Dow Corning # 111 FDA
approved silicone compound. Ribbed
piston design reduces secondary shock
and flared piston skirt prevents hard
particles suspended in the water supply
from contacting the o-rings to provide
increased product life and performance.
LARGE AIR CHAMBER VOLUME.
Provides better dampening for superior
water hammer arrestor performance.
TEMPERATURE RANGE. Maximum
working temperature is 250F
OPERATING PRESSURE. Up to 350
P.S.I.G. for effective and safe operation.
Patent # 6,539,976
LEAD FREE
SOLDER JOINT
F
MODEL
NO.
SIZE
TYPE
MWH-A
MWH-B
MWH-C
MWH-D
MWH-E
MWH-F
A
B
C
D
E
F
M.P.T. BRASS
CONNECTION
FIXTURE UNIT
CAPACITY
1-11
12-30
31-60
61-113
114-154
155-330
Job Name:
Section No:
Schedule No:
A
(LENGTH)
B
(DIAMETER)
F
M.P.T. CONN.
6"
7 1/2"
9"
10 1/2"
11 1/4"
13"
1 1/8"
1 1/8"
1 3/8"
1 5/8"
2 1/8"
2 5/8"
1/2"
3/4"
1"
1 1/4"
1 1/2"
2"
Page No:
Contractor:
Purchase Order No:
MIFAB reserves the right to make changes in material and design without formal notice and obligation.
Page W3
USA: 1-800-465-2736 www.mifab.com CAN: 1-800-387-3880
C
Technical Data
ClassicSeries™
surface-MOUNTED
SEAT-COVER DISPENSER
B-221
15-3/4''
400mm
3-1/2''
Finish Face of Wall
8-3/4''
220mm
2''
11''
280mm
30'' to 48'' 760 to 1220mm
4-1/2''
115mm
Recommended Mounting Height Off Floor
For Barrier-Free Design
50mm
S
45'' to 59'' 1145 to 1500mm
S
Recommended Mounting Height Off Floor
90mm
MATERIALS:
18-8 S, type-304, 22-gauge (0.8mm) stainless steel with satin finish. All-welded construction with beveled opening.
OPERATION:
Dispenses single- or half-fold paper toilet seat covers from beveled opening. Dispenser fills from bottom through concealed
opening. Capacity: 250 toilet seat covers.
INSTALLATION:
Mount unit on wall or toilet partition with two flat-head screws, not furnished by manufacturer, at points indicated by an S. For
plaster or dry wall construction, provide concealed backing that complies with local building codes, then secure unit with flathead screws not furnished. For other wall surfaces, provide fiber plugs or expansion shields for use with screws, not furnished,
or provide 1/8'' (3mm) toggle bolts or expansion bolts.
Note: Provide a 5'' (125mm) minimum clearance from bottom of dispenser to top of any horizontal projection to provide room
for filling dispenser from bottom.
SPECIFICATION:
Surface-mounted toilet-seat-cover dispenser shall be type-304, 22-gauge (0.8mm) stainless steel with all-welded construction;
exposed surfaces shall have satin finish. Dispenser shall have a concealed opening in bottom for filling. Capacity shall be 250
paper toilet seat covers.
Surface-Mounted Seat-Cover Dispenser shall be Model B-221 of Bobrick Washroom Equipment, Inc., Clifton
Park, New York; Jackson, Tennessee; Los Angeles, California; Bobrick Washroom Equipment Company,
Scarborough, Ontario; Bobrick Washroom Equipment Pty. Ltd., Australia; and Bobrick Washroom Equipment
Limited, United Kingdom.
The illustrations and descriptions herein are applicable to production as of the date of this Technical Data Sheet.
The manufacturer reserves the right to, and does from time to time, make changes and improvements in designs and dimensions.
Revised 8/07
Printed in U.S.A.
© 2007 by Bobrick Washroom Equipment, Inc.
GLASS MIRROR WITH
STAINLESS STEEL
ANGLE FRAME
Technical Data
B-290
SERIES
Designer's Notes:
1. Special-order sizes available on request.
2. Maximum size one-piece angle-frame mirror, 144'' x 72'' (366 x 183cm); minimum size, 12'' x 12'' (30 x 30cm).
Maximum frame size available, 180'' x 72'' (457 x 183cm) with two pieces of glass in one-piece frame. Stainless
steel I-section with polished finish covers seam where two pieces of glass butt together.
3. All Bobrick framed mirrors are manufactured to overall width and height dimensions. EXAMPLE: A 24'' x 36''
(61 x 91cm) mirror will be furnished 24'' x 36'' (61 x 91cm) outside-of-frame to outside-of-frame.
4. To specify special sizes use Series Number followed by width then height in inches. EXAMPLE: B-290 2024.
5. Bobrick framed mirrors are manufactured to a tolerance ± 1/8'' (3.2mm).
6. For sufficient space to lift mirror onto wall hanger(s), provide 3-1/4'' (85mm) minimum clearance above
center line of mounting screw holes.
Snap Locking Design
Lock Tab Design
(Rear View)
(Rear View)
1/2''
1/2''
13mm
2-1/2''
65mm
S
13mm
1/2"
25mm
Mirror Width
Mirror
2-1/2''
65mm
S
4-1/2"
114mm
S
Reinforcement
Wall
S
2-9/16''
S
4'' or 5" Typ.
100 or 125mm
3"
76mm
Bracket
65mm
3"
76mm
S
Wall
Bracket
Frame
Frame
Lock Tab
Slide Key between
Mirror and Wall.
Depress Tab on
back Panel and
remove Mirror.
Side View
Back Plate/Wall Hanger
Mirror
Lock Tab
Mirror
Key
Mirror
Contact factory for key.
S
STANDARD B-290 SERIES2-9/16''
MIRRORS
Figure: 2
Figure: 1
STANDARD B-290 SERIES MIRRORS
65mm
OVERALL SIZE
MODEL
NO.
OVERALL SIZE
MODEL
NO.
W
H
B-290 1830
B-290 1836
B-290 2430
B-290 2436
18'' (46cm) 18'' (46cm) 24'' (61cm) 24'' (61cm) 30'' (76cm)
36'' (91cm)
30'' (76cm)
36'' (91cm))
4'' or 5"B-290
Typ.
2448
B-290 2460
100 or 125mm
B-290 2472
W
H
24'' (61cm) 48'' (122cm)
24'' (61cm) 60'' (152cm)
24'' (61cm) 72'' (183cm))
S
All Other Size Mirrors
Frame
MATERIALS:
Frame — 18-8, heavy-gauge stainless steel, 3/4" x 3/4" (19 x 19mm) angle with satin finish. One-piece, roll-formed
construction forms continuous integral stiffener on all sides. Bevel design on front of angle holds frame tightly against mirror.
Corners of mirror frame are heliarc welded, ground and polish smooth. Galvanized steel back is fastened to frame with
concealed screws and equipped with integral horizontal hanging brackets near the top and bottom of the mirror for hanging
the mirror and to prevent the mirror from pulling away from the wall. Locking devices secure mirror to concealed wall hanger.
Mirror — No. 1 quality, 1/4" (6mm) select float glass (standard glass): selected for silvering, electrolytically copper-plated
by the galvanic process, and guaranteed for 15 years against silver spoilage. All edges protected by plastic filler strips; back is
protected by full-size, shock-absorbing, water-resistant, nonabrasive, 3/16" (5mm) thick polyethylene padding.
Side View
Back Plate/Wall Hanger
Concealed Wall Hanger — Fabricated of galvanized steel. Incorporates lower support member, which engages lower
backplate louvers to keep bottom of mirror against wall.
Mirror
The illustrations and descriptions herein are applicable to production as of the date of this Technical Data Sheet.
The manufacturer reserves the right to, and does from time to time, make changes and improvements in designs and dimensions.
continued . . .
Rev. 3/6/15 R/B
Printed in U.S.A.
© 2015 by Bobrick Washroom Equipment, Inc.
INSTALLATION:
Mount wall hanger on wall with screws (not furnished) at points indicated by an S. For plaster or dry wall construction, provide
backing to comply with local building codes, then secure wall hanger with screws (not furnished). When providing a concealed
backing, allow backing to cover range of mounting hole locations shown on drawing. For other wall surfaces, provide fiber
plugs or expansion shields for use with screws (not furnished), or provide 1/8" (3mm) toggle bolts or expansion bolts. Hang
mirror on wall hanger with all four backplate louvers engaged behind horizontal wall hanger members. To do this, mirror must
be centered in front of the wall hanger horizontally, pressed flat against the wall approximately 1" (25mm) above final position
and then lowered into final position.
Snap Locking Design — Locking devices automatically secure mirror to concealed wall hanger when it is lowered into final
position (see figure 3). Locking devices may be unlocked by inserting two flat blade screwdrivers behind each side of mirror
near the bottom or under the bottom of the mirror and pulling mirror bottom forward and then up.
Lock Tab Design — Locking devisec automatically secure mirri to concealed wall hanger when it is lowered into final
position (see figure 5). Locking device may be unlocked by sliding Key between mirror and wall and depressing tab on back
panel. If key is required, please the factory.
Snap Locking Design
Lock Tab Design
(Front View)
(Front View)
Approx. 1"
(25mm)
CL
Final
Position
S
Approx. 1"
(25mm)
Initial
Position
S
CL
Initial
Position
Final
Position
S
S
Figure: 4
Figure: 5
SPECIFICATION:
Mirror shall have a one-piece, stainless steel angle frame, 3/4" x 3/4" (19 x 19mm) with continuous integral stiffener on all
sides and beveled front to hold frame tightly against mirror; corners shall be heliarc welded, ground, and polished smooth;
all exposed surfaces shall have satin finish. Reflective surfaces shall be guaranteed for 15 years against silver spoilage. All
edges shall be protected by plastic filler strips and the back shall be protected by full-size, shock-absorbing, water-resistant,
nonabrasive, 3/16" (5mm) thick polyethylene padding. Galvanized steel back shall have integral horizontal hanging brackets
located at top and bottom for mounting on concealed wall hanger and to prevent the mirror from pulling away from the wall.
Locking devices secure mirror to concealed wall hanger. Mirror shall be removable from wall hanger for reglazing mirror.
Framed Mirror shall be Model B-290 _______________ (insert width and height) of Bobrick Washroom Equipment,
Inc., Clifton Park, New York; Jackson, Tennessee; Los Angeles, California; Bobrick Washroom Equipment
Company, Scarborough, Ontario; Bobrick Washroom Equipment Pty. Ltd., Australia; and Bobrick Washroom
Equipment Limited, United Kingdom.
The illustrations and descriptions herein are applicable to production as of the date of this Technical Data Sheet.
The manufacturer reserves the right to, and does from time to time, make changes and improvements in designs and dimensions.
B-290 Rev. 3/6/15 R/B
Printed in U.S.A.
© 2015 by Bobrick Washroom Equipment, Inc.
Technical Data
SURFACE-MOUNTED
PAPER TOWEL
DISPENSER
B-2621
Finish Face of Wall
10-13/16"
275mm
3-15/16"
7-1/2"
100mm
S
7-1/8"
180mm
Door
3-1/2"
90mm
S
2"
50mm
47'' 1195mm
Knob Latch
58" to 62" 1475 to 1575mm
S
Recommended Mounting Height Off Floor
For Accessible Design
190mm
Recommended Mounting Height Off Floor
S
MATERIALS:
Cabinet — 18-8, type-304, 22-gauge (0.8mm) stainless steel. All-welded construction. Exposed surfaces have satin finish. Towel
tray has hemmed opening to dispense paper towels without tearing.
Door — 18-8, type-304, 22-gauge (0.8mm) stainless steel with satin finish. Secured to cabinet with a full-length stainless
steel piano-hinge. Equipped with a knob latch.
Optional: Order Bobrick Part No. 262-130 TowelMate® available as on optional accessory. TowelMate accessory allows for
paper towels to dispense one at a time without bulging, sagging or falling through the towel tray opening. TowelMate fits
Gamco and most manufacturers' similar models.
OPERATION:
Unit dispenses C-fold and multifold paper towels 3-1/8" to 3-13/16" (79–97mm) deep. Slots in sides of cabinet indicate refill
time. Capacity: 200 C-fold or 275 multifold paper towels. To dispense narrower towels 2-1/2" to 3-1/8" (64–79mm) deep, order
optional TowelMate accessory Bobrick Part No. 262-130.
INSTALLATION:
Mount unit on wall with four #10 x 1-1/4" (4.8 x 32mm) sheet-metal screws (not furnished) at points indicated by an S. For plaster or dry wall construction, provide concealed backing to comply with local building codes, then secure unit with
sheet-metal screws. For other wall surfaces, provide fiber plugs or expansion shields for use with sheet-metal screws, or provide 1/8" (3mm) toggle bolts or expansion bolts.
SPECIFICATION:
Surface-mounted paper towel dispenser shall be type-304 stainless steel with all-welded construction; exposed surfaces shall
have satin finish. Door shall be secured to cabinet with a full-length stainless steel piano-hinge and equipped with a knob latch.
Paper towel tray shall have hemmed opening to dispense paper towels without tearing. Unit shall be capable of dispensing 200
C-fold or 275 multifold paper towel measuring 3-1/8" to 3-13/16" (79 to 97mm) deep. Narrower paper towels 2-1/2" to 3-1/8"
(65 to 79mm) deep may be efficiently dispensed with the use of an optional TowelMate accessory, Bobrick Part No. 262-130.
TowelMate accessory allows for paper towels to dispense one at a time without bulging, sagging or falling through the towel
tray opening.
Surface-Mounted Paper Towel Dispenser shall be Model B-2621 of Bobrick Washroom Equipment, Inc.,
Clifton Park, New York; Jackson, Tennessee; Los Angeles, California; Bobrick Washroom Equipment Company,
Scarborough, Ontario; Bobrick Washroom Equipment Pty. Ltd., Australia; and Bobrick Washroom Equipment
Limited, United Kingdom.
The illustrations and descriptions herein are applicable to production as of the date of this Technical Data Sheet.
The manufacturer reserves the right to, and does from time to time, make changes and improvements in designs and dimensions.
Rev. 6/30/15 R/B, S/C Printed in U.S.A.
© 2015 by Bobrick Washroom Equipment, Inc.
RECESSED
MULTI-ROLL TOILET
TISSUE DISPENSER
Technical Data
6-1/16''
1-3/8''
35mm
Typ.
S
155mm
Finish Face of Wall
2-15/16''
S
75mm
B-3888
1-3/4''
44mm
11-1/16''
Stainless
Steel Flange
12-1/2''
320mm
280mm
Toilet Tissue
Spindles (2)
Pivot Point
S
S
S
2-3/16''
7-9/16''
28'' 710mm
Stainless
Steel Door
28'' to 36'' 710 to 915mm
6''
150mm
Recommended Mounting Height Off Floor
for Barrier-Free Design
Lock & Key
Recommended Mounting Height Off Floor
Typ. S
55mm
190mm
1/8''
3mm
3''
Rough Wall Opening
6-1/4" (160mm) wide
11-1/4" (290mm) high
3-1/8" (80mm) minimum
recessed depth
76mm
1''
25mm
MATERIALS:
Cabinet — 18-8 S, type-304, 22-gauge (0.8mm) stainless steel. Welded construction. Exposed surfaces have satin finish.
Flange — 18-8 S, type-304, 22-gauge (0.8mm) stainless steel with satin finish. Drawn, one-piece, seamless construction.
Door — 18-8 S, type-304, 22-gauge (0.8mm) stainless steel with 18-gauge (1.2mm) stainless steel door frame. Exposed surfaces have
satin finish. Front of door is drawn, one-piece, seamless construction. Secured to cabinet with two rivets. Equipped with a tumbler lock
keyed like other Bobrick washroom accessories.
Dispensing Mechanism, Inner Housing and Cam — 18-8 S, type-304, 18-gauge (1.2mm) stainless steel.
Spindles (2) — Heavy-duty, one-piece, molded ABS. Theft-resistant, spindles retained in dispensing mechanism when door is locked.
OPERATION:
Unit holds two standard-core toilet tissue rolls up to 5-1/4" (133mm) diameter (1800 sheets). Tissue rolls are loaded and locked into
dispensing mechanism. Extra roll automatically drops in place when bottom roll is depleted. Depleted rolls can only be removed after
unlocking door.
INSTALLATION:
Provide framed rough wall opening 6-1/4" wide x 11-1/4" high (160 x 290mm). Minimum recessed depth required to finish face of
wall is 3-1/8" (80mm). Allow clearance for construction features that may protrude into opening from opposite wall. Coordinate with
mechanical engineer to avoid pipes, vents, and conduits. Mount unit with shims between framing and cabinet at all points indicated by
an S, then secure unit with sheet-metal screws (not furnished).
SPECIFICATION:
Recessed multi-roll toilet tissue dispenser shall be type-304 stainless steel with welded construction, including dispensing mechanism,
inner housing and cam; exposed surfaces shall have satin finish. Front of toilet tissue dispenser door shall be drawn, one-piece,
seamless construction. Door shall be secured to cabinet with two rivets and equipped with a tumbler lock keyed like other Bobrick
washroom accessories. Flange shall be drawn, one-piece, seamless construction. Unit shall dispense two standard-core toilet tissue
rolls up to 5-1/4" (133mm) diameter (1800 sheets). Extra roll shall automatically drop in place when bottom roll is depleted. Unit shall
be equipped with two heavy-duty, one-piece, molded ABS spindles. Theft-resistant, spindles retained in dispensing mechanism when
door is locked.
Recessed Multi-Roll Toilet Tissue Dispenser shall be Model B-3888 of Bobrick Washroom Equipment, Inc., Clifton Park,
New York; Jackson, Tennessee; Los Angeles, California; Bobrick Washroom Equipment Company, Scarborough, Ontario;
Bobrick Washroom Equipment Pty. Ltd., Australia; and Bobrick Washroom Equipment Limited, United Kingdom.
The illustrations and descriptions herein are applicable to production as of the date of this Technical Data Sheet.
The manufacturer reserves the right to, and does from time to time, make changes and improvements in designs and dimensions.
Revised 11/21/12
Printed in U.S.A.
© 2012 by Bobrick Washroom Equipment, Inc.
B-6806
1½" (38mm) DIAMETER
STAINLESS STEEL GRAB
BARS WITH snap flange
Technical Data
Specify Finish Required:
SERIES
 Satin finish
 Satin finish with peened gripping surface; add suffix .99 to model number
Intermediate Flange
End Mounting Flange
2''
2-5/8''
50mm
65mm
3-1/8''
3-1/8''
80mm
80mm
2-1/4''
2-1/4''
55mm
55mm
1-1/2''
38mm
Snap Flange Cover
3-1/4''
3-1/8''
85mm
80mm
Dia.
5/16''
8mm
4''
100mm
36''
50''
915mm
L
1270mm
L
39-7/8''
1005mm
57-7/8''
1470mm
Edge of
Flange to Wall
TWO-WALL WHEELCHAIR
TOILET COMPARTMENT
VERTICAL
HORIZONTAL
B-6806 x 12, 18, 24, 30, 36, 42, 48
4''
100mm
100mm
24''
610mm
32''
B-68137
4''
4''
100mm
Edge of
Flange to Wall
42''
15-7/8''
1065mm
405mm
50''
26-7/8''
815mm
1270mm
685mm
39-7/8''
1015mm
27-7/8''
710mm
Edge of
Flange to Wall
Edge of
Flange to Wall
45-7/8''
19-3/4''
1165mm
500mm
34-3/4''
885mm
Edge of
Flange to Wall
57-7/8''
1470mm
Edge of
Flange to Wall
Edge of
Flange to Wall
Edge of
Flange to Wall
HORIZONTAL TUB / SHOWER / TOILET
COMPARTMENT BAR 24 x 36
HORIZONTAL TWO-WALL BAR
for Shower Stall
TWO-WALL
TOILET COMPARTMENT BAR 42 x 54
B-68616
B-6861
B-6897
continued . . .
The illustrations and descriptions herein are applicable to production as of the date of this Technical Data Sheet.
The manufacturer reserves the right to, and does from time to time, make changes and improvements in designs and dimensions.
Rev. 8/16/13 S/B Printed in U.S.A.
© 2013 by Bobrick Washroom Equipment, Inc.
materials:
Grab Bar — 18-8 S, type-304, 18-gauge (1.2mm) stainless steel tubing with satin-finish. 1-1/2" (38mm) outside diameter. Ends are heliarc welded to flanges.
Clearance between the grab bar and wall is 1-1/2" (38mm).
Concealed Mounting Flanges — 18-8 S, type-304, 1/8" (3mm) thick, stainless steel plate; end flanges 2" x 3-1/8" (50 x 80mm) with two holes for attachment
to wall. Intermediate flanges 2-5/8" x 3-1/8" (65 x 80mm) wide x 3-1/8" (80mm) diameter.
Snap Flange Covers — 18-8 S, type-304, 22-gauge (0.8mm) drawn stainless steel with satin-finish. 3-1/4" (85mm) diameter x 1/2" (13mm) deep. Each cover
snaps over mounting flange to conceal mounting screws.
strength:
Bobrick grab bars that provide 1-1/2" (38mm) clearance from wall can support loads in excess of 900 pounds (408kg) if properly installed. Other grab bar
configurations can support loads in excess of 250 pounds (113kg) if properly installed, complying with accessible design (including ADAAG in the U.S.A.) for
structural strength
Safety Warning: Grab bars are no stronger than the anchors and walls to which they are attached and, therefore, must be firmly secured in order to support the loads for which they are intended. To avoid potential injur y, the building owner or maintenance personnel should remove the grab bar from ser vice if the grab bar is not adequately secured to wall or if there is any obser ved damage to the welds.
installation:
Provide concealed anchor device or backing as specified or required in accordance with local building codes before wall is finished. Fasten concealed
mounting flanges to anchor device or backing with two screws in each flange. Snap flange covers over each mounting flange to conceal mounting screws.
Concealed anchor devices and mounting screws are not included with Bobrick grab bars and must be specified as an accessory.
For Grab Bars with an Intermediate Flange(s), Pull Snap-Flange Covers away from mounting flanges. Place grab bar in desired mounting location. Use
intermediate flange as a template to mark location of mounting screws at intermediate flange only. Mark screw locations at the center of the slot in the middle
of the double-keyhole shaped mounting holes (2) in the intermediate flange. Remove grab bar from wall. Drive the intermediate flange mounting screws into
wall at marked locations. Note: Make sure to leave a space of just over 1/8'' (3.17mm) between the underside of the screw head and the wall. Install grab
bar on the wall by placing the round ends of the intermediate flange double-keyhole shaped mounting holes over the mounting screws (2) are located in the
middle of the flange slots. Install the mounting screws into the wall at the end flanges and secure tightly. Tighten the mounting screws at the intermediate
flange. Press all snap-flange covers into place to conceal mounting flanges.
Note: Recommend use of 1/4'' or #14 sheet metal or wood screws to install Intermediate Flange. #12 screws may also be used.
Important Notes:
1. Mounting Kits — Bobrick offers a mounting kit for installing grab bars; one Bobrick mounting kit is required for each flange.
Mounting Kit No.
252-30
Description
Consists of #14 x 2½'' type-304 stainless steel,
Phillips round-head, sheet-metal screws.
2. Grab Bar Fastener — Bobrick offers a grab bar fastening system that secures all Bobrick grab bar series; one Bobrick fastener is required for each flange. Install grab bar without backing in wall requires minimum 5/8" (16mm) thick painted or tiled drywall.
WingIt™ Fastener No.
251-4
Description
Consists of 10–32 x 5/16'' round-head, Phillips 18/8 stainless steel screws. (1) WingIt grab bar fastener.
3.
Optional Anchor Device — Bobrick grab bar anchor device includes stainless steel machine screws to be used for attaching grab bars to anchors. one Bobrick concealed anchor device is required for each flange.
Optional Anchor No.
Description
2583
Anchor for 3/4" to 1" (19-25mm) panel
1 anchor required for each flange.
2586
Anchor for 1/2" to 1" (13mm) panel
1 anchor required for each flange.
specification:
Grab bar shall be type-304 stainless steel with satin-finish. Grab bar shall have 18-gauge (1.2mm) wall thickness and 1-1/2" (38mm) outside diameter.
Clearance between the grab bar and wall shall be 1-1/2" (38mm). Concealed mounting flanges shall be 1/8" (3mm) thick stainless steel plate, 2" x 3-1/8" (50
x 80mm), and equipped with two screw holes for attachment to wall. Flange covers shall be 22 gauge (0.8mm), 3-1/4" (85mm) diameter x 1/2" (13mm) deep,
and shall snap over mounting flange to conceal mounting screws and/or WingIt fasteners. Ends of grab bar shall pass through concealed mounting flanges
and be heliarc welded to form one structural unit. Grab bar shall comply with accessible design (including ADAAG in the U.S.A.) for structural strength.
Grab Bar shall be Model __________ (insert model number) of Bobrick Washroom Equipment, Inc., Clifton Park, New York; Jackson,
Tennessee; Los Angeles, California; Bobrick Washroom Equipment Company, Scarborough, Ontario; Bobrick Washroom Equipment Pty. Ltd.,
Australia; and Bobrick Washroom Equipment Limited, United Kingdom.
The illustrations and descriptions herein are applicable to production as of the date of this Technical Data Sheet.
The manufacturer reserves the right to, and does from time to time, make changes and improvements in designs and dimensions.
B-6806 Rev. 8/16/13 S/B
Printed in U.S.A.
© 2013 by Bobrick Washroom Equipment, Inc.
RECESSED DUAL-ROLL
TOILET TISSUE DISPENSER
WITH HOODS
Technical Data
B-699
B-6997
(FOR STUD WALLS OR COUNTERTOP APRONS)
Specify Model Required:
… Model B-699
… Model B-6997
Bright polished stainless steel
Satin-finish stainless steel
Finish Face of Wall
12-5/16''
2-3/4''
1-7/8''
315mm
70mm
50mm
Countersunk
Mounting
Holes (4)
6-3/16''
S
3-1/16''
155mm
80mm
Hoods
(2)
Mounting
Clamp
Spindles
11-3/16''
9/16''
285mm
15mm
Typ.
Rough Opening
11-3/4" (300mm) wide
5-1/4" (135mm) high
3-3/8" (86mm) minimum
recessed depth
MATERIALS:
Shell and Flange — 18-8 S, type-304, 22-gauge (0.8mm) stainless steel. Drawn and beveled, one-piece, seamless construction
with four countersunk mounting holes.
Support Posts (4) — Heavy-duty cast zamac with chrome-plated finish.
Hoods (2) — 18-8 S, type-304, 18-gauge (1.2mm) stainless steel. Hoods hinged to shell.
Mounting Bracket — Plated-steel mounting clamp attaches to back of unit with two sheet-metal screws for installation in stud
walls or countertop aprons.
Spindles (2) — Chrome-plated plastic. Equipped with heavy-duty internal springs.
Designer's Note: Theft-resistant toilet tissue spindles, which are removable only with special key provided, are available as an
optional accessory. To specify, add suffix .60 to model number. Example: B-699.60.
INSTALLATION:
Provide framed rough opening 11-3/4" wide x 5-1/4" high (300 x 135mm). Minimum recessed depth required from finish face
of wall or apron is 3-3/8" (86mm).
For installation in stud walls or countertop aprons without backing, loosely attach mounting clamp to back of unit with
mounting screws. Insert into rough opening. Adjust mounting clamp so it grips surface inside rough opening. Secure in place
by tightening four mounting screws.
For installation in stud walls or countertop aprons with backing, discard mounting clamp furnished with unit. Insert unit only
into rough opening and secure with sheet-metal screws furnished. Backing must comply with local building codes.
SPECIFICATION:
Recessed dual-roll toilet tissue dispenser shall be type-304 stainless steel with __________ (insert one: bright polished or satin)
finish. Shell and flange shall be drawn and beveled, one-piece, seamless construction. Unit shall be equipped with 18-gauge
(1.2mm) hoods hinged to shell and furnished with plated-steel mounting clamp for installation in stud walls or countertop
aprons. *Spindles shall be chrome-plated plastic with heavy-duty internal springs. Manufacturer's service and parts manual
shall be provided to the building owner/manager upon request.
*To specify theft-resistant spindles as an optional accessory, add to specification: Theft-resistant toilet tissue spindles shall be
removable only with special key provided.
Recessed Dual-Roll Toilet Tissue Dispenser With Hoods shall be Model __________ (insert model number) of Bobrick
Washroom Equipment, Inc., Clifton Park, New York; Jackson, Tennessee; Los Angeles, California; and Bobrick
Washroom Equipment Company, Scarborough, Ontario; Bobrick Washroom Equipment Pty. Ltd., Australia; and
Bobrick Washroom Equipment Limited, United Kingdom.
The illustrations and descriptions herein are applicable to production as of the date of this Technical Data Sheet.
The manufacturer reserves the right to, and does from time to time, make changes and improvements in designs and dimensions.
Revised 5/06
Printed in U.S.A.
© 2006 by Bobrick Washroom Equipment, Inc.
110-865 | BAYWEST 86500 Hands-Free Dispenser - Silhouette® OptiServ™
Page 1 of 2
Subtotal:
$0.00
0 Items in your cart
You're here : Home
Dispensers - Paper Products
Dispensers - Paper Towel
110-865 - BAYWEST 86500 Hands-Free Dispenser - Silhouette® OptiServ™
Welcome! Sign in
SEARCH
Search Over 10,000 Products!
Roll Towel
Email
Password
Lost Username/Password? or register
PRODUCT CATEGORIES
Clearance Items
Green Products
BAYWEST 86500 Hands-Free Dispenser - Silhouette® OptiServ™
Free Shipping Items
Item #: 110-865 By ( BAYWEST )
New Hot Products
Bags & Can Liners
Product Description
Features & Benefits
Specifications
Request Quote
Chemicals & Janitorial Supply
Dispensers - Paper Products
Dispensers - Paper Towel
C-Fold & Multi-Fold
Center Pull
Roll Towel
Singlefold Towel Dispensers
Dispensers - Skin Care
Facility Maintenance & Safety
Bay West#: 86500
UPC#: 0 85806 86500 8
Description: Controlled Roll Towel Dispenser, fit with 300-61990 and 61990
Color: Black Translucent
Dispenser Size (W" x H" x D"): 11 11/16 x 16 11/16 x 9 7/16
Dispenser Weight 6.6 lbs
Case Size (W" x H" x D"): 16 3/4 x 12 1/4 x 9 9/16
Case Shipping Weight: 8 lbs
Dispenser Case Cube: 1.14
Cases Per Unit: 90
Supply
Floor & Carpet Care
Food Service
Gloves
Item Number: 110-865
ROLL TOWEL DSP NO TOUCH
For roll towel # 333-314
Silhouette® OptiServ™
OptiServ™ Hands-Free Dispenser
Retail Price: $49.99
SmartJan:$29.99
You Save :$20.00 Per Each
Laundry Products
Qty:
Mops, Brooms & Brushes
Odor Control
Shipping Weight per Each : 8.00 lbs
Packaging Supplies
NOTE: The product title and description supersedes the picture shown. The picture provided by the
manufacturer is not always exact.
1
Paper Products
Skin Care & Personal Hygiene
Smallwares & Equipment
Are we missing something
Storage & Material Handling
If you've noticed an error on this page please let us know ...
Waste Receptacles
Windows Glass & Mirrors
Wood Floor Care
MANUFACTURERS LIST
( See all SmartJan products by BAYWEST)
BAYWEST
QUICK ORDER
Qty.
Item #
Qty.
Item #
Qty.
Item #
Qty.
Item #
Qty.
Item #
BAYWEST 31400 Controlled Roll
Towel (6x800) - EcoS
BAYWEST 89500 Lever Dispenser Silhouette® Compa
BAYWEST 87510 OptiServ Hybrid™
Dispenser - Hands
BAYWEST 80010 Electronic Touch
Free Battery - Silh
Retail Price: $71.94
Retail Price: $57.00
Retail Price: $88.00
Retail Price: $69.50
SmartJan:$36.95
You Save :$20.05
SmartJan:$34.99
You Save :$53.01
SmartJan:$44.75
You Save :$24.75
SmartJan:$49.95
You Save :$21.99
Per
Per
Per
Per
CS
EA
EA
EA
BAYWEST 80030 Silhouette® Wave'n Dry® Towel Di
BAYWEST 80040 Silhouette® Wave'n Dry® Towel Di
BAYWEST 89400 Button-Lever
Dispenser - Silhouette�
BAYWEST 86600 Hands-Free
Dispenser - Silhouette®
FIND US ON
http://www.smartjan.com/110-865-baywest-86500-hands-free-dispenser-silhouette-optiserv 11/11/2013
110-865 | BAYWEST 86500 Hands-Free Dispenser - Silhouette® OptiServ™
Retail Price: $59.95
Retail Price: $59.95
Retail Price: $49.90
OnSale:$9.99
You Save :$49.96
OnSale:$9.99
You Save :$49.96
SmartJan:$36.95
You Save :$12.95
Page 2 of 2
Retail Price: $40.00
SmartJan:$24.99
You Save :$15.01
Per
Per
Per
Per
EA
EA
EA
EA
Show More Related Product ....
SmartJan
About Us
Contact Us
Shipping Locations
Top Brands
Help
Payment Methods
Shopping Policy
FAQ`s
Return Policy
We accept Major Credit Cards
Site Info
Terms and Conditions of
Use
Sitemap
Can`t find it
Smart Search
Shipping with
Featured Categories
MSDS
On Sale
Environ Friendly Products
Manuals
Technical Sheets
Transactions Secured By
My Account
View Cart
Shopping List
My Catalog
Order History
Shipping Locations
SSL By Trustwave
Copyright © 2013 SmartJan Co. All Rights Reserved.
Developed by Terawebsite.com
http://www.smartjan.com/110-865-baywest-86500-hands-free-dispenser-silhouette-optiserv 11/11/2013
7/24/13
STOKO® Skin Care - Stoko Refresh® Foam Dispenser white dispenser
Home | Contact Us | MSDS Quick Find | Distributor Resources
Search Stoko Skin Care
Corporate
Markets
Product Catalog
3 Point Program
Videos
Find a Skin Expert
Stoko Products → Dispensers → Stoko Refresh® Foam Dispenser → Stoko Refresh® Foam Dispenser white dispenser
Stoko Refresh® Foam Dispenser white dispenser
E-mail this product to a friend
Small, attractive plastic dispenser perfect for front-end restrooms
New pump with every refill changeout for better hygiene and no clogging
Available in white, black and silver, chrome-look finish
SKU: 30290
Home | Corporate | Markets | Product Catalog | 3 Point Program | Find A Skin Expert | MSDS Quick Find | Distributor Resources | Contact Us | Site Map
Copyright 2010 Stoko Skin Care
Web Design and Development by BEM Interactive
www.stokoskincare.com/p-100-stoko-refresh-foam-dispenser-white-dispenser.aspx
1/1
DN-7111:J • A-13
NFS2-640(E)
Intelligent Addressable
Fire Alarm System
Intelligent Fire Alarm Control Panels
General
The NFS2-640 intelligent Fire Alarm Control Panel is part of
the ONYX® Series of Fire Alarm Controls from NOTIFIER.
In stand-alone or network configurations, ONYX Series products meet virtually every application requirement.
The NFS2-640’s modular design makes system planning easier. The panel can be configured with just a few devices for
small building applications, or networked with many devices to
protect a large campus or a high-rise office block. Simply add
additional peripheral equipment to suit the application.
A host of other options are available, including single- or multichannel voice; firefighter’s telephone; LED, LCD, or PC-based
graphic annunciators; networking; advanced detection products for challenging environments; wireless fire protection; and
many additional options.
NFS2-640-DVC_right.jpg
NOTE: Unless called out with a version-specific “E” at the end of
the part number, “NFS2-640” refers to models NFS2-640 and
NFS2-640E; similarly, “CPU2-640” refers to models CPU2-640
and CPU2-640E.
Features
• Certified for seismic applications when used with the appropriate seismic mounting kit.
• Approved for Marine applications when used with listed
compatible equipment. See DN-60688.
• One, expandable to two, isolated intelligent Signaling Line
Circuit (SLC) Style 4, 6 or 7.
• Wireless fire protection using SWIFT Smart Wireless Integrated Fire Technology. See DN-60820.
• Up to 159 detectors and 159 modules per SLC; 318 devices
per loop/636 per FACP or network node.
– Detectors can be any mix of ion, photo, thermal, or multisensor; wireless detectors are available for use with the
FWSG.
– Modules include addressable pull stations, normally open
contact devices, two-wire smoke detectors, notification, or
relay; wireless modules are available for use with the
FWSG.
• Standard 80-character display, 640-character large display
(NCA-2), or display-less (a node on a network).
• Network options:
– High-speed network for up to 200 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM,
ONYXWorks, NFS-3030, NFS-640, and NCA).
– Standard network for up to 103 nodes (NFS2-3030,
NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM,
ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200,
AFP-300/400, AFP-1010, and AM2020). Up to 54 nodes
when DVC-EM is used in network paging.
• 6.0 A switch mode power supply with four Class A/B built-in
Notification Appliance Circuits (NAC). Selectable System
Sensor, Wheelock, or Gentex strobe synchronization.
• Built-in Alarm, Trouble, Security, and Supervisory relays.
• VeriFire® Tools online or offline programming utility. Upload/
Download, save, store, check, compare, and simulate panel
databases. Upgrade panel firmware.
• Autoprogramming and Walk Test reports.
NFS2-640
• Multiple central station communication options:
– Standard UDACT
– Internet
– Internet/GSM
• 80-character remote annunciators (up to 32).
• EIA-485 annunciators, including custom graphics.
• Printer interface (80-column and 40-column printers).
• History file with 800-event capacity in nonvolatile memory,
plus separate 200-event alarm-only file.
• Alarm Verification selection per point, with automatic
counter.
• Presignal/Positive Alarm Sequence (PAS).
• Silence inhibit and Auto Silence timer options.
• March time/temporal/California two-stage coding/strobe
synchronization.
• Field-programmable on panel or on PC, with VeriFire Tools
program check, compare, simulate.
• Full QWERTY keypad.
• Battery charger supports 18 – 200 AH batteries.
• Non-alarm points for lower priority functions.
• Remote ACK/Signal Silence/System Reset/Drill via monitor
modules.
• Automatic time control functions, with holiday exceptions.
• Surface Mount Technology (SMT) electronics.
• Extensive, built-in transient protection.
• Powerful Boolean logic equations.
DN-7111:J • 09/09/2014 — Page 1 of 8
• Support for SCS Series smoke control system in HVAC
mode.
NCA-2 AS PRIMARY DISPLAY
• Backlit, 640-character display.
• Supports SCS Series smoke control system in FSCS mode
when SCS is connected to the NCA-2 used as primary
display.
• Supports DVC digital audio loop.
• Printer and CRT EIA-232 ports.
• EIA-485 annunciator and terminal mode ports.
• Alarm, Trouble, Supervisory, and Security relays.
FLASHSCAN® INTELLIGENT FEATURES
•
•
•
•
•
•
•
•
•
Polls up to 318 devices in less than two seconds.
Activates up to 159 outputs in less than five seconds.
Multicolor LEDs blink device address during Walk Test.
Fully digital, high-precision protocol (U.S. Patent
5,539,389).
Manual sensitivity adjustment — up to nine levels.
Pre-alarm ONYX intelligent sensing — up to nine levels.
Day/Night automatic sensitivity adjustment.
Sensitivity windows:
– Ion – 0.5 to 2.5%/foot obscuration.
– Photo – 0.5 to 2.35%/foot obscuration.
– Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
– Acclimate Plus™ – 0.5 to 4.0%/foot obscuration.
– IntelliQuad™ – 1.0 to 4.0%/foot obscuration.
– IntelliQuad™ PLUS – 1.0 to 4.0%/foot obscuration
Drift compensation (U.S. Patent 5,764,142).
• Degraded mode — in the unlikely event that the CPU2-640
microprocessor fails, FlashScan detectors revert to
degraded operation and can activate the CPU2-640 NAC
circuits and alarm relay. Each of the four built-in panel
circuits includes a Disable/Enable switch for this feature.
• Multi-detector algorithm involves nearby detectors in alarm
decision (U.S. Patent 5,627,515).
• Automatic detector sensitivity testing (NFPA-72 compliant).
• Maintenance alert (two levels).
• Self-optimizing pre-alarm.
FSL-751 (VERY INTELLIGENT EARLY WARNING)
SMOKE DETECTION TECHNOLOGY
• Advanced ONYX intelligent sensing algorithms differentiate
between smoke and non-smoke signals (U.S. Patent
5,831,524).
• Addressable operation pinpoints the fire location.
• Early warning performance comparable to the best aspiration systems at a fraction of the lifetime cost.
FAPT-851 ACCLIMATE PLUS
LOW-PROFILE INTELLIGENT MULTI-SENSOR
• Detector automatically adjusts sensitivity levels without
operator intervention or programming. Sensitivity increases
with heat.
• Microprocessor-based technology; combination photo and
thermal technology.
• Low-temperature warning signal at 40°F ± 5°F (4.44°C ±
2.77°C).
SLC Intelligent Loop 1
Up to 32 remote displays
DEVICES
FWSG
LCD2-80
FDU-80
FSC-851 IntelliQuad
FAPT-851 Acclimate PLUS
FSL-751 FlashScan VIEW
FSP-851 Photo
FSI-851 Ion
FST-851 Thermal
FSA-8000
...etc.
NBG-12LX
XP6/10 I/O Modules
FMM-1
IDC
FCM-1
NAC
FRM-1
Relay Contact
SLC Intelligent Loop 2
EIA-485
EIA-485
KDM-R2 display
OR
NCA-2
OR
with no display
ACM-8R
Relay Control
EIA-232
Sample
System
Options
2048 annunciator/control points
Optional 636-point UDACT
NFS2-640
“C” cabinet size shown
Page 2 of 8 — DN-7111:J • 09/09/2014
ACM/AEM-24AT
LED Annunciator
PRN Series Printer
LDM-32
Custom Graphics
Dual phone
lines to
Central
Station
7111blok-2014.wmf
FSC-851 INTELLIQUAD
ADVANCED MULTI-CRITERIA DETECTOR
• Detects all four major elements of a fire (smoke, heat, CO,
and flame).
• Automatic drift compensation of smoke sensor and CO cell.
• High nuisance-alarm immunity.
FSA-8000 INTELLIGENT FAAST DETECTOR
• Connects directly to the SLC loop of compatible ONYX
series panels
• Provides five event thresholds that can be individually programmed with descriptive labels for control-by-event programming; uses five detector addresses.
• Uses patented particle separator and field-replaceable filter
to remove contaminants.
• Advanced algorithms reject common nuisance conditions
FCO-851 INTELLIQUAD™ PLUS
ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR
• Detects all four major elements of a fire.
• Separate signal for life-safety CO detection.
• Optional addressable sounder base for Temp-3 (fire) or
Temp-4 (CO) tone.
• Automatic drift compensation of smoke sensor and CO cell.
• High nuisance-alarm immunity.
SWIFT WIRELESS
• Self-healing mesh wireless protocol.
• Each SWIFT Gateway supports up to 50 devices: 1 wireless
gateway and up to 49 SWIFT devices.
• Up to 4 wireless gateways can be installed with overlapping
network coverage.
RELEASING FEATURES
•
•
•
•
•
Ten independent hazards.
Sophisticated cross-zone (three options).
Delay timer and Discharge timers (adjustable).
Abort (four options).
Low-pressure CO2 listed.
DIGITAL VOICE AND TELEPHONE FEATURES
• Up to eight channels of digital audio.
• 35, 50, 75, and 100/125 watt digital amplifiers (DAA2/DAX
series and DS series; NCA-2 required as primary display).
• Solid-state digital message generation.
• Firefighter telephone option.
• 30- to 120-watt high-efficiency amplifiers (AA Series).
• Backup tone generator and amplifier option.
• NFS2-640 can also integrate with the FirstCommand Emergency Communications System. See DN-60772.
HIGH-EFFICIENCY OFFLINE SWITCHING
3.0 A POWER SUPPLY (6.0 A IN ALARM)
• 120 VAC (NFS2-640); 240 VAC (NFS2-640E).
• Displays battery current/voltage on panel (with display).
FlashScan, Exclusive
World-Leading Detector Protocol
At the heart of the NFS2-640 is a set of detection devices and
device protocol — FlashScan (U.S. Patent 5,539,389). FlashScan is an all-digital protocol that gives superior precision and
high noise immunity.
In addition to providing quick identification of an active input
device, this protocol can also activate many output devices in a
fraction of the time required by competitive protocols. This high
speed also allows the NFS2-640 to have the largest device per
loop capacity in the industry — 318 points — yet every input
and output device is sampled in less than two seconds. The
microprocessor-based FlashScan detectors have bicolor LEDs
that can be coded to provide diagnostic information, such as
device address during Walk Test.
ONYX Intelligent Sensing
Intelligent sensing is a set of software algorithms that provides
the NFS2-640 with industry-leading smoke detection capability. These complex algorithms require many calculations on
each reading of each detector, and are made possible by the
high-speed microcomputer used by the NFS2-640.
Drift Compensation and Smoothing: Drift compensation
allows the detector to retain its original ability to detect actual
smoke, and resist false alarms, even as dirt accumulates. It
reduces maintenance requirements by allowing the system to
automatically perform the periodic sensitivity measurements
required by NFPA 72. Smoothing filters are also provided by
software to remove transient noise signals, such as those
caused by electrical interference.
Maintenance Warnings: When the drift compensation performed for a detector reaches a certain level, the performance
of the detector may be compromised, and special warnings
are given. There are three warning levels: (1) Low Chamber
value; (2) Maintenance Alert, indicative of dust accumulation
that is near but below the allowed limit; (3) Maintenance
Urgent, indicative of dust accumulation above the allowed limit.
Sensitivity Adjust: Nine sensitivity levels are provided for
alarm detection. These levels can be set manually, or can
change automatically between day and night. Nine levels of
pre-alarm sensitivity can also be selected, based on predetermined levels of alarm. Pre-alarm operation can be latching or
self-restoring, and can be used to activate special control functions.
Self-Optimizing Pre-Alarm: Each detector may be set for
“Self-Optimizing” pre-alarm. In this special mode, the detector
“learns” its normal environment, measuring the peak analog
readings over a long period of time, and setting the pre-alarm
level just above these normal peaks.
Cooperating Multi-Detector Sensing: A patented feature of
ONYX intelligent sensing is the ability of a smoke sensor to
consider readings from nearby sensors in making alarm or
pre-alarm decisions. Without statistical sacrifice in the ability to
resist false alarms, it allows a sensor to increase its sensitivity
to actual smoke by a factor of almost two to one.
Field Programming Options
Autoprogram is a timesaving feature. The FACP “learns” what
devices are physically connected and automatically loads
them in the program with default values for all parameters.
Requiring less than one minute to run, this routine allows the
user to have almost immediate fire protection in a new installation, even if only a portion of the detectors are installed.
Keypad Program Edit (with KDM-R2) The NFS2-640, like all
NOTIFIER intelligent panels, has the exclusive feature of program creation and editing capability from the front panel keypad, while continuing to provide fire protection. The
architecture of the NFS2-640 software is such that each point
entry carries its own program, including control-by-event links
to other points. This allows the program to be entered with
independent per-point segments, while the NFS2-640 simultaneously monitors other (already installed) points for alarm conditions.
DN-7111:J • 09/09/2014 — Page 3 of 8
VeriFire® Tools is an offline programming and test utility that
can greatly reduce installation programming time, and
increase confidence in the site-specific software. It is Windows®-based and provides technologically advanced capabilities to aid the installer. The installer may create the entire
program for the NFS2-640 in the comfort of the office, test it,
store a backup file, then bring it to the site and download from
a laptop into the panel.
Placement of Equipment
in Chassis and Cabinet
The following guidelines outline the NFS2-640’s flexible system design.
Rows: The first row of equipment in the cabinet mounts in the
chassis shipped with the FACP. Mount the second, third, or
fourth rows of equipment in a CHS-4 series chassis or, for Digital Voice Command products, in CA-1 or CA-2. (For DVC-EM
and DAA2/DAX components see DVC Manual; for DS series
components see DS-AMP Manual; for DVC-AO applications,
see AA Series Installation Manual). Other options are available; see your panel’s installation manual.
Wiring: When designing the cabinet layout, consider separation of power-limited and non-power-limited wiring as discussed in the NFS2-640 Installation Manual.
Positions: A chassis offers four basic side-by-side positions
for components; the number of modules that can be mounted
in each position depends on the chassis model and the size of
the individual module. There are a variety of standoffs and
hardware items available for different combinations and configurations of components.
It is critical that all mounting holes of the NFS2-640 are
secured with a screw or standoff to ensure continuity of Earth
Ground.
Layers: The control panel’s chassis accepts four layers of
equipment, including the control panel. The CPU2-640 fills
three positions (left to right) in the first-installed layer (the back
of the chassis); its integral power supply occupies the center
two positions in the next two layers; the optional display occupies (the left) two positions at the front, flush with the door.
Some equipment, such as the NCA-2, may be mounted in the
dress panel directly in front of the control panel. The NCA-2
can be used as a primary display for the NFS2-640 (use NCA/
640-2-KIT) by directly connecting their network ports (required
in Canadian stand-alone applications); see NCA-2 data sheet
for mounting options (DN-7047).
Expansion: Installing an LEM-320 Loop Expander Module
adds a second SLC loop to the control panel. The LEM-320 is
mounted onto the CPU2-640, occupying the middle-right, second (back) slot on the chassis.
Networking: If networking two or more control panels, each
unit requires a Network Communication Module or HighSpeed Network Communication Module. (HS-NCM can support two nodes; see “Networking Options” on page 5). These
modules can be installed in any option board position (see
manual), and additional option boards can be mounted in front
of the network communication modules.
KDM-R2 Controls and Indicators
Program Keypad: QWERTY type (keyboard layout, see
figure).
12 LED indicators: Power; Fire Alarm; Pre-Alarm; Security;
Supervisory; System Trouble; Signals Silenced; Points Disabled; Control Active; Abort; Pre-Discharge; Discharge.
Keypad Switch Controls: Acknowledge/Scroll Display; Signal
Silence; Drill; System Reset; Lamp Test.
Page 4 of 8 — DN-7111:J • 09/09/2014
LCD Display: 80 characters (2 x 40) with long-life LED
backlight.
Product Line Information
•
•
•
•
•
•
•
•
•
“Configuration Guidelines” on page 4
“Networking Options” on page 5
“Auxiliary Power Supplies and Batteries” on page 5
“Audio Options” on page 5
“Compatible Devices, EIA-232 Ports” on page 5
“Compatible Devices, EIA-485 Ports” on page 5
“Compatible Intelligent Devices” on page 6
“Enclosures, Chassis, and Dress Plates” on page 7
“Other Options” on page 7
CONFIGURATION GUIDELINES
Stand-alone and network systems require a main display. On
systems with one FACP (one CPU2-640/-640E), display
options are the KDM-R2 or the NCA-2. On network systems
(two or more networked fire panel nodes), at least one NCA-2,
NCS, or ONYXWorks annunciation device is required. Other
options listed as follows;
KDM-R2: 80-character backlit LCD display with QWERTY programming and control keypad. Order two BMP-1 blank modules and DP-DISP2 mounting plate separately. Requires top
row of a cabinet. Required for each stand-alone 80-character
display system. The KDM-R2 may mount in network nodes to
display “local” node information as long as at least one NCA-2
or NCS/ONYXWorks network display is on the system to display network information. (Non-English versions also available:
KDM-R2-FR, KDM-R2-PO, KDM-R2-SP.)
NCA-2: Network Control Annunciator, 640 characters. On single CPU2-640/-640E systems, the optional NCA-2 can be
used as the Primary Display for the panel and connects
directly to the CPU2-640/-640E. On network systems (two or
more networked fire panel nodes), one network display (either
NCA-2 or NCS/ONYXWorks) is required for every system. On
network systems, the NCA-2 connects to (and requires) a
standard Network Communication Module or High-Speed Network Communication Module. Mounts in a row of FACP node
or in two annunciator positions. Mounting options include the
DP-DISP2, ADP-4B, or in an annunciator box, such as the
ABS-2D. In CAB-4 top-row applications, a DP-DISP2 and two
BMP-1 blank modules are required for mounting. Required for
NFS2-640 applications employing the DVC-EM with DAL
devices. Non-English versions are available. For marine applications, order NCA-2-M; for non-English Marine applications,
order NCA-2-M and the appropriate KP-KIT-XX. See DN-7047.
CPU2-640: Central processing unit (CPU) with integral 3.0 A
(6.0 A in alarm) power supply for an NFS2-640 system.
Includes control panel factory-mounted on a chassis; one Signaling Line Circuit expandable to two; documentation kit.
Order one per system or as necessary (up to 103 network
nodes) on a network system. (Non-English versions also available: CPU2-640-FR, CPU2-640-PO, CPU2-640-SP.)
CPU2-640E: Same as CPU2-640 but requires 240 VAC, 1.5 A,
(3.0 A in alarm). (Non-English versions also available: CPU2640E-PO, CPU2-640E-SP.)
NCA/640-2-KIT: Bracket installation kit required to mount
NCA-2 to the CPU2-640/-640E’s standard chassis.
DP-DISP2: Dress panel for top row in cabinet with CPU2-640/
640E installed.
ADP2-640: Dress panel for middle rows with CPU2-640/640E.
BMP-1: Blank module for unused module positions.
BP2-4: Battery plate, required.
LEM-320: Loop Expander Module. Expands each NFS2-640
to two Signaling Line Circuits. See DN-6881.
NETWORKING OPTIONS
NCM-W, NCM-F: Standard Network Communications Modules. Wire and multi-mode fiber versions available. See DN6861.
HS-NCM-W/MF/SF/WMF/WSF/MFSF: High-speed Network
Communications Modules that can connect to two nodes.
Wire, single-mode fiber, multi-mode fiber, and media conversion models are available. See DN-60454.
RPT-W, RPT-F, RPT-WF: Standard-network repeater board
with wire connection (RPT-W), multi-mode fiber connection
(RPT-F), or allowing a change in media type between wire and
fiber (RPT-WF). Not used with high-speed networks. See DN6971.
ONYXWorks: UL-listed graphics PC workstation, software,
and computer hardware. See DN-7048 for specific part numbers.
NFN-GW-EM-3: NFN Gateway, embedded. (Replaces NFNGW-EM.) See DN-60499.
DS-AMP/E: 125W, 25 VRMS, or 100W, 70VRMS. 70VRMS
requires DS-XF70V step-up transformer. Digital Series Amplifier, part of the DS-DB system. See DN-60663.
DS-RFM, DS-FM, DS-SFM: Fiber conversion modules for
DVC-EM, DS-DB distribution board, and DAX and DAA2
Series amplifiers. See DN-60633.
DVC-AO: DVC Analog Output board provides four analog output circuits for use with AA Series amplifiers. Four-channel
operation supported. See DN-7045.
DAA2-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly with power supply; includes chassis. See DN-60556.
DAA2-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier
assembly with power supply; includes chassis. See DN-60556.
DAA2-7525(E): 75W, 25 Vrms digital audio amplifier assembly
with power supply; includes chassis. See DN-60556.
DAX-3525(E): 35W, 25 Vrms Digital Audio Amplifier assembly
with power supply, includes chassis. See DN-60561.
DAX-3570(E): 35W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
NWS-3: NOTI•FIRE•NET™ Web Server. See DN-6928.
DAX-5025(E): 50W, 25 Vrms Digital Audio Amplifier assembly
with power supply, includes chassis. See DN-60561.
CAP-GW: Common Alerting Protocol Gateway. See DN60576.
DAX-5070(E): 50W, 70.7 Vrms Digital Audio Amplifier assembly with power supply, includes chassis. See DN-60561.
VESDA-HLI-GW: VESDAnet high-level interface gateway. See
DN-60753.
TELH-1: Firefighter’s Telephone Handset for use with the
DVC-EM when mounted in the CA-2 chassis. See DN-7045.
LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic
and high-speed NOTI•FIRE•NET networks through the NFN
Gateway. See DN-60679.
CMIC-1: Optional microphone and microphone well assembly
used with the CA-1 chassis.
OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW. See
DN-60679.
AUXILIARY POWER SUPPLIES AND BATTERIES
ACPS-610: 6.0 A or 10.0 A addressable charging power supply. See DN-60244.
APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes
of power for peripheral devices. Includes battery input and
transfer relay, and overcurrent protection. Mounts on two of
four positions on a CHS-4L or CHS-4 chassis. See DN-5952.
FCPS-24S6/S8: Remote 6 A and 8 A power supplies with battery charger. See DN-6927.
BAT Series: Batteries. NFS2-640 uses two 12 volt, 18 to 200
AH batteries. See DN-6933.
AUDIO OPTIONS
NOTE: For mounting hardware, see “Enclosures, Chassis, and
Dress Plates” on page 7 and peripheral data sheets.
DVC-EM: Digital Voice Command, digital audio processor with
message storage for up to 32 minutes of standard quality (4
minutes at high quality) digital audio. Capable of playing up to
eight simultaneous messages when used with Digital Audio
Loop (DAL) devices. See DN-7045.
RM-1/RM-1SA: Remote microphone assemblies, mount on
ADP-4 (RM-1) dress panel or CAB-RM/-RMR (RM-1SA)
stand-alone cabinets. See DN-6728.
AA-30: Audio Amplifier, 30 watts, 25 Vrms. Includes amplifier
and audio input supervision, backup input, and automatic switchover, power supply, cables. See DN-3224.
AA-120/AA-100: Audio Amplifier provides up to 120 watts of
25 VRMS audio power for the NFS-640. The amplifier contains
an integral chassis for mounting to a CAB-B4, -C4, or -D4
backbox (consumes one row). Switch-mode power. Includes
audio input and amplified output supervision, backup input,
and automatic switchover to backup tone. Order the AA-100
for 70.7 VRMS systems and 100 watts of power. See DN-3224.
DAA Series Digital Audio Amplifiers: Legacy DAA Series
amplifiers are compatible with DVC-EM systems running
SR4.0. For specific information on DAA-50 series amplifiers,
refer to DN-7046. For information on DAA-7525 Series, refer to
DN-60257.
NFC-25/50: 25 watt, 25 VRMS, emergency Voice Evacuation
Control Panel (VECP) with integral commercial microphone,
digital message generator, and single-/dual-channel Class A
or Class B speaker circuits. See DN-60772.
COMPATIBLE DEVICES, EIA-232 PORTS
DVC-RPU: Digital Voice Command Remote Paging Unit for
use with DVC-EM. Includes the keypad/display. See DN60726.
PRN-6: 80-column printer. See DN-6956.
DS-DB: Digital Series Distribution Board, provides bulk amplification capabilities to the DVC-EM while retaining digital audio
distribuition capabilities. Can be configured with up to four DSAMPs, supplying high-level risers spread throughout an installation. See DN-60565.
DPI-232: Direct Panel Interface, specialized modem for
extending serial data links to remotely located FACPs and/or
peripherals. See DN-6870.
DVC-KD: DVC-EM keypad for local annunciation and controls;
status LEDs and 24 user-programmable buttons. See DN7045.
ACM-24AT: ONYX Series ACS annunciator – up to 96 points
of annunciation with Alarm or Active LED, Trouble LED, and
switch per circuit. Active/Alarm LEDs can be programmed (by
VS4095/5: Printer, 40-column, 24V. Mounted in external backbox. See DN-3260.
COMPATIBLE DEVICES, EIA-485 PORTS
DN-7111:J • 09/09/2014 — Page 5 of 8
powered-up switch selection) by point to be red, green, or yellow; the Trouble LED is always yellow. See DN-6862.
FST-851: FlashScan thermal detector 135°F (57°C). See DN6936.
AEM-24AT: Same LED and switch capabilities as ACM-24AT,
expands the ACM-24AT to 48, 72, or 96 points. See DN-6862.
FST-851R: FlashScan thermal detector 135°F (57°C) with
rate-of-rise. See DN-6936.
ACM-48A: ONYX Series ACS annunciator – up to 96 points of
annunciation with Alarm or Active LED per circuit. Active/
Alarm LEDs can be programmed (by powered-up switch selection) in groups of 24 to be red, green, or yellow. Expandable to
96 points with one AEM-48A. See DN-6862.
FST-851H: FlashScan 190°F (88°C) high-temperature thermal
detector. See DN-6936.
AEM-48A: Same LED capabilities as ACM-48A, expands the
ACM-48A to 96 points. See DN-6862.
ACM-8R: Remote Relay Module with eight Form-C contacts.
Can be located up to 6,000 ft. (1828.8 m) from panel on four
wires. See DN-3558.
FDU-80: Terminal mode. 80-character, backlit LCD display.
Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per
FACP. See DN-6820.
LCD2-80: Terminal and ACS mode. 80-character, backlit LCD
display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32
per FACP. See DN-60548.
LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDMR32; remote custom graphic driver modules. See DN-0551.
FAPT-851: FlashScan Acclimate Plus low-profile multi-sensor
detector. See DN-6937.
FSL-751: FlashScan VIEW laser photo detector. See DN6886.
DNR: InnovairFlex low-flow non-relay duct-detector housing
(order FSP-851R separately). Replaces FSD-751PL/FSD751RPL. See DN-60429.
DNRW: Same as above with NEMA-4 rating, watertight. See
DN-60429.
B224RB: Low-profile relay base. See DN-60054.
B224BI: Isolator base for low-profile detectors. See DN60054.
B210LP: Low-profile base. Standard U.S. style. Replaces
B710LP. See DN-60054.
B501: European-style, 4" (10.16 cm) base. See DN-60054.
SCS: Smoke control stations SCS-8, SCE-8, with lamp drivers
SCS-8L, SCE-8L; eight (expandable to 16) circuits (HVAC
only). See DN-4818.
B200S: Intelligent programmable sounder base, capable of
producing a variety of tone patterns including ANSI Temporal
3. Compatible with sychronization protocol. See DN-60054.
TM-4: Transmitter Module. Includes three reverse-polarity circuits and one municipal box circuit. Mounts in panel module
position (single-address-style) or in CHS2-M2 position. See
DN-6860.
B200SCOA: Based on B200SA, with added CO detector
markings in English/French. For Canadian applications only.
UDACT-2: Universal Digital Alarm Communicator Transmitter,
636 channel. See DN-60686.
UZC-256: Programmable Universal Zone Coder provides positive non-interfering successive zone coding. Microprocessorcontrolled, field-programmable from IBM®-compatible PCs
(requires optional programming kit). Up to 256 programmable
codes. Mounts in BB-UZC or other compatible chassis (purchased separately). See DN-3404.
COMPATIBLE INTELLIGENT DEVICES
FWSG Wireless SWIFT Gateway: Addressable gateway supports wireless SLC devices. Not appropriate for ULC applications. See DN-60820.
FSA-8000: Intelligent FAAST Fire Alarm Aspiration Sensing
Technology®. Intelligent aspirating smoke detector. For Canadian applications, order FSA-8000A. See DN-60792.
FSB-200: Intelligent beam smoke detector. See DN-6985.
FSB-200S: Intelligent beam smoke detector with integral sensitivity test. See DN-6985.
FSC-851: FlashScan IntelliQuad Advanced Multi-Criteria
Detector. See DN-60412.
FCO-851: FlashScan IntelliQuad PLUS Advanced Multi-Criteria Fire/CO Detector. See DN-60689.
FSI-851: Low-profile FlashScan ionization detector. See DN6934.
FSP-851: Low-profile FlashScan photoelectric detector. See
DN-6935.
FSP-851T: FSP-851 plus dual electronic thermistors that add
135°F (57°C) fixed-temperature thermal sensing. See DN6935.
FSP-851R: FSP-851, remote-test capable. For use with
DNR(W). See DN-6935.
Page 6 of 8 — DN-7111:J • 09/09/2014
B200SR: Sounder base, Temporal 3 or Continuous tone. See
DN-60054.
FMM-1: FlashScan monitor module. See DN-6720.
FDM-1: FlashScan dual monitor module. See DN-6720.
FZM-1: FlashScan two-wire detector monitor module. See DN6720.
FMM-101: FlashScan miniature monitor module. See DN6720.
FTM-1: Firephone Telephone Module connects a remote firefighter telephone to a centralized telephone console. Reports
status to panel. Wiring to jacks and handsets is supervised.
See DN-6989.
FCM-1: FlashScan control module. See DN-6720.
FCM-1-REL: FlashScan releasing control module. See DN60390.
FRM-1: FlashScan relay module. See DN-6720.
FDRM-1: FlashScan dual monitor/dual relay module. See DN60709.
NBG-12LX: Manual pull station, addressable. See DN-6726.
ISO-X: Isolator module. See DN-2243. See DN-2243.
XP6-C: FlashScan six-circuit supervised control module. See
DN-6924.
XP6-MA: FlashScan six-zone interface module; connects
intelligent alarm system to two-wire conventional detection
zone. See DN-6925.
XP6-R: FlashScan six-relay (Form-C) control module. See
DN-6926.
XP10-M: FlashScan ten-input monitor module. See DN-6923.
SLC-IM: SLC integration module, for VESDAnet detectors.
See DN-60755.
ENCLOSURES, CHASSIS, AND DRESS PLATES
DPA-2B: Dress panel used with CA-2 chassis assembly.
CAB-4 Series Enclosure: NFS2-640 mounts in a standard
CAB-4 Series enclosure (available in four sizes, “A” through
“D”). Backbox and door ordered seperately; requires BP2-4
battery plate. A trim ring option is available for semi-flush
mounting. See DN-6857.
VP-2B: Dress panel, required when CA-2 chassis is installed
in the top two cabinet rows.
EQ Series Cabinets: EQ series cabinets will house amplifiers,
power supplies, battery chargers and control modules. EQ
cabinets are available in three sizes, “B” through “D”. See DN60229. .
CAB-BM Marine System: Protects equipment in shipboard
and waterfront applications. Also order BB-MB for systems
using 100 AH batteries. For a full list of required and optional
equipment, see DN-60688.
CHS-4: Chassis for mounting up to four APS-6Rs.
CHS-4L: Low-profile four-position Chassis. Mounts two AA-30
amplifiers or one AMG-E and one AA-30.
DP-1B: Blank dress panel. Provides dead-front panel for
unused tiers; covers DAA2/DAX series or AA-series amplifier.
DPA-1A4: Dress panel, used with the CA-1 chassis when the
CMIC-1 is not used. Provides mounting options on right two
bays for two ACS annunciators, or for blank plates. See DN7045.
BP-CA2: Blank plate for CA-2 chassis.
BB-UZC: Backbox for housing the UZC-256 in applications
where the UZC-256 will not fit in panel enclosure. Black; for
red, order BB-UZC-R.
SEISKIT-CAB: Seismic mounting kit. Required for seismiccertified applications with NFS2-640 and other equipment
mounted in CAB-4 Series Enclosures. Includes battery bracket
for two 26 AH batteries.
SEISKIT-LBB: Seismic kit for the NFS-LBB. Includes battery
bracket for two 55 AH batteries.
OTHER OPTIONS
NFS-LBB: Battery Box (required for batteries larger than 26
AH).
411: Slave digital alarm communicator. See DN-6619.
NFS-LBBR: Same as above but red.
IPDACT-2/2UD, IPDACT Internet Monitoring Module: Connects to primary and secondary DACT telephone output ports
for internet communications over customer-provided Ethernet
connection. Requires compatible Teldat VisorALARM Central
Station Receiver. Can use DHCP or static IP. See DN-60408.
CHS-BH1: Battery chassis; holds two 12.0 AH batteries.
Mounts one the left side of DAA2 chassis. See DN-7046.
CA-1: Chassis, occupies one tier of a CAB-4 Series enclosure.
The left side accommodates one DVC-EM and a DVC-KD
(optional); and the right side houses a CMIC-1 microphone
and its well (optional). See DN-7045.
CA-2: Chassis assembly, occupies two tiers of a CAB-4 Series
enclosure. The left side accommodates one DVC-EM mounted
on a half-chassis and one NCA-2 mounted on a half-chassis.
The right side houses a microphone/handset well. The CA-2
assembly includes CMIC-1 microphone. ADDR Series doors
with two-tier visibility are available for use with the CA-2 configuration: ADDR-B4, ADDR-C4, ADDR-D4 (below).
CFFT-1: Chassis to mount firefighter’s telephone and one ACS
annunciator in a CAB-4 row. Includes TELH-1 firefighter’s
handset for the DVC-EM, chassis, phone well and mounting
hardware. Order DP-CFFT dress panel separately.
DP-CFFT: CFFT-1 dress panel. Requires BMP-1 if no ACS
annunciator is installed.
ADDR-B4*: Two-tier-sized door designed for use with the CA2 chassis configuration. ADDR Series doors are similar to
CAB-4 Series “DR” doors, but a clear window space exposes
the top two tiers of the CAB-4 enclosure. Use an SBB-B4
backbox with the ADDR-B4. See DN-7045, DN-6857.
ADDR-C4*: Three-tier-sized door, designed for use with the
CA-2 chassis configuration. ADDR Series doors are similar to
CAB-4 Series “DR” doors, but a clear window space exposes
the top two tiers of the CAB-4 enclosure. Use an SBB-C4
backbox with the ADDR-C4. See DN-7045, DN-6857.
ADDR-D4*: Four-tier-sized door designed for use with the CA2 chassis configuration. ADDR Series doors are similar to
CAB-4 Series “DR” doors, but a clear window space exposes
the top two tiers of the CAB-4 enclosure. Use an SBB-D4
backbox with the ADDR-D4. See DN-7045, DN-6857.
*Use ADDR-B4/C4/D4 when CA-2 chassis is installed in top
two rows with NCA-2 or BP-CA2. Use standard door when CA2 is not installed in top two rows. For additional configuration
information, see the DVC application guide on http://esd.notifier.com.
DPA-1: Dress panel, used with the CA-1 chassis when configured with a DVC-EM, DVC-KD, and CMIC-1. See DN-7045.
411UDAC: Digital alarm communicator. See DN-6746.
IPCHSKIT: IP Communicator Chassis Mounting Kit. For
mounting an IPDACT-2/2UD onto the panel chassis or CHS-4
series chassis. Use IPENC for external mounting applications.
IPSPLT: Y-adapter option allow connection of both panel dialer
outputs to one IPDACT-2/2UD cable input.
IPENC: External enclosure for IPDACT, includes IPBRKT
mounting bracket; Red. For Black order IPENC-B.
IPGSM-4G: Internet and Digital Cellular Fire Alarm Communicator. Provides selectable configurable paths: cellular only, IP only,
or IP primary with cellular backup. Connects to the primary and
secondary ports of a DACT. For Canadian applications order
IPGSM-4GC. See DH-60769.
NOTE: For other options including compatibility with retrofit equipment, refer to the panel's installation manual, the SLC manual, and
the Device Compatibility Document.
System Specifications
SYSTEM CAPACITY
•
•
•
•
•
•
Intelligent Signaling Line Circuits ............1 expandable to 2
Intelligent detectors ......................................... 159 per loop
Addressable monitor/control modules .............. 159 per loop
Programmable software zones......................................... 99
Special programming zones ............................................. 14
LCD annunciators per CPU2-640/-640E
and NCA-2 (observe power)............................................. 32
• ACS annunciators per
CPU2-640/-640E .......................... 32 addresses x 64 points
• ACS annunciators per
NCA-2.................................. 32 addresses x 64 or 96 points
NOTE: The NCA-2 supports up to 96 annunciator address points
per ACM-24AT/-48A.
ELECTRICAL SPECIFICATIONS
• Primary input power:
– CPU2-640 board: 120 VAC, 50/60 Hz, 5.0 A.
– CPU2-640E board: 220/240 VAC, 50/60 Hz, 2.5 A.
DN-7111:J • 09/09/2014 — Page 7 of 8
• Current draw (standby/alarm):
– CPU2-640(E) board: 0.250 A. Add 0.035 A for each NAC
in use.
– KDM-R2: 0.100 A.
– LEM-320: 0.100 A.
• Total output 24 V power: 6.0 A in alarm.
NOTE: The power supply has a total of 6.0 A. of available power.
This is shared by all internal circuits. See Installation Manual for a
complete current draw calculation sheet.
• Standard notification circuits (4): 1.5 A each.
• Resettable regulated 24V power: 1.25 A.
• Two non-resettable regulated 24V power outputs:
– 1.25 A.
– 0.50 A.
• Non-resettable 5V power: 0.15 A.
• Battery charger range: 18 AH – 200 AH. Use separate cabinet for batteries over 26 AH.
• Float rate: 27.6 V.
CABINET SPECIFICATIONS
• Systems can be installed in CAB-4 Series cabinets (four
sizes with various door options, see DN-6857). Requires
BP2-4 Battery Plate.
SHIPPING WEIGHT
• CPU2-640/-640: 14.3 lb (6.49 kg).
• CPU2-640/-640E: 14.55 lb (6.60 kg).
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH
(noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the
useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that
this system and its peripherals be installed in an environment
with a normal room temperature of 15 – 27°C/60 – 80°F.
requirements are followed, systems are approved by the following agencies:
• US Coast Guard 161.002/50/0, 161.002/55/0 (Standard 46
CFR and 161.002).
• Lloyd's Register 11/600013 (ENV 3 category).
• American Bureau of Shipping (ABS) Type Approval.
NOTE: For information on marine applications, see DN-60688.
STANDARDS
The NFS2-640 complies with the following UL Standards and
NFPA 72, International Building Code (IBC), and California
Building Code (CBC) Fire Alarm Systems requirements:
• UL 864, 9th Edition (Fire).
• UL 1076 (Burglary).
• UL 2572 (Mass Notification Systems). (NFS2-640 version
20 or higher.)
• LOCAL (Automatic, Manual, Waterflow and Sprinkler
Supervisory).
• AUXILIARY (Automatic, Manual and Waterflow) (requires
TM-4).
• REMOTE STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory) (requires TM-4).
• PROPRIETARY (Automatic, Manual and Waterflow).
Not applicable for FM.
• EMERGENCY VOICE/ALARM.
• OT, PSDN (Other Technologies, Packet-switched Data Network).
• IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
• CBC 2007 (Seismic).
AGENCY LISTINGS AND APPROVALS
The listings and approvals below apply to the basic NFS2-640
control panel. In some cases, certain modules may not be
listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
• UL Listed: S635.
• ULC Listed: S635.
• FM Approved.
• MEA: 128-07-E.
• Fire Dept. of New York: #6121.
• CSFM: 7165-0028:0243.
• City of Chicago.
• City and County of Denver.
• CCCF listed.
Marine Applications: Marine approved systems must be configured using components itemized in this document. (See
Main System Components, in “Product Line Information.) Specific connections and requirements for those components are
described in the installation document, PN 54756. When these
IntelliQuad™, NOTI•FIRE•NET™, ONYXWorks™, and SWIFT™ are
trademarks; and Acclimate® Plus™, FirstCommand®, FlashScan®,
NOTIFIER®, ONYX®, VeriFire®, and VIEW® are registered
trademarks of Honeywell International Inc. Microsoft® and Windows®
are registered trademarks of Microsoft Corporation. IBM® is a registered
trademark of IBM Corporation.
©2014 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 8 of 8 — DN-7111:J • 09/09/2014
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7165-0028:0243
Page 1 of 4
CATEGORY:
7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE:
NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: [email protected]
DESIGN:
Models NFS2-640, NFS-320/C (R), and NFS-320SYS fire alarm control units. Local,
auxiliary, remote station (PPU), proprietary (PPU), central station (PPU), manual, automatic,
waterfowl and sprinkler supervisory services. Also suitable for releasing service, Process
Management and Emergency Voice/Alarm communication System *. Model numbers may
be followed by an “R” suffix representing the enclosure color being red. Refer to listee's data
sheet for additional detailed product description and operational considerations. System
components:
ACM-8R, -16AT, -32A, -24AT, -48A; Annunciator Control Modules
ACPS-610, AMPS-24; Addressable power supply/charger
ADP-4B, -A4, -1, -2, DP-DISP2; Dress Panel
AEM-16AT, -32A, -24AT, -48A; Annunciator Expander Modules
AFM-16A, -16AT, -32A; Annunciator Fixed Modules
AKS-1B; Annunciator Key Switch
APS2-6R; Power supply
BB-100, -200, NFS-LBB/-LBBR; Battery Boxes
BGRA-SCS, BGRB-SCS; Smoke Control Station
BMP-1; Blank Module
BP-4, BP2-4; Battery Dress Plates
CAB-3/-4 Series; Enclosure
CAB-RP, CAB-RPR; Cabinets
CEF-SCS; Smoke Control Station
CHS-4, CHS-4N, CHS-4L; Chassis
CPU2-640, CPU-320SYS; CPU Board
CRT-2; Display Terminal
DP-1B; Blank Panel
DPA-1A4/1/2, DP-DISP2; Dress Panel
DPI-232; Panel Interface
DR-A4, DR-A4B, DR-A4BR, DR-A4R; Door Assembly
DR-AA4, DR-AA4B, DR-AA4BR, DR-AA4R; Door Assembly
DR-B3F; Door Assembly
DR-B4, DR-B4B, DR-B4BR, DR-B4R; Door Assembly
DR-C4, DR-C4B, DR-C4BR, DR-C4R; Door Assembly
DR-D4, DR-D4B, DR-D4BR, DR-D4R; Door Assembly
*Rev. 10-29-13 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
Listing No.
7165-0028:0243
Page 2 of 4
EQ Series; Cabinets
EQBB-B4, EQBB-C4, EQBB-D4; Backbox Assembly
EQDR-B4, EQDR-C4, EQDR-D4; Door Assembly
FCM-1, FCM-1-REL; Releasing Control Module
FCPS-24S6, -24S8; Field Charger/Power Supply
FDM-1; Dual Monitor Module
FDRM-1:Multiple Module with two Relay Outputs
FDU-80/-80G; Remote Annunciator
FIRSTVISION-LCD/ENC; Interactive Firefighters’ display/enclosure
FRM-1; Relay Module
FTM-1; Control Module
FZM-1, FMM-1, FMM-101; Monitor Modules
HS-NCM-W/-MF/-SF/-WMF/-WSF/-MSSF; High Speed Network Control Modules
IPDACT-2/-2UD; IP Fire Alarm Communicator
ISO-X; Isolator Module
KAPS-24, CPS-24; Power Supply
KDM-R2; Keyboard Display Module
LCD-80, -160; Annunciators
LCD-80TM; Annunciator Terminal Module LCD
LCD2-80; Remote Annunciator
LDM-32/-E32/-R32; Lamp Driver Module
LEM-320/ELEM-320; Loop Expander Module
NBG-12LRA; Agent Releasing Abort Station
NBG-12LX; Addressable Manual Pull Station
NCA, NCA-2; Network Communication Annunciator
NCM-W, -F; Network Control Module
NCS4-W-ONYX, NCS4-F-ONYX; Network Control Station
NCS5-W-ONYX, NCS5-F-ONYX; Network Control Station
NFS-LBB/NFS-LBBR; Battery Box/Red
NFS-320SYS; Chassis
NFV-25/50, NFV-25/50ZS/ZST; Voice Evacuation Control Panels
NFV-25/50DA, NFV-25/50DAZS; Distributed Audio Panels
ONYXWorks-EW/-NW-/NF/-HNW/-HNMF/-HNSF/-TS/-EW-TS/-NF-TS/-HW-TS/
-HNMFT/-HNSFT/-HNWT; PC workstation for NOTI●FIRE●NET, Wire/Fiber/
with Touch screen monitors
PRN-6; Printer
RKS-S; Remote Security Key Switch
RPT-W, -485W; Repeater Wire
RPT-F; Repeater Fiber
RPT -485FW; Repeater Fiber/Wire
RSA-SCS, RSB-SCS, RSC-SCS, RSD-SCS, RSE-SCS; Smoke Control Station
SBB-A3F; Backbox Assembly
SBB-A4, SBB-A4R, SBB-AA4, SBB-AA4R; Backbox Assembly
SBB-B4, SBB-B4R-L8, SBB-C4, SBB-C4R; Backbox Assembly
SBB-D4, SBB-D4R; Backbox Assembly
*Rev. 10-29-13 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
Listing No.
7165-0028:0243
Page 3 of 4
SCE-8; Smoke Control Expander
SCS-8L; Smoke Control Lamp Driver Station
SCE-8L; Smoke Control Expander Lamp
SCS-8; Smoke Control Station
STS-1; Security Tamper Switch
TM-4; Transmitter Module
TR-A4/-B3N/-B4/-C4/-D3N/-D4; Trim Ring
UDACT, UDACT-2; Universal DACT
UZC-256; Universal Zone Coder
VP-2B; Dress Panel
XP5-C/-M; Transponder Modules
XP6-C; Supervised Control Modules
XP6-MA; Six Zone Interface Modules
XP6-R; Six Relay Control Modules
XP10-M(A); Ten Input Monitor Modules
XPM-8L; Transponder Monitor Modules
The following models are intended for use on NFS2-640 only:
AA-30, -100, -120; Amplifiers
ACT-1, -2, -4, -25, -70; Audio Coupling Transformer
ADDR-B4/-B4R/-C4/-C4R/-D4/-D4R; Door Assemblies
AMG-E; Audio Message Generator
AVL-1; Audio Voice Link
BDA-25V/-70V; Backup Digital Audio Amplifiers
CHS2-M2, CA-1, CA-2; Chassis
CMIC-1, CMIC-RP; Microphone Assembly
DAA-5025/-5070; Digital Audio Amplifiers
DAA-5025F/DAA-5025SF; Digital Audio Amplifiers
DAA-5070F/DAA-5070SF; Digital Audio Amplifiers, Fiber Mode
DAA-75 Series; Digital Audio Amplifiers
DAA-7525, DAA-7525F, DAA-7525SF; Digital Audio Amplifiers
DAA2-5025/-5070/-7525; Digital Audio Amplifiers
DAX-3525/-3570/-5025/-5070; Digital Audio Amplifiers
DS-AMP/E; Digital Series Audio Amplifier
DS-BDA; Digital Series Backup Amplifier
DS-DB; Digital Series Distribution Board
DS-FM, DS-RFM, DS-SFM; Digital Series Fiber Module
DVC; Digital Voice Command
DVC-EM/-EMF/-EMSF; Digital Voice Command Extended Memory Module
DVC-RPU; Remote Paging Unit
FFT-7, -7S; Fire Fighter’s Telephone
FHS; Fireman’s Handset
FPJ; Fireman’s Phone Jack
RM-1, RM-1SA; Remote Microphone
*Rev. 10-29-13 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
Listing No.
7165-0028:0243
Page 4 of 4
TELH-1; Telephone Assembly
XPIQ; Transponder Quad Intelligent Audio
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical ratings, and UL Label
APPROVAL:
Listed as fire alarm control units suitable for use in high-rise applications when used in
conjunction with separately listed compatible initiating and indicating devices. *Control units
may be used with Notifier's First Command NFC-50/100 emergency voice evacuation panals
(CSFM # 6911-0028:0265). This control unit can generate the temporal code pattern fire
alarm signal as required per NFPA 72. Refer to manufacturer’s Installation Manual for details.
This control unit meets the requirements of UL Standard 864, 9th
Edition.
NOTE:
1. For Fire Alarm Verification feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 Seconds.
2. Combined with 7170-028:244
*Rev. 10-29-13 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
DN-60772:A6
NFC-50/100(E)
Notifier First Command
Voice Evacuation & Emergency Communications System
General
Notifier’s First Command NFC-50/100 and NFC-50/100E are
multipurpose emergency voice evacuation panels for fire applications, mass notification applications, or both. The First Command delivers 50 or 100 watts of audio power for distribution to
up to eight speaker circuits (i.e. zones). The NFC-50/100(E)
comes standard with a single speaker circuit and a built-in 50
watt, 25V amplifier. A secondary 50 watt amplifier (NFC-BDA25/70V) can be added for single speaker circuit backup or to
increase system capacity to two speaker circuits and an additional 50 watts of audio power. An optional NFC-CE6 module
added to the NFC-50/100(E) will upgrade the system to a maximum of eight speaker circuit outputs. All speaker output circuits can be wired in either Style Y (Class B) or Style Z (Class
A) configuration. The NFC-50/100(E) has fourteen field programmable messages (up to 60 seconds each), built-in field
configurable pre- and post-announce tone generators and a
fully supervised Notification Appliance Circuit (NAC) with 2.0
amps of synchronized NAC power. The NFC-50/100(E)
includes three built-in Form-C relay contacts, (AC power, trouble and MNS active) a NAC follower and 500mA special application power. A built-in power supply delivers operational
power and an onboard battery charger supports charging up
to 26AH batteries (NFC cabinet holds up to 18AH batteries).
For fire protection applications, the NFC-50/100(E) is an
adjunct (slave) to any UL listed FACP, providing reverse polarity or contact closure; can be used as a stand-alone unit for
non-fire applications. For seamless integration between fire
and mass notification, the NFC-50/100(E) can be directly activated via serial communication between the NFW2-100, NFS320, or NFS2-640. Activation of the NFC-50/100(E) via other
FACPs uses the eight on board Command Input Circuits
(CMDs). Two of the eight CMD circuits (CMD 1 & CMD 2) can
be individually field programmed for activation by an FACP
Notification Appliance Circuit reverse polarity and all eight can
be activated by a contact closure. In addition, the NFC-50/
100(E) can be activated from a building's Private Branch
Exchange (PBX) with the integral night ring feature.
All NFC-50/100(E) programming is done by using a simple,
built-in programming utility accessed from any laptop. For
added flexibility, the NFC-50/100(E) supports both 25V and
70V speaker output operation. By adding a 70V transformer
conversion module (NFC-XRM-70V) or an additional 70 volt
secondary amplifier (NFC-BDA-25/70V) the system supports
70 volt speaker devices.
The NFC-50/100(E) can expand in order to accommodate
larger or more complex installations. To add more control and
increase system capacity, any combination of up to eight
external remote consoles (including the NFC-LOC, NFC-RPU,
and NFC-RM) and up to eight distributed audio amplifiers
(including the NFC-50DA(E), NFC-100DA(E) and NFC-125DA(E) can be connected on the external data bus and audio
riser data bus to create a fully integrated command center. A
fully loaded system supports up to 1100 watts of total audio
power and up to 24 speaker circuit outputs.
TYPICAL APPLICATIONS
•
Schools
•
Nursing Homes
•
Factories
•
Theaters
•
Military facilities
•
Restaurants
•
Auditoriums
•
Places of Worship
•
Office Buildings
Features
• UL Listed to UL 2572 Communication (Control Units Mass
Notification Systems) and UL 864 (emergency voice evacuation for fire)
• Modular design for system flexibility and easy expansion
• Removable terminal blocks
• 50 watts of 25V audio power (expandable to 100 watts)
RMS
• 2 amp Notification Appliance Circuit (NAC) output, sync
generator, or follower for System Sensor, Wheelock or Gentex protocols
• Optional 70Vtransformer available for the primary amplifier.
(Note that speaker wiring continues to be supervised in
standby, alarm and when background music is playing with
this optional transformer installed)
• Eight Command Input Circuits to activate messages 1 to 8:
– CMD1 and CMD2 are field selectable to be activated from
12 or 24 VDC Notification Appliance Circuits (reverse
polarity) or contact closures
– CMD3-CMD8 are activated by contact closures
• Speaker Circuits
– Single Style Y (Class B) or Style Z (Class A) speaker Circuit
DN-60772:A6 • 10/23/2015 — Page 1 of 6
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
– Two Style Y (Class B) or Style Z (Class A) speaker circuits (with optional NFC-BDA-25/70V Audio Amplifier
installed)
– Eight Style Y (Class B) or Style Z (Class A) speaker circuits (with optional NFC-BDA-25/70V and NFC-CE6
installed)
520Hz square wave tones available, which can be
uploaded to the NFC-50/100 to meet NFPA Low Frequency
requirements (Refer to the Device Compatibility Document
15378 for listed compatible speakers.)
NFC-50/100(E) can be controlled by an FACP via the ANN/
ACS (EIA-485) link of the NFW2-100, and via the ACS
(EIA-485) link of the NFS-320 or NFS2-640. The NFS-320
or NFS2-640 must be firmware version 20.0 or higher.
Certified for seismic applications when used with the appropriate seismic mounting kit
Integral supervised microphone
Microphone time-out feature which reverts back to prerecorded message if emergency page exceeds the programmed time
14 recorded messages
Field-selectable message and custom message recording
capability using the local microphone, a USB port, or an
external audio input
External Audio Input can be used for background music
Up to 60 second message duration for all messages
Integral tone generators field selectable for multiple tone
types
Powered by integral AC power supply or batteries during
AC fail
Programmable delay of immediate, 2 hours or 6 hours
reporting of AC Loss
Piezo sounder for local trouble
100 event history log
Three Form-C relays:
– AC Power Loss Relay - TB1
– System Trouble Relay - TB2
– MNS Active - TB3
500mA (0.5A) Special Application (auxiliary power) output
for addressable modules when interfaced with compatible
addressable FACPs and End-of-Line power supervision
relays
System Status LEDs (Refer to “Controls and Indicators” in
product manual LS10001-001NF-E.)
Integral Dress Panel
Optional TR-CE-B semi-flush trim ring
Any combination of up to eight (8) external remote consoles:
– Optional NFC-RM Remote Microphone (includes cabinet)
See DN-60778.
– Optional NFC-RPU Remote Page Unit (includes cabinet)
See DN-60775.
– Optional NFC-LOC Local operator console (includes cabinet) See DN-60777.
Any combination of up to eight (8) distributed audio amplifiers:
Optional NFC-50DA(E) distributed amplifier, 50 watts. See
DN-60776.
Optional NFC-125DA(E) distributed amplifier, 125 watts.
See DN-60776.
Optional NFC-50/100 distributed amplifier with backup
capability, 50/100 watts. See DN-60776.
Page 2 of 6 — DN-60772:A6 • 10/23/2015
Optional Internal Expansion Modules
NFC-CE6: Circuit Expander Module provides connections for
up to six Style Z (Class A) or Style Y (Class B) speaker circuits. Circuits are configured through the web-based programming utility.
NFC-BDA-25V: 25V, 50 watt audio amplifier module. Adding a
second speaker circuit increases the total NFC-50/100 power
output to 100 watts or can also be used as a backup amplifier.
NFC-BDA-70V: 70V, 50 watt audio amplifier module. Adding a
second speaker circuit increases the total NFC-50/100 power
output to 100 watts or can also be used as a backup amplifier.
NFC-XRM-70V: 70V Transformer Conversion Module. Converts the NFC-50/100(E) primary amplifier to a 70V output.
This transformer mounts directly to the NFC-50/100(E) main
control board by two metal brackets.
Control and Indicators
PUSH BUTTON CONTROLS
• All Call
• Message Select 1-14
• MNS Control
• Diagnostic Select
• System Control
• Trouble Silence
• Speaker Select 1-24
• Console Lamp Test
LED Status Indicators (visible with
door closed)
Fire System Active (green)
LOC/RPU/RM 1-8 Active
(green)
MNS Control (green)
Main Console Fault (yellow)
System Control (green)
AC Power (green)
System in Use (green)
Ground Fault (yellow)
Speaker Zone 1-24 Active
(green)
Charger Fault (yellow)
Speaker Zone 1-24 Fault
(yellow)
Battery Fault (yellow)
OK to Page (green)
Data Bus Fault (yellow)
Microphone Trouble (yellow)
NAC Fault (yellow)
Message 1-8 Active (red)
NAC Active (green)
Message 1-8 Fault (yellow)
System Trouble (yellow)
Remote Amplifier 1-8 Fault
(yellow)
Audio Riser Fault (yellow)
LOC/RPU/RM 1-8 Fault
(yellow)
NFC-125DA: Distributed (Remote) Audio Amplifier, 125 watts.
Please refer to the data sheet DN-60776 for more information.
NFC-125DAE: Export version. Distributed (Remote) Audio
Amplifier, 125 watts. (240 VAC, 50Hz). Please refer to the data
sheet DN-60776 for more information.
NFC-50/100DA: Distributed (Remote) Audio Amplifier with back
up, 50 watts/100 watts at 25Vrms or 70Vrms. Please refer to the
data sheet DN-60776 for more information.
NFC-50/100DAE: Export version. Distributed (Remote) Audio
Amplifier with back up, 50 watts/100 watts (240 VAC, 50Hz).
Please refer to the data sheet DN-60776 for more information.
NFC-BDA-BU: Expander card for ECC-50BDA remote amplifier
for 100 watt primary / 50 watt back up operation.Please refer to
the data sheet DN-60776 for more information.
NFC-CE4: Distributed Audio Speaker Circuit/Zone expander
module.
NFC-FFT: Fire Fighter Telephone System. Please refer to the
data sheet DN-60779 for more information.
NFC-RTZM: Remote Telephone Zone Module. Allows for
secure access to the NFC via cell phone or remote telephone
means; not UL listed.Please refer to the data sheet DN-60818
for more information.
SEISKIT-COMMENC: Seismic kit for the NFC-50/100.
Includes battery bracket for two 12 AH or 18 AH batteries.
LED Indicators (visible with door and
dress panel open)
N-FPJ: Remote Phone Jack.
• Speaker Volume Control Fault (yellow).
• Option Card Fault (yellow).
• Amplifier Over Current Fault (yellow).
FHSC-R: Fire Fighters Handset Cabinet Recessed.
Product Line Information
THUMBLTCH: Optional Thumb Latch. (Non UL-Listed).
NFC-50/100: (Primary Operating Console) 50 Watt, 25V single
speaker zone emergency voice evacuation system, integral
microphone, built in tone generator and 14 recordable messages.
CHG-75: 25 to 75 ampere-hours (AH) External Battery Charger.
NFC-50/100E: Export version (Primary Operating Console) 50
Watt, 25V single speaker zone emergency voice evacuation
system, integral microphone, built in tone generator and 14
recordable messages. (240 VAC, 50Hz).
BAT-1270: Battery,12 volt,7.0 AH (Two required).
NFC-CE6: Speaker Circuit/Zone Expander Module.
BAT-12260: Battery, 12 volt, 26.0 AH (Two required).
NFC-BDA-25V: 25V, 50 watt audio amplifier module. Adding a
second speaker circuit increases the total NFC-50/100 power
output to 100 watts or can also be used as a backup amplifier.
BB-26: Battery cabinet mounts up to two 26 AH batteries.
NFC-BDA-70V: 70V, 50 watt audio amplifier module. Adding a
second speaker circuit increases the total NFC-50/100 power
output to 100 watts or can also be used as a backup amplifier.
See product manual, part number LS10001-001NF-E for
detailed wiring requirements.
NFC-XRM-70V: 70V Transformer Conversion Module. Converts the NFC-50/100(E) primary amplifier to a 70V output.
This transformer mounts directly to the NFC-50/100(E) main
control board by two metal brackets.
NFC-LOC: Local Operator Console (Complete user interface),
Please refer to the data sheet DN-60777 for more information.
NFC-RPU: Remote Page Unit Hand held microphone, 14
message buttons. Please refer to the data sheet DN-60775 for
more information.
FHS-F: Fire Fighters Remote Handset.
FHSC-S: Fire Fighters Handset Cabinet Surface Mount
TR-CE-B: Optional Trim Ring.
CHG-120: 25-120 ampere-hours (AH) External Battery Charger.
ECC-MICROPHONE: Replacement Microphone only.
BAT-12120: Battery,12 volt,12.0 AH (Two required).
BAT-12180: Battery,12 volt, 18.0 AH (Two required).
Wiring Requirements
Total System Capacity: (NFC-50/100(E)
only)
•
•
•
•
•
•
Total Built-in Audio Power: 50 Watts.
Total Expandable Audio Power: 100 Watts.
Total Built-in Speaker Circuits: 2.
Total Expandable Speaker Circuits: 8.
Audio Message Max Time Duration: 60 seconds.
External Audio Input: 1.
NFC-RM: Remote Microphone only. Please refer to the data
sheet DN-60778 for more information.
Total System Capacity: (Fully Loaded
System)
NFC-50DA: Distributed (Remote) Audio Amplifier, 50 watts.
Please refer to the data sheet DN-60776 for more information.
•
•
•
•
NFC-50DAE: Export version. Distributed (Remote) Audio
Amplifier, 50 watts. (240 VAC, 50Hz). Please refer to the data
sheet DN-60776 for more information.
Total Distributed Audio Power: 1100 Watts.
Total Speaker Circuits Per System: 24.
Total Remote Consoles Supported: 8.
Total Distributed Audio Amplifiers Supported: 8.
DN-60772:A6 • 10/23/2015 — Page 3 of 6
horns/strobes
Internal options
NAC Circuit
TB19
NFC-BDA25/70V
optional amplifier
Speaker Circuits
TB20 & TB21
NFC-CE6 circuit expander
NFC-FFT firefighter telephone
remote
NFC-LOC
consoles local operator console
NFC-RPU
remote paging unit
NFC-RM
remote microphone
TB4
TB12
external battery
charger - J7
distributed audio
TB22
NFC-50DA 50W
CHG-120 charger
remote amplifier
NFC-125DA 125W
remote amplifier
NFC-50/100DA
50/100W remote
amplifier
CHG-75 charger
NFC-50/100(E) FirstCommand (Possible Configurations)
Page 4 of 6 — DN-60772:A6 • 10/23/2015
• End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252) required
for Style Y (Class B) operation.
Electrical Specifications
PRIMARY (AC) POWER (TB15)
NFC-50/100: 120 VAC, 60 Hz, 3.5 amps.
Speaker Circuits
NFC-50/100E: 240 VAC, 50 Hz, 2.0 amps.
• Primary Speaker Circuit (TB20)
• Secondary Speaker Circuit (TB21) (with optional amplifier
only).
– Circuit can be wired Style Y (Class B) or Style Z (Class A).
– Power-limited circuitry.
– Normal Operating Voltage: 25 VRMS @ 2 amps max and
maximum Load Impedance of 12.5Ω (70V @ 700 mA
max. with maximum load Impedance of 100Ω operation
possible by plugging optional NFC-XRM-70V conversion
transformer into J12 of the main control board).
– Output Power: 50 watts (10 watts when background
music is employed).
– Frequency Range: 400Hz - 4,000Hz.
– Maximum total capacitance for each speaker circuit: 250
µF.
– End-of-Line Resistor required for Style Y circuit: 15 KΩ, 1
watt (P/N: ELR-15K).
Wire size: minimum #14 AWG (2.00mm2) with 600 V insulation.
SECONDARY POWER (BATTERY) CHARGING CIRCUIT (J7)
•
•
•
•
Supports lead-acid batteries only.
Float charge voltage at 27.3V
Maximum charge current: 1.0 Amp
Maximum battery charge capability: 2.8 Amps, 26AH (NFC
cabinet holds max. 18AH battery).
• Minimum Battery size:12 Amp Hour.
AC LOSS RELAY CONTACT RATING (TB3)
• 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
FORM C - TROUBLE RELAY CONTACT RATING (TB2)
• 2.0 amps @ 30 VDC (resistive), 0.5 amp @ 30 VAC (resistive).
MNS ACTIVE RELAY CONTACT RATING (TB1)
• 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
NOTIFICATION APPLIANCE CIRCUIT (NAC) OUTPUT
RATING (TB19)
•
•
•
•
One (1) Style Y (Class B) or Style Z (Class A) circuit.
Power-limited circuitry, (Class 2) supervised.
Nominal operating voltage: 24 VDC.
Maximum signaling current for special application power:
2.0A.
• Maximum signaling current for regulated power: 200mA.
• Maximum wiring impedance: 1Ω.
• Current limit: fuse-less, electronic, power-limited.
• End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252) required
for Style Y (Class B) operation.
Refer to the Device Compatibility Document 15378 for listed
compatible devices.
NAC FOLLOWER OUTPUT REMOTE SYNC (TB18)
• Connections for FACP NAC synchronization trigger signal.
• Output terminals: pass-through to other system components.
• Trigger input voltage: 9 to 32 VDC, 24 VDC rated.
• Input current draw in Alarm condition: 10 mA at rated voltage.
SPECIAL
(TB17)
APPLICATION
POWER
(AUX.
POWER)
• 500 mA @ 24 VDC.
• Used for powering addressable modules and associated
End-of-Line power supervision relays.
Power-limited circuitry. Refer to the Device Compatibility Document 15378 for a list of compatible devices.
Command Input Circuits (alarm polarities shown)
CMD1 - TB4 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals which provide feed
through of the NAC circuits to NAC devices down stream.
CMD2 - TB5 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals which provide feed
through of the NAC circuits to NAC devices downstream.
CMD3 - TB6 Terminals 1(+) & 2(-) are input terminals for contact closure only.
CMD4 - TB6 Terminals 3(+) & 4(-) are input terminals for contact closure only.
CMD5 - TB7 Terminals 1(+) & 2(-) are input terminals for contact closure only.
CMD6 - TB7 Terminals 3(+) & 4(-) are input terminals for contact closure only.
CMD7 - TB8 Terminals 1(+) & 2(-) are input terminals for contact closure only.
CMD8 - TB8 Terminals 3(+) & 4(-) are input terminals for contact closure only.
• Power-limited and supervised circuitry.
• Normal Operating Voltage Range: 10.5 VDC - 29 VDC;
(Maximum Voltage: 29 VDC).
• NAC Reverse Polarity Current (requires End-of-Line Resistor from NAC): 1.6 mA maximum.
• Contact Closure Operation Current (requires 4.7KΩ, ½ watt
End-of-Line Resistor P/N 27072): 6.6 mA maximum.
• Maximum Wiring Impedance CMD1 - CMD8 (Contact Closure Operation): 200Ω.
NOTE: When the system is programmed for Mass Notification,
CMD1and CMD2 will be programmed for Reverse Polarity only.
See manual P/N LS10001-001NF-E for more details.
SPEAKER VOLUME CONTROL OVERRIDE (TB23)
MAXIMUM INPUT IMPEDANCE:
•
•
•
•
•
•
• CMD1 & CMD2 (Reverse Polarity Operation): 20KΩ.
• CMD1 - CMD8 (Contact Closure Operation): 4.75KΩ.
Style Y (Class B) or Style Z (Class A) circuit.
Special application power.
Power-limited circuitry, supervised.
Nominal operating voltage: 24 VDC.
Maximum signaling current: 0.25 amps.
Current limit: fuse-less, electronic, power-limited.
NIGHT RING INPUT - TB16, TERMINALS 1 (+) & 2 (-)
• Contact closure input.
• Isolated, non-supervised.
• Operation current: 3.8 mA, maximum.
DN-60772:A6 • 10/23/2015 — Page 5 of 6
• Maximum wiring impedance: 30KΩ.
• Minimum isolation withstand voltage: 1500 VRMS.
EXTERNAL OPERATOR INTERFACE POWER OUTPUT
(TB24)
• Non-resettable power for external operator interface components.
• Power-limited circuitry, non-supervised.
• Nominal operating voltage: 24 VDC.
• Maximum output current: 0.80 amps.
• Current limit: fuse-less, electronic, power-limited circuit.
EXTERNAL DATA BUS (EIA-485) (TB12)
•
•
•
•
Data connections for external operator interface components.
Redundant transceiver circuitry for Class A operability.
Power-limited circuitry, supervised.
Maximum wiring impedance: 13.2Ω
FACP DATA BUS (EIA-485) (TB13)
•
•
•
•
•
•
•
•
•
•
•
Dedicated connection to FACP serial bus.
Output terminals: pass-through to other system components.
Isolated, supervised.
Minimum isolation withstand voltage: 1500 VRMS.
Maximum wiring impedance: 40Ω (ANN-BUS), 26Ω (ACS-BUS).
External Audio Riser (TB22).
Style Y (Class B) or Style Z (Class A) audio connections to
external operator interface components.
Power-limited circuitry, supervised.
Audio signal level: 3.85 V, maximum.
Frequency range: 400 Hz - 4 KHz RMS.
Frequency range (NFC-50/125DA): 800Hz - 2KHz RMS.
EXTERNAL AUDIO INPUT (TB5)
• Input Impedance: 8.5KΩ nominal @1KHz
• Input Voltage: 700 mV rms maximum
• Input Current: 0.1 mA maximum @ 700 mV
NOTE: Some laptops/personal computers only provide an audio
output for headphones. It may be necessary to adjust the headphone output level for proper recording of voice messages.
NFC-CE6 Circuit Expander Module
Specifications
• Power-limited circuitry.
• Up to six (6) circuits on the NFC-CE6 can be wired as Style
Y (Class B) or Style Z (Class A).
• Normal Operating Voltage for Speaker Circuits: 25 [email protected] 2.0
amps max. (Maximum Load Impedance of 12.5Ω).
• 70.0 V @ 700 mA max. with maximum Load Impedance of
100Ω operation possible for the primary circuit by plugging
in an optional NFC-XRM-70V conversion transformer into
J12 of the main control board. The same operation is possible for the optional 50W amplifier by selecting the NFCBDA-70V model.
• Speaker circuit wiring is supervised during standby, background music, and alarm.
• Output Power: 50 watts total; Frequency Range: 400Hz 4,000Hz.
• Maximum total capacitance: 250 µF. (Note that the total
capacitance for the speaker outputs must not exceed the
maximum of 250 µF).
• End-of-Line Resistor required for Style Y (Class B) speaker
circuit: 15 KΩ, 1 watt (P/N: ELR-15K) TB13 on the main
control board: ACS/ANN (EIA-485) electrically isolated link
to FACP provides programmed speaker control.
Cabinet Specifications
• Backbox: 19.0"(48.26 cm) high x 16.65"(42.29 cm) wide x
5.20"(13.23 cm) deep.
• Door: 19.26” (48.92 cm) high x 16.82”(42.73 cm) wide x
0.12”(0.30 cm) deep.
• Trim Ring (TR-CE-B): 22.00” (55.88 cm) high x 19.65”
(49.91 cm) wide.
Shipping Specifications
Base Unit Weight: 27.85 lbs (12.63 kg).
Temperature and Humidity ranges
This system meets NFPA requirements for operation at 0-49º
C/32-120º F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature
ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with
a normal room temperature of 15-27º C/60-80º F.
Agency Listings and Approvals
The listings and approvals below apply to the basic NFC-50/
100(E) control panel. In some cases, certain modules may not
be listed by certain approval agencies or listing may be in process. Consult factory for latest listing status.
•
•
•
•
UL/ULC Listed S635.
Compliant with UFC 4-021-01.
CSFM: 6911-0028:0265.
NYC Fire Dept.Certificate of Approval: #6163
Standards and Codes
The NFC-50/100(E) complies with the following UL Standards,
NFPA 72, International Building Codes, and California Building
Codes.
• UL 864.
• UL 2572.
• IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
• CBC 2007 (Seismic)
First Command® and Notifier® are registered trademarks of Honeywell
International Inc.
©2015 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 6 of 6 — DN-60772:A6 • 10/23/2015
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
6911-0028:0265
Page 1 of 1
CATEGORY:
6911 -- VOICE COMMUNICATION SYSTEMS CONTROL UNITS
LISTEE:
NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: [email protected]
DESIGN:
Models NFC-50/100 and NFC-50/100E. These are 50-watt audio emergency voice evacuation
panels expandable to 100-watt for fire applications, mass notification applications, or both.
Refer to listee's data sheet for additional detailed product description and operational
considerations. System components:
ECC-MCB; Main Control Board
ECC-DKVCM; Display Board
NFC-BDA-25V; Amplifier Module 25 VRMS
NFC-BDA-70V; Amplifier Module 70 VRMS
NFC-CE6; Speaker Circuit Expander Module
NFC-XRM-70V; Transformer Module 70.7 VRMS
RATING:
Primary Operating: 120 V, 60 Hz, 3.5 A or 240 V, 50 Hz, 2 A
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical rating, and UL label.
APPROVAL:
Listed as voice communication systems for use with separately listed compatible fire alarm
control units to provide emergency voice evacuation signals. Refer to listee’s Installation
Instruction Manual for details.
XLF:
6911-0075:0226
08-06-13 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
DN-60548:B2
LCD2-80
Liquid Crystal Display
Terminal Mode Annunciator
Annunciators
General
The LCD2-80 is a backlit LCD annunciator for the NOTIFIER
fire alarm control panels, or network control annunciators that
support the 80-character display format. LCD2-80s may be
connected onto the four-wire EIA-485 terminal port.
The LCD2-80 mimics the display of NFS2-640, NFS2-3030,
NFS-320, NCA-2 and legacy panels that supported the LCD80/LCD-80TM. The NFS2-3030 and the NCA-2 also support
LCD2-80s when set for LCD-80 supervision. Up to 32 LCD280s can annunciate and provide remote reset, acknowledge,
drill and silence of the control panel from remote locations.
NOTE: The LCD2-80 can be used with legacy panels that supported the LCD-80 terminal mode operation. Please refer to the
LCD2-80 manual for more information.
• 80-character backlit Liquid Crystal Display (20 characters x
4 lines).
• Display mimics panel or NCA
– Event message.
– 20 characters for point label.
– 12 characters for extended label.
– Time, date and point address.
• Control switches for System Acknowledge, Signal Silence
Drill and System Reset.
• Up to 6000 foot segments between units.
• Local piezo sounder with alarm/trouble resound.
• Displays all analog, addressable points.
• Displays device type identifiers.
• Displays device and zone custom alpha labels.
• LCD2-80 mounts with any CHS-4 chassis slot.
• Slide-in label can be customized.
• LEDS for general off-normal events with UL 864 9th Edition
Panels.
JCILCD2-80.jpg
Features
NOTE: The LEDs are only applicable when used with UL 864
Ninth Edition listed panels: NFS-320, NFS2-640, NFS2-3030 and
NCA-2.
• Flush/surface/panel mount option.
• No programming necessary. LCD2-80 displays time, date,
and custom messages received from the compatible panel
or network annunciator.
• LCD2-80 is 8.25" (20.96 cm) high, 4.375" (11.11 cm) wide,
and 1.75" (4.45 cm) deep.
• Up to 32 LCD2-80s may be used on one EIA-485 circuit.
NOTE: Must have sufficient regulated 24 volt power.
6,000 ft (1828.8 m)
Maximum wire length between each LCD2-80
EIA-485
(2 wires)
24 VDC
(2 wires)
EIA-485 return (2 wires)
NFS-320, NFS2-640, NFS2-3030, or NCA-2 connecting to LCD2-80
DN-60548:B2 • 05/25/12 — Page 1 of 2
The ABF-1DB Backbox
The ABF-1DB is a semi-flush-mount backbox for the NOTIFIER LCD2-80 Series Annunciator. The ABF-1DB mounts one
LCD2-80. It includes an attractive smoked-glass door with
NOTIFIER keylock.
ABF-2DB: Annunciator semi-flush mount backbox. Black with
a smoked glass door with a keylock.
AKS-1B: Key Switch (black) to enable/disable controls when
mounted in ABF-1B or ABS-1TB.
Dimensions, BOX only:
Agency Listings and Approvals
9.938" (25.24 cm) high, 4.625" (11.75 cm) wide, 2.5" (6.35 cm)
deep.
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
Dimensions, DOOR only:
10.713" (27.21 cm) high, 6.0" (15.24 cm) wide, 0.75" (1.9 cm)
deep.
Related Options
ABF-1DB: Semi-flush box with alternative smoked-glass
door, any keylock.
•
•
•
•
•
UL Listed: S635
ULC Listed: S635
FDNY: COA# 6067, 6065
CSFM: 7165-0028:0243, 7165-0028-0224
FM Approved
ADP-4B: Annunciator dress plate, black. Allows panel mounting of up to four LCD2-80 modules in a CAB-4 Series cabinet.
ABF-1B: Annunciator flush box, 9.938" (25.24 cm) high,
4.625" (11.75 cm) wide, and 2.5" (6.35 cm) deep. Order AKS1B key switch and APJ-1B phone jack if desired. Can also be
mounted in ABF-2B or ABF-4B annunciator backboxes.
ABS-1TB: Deep surface backbox (mounts one LCD2-80).
ABS-2B: Annunciator surface box, 8.5" (21.59 cm) high x
8.92" (22.66 cm) x 2" (5.08 cm) deep. Knockouts are provided
for use with 1/2" (1.27 cm) conduit. The annunciators mount
directly to the ABS-2B without a dress plate.
ABS-2D: Annunciator backbox, surface, black.
ABF-2B: Annunciator flush box, 9.938" (25.24 cm) high x
9.188" (23.34 cm) wide x 3.75" (9.525 cm) deep. Includes a
painted metal trim plate [11" (27.94 cm) high x 10.625" (26.99
cm) wide] and adhesive-backed annunciator label.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-60548:B2 • 05/25/12
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7165-0028:0224
Page 1 of 4
CATEGORY:
7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE:
NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: [email protected]
DESIGN:
Model NFS-3030, NFS-3030E, NFS2-3030, NFS2-3030E fire alarm control units. Local,
auxiliary, remote station (PPU), proprietary (PPU), central station (PPU), automatic, manual,
waterflow and sprinkler supervisory services. Suitable for use as a releasing service,
Emergency Voice/Alarm Communication System and Process/Energy Management
Equipment. Refer to listee's data sheet for detailed product description and operational
considerations. System components:
AA-30/-100/-120; Amplifiers
ACM-8R/-16AT/-24AT/-32A/-48A; Annunciator Control Modules
ACPS-610; Addressable/Charger Power Supply
ACPS-2406; Addressable Charger/Power Supply
ACT-1/-2/-4/-25/-70; Audio Coupling Transformer
ADDR-B4/-B4R/-C4/-C4R/-D4/-D4R; Doors
AEM-16AT/-24AT/-32A/-48A; Annunciator Expander Modules
AFM-16A/-16AT/-32A; Annunciator Fixed Modules
AKS-1B; Annunciator Key Switch
AMG-1/-E; Audio Message Generator
AMPS-24, CPS-24; Addressable Main Power Supply
APS-6R, APS2-6R; Auxiliary Power Supply
ARM-4; Auxiliary Relay Module
BDA-25V/-70V; Backup Digital Audio Amplifiers
BGRA-SCS, BGRB-SCS, CEF-SCS, RSA-SCS, RSB-SCS, RSC-SCS, RSD-SCS,
RSE-SCS; Smoke Control Station
BB-17/-25/-100/-200; Battery Box
BMP-1; Blank Module
BP-4; Battery Panel
BP2-4; Dress Panel
CA-1/-2; Chassis
CAB-3/4 Series, EQ Series; Enclosures
*CAB-RP, CAB-RPR; Cabinets
CHG-120; Battery Charger
CHS-4L/-4MB/-4N/-6/-M3/-PS/-BH1; Chassis
CMIC-1, CMIC-RP*; Microphone Assembly
CPU2-3030D/CPU2-3030ND; CPU Board
*Rev. 05-08-12 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
Listing No.
7165-0028:0224
Page 2 of 4
CRE-4; Control Relay Expander
CRM-4RK; Control Relay Module
CRT-2; Display Terminal
DAA-5025/-5070; Digital Audio Amplifiers
DAA-5025F/DAA-5025SF; Digital Audio Amplifiers, Fiber Mode
DAA-5070F/DAA-5070SF; Digital Audio Amplifiers, Fiber Mode
DAA2-5025/-5070/-7525; Digital Audio Amplifiers
DAA-7525, DAA-7525F, DAA-7525SF Series; Digital Audio Amplifiers
DAA-PS; Power Supply
DAX-3525/-3570/-5025/-5070; Digital Audio Amplifiers
DCM-4RK; Dual Channel Module
DP-1B; Blank Panel
DP-DISP; Display Dress Panel
DR-A4, DR-A4B, DR-A4BR, DR-A4R; Door Assembly
DR-AA4, DR-AA4B, DR-AA4BR, DR-AA4R; Door Assembly
DR-B3F; Door Assembly
DR-B4, DR-B4B, DR-B4BR, DR-B4R; Door Assembly
DR-C4, DR-C4B, DR-C4BR, DR-C4R; Door Assembly
DR-D4, DR-D4B, DR-D4BR, DR-D4R; Door Assembly
DS-AMP/E; Digital Series Audio Amplifier
DS-BDA; Digital Series Backup Amplifier
DS-DB; Digital Series Distribution Board
DS-FM, DS-RFM, DS-SFM; Digital Series Fiber Module
DPDW-1B, DPSW-1B, XPDP; Dress Panels
VP-2B, DPA-1/-1A4/-2; Dress Panels
DPI-232; Direct Panel Interface
DVC-AO; Digital Voice Command
DVC-EM; Extended Memory
DVC-EMF/DVC-EMSF; Digital Voice Command/Ext Memory
DVC-KD; Keypad Board
*DVC-RPU; Remote Paging Unit
EQBB-B4, EQBB-C4, EQBB-D4; Backbox Assembly
EQDR-B4, EQDR-C4, EQDR-D4; Door Assembly
FCM-1-REL; Releasing Control Module
FCPS-24S6/S8; Field Charger/Power Supply
FFT-7/-7S; Fire Fighter's Telephones
FIRSTVISION-LCD; Interactive Firefighters’ Display
FIRSTVISION-ENC; FirstVision Backbox Enclosure and Door
FMM-4-20; Analog Input Module
FHS; Fireman's Handset
FCM-1; Addressable control module
FDM-1; Dual monitor module
FDRM-1*; Dual Relay/Monitor Module
FMM-1; Monitor module
FMM-101; Miniature monitor module
*Rev. 05-08-12 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
Listing No.
7165-0028:0224
Page 3 of 4
FRM-1; Addressable relay module
FTM-1; Firephone Control Module
FPJ; Fireman's Phone Jack
FZM-1; Two-wire detector monitor module
HS-NCM-W/-MF/SF/-WMF/-WSF/-MFSF; High Speed Network Control Modules
ICE-4; Indicating Control Expander
ICM-4RK; Indicating Circuit Module
IPDACT-2/-2UD/IPENC; IP Digital Alarm Communicator
ISO-X; Isolator Module
IZE-A; Initiating Zone Expander
IZM-8RK; Initiating Zone Module
LCD-80, -160; Liquid Crystal Display Module
LCD2-80; Liquid Crystal Display
LCM-320; Loop Control Module
LDM-32/-E32/-R32; Lamp Driver Module
LEM-320; Loop Expander Module
MP-1B; Blank Panel
MPS-24B; Power Supply Module
NBG-12; Series Addressable Manual Pull Station
NBG-12LX; Manual pull station, addressable. See DN-6726
NCA/NCA-2; Network Control Annunciator
NCM-W/-F; Network Control Module
NCS4-W-ONYX, NCS4-F-ONYX; Network Control Station, Wire/Fiber
NCS5-W-ONYX, NCS5-F-ONYX; Network Control Station, Wire/Fiber
ONYXWorks-EW/-NW/NF/-HNW/-HNMF/-HNSF/-TS/-EW-TS/-NF-TS/-HW-TS/-HNMFT/
-HNSFT/- HNWT; Graphics PC workstation for NOTI-FIRE-NET Wire/Fiber/with Touch-screen
monitors
N-ELR; End of Line Resistors
NFS-LBB/-LBBR; Battery Box
PRN-6; Printer
R-120/-2.2K/-27K/-470/-47K; End of Line Resistors
RA-400/-400Z; Remote Annunciators
RKS-S; Remote Security Keyswitch
RM-1/-1SA; Remote Microphone
RPJ-1; Remote Paging Jack
RPT-W/-F/-485W/-485WF; Repeater
SBB-A3F; Backbox Assembly
SBB-A4, SBB-A4R, SBB-AA4, SBB-AA4R; Backbox Assembly
SBB-B4, SBB-B4R-L8, SBB-C4, SBB-C4R; Backbox Assembly
SBB-D4, SBB-D4R; Backbox Assembly
SCS-8; Smoke Control Station
SCS-8L; Smoke Control Lamp Driver Station
SCE-8; Smoke Control Expander
SCE-8L; Smoke Control Expander Lamp
STS-1; Security Tamper Switch
*Rev. 05-08-12 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
Listing No.
7165-0028:0224
Page 4 of 4
TM-4; Transmitter Module
TR-A4/-B3N/-B4/-C4/-D3N/-D4; Trim Ring
UDACT, UDACT-2; Universal DACT
UZC-256/BB--UZC; Universal Zone Coder/Backbox
VCE-4; Voice Control Expander
VCM-4RK; Voice Control Module
VS4095/5; Keltron Remote Printer
XP5-C/-M; Transponder
XPC-8; Transponder Control Module
XPIQ; Transponder Quad Intelligent Audio Module
XPM-8/-8L; Transponder Monitor Modules
XPP-1; Transponder Processor
XPR-8; Transponder Relay Module
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical rating and UL label.
APPROVAL:
Listed as fire alarm control units suitable for high rise applications for use with separately
listed compatible initiating and indicating devices. This control unit can generate the temporal
code pattern fire alarm signal as required per NFPA 72, 2002 Edition. Refer to listee's
Installation Instructions Manual for details.
This control unit meets the requirements of UL Standard 864, 9th Edition.
NOTE:
1. For Fire Alarm Verification feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.
2. Combined with Listing No. 7170-0028:223
*Rev. 05-08-12 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
dn-6927:a
FCPS-24S6(C/E) & FCPS24S8(C/E)
6- & 8-Amp 24-Volt
Remote Power Supplies
Power Supplies
General
The FCPS-24S6E (6-amp) and FCPS-24S8E (8-amp) are
remote power supplies with battery charger. The FCPS-24S6/24S8 may be connected to any 12 or 24 volt fire alarm control
panel (FACP) or may be used as stand-alone supplies. Primary applications include notification appliance (bell) circuit
(NAC) expansion (to support ADA requirements and NAC synchronization) or auxiliary power to support 24 volt system
accessories. The FCPS-24S6/-24S8 provides regulated and
filtered 24 VDC power to four notification appliance circuits
configured as either four Class B (Style Y) or Class A (Style Z,
with ZNAC-4 option module). Alternately, the four outputs may
be configured as all non-resettable, all resettable or two nonresettable and two resettable. The FCPS-24S6/-24S8 also
contains a battery charger capable of charging up to 18 AH
batteries. FCPS-24S6C & FCPS-24S8C are ULC-listed.
NOTE: Unless otherwise specified, the terms FCPS-24S6 and
FCPS-24S8 used in this document refers to the standard FCPS24S6 and FCPS-24S8, FCPS-24S6C and FCPS-24S8C, the
FCPS-24S6E and FCPS-24S8E
Features
• UL-Listed NAC synchronization using System Sensor,
Wheelock, or Gentex “Commander2” appliances.
• Operates as a “sync-follower” or as a “sync-generator”
(default). See note on page 2.
• Contains two fully-isolated input/control circuits - triggered
from FACP NAC (NAC expander mode) or jumped permanently “ON” (stand-alone mode).
• Four Class B (Style Y) or four Class A (Style Z, with
ZNAC-4 module) NACs.
• 6-amp (FCPS-24S6) or 8-amp (FCPS-24S8) full load output, with 3 amps maximum/circuit, in NAC expander mode
(UL 864).
• 4-amp (FCPS-24S6) or 6-amp (FCPS-24S8) continuous
output in stand-alone mode (UL 1481).
• Compatible with coded inputs; signals passed through.
• Optional power-supervision relay (EOLR-1).
• In stand-alone mode, output power circuits may be configured as: resettable, (reset line from FACP required),
non-resettable, or a mix of two and two.
• Fully regulated and filtered power output - optimal for powering four-wire smoke detectors, annunciators, and other
system peripherals requiring regulated/filtered power.
• Power-limiting technology meets UL power-limiting requirements.
• Form-C normally-closed trouble relay.
• Fully supervised power supply, battery, and NACs.
• Selectable earth fault detection.
• AC trouble report selectable for immediate 2-hour delay.
• Works with virtually any UL 864 fire alarm control which utilizes an industry-standard reverse-polarity notification circuit (including unfiltered and unregulated bell power).
• Requires input trigger voltage of 9 - 32 VDC.
• Self-contained in compact, locking cabinet - 15”H x 14.5”W
x 2.75”D (cm: 38.1H x 36.83W x 6.985D).
6927pho1.jpg
• Includes integral battery charger capable of charging up to
18 AH batteries. Cabinet capable of housing 7.0 AH batteries.
• Battery charger may be disabled via DIP switch for applications requiring larger batteries.
• Fixed, clamp-type terminal blocks accommodate up to 12
AWG (3.1mm2) wire.
Specifications
Primary (AC) Power:
• FCPS-24S6C/-24S8C: 120 VAC, 60 Hz, 3.2A maximum.
• FCPS-24S6E/-24S8E: 240 VAC, 50 Hz, 1.6A maximum.
• Wire Size: minimum #14 AWG (2.0mm2) with 600 V insulation.
Control Input Circuit:
• Trigger Input Voltage: 9 to 32 VDC.
• Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9
- 16 V).
Trouble Contact Rating: 5 A at 24 VDC.
Auxiliary Power Output: Specific application power 500 mA
maximum.
Output Circuits:
• +24 VDC filtered, regulated.
• 3.0 A maximum for any one circuit.
• Total continuous current for all outputs (stand-alone mode):
– FCPS-24S6: 4.0 A maximum.
– FCPS-24S8: 6.0 A maximum.
• Total short-term current for all outputs (NAC expander mode):
– FCPS-24S6: 6.0 A maximum.
– FCPS-24S8: 8.0 A maximum.
Secondary Power (Battery) Charging Circuit:
• Supports lead-acid batteries only.
• Float-charge voltage: 27.6 VDC.
dn-6927:a • 04/30/09 — Page 1 of 2
• Maximum current charge: 1.5 A.
• Maximum battery capacity: 18 AH.
Applications
Example 1: Expand notification appliance power an additional
6.0 A (FCPS-24S6) or 8.0 A (FCPS-24S8). Use up to four
Class B (Style Y) outputs or four Class A (Style Z) outputs
(using ZNAC-4). For example, the FACP notification appliance
circuits will activate the FCPS when reverse-polarity activation
occurs. Trouble conditions on the FCPS are sensed by the
FACP through the notification appliance circuit.
Example 2: Use the FCPS to expand auxiliary regulated 24volt system power up to 4.0 A (FCPS-24S6) or up to 6.0 A
(FCPS-24S8). Both resettable and non-resettable power
options are available. Resettable outputs are created by connecting the resettable output from the FACP to one or both of
the FCPS inputs.
Example 3: Use addressable control modules to activate the
FCPS instead of activating it through the FACP notification
appliance circuits. This typically allows for mounting the FCPS
at greater distances* away from the FACP while expanding
system architecture in various applications.
Standards and Codes
The FCPS-24S6 and FCPS-24S8 comply with the following
standards:
• NFPA 72 National Fire Alarm Code.
• UL 864 Standard for Control Units for Fire Alarm Systems
(NAC expander mode).
• UL 1481 Power Supplies for Fire Alarm Systems.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
•
•
•
•
•
UL Listed: S635, S674
ULC Listed: S635 (FCPS-24S6C & FCPS-24S8C)
CSFM Approved: 7315-0028:225
MEA: 299-02-E
FM Approved
Ordering Information
For example, an addressable control module is used to activate the FCPS, and an addressable monitor module is used to
sense FCPS trouble conditions. Local auxiliary power output
from the FCPS provides power to the addressable control
module.
FCPS-24S6: 6.0 A, 120 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
*NOTE: Addressable FACPs are capable of locating control and
monitor modules at distances of up to 12,500 feet (3,810 meters).
FCPS-24S6R: Same as FCPS-24S6 with red enclosure.
Sync Follower/Generator Note
In some installations, it is necessary to synchronize the flash
timing of all strobes in the system for ADA compliance.
Strobes accomplish this by monitoring very short timing pulses
on the NAC power which are created by the FACP. When
installed at the end of a NAC wire run, the FCPS-24S6/-24S8
can track (i.e. “follow”) the strobe synchronization timing
pulses on the existing NAC wire run. This maintains the overall
system flash timing of the additional strobes attaches to the
FCPS.
FCPS-24S6C: Same as above, ULC-listed.
FCPS-24S6E: 6.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
FCPS-24S8: 8.0 A, 120 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
FCPS-24S8C Same as above, ULC-listed.
FCPS-24S8R: Same as FCPS-24S8 with red enclosure.
When the FCPS-24S6/-24S8 is configured (via DIP switch settings) as a “sync follower,” the FCPS’s NAC outputs track the
strobe synchronization pulses present at the FCPS’s sync
input terminal. The pulses originate from an upstream FACP or
other power supply.
FCPS-24S8E: 8.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15”H x 14.5”W x 2.75”D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
When the FCPS-24S6/-24S8 are configured (via DIP switch
settings) as a “sync generator,” the FCPS’s sync input terminals are not used. Rather, the FCPS is the originator of the
strobe synchronization pulses on the FCPS’s NAC outputs. In
“sync generator” mode, the sync type (System Sensor, Wheelock, or Gentex) is selectable via DIP switch settings.
EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire
smoke detector power.
ZNAC-4: Class A (Style Y) NAC option module.
BAT-1270: Battery, 12-volt, 7.0 AH (two required, see BAT
Series data sheet DN-6933).
PS-1270: Battery, 12-volt, 7.0 AH (two required, see PS
Series data sheet DN-1109)
System Sensor® and NOTIFIER® are registered trademarks of Honeywell
International Inc.
©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — dn-6927:a • 04/30/09
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7315-0028:0225
Page 1 of 1
CATEGORY:
7315 -- POWER UNITS
LISTEE:
NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: [email protected]
DESIGN:
Models FCPS-24S6 and FCPS-24S8 are power limited power supply/battery chargers used
for supervision and expanded power driving capability of up to four Notification Appliance
Circuits (FACP Fire Circuits, Signaling Devices) or resettable/non resettable outputs. Model
ZNAC-4 Class A converter. Refer to listee’s data sheet for additional detailed product
description and operational considerations.
RATING:
120 VAC, 24 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical rating and UL label.
APPROVAL:
Listed as a Power Supply/Battery Charger for use with separately listed compatible fire alarm
control units.
XLF:
7315-0075:0206
1-24-03KK
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
DN-6937:D
FAPT-851(A)
Acclimate® Plus™ Multi-Sensor
Low-Profile Intelligent Detector
Intelligent/Addressable Devices
General
The Acclimate Plus detector uses a combination of photoelectric and thermal sensing technologies to increase immunity to
false alarms. Unlike traditional intelligent detectors, the Acclimate Plus detector has a microprocessor in the detector head
that processes alarm data. As a result, the Acclimate Plus
detector adjusts its sensitivity automatically, without operator
intervention or control panel programming.
Areas where the Acclimate Plus detector is especially useful
include office complexes, schools, college campuses, manufacturing and industrial facilities, and anywhere else the use of
a particular area may change. The Acclimate Plus detector
automatically adjusts its sensitivity to the environment.
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed to greatly enhance the speed of communication between analog intelligent devices and compatible
systems. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information,
the panel’s CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five
times that of earlier designs.
Features
• Automatically adjusts sensitivity levels without operator
intervention or programming. Sensitivity increases with
heat.
• Microprocessor-based, combination photo and thermal
technology.
• Compatible with all Notifier Onyx and CLIP series Fire
Alarm Control Panels (FACPs).
• Addressable-analog communication.
• Sleek, low-profile design.
• Two-wire SLC connection.
• Rotary, decimal addressing (1-99 on CLIP systems, 1-159
on FlashScan systems).
• Addresses can be viewed and changed without electronic
programmers.
• Dual bi-color LED design provides 360° viewing angle.
• LEDs lock red when in alarm. In FlashScan, LEDs flash
green in standby for normal condition.
• Built-in tamper-resistant feature.
• Constructed of off-white fire-resistant plastic, designed to
commercial standards, and offers an attractive appearance.
• SEMS screws for wiring of the separate base.
• Several base options, including relay, isolator, and sounder.
• Built-in functional test switch activated by external magnet.
• Listed to UL 268.
• Capable of heat-only alarm mode, enabled by a special
command from the panel. Smoke alarms are ignored.
• Low-temperature signal at 45°F +/– 10°F (7.22°C +/–
5.54°C).
FAPT-851(A) in B210LP(A) Base
FAPT-851 with B210.png
The Notifier FAPT-851(A) Acclimate® Plus™ detector is an
intelligent, addressable, multi-sensing, low-profile detector
designed for use with Notifier Notifier Onyx and CLIP series
Fire Alarm Control Panels (FACPs).
Specifications
Sensitivity: auto-adjusting levels: 1 to 2%/ft. and 2 to 4%/ft.
with classic CLIP systems; 1 to 2, 2 to 3, and 3 to 4%/ft. with
systems; fixed-sensitivity levels: 1, 2, and 4%/ft. with classic
CLIP systems; 0.5, 1, 2, 3, and 4%/ft. with FlashScan systems.
Size: 2.0" (5.3 cm) high; base determines diameter.
– B210LP(A): 6.1" (15.5 cm) diameter.
– B501(A): 4.1" (10.4 cm) diameter.
– B200S(A): 6.875" (17.46 cm) diameter.
– B200SR(A): 6.875" (17.46 cm) diameter.
– B224RB(A): 6.2" (15.748 cm) diameter.
Shipping weight: 5.2 oz. (147 g).
Operating temperature: 0°C to 38°C (32°F to 100°F).
UL-Listed velocity range: 0 – 4000 ft./min. (1219.2 m/min.),
suitable for installation in ducts.
Relative humidity: 10% – 93% noncondensing.
Thermal sensing rating: fixed-temperature setpoint 135°F
(57°C).
ELECTRICAL SPECIFICATIONS
Voltage range: 15 – 32 volts DC peak.
Standby current (max. avg.): 300 μA.
Loop resistance: 50 ohms maximum; varies according to
control panel used. Refer to panel installation manuals.
LED current (max.): 6.5 mA @ 24 VDC (“ON”).
Installation
The FAPT-851(A) plug-in detector uses a separate base to
simplify installation, service, and maintenance. A special tool
allows maintenance personnel to plug-in and remove detectors without using a ladder. Suitable mounting base boxes
include:
DN-6937:D • 12/07/2011 — Page 1 of 2
• 4.0" (10.16 cm) square box.
• 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box.
• Single-gang box (except relay or isolator base).
ACCESSORIES
NOTE: The FAPT-851(A) detector has the unique ability to adjust
sensitivity according to the environment, based on heat and
smoke levels. Avoid installing these detectors in locations that are
susceptible to rapid and high temperature changes. An example of
an incorrect application would be near or in line with the output of a
self-contained heater.
F110BP: Bulk pack of F110; package contains 15.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this. In some cases, certain modules or applications may not
be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
UL Listed: S1115.
ULC Listed: S1115.
MEA Listed: 225-02-E.
FM Approved.
CSFM: 7272-0028:0206.
U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0
(NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).
• Lloyd’s Register: 11/600013 (NFS2-640, NFS-320/NFS320C, excluding B210LP(A)).
• Maryland State Fire Marshal: Permit # 2122.
•
•
•
•
•
•
F110: Retrofit flange to convert B210LP to match the B710LP
profile, or to convert older high-profile bases to low-profile.
F210: Replacement flange for B210LP(A) base.
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Fits U.S.
single-gang electrical box. Supported by B210LP(A) and
B501(A) bases only.
SMB600: Surface mounting kit for use with B210LP(A).
M02-04-00: Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or
removal of FlashScan® Series detector heads from base in
high ceiling installations.
T55-127-010: Detector removal tool without pole.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524
m) sections.
Ordering Information
NOTE: “A” suffix indicates ULC Listed model.
FAPT-851: Low-profile intelligent multi-sensor detector.
FAPT-851A: Same as FAPT-851 but with ULC Listing.
INTELLIGENT BASES
NOTE: “A” suffix indicates ULC Listed model.
NOTE: For details about intelligent bases and their mounting, see
DN-60054.
B210LP(A): Plug-in detector base; standard U.S. flanged lowprofile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.
B501(A): Flangeless mounting base.
B501BP: Bulk pack of B501; package contains 10.
B200S(A): Intelligent, programmable sounder base capable of
producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone,
and custom tone.
B200SR(A): Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone.
Replaces B501BH series bases in retrofit applications.
B224RB(A): Relay base Screw terminals: up to 14 AWG (2.0
mm²). Relay type Form-C. Rating: 2.0 A @ 30 VDC resistive;
0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.
B224BI(A): Isolator base. Maximum: 25 devices between isolator bases.
Notifier®, ONYX®, FlashScan®, and Acclimate® are registered trademarks
and Acclimate Plus™ is a trademark of Honeywell International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6937:D • 12/07/2011
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7272-0028:0206
Page 1 of 1
CATEGORY:
7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE:
NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: [email protected]
DESIGN:
Models FSP-751, HPX-751, FSP-751T, FSH-751, FAPT-751, FAPT-851, FSP-851,
FSP-851R* and FSP-851T photoelectric type smoke detectors. Models FSP-751T and
FSP-851T employ a 135°F supplement integral heat sensor which only assists in a fire
situation. This thermal circuitry is NOT approved for use in lieu of a required heat detector.
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING:
24 VDC
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, product number, electrical rating and UL label.
APPROVAL:
Listed as photoelectric type smoke detector for use with listee's separately listed compatible
base and fire alarm control units. Models FSP-751, FSP-751T, FAPT-751, FAPT-851,
FSP-851, FSP-851R*, FSP-851T are suitable for open areas and inside duct installation with
air velocities between 0-4000 fpm. Model HPX-751 is suitable for open areas with air
velocities between 0-300 fpm. Model FSH-751 is suitable for open areas with air velocity
between 0-4000 fpm.
NOTE:
Combined with 7272-0028:208
The photoelectric type detectors are generally more effective at detecting slow, smoldering
fires that smolder for hours before bursting into flame. Sources of these fires may include
cigarettes burning in couches or bedding. The ionization type detectors are generally more
effective at detecting fast, flaming fires that consume combustible materials rapidly and
spread quickly. Sources of these fires may include paper burning in a waste container or a
grease fire in the kitchen.
*Rev. 01-07-2009 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
DN-6936:B • H-211
FST-851(A) Series
Intelligent Thermal (Heat) Detectors
with FlashScan®
Intelligent / Addressable Devices
Notifier FST-851(A) Series intelligent plug-in thermal detectors
with integral communication has features that surpass conventional detectors. Point ID capability allows each detector’s
address to be set with rotary, decimal address switches, providing exact detector locations. FST-851(A) Series thermal
detectors use an innovative thermistor sensing circuit to produce 135°F/57°C fixed-temperature (FST-851/A) and rate-ofrise thermal detection (FST-851R/A) in a low-profile package.
FST-851H(A) provides fixed high-temperature detection at
190°F/88°C. These thermal detectors provide effective, intelligent property protection in a variety of applications. FST851(A) Series detectors are compatible with Notifier Onyx and
CLIP series Fire Alarm Control Panels (FACPs).
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by Notifier Engineering that greatly enhances
the speed of communication between analog intelligent
devices and certain NOTIFIER systems. Intelligent devices
communicate in a grouped fashion. If one of the devices within
the group has new information, the panel’s CPU stops the
group poll and concentrates on single points. The net effect is
response speed greater than five times that of earlier designs.
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Sleek, low-profile, stylish design.
State-of-the-art thermistor technology for fast response.
Rate-of-rise model (FST-851R/A), 15°F (8.3°C) per minute.
Factory preset fixed temperature at 135°F (57°C); high-temperature model fixed at 190°F (88°C).
Addressable by device.
Compatible with FlashScan® and CLIP protocol systems.
Rotary, decimal addressing (1-99 on CLIP systems, 1-159
on FlashScan systems).
Two-wire SLC connection.
Visible LEDs “blink” every time the unit is addressed.
360°-field viewing angle of the visual alarm indicators (two
bi-color LEDs). LEDs blink green in Normal condition and
turn on steady red in Alarm.
Integral communications and built-in device-type identification.
Remote test feature from the panel.
Built-in functional test switch activated by external magnet.
Walk test with address display (an address of 121 will blink
the detector LED 12-(pause)-1).
Low standby current.
Backward-compatible.
Built-in tamper-resistant feature.
Designed for direct-surface or electrical-box mounting.
Sealed against back pressure.
Plugs into separate base for ease of installation and maintenance. Separate base allows interchange of photoelectric, ionization and thermal sensors.
SEMS screws for wiring of the separate base.
Constructed of off-white fire-resistant plastic, designed to
commercial standards, and offers an attractive appearance.
FST-851(A) in B210LP(A) Base
B210-2251.jpg
General
• 94-5V plastic flammability rating.
• Remote LED output connection to optional RA100Z(A)
remote LED annunciator.
• Optional sounder, relay, and isolator bases.
• Optional flanced surface mounting kit.
Specifications
Size: 2.1" (5.3 cm) high; base determines diameter.
– B210LP(A): 6.1" (15.5 cm) diameter.
– B501(A): 4.1" (10.4 cm) diameter.
– B200S(A): 6.875" (17.46 cm) diameter.
– B200SR(A): 6.875" (17.46 cm) diameter.
– B224RB(A): 6.2" (15.748 cm) diameter.
– B224BI(A): 6.2" (15.748 cm) diameter.
Shipping weight: 4.8 oz. (137 g).
Operating temperature range: FST-851(A) Series, FST851R(A): –20°C to 38°C (–4°F to 100°F); FST-851H(A): –20°C
to 66°C (–4°F to 150°F).
Detector spacing: UL approved for 50 ft. (15.24 m) center to
center. FM approved for 25 x 25 ft. (7.62 x 7.62 m) spacing.
Relative humidity: 10% – 93% noncondensing.
Thermal ratings: fixed-temperature setpoint 135°F (57°C),
rate-of-rise detection 15°F (8.3°C) per minute, high temperature heat 190°F (88°C).
ELECTRICAL SPECIFICATIONS
Voltage range: 15 - 32 volts DC peak.
Standby current (max. avg.): 300 μA @ 24 VDC (one communication every 5 seconds with LED enabled).
LED current (max.): 6.5 mA @ 24 VDC (“ON”).
Applications
Use thermal detectors for protection of property. For further
information, go to systemsensor.com for manual I56-407-00,
Applications Manual for System Smoke Detectors, which provides detailed information on detector spacing, placement,
zoning, wiring, and special applications.
DN-6936:B • 12/07/2011 — Page 1 of 2
Installation
The FST Series plug-in intelligent thermal detectors use a separate base to simplify installation, service, and maintenance.
Installation instructions are shipped with each detector. A special tool allows maintenance personnel to plug in and remove
detectors without using a ladder
Mount base (all base types) on an electrical backbox which is
at least 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see DN-60054.
NOTE: 1) Because of the inherent supervision provided by the
SLC loop, end-of-line resistors are not required. Wiring “T-taps” or
branches are permitted for Style 4 (Class “B”) wiring. 2) When
using relay or sounder bases, consult the ISO-X(A) installation
sheet I56-1380 for device limitations between isolator modules
and isolator bases.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document.In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
UL Listed: S747.
ULC Listed: S6978.
MEA Listed: 383-02-E.
FM Approved.
CSFM: 7270-0028:0196.
BSMI: CI313066760025.
CCCF: Certif. # 2004081801000018.
U.S. Coast Guard: 161.002/42/1 (NFS-640); 161.002/50/0
(NFS2-640/NFS-320/NFS-320C, excluding B210LP(A)).
• Lloyd’s Register: 11/600013 (NFS2-640/NFS-320/NFS320C, excluding B210LP(A)).
•
•
•
•
•
•
•
•
with ANSI Temporal 3, ANSI Temporal 4, continuous tone,
marching tone, and custom tone.
B200SR(A): Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone.
Replaces B501BH series bases in retrofit applications.
B224RB(A): Intelligent relay base. Screw terminals: up to 14
AWG (2.0 mm²). Relay type: Form-C. Rating: 2.0 A @ 30 VDC
resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive.
B224BI(A): Intelligent isolator base. Isolates SLC from loop
shorts. Maximum: 25 devices between isolator bases; see
Note 2 under Installation.
ACCESSORIES
F110: Retrofit flange to convert B210LP(A) to match the
B710LP(A) profile, or to convert older high-profile bases to
low-profile.
F110BP: Bulk pack of F110; package contains 15.
F210: Replacement flange for B210LP(A) base.
RA100Z(A): Remote LED annunciator. 3 – 32 VDC. Fits U.S.
single-gang electrical box. Supported by B210LP(A) and
B501(A) bases only.
SMB600: Surface mounting kit, flanged.
M02-04-00: Test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows installation and/or
removal of FlashScan® Series detector heads from base in
high ceiling installations. Includes T55-127-010.
T55-127-010: Detector removal tool without pole.
XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524
m) sections.
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
FST-851: Intelligent thermal detector. Must be mounted to one
of the bases listed below.
FST-851A: Same as FST-851 but with ULC Listing.
FST-851R: Intelligent thermal detector with rate-of-rise feature.
FST-851RA: Same as FST-851R but with ULC Listing.
FST-851H: Intelligent high-temperature thermal detector.
FST-851HA: Same as FST-851H but with ULC Listing.
INTELLIGENT BASES
NOTE: “A” suffix indicates ULC Listed model.
NOTE: For details about intelligent bases and their mounting, see
DN-60054.
B210LP(A): Standard U.S. flanged low-profile mounting base.
B210LPBP: Bulk pack of B210LP; package contains 10.
B501(A): Standard European flangeless mounting base.
B501BP: Bulk pack of B501; package contains 10.
B200S(A): Addressable Intelligent, programmable sounder
base capable of producing sound output in high or low volume
Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6936:B • 12/07/2011
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7270-0028:0196
Page 1 of 1
CATEGORY:
7270 -- HEAT DETECTOR
LISTEE:
NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: [email protected]
DESIGN:
Models FST-751, *-851, *-851R, *-851H (fixed temperature) and FST-751R (fixed temperature
with Rate-of-Rise) electronic heat detectors. Refer to listee's data sheet for additional
detailed product description and operational considerations.
RATING:
*Models FST-751, -751R, -851, and -851R = 135°F fixed temperature
*Model FST-851H = 190°F fixed temperature
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical ratings, and UL label.
APPROVAL:
Listed as heat detectors for use with Models B501 or B710LP base (CSFM Listing No.
7300-0028:173) and separately listed compatable fire alarm control units. Refer to listee’s
Installation Instructions Manual for details.
*Rev. 2-04-2003KK
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
Indoor SelectableOutput Horns,
Strobes, and
Horn Strobes for
Wall Applications
SpectrAlert® Advance audible visible notification products
are rich with features guaranteed to cut installation times
and maximize profits.
Features
• Plug-in design with minimal intrusion into the back box
• Tamper-resistant construction
• A
utomatic selection of 12- or 24-volt operation at
15 and 15/75 candela
• F
ield-selectable candela settings on wall units: 15, 15/75,
30, 75, 95, 110, 115, 135, 150, 177, and 185
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for horn tone and three volume selections
• Universal mounting plate for wall units
• M
ounting plate shorting spring checks wiring continuity before
device installation
• Electrically Compatible with legacy SpectrAlert devices
• Compatible with MDL3 sync module
• Listed for ceiling or wall mounting
3023572
Like the entire SpectrAlert Advance product line, wall-mount horns,
strobes, and horn strobes include a variety of features that increase
their application versatility while simplifying installation. All devices
feature plug-in designs with minimal intrusion into the back box,
making installations fast and foolproof while virtually eliminating
costly and time-consuming ground faults.
To further simplify installation and protect devices from construction
damage, SpectrAlert Advance utilizes a universal mounting plate
with an onboard shorting spring, so installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with three volume selections.
Agency Listings
S4011 (chimes, horn strobes, horns)
S5512 (strobes)
The SpectrAlert Advance series offers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry.
With white and red plastic housings, wall and ceiling mounting
options, and plain and FIRE-printed devices, SpectrAlert Advance
can meet virtually any application requirement.
MEA452-05-E
7125-1653:186 (indoor strobes)
7125-1653:188 (horn strobes,
chime strobes)
7135-1653:189 (horns, chimes)
SpectrAlert Advance Specifications
Architect/Engineer Specifications
General
SpectrAlert Advance horns, strobes, and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or
double-gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall
be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or fullwave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95,
110, 115, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service.
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire
products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded
power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature
Humidity Range
Strobe Flash Rate
Nominal Voltage
Operating Voltage Range2
Operating Voltage Range MDL3 Sync Module
Input Terminal Wire Gauge
Wall-Mount Dimensions (including lens)
Horn Dimensions
Wall-Mount Trim Ring Dimensions (sold as a 5 pack) (TR-HS)
32°F to 120°F (0°C to 49°C)
10 to 93% non-condensing
1 flash per second
Regulated 12 DC/FWR or regulated 24 DC/FWR1
8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
12 to 18 AWG
5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D)
5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D)
5.7˝ L × 4.8˝ W × 0.35˝ D (145 mm L × 122 mm W × 9 mm D)
Notes:
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
UL Current Draw Data
UL Max. Strobe Current Draw (mA RMS)
8–17.5 Volts
Candela DC
FWR
Standard
15
123
128
Candela
15/75
142
148
Range
30
NA
NA
75
NA
NA
95
NA
NA
110
NA
NA
115
NA
NA
High
135
NA
NA
Candela
150
NA
NA
Range
177
NA
NA
185
NA
NA
16–33 Volts
DC
FWR
66
71
77
81
94
96
158
153
181
176
202
195
210
205
228
207
246
220
281
251
286
258
UL Max. Horn Current Draw (mA RMS)
8–17.5 Volts
Sound Pattern
dB
DC
FWR
Temporal
High
57
55
Temporal
Medium
44
49
Temporal
Low
38
44
Non-temporal
High
57
56
Non-temporal
Medium
42
50
Non-temporal
Low
41
44
Coded
High
57
55
Coded
Medium
44
51
Coded
Low
40
46
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)
8–17.5 Volts
16–33 Volts
DC Input
15
15/75
15
15/75
30
75
Temporal High
137
147
79
90
107
176
Temporal Medium
132
144
69
80
97
157
Temporal Low
132
143
66
77
93
154
Non-Temporal High
141
152
91
100
116
176
Non-Temporal Medium
133
145
75
85
102
163
Non-Temporal Low
131
144
68
79
96
156
FWR Input
Temporal High
136
155
88
97
112
168
Temporal Medium
129
152
78
88
103
160
Temporal Low
129
151
76
86
101
160
Non-Temporal High
142
161
103
112
126
181
Non-Temporal Medium
134
155
85
95
110
166
Non-Temporal Low
132
154
80
90
105
161
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)
16–33 Volts
DC Input
135
150
177
185
FWR Input
Temporal High
245
259
290
297
Temporal High
Temporal Medium
235
253
288
297
Temporal Medium
Temporal Low
232
251
282
292
Temporal Low
Non-Temporal High
255
270
303
309
Non-Temporal High
Non-Temporal Medium
242
259
293
299
Non-Temporal Medium
Non-Temporal Low
238
254
291
295
Non-Temporal Low
Horn and Horn Strobe Output (dBA)
Switch
Position
1
2
3
4
5
6
7†
8†
9†
Sound Pattern
Temporal
Temporal
Temporal
Non-Temporal
Non-Temporal
Non-Temporal
Coded
Coded
Coded
dB
High
Medium
Low
High
Medium
Low
High
Medium
Low
8–17.5
Volts
DC FWR
78 78
75 75
71 71
82 82
78 78
73 74
82 82
78 78
74 75
16–33
Volts
DC FWR
84 84
80 80
76 76
88 88
85 85
81 81
88 88
85 85
81 81
Settings 7, 8, and 9 are not available on 2-wire horn strobes.
†
95
194
182
179
201
187
182
110
212
201
198
221
207
201
115
218
210
207
229
216
210
190
184
184
203
189
184
210
202
194
221
208
202
218
206
201
229
216
211
16–33 Volts
135
150
215
231
209
224
207
221
233
248
219
232
214
229
Horn Tones and Sound Output Data
24-Volt Nominal
Reverberant Anechoic
DC
FWR
DC FWR
88
88
99 98
86
86
96 96
83
80
94 89
93
92
100 100
90
90
98 98
88
84
96 92
93
92
101 101
90
90
97 98
88
85
96 92
16–33 Volts
DC
FWR
69
75
58
69
44
48
69
75
60
69
50
50
69
75
56
69
52
50
177
258
250
248
275
262
256
185
265
258
256
281
267
262
SpectrAlert Advance Dimensions
4.7˝
6.8˝
Dia.
2.5˝
2.5˝
5.6˝
Wall-mount horn strobes
SpectrAlert Advance Ordering Information
Model
Description
Wall Horn Strobes
P2R
2-Wire Horn Strobe, Standard cd, Red
P2R-P
2-Wire Horn Strobe, Standard cd, Red, Plain
P2R-SP
2-Wire Horn Strobe, Standard cd, Red, “FUEGO”
P2RH
2-Wire Horn Strobe, High cd, Red
P2RH-P
2-Wire Horn Strobe, High cd, Red, Plain
P2W
2-Wire Horn Strobe, Standard cd, White
P2W-P
2-Wire Horn Strobe, Standard cd, White, Plain
P2WH
2-Wire Horn Strobe, High cd, White
P2WH-P
2-Wire Horn Strobe, High cd, White, Plain
P4R
4-Wire Horn Strobe, Standard cd, Red
P4R-P
4-Wire Horn Strobe, Standard cd, Red, Plain
P4RH
4-Wire Horn Strobe, High cd, Red
P4W
4-Wire Horn Strobe, Standard cd, White
Wall Strobes
SR
Strobe, Standard cd, Red
SR-P
Strobe, Standard cd, Red, Plain
SR-SP
Strobe, Standard cd, Red, “FUEGO”
Model
Description
Wall Strobes (cont.)
SRH
Strobe, High cd, Red
SRH-P
Strobe, High cd, Red, Plain
SRH-SP
Strobe, High cd, Red, “FUEGO”
SW
Strobe, Standard cd, White
SW-P
Strobe, Standard cd, White, Plain
SWH
Strobe, High cd, White
SWH-P
Strobe, High cd, White, Plain
Horns
HR
Horn, Red
HW
Horn, White
Accessories
TR-HS
Trim Ring, Wall, Red
SBBR
Indoor Surface Mount Back Box, Red
SBBW
Indoor Surface Mount Back Box, White
Notes:
All -P models have a plain housing (no “FIRE” marking on cover)
All -SP models have “FUEGO” marking on cover
“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings.
“High cd” refers to strobes that include 135, 150, 177, and 185 candela settings.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
www.systemsensor.com
©2014 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
AVDS10201 • 1/14
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7125-1653:0186
Page 1 of 1
CATEGORY:
7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE:
System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245
Email: [email protected]
DESIGN:
Synchronous type strobe lights, Models SR, SRH, SW, SW-CLR-ALERT, SWH, SCR,
SCRH, SCW, SCW-CLR-ALERT and SCWH followed by the suffix -P, -SP, -PG, or none.
Intended for indoor use mounted on the wall or the ceiling. Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING:
8-17.5 or 16-33 VDC/FWR
Candela: 15, 15/75, 30, 75, 95, 110, 115, *135, *150, *177, *185cd
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical rating and UL label.
APPROVAL:
Listed as strobe lights suitable for hearing impaired application when used with separately
listed compatible fire alarm control units. Suitable for indoor use, wall or ceiling mounted.
Refer to listee’s Installation Instruction Manual for details.
*Rev. 03-11-10 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
Indoor SelectableOutput Speaker
Strobes and Dual
Voltage Evacuation
Speakers for Wall
Applications
The SpectrAlert® Advance selectable output speaker
strobes and dual-voltage evacuation speakers can reduce
ground faults and enable faster installation.
Features
• Plug-in design and protective cover reduce ground faults
• U
niversal mounting plate with an onboard shorting spring tests
wiring continuity before installation
• No extension ring required
• F
ield selectable candela settings:
Standard: 15, 15/75, 30, 75, 95, 110, 115
High: 135, 150, 177, 185
• A
utomatic selection of 12- or 24-volt operation at 15 and 15/75 candela
• R
otary switch simplifies field selection of speaker voltage (25 and 70.7 Vrms) and power settings (¼, ½, 1 and 2 watts)
• SP speakers offer high fidelity sound output
• SPV speakers offer high volume sound output
• Compatible with System Sensor synchronization protocol
• Electrical compatibility with existing SpectrAlert products
• Optional tamper resistant Torx head screw included
• Listed for ceiling or wall mounting
Agency Listings
S4048
7320-1653:201
10-08-E
The SpectrAlert Advance Series of speakers and speaker
strobes reduce costly ground faults using a plug-in design and
universal mounting plate that allow the installer to pre-wire mounting
plates, dress the wires, and confirm wiring continuity before plugging
in the speakers. In addition, a protective plastic cover prevents
nicked wires by covering exposed speaker components.
These devices also enable faster installations by providing instant
feedback to ensure that wiring is properly connected, rotary switches
to select voltage and power settings, and 11 field-selectable candela
settings for both wall and ceiling speaker strobes.
The low total harmonic distortion of the SP speaker offers high fidelity
sound output while the SPV speaker offers high volume sound output
for use in high ambient noise applications.
SpectrAlert Advance makes installation easy
• Attach a universal mounting plate to a 4 × 4 × 21⁄8 inch back box .
Flush-mount applications do not require an extension ring.
• Connect the notification appliance circuit or speaker wiring to the
terminals on the mounting plate.
• Attach the speaker or speaker strobe to the mounting plate by
inserting the product tabs into the mounting plate grooves. Rotate
the device into position to lock the product pins into the mounting
plate terminals. The device will temporarily hold in place with a
catch until it is secured with a captured mounting screw.
SpectrAlert Advance Speaker and Speaker Strobe Specifications
Architectural/Engineering Specifications
General
SpectrAlert Advance speaker and speaker strobes shall mount to a 4 × 4 × 21⁄8-inch back box. A universal mounting plate shall be used for
mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also,
SpectrAlert Advance speaker strobes, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt rated notification
appliance circuit outputs shall operate between nine and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between
17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32°F and 120°F from a regulated DC, or full-wave rectified,
unfiltered power supply. Speaker strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150,
177, 185.
Speaker
The speaker shall be a System Sensor SpectrAlert Advance model _______ dual-voltage transformer speaker capable of operating at 25.0 or
70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service. The speaker shall have a frequency range
of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that are
selected by rotary switches.
Speaker Strobe combination
The speaker strobe shall be a System Sensor SpectrAlert Advance model __________ listed to UL1480 and UL 1971 and be approved for fire
protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch, and shall
have a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch. The strobe shall comply
with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe
light shall consist of a xenon flash tube and associated lens/reflector system.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize
SpectrAlert strobes at 1 Hz. The module shall mount to a 411⁄16 × 411⁄16 × 21⁄8-inch back box. The module shall also control two Style Y
(class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization
modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical Specifications
Operating Temperature
Humidity Range
Dimensions, Wall-Mount
SPS Speaker Strobe
SPSV Speaker Strobe
SP Speaker
SPSV Speaker
Electrical/Operating Specifications
Nominal Voltage (speakers)
Maximum Supervisory Voltage (speakers)
Strobe Flash Rate
Nominal Voltage (strobes)
Operating Voltage Range (includes fire
alarm panels with built in sync)
Operating Voltage with MDL Sync Module
Frequency Range
Power
AVDS00801
32°F to 120°F (0°C to 49°C)
10 to 93% non-condensing
6.0 in L × 5.0 in W × 4.7 in D (including lens and speaker)
6.0 in L × 5.0 in W × 4.9 in D (including lens and speaker)
6.0 in L × 5.0 in W × 2.8 in D
6.0 in L × 5.0 in W × 2.9 in D
25 Volts or 70.7 Volts (nominal)
50 VDC
1 flash per second
Regulated 12 VDC/FWR or regulated 24 DC/FWR
8 to 17.5 V (12 V nominal) or 16 to 33V (24 V nominal)
9 to 17.5 V (12 V nominal) or 17 to 33V (24 V nominal)
400 to 4000 Hz
¼, ½, 1, 2 watts
UL Current Draw Data
UL Max. Strobe Current Draw (mA RMS)
Standard
Candela Range
High
Candela Range
Candela
15
15/75
30
75
95
110
115
135
150
177
185
Sound Output
UL Reverberant (dBA @ 10 ft.)
Wall-Mount SP Series
Wall-Mount SPV Series
Wall-Mount SPS Series
Wall-Mount SPSV Series
8 to 17.5 Volts
DC
123
142
NA
NA
NA
NA
NA
NA
NA
NA
NA
FWR
128
148
NA
NA
NA
NA
NA
NA
NA
NA
NA
16 to 33 Volts
DC
66
77
94
158
181
202
210
228
246
281
286
FWR
71
81
96
153
176
195
205
207
220
251
258
2W
86
90
85
89
1W
83
87
82
86
½W
80
84
79
83
¼W
77
81
76
80
Dimensions
5.00˝
.97˝
5.98˝
1.84˝
5.00˝
2.83˝
1.60˝
1.84˝
5.97˝
Wall-Mount SP Speaker
Wall-Mount SPS Speaker Strobe
AVDS00801
Surface Mounting
Wall-Mount Speaker Strobe with SPBBS Back
Ordering Information for SpectrAlert® Advance Speakers and Speaker Strobes
Wall Mount
White
SPW
SPWV
SPSW*
SPSW-ALERT
SPSW-CLR-ALERT
SPSWH*
SPSWV*
Accessories
White
RFPW
SPBBSW
TRW
Red
SPR
SPRV
SPSR*
—
—
SPSRH*
SPSRV*
Description
Speaker only
Speaker only, High dB
Speaker Strobe, Standard cd
Speaker Strobe, Standard cd, Amber Lens
Speaker Strobe, Standard cd, Clear Lens
Speaker Strobe, High cd
Speaker Strobe, Standard cd, High dB
Red
RFP
SPBBS
TR
Description
7 in × 9.5 in Retrofit Plate
Wall Mount Back Box Skirt
Wall Mount Trim Ring
Notes:
* Add -P to model number for plain housing (no “FIRE” marking on the cover) e.g. SPSW-P
‡ “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and
185 candela settings.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2012 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
AVDS00801 • 3/12
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7320-1653:0201
Page 1 of 1
CATEGORY:
7320 -- SPEAKERS
LISTEE:
System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245
Email: [email protected]
DESIGN:
Models SPR,SPW,SPRV, and SPWV SpectrAlert Speakers - Rectangular enclosure.
Models SPCW, SPCR, SPCWV, and SPCRV SpectrAlert Speakers with round enclosure.
Models SPSR, SPSRH, SPSW, SPSW-ALERT, SPSW-CLR-ALERT,
*SPSWK-CLR-ALERT, SPSWH, SPSRV, and SPSWV SpectrAlert Speaker/Strobe with
rectangular enclosure. Models SPSCR, SPSCRH, SPSCW, *SPSCWK-CLR-ALERT,
SPSCWH, SPSCRV, SPSCRVH, SPSCWV, and SPSCWVH SpectrAlert Speaker/Strobe
with round enclosure. Model SPSCW-CLR-ALERT Speaker/Strobe. Model SPSW-ALERT
has amber lens and is intended for non-fire use.
All models identified are intended for indoor use mounted on the wall or ceiling. Models with
a “K” in the suffix are suitable for indoor or outdoor use with an operating temperature rating
of -40°C to +66°C (-40°F to +151°F) and have a NEMA 4X enclosure rating when used with
models PWBB, PWBBW (wall) or the model PWBBCW (ceiling) plastic weatherproof back
boxes or with Model MWBBW (Wall), MWBB (Wall) or MWBBCW (Ceiling) metal
weatherproof back boxes. Models with a “- P” in the suffix have plain housings with no
lettering on the enclosure. Models not containing “- P”, in the suffix have English lettering
reading “FIRE” on the housing. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING:
Nominal Voltage: 25 Vrms or 70 Vrms
Power Settings: ¼, ½, 1, 2 Watts
Frequency Range: 400 - 4000 Hz
INSTALLATION:
In accordance with listee's printed installation instructions, NFPA 72, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical rating and UL label.
APPROVAL:
Listed as speaker/strobes when used with separately listed compatible fire alarm control
units. Suitable for wall or ceiling mount.
These speaker/strobes do not generate a distinctive three-pulse temporal code pattern (for
total evacuation) as required per NFPA 72, 2010 edition. If required, the appliances must be
used with a fire alarm control unit that can generate the temporal pattern signal.
*Corrected 02-06-12 bh
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
Outdoor, SelectableOutput Speaker
Strobes and DualVoltage Evacuation
Speakers for Wall
Applications
SpectrAlert® Advance outdoor, selectable-output speaker
strobes and dual-voltage evacuation speakers meet
virtually any outdoor application requirement.
Features
• Weatherproof per NEMA 4X, IP56
• Rated from -40°F to 151°F
• Plug-in design reduces ground faults
• Universal mounting plate with onboard shorting spring that tests
wiring continuity before devices are installed
• Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115,
135, 150, 177, and 185
• Automatic selection of 12- or 24-volt operation at 15 and
15/75 candela
• Rotary switch for speaker voltage (25 and 70.7 Vrms) and power
settings (1/4, 1/2, 1 and 2 watts)
• Compatible with System Sensor synchronization protocol and
legacy SpectrAlert products
• Tamper-resistant construction
• Listed for ceiling or wall mounting
Agency Listings
75S0
7320-1653:201
10-08-E
SpectrAlert Advance offers the broadest line of outdoor
speakers and speaker strobes in the industry. From metal and plastic
outdoor back boxes, to white and red plastic housings, to wall and
ceiling mounting options, SpectrAlert Advance can meet virtually any
application requirement.
Wall-mount outdoor speakers and speaker strobes can be used
indoors or outdoors in wet or dry applications, and can provide
reliable operation from −40°F to 151°F. These speakers provide
a broad frequency response range, low harmonic distortion and
maintain a high sound pressure level at all tap settings to provide
accurate and intelligible broadcast of evacuation messages.
Like the entire SpectrAlert Advance line, wall-mount outdoor speakers
and speaker strobes include a variety of features that increase
application flexibility and simplify installation. First, field-selectable
settings, including candela, speaker voltage and power settings, and
automatic selection of 12- or 24-volt operation enable installers to
easily adapt devices to meet requirements.
Next, these devices use a universal mounting plate with an onboard
shorting spring that ensures wiring continuity before devices are
installed, so installers can verify proper wiring without mounting the
devices and exposing them to potential construction damage. Once
the plates are mounted, all SpectrAlert Advance devices utilize a
plug-in design with a single captured screw to speed installation and
virtually eliminate costly ground faults.
Outdoor devices ship with weatherproof plastic back boxes (metal
back boxes are available separately) that accommodate in-andout wiring for daisy chaining devices. Plastic back boxes feature
removable side flanges and improved resistance to saltwater
corrosion. Knock-outs located on the back eliminate the need to drill
holes for screw-in mounting. Plastic and metal weatherproof back
boxes come with ¾-inch top and bottom conduit entries and ¾-inch
knock-outs at the back. A screw-in NPT plug with an O-ring gasket
for a watertight seal is included with each back box.
SpectrAlert® Advance Outdoor Speaker and Speaker Strobe Specifications
Architectural/Engineering Specifications
General
SpectrAlert Advance outdoor speakers and speaker strobes shall mount to a weatherproof back box. A universal mounting plate shall be
used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting
plate. Also, SpectrAlert Advance speaker strobes, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded
notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated
notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate
between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between –40°F and 151°F from a regulated DC, or full-wave
rectified, unfiltered power supply.
Speaker
Speaker shall be a System Sensor SpectrAlert Advance Model ______ dual-voltage transformer speaker capable of operating at 25.0 or 70.7
nominal Vrms. Speaker shall be listed to Underwriters Laboratories Standard S4048 for outdoor fire protective signaling systems. Speaker
shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature from –40°F to 150.8°F. Speaker shall have power
taps and wattage settings that are selected by rotary switches. The speaker must be installed with its weatherproof back box in order to
remain outdoor approved per UL listing S4048. The speaker shall be suitable for use in air handling spaces and wet environments.
Speaker Strobe Combination
The speaker strobe shall be a System Sensor Model _____ listed to UL 1638 and UL 1480 and be approved for fire protective signaling
systems. Speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms and shall have a frequency range of 400 to 4,000 Hz. Speaker
shall have power taps that are selected by rotary switch. The strobe shall consist of a xenon flash tube with associated lens/reflector system
and operate on either 12 or 24 volts. The strobe shall also feature selectable candela output, providing options for 15 or 15/75 candela when
operating on 12 volts and 15, 15/75, 30, 75, 110, 115, 135, 150, 177 or 185 candela when operating on 24 volts. The strobe shall comply with
the Americans with Disabilities Act requirement for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage
range. The speaker strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The speaker strobe
shall be suitable for use in wet environments.
Physical Specifications
Operating Temperature
Dimensions, Wall-Mount
SPS Speaker Strobe
SP Speaker
Dimensions, Wall-Mount Weatherproof Back Box
Electrical/Operating Specifications
Nominal Voltage (speakers)
Maximum Supervisory Voltage (speakers)
Strobe Flash Rate
Nominal Voltage (strobes)
Operating Voltage Range (includes fire alarm
panels with built in sync)
Operating Voltage with MDL Sync Module
Frequency Range
Power
AVDS01001
–40°F to 151°F (–40°C to 66°C)
6.0˝ L × 5.0˝ W × 4.7˝ D (including lens and speaker)
6.0˝ L × 5.0˝ W × 2.9˝ D
6.5˝ L × 5.5˝ H × 2.9˝ D
25 V or 70.7 V (nominal)
50 VDC
1 flash per second
Regulated 12 VDC/FWR or regulated 24 DC/FWR
8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
9 to 17.5 V (12 V nominal) or 17 to 33 V (24 V nominal)
400 to 4,000 Hz
¼, ½, 1, 2 watts
UL Current Draw Data
Candela Derating
UL Max. Strobe Current Draw (mA RMS)
8 to 17.5 Volts
DC
FWR
Candela
Standard
15
123
128
Candela Range
15/75
142
148
30
NA
NA
75
NA
NA
95
NA
NA
110
NA
NA
115
NA
NA
High
135
NA
NA
Candela Range
150
NA
NA
177
NA
NA
185
NA
NA
Sound Output
UL Reverberant (dBA @ 10 ft.)
2W
1W
Outdoor Speaker
90
87
Outdoor Speaker/Strobe
89
86
For K series products used at low
temperatures, listed candela ratings must be
reduced in accordance with this table.
16 to 33 Volts
DC
FWR
66
71
77
81
94
96
158
153
181
176
202
195
210
205
228
207
246
220
281
251
286
258
½W
84
83
Strobe Output (cd)
Listed Candela
15
15/75
30
75
95
110
115
135
150
177
185
¼W
81
80
Candela rating at
–40°F
Do not use below 32°F
44
70
110
115
135
150
177
185
Dimensions
5.48˝
.97˝
6.45˝
2.83˝
5.48˝
2.83˝
1.60˝
2.83˝
6.45˝
Wall-Mount Outdoor Speaker
Wall-Mount Outdoor Speaker Strobe
AVDS01001
Surface Mounting
Wall-Mount Speaker Strobe with Plastic Weatherproof Back Box
Wall-Mount Speaker with Plastic Weatherproof Back Box
Wall-Mount Speaker Strobe with Metal Weatherproof Back Box
Wall-Mount Speaker with Metal Weatherproof Back Box
Ordering Information for SpectrAlert® Advance Outdoor Speakers and Speaker Strobes
Wall Mount
White
SPWK*
SPSWK*†
SPSWK-CLRALERT
—
Accessories
White
MWBBW
Red
SPRK*
SPSRK*†
—
SPSRHK
Description
Outdoor Speaker (includes plastic weatherproof back box)
Outdoor Speaker Strobe, Standard cd (includes plastic weatherproof back box)
Outdoor Speaker Strobe, Standard cd, Clear Lens, ALERT Printed
(includes plastic weatherproof back box)
Outdoor Speaker Strobe, High cd (135,150,177,185) (includes plastic weatherproof back box)
Red
MWBB
Description
Wall, Metal Weatherproof Back Box
Notes:
*Add “-R” to model number for weatherproof replacement device (no back box included), e.g., SPWK-R.
†
Add “-P” to model number for plain housing (no “FIRE” marking on cover), e.g., SPSWK-P.
“Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185
candela settings. When replacing standard outdoor units, both the device and back box must be replaced.
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2012 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
AVDS01001 • 03/12
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7320-1653:0201
Page 1 of 1
CATEGORY:
7320 -- SPEAKERS
LISTEE:
System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245
Email: [email protected]
DESIGN:
Models SPR,SPW,SPRV, and SPWV SpectrAlert Speakers - Rectangular enclosure.
Models SPCW, SPCR, SPCWV, and SPCRV SpectrAlert Speakers with round enclosure.
Models SPSR, SPSRH, SPSW, SPSW-ALERT, SPSW-CLR-ALERT,
*SPSWK-CLR-ALERT, SPSWH, SPSRV, and SPSWV SpectrAlert Speaker/Strobe with
rectangular enclosure. Models SPSCR, SPSCRH, SPSCW, *SPSCWK-CLR-ALERT,
SPSCWH, SPSCRV, SPSCRVH, SPSCWV, and SPSCWVH SpectrAlert Speaker/Strobe
with round enclosure. Model SPSCW-CLR-ALERT Speaker/Strobe. Model SPSW-ALERT
has amber lens and is intended for non-fire use.
All models identified are intended for indoor use mounted on the wall or ceiling. Models with
a “K” in the suffix are suitable for indoor or outdoor use with an operating temperature rating
of -40°C to +66°C (-40°F to +151°F) and have a NEMA 4X enclosure rating when used with
models PWBB, PWBBW (wall) or the model PWBBCW (ceiling) plastic weatherproof back
boxes or with Model MWBBW (Wall), MWBB (Wall) or MWBBCW (Ceiling) metal
weatherproof back boxes. Models with a “- P” in the suffix have plain housings with no
lettering on the enclosure. Models not containing “- P”, in the suffix have English lettering
reading “FIRE” on the housing. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING:
Nominal Voltage: 25 Vrms or 70 Vrms
Power Settings: ¼, ½, 1, 2 Watts
Frequency Range: 400 - 4000 Hz
INSTALLATION:
In accordance with listee's printed installation instructions, NFPA 72, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, model number, electrical rating and UL label.
APPROVAL:
Listed as speaker/strobes when used with separately listed compatible fire alarm control
units. Suitable for wall or ceiling mount.
These speaker/strobes do not generate a distinctive three-pulse temporal code pattern (for
total evacuation) as required per NFPA 72, 2010 edition. If required, the appliances must be
used with a fire alarm control unit that can generate the temporal pattern signal.
*Corrected 02-06-12 bh
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
DN-6720:C • H-220
FMM-1(A), FMM-101(A),
FZM-1(A) & FDM-1(A)
Monitor Modules with FlashScan®
Intelligent/Addressable Devices
General
Four different monitor modules are available for Notifier’s intelligent control panels for a variety of applications. Monitor modules supervise a circuit of dry-contact input devices, such as
conventional heat detectors and pull stations, or monitor and
power a circuit of two-wire smoke detectors (FZM-1(A)).
FMM-1(A) is a standard-sized module (typically mounts to a 4"
[10.16 cm] square box) that supervises either a Style D (Class
A) or Style B (Class B) circuit of dry-contact input devices.
FMM-101(A) is a miniature monitor module a mere 1.3" (3.302
cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that supervises a Style B (Class B) circuit of dry-contact input devices.
Its compact design allows the FMM-101(A) to be mounted in a
single-gang box behind the device it monitors.
FDM-1(A) is a standard-sized dual monitor module that monitors and supervises two independent two-wire Style B (Class
B) dry-contact initiating device circuits (IDCs) at two separate,
consecutive addresses in intelligent, two-wire systems.
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER that greatly increases the speed
of communication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the
devices within the group has new information, the panel CPU
stops the group poll and concentrates on single points. The
net effect is response speed greater than five times that of
other designs.
FMM-1(A) Monitor Module
• Built-in type identification automatically identifies this device
as a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional power
required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
• LED flashes green during normal operation (this is a programmable option) and latches on steady red to indicate
alarm.
The FMM-1(A) Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The FMM-1(A) can be used to replace MMX-1(A)
modules in existing systems.
6999cov.jpg
FZM-1(A) is a standard-sized module that monitors and supervises compatible two-wire, 24 volt, smoke detectors on a Style
D (Class A) or Style B (Class B) circuit.
FMM-1(A) (Type H)
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.
FMM-1(A) OPERATION
Each FMM-1(A) uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limitations on the loop).
FMM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 350 μA (LED flashing), 1 communication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 40 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
FMM-1(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normallyopen dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class
DN-6720:C • 10/06/2010 — Page 1 of 4
FMM-101(A) Mini Monitor Module
• Built-in type identification automatically identifies this device
as a monitor module to the panel.
• Powered directly by two-wire SLC loop. No additional power
required.
• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops;
01 – 99 on CLIP loops.
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x
0.65" (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.
FZM-1(A) Interface Module
6720m101.wmf
• Supports compatible two-wire smoke detectors.
• Supervises IDC wiring and connection of external power
source.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address: 01 – 159 on FlashScan loops,
01 – 99 on CLIP loops.
• LED flashes during normal operation; this is a programmable option.
• LED latches steady to indicate alarm on command from
control panel.
The FZM-1(A) Interface Module is intended for use in intelligent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor twowire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. The FZM-1(A)
can be used to replace MMX-2(A) modules in existing systems.
FZM-1(A) APPLICATIONS
The FMM-101(A) Mini Monitor Module can be installed in a
single-gang junction directly behind the monitored unit. Its
small size and light weight allow it to be installed without rigid
mounting. The FMM-101(A) is intended for use in intelligent,
two-wire systems where the individual address of each module
is selected using rotary switches. It provides a two-wire initiating device circuit for normally-open-contact fire alarm and
security devices. The FMM-101(A) can be used to replace
MMX-101(A) modules in existing systems.
FMM-101(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke
detectors, manual fire alarm pull stations, waterflow devices, or
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/device
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
A 47K ohm End-of-Line Resistor (provided) terminates the circuit.
Use the FZM-1(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B
(Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K
ohm End-of-Line Resistor (provided) terminates the end of the
Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 ohms). Install ELR across terminals 8 and 9 for
Style D application.
FZM-1(A) OPERATION
Each FZM-1(A) uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limitations on the loop).
FZM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
FMM-101(A) OPERATION
Maximum current draw: 5.1 mA (LED on).
Each FMM-101(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC).
Maximum IDC wiring resistance: 25 ohms.
FMM-101(A) SPECIFICATIONS
External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
maximum. Current: 90 mA per module maximum.
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 μA, 1 communication every
5 seconds, 47k EOL; 600 μA Max. (Communicating, IDC
Shorted).
Maximum IDC wiring resistance: 40 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 400 μA.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Page 2 of 4 — DN-6720:C • 10/06/2010
Average operating current: 300 μA, 1 communication and 1
LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
FDM1(A) Dual Monitor Module
The FDM-1(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two-wire
initiating device circuits (IDCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices; or either normally open or normally closed security devices. The module has a single panelcontrolled LED.
NOTE: The FDM-1(A) provides two Style B (Class B) IDC circuits
ONLY. Style D (Class A) IDC circuits are NOT supported in any
application.
– 161.002/23/3 (AFP-200: FMM-1/-101, FZM-1)
– 161.002/42/1 (NFS-640: FMM-1/-101)
• Lloyd’s Register:
– 03/60011/E1 (FMM-1/-101, FZM-1)
– 94/60004/E2 (AFP-200: except FDM-1)
– 02/60007 (NFS-640: FDM-1)
• FDNY: COA #6038 (NFS2-640, NFS-320), COA# 6058
(NFS2-3030)
Product Line Information
FDM-1(A) SPECIFICATIONS
NOTE: “A” suffix indicates ULC-listed model.
Normal operating voltage range: 15 to 32 VDC.
FMM-1(A): Monitor module.
Maximum current draw: 6.4 mA (LED on).
FMM-101(A): Monitor module, miniature.
Average operating current: 750 μA (LED flashing).
FZM-1(A): Monitor module, two-wire detectors.
Maximum IDC wiring resistance: 1,500 ohms.
FDM-1(A): Monitor module, dual, two independent Class B circuits.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 μA
SMB500: Optional surface-mount backbox.
EOL resistance: 47K ohms.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 51253.
Maximum SLC Wiring resistance: 40 Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
FDM-1(A) AUTOMATIC ADDRESSING
The FDM-1(A) automatically assigns itself to two addressable
points, starting with the original address. For example, if the
FDM-1(A) is set to address “26”, then it will automatically
assign itself to addresses “26” and “27”.
NOTE: “Ones” addresses on the FDM-1(A) are 0, 2, 4, 6, or 8 only.
Terminals 6 and 7 use the first address, and terminals 8 and 9 use
the second address.
!
CAUTION:
Avoid duplicating addresses on the system.
Installation
FMM-1(A), FZM-1(A), and FDM-1(A) modules mount directly
to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep,
electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform
to applicable local codes, ordinances, and regulations. These
modules are intended for power-limited wiring only.
The FMM-101(A) module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for latest listing status.
•
•
•
•
•
•
UL: S635
ULC: S635
FM Approved
CSFM: 7300-0028:0219
MEA: 457-99-E
U.S. Coast Guard:
DN-6720:C • 10/06/2010 — Page 3 of 4
FlashScan® and NOTIFIER® are registered trademarks and FireWatch™ is
a trademark of Honeywell International Inc.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 4 of 4 — DN-6720:C • 10/06/2010
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7300-0028:0219
Page 1 of 1
CATEGORY:
7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE:
NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: [email protected]
DESIGN:
Models XP6-R relay module, XP6-C, supervising control module, XP10-M input monitor
module, XP6-MA six zone interface module, FMM-1, FMM-101, FZM-1, FSM-101, FDM-1,
FTM-1 monitor modules, FCM-1, FRM-1 control modules, and *FDRM-1 with 2 input/2 output
relay module. All devices are intended to be connected between the signaling line circuit of a
compatible fire alarm control panel. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING:
16-33 VDC Primary
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, product number and UL label.
APPROVAL:
Listed as control unit accessories for use with listee's separately listed compatible fire alarm
control units. Model FTM-1 is intended to be used with Notifier Models NFS-640, NFS2-640
(CSFM Listing No. 7165-0028:214), NFS-3030, NFS2-3030 (CSFM Listing No.
7165-0028:224) Fire Alarm Control Units.
NOTE:
If an external power supply is used for Model XP6-MA, the negative of the external power
supply is referenced to the negative of the auxiliary supply of the compatible control panel.
This is done in order to detect ground faults on the initiating circuit.
*Rev. 10-24-11 mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016
Authorized By:
DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires
June 30, 2017
DN-6724:B3
FCM-1(A) & FRM-1(A)
Series
Control and Relay Modules
Intelligent / Addressable Devices
General
FCM-1(A) Control Module: The FCM-1(A) Addressable Control Module provides Notifier intelligent fire alarm control panels a circuit for Notification Appliances (horns, strobes,
speakers, etc.). Addressability allows the FCM-1(A) to be activated, either manually or through panel programming, on a
select (zone or area of coverage) basis.
FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay
Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, dampers,
control equipment, etc. Addressability allows the dry contact to
be activated, either manually or through panel programming,
on a select basis.
7000cov.JPG
FlashScan® (U.S. Patent 5,539,389) is a communication protocol developed by NOTIFIER Engineering that greatly
enhances the speed of communication between analog intelligent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater than
five times that of other designs.
FCM-1(A)
Features
• Built-in type identification automatically identifies these
devices to the control panel.
• Internal circuitry and relay powered directly by two-wire
SLC loop. The FCM-1(A) module requires power (for horns,
strobes, etc.), or audio (for speakers).
• Integral LED “blinks” green each time a communication is
received from the control panel and turns on in steady red
when activated.
• LED blink may be deselected globally (affects all devices).
• High noise immunity (EMF/RFI).
• The FCM-1(A) may be used to switch 24-volt NAC power,
audio (up to 70.7 Vrms).
• Wide viewing angle of LED.
• SEMS screws with clamping plates for wiring ease.
• Direct-dial entry of address 01– 159 for FlashScan loops,
01 – 99 for CLIP mode loops.
• Speaker, and audible/visual applications may be wired for
Class B or A (Style Y or Z).
Applications
The FCM-1(A) is used to switch 24 VDC audible/visual power,
high-level audio (speakers). The FRM-1(A) may be programmed to operate dry contacts for applications such as door
holders or Air Handling Unit shutdown, and to reset four-wire
smoke detector power.
• The FCM-1(A) is configured for a single Class B (Style Y) or
Class A (Style Z) Notification Appliance Circuit.
• The FRM-1(A) provides two Form-C dry contacts that
switch together.
Operation
Each FCM-1(A) or FRM-1(A) uses one of 159 possible module
addresses on a SLC loop (99 on CLIP loops). It responds to
regular polls from the control panel and reports its type and
status, including the open/normal/short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll
received. On command, it activates its internal relay. The
FCM-1(A) supervises Class B (Style Y) or Class A (Style Z)
notification or control circuits.
Upon code command from the panel, the FCM-1(A) will disconnect the supervision and connect the external power supply in the proper polarity across the load device. The
disconnection of the supervision provides a positive indication
to the panel that the control relay actually turned ON. The
external power supply is always relay isolated from the communication loop so that a trouble condition on the external
power supply will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The
address may be set before or after mounting. The built-in
TYPE CODE (not settable) will identify the module to the control panel, so as to differentiate between a module and a sensor address.
NOTE: Refer to the SLC Manual (PN 51253) for details regarding
releasing applications with the FCM-1(A). Refer to the FCM-1-REL
datasheet (DN-60390) for new FlashScan® releasing applications.
Specifications for FCM-1(A)
Construction
Maximum current draw: 6.5 mA (LED on).
• The face plate is made of off-white heat-resistant plastic.
• Controls include two rotary switches for direct-dial entry of
address (01-159).
Average operating current: 350 μA direct poll, 375 μA group
poll with LED flashing, 485 μA Max. (LED flashing, NAC
shorted.)
Normal operating voltage: 15 to 32 VDC.
DN-6724:B3 • 2/17/2011 — Page 1 of 2
Maximum NAC Line Loss: 4 VDC.
External supply voltage (between Terminals T10 and
T11): Maximum (NAC): Regulated 24 VDC; Maximum
(Speakers): 70.7 V RMS, 50W.
Drain on external supply: 1.7 mA maximum using 24 VDC
supply; 2.2 mA Maximum using 80 VRMS supply.
Max NAC Current Ratings: For class B wiring system, the
current rating is 3A; For class A wiring system, the current rating is 2A.
Temperature range: 32°F to 120°F (0°C to 49°C).
Contact Ratings for FRM-1(A)
Current
Rating
Load
Description
Application
30 VDC
Resistive
Non-Coded
2A
30 VDC
Resistive
Coded
.9 A
110 VDC
Resistive
Non-Coded
.9 A
125 VDC
Resistive
Non-Coded
.5 A
30 VDC
Inductive
(L/R=5ms)
Coded
1A
30 VDC
Inductive
(L/R=2ms)
Coded
.3 A
125 VAC
Inductive
(PF=0.35)
Non-Coded
1.5 A
25 VAC
Inductive
(PF=0.35)
Non-Coded
.7 A
70.7 VAC
Inductive
(PF=0.35)
Non-Coded
2A
25 VAC
Inductive
(PF=0.35)
Non-Coded
3A
Maximum
Voltage
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm) deep box.
Accessories: SMB500 Electrical Box; CB500 Barrier
Specifications for FRM-1(A)
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 6.5 mA (LED on).
Average operating current: 230 μA direct poll; 255 μA group
poll.
EOL resistance: not used.
Temperature range: 32°F to 120°F (0°C to 49°C).
NOTE: Maximum (Speakers): 70.7 V RMS, 50 W
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125" (53.975 mm) deep box.
Accessories: SMB500 Electrical Box; CB500 Barrier
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for latest listing status.
•
•
•
•
•
•
UL: S635
ULC: S3705 (A version only)
FM Approved
CSFM: 7300-0028:0219
MEA: 14-00-E
FDNY: COA #6067, #6065
Product Line Information
NOTE: “A” suffix indicates ULC Listed model.
FCM-1(A): Intelligent Addressable Control Module.
FRM-1(A): Intelligent Addressable Relay Module.
A2143-20: Capacitor, required for Class A (Style Z) operation
of speakers.
SMB500: Optional Surface-Mount Backbox.
CB500: Control Module Barrier — required by UL for separating power-limited and non-power limited wiring in the same
junction box as FCM-1(A).
NOTE: For installation instructions, see the following documents:
• FCM-1(A) Installation document I56-1169.
• FRM-1(A) Installation document I56-3502.
• Notifier SLC Wiring Manual, document 51253.
Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2 — DN-6724:B3 • 2/17/2011
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
7300-0028:0219
Page 1 of 1
CATEGORY:
7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE:
NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: [email protected]
DESIGN:
Models XP6-R relay module, XP6-C, supervising control module, XP10-M input monitor
module, XP6-MA six zone interface module, FMM-1, FMM-101, FZM-1, FSM-101, FDM-1,
FTM-1 monitor modules, FCM-1, FRM-1 control modules, and *FDRM-1 with 2 input/2 output
relay module. All devices are intended to be connected between the signaling line circuit of a
compatible fire alarm control panel. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING:
16-33 VDC Primary
INSTALLATION:
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in manner acceptable to the authority having jurisdiction.
MARKING:
Listee's name, product number and UL label.
APPROVAL:
Listed as control unit accessories for use with listee's separately listed compatible fire alarm
control units. Model FTM-1 is intended to be used with Notifier Models NFS-640, NFS2-640
(CSFM Listing No. 7165-0028:214), NFS-3030, NFS2-3030 (CSFM Listing No.
7165-0028:224) Fire Alarm Control Units.
NOTE:
If an external power supply is used for Model XP6-MA, the negative of the external power
supply is referenced to the negative of the auxiliary supply of the compatible control panel.
This is done in order to detect ground faults on the initiating circuit.
*Rev. 10-24-11 mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria.
Refer to listee’s data sheet, installation instructions and/or other
Date Issued:
July 01, 2016