INSTALLATION
INSTRUCTIONS
EL195UHE
E 2014 Lennox Industries Inc.
Dallas, Texas, USA
ELITE® SERIES GAS FURNACE
UPFLOW / HORIZONTAL AIR DISCHARGE
507274-01
07/2014
Supersedes 05/2014
Litho U.S.A.
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be ignored.
When you see this symbol on labels or in manuals, be alert
to the potential for personal injury or death.
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
AIR FLOW
HORIZONTAL LEFT
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person­
al injury or loss of life. Installation and service must
be performed by a licensed professional HVAC in­
staller (or equivalent), service agency or the gas sup­
plier.
AIR FLOW
AIR FLOW
UPFLOW
HORIZONTAL RIGHT
Table of Contents
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EL195UHE Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . . .
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Furnace as a Construction Heater . . . . . . . . . . .
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution, Ventilation Air . . . . . . . . . . . . . . .
Setting Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe and Fittings Specifications . . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure . . . . . . . . . . . . . . . . . . . . . . .
Venting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
3
3
3
4
5
5
8
13
13
13
16
16
Page 1
Vent Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Measurement . . . . . . . . . . . . . . . . . . . . . .
Proper Combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Testing Combustion Air For Non-Direct Vent . . . . . . . .
Other Unit Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . .
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start Up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
36
39
42
44
44
44
46
47
48
49
51
EL195UHE Unit Dimensions - inches (mm)
1NOTE
EXHAUST AIR
OUTLET
3−1/4
(83)
− 60C and 60D size units that require air
volumes 1800 cfm or over (850 L/s) must have
one of the following
1. Single side return air with transition, to accommodate
20 x 25 x 1 in. (508 x 635 x 25 mm) air filter.
Required to maintain proper air velocity. See figure 13.
2. Single side return air with optional Return Air Base
3. Bottom return air.
4. Return air from both sides.
5. Bottom and one side return air.
See Blower Performancetables for additional information.
1−7/8 (48)
D
SUPPLY AIR
OPENING
COMBUSTION
AIR INTAKE
2
Optional External Side Return Air Filter Kit is not for use
with the optional Return Air Base.
2 OPTIONAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
23−3/4
(603)
25
(635)
TOP VIEW
A
B
27−3/4
(705)
1−1/2 (38)
Front Panel
6−9/16 (167)
Left
9 (229)
Right
12−5/8 (321)
(Either Side)
2 OPTIONAL
SIDE RETURN
AIR FILTER KIT
(Either Side)
2 (51)
(Either Side)
GAS PIPING INLET
(Either Side)
CONDENSATE
TRAP CONNECTION
(Either Side)
6−1/2 (165)
(Either Side)
33
(838)
ELECTRICAL
INLET
(Either Side)
1−1/2
(38)
23
(584)
14−3/4
(375)
1
16
(406)
C
1−15/16 (49)
5/8
(16)
3/4
(19)
3−1/4
(83)
23−1/2
(597)
1 Bottom Return
Air Opening
1 Bottom
Return
Air Opening
FRONT VIEW
Model No.
14
(356)
Side Return
Air Opening
(Either Side)
AIR FLOW
3/4
(19)
9/16
(14)
19−7/16
(494)
9/16 (14)
SIDE VIEW
A
B
C
D
in.
mm
in.
mm
in.
mm
in.
mm
EL195UH070XE36B
17−1/2
446
16−3/8
416
16
406
7−5/8
194
EL195UH090XE48C
EL195UH110XE60C
21
EL195UH135XE60D
24−1/2
EL195UH045XE36B
533
622
19−7/8
23−3/8
505
594
Page 2
19−1/2
23
495
584
9−3/8
11−1/8
238
283
EL195UHE Gas Furnace
Shipping and Packing List
The EL195UHE Category IV gas furnace is shipped ready
for installation in the upflow or horizontal position. The fur­
nace is shipped with the bottom panel in place. The bottom
panel must be removed if the unit is to be installed in hori­
zontal or upflow applications with bottom return air.
The EL195UHE can be installed as either a Direct Vent
or a Non-Direct Vent gas central furnace.
The furnace is equipped for installation in natural gas ap­
plications. A conversion kit (ordered separately) is required
for use in propane/LP gas applications.
NOTE - In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors. In
Non-Direct Vent installations, combustion air is taken from
indoors or ventilated attic or crawlspace and flue gases are
discharged outdoors. See figures 1 and 2 for applications
involving roof termination.
DIRECT VENT INSTALLATION
NON-DIRECT VENT
INSTALLATION
EXHAUST OUTLET
COMBUSTION
AIR INTAKE OUTSIDE
OF HOUSE
EXHAUST
OUTLET
Package 1 of 1 contains
1 - Assembled EL195UHE unit
1 - Bag assembly containing the following:
1 - Snap bushing
1 - 1/2” diameter threaded street elbow
1 - Snap plug
1 - Wire tie
1 - Condensate trap
1 - Condensate trap cap
1 - Condensate trap clamp
1 - 2” diameter debris screen
1 - 3/4” Threaded street elbow
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
The following items may also be ordered separately:
1 - Thermostat
1 - LP/Propane changeover kit
1 - Return air base kit
1 - Horizontal suspension kit
1 - High altitude pressure switch
Safety Information
COMBUSTION
AIR INTAKE
INSIDE
OF HOUSE
FIGURE 1
NON-DIRECT VENT
INSTALLATION
Improper installation, adjustment, alteration, service
or maintenance can cause property damage,
personal injury or loss of life. Installation and service
must be performed by a licensed professional in­
staller (or equivalent), service agency or the gas sup­
plier.
CAUTION
NON-DIRECT VENT
INSTALLATION
EXHAUST
OUTLET
WARNING
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
EXHAUST
OUTLET
DANGER
Danger of explosion.
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
ATTIC SPACE
COMBUSTION
AIR INTAKE INSIDE
VENTILATED
CRAWL SPACE
There are circumstances in which odorant used with
LP/propane gas can lose its scent. In case of a leak,
LP/propane gas will settle close to the floor and may
be difficult to smell. An LP/propane leak detector
should be installed in all LP applications.
Use only the type of gas approved for use with this furnace.
Refer to unit nameplate.
EL195UHE units are CSA International certified to ANSI
Z21.47 and CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units
FIGURE 2
Page 3
must be installed according to the current National Fuel
Gas Code (ANSI‐Z223.1/NFPA 54). The National Fuel
Gas Code is available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National
Standard of Canada CSA‐B149 Natural Gas and Propane
Installation Codes, local plumbing or waste water codes
and other applicable local codes.
In order to ensure proper unit operation in non-direct vent
applications, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code
or CSA‐B149 standard.
Installation Locations
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the table in figure 12. Accessibility and
service clearances must take precedence over fire protec­
tion clearances.
NOTE - For installation on combustible floors, the furnace
shall not be installed directly on carpeting, tile, or other
combustible material other than wood flooring.
For installation in a residential garage, the furnace must be
installed so that the burner(s) and the ignition source are
located no less than 18 inches (457 mm) above the floor.
The furnace must be located or protected to avoid physical
damage by vehicles. When a furnace is installed in a public
garage, hangar, or other building that has a hazardous at­
mosphere, the furnace must be installed according to rec­
ommended good practice requirements and current Na­
tional Fuel Gas Code or CSA B149 standards.
NOTE - Furnace must be adjusted to obtain a temperature
rise within the range specified on the unit nameplate. Fail­
ure to do so may cause erratic limit operation and prema­
ture heat exchanger failure.
This EL195UHE furnace must be installed so that its
electrical components are protected from water.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling coils (figure 3), it
shall be installed in parallel with, or on the upstream side of,
cooling coils to avoid condensation in the heating compart­
ment. With a parallel flow arrangement, a damper (or other
means to control the flow of air) must adequately prevent
chilled air from entering the furnace. If the damper is manu­
ally operated, it must be equipped to prevent operation of
either the heating or the cooling unit, unless it is in the full
HEAT or COOL setting.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric
Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad­
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of the
Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Heating Unit Installed Parallel to Air Handler Unit
Dampers
(open during heating operation only)
Gas Unit
AIR FLOW
AIR FLOW
Air Handler Unit
Dampers
(open during cooling operation only)
Heating Unit Installed Upstream of Cooling Coil
AIR FLOW
Gas Unit
AIR FLOW
Cooling Coil
FIGURE 3
NOTE - This furnace is designed for a minimum continuous
return air temperature of 60°F (16°C) or an intermittent op­
eration down to 55°F (13°C) dry bulb for cases where a
night setback thermostat is used. Return air temperature
must not exceed 85°F (29°C) dry bulb.
The EL195UHE furnace may be installed in alcoves, clos­
ets, attics, basements, garages, crawl spaces and utility
rooms in the upflow or horizontal position.
This furnace design has not been CSA certified for installa­
tion in mobile homes, recreational vehicles, or outdoors.
Use of Furnace as Construction Heater
Lennox does not recommend the use of EL195UHE units
as a construction heater during any phase of construction.
Very low return air temperatures, harmful vapors and op­
eration of the unit with clogged or misplaced filters will dam­
age the unit.
EL195UHE units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
D The vent system must be permanently installed per
these installation instructions.
D A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not
allowed.
D The return air duct must be provided and sealed to the
furnace.
D Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
Page 4
D
Air filters must be installed in the system and must be
maintained during construction.
D
Air filters must be replaced upon construction comple­
tion.
D
The input rate and temperature rise must be set per the
furnace rating plate.
D
One hundred percent (100%) outdoor air must be pro­
vided for combustion air requirements during construc­
tion. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
D
The furnace heat exchanger, components, duct sys­
tem, air filters and evaporator coils must be thoroughly
cleaned following final construction clean-up.
D
All furnace operating conditions (including ignition, in­
put rate, temperature rise and venting) must be verified
according to these installation instructions.
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the fol­
lowing general recommendations must be considered
when installing a EL195UHE furnace:
• Place the furnace as close to the center of the air dis­
tribution system as possible. The furnace should also be
located close to the vent termination point.
• When the furnace is installed in non-direct vent applica­
tions, do not install the furnace where drafts might blow
directly into it. This could cause improper combustion
and unsafe operation.
• When the furnace is installed in non-direct vent applica­
tions, do not block the furnace combustion air opening
with clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
• When the furnace is installed in an attic or other insu­
lated space, keep insulation away from the furnace.
• When the furnace is installed in an unconditioned
space, consider provisions required to prevent freezing
of condensate drain system.
• Please consult the manufacturer of your evaporator coil
for their recommendations on distance required
between the heat exchanger and their drain pan. Ad­
equate space must be provided between the drain pan
and the furnace heat exchanger.
CAUTION
EL195UHE unit should not be installed in areas nor­
mally subject to freezing temperatures.
Page 5
WARNING
The State of California has determined that this prod­
uct may contain or produce a chemical or chemicals,
in very low doses, which may cause serious illness
or death. It may also cause cancer, birth defects or
reproductive harm.
WARNING
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rust­
ing and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the com­
bustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
Combustion, Dilution & Ventilation Air
If the EL195UHE is installed as a Non-Direct Vent Fur­
nace, follow the guidelines in this section.
NOTE - In Non-Direct Vent installations, combustion air is
taken from indoors or ventilated attic or crawlspace and
flue gases are discharged out-doors.
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today's homes, tight construction prac­
tices make it necessary to bring in air from outside for com­
bustion. Take into account that exhaust fans, appliance
vents, chimneys, and fireplaces force additional air that
could be used for combustion out of the house. Unless out­
side air is brought into the house for combustion, negative
pressure (outside pressure is greater than inside pressure)
will build to the point that a downdraft can occur in the fur­
nace vent pipe or chimney. As a result, combustion gases
enter the living space creating a potentially dangerous situ­
ation.
In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in
this section to install EL195UHE furnaces to ensure effi­
cient and safe operation. You must consider combustion
air needs and requirements for exhaust vents and gas pip­
ing. A portion of this information has been reprinted with
permission from the National Fuel Gas Code (ANSIZ223.1/NFPA 54). This reprinted material is not the com­
plete and official position of the ANSI on the referenced
subject, which is represented only by the standard in its en­
tirety.
In Canada, refer to the CSA B149 installation codes.
CAUTION
Do not install the furnace in a corrosive or contami­
nated atmosphere. Meet all combustion and ventila­
tion air requirements, as well as all local codes.
All gas‐fired appliances require air for the combustion pro­
cess. If sufficient combustion air is not available, the fur­
nace or other appliance will operate inefficiently and un­
safely. Enough air must be provided to meet the needs of
all fuel-burning appliances and appliances such as ex­
haust fans which force air out of the house. When fire­
places, exhaust fans, or clothes dryers are used at the
same time as the furnace, much more air is required to en­
sure proper combustion and to prevent a downdraft. Insuf­
ficient air causes incomplete combustion which can result
in carbon monoxide.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space con­
taining the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform
or at the return air duct connection can cause a potentially
dangerous negative pressure condition. Air for combustion
and ventilation can be brought into the confined space ei­
ther from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a
space categorized as unconfined, air can be brought in by
providing two permanent openings between the two
spaces. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas-fired equipment in the confined
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See figure 4.
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM INSIDE
In addition to providing combustion air, fresh outdoor air di­
lutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace compo­
nents.
ROOF TERMINATED
EXHAUST PIPE
The requirements for providing air for combustion and ven­
tilation depend largely on whether the furnace is installed in
an unconfined or a confined space.
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com­
bined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be un­
confined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the Air
from Outside section.
Confined Space
A confined space is an area with a volume less than 50 cu­
bic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the
com-bined input rating of all appliances installed in that
space. This definition includes furnace closets or small
equipment rooms.
EL195UH
E
OPENINGS
(To Adjacent
Unconfined
Space)
NOTE - Each opening shall have a free area of at least one square inch
per 1,000 Btu (645mm 2 per .29kW) per hour of the total input rating of
all equipment in the enclosure, but not less than 100 square inches
(64516mm.2).
FIGURE 4
Air from Outside
If air from outside is brought in for combustion and ventila­
tion, the confined space shall be provided with two perma­
nent openings. One opening shall be within 12” (305mm) of
the top of the enclosure and one within 12” (305mm) of the
bottom. These openings must communicate directly or by
ducts with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors or indirectly through verti­
cal ducts. Each opening shall have a minimum free area of
1 square inch per 4,000 Btu (645mm2 per 1.17kW) per hour
of total input rating of all equipment in the enclosure. When
communicating with the outdoors through horizontal ducts,
each opening shall have a minimum free area of 1 square
Page 6
inch per 2,000 Btu (645mm2 per .59kW) per total input rat­
ing of all equipment in the enclosure (See figure 5).It is also
permissible to bring in air for combustion from a ventilated
attic (figure 6) or ventilated crawl space (figure 7).
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
ROOF TERMINATED
EXHAUST PIPE
Ventilation
Louvers
(Crawl space)
Furnace
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
INLET
AIR
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
VENTILATION
LOUVERS
(For unheated
crawl space)
*Intake Debris Screen Provided)
* See table 6 for maximum vent lengths
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 5
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
*Intake Debris
Screen
(Provided)
Furnace
* See table 6 for maximum vent lengths
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 6
Page 7
FIGURE 7
If air from outside is brought in for combustion and ventila­
tion, the confined space must have two permanent open­
ings. One opening shall be within 12 inches (305 mm) of the
top of the enclosure and one opening within 12 inches (305
mm) of the bottom. These openings must communicate di­
rectly or by ducts with the outdoors or spaces (crawl or at­
tic) that freely communicate with the outdoors or indirectly
through vertical ducts. Each opening shall have a minimum
free area of 1 square inch (645 mm2) per 4,000 Btu (1.17
kW) per hour of total input rating of all equipment in the en­
closure. See figures 5 and 8. When communicating with
the outdoors through horizontal ducts, each opening shall
have a minimum free area of 1 square inch (645 mm2) per
2,000 Btu (.56 kW) per total input rating of all equipment in
the enclosure. See figure 9.
When ducts are used, they shall be of the same cross-sec­
tional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens must
be considered. If the design and free area of protective cov­
ering is not known for calculating the size opening required,
it may be assumed that wood louvers will have 20 to 25 per­
cent free area and metal louvers and grilles will have 60 to
75 percent free area. Louvers and grilles must be fixed in
the open position or interlocked with the equipment so that
they are opened automatically during equipment opera­
tion.
EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
flexible mounting leg). See figure 10. The bolt and washer
must be removed before the furnace is placed into op­
eration. After the bolt and washer have been removed, the
rigid leg will not touch the blower housing.
VENTILATION LOUVERS
(Each end of attic)
Units with 1/2 or 3/4 HP Blower Motor
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
RIGID LEG
(Remove shipping bolt
and washer)
INLET AIR
(Ends 12” above
bottom)
FURNACE
NOTE-The inlet and outlet air openings shall each have a free area of
at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour
of the total input rating of all equipment in the enclosure.
FIGURE 10
Installation - Setting Equipment
FIGURE 8
EQUIPMENT IN CONFINED SPACE ALL AIR FROM OUTSIDE
WARNING
Do not connect the return air duct to the back of the
furnace. Doing so will adversely affect the operation
of the safety control devices, which could result in
personal injury or death.
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
WARNING
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
INLET AIR
NOTE-Each air duct opening shall have a free area of at least one
square inch per 2,000 Btu (645mm2 per .59kW) per hour of the total
input rating of all equipment in the enclosure. If the equipment room
is located against an outside wall and the air openings communi­
cate directly with the outdoors, each opening shall have a free area
of at least 1 square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all other equipment in the enclosure.
FIGURE 9
Shipping Bolt Removal
Units with 1/2 and 3/4 hp blower motor are equipped with
three flexible legs and one rigid leg. The rigid leg is
equipped with a shipping bolt and a flat white plastic wash­
er (rather than the rubber mounting grommet used with a
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into
living space resulting in personal injury or death.
Upflow Applications
The EL195UHE gas furnace can be installed as shipped in
the upflow position. Refer to figure 12 for clearances. Se­
lect a location that allows for the required clearances that
are listed on the unit nameplate. Also consider gas supply
connections, electrical supply, vent connection, conden­
sate trap and drain connections, and installation and ser­
vice clearances [24 inches (610 mm) at unit front]. The unit
must be level from side to side. The unit may be positioned
from level to ½” toward the front. See figure 11.
Allow for clearances to combustible materials as indicated
on the unit nameplate.
Page 8
SETTING EQUIPMENT
UPFLOW APPLICATION
UNIT
FRONT
UNIT
FRONT
AIR FLOW
AIR FLOW
FRONT VIEW
SIDE VIEW
1/2”
max.
SIDE VIEW
HORIZONTAL APPLICATION
UNIT
FRONT
AIR FLOW
1/2”
max.
END VIEW
FRONT VIEW
Unit must be level side-to-side. Unit may be positioned from level to 1/2” toward the front to aid in draining.
FIGURE 11
Page 9
Return Air Guidelines
WARNING
Improper installation of the furnace can result in per­
sonal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or air in the living space. Use sheet metal screws and
joint tape to seal return air system to furnace.
In platform installations with furnace return, the fur­
nace should be sealed airtight to the return air ple­
num. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Al­
low absolutely no sagging, cracks, gaps, etc.
For no reason should return and supply air duct sys­
tems ever be connected to or from other heating de­
vices such as a fireplace or stove, etc. Fire, explo­
sion, carbon monoxide poisoning, personal injury
and/or property damage could result.
Installation Clearances
Top
Left Side
Return air can be brought in through the bottom or either
side of the furnace installed in an upflow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on page 2.
Refer to Engineering Handbook for additional information.
EL195UHE applications which include side return air
and a condensate trap installed on the same side of the
cabinet (trap can be installed remotely within 5 ft.) re­
quire either a return air base or field-fabricated transi­
tion to accommodate an optional IAQ accessory taller
than 14.5”. See figure 13.
Side Return Air
(with transition and filter)
Right Side
20” X 25” X 1”
(508mm X635mm X 25mm)
1-1/2 in. Air Filter
Bottom (Floor)
Top/Plenum
1 in. (25 mm)
*Front
0
Back
0
Sides
0†
Vent
0
Floor
0‡
Return
Air
Plenum
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap.
‡For installations on a combustible floor, do not install the fur­
nace directly on carpeting, tile or other combustible materials oth­
er than wood flooring.
Transition
FIGURE 13
FIGURE 12
Page 10
Optional Return Air Base
(Upflow Applications Only)
FURNACE
FRONT
INDOOR AIR
QUALITY
CABINET
(PCO, Filter
Cabinet, etc.)
AIR FLOW
17−1/2 (446) B Width (50W98)
21 (533) C Width (50W99)
24−1/2 (622) D Width (51W00)
IF BASE
IS USED
WITHOUT
IAQ CABINET,
A SINGLE
RETURN AIR
PLENUM
MUST
COVER BOTH
UNIT AND
RETURN
AIR BASE
OPENINGS
3−1/4
(83)
7−1/4
(184)
1 23
(584)
Overall
(Maximum)
1
Minimum
11 (279)
2 Maximum
1 Unit side return air
14 (356)
Opening
5−5/8
(143)
(570)
Overall
(Maximum)
SIDE RETURN
AIR OPENINGS
(Either Side)
23
(584)
26−7/8
(683)
OPTIONAL
RETURN
AIR BASE
1 22−7/16
3/4
(19)
SIDE VIEW
FRONT VIEW
NOTE- Optional side return air filter kits are not for use with return air base.
1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm of air and over (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air
opening. The size of the opening must not extend beyond the markings on the furnace cabinet.
2 To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
FIGURE 14
Removing the Bottom Panel
Removing the Bottom Panel
Remove the two screws that secure the bottom cap to the
furnace. Pivot the bottom cap down to release the bottom
panel. Once the bottom panel has been removed, reinstall
the bottom cap. See figure 15.
Horizontal Applications
WARNING
Do not install the furnace on its front or back.
See figure 16.
Screw
Bottom Cap
Bottom Panel
Front
FIGURE 15
Back
FIGURE 16
Page 11
The EL195UHE furnace can be installed in horizontal ap­
plications with either right- or left-hand air discharge.
Refer to figure 17 for clearances in horizontal applications.
TYPICAL HORIZONTAL APPLICATION
Internal Brace
(provided with kit)
Metal Strap
(typical)
Horizontal Application
Installation Clearances
Bracket
(typical)
Right-Hand Discharge
Left End
Right End
Air
Flow
Air
Flow
Air Flow
Bottom (Floor)**
Left-Hand Discharge
Top
Left End
FIGURE 18
Right End
Air
Flow
Air
Flow
Bottom (Floor)**
Top
0
Front*
0
NOTE - When the furnace is installed on a platform or with
the horizontal suspension kit in a crawlspace, it must be
elevated enough to avoid water damage, accommodate
drain trap and to allow the evaporator coil to drain.
Back
0
Platform Installation of Horizontal Unit
Ends
0
Vent
0
1 - Select location for unit keeping in mind service and
other necessary clearances. See figure 17.
Floor
0‡
2 - Construct a raised wooden frame and cover frame
with a plywood sheet. If unit is installed above finished
space, fabricate an auxiliary drain pan to be installed
under unit. Set unit in drain pan as shown in figure 19.
Leave 8 inches for service clearance below unit for
condensate trap.
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
**An 8” service clearance must be maintained below the unit to
provide for servicing of the condensate trap.
‡For installations on a combustible floor, do not install the fur­
nace directly on carpeting, tile or other combustible materials oth­
er than wood flooring.
FIGURE 17
Suspended Installation of Horizontal Unit
This furnace may be installed in either an attic or a crawl­
space. Either suspend the furnace from roof rafters or floor
joists, as shown in figure 18, or install the furnace on a plat­
form, as shown in figure 19. A horizontal suspension kit
(51W10) may be ordered from Lennox or use equivalent.
NOTE - Heavy-gauge sheet metal straps may be used to
suspend the unit from roof rafters or ceiling joists. When
straps are used to suspend the unit in this way, support
must be provided for both the ends. The straps must not in­
terfere with the plenum or exhaust piping installation. Cool­
ing coils and supply and return air plenums must be
supported separately.
3 - Provide a service platform in front of unit. When instal­
ling the unit in a crawl space, a proper support platform
may be created using cement blocks.
4 - Route auxiliary drain line so that water draining from
this outlet will be easily noticed by the homeowner.
5 - If necessary, run the condensate line into a conden­
sate pump to meet drain line slope requirements. The
pump must be rated for use with condensing furnaces.
Protect the condensate discharge line from the pump
to the outside to avoid freezing.
6 - Continue with exhaust, condensate and intake piping
installation according to instructions.
Page 12
Duct System
INTAKE PIPE
EXHAUST PIPE
*GAS
CONNECTOR
*Gas connector may be
used for Canadian
installation if accept­
able by local authority
having jurisdiction.
RAISED
PLATFORM
SERVICE PLATFORM
FIGURE 19
Return Air -- Horizontal Applications
Return air may be brought in only through the end of a fur­
nace installed in the horizontal position. The furnace is
equipped with a removable bottom panel to facilitate instal­
lation. See figure 15.
Filters
This unit is not equipped with a filter or rack. A field-pro­
vided high velocity rated filter is required for the unit to oper­
ate properly. Table 1 lists recommended filter sizes.
A filter must be in place whenever the unit is operating.
IMPORTANT
If a high­efficiency filter is being installed as part of
this system to ensure better indoor air quality, the fil­
ter must be properly sized. High­efficiency filters
have a higher static pressure drop than standard­ef­
ficiency glass/foam filters. If the pressure drop is too
great, system capacity and performance may be re­
duced. The pressure drop may also cause the limit to
trip more frequently during the winter and the indoor
coil to freeze in the summer, resulting in an increase
in the number of service calls.
Before using any filter with this system, check the
specifications provided by the filter manufacturer
against the data given in the appropriate Lennox
Product Specifications bulletin. Additional informa­
tion is provided in Service and Application Note
ACC­00­2 (August 2000).
TABLE 1
Filter Size
Furnace
Cabinet Width
Side Return
Bottom Return
17-1/2”
16 X 25 X 1 (1)
16 X 25 X 1 (1)
21”
16 X 25 X 1 (1)
20 X 25 X 1 (1)
24-1/2”
16 X 25 X 1 (2)
24 X 25 X 1 (1)
Page 13
Use industry‐approved standards to size and install the
supply and return air duct system. Refer to ACCA Manual
D. This will result in a quiet and low‐static system that has
uniform air distribution.
NOTE - This furnace is not certified for operation in heating
mode (indoor blower operating at selected heating speed)
with an external static pressure which exceeds 0.5 inches
w.c. Operation at these conditions may result in improper
limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable
access panel should be installed in the supply air duct. The
access panel should be large enough to permit inspection
of the heat exchanger. The furnace access panel must al­
ways be in place when the furnace is operating and it must
not allow leaks.
Return Air Plenum
NOTE - Return air must not be drawn from a room
where this furnace, or any other gas-fueled appliance
(i.e., water heater), or carbon monoxide-producing de­
vice (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pressure
is created in the room. If a gas appliance is operating in a
room with negative pressure, the flue products can be
pulled back down the vent pipe and into the room. This re­
verse flow of the flue gas may result in incomplete com­
bustion and the formation of carbon monoxide gas. This
raw gas or toxic fumes might then be distributed throughout
the house by the furnace duct system.
Return air can be brought in through the bottom or either
side of the furnace (return air brought into either side of fur­
nace allowed in upflow applications only). If a furnace with
bottom return air is installed on a platform, make an airtight
seal between the bottom of the furnace and the platform to
ensure that the unit operates properly and safely. Use fi­
berglass sealing strips, caulking, or equivalent sealing
method between the plenum and the furnace cabinet to en­
sure a tight seal. If a filter is installed, size the return air duct
to fit the filter frame.
Pipe & Fittings Specifications
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the Ameri­
can Society for Testing and Materials (ANSI/ASTM) stan­
dards. The solvent shall be free flowing and contain no
lumps, undissolved particles or any foreign matter that ad­
versely affects the joint strength or chemical resistance of
the cement. The cement shall show no gelation, stratifica­
tion, or separation that cannot be removed by stirring. Re­
fer to the table 2 below for approved piping and fitting ma­
terials.
CAUTION
IMPORTANT
Solvent cements for plastic pipe are flammable liq­
uids and should be kept away from all sources of
ignition. Do not use excessive amounts of solvent
cement when making joints. Good ventilation should
be maintained to reduce fire hazard and to minimize
breathing of solvent vapors. Avoid contact of ce­
ment with skin and eyes.
TABLE 2
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe)
Schedule 40 PVC (Cellular Core Pipe)
D1785
F891
Schedule 40 PVC (Fittings)
D2466
Schedule 40 CPVC (Pipe)
F441
Schedule 40 CPVC (Fittings)
SDR-21 PVC or SDR-26 PVC (Pipe)
SDR-21 CPVC or SDR-26 CPVC (Pipe)
Schedule 40 ABS Cellular Core DWV (Pipe)
F438
D2241
F442
F628
Schedule 40 ABS (Pipe)
D1527
Schedule 40 ABS (Fittings)
D2468
ABS-DWV (Drain Waste & Vent)
(Pipe & Fittings)
D2661
PVC-DWV (Drain Waste & Vent)
Pipe & Fittings)
D2665
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer
PVC Solvent Cement
CPVC Solvent Cement
ABS Solvent Cement
ASTM
SPECIFICATION
F493
D2235
D2564, D2235, F493
ABS to PVC or CPVC Transition Solvent
Cement
D3138
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
Use PVC primer and solvent cement or ABS solvent ce­
ment meeting ASTM specifications, refer to Table 2. As an
alternate, use all purpose cement, to bond ABS, PVC, or
CPVC pipe when using fittings and pipe made of the same
materials. Use transition solvent cement when bonding
ABS to either PVC or CPVC.
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used for
vent pipe hangers. Uniformly apply a liberal coat of PVC
primer for PVC or use a clean dry cloth for ABS to clean in­
side socket surface of fitting and male end of pipe to depth
of fitting socket.
Canadian Applications Only - Pipe, fittings, primer and
solvent cement used to vent (exhaust) this appliance must
be certified to ULC S636 and supplied by a single
manufacturer as part of an approved vent (exhaust) sys­
tem. In addition, the first three feet of vent pipe from the fur­
nace flue collar must be accessible for inspection.
F656
D2564
PVC/CPVC/ABS All Purpose Cement For
Fittings & Pipe of the same material
CANADA PIPE & FITTING & SOLVENT
CEMENT
EL195UHE exhaust and intake connections are
made of PVC. Use PVC primer and solvent cement
when using PVC vent pipe. When using ABS vent
pipe, use transitional solvent cement to make con­
nections to the PVC fittings in the unit.
MARKING
ULCS636
ABS to PVC or CPVC Transition Cement
POLYPROPYLENE VENTING SYSTEM
PolyPro by Duravent
ULC-S636
Page 14
TABLE 3
OUTDOOR TERMINATION USAGE*
STANDARD KITS
Input Size
045
070
090
110
135
Vent
Pipe
Dia. in.
Flush­
Mount
Kit
Wall Kit
CONCENTRIC KITS
Wall Ring Kit
2 inch
1-1/2 inch
2 inch
71M80
(US)
444W92
(CA)
69M29
(US)
444W92
(CA)
3 inch
2 inch
3 inch
51W11
(US)
51W12
(CA)
22G44 (US)
430G28 (CA)
44J40
(US)
481J20 (CA)
15F74
2
3YES
YES
1YES
1YES
5YES
2YES
2-1/2
3YES
YES
1YES
1YES
5YES
2YES
3
3YES
YES
1YES
1YES
5YES
2YES
2
3YES
YES
1YES
1YES
5YES
2YES
2-1/2
3YES
YES
1YES
1YES
5YES
2YES
3
3YES
YES
1YES
1YES
5YES
2YES
2
3YES
YES
YES
5YES
YES
YES
2-1/2
3YES
YES
YES
5YES
YES
YES
3
3YES
YES
YES
5YES
YES
YES
2
YES
YES
YES
5YES
YES
YES
2-1/2
YES
YES
5YES
YES
YES
3
YES
YES
5YES
YES
YES
3
YES
YES
5YES
Field
Fabricated
60L46 (US)
(CA)
444W93
YES
NOTE - Standard Terminations do not include any vent pipe or elbows external to the structure. Any vent pipe or elbows external to the structure must be included in total vent length
calculations. See vent length tables.
* Kits must be properly installed according to kit instructions.
1Requires field-provided outdoor 1-1/2” exhaust accelerator.
2Concentric kits 71M80 and 44W92 include 1-1/2” outdoor accelerator, when used with 045 and 070 input models.
3 Flush mount kits 51W11 and 51W12 includes 1-1/2 in. outdoor exhaust accelerator, required when used with 045, 070 and 090 input models.
4 Termination kits 30G28, 44W92, 44W93 and 81J20 are certified to ULC S636 for use in Canada only.
5 See table 8 for vent accelerator requirements.
Page 15
Venting Practices
Joint Cementing Procedure
All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.
Piping Suspension Guidelines
DANGER
SCHEDULE 40
PVC - 5'
all other pipe* - 3'
DANGER OF EXPLOSION!
Fumes from PVC glue may ignite during system
check. Allow fumes to dissipate for at least 5 minutes
before placing unit into operation.
1 - Measure and cut vent pipe to desired length.
2 - Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in a
leaking joint.
NOTE - Check the inside of vent pipe thoroughly for
any obstruction that may alter furnace operation.
3 - Clean and dry surfaces to be joined.
4 - Test fit joint and mark depth of fitting on outside of
pipe.
5 - Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket
surface of fitting and male end of pipe to depth of fitting
socket.
NOTE - Time is critical at this stage. Do not allow prim­
er to dry before applying cement.
6 - Promptly apply solvent cement to end of pipe and in­
side socket surface of fitting. Cement should be ap­
plied lightly but uniformly to inside of socket. Take care
to keep excess cement out of socket. Apply second
coat to end of pipe.
7 - Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe
are wet with cement, forcefully insert end of pipe into
socket until it bottoms out. Turn PVC pipe 1/4 turn dur­
ing assembly (but not after pipe is fully inserted) to dis­
tribute cement evenly. DO NOT turn ABS or cellular
core pipe.
NOTE - Assembly should be completed within 20 sec­
onds after last application of cement. Hammer blows
should not be used when inserting pipe.
8 - After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a bead
around its entire perimeter. Any gaps may indicate an
improper assembly due to insufficient solvent.
9 - Handle joints carefully until completely set.
* See table 2 for allowable pipe.
NOTE - Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
Wall Thickness Guidelines
24” maximum
3/4” minimum
inside
Wall
outside
FIGURE 20
1 - In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on
all sides of pipe through center of hole using a hanger.
2 - When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a
vacation home, make provisions for draining conden­
sate collection trap and lines.
Page 16
REPLACING FURNACE THAT
WAS PART OF A COMMON
VENT SYSTEM
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced
by EL195)
WATER
HEATER
OPENINGS
(To Adjacent
Room)
If an EL195UHE furnace replaces a furnace which was
commonly vented with another gas appliance, the size of
the existing vent pipe for that gas appliance must be
checked. Without the heat of the original furnace flue prod­
ucts, the existing vent pipe is probably oversized for the
single water heater or other appliance. The vent should be
checked for proper draw with the remaining appliance.
FIGURE 21
Exhaust Piping (Figures 24 and 25)
Route piping to outside of structure. Continue with installa­
tion following instructions given in piping termination sec­
tion.
The EL195UHE can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
NOTE - In Non‐Direct Vent installations, combustion air is
taken from indoors and flue gases are discharged out­
doors. In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing -- Size pipe according to
tables 4 and 5. Count all elbows inside and outside the
home. Table 4 lists the minimum vent pipe lengths per­
mitted. Table 5 lists the maximum pipe lengths permitted.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as it
exits the termination. Refer to table 8.
In some applications which permit the use of several differ­
ent sizes of vent pipe, a combination vent pipe may be
used. Contact Lennox' Application Department for assis­
tance in sizing vent pipe in these applications.
NOTE - The exhaust collar on all models is sized to accom­
modate 2” Schedule 40 vent pipe. In horizontal applica­
tions, any transition to exhaust pipe larger than 2” must be
made in vertical runs of the pipe. Therefore a 2” elbow must
be added before the pipe is transitioned to any size larger
than 2”. This elbow must be added to the elbow count used
to determine acceptable vent lengths. Contact the Applica­
tion Department for more information concerning sizing of
vent systems which include multiple pipe sizes.
CAUTION
Exhaust Pipe
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If verti­
cal discharge through an existing unused stack is re­
quired, insert PVC pipe inside the stack until the end
is even with the top or outlet end of the metal stack.
12” Min.
12” max
of straight pipe
CAUTION
The exhaust vent pipe operates under positive pres­
sure and must be completely sealed to prevent leak­
age of combustion products into the living space.
Vent Piping Guidelines
NOTE - Lennox has approved the use of DuraVent ® manu­
factured vent pipe and terminations as an option to PVC.
When using the PolyPro ® by DuraVent venting system the
vent pipe requirements stated in the unit installation in­
struction – minimum & maximum vent lengths, termination
clearances, etc. – apply and must be followed. Follow the
instructions provided with PoyPro by DuraVent venting
system for assembly or if requirements are more restrict­
ive. The PolyPro by Duravent venting system must also fol­
low the uninsulated and unconditioned space criteria listed
in table 7.
Page 17
Horizontal Application
NOTE - All horizontal runs of exhaust pipe must slope back to­
ward unit. A minimum of 1/4” (6mm) drop for each 12” (305mm)
of horizontal run is mandatory for drainage.
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE - Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
FIGURE 22
TABLE 4
MINIMUM VENT PIPE LENGTHS
EL195UHE
MODEL
045, 070, 090, 110, 135
MIN. VENT LENGTH*
15 ft. or
5 ft. plus 2 elbows or
10 ft. plus 1 elbow
*Any approved termination may be added to the minimum length listed.
Use the following steps to correctly size vent pipe diameter.
Pipe Size Process
1
2
3
What is the
furnace capacity?
045, 070, 090,
110 or 135?
IMPORTANT
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups
and may block the terminations.
Which style termination
being used?
Standard or concentric?
See table 3..
Which needs
most elbows?
Intake or
exhaust?
How many elbows?
4 Count all elbows inside
and outside house.
5
Desired pipe size?
2”, 2-1/2”, 3”
What is the altitude of
6 the furnace installation?
7
Use table 5 or 6 to find
max intake or exhaust pipe
length. Includes all vent
pipe and elbows inside and
outside the house.
FIGURE 23
Page 18
TABLE 5
Maximum Allowable Intake or Exhaust Vent Length in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be
same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Standard Termination at Elevation 0 - 4500 ft
Number Of
90° Elbows
Used
2” Pipe
2-1/2” Pipe
3” Pipe
Model
Model
Model
045
070
090
110
1
81
66
44
2
76
61
39
3
71
56
34
4
66
51
29
5
61
46
24
6
56
41
19
7
51
36
14
8
46
31
9
41
26
10
36
21
135
045
070
090
110
24
115
115
93
19
110
110
88
14
105
105
100
100
95
95
n/a
n/a
n/a
135
045
070
090
110
135
58
138
137
118
118
114
53
133
132
113
113
109
83
48
128
127
108
108
104
78
43
123
122
103
103
99
73
38
118
117
98
98
94
n/a
90
90
68
33
113
112
93
93
89
85
85
63
28
108
107
88
88
84
80
80
58
23
103
102
83
83
79
75
75
53
18
98
97
78
78
74
70
70
48
13
93
92
73
73
69
Standard Termination Elevation 4500 - 10,000 ft
Number Of
90° Elbows
Used
2” Pipe
2-1/2” Pipe
Model
045
070
090
1
81
66
2
76
3
71
4
5
3” Pipe
Model
070
090
110
44
115
115
93
61
39
110
110
56
34
105
105
66
51
29
100
61
46
24
95
56
41
19
7
51
36
14
8
46
31
9
41
26
10
36
21
n/a
n/a
135
Model
045
6
110
n/a
135
045
070
090
110
135
58
138
137
118
118
114
88
53
133
132
113
113
109
83
48
128
127
108
108
104
100
78
43
123
122
103
103
99
95
73
38
118
117
98
98
94
113
112
93
93
89
n/a
90
90
68
33
85
85
63
28
108
107
88
88
84
80
80
58
23
103
102
83
83
79
75
75
53
18
98
97
78
78
74
70
70
48
13
93
92
73
73
69
Page 19
TABLE 5 Continued
Maximum Allowable Intake or Exhaust Vent Length in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be
same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Concentric Termination at Elevation 0 - 4500 ft
Number Of
90° Elbows
Used
2” Pipe
2-1/2” Pipe
3” Pipe
Model
Model
Model
045
070
090
110
045
070
090
110
045
070
090
110
135
1
73
58
42
22
135
105
105
89
54
121
121
114
114
105
2
68
53
37
17
100
100
84
49
116
116
109
109
100
3
63
48
32
12
95
95
79
44
111
111
104
104
95
4
58
43
27
90
90
74
39
106
106
99
99
90
5
53
38
22
85
85
69
34
101
101
94
94
85
6
48
33
17
80
80
64
29
96
96
89
89
80
7
43
28
12
75
75
59
24
91
91
84
84
75
8
38
23
70
70
54
19
86
86
79
79
70
9
33
18
65
65
49
14
81
81
74
74
65
10
28
13
60
60
44
n/a
76
76
69
69
60
n/a
n/a
n/a
135
n/a
Concentric Termination Elevation 4501 - 10,000 ft
Number Of
90° Elbows
Used
2” Pipe
2-1/2” Pipe
3” Pipe
Model
Model
Model
045
070
090
045
070
090
110
045
070
090
110
135
1
73
58
42
105
105
89
54
121
121
114
114
105
2
68
53
37
100
100
84
49
116
116
109
109
100
3
63
48
32
95
95
79
44
111
111
104
104
95
4
58
43
27
90
90
74
39
106
106
99
99
90
5
53
38
22
85
85
69
34
101
101
94
94
85
6
48
33
17
80
80
64
29
96
96
89
89
80
7
43
28
12
75
75
59
24
91
91
84
84
75
8
38
23
70
70
54
19
86
86
79
79
70
9
33
18
65
65
49
14
81
81
74
74
65
10
28
13
60
60
44
n/a
76
76
69
69
60
n/a
110
n/a
135
n/a
Page 20
135
n/a
TABLE 6
Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated
Attic or Crawl Space For Intake Air in Feet
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length calculation.
Standard Termination at Elevation 0 - 4500 ft
Number Of
90° Elbows
Used
2” Pipe
2-1/2” Pipe
3” Pipe
Model
Model
Model
045
070
090
110
045
070
090
110
045
070
090
110
135
1
71
56
34
14
135
100
100
78
43
118
117
98
98
94
2
66
51
29
9
95
95
73
38
113
112
93
93
89
3
61
46
24
4
90
90
68
33
108
107
88
88
84
4
56
41
19
85
85
63
28
103
102
83
83
79
5
51
36
14
80
80
58
23
98
97
78
78
74
6
46
31
9
85
75
63
18
93
92
73
73
69
7
41
26
4
70
70
48
13
88
87
68
68
64
8
36
21
65
65
43
8
83
82
63
63
59
9
31
16
60
60
38
3
78
77
58
58
54
10
26
11
55
55
33
n/a
73
72
53
53
49
n/a
n/a
n/a
135
n/a
Standard Termination Elevation 4500 - 10,000 ft
Number Of
90° Elbows
Used
2” Pipe
2-1/2” Pipe
3” Pipe
Model
Model
Model
045
070
090
045
070
090
110
045
070
090
110
135
1
71
56
34
100
100
78
43
118
117
98
98
94
2
66
51
29
95
95
73
38
113
112
93
93
89
3
61
46
24
90
90
68
33
118
107
88
88
84
4
56
41
19
85
85
63
28
113
102
83
83
79
5
51
36
14
80
80
58
23
98
97
78
78
74
6
46
31
9
85
85
53
18
93
92
73
73
69
7
41
26
4
70
70
48
13
98
87
68
68
64
8
36
21
65
65
43
8
93
82
63
63
59
9
31
16
60
60
38
3
78
77
58
58
54
10
26
11
55
55
33
n/a
73
72
53
53
49
n/a
110
n/a
135
n/a
Page 21
135
n/a
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR
NON-DIRECT VENT APPLICATIONS
EXHAUST
EXHAUST INTAKE
INTAKE
2”
2”
2”
2”
or
3”
3”
TRANSITION
2”
TRANSITION
2”
*2”
*2”
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
FIGURE 24
TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON-DIRECT VENT
APPLICATIONS (RIGHT HAND DISCHARGE SHOWN)
45°
MAX
12” max.
2”
EXHAUST
45°
MAX
2”
or
2”
2”
2”
2”
or
2”
*2”
2”
SIDE VIEW
2”
2”
INTAKE
3”
TRANSITION
3”
*2”
EXHAUST
*2”
*2”
*2”
INTAKE
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
FIGURE 25
Page 22
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
Intake Piping
The EL195UHE furnace may be installed in either direct
vent or non-direct vent applications. In non-direct vent
applications, when intake air will be drawn into the furnace
from the surrounding space, the indoor air quality must be
considered and guidelines listed in Combustion, Dilution
and Ventilation Air section must be followed.
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW NON−DIRECT
VENT APPLICATIONS
INTAKE
DEBRIS
SCREEN
(Provided)
Follow the next two steps when installing the unit in Direct
Vent applications, where combustion air is taken from
outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct
vent applications (outdoors).
1 - Use transition solvent cement or a sheet metal screw
to secure the intake pipe to the inlet air connector.
2 - Route piping to outside of structure. Continue with
installation following instructions given in general
guidelines for piping terminations and intake and ex­
haust piping terminations for direct vent sections. Re­
fer to table 5 for pipe sizes.
Follow the next two steps when installing the unit in Non‐
Direct Vent applications where combustion air is taken
from indoors and flue gases are discharged outdoors.
1 - Use field-provided materials and the factory-provided
air intake screen to route the intake piping as shown in
figure 26 or 27. Maintain a minimum clearance of 3”
(76mm) around the air intake opening. The air intake
opening (with the protective screen) should always be
directed forward or to either side in the upflow position,
and either straight out or downward in the horizontal
position.
The air intake piping must not terminate too close
to the flooring or a platform. Ensure that the intake
air inlet will not be obstructed by loose insulation
or other items that may clog the debris screen.
NOTE - Debris screen and elbow may be rotated, so that
screen may be positioned to face forward or to either side.
FIGURE 26
TYPICAL AIR INTAKE PIPE CONNECTIONS
HORIZONTAL NON−DIRECT VENT APPLICATIONS
(Horizontal Right−Hand Air Discharge Application Shown)
PVC pipe
coupling
2 - If intake air is drawn from a ventilated attic (figure 28)
or ventilated crawlspace (figure 29) the exhaust vent
length must not exceed those listed in table 6. If 3” di­
ameter pipe is used, reduce to 2” diameter pipe at the
termination point to accommodate the debris screen.
OR
3 - Use a sheet metal screw to secure the intake pipe to
the connector, if desired.
INTAKE
DEBRIS
SCREEN
(Provided)
NOTE - Debris screen may be positioned straight out
(preferred) or with an elbow rotated to face down.
FIGURE 27
Page 23
CAUTION
If this unit is being installed in an application with
combustion air coming in from a space serviced by
an exhaust fan, power exhaust fan, or other device
which may create a negative pressure in the space,
take care when sizing the inlet air opening. The in­
let air opening must be sized to accommodate the
maximum volume of exhausted air as well as the
maximum volume of combustion air required for
all gas appliances serviced by this space.
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Attic and Outlet Air to Outside)
Ventilation Louvers
Inlet Air
(Minimum
12 in.(305mm) Above
attic floor)
Roof Terminated
Exhaust Pipe
*Intake Debris
Screen
(Provided)
Furnace
* See table 6 for maximum vent lengths
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 28
EQUIPMENT IN CONFINED SPACE
(Inlet Air from Ventilated Crawlspace and Outlet Air to Outside)
Roof Terminated
Exhaust Pipe
Ventilation
Louvers
(Crawl space)
Furnace
Coupling or
3 in. to 2 in.
Transition
(Field Provided)
Inlet Air
(Minimum
12 in.(305mm)
Above crawl
space floor)
General Guidelines for Vent Terminations
In Non‐Direct Vent applications, combustion air is taken
from indoors and the flue gases are discharged to the out­
doors. The EL195UHE is then classified as a non‐direct
vent, Category IV gas furnace.
In Direct Vent applications, combustion air is taken from
outdoors and the flue gases are discharged to the out­
doors. The EL195UHE is then classified as a direct vent,
Category IV gas furnace.
In both Non‐Direct Vent and Direct Vent applications, the
vent termination is limited by local building codes. In the ab­
sence of local codes, refer to the current National Fuel Gas
Code ANSI Z223-1/NFPA 54 in U.S.A., and current CSAB149 Natural Gas and Propane Installation Codes in Can­
ada for details.
Position termination according to location given in figure 31
or 32. In addition, position termination so it is free from any
obstructions and 12” above the average snow accumula­
tion.
At vent termination, care must be taken to maintain
protective coatings over building materials (prolonged
exposure to exhaust condensate can destroy protective
coatings). It is recommended that the exhaust outlet not be
located within 6 feet (1.8m) of an outdoor AC unit because
the condensate can damage the painted coating.
NOTE - See table 7 for maximum allowed exhaust pipe
length without insulation in unconditioned space during
winter design temperatures below 32°F (0°C). If required
exhaust pipe should be insulated with 1/2” (13mm) Arma­
flex or equivalent. In extreme cold climate areas, 3/4”
(19mm) Armaflex or equivalent may be necessary. Insula­
tion must be protected from deterioration. Armaflex with
UV protection is permissable. Basements or other en­
closed areas that are not exposed to the outdoor ambient
temperature and are above 32 degrees F (0°C) are to be
considered conditioned spaces.
IMPORTANT
Do not use screens or perforated metal in exhaust
terminations. Doing so will cause freeze-ups and
may block the terminations.
*Intake Debris Screen Provided)
* See table 6 for maximum vent lengths
NOTE-The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 29
IMPORTANT
For Canadian Installations Only:
In accordance to CSA International B149 installation
codes, the minimum allowed distance between the
combustion air intake inlet and the exhaust outlet of
other appliances shall not be less than 12 inches
(305mm).
Page 24
TABLE 7
Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For
Winter Design Temperatures Single - Stage High Efficiency Furnace
Winter Design
Temperatures1 °F (°C)
Unit Input Size
Vent Pipe
Diameter
045
070
PVC
2PP
090
PVC
2PP
110
PVC
2PP
135
PVC
2PP
PVC
2PP
32 to 21
2 in.
26
24
44
41
44
44
24
24
N/A
N/A
(0 to -6)
2-1/2 in.
18
N/A
32
N/A
50
N/A
58
N/A
N/A
N/A
3 in.
14
12
26
23
38
33
55
49
60
53
2 in
16
15
28
26
40
37
24
24
N/A
N/A
2-1/2 in.
12
N/A
20
N/A
30
N/A
44
N/A
N/A
N/A
3 in.
9
8
16
14
26
23
32
28
40
35
2 in.
10
9
20
18
30
28
24
24
N/A
N/A
2-1/2 in.
8
N/A
14
N/A
20
N/A
32
N/A
N/A
N/A
3 in.
4
3
10
8
16
14
26
23
30
26
20 to 1
(-7 to -17)
0 to -20
(-18 to -29)
1Refer
to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
vent pipe (PP)
NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the
maximum allowable intake or exhaust vent length listed in table 5 or 6 which ever is less.
NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See figure30.
2 Poly-Propylene
Conditioned
Space
Pipe Insulation
Conditioned
Space
Unconditioned
Space
FIGURE 30
Page 25
Exhaust
Pipe
Intake
Pipe
VENT TERMINATION CLEARANCES
FOR NON-DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
Fixed
Closed
Operable
F
B
B
C
I
Fixed
Closed
Operable
M
B
K
J
A
B
AREA WHERE TERMINAL
IS NOT PERMITTED
AIR SUPPLY INLET
VENT TERMINAL
US Installations1
A=
Clearance above grade, veranda,
porch, deck or balcony
B=
Clearance to window or
door that may be opened
C=
Clearance to permanently
closed window
D=
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610 mm)
from the center line of the terminal
E=
Clearance to unventilated soffit
F=
Clearance to outside corner
G=
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
4 feet (1.2 m) below or to side of opening;
1 foot (30cm) above opening
Canadian Installations2
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12”
* 12”
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* No minimum to outside corner
*
Clearance to inside corner
* Equal to or greater than soffit depth.
* No minimum to outside corner
*
H=
Clearance to each side of center line ex­
tended above meter / regulator assembly
* 3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
I=
Clearance to service regulator
vent outlet
Clearance to non-mechanical air
supply inlet to building or the com­
bustion air inlet to any other ap­
pliance
* 3 feet (.9m)
3 feet (.9m)
J=
K=
L=
M=
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
Clearance to mechanical air sup­
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch, deck or balcony
3 feet (.9m) above if within 10 feet
(3m) horizontally
7 feet (2.1m)†
7 feet (2.1m)†
*12 inches (305mm)‡
1 In
2 In
accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is
located between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open
on a minimum of two sides beneath the floor. Lennox recommends
avoiding this location if possible.
FIGURE 31
Page 26
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these instal­
lation instructions.”
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
Fixed
Closed
Operable
F
B
B
C
I
Fixed
Closed
Operable
M
B
A
K
J
B
AREA WHERE TERMINAL
IS NOT PERMITTED
AIR SUPPLY INLET
VENT TERMINAL
US Installations1
A=
Clearance above grade, veranda,
porch, deck or balcony
B=
Clearance to window or
door that may be opened
C=
Clearance to permanently
closed window
D=
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (610mm)
from the center line of the terminal
E=
Clearance to unventilated soffit
F=
Clearance to outside corner
G=
Clearance to inside corner
H=
Clearance to each side of center line ex­
tended above meter / regulator assembly
I=
Clearance to service regulator
vent outlet
Clearance to non-mechanical air
supply inlet to building or the com­
bustion air inlet to any other ap­
pliance
J=
K=
L=
Clearance to mechanical air sup­
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
1 In
12 inches (305mm) or 12 in. (305mm)
above average snow accumulation.
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap­
Btuh (3kw), 12 inches (305mm) for
pliances > 10,000 Btuh (3kw) and <50,000
appliances > 10,000 Btuh (3kw) and
Btuh (15 kw), 12 inches (305mm) for ap­
<100,000 Btuh (30kw), 36 inches (.9m)
pliances > 50,000 Btuh (15kw)
for appliances > 100,000 Btuh (30kw)
* 12”
* 12”
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
* No minimum to outside corner
*
* 3 feet (.9m)
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000 6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (228mm) for ap­
Btuh (3kw), 12 inches (305mm) for
pliances > 10,000 Btuh (3kw) and <50,000
appliances > 10,000 Btuh (3kw) and
Btuh (15 kw), 12 inches (305mm) for ap­
<100,000 Btuh (30kw), 36 inches (.9m)
pliances > 50,000 Btuh (15kw)
for appliances > 100,000 Btuh (30kw)
3 feet (.9m) above if within 10 feet
6 feet (1.8m)
(3m) horizontally
7 feet (2.1m)†
* 7 feet (2.1m)
M = Clearance under veranda, porch, deck or balcony
2 In
Canadian Installations2
*12 inches (305mm)‡
accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located
between two single family dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of
two sides beneath the floor. Lennox recommends avoiding this location if possible.
FIGURE 32
Page 27
12 inches (305mm)‡
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clearance will be in accordance with local installation
codes and the requirements of the gas supplier and these
installation instructions.”
Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations
NOTE - In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged to outdoors.
NOTE - Flue gas may be slightly acidic and may adversely
affect some building materials. If any vent termination is
used and the flue gasses may impinge on the building ma­
terial, a corrosion-resistant shield (minimum 24 inches
square) should be used to protect the wall surface. If the
optional tee is used, the protective shield is recommended.
The shield should be constructed using wood, plastic,
sheet metal or other suitable material. All seams, joints,
cracks, etc. in the affected area should be sealed using an
appropriate sealant. See figure 41.
Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In at­
tic or closet installations, vertical termination through the
roof is preferred. Figures 33 through 40 show typical
terminations.
1 - Intake and exhaust terminations are not required to be
in the same pressure zone. You may exit the intake on
one side of the structure and the exhaust on another
side (figure 34). You may exit the exhaust out the roof
and the intake out the side of the structure (figure 35).
2 - Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to il­
lustrations). Maximum separation is 3” (76mm) on roof
terminations and 6” (152mm) on side wall termina­
tions.
NOTE - When venting in different pressure zones, the
maximum separation requirement of intake and ex­
haust pipe DOES NOT apply.
3 - On roof terminations, the intake piping should termi­
nate straight down using two 90° elbows (See figure
33).
4 - Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust pip­
ing at the point where it exits the structure to improve
the velocity of exhaust away from the intake piping.
See table 8.
NOTE - Care must be taken to avoid recirculation of ex­
haust back into intake pipe.
Inches(mm)
3”(76mm) MAX.
SIZE TERMINATION
PIPE PER TABLE 8.
UNCONDITIONED
ATTIC SPACE
8” (203mm) MIN
12” (305mm) ABOVE
AVERAGE SNOW
ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 33
Exiting Exhaust and Intake Vent
(different pressure zones)
Exhaust
Pipe
Furnace
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
FIGURE 34
Exiting Exhaust and Intake Vent
(different pressure zones)
Roof Terminated
Exhaust Pipe
5 - On field-supplied terminations for side wall exit, ex­
haust piping may extend a maximum of 12 inches
(305mm) for 2” PVC and 20 inches (508mm) for 3”
(76mm) PVC beyond the outside wall. Intake piping
should be as short as possible. See figure 41.
6 - On field-supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of the
intake pipe without a termination elbow is 8” and a
minimum distance of 6” with a termination elbow. See
figure 41.
Furnace
Inlet Air
(Minimum 12 in.
305 MM) above
grade or snow
accumulation
FIGURE 35
TABLE 8
EXHAUST PIPE TERMINATION SIZE REDUCTION
EL195UHE
MODEL
Termination
Pipe Size
1-1/2” (38mm)
*045 and 070
*090
2” (51mm)
110
2” (51mm)
135
2” (51mm)
*EL195UHE-045, -070 and -090 units with the flush mount termination
must use the 1-1/2”accelerator supplied with the kit.
Page 28
7 - If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other ob­
structions, piping must be supported. At least one
bracket must be used within 6” from the top of the el­
bow and then every 24” (610mm) as shown in figure
41, to prevent any movement in any direction. When
exhaust and intake piping must be run up an outside
wall, the exhaust piping must be terminated with pipe
sized per table 8.The intake piping may be equipped
with a 90° elbow turndown. Using turndown will add 5
feet (1.5m) to the equivalent length of the pipe.
8 - A multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in figure 39.
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
1-1/2” (38mm) accelerator
provided on 71M80 & 44W92
kits for EL195UHE045P24B,
070P24B & 070P36B
OUTSIDE
WALL
INTAKE
AIR
EXHAUST
VENT
INTAKE
AIR
EXHAUST
VENT
INTAKE 12” (305mm) Min.
above grade or
AIR
CLAMP
(Not Furnished)
average snow
accumulation.
GRADE
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
FIGURE 38
2” EXTENSION FOR 2” PVC
PIPE1” EXTENSION FOR 3”
PVC PIPE
FURNACE
EXHAUST
PIPE
4''
EXHAUST
VENT
12”
(305mm)
5-1/2”
(140mm)
5”
(127mm)
INTAKE
AIR
FURNACE
INTAKE
PIPE
18” MAX.
(457mm)
GLUE EXHAUST
END FLUSH INTO
TERMINATION
Front View
EXHAUST VENT
12” (305mm) Min.
above grade or
average snow
INTAKE accumulation.
AIR
Inches (mm)
FLAT
SIDE
1-1/2” ACCELERATOR
(all -45, -070 and -090 units)
FLUSH-MOUNT SIDE WALL TERMINATION
51W11 (US) or 51W12 (Canada)
optional intake elbow
Side View
FIGURE 36
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
(30G28 or 81J20)
FIGURE 39
EXHAUST
VENT
12” (305mm)
Minimum
Above Average
Snow
Accumulation
1 1/2” (38mm) accelerator
provided on 71M80 & 44W92
kits for EL195UHE045P24B,
070P24B & 070P36B
INTAKE
AIR
EL195UHE DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
FLASHING
(Not Furnished)
3”-8”
(76mm-203mm)
*SIZE TERMINATION
PIPE PER TABLE 8.
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE *
8” - 12”
(203mm - 305mm)
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
SHEET METAL STRAP
(Clamp and sheet metal strap
must be field installed to support
the weight of the termination kit.)
INTAKE PIPE
INSULATION (optional)
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
ALTERNATE
INTAKE PIPE
CLAMP
FIELD-PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
INSULATE
TO FORM
SEAL
3” - 8”
(76mm203mm)
NOTE - Do not discharge exhaust gases directly into any chimney
or vent stack. If vertical discharge through an existing unused
chimney or stack is required, insert piping inside chimney until the
pipe open end is above top of chimney and terminate as illus­
trated. In any exterior portion of chimney, the exhaust vent must
be insulated.
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
FIGURE 37
FIGURE 40
Page 29
EXTERIOR
PORTION OF
CHIMNEY
FIELD FABRICATED WALL TERMINATION
NOTE − FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
2” (51mm) 3” (76mm)
Vent Pipe Vent Pipe
D
D
B
Intake
Elbow
C1
A
B
C2
A
STRAIGHT
APPPLICATION
A− Minimum clearance
above grade or average
snow accumulation
12” (305 mm)
12” (305 mm)
B− Maximum horizontal
separation between
intake and exhaust
6” (152 mm)
6” (152 mm)
C1 -Minimum from end of
exhaust to inlet of intake 8” (203 mm)
8” (203 mm)
C2 -Minimum from end of
exhaust to inlet of intake 6” (152 mm)
6” (152 mm)
D− Maximum exhaust
pipe length
20” (508 mm)
12” (305 mm)
E− Maximum wall support
distance from top of each 6” (152 mm)
pipe (intake/exhaust)
* WALL
SUPPORT
D
D
E
E
B
B
A
C1
EXTENDED
APPLICATION
A
C2
6” (152 mm)
See venting table 5 for maximum venting lengths
with this arrangement.
* Use wall support every 24” (610 mm). Use two
wall supports if extension is greater than
24” (610 mm) but less than 48” (1219 mm).
NOTE − One wall support must be within 6” (152 mm)
from top of each pipe (intake and exhaust) to prevent
movement in any direction.
ALTERNATE TERMINATIONS (TEE & FORTY−FIVE DEGREE ELBOWS ONLY)
B
D
B
Exhaust
D
1
C
C
2
Intake
Elbow
A
3
1
E
Intake
B
B− Horizontal
separation between
intake and exhaust
C− Minimum from
end of exhaust to
inlet of intake
A
Front View of
Intake and Exhaust
D
A− Clearance above
grade or average snow
accumulation
D− Exhaust pipe length
2” (51MM)
Vent Pipe
3” (76MM)
Vent Pipe
12” (305 mm) Min.
12” (305 mm) Min.
6” (152 mm) Min.
6” (152 mm) Min.
24” (610 mm) Max. 24” (610 mm) Max.
9” (227 mm) Min.
9” (227 mm) Min.
12” (305 mm) Min. 12” (305 mm) Min.
16” (405 mm) Max. 20” (508 mm) Max.
E− Wall support distance
from top of each pipe
6” (152 mm) Max.
(intake/exhaust)
6” (152 mm) Max.
Exhaust
12”
C
2
A
1
The exhaust termination tee should be connected to the 2” or 3” PVC flue pipe as shown in the illustration.
Do not use an accelerator in applications that include an exhaust termination tee.
The accelerator is not required.
2 As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield
(24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield
is recommended. The shield should be constructed using wood, sheet metal or other suitable material.
All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant.
3 Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust
away from adjacent property. The exhaust must never be directed toward the combustion air inlet.
FIGURE 41
Page 30
Details of Exhaust Piping Terminations for Non‐Direct
Vent Applications
Exhaust pipes may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is pre­
ferred. Figures 42 through 43 show typical terminations.
1 - Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in
table 8.The specified pipe size ensures proper veloc­
ity required to move the exhaust gases away from the
building.
2 - On field supplied terminations for side wall exit, ex­
haust piping may extend a maximum of 12 inches
(305mm) for 2” PVC and 20 inches (508mm) for 3”
(76mm) PVC beyond the outside wall.
3 - If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, pip­
ing must be supported every 24 inches (610mm).
When exhaust piping must be run up an outside wall,
any reduction in exhaust pipe size must be done after
the final elbow.
4 - Distance between exhaust pipe terminations on mul­
tiple furnaces must meet local codes.
SIZE TERMINATION
PIPE PER TABLE 8.
12” (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
3” (76mm) OR
2” (51mm) PVC
UNCONDITIONED
ATTIC SPACE
PROVIDE SUPPORT
FOR EXHAUST LINES
NON-DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 42
Page 31
EL195UHE NON-DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
SIZE TERMINATION
PIPE PER TABLE 8.
Minimum 12” (305MM)
above chimney top
plate or average snow
accumulation
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
EXTERIOR
PORTION OF
CHIMNEY
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver­
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus­
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 43
Condensate Piping
This unit is designed for either right‐ or left‐side exit of con­
densate piping in upflow applications. In horizontal applica­
tions, the condensate trap must extend below the unit. An
8” service clearance is required for the condensate trap.
Refer to figures 44 and 46 for condensate trap locations.
Figure 52 shows trap assembly using 1/2” PVC or 3/4”
PVC.
NOTE - If necessary the condensate trap may be installed
up to 5’ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4” per ft. toward trap.
1 - Determine which side condensate piping will exit the
unit, location of trap, field-provided fittings and length
of PVC pipe required to reach available drain.
2 - Use a large flat head screw driver or a 1/2” drive socket
extension and remove plug (figure 44) from the cold
end header box at the appropriate location on the side
of the unit. Install provided 3/4 NPT street elbow fitting
into cold end header box. Use Teflon tape or appropri­
ate pipe dope.
3 - Install the cap over the clean out opening at the base
of the trap. Secure with clamp. See figure 52.
4 - Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in fig­
ure 52. Route the condensate line to an open drain.
Condensate line must maintain a 1/4” downward slope
from the furnace to the drain.
CAUTION
Do not use copper tubing or existing copper conden­
sate lines for drain line.
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
Field Provided Drain Components
Trap
(same on
right side)
1-1/2 in.
Elbow
Plug
(same on left side)
Tubing
Barbed Fitting
Hose Clamp
NOTE - In upflow applications where side return
air filter is installed on same side as the conden­
sate trap, filter rack must be installed beyond
condensate trap or trap must be re-located to
avoid interference.
FIGURE 44
5 - Figures 47 and 49 show the furnace and evaporator
coil using a separate drain. If necessary the conden­
sate line from the furnace and evaporator coil can
drain together. See figures 48, 50 and 51.
Upflow furnace (figure 50) - In upflow furnace applica­
tions the field provided vent must be a minimum 1” to a
maximum 2” length above the condensate drain outlet
connection. Any length above 2” may result in a
flooded heat exchanger if the combined primary drain
line were to become restricted.
Horizontal furnace (figure 51) - In horizontal furnace
applications the field provided vent must be a mini­
mum 4” to a maximum 5” length above the condensate
drain outlet connection. Any length above 5” may re­
sult in a flooded heat exchanger if the combined pri­
mary drain line were to become restricted.
NOTE - In horizontal applications it is recommended to
install a secondary drain pan underneath the unit and
trap assembly.
NOTE - Appropriately sized tubing and barbed fitting
may be used for condensate drain. Attach to the drain
on the trap using a hose clamp. See figure 45.
FIGURE 45
6 - If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start-Up section.
Condensate line must slope downward away from the
trap to drain. If drain level is above condensate trap,
condensate pump must be used. Condensate drain
line should be routed within the conditioned space to
avoid freezing of condensate and blockage of drain
line. If this is not possible, a heat cable kit may be used
on the condensate trap and line. Heating cable kit is
available from Lennox in various lengths; 6 ft. (1.8m) kit no. 26K68; 24 ft. (7.3m) - kit no. 26K69; and 50 ft.
(15.2m) - kit no. 26K70.
Page 32
CONDENSATE TRAP LOCATIONS
Condensate Trap With Optional Overflow Switch
(Unit shown in upflow position with remote trap)
From Evaporator Coil
Horizontal Furnace 4” Min. to 5” Max.above
condensatedrain connection)
Field ProvidedVent
Min. 1” Above Condensate
Drain Connection
1” Min.
2” Max.
Furnace Condensate
Drain Connection
*5’ max.
PVC PipeOnly
Optional
Trap can be installed a
maximum 5' from furnace
To Drain
*Piping from furnace must slope down a minimum of
1/4” per ft. toward trap.
FIGURE 48
FIGURE 46
EL195UHE With Evaporator
Coil Using A Separate Drain
Evaporator drain
line required
(Trap at coil is optional)
Field Provided Vent
(1” min. 2” max. above
condensate connec­
tion)
Condensate
Drain Connection
FIGURE 47
Page 33
EL195UHE with Evaporatoir Coil Using a Separate Drain
(Unit shown in horizontal left-hand discharge position)
Field Provided Vent
(4” min. to 5” max. above
condensate connection)
Evaporator
Coil
4”min
5”max
5’ max.
PVC Pipe Only
Condensate
Drain Connection
Drain Pan
(Trap at coil is optional)
Piping from furnace and evaporator coil must slope down a minimum 1/4” per ft. toward trap
.
FIGURE 49
EL195UHE with Evaporator
Coil Using a Common Drain
IMPORTANT
Evaporator drain
line required
When combining the furnace and evaporator
coil drains together, the A/C condensate drain
outlet must be vented to relieve pressure in or­
der for the furnace pressure switch to operate
properly.
(Trap at coil is optional)
(1” min. to 2” Max.above
condensate drain connection)
Condensate
Drain Connection
FIGURE 50
EL195UHE with Evaporator Coil Using a Common Drain
(Unit shown in horizontal left-hand discharge position)
(4” min. to 5” Max.above
condensate drain connection)
Evaporator
Coil
4”min
5”max
5’ max.
PVC Pipe Only
Drain Pan
(Trap at coil is optional)
Piping from furnace and evaporator coil must
slope down a minimum 1/4” per ft. toward trap
FIGURE 51
Page 34
TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC
Optional Condensate Drain Connection
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
90° Street Elbow
3/4 inch PVC
(not furnished)
Adapter 3/4 inch slip X
3/4 inch mpt (not furnished)
Condensate Drain
Connection In Unit
90° Street Elbow
3/4 inch PVC
( furnished)
1 (25 mm) Min.
2 (50 mm) Max.
Above Top Of
Condensate Drain
Connection In Unit
Vent
Condensate Drain
Connection In Unit
5 Feet
Maximum
90° Elbow 3/4 inch PVC
(Not Furnished)
To
Trap
Optional DrainPiping FromTrap
3/4 inch PVC Pipe
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Coupling 3/4 inch slip X slip
(Not Furnished)
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
Drain Trap
Assembly
(Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
To
Drain
Drain Assembly for 3/4 inch Drain Pipe
Drain Trap
Clean Out
90° Elbow
3/4 inch PVC
(Not Furnished)
90° Elbow
3/4 inch PVC
(Not Furnished)
To Coupling 3/4 inch slip X slip
Drain
(Not Furnished)
To
Drain
DrainTrap Assembly with 1/2 inch Piping
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
DrainTrap Assembly
(Furnished)
Vent
1 (25 mm) Min. 2 (50 mm) Max. Above Top
Of Condensate Drain Connection In Unit
Vent
3/4 inch
1/2 inch
7
(178)
DrainTrap Assembly with 3/4 inch Piping
Condensate Drain
Connection In Unit
Condensate Drain
Connection In Unit
To
Drain
To
Drain
FIGURE 52
Page 35
Gas Piping
Gas supply piping should not allow more than 0.5”W.C.
drop in pressure between gas meter and unit. Supply gas
pipe must not be smaller than unit gas connection.
6 - In some localities, codes may require installation of a
manual main shut‐off valve and union (furnished by in­
staller) external to the unit. Union must be of the
ground joint type.
IMPORTANT
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petro­
leum gases.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory- and field-installed) for gas leaks. Use
a leak detecting solution or other preferred means.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.
The furnace must be isolated from the gas supply system
by closing its individual manual shut‐off valve during any
pressure testing of the gas supply system at pressures
greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet. The flexible connector can then
be added between the black iron pipe and the gas
supply line.
WARNING
Do not exceed 600 in-lbs (50 ft-lbs) torque when at­
taching the gas piping to the gas valve.
MANUAL MAIN SHUT-OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
1 - Gas piping may be routed into the unit through either
the left‐ or right‐hand side. Supply piping enters into
the gas valve from the side of the valve as shown in
figure 54.
1/8” N.P.T.
PLUGGED TAP
2 - When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be con­
sidered to avoid excessive pressure drop. Table 9 lists
recommended pipe sizes for typical applications.
4 - Piping should be sloped 1/4 inch per 15 feet (6mm per
5.6m) upward toward the gas meter from the furnace.
The piping must be supported at proper intervals, ev­
ery 8 to 10 feet (2.44 to 3.05m), using suitable hangers
or straps. Install a drip leg in vertical pipe runs to serve
as a trap for sediment or condensate.
5 - A 1/8” N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See figure 59.
FURNACE
ISOLATE
GAS VALVE
FIGURE 53
NOTE - Use two wrenches when connecting gas pip­
ing to avoid transferring torque to the manifold.
3 - Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or eleva­
tor shafts. Center gas line through piping hole. Gas
line should not touch side of unit. See figures 54 and
55.
CAP
IMPORTANT
When testing pressure of gas lines, gas valve must
be disconnected and isolated. See figure 53. Gas
valves can be damaged if subjected to pressures
greater than 1/2 psig (3.48 kPa).
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could
result in serious injury, death, or property damage.
Never use an open flame to test for gas leaks. Check
all connections using a commercially available soap
solution made specifically for leak detection. Some
soaps used for leak detection are corrosive to cer­
tain metals. Carefully rinse piping thoroughly after
leak test has been completed.
Page 36
Left Side Piping
(Standard)
Right Side Piping
(Alternate)
MANUAL
MAIN SHUT-OFF
VALVE
MANUAL
MAIN SHUT-OFF
VALVE
GROUND
JOINT
UNION
GROUND
JOINT
UNION
Gas Valve
Gas Valve
DRIP LEG
DRIP LEG
FIELD
PROVIDED
AND INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 54
Horizontal Applications
Possible Gas Piping Configurations
MANUAL
MAIN SHUT-OFF
VALVE
MANUAL
MAIN SHUT-OFF
VALVE
Horizontal Application
Left-Side Air Discharge
GROUND
JOINT
UNION
GROUND
JOINT
UNION
DRIP LEG
DRIP LEG
Gas Valve
Horizontal Application
Right-Side Air Discharge
MANUAL
MAIN SHUT-OFF
VALVE
Gas Valve
FIELD
PROVIDED
AND INSTALLED
NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 55
Page 37
GROUND
JOINT
UNION
DRIP LEG
TABLE 9
GAS PIPE CAPACITY - FT3/HR (kL/HR)
Nominal
Iron Pipe
Size
inches
(mm)
Internal
Diameter
inches
(mm)
10
(3.048)
20
(6.096)
30
(9.144)
40
(12.192)
50
(15.240)
60
(18.288)
70
(21.336)
80
(24.384)
90
(27.432)
100
(30.480)
1/2
(12.7)
.622
(17.799)
172
(4.87)
118
(3.34)
95
(2.69)
81
(2.29)
72
(2.03)
65
(1.84)
60
(1.69)
56
(1.58)
52
(1.47)
50
(1.42)
3/4
(19.05)
.824
(20.930)
360
(10.19)
247
(7.00)
199
(5.63)
170
(4.81)
151
(4.28)
137
(3.87)
126
(3.56)
117
(3.31)
110
(3.11)
104
(2.94)
1
(25.4)
1.049
(26.645)
678
(19.19)
466
(13.19)
374
(10.59)
320
(9.06)
284
(8.04)
257
(7.27)
237
(6.71)
220
(6.23)
207
(5.86)
195
(5.52)
1-1/4
(31.75)
1.380
(35.052)
1350
(38.22)
957
(27.09)
768
(22.25)
657
(18.60)
583
(16.50)
528
(14.95)
486
(13.76)
452
(12.79)
424
(12.00)
400
(11.33)
1-1/2
(38.1)
1.610
(40.894)
2090
(59.18)
1430
(40.49)
1150
(32.56)
985
(27.89)
873
(24.72)
791
(22.39)
728
(20.61)
677
(19.17)
635
(17.98)
600
(17.00)
2
(50.8)
2.067
(52.502)
4020
(113.83)
2760
(78.15)
2220
(62.86)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1160
(32.844)
2-1/2
(63.5)
2.469
(67.713)
6400
(181.22)
4400
(124.59)
3530
(99.95)
3020
(85.51)
2680
(75.88)
2480
(70.22)
2230
(63.14)
2080
(58.89)
1950
(55.22)
1840
(52.10)
3
(76.2)
3.068
(77.927)
11300
(319.98)
7780
(220.30)
6250
(176.98)
5350
(151.49)
4740
(134.22)
4290
(121.47)
3950
(111.85)
3670
(103.92)
3450
(97.69)
3260
(92.31)
Length of Pipe - feet (m)
NOTE - Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas ap­
pliances, the venting system is likely to be too large to prop­
erly vent the remaining attached appliances.
Conduct the following test while each appliance is operat­
ing and the other appliances (which are not operating) re­
main connected to the common venting system. If the vent­
ing system has been installed improperly, you must
correct the system as indicated in the general venting re­
quirements section.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon mon­
oxide poisoning or death.
The following steps shall be followed for each ap­
pliance connected to the venting system being
placed into operation, while all other appliances
connected to the venting system are not in
operation:
3 - Close all building doors and windows and all doors be­
tween the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dry­
ers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will oper­
ate at maximum speed. Do not operate a summer ex­
haust fan. Close fireplace dampers.
4 - Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 - After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle.
6 - After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace damp­
ers, and any other gas-burning appliances to their pre­
vious mode of operation.
7 - If a venting problem is found during any of the preced­
ing tests, the common venting system must be modi­
fied to correct the problem.
1 - Seal any unused openings in the common venting sys­
tem.
2 - Inspect the venting system for proper size and horizon­
tal pitch. Determine that there is no blockage, restric­
tion, leakage, corrosion, or other deficiencies which
could cause an unsafe condition.
Page 38
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current stan­
dards of the National Fuel Gas Code ANSI Z223.1.
The unit is equipped with a field make-up box. The makeup box may be moved to the right side of the furnace to fa­
cilitate installation. Secure the excess wire to the existing
harness to protect it from damage.
Electrical
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
Refer to figure 57 for field wiring, schematic wiring diagram
and troubleshooting.
CAUTION
Electrostatic discharge can affect elec­
tronic components. Take precautions
to neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
WARNING
Electric Shock Hazard. Can cause
injury or death. Unit must be properly
grounded in accordance with national
and local codes.
WARNING
Fire Hazard. Use of aluminum wire with this product
may result in a fire, causing property damage, severe
injury or death. Use copper wire only with this
product.
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
NOTE - Unit nameplate states maximum current draw.
Maximum Over-Current Protection allowed is 15 AMP.
CAUTION
Failure to use properly sized wiring and circuit
breaker may result in property damage. Size wiring
and circuit breaker(s) per Product Specifications
bulletin (EHB) and unit rating plate.
Holes are on both sides of the furnace cabinet to facilitate
wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
Before connecting the thermostat check to make sure the
wires will be long enough for servicing at a later date. Make
sure that thermostat wire is long enough to facilitate future
removal of blower for service.
INTERIOR MAKE-UP BOX INSTALLATION
remove and relocate
plug to unused
opening on left side
Complete the wiring connections to the equipment. Use the
provided unit wiring diagram and the field wiring diagram
shown in figure 57. Use 18-gauge wire or larger that is suit­
able for Class II rating for thermostat connections.
MAKE-UP
BOX
Electrically ground the unit according to local codes or, in
the absence of local codes, according to the current Na­
tional Electric Code (ANSI/NFPA No. 70) for the USA and
current Canadian Electric Code part 1 (CSA standard
C22.1) for Canada. A green ground wire is provided in the
field make-up box.
NOTE - The EL195UHE furnace contains electronic
components that are polarity sensitive. Make sure that the
furnace is wired correctly and is properly grounded.
Right Side
FIGURE 56
Page 39
Accessory Terminals
One line voltage “EAC” 1/4” spade terminal is provided on
the furnace integrated control. See figure 58 for integrated
control configuration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one
amp can be connected to this terminal with the neutral leg
of the circuit being connected to one of the provided neutral
terminals. If an accessory rated at greater than one amp is
connected to this terminal, it is necessary to use an exter­
nal relay.
One line voltage “120 HUM” 1/4” spade terminal is pro­
vided on the furnace integrated control. See figure 58 for
integrated control configuration. This terminal is energized
in the heating mode when the combustion air inducer is
operating. Any humidifier rated up to one amp can be con­
nected to this terminal with the neutral leg of the circuit be­
ing connected to one of the provided neutral terminals. If a
humidifier rated at greater than one amp is connected to
this terminal, it is necessary to use an external relay relay.
One 24V ”H” 1/4” spade terminal is provided on the furnace
integrated control. See figure 58 for integrated control con­
figuration. The terminal is energized in the heating mode
when the combustion air inducer is operating and the pres­
sure switch is closed. Any humidifier rated up to 0.5 amp
can be connected to this terminal with the ground leg of the
circuit connected to ground or the ”C” terminal.
Install the room thermostat according to the instruc­
tions provided with the thermostat. See figure 57 for
thermostat designations. If the furnace is being
matched with a heat pump, refer to the FM21 installa­
tion instruction or appropriate dual fuel thermostat in­
structions.
Indoor Blower Speeds
1 - When the thermostat is set to “FAN ON,” the indoor
blower will run continuously on the fan speed (FAN)
when there is no cooling or heating demand.
2 - When the EL195UHE is running in the heating mode,
the indoor blower will run on the heating speed
(HEAT).
3 - When there is a cooling demand, the indoor blower will
run on the cooling speed (COOL).
Generator Use - Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
D The furnace requires 120 volts + 10% (Range: 108
volts to 132 volts).
D The furnace operates at 60 Hz + 5% (Range: 57 Hz to
63 Hz).
D The furnace integrated control requires both polarity
and proper ground. Both polarity and proper grounding
should be checked before attempting to operate the
furnace on either permanent or temporary power.
D Generator should have a wave form distortion of less
than 5% THD (total harmonic distortion).
Page 40
TYPICAL EL195UHE WIRING DIAGRAM
FIGURE 57
Page 41
Unit Start-Up
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
Do not use this furnace if any part has been under­
water. A flood-damaged furnace is extremely dan­
gerous. Attempts to use the furnace can result in fire
or explosion. Immediately call a qualified service
technician to inspect the furnace and to replace all
gas controls, control system parts, and electrical
parts that have been wet or to replace the furnace, if
deemed necessary.
WARNING
Danger of explosion. Can cause injury
or product or property damage. Should
the gas supply fail to shut off or if
overheating occurs, shut off the gas
valve to the furnace before shutting off
the electrical supply.
RED LED
BLOWER OFF DELAY
RECALL BUTTON
FIGURE 58
CAUTION
TABLE 10
1/4” QUICK CONNECT TERMINALS
120HUM
Humidifier 120VAC
LINE
120VAC
XFMR
Transformer 120VAC
CIRC
Indoor blower 120VAC
EAC
Indoor air quality accessary 120VAC
NEUTRALS
Common 120VAC
Before attempting to perform any service or mainte­
nance, turn the electrical power to unit OFF at dis­
connect switch.
BEFORE LIGHTING the unit, smell all around the furnace
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
COOL
Cooling tap 24VAC
The gas valve on the EL195UHE is equipped with a gas
control switch (lever). Use only your hand to move switch.
Never use tools. If the the switch will not move by hand, do
not try to repair it. Force or attempted repair may result in a
fire or explosion.
HEAT
Heating tap 24VAC
Placing the furnace into operation:
FAN
Continuous blower 24 VAC
PARK (no power)
Park terminal for speed taps
FS
Flame sense
24 COM
Common 24VAC
HUM24
Humidifier 24VAC
3/16” QUICK CONNECT TERMINALS
EL195UHE units are equipped with an automatic hot sur­
face ignition system. Do not attempt to manually light burn­
ers on this furnace. Each time the thermostat calls for heat,
the burners will automatically light. The ignitor does not get
hot when there is no call for heat on these units.
Page 42
Priming Condensate Trap
The condensate trap should be primed with water prior to
start-up to ensure proper condensate drainage. Either pour
10 fl. oz. (300 ml) of water into the trap, or follow these steps
to prime the trap:
1 - Follow the lighting instructions to place the unit into op­
eration.
2 - Set the thermostat to initiate a heating demand.
3 - Allow the burners to fire for approximately 3 minutes.
4 - Adjust the thermostat to deactivate the heating de­
mand.
5 - Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again al­
low the burners to fire for approximately 3 minutes.
6 - Adjust the thermostat to deactivate the heating de­
mand and wait for the combustion air inducer to stop.
At this point, the trap should be primed with sufficient
water to ensure proper condensate drain operation.
9 - Replace the access panel.
10- Turn on all electrical power to to the unit.
11- Set the thermostat to desired setting.
NOTE - When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
12- If the appliance will not operate, follow the instructions
“Turning Off Gas to Unit” and call your service techni­
cian or gas supplier.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation (Figure 59)
1 - STOP! Read the safety information at the beginning of
this section.
2 - Set the thermostat to the lowest setting.
3 - Turn off all electrical power to the unit.
4 - This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 - Remove the access panel.
6 - Move gas valve switch to OFF. See figure 59.
7 - Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's instruc­
tions. If you do not smell gas go to next step.
8 - Move gas valve switch to ON. See figure 59.
MANIFOLD PRESSURE
ADJUSTMENT SCREW
(under barbed fitting)
MANIFOLD
PRESSURE
OUTLET
PORT
INLET
PRESSURE
PORT
GAS VALVE SHOWN IN ON POSITION
FIGURE 59
Page 43
Turning Off Gas to Unit
1 - Set the thermostat to the lowest setting.
2 - Turn off all electrical power to the unit if service is to be
performed.
3 - Remove the access panel.
4 - Move gas valve switch to OFF.
5 - Replace the access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 - Is the thermostat calling for heat?
2 - Are access panels securely in place?
3 - Is the main disconnect switch closed?
4 - Is there a blown fuse or tripped breaker?
5 - Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 - Is gas turned on at the meter?
7 - Is the manual main shut‐off valve open?
8 - Is the internal manual shut‐off valve open?
9 - Is the unit ignition system in lockout? If the unit locks
out again, inspect the unit for blockages.
Heating Sequence Of Operation
1 - When thermostat calls for heat, combustion air inducer
starts.
2 - Combustion air pressure switch proves blower opera­
tion. Switch is factory set and requires no adjustment.
3 - After a 15-second prepurge, the hot surface ignitor en­
ergizes.
4 - After a 20-second ignitor warm-up period, the gas
valve solenoid opens. A 4-second trial for ignition peri­
od begins.”
5 - Gas is ignited, flame sensor proves the flame, and the
combustion process continues.
6 - If flame is not detected after first ignition trial, the igni­
tion control will repeat steps 3 and 4 four more times
before locking out the gas valve (“WATCHGUARD”
flame failure mode). The ignition control will then auto­
matically repeat steps 1 through 6 after 60 minutes.
To interrupt the 60-minute “WATCHGUARD” period,
move thermostat from “Heat” to “OFF” then back to
“Heat”. Heating sequence then restarts at step 1.
1 - Connect the test gauge positive side “+“ to manifold
pressure tap on gas valve.
Gas Pressure Adjustment
Gas Flow (Approximate)
2 - Tee into the gas valve regulator vent hose and con­
nect to test gauge negative “-”.
3 - Start unit and let run for 5 minutes to allow for steady
state conditions.
TABLE 11
GAS METER CLOCKING CHART
Seconds for One Revolution
Natural
LP
EL195
Unit
1 cu ft
2 cu ft
1 cu ft
2 cu ft
Dial
Dial
Dial
DIAL
-045
80
160
200
400
-070
55
110
136
272
-090
41
82
102
204
-110
33
66
82
164
-135
27
54
68
136
Natural-1000 btu/cu ft
4 - After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
12.
NOTE - Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to remove
barbed fitting and replace threaded plug.
TABLE 12
Supply Line and Manifold Pressure (inches w.c.)
LP-2500 btu/cu ft
Furnace should operate at least 5 minutes before checking
gas flow. Determine time in seconds for two revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.) Divide by two and compare to time in table
11 below. If manifold pressure matches table 12 and rate is
incorrect, check gas orifices for proper size and restriction.
Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut off all other gas
appliances connected to meter.
Supply Pressure Measurement
When testing supply gas pressure, use the 1/8” N.P.T.
plugged tap or pressure post located on the gas valve to
facilitate test gauge connection. See figure 59. Check gas
line pressure with unit firing at maximum rate. Low pres­
sure may result in erratic operation or underfire. High pres­
sure can result in permanent damage to gas valve or over­
fire.
On multiple unit installations, each unit should be checked
separately, with and without units operating. Supply pres­
sure must fall within range listed in table 12.
Check Manifold Pressure
After supply pressure has been checked and adjusted,
check manifold pressure. Move pressure gauge to outlet
pressure tap located on unit gas valve (GV1).
Checks of manifold pressure are made as verification of
proper regulator adjustment.
IMPORTANT
For safety, connect a shut‐off valve between the
manometer and the gas tap to permit shut off of
gas pressure to the manometer.
Follow the steps below. Gas manifold Kit 10L34 provides
additional components if needed.
Unit
Fuel
Manifold
Pressure
Line Pressure
All
Nat
3.5
4.5 - 10.5
All
LP/Propane
10.0
11.0 - 13.0
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking com­
bustion. Take combustion sample beyond the flue outlet
and compare to the tables below.
TABLE 13
EL195
CO2% For Nat
CO2% For LP
Unit
-045
-070
-090
7.2 - 8.2
8.6 - 9.6
-110
-135
The maximum carbon monoxide reading should not exceed 50 ppm.
High Altitude Information
NOTE - In Canada, certification for installations at eleva­
tions over 4500 feet (1372 m) is the jurisdiction of local au­
thorities.
Units may be installed at altitudes up to 10,000 ft. above
sea level. See table 15 for de-rate manifold values. Units
installed at altitude of 7501 - 10,000 feet require an orifice
change. Units installed at altitude of 4501 - 10,000 feet re­
quire a pressure switch change which can be ordered sep­
arately. Table 15 lists conversion kit and pressure switch
requirements at varying altitudes.
The combustion air pressure switch is factory-set and re­
quires no adjustment.
Page 44
TABLE 14
Manifold and Supply Line Pressure 0-10,000ft.
Manifold Pressure in. wg.
EL195
Unit
All
Sizes
Gas
Supply Line
Pressure
in. w.g.
0 - 10000 ft.
0-4500 ft.
4501-5500 ft.
5501-6500 ft.
6501 - 7500ft.
7501 - 10000ft.
Natural
3.5
3.3
3.2
3.1
3.5
4.5
13.0
LP/propane
10.0
9.4
9.1
8.9
10.0
11.0
13.0
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion
procedure.
TABLE 15
LP/Propane Conversion Kit and Pressure Switch Requirements at Varying Altitudes
EL195
Unit
Natural to
LP/Propane
High Altitude
Natural Burner
Orifice Kit
High Altitude
LP/Propane Burner
Orifice Kit
0 - 7500 ft
(0 - 2286m)
7501 - 10,000 ft
(2286 - 3038m)
7501 - 10,000 ft
(2286 - 3038m)
High Altitude Pressure Switch
4501 - 7500 ft
(1373 - 2286m)
7501 -10,000 ft
(2286 - 3048m)
-045
No Change
93W87
-070
93W93
93W86
93W92
93W86
-110
93W93
93W86
-135
93W92
93W86
-090
*69W73
73W37
*68W68
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory-installed pressure switch from 0-4500 feet (0-1370 m).
Page 45
Testing for Proper Venting and Sufficient Combustion Air for Non-Direct Vent Applications
WARNING
CARBON MONOXIDE POISONING HAZARD!
3-
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monox­
ide poisoning or death.
The following steps shall be followed for each ap­
pliance connected to the venting system being
placed into operation, while all other appliances con­
nected to the venting system are not in operation.
45-
After the EL195UHE gas furnace has been started, the fol­
lowing test should be conducted to ensure proper venting
and sufficient combustion air has been provided to the
EL195UHE as well as to other gas‐fired appliances which
are separately vented.
If a EL195UHE furnace replaces a Category I furnace
which was commonly vented with another gas appliance,
the size of the existing vent pipe for that gas appliance must
be checked. Without the heat of the original furnace flue
products, the existing vent pipe is probably oversized for
the single water heater or other appliance. The vent should
be checked for proper draw with the remaining appliance.
The test should be conducted while all appliances (both in
operation and those not in operation) are connected to the
venting system being tested. If the venting system has
been installed improperly, or if provisions have not been
made for sufficient amounts of combustion air, corrections
must be made as outlined in the previous section.
6-
7-
8-
9-
1 - Seal any unused openings in the venting system.
2 - Visually inspect the venting system for proper size and
Page 46
horizontal pitch. Determine there is no blockage or re­
striction, leakage, corrosion, or other deficiencies
which could cause an unsafe condition.
To the extent that it is practical, close all building doors
and windows and all doors between the space in
which the appliances connected to the venting system
are located and other spaces of the building.
Close fireplace dampers.
Turn on clothes dryers and any appliances not con­
nected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan.
Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so
appliance will operate continuously.
Use the flame of match or candle to test for spillage of
flue gases at the draft hood relief opening after 5 min­
utes of main burner operation.
If improper venting is observed during any of the
above tests, the venting system must be corrected or
sufficient combustion/make‐up air must be provided.
The venting system should be re‐sized to approach
the minimum size as determined by using the ap­
propriate tables in appendix G in the current standards
of the National Fuel Gas Code ANSI-Z223.1/NPFA 54
in the U.S.A., and the appropriate Natural Gas and
Propane appliances venting sizing tables in the cur­
rent standard of the CSA-B149 Natural Gas and Pro­
pane Installation Codes in Canada.
After determining that each appliance remaining con­
nected to the common venting system properly vents
when tested as indicated in step 3, return doors, win­
dows, exhaust fans, fireplace dampers and any other
gas‐burning appliance to their previous condition of
use.
Other Unit Adjustments
HEAT FAN‐OFF TIME IN SECONDS
Fan On Delay
The heat fan on time of 30 seconds is not adjustable. The
cool fan on delay is 2 seconds and not adjustable.
Fan Off Delay
The heat fan off delay (amount of time that the blower oper­
ates after the heat demand has been satisfied) may be ad­
justed by changing the jumper position across the five pins
on the integrated control. The unit is shipped with a factory
fan off setting of 90 seconds. The fan off delay affects com­
fort and is adjustable to satisfy individual applications. Ad­
just the fan off delay to achieve a supply air temperature be­
tween 90° and 110°F at the moment that the blower is
de-energized. Longer off delay settings provide lower re­
turn air temperatures; shorter settings provide higher re­
turn air temperatures. See figure 60.
The cool fan off delay (amount of time that the blower oper­
ates after the cool demand has been satisfied) is 45 sec­
onds and not adjustable.
Blower Speeds
Follow the steps below to change the blower speeds.
1 - Turn off electrical power to furnace.
2 - Remove blower access panel.
3 - Disconnect existing speed tap at integrated control
speed terminal.
NOTE - Termination of any unused motor leads must be in­
sulated.
Page 47
NO JUMPER
60
90
120
180
60
90
120
180
60
90
120
180
To adjust fan-off timing, reposition jumper across pins to
achieve desired setting.
60 Second
90 Second
120 Second
180 Second
off Time
off Time
off Time
off Time
60
90
120
180
Primary Limit.
The primary limit is located on the heating compartment
vestibule panel. This limit is factory set and requires no ad­
justment.
Flame Rollout Switches (Two)
These manually reset switches are located in the burner
box.
Pressure Switch
The pressure switch is located in the heating compartment
on the cold end header box. This switch checks for proper
combustion air inducer operation before allowing ignition
trial. The switch is factory-set and must not be adjusted.
Temperature Rise
After the furnace has been started and supply and return
air temperatures have been allowed to stabilize, check the
temperature rise. If necessary, adjust the blower speed to
maintain the temperature rise within the range shown on
the unit nameplate. Increase the blower speed to decrease
the temperature. Decrease the blower speed to increase
the temperature rise. Failure to adjust the temperature rise
may cause erratic limit operation.
Fan Control
FIGURE 60
4 - Place unused blower speed tap on integrated control
“PARK” terminal or insulate.
5 - Refer to blower speed selection chart on unit wiring
diagram for desired heating or cooling speed. See
Product Specifications Bulletin for blower perfor­
mance data.
6 - Connect selected speed tap at integrated control
speed terminal.
7 - Resecure blower access panel.
8 - Turn on electrical power to furnace.
9 - Recheck temperature rise.
Electronic Ignition
The integrated control has an added feature of an internal
Watchguard control. The feature serves as an automatic
reset device for integrated control lockout caused by igni­
tion failure. This type of lockout is usually due to low gas
line pressure. After one hour of continuous thermostat de­
mand for heat, the Watchguard will break and remake ther­
mostat demand to the furnace and automatically reset the
integrated control to begin the ignition sequence.
Exhaust and Air Intake Pipe
1 - Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2 - Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut off at pressure switch. Check ter­
mination for blockages.
3 - Obstructed pipe or termination may cause rollout
switches to open. Reset manual flame rollout switches
on burner box assembly if necessary.
Winterizing and Condensate Trap Care
1 - Turn off power to the furnace.
Service
2 - Have a shallow pan ready to empty condensate water.
WARNING
3 - Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the
clean out cap.
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result
in dangerous operation, serious injury, death or
property damage.
Improper servicing could result in dangerous opera­
tion, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior to dis­
connecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
At the beginning of each heating season, system should be
checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal inju­
ry or death.
Filters
All air filters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the filters when
necessary to ensure proper furnace operation. Table 1 lists
recommended filter sizes.
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.
NOTE - After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
Electrical
1 - Check all wiring for loose connections.
2 - Check for the correct voltage at the furnace (furnace
operating).
3 - Check amp-draw on the blower motor with blower ac­
cess panel in place..
Unit Nameplate__________Actual__________
Cleaning the Burner Assembly
If cleaning the burners becomes necessary, follow the
steps below:
1 - Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels.
2 - Disconnect the wires from the gas valve.
3 - Remove the burner box cover (if equipped).
4 - Disconnect the gas supply line from the gas valve. Re­
move gas valve/manifold assembly.
5 - Mark and disconnect sensor wire from the sensor. Dis­
connect wires from flame rollout switches.
6 - Disconnect combustion air intake pipe. It may be nec­
essary to cut the existing pipe to remove burner box
assembly.
7 - Remove four screws which secure burner box assem­
bly to vest panel. Remove burner box from the unit.
8 - Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect
the inside of the burners and crossovers for any block­
age caused by foreign matter. Remove any blockage.
9 - Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the
center of the burner ports.
10 - Reconnect the sensor wire and reconnect the 2-pin
plug to the ignitor wiring harness. Reconnect wires to
flame rollout switches.
11 - Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burn­
er box cover.
12 - Reconnect wires to gas valve.
13 - Replace the blower compartment access panel.
14 - Refer to instruction on verifying gas and electrical con­
nections when re-establishing supplies.
15 - Follow lighting instructions to light and operate fur­
nace for 5 minutes to ensure that heat exchanger is
clean and dry and that furnace is operating properly.
16 - Replace heating compartment access panel.
Page 48
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model
number listed on the CSA nameplate -- Example: EL195UH045XE36B-01. All service must be performed by a licensed
professional installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Outer access panel
Blower access panel
Top Cap
Control Panel Parts
Transformer
Integrated control board
Door interlock switch
Blower Parts
Blower wheel
Motor
Motor mounting frame
Blower housing cutoff plate
Heating Parts
Flame Sensor
Heat exchanger assembly
Gas manifold
Combustion air inducer
Gas valve
Main burner cluster
Main burner orifices
Pressure switch
Ignitor
Primary limit control
Flame rollout switches
FOR THE PROVINCE OF ONTARIO, HORIZONTAL SIDEWALL VENT APPLICATIONS ONLY
For exterior horizontal venting applications, the 2” X 1.5”
reducer for 2” venting at the point where the exhaust pipe
exits the structure is not required in direct or non­direct vent
applications in the Province of Ontario. In these applica­
tions, the vent should be oriented such that the exhaust
Page 49
plume is unobjectionable. If the installation requires more
separation between the flue gases and the building struc­
ture, a reducer may be installed on the exhaust pipe to in­
crease the flue gas velocity.
Requirements for Commonwealth of Massachusetts
Modifications to NFPA-54, Chapter 10
Revise NFPA-54 section 10.8.3 to add the following re­
quirements:
For all side wall, horizontally vented, gas-fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above the finished grade in the area of the venting, in­
cluding but not limited to decks and porches, the following
requirements shall be satisfied:
1 - INSTALLATION OF CARBON MONOXIDE DETEC­
TORS. At the time of installation of the side wall, hori­
zontally vented, gas-fueled equipment, the installing
plumber or gasfitter shall observe that a hard-wired
carbon monoxide detector with an alarm and battery
backup is installed on the floor level where the gas
equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery-oper­
ated or hard-wired carbon monoxide detector with an
alarm is installed on each additional level of the dwell­
ing, building or structure served by the side wall, hori­
zontally vented, gas-fueled equipment. It shall be the
responsibility of the property owner to secure the ser­
vices of qualified licensed professionals for the instal­
lation of hard-wired carbon monoxide detectors.
a - In the event that the side wall, horizontally vented,
gas-fueled equipment is installed in a crawl space
or an attic, the hard-wired carbon monoxide detec­
tor with alarm and battery back-up may be installed
on the next adjacent floor level.
b - In the event that the requirements of this subdivi­
sion cannot be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30) day
period, a battery-operated carbon monoxide detec­
tor with an alarm shall be installed.
2 - APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accor­
dance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certi­
fied.
3 - SIGNAGE. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade di­
rectly in line with the exhaust vent terminal for the hori­
zontally vented, gas-fueled heating appliance or
equipment. The sign shall read, in print size no less
than one-half (1/2) inch in size, “GAS VENT DIRECT­
LY BELOW. KEEP CLEAR OF ALL OBSTRUC­
TIONS.”
4 - INSPECTION. The state or local gas inspector of the
side wall, horizontally vented, gas-fueled equipment
shall not approve the installation unless, upon inspec­
tion, the inspector observes carbon monoxide detec­
tors and signage installed in accordance with the pro­
visions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt
from 24 CMR 5.08(2)(a) 1 through 4:
1 - The equipment listed in Chapter 10 entitled “Equip­
ment Not Required to Be Vented” in the most current
edition of NFPA 54 as adopted by the Board; and
2 - Product Approved side wall, horizontally vented, gasfueled equipment installed in a room or structure sepa­
rate from the dwelling, building or structure used in
whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas-fueled equipment provides a vent­
ing system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
1 - Detailed instructions for the installation of the venting
system design or the venting system components:
and
2 - A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas-fueled equipment does not pro­
vide the parts for venting the flue gases, but identifies “spe­
cial venting systems,” the following requirements shall be
satisfied by the manufacturer:
1 - The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2
The “special venting systems” shall be Product Ap­
proved by the Board, and the instructions for that sys­
tem shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas-fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instruc­
tions shall remain with the appliance or equipment at
the completion of the installation.
Page 50
Start-Up & Performance Check List
UNIT SET UP
Furnace:
Model Number_______________
Serial Number_________________
Line Voltage
SUPPLY
AIR
2
4
1
GAS SUPPLY
Natural Gas
LP Propane Gas
3
Piping Connections Tight
2
Leak Tested
Flter
Supply Line Pressure “W.C.________
RETURN AIR
1
Gas Supply Pressure
3
1
DUCT SYSTEM
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
2
RETURN DUCT
INTAKE / EXHAUST PIPE
Sealed
All Joints Primed and Glued
Filter Installed and Clean
Terminations Installed Properly
Grilles Unobstructed
Horizontal Pipes Sloped (if applicable)
4
Condensate Trap Primed / Line Sloped
VOLTAGE CHECK
Supply Voltage _____
Electrical Connections Tight
Pipes Supported
Heat Cable Installed and Operable (if applicable)
Page 51
UNIT OPERATION
HEATING MODE
1
2
COOLING MODE
GAS MANIFOLD PRESSURE “W.C._____
COMBUSTION SAMPLE CO2%______CO PPM_______
3
INDOOR BLOWER
AMPS______
4
TEMPERATURE DROP
Return Duct Temperature _________
Supply Duct Temperature _ _______
3
INDOOR BLOWER
AMPS______
4
TEMPERATURE RISE
Temperature Drop = _________
5
Supply Duct Temperature ________
Return Duct Temperature _ _____
Temperature Rise = ________
5
6
TOTAL EXTERNAL STATIC
Supply External Static _______
Return External Static + ______
Total External Static = _______
8
DRAIN LINE
Leak Free
9
CONDENSATE LINE
THERMOSTAT
Adjusted and Programmed
Leak Free
7
TOTAL EXTERNAL STATIC (dry coil)
Supply External Static _______
Return External Static + ______
Total External Static = _______
Explained Operation to Owner
VENT PIPE
Leak Free
Combustion CO2
2
7
SUPPLY
AIR
Thermostat
Temperatures
8
Gas Manifold Pressure
9
4
1
Blower Motor Amps
3
6
Duct Static
High +
RETURN AIR
5
Low -
Contractor's: Name_________________________Telephone_____________Checklist Completed____________________
Job Address_____-________________________________Technician's Name___________________________________
Page 52