www.thepwrhouse.net - The Power House | Diesel Generator Sets

1500 r.p.m. 50 Hz.
231/400 VAC
Power Output Ratings
Standby Power (ESP)
Standby power is defined as the maximum power
available during a variable electrical power
sequence, under the stated operating conditions,
for which a generating set is capable ofdelivering
in theevent of a utility power outage orunder test
conditions for up to 500 hours of operation per
year under average of 70% load.Overloading is not
permissible
Standby Power (ESP)
Prime Power (PRP)
50 Hz. / 400 V
500
400
450
360
kVA
kW
kVA
kW
Engine
Manufacturer
Prime Power (PRP)
Model
Prime power is defined as being the maximum
No of Cylinder / Configuration
power which a generating set is capable of
Displacement lt
delivering continuously whilst supplying a variable Bore / Stroke
electrical load. Average load should be 70%. The
Compression Ratio
generator can be overloaded 10% for 1 hour per 12
Aspiration
hours.
Governor Type
Cooling System
Coolant Capacity
Lubrication Oil Capacity
Electrical System
Speed / Frequency
Engine Stand-by Power
Fuel Consumption lt/h
Exhaust Outlet Temperature
Exhaust Gas Flow
Combustion Air Flow
Cooling Air Flow
lt
mm
lt
lt
VDC
rpm
kWm
110%
100%
75%
50%
°C
m³/min
m³/min
m³/min
DOOSAN
P158LE
V-8
14,6
128/142
15:01
Turbo charged and Inter Cooled
ELECTRONIC
WATER
88,5
35
24
1500 rpm / 50 Hz
414
102,9
89,3
65,1
43,9
580
78,3
25,3
410
Alternator
Manufacturer
Origin
Model
Power Factor
No of Bearing
No of Poles
No of Leads
Voltage Regulation ( Steady State)
Insulation
Degree of Protection
Excitation System
Connection Type
Total Harmonic Content (No Load)
Frequency
Voltage Output
Rated Power (Standby)
Efficiency
Technical information and values are according to
ISO8528, ISO3046,NEMA MG1.22, IEC 600341, BS
49995000, VDE 0530 standards. Producing with
ISO9001, CE standards.
Hz
VAC
kVA
%
0,8
SINGLE
4
12
± %0,5
H
IP23
AVR, BRUSHLESS
STAR
< %2
50
230/400
DIMENSION
Canopied
Open Skid
L x W x H (mm)
4900X1600X2500
3360X1400X2040
Weight (kg)
4200
2950
Fuel Tank (lt)
850
850
All information given in this leaflet is intended for
general purposes only. Due to a policy continuous
improvement REAL reserves the right to amend
details and specifications without notice and all
information given is subject to the REAL's current
condition of sales.
ISO 9001:2000
www.thepwrhouse.net
1500
231/400
d/dak.50
VAC
1500
231/400
d/dak.50
VAC
1500 r.p.m. 50 Hz.
231/400 VAC
VAC 231/400
DESIGN SPECIFICATIONS
High quality, reliable and complate power unit,Compact design,Easy start and maintenance possibility,Every generating set is subjected to a comprehensive test programme which includes full load
testing and checking and providing of all control and safety shut down functions testing,Full engineered with a wide range of options and accessories:Canopy,soundproof and on road trailer.
STANDARD GENSET SPECIFICATIONS
ENGINE
DOOSAN heavy duty diesel engine - Four stroke, water cooled, turbocharged, charge air cooled - Direct injection fuel system - 24 VDC starter and charge alternator,
Replaceable fuel filter, oil filter and dry element air filter - Cooling radiator and fan - Starter battery (with lead acid) including Rack and Cables - Flexible fuel connection hoses and oil sump drain valve Industrial capacity exhaust silencer and steel bellows - Jacket water heater (at automatic models) - Operation mauals and circuit diagram documents
ALTERNATOR
Brushless, single bearing system, 4 poles - Insulation class H - Standard degree of protection IP21 - Self-exciting and self-regulating - Impregnation with tropicalised epoxy varnish
Solid state Automatic Voltage Regulator
BASE FRAME
The complete genset is mounted as whole on a heavy-duty fabricated, steel base frame. Antivibration pads are fixed between the engine/ alternator feet and the base frame - Base frame design
incorporates an integral fuel tank - The generating set can be lifted or carefully pushed / pulled by the base frame,Lifting eyes allow easy transportation by a crain - Dial type fuel gauge and drain plug on
the fuel tank.
CANOPY
All canopy parts are designed with modular principles - without welding assembly - Doors on each side - All metal canopy parts are painted by electrostatic - Exhaust silencer is protected against
environment influencespolyester powder paint - Thermally insulated engine exhaust system - Emergency stop push button is installed outside of canopy - Easy lifting and moving
Easy mainteneance and operation
CONTROL SYSTEM
Panel Equipments;
Control, supervision and protection panel is mounted on the genset base frame.
The control panel is equipped as follows:
1-Auto. Mains Failure Control Panel
Control Panel Equipments:
Conrtol panel with DSE 7220 module
Static battery charger
Emergency stop push button
Automatic shutdown on fault conditions
The module is used to monitor a mains supply and automatic start a stand-by generating set.
Micro-processor based design
Monitors engine performance and AC power output
LED and LCD alarm indication
Front panel configuration of timers and alarm trip points
provides signal to change over switch panel
event logging of shutdown alarms
Remote communication via RS232 port or RS485 modbus output
easy push button control
STOP/RESET-MANUAL-AUTO-TEST-START
Operation indicators accesed by the LCD display scroll push button.
Under/Over Speed
High Engine Temperature
Low Oil Pressure
Under/over generator volts
Under/over generator frequency
under/over mains frequency
under/over mains voltage
Low/High battery volts
Fail to start
Fail to stop
Charge fail
Over current
Emergency stop
CAN data fail
CAN ECU fail
Metering via LCD Display:
LED indications
Generator Volts (L-L/L-N)
Generator Amps (L1-L2-L3)
Generator Frequency (Hz)
Engine hours run
Engine oil pressure (PSI&Bar)
Engine speed RPM
Engine temperature (C & F)
Generator kVA
Generator kW
Generator power factor
Mains Frequency (Hz)
Mains Volts (F-F/F-N)
Plant battery volts
Mains available
Generator available
Mains on load
Generator on Load
1.1 Generating Set control module DSE 7220 features:
2. Power Outlet Terminal Board Mounted on the Genset Baseframe
ISO 9001:2000
www.thepwrhouse.net