SmartOnline 3-Phase 120/208V 30kVA 24kW
Double-Conversion UPS, Extended Run, 2 internal
batteries, SNMPWEBCARD Option, Tower, DB9
Serial, Hardwire
Highlights
30,000 VA (30kVA) tower UPS
with internal batteries
Saves valuable space and
simplifies runtime scalability
3-phase hardwire input and
MODEL NUMBER: SU30K3/3
output (120/208VAC). Wide input
voltage correction range (96 144V AC / 166 - 250V AC)
IGBT technology and zero
transfer time, on-line,
double-conversion operation
3 communication ports, SNMP
card slot and EPO jack
Package Includes
SU30K3/3 UPS System (power
and battery components in one
module)
PowerAlert Software and cabling
Warranty information
Description
Tripp Lite's SU30K3/3 30kVA SmartOnline 3-Phase Intelligent, True On-Line UPS System has been redesigned
Instruction manual
to save valuable space and simplify runtime scalability. Power and battery components are combined into a single, small-footprint module(the smallest in its
class). A robust internal battery runtime capability can be easily extended by installing additional optional internal battery packs through the convenient front
panel access door. The SU30K3/3 provides mission-critical equipment with the highest level of power protection available. Large capacity 30,000VA/24,000
watt UPS continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly
regulated, continuous sine wave output with zero transfer time offers compatibility with all equipment types. IGBT inverter technology produces output power
with <3% THD(total harmonic distortion), allowing connected equipment to perform at its peak. A 3:1 crest factor safely supports a variety of equipment, even
those with wildly-fluctuating power demands. Extremely efficient operation saves money by lowering electricity consumption. Hardwire input and output
connections support a variety of permanent or PDU style power connections. SU30K3/3 features 120/208V AC, 3-phase, 4-wire(plus ground), wye input and
output. It also features a wide input voltage correction range: 96-144/166-250V AC. Frequency is 50 or 60 Hz(auto-selectable). SU30K3/3 includes internal
power and battery components in a single small footprint tower module. Battery support can be extended with additional internal battery packs. A manual
bypass switch as well as an automatic bypass function ensure 100% availability of connected equipment by safely passing through AC power when the UPS
requires maintenance. Three built-in communication ports(RS-232, contact closure and AS-400) work with included PowerAlert Software to simultaneously
provide shutdown commands and reporting on multiple servers without the need for costly accessories. An accessory slot accepts an optional internal SNMP
card(model # SNMPWEBCARD) for remote shutdowns, reboots and more. A Battery Start Switch allows cold restart of UPS during a prolonged blackout to
utilize its batteries for periodic system access or data retrieval. An Emergency Power Off button turns UPS output OFF and disables Bypass output. Built-in
Emergency Power Off(EPO) interface supports remote emergency shutdown in large facilities. Front panel combination LCD/LED display alerts users to a
variety of UPS operational modes and conditions. A start-up service program is recommended to enhance the reliability of the installation.
Features
Saves valuable space: power and battery components combined into a single small-footprint module
Simplifies runtime scalability: convenient front panel battery access for expandable runtime with additional internal battery packs
True on-line, double conversion UPS with IGBT technology provides pure, sine wave AC output at all times
1/5
Performance Technology Solutions
14405 West Colfax Ave, Suite 225
Lakewood, CO 80401
(303) 536-7818 | sales@ptsups.com
Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
30,000VA/24,000 watt power capacity with 3-phase, hardwire 120/208V AC input/output connections
Features a wide input voltage correction range: 96 - 144/166 - 250V AC
Included internal batteries provide 13 minutes runtime at half load(12,000 watts) and 5 minutes runtime at full load(24,000 watts)
3:1 crest factor safely supports a variety of equipment, even those with wildly-fluctuating power demands
Extend runtime by installing an optional internal battery pack(model # SURBC2030) through the front panel access door. SU30K3/3 includes 3 internal
battery packs and accepts 1 additional internal battery pack. A standalone battery module compartment with a 4 battery pack capacity and daisy-chain
capability(model # SUBF2030) is available to further extend runtime.
3 communication ports(RS-232, contact closure and AS-400)
Slot for optional SNMP card(model # SNMPWEBCARD)
Manual bypass switch as well as an automatic bypass function ensures 100% availability of connected equipment by safely passing through AC power
when the UPS system requires maintenance
Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for periodic system access or data retrieval
Emergency Power Off button turns UPS output OFF and disables Bypass output
PowerAlert Universal UPS Power Management Software and 6 ft. communication cable included
Start-up service program is recommended to enhance the reliability of the installation
Built-in Emergency Power Off(EPO) interface supports remote emergency shutdown in large facilities
Combination LED/LCD display
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
30000
Output kVA Capacity (kVA)
30
Output Watt Capacity (Watts)
24000
Output kW Capacity (kW)
24
Power Factor
0.8
Crest Factor
3:1
Nominal Output Voltage(s)
Supported
120/208V; 3-Phase Wye
Frequency Compatibility
50 / 60 Hz
Output Voltage Regulation (Line
Mode)
+/- 2%
Output Voltage Regulation (Battery
Mode)
+/- 2%
Output Receptacles
Hardwire
Output AC Waveform (AC Mode)
Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave
INPUT
2/5
Performance Technology Solutions
14405 West Colfax Ave, Suite 225
Lakewood, CO 80401
(303) 536-7818 | sales@ptsups.com
Rated input current (Maximum Load)
90A (per phase, online)
Nominal Input Voltage(s) Supported
120/208V AC (3ph wye)
Nominal Input Voltage Description
3-Phase Wye, 4 wire (L1, L2, L3, N, G)
UPS Input Connection Type
Hardwire
Input Phase
3-Phase
BATTERY
Full Load Runtime (min.)
5 min. (24kw)
Half Load Runtime (min.)
13 min. (12kw)
Expandable Battery Runtime
Supports extended runtime with optional external battery packs
External Battery Pack Compatibility
BP240V350 ; BP240V400 ; BP240V400C; BP240V500 ; BP240V500C; SUBF2030(holds 4 SURBC2030);
SURBC2030
Expandable Runtime Description
Includes a battery housing with space for 1 optional SURBC2030 battery pack for extended runtime. Additional
runtime capacity is available by adding SUBF2030 and additional SURBC2030 batteries - see runtime chart for
specific recommendations
DC System Voltage (VDC)
240
Battery Recharge Rate (Included
Batteries)
2 - 4 hours from 10% to 90%
Internal UPS Replacement Battery
Cartridge
SURBC2030
Battery Access
Front panel internal battery access door
Battery Replacement Description
Hot-swappable, replaceable batteries
Expandable Runtime
Yes
VOLTAGE REGULATION
Voltage Regulation Description
Online, double-conversion power conditioning
Overvoltage Correction
Maintains continuous operation without using battery power during overvoltages to 144 / 250 (3-Phase, 4-Wire,
wye), reducing output within 2% of nominal
Undervoltage Correction
Maintains continuous operation without using battery power during brownout / undervoltage conditions to 96 / 166
(3-Phase, 4-Wire, wye)
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display
SELECTABLE LCD DISPLAY: indicates a wide range of UPS operational and fault/warning conditions including
operational mode, alarm/shutdown conditions, input/output voltage/frequency, battery voltage, load percentage and
more (see manual)
Switches
ON button turns UPS's inverter ON. "OFF" button turns UPS's inverter OFF. "Select" Button browses through items
displayed on LCD screen. "Enter" button selects items displayed on LCD screen. "Select" and "Enter" buttons used
simultaneously mute UPS alar
Alarm Cancel Operation
Power-fail alarm can be silenced using alarm-cancel switch
Audible Alarm
Alarms warn against a variety of operational conditions: low-battery, overload, shutdown, bypass and more
LED Indicators
7 LED DISPLAY: AC input, bypass input, AC-DC charger, DC-AC inverter, AC output, bypass operation and
battery operation
3/5
Performance Technology Solutions
14405 West Colfax Ave, Suite 225
Lakewood, CO 80401
(303) 536-7818 | sales@ptsups.com
SURGE / NOISE SUPPRESSION
EMI / RFI AC Noise Suppression
Yes
AC Suppression Joule Rating
2032
AC Suppression Response Time
Instantaneous
PHYSICAL
Installation Form Factors Supported
with Included Accessories
Tower
Primary Form Factor
Tower
UPS Power Module Dimensions
(hwd, in.)
35.9 x 19.5 x 37.9
UPS Power Module Dimensions
(hwd, cm)
91.2 x 49.5 x 96.3
UPS Power Module Weight (lbs.)
662
UPS Power Module Weight (kg)
300.5
UPS Shipping Dimensions (hwd / in.)
43 x 28 x 44.5
UPS Shipping Dimensions (hwd /
cm)
109.2 x 71.1 x 113
Shipping Weight (lbs.)
750
Shipping Weight (kg)
340.5
Cooling Method
Fans
UPS Housing Material
Steel
ENVIRONMENTAL
Operating Temperature Range
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
Storage Temperature Range
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Relative Humidity
5 to 95%, non-condensing
AC Mode BTU / Hr. (Full Load)
11171
COMMUNICATIONS
Communications Interface
DB9 Serial; Contact closure; Slot for SNMP/Web interface
Network Monitoring Port Description
RS232, contact closure and AS400 monitoring ports are supported by 3 separate DB9 ports
PowerAlert Software
Included
Communications Cable
DB9 cabling included
LINE / BATTERY TRANSFER
Transfer Time
No transfer time (0 ms.) in online, double-conversion mode
4/5
Performance Technology Solutions
14405 West Colfax Ave, Suite 225
Lakewood, CO 80401
(303) 536-7818 | sales@ptsups.com
Low Voltage Transfer to Battery
Power (Setpoint)
Maintains continuous operation during undervoltages as low as 96/166V AC (3-Phase, 4-Wire, wye). Below this
point, output is maintained utilizing battery reserves.
High Voltage Transfer to Battery
Power (Setpoint)
Maintains continuous operation during overvoltages as high as 144 / 250V AC (3-Phase, 4-Wire, wye). Above this
point, output is maintained utilizing battery reserves.
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Automatic inverter bypass; Hot swappable batteries
CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)
WARRANTY
Product Warranty Period (U.S. &
Canada)
1-year limited warranty
Product Warranty Period
(International)
2-year limited warranty
Product Warranty Period (Mexico)
1-year limited warranty
Product Warranty Period (Puerto
Rico)
2-year limited warranty
© 2015 Tripp Lite. All rights reserved. All product and company names are trademarks or registered trademarks of their respective holders. Use of them does
not imply any affiliation with or endorsement by them. Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.
Tripp Lite uses primary and third-party agencies to test its products for compliance with standards. See a list of Tripp Lite's testing agencies:
http://www.tripplite.com/products/product-certification-agencies
5/5