SPEAKMAN COMPANY
SE-582 Installation, Maintenance & Operation Instructions
EYESAVER® EYEWASH
DESCRIPTION
Emergency eyewash, for wall mounting, supplied with stainless steel bowl, stay-open full flow ball valve; activated by
stainless steel push handle; heavy duty wall mounting plate, twin spray heads with individual flow restrictors, and flip-off dust
covers.
SPECIFICATIONS
BOWL: 300 Series Stainless Steel.
SPRAY HEADS: (2) Aerated Yellow ABS Plastic Spray Outlet, Sprayface, and Dust Cover.
VALVE: 1/2” NPT Female Brass, Chrome-Plated.
ACTIVATOR: Stainless Steel Push Handle.
INLET: 1/2” NPT Female.
PLATE: Cold-Rolled Steel, Powder Coating Safety Green.
SHIPPING WEIGHT: 10.11 lbs.
EMERGENCY SIGN: 7-7/8” x 7-7/8” Plastic Wall Sign.
OPTIONS
◊
◊
◊
◊
◊
◊
AL1 (Air Horn Alarm)
AL2 (Electrical Alarm)
AL3 (Electrical Alarm)
AL2-C1D2 (Electrical Alarm / Haz. Area)
AL3-C1D2 (Electrical Alarm / Haz. Area)
FLW (Flow Switch)
◊
◊
◊
◊
◊
◊
HS (Hand-held Spray)
PT (P-Trap)
VPL (Vapor Proof Light)
SGN4 (Eye Wash Floor Sign)
FPV (Anti-Freeze Protection Valve)
SPV (Anti-Scald Protection Valve)
◊
◊
◊
◊
◊
◊
SSBV2 (1/2” Stainless Steel Valve)
ILS (In-Line Strainer)
INSTALLATION
Review drawing (as shown on other side) to assure proper installation. The unit should be mounted to a structural member that
will ensure structural rigidity. Use appropriate wall anchors and be sure the wall bracket is level to ensure proper flow pattern
and to avoid unnecessary water spillage. Connect a water supply to the unit (use pipe sealant on all joints) that is a 1/2”
minimum uninterrupted source of potable water. Failure to use potable water can result in emergency units producing impure
or contaminated water causing possible further injury. The drain tailpiece or waste should be connected to an adequate drain in
compliance with local plumbing codes.
OPERATION
The eyewash is activated by pushing the push handle back 90°. The unit will operate until the push handle is manually pulled
back up to the off position.
TESTING PROGRAM
The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated on a weekly
basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag (91-0635) with each unit.
On this tag the date of inspection and the inspectors initials should be noted.
MAINTENANCE
The valve and the eyewash are
the only portions of the unit that
may require maintenance.
Should you need parts to repair
this unit, please reference the
parts listing below for correct
part numbers. Reference
additional technical sheet
(supplied) for information on the
SE-910 ball valve. Before any
maintenance is done be sure to
shut the water supply off.
WARNING: Use only genuine
Speakman parts when
repairing or replacing
components.
To order parts call 1-800-5372107.
SE-582 REPLACEMENT/REPAIR PARTS
ITEM
1
2
3
4
PART/GROUP #
G05-0714
68-0035-MO-P
SE-910
43-0642
DESCRIPTION
Aerated Bullhorn Assy.
S/S Round Bowl
1/2” Stay-Open Ball Valve
with Paddle Handle
Drain Pipe
FLOW DATA
EYEWASH:
FLOW PRESSURE PSI (BAR)
FLOW RATE GPM (LPM)
30 (2.07)
3.6 (13.3)
NOTE: This unit should be connected to an uninterrupted source of potable water, with a minimum flowing
pressure of 30 PSI and a maximum static pressure of 125 PSI.
Note: All units meet existing
ANSI Z358.1 Standards and
OSHA Rules. Product
improvements may cause
specification and dimensional
changes without notice.
12/06
92-1457
Rev-8
">