800-453-5464
sales@kingwireinc.com
TYPE MC CABLE
APPLICATION: Type MC Cable can be used to replace wire and conduit in applications such
as cable tray, power lighting, service feeders and branch circuits as permitted
by the National Electrical Code.
PRODUCT Type MC cable is constructed with 3 or 4 8000 series compact stranded
FEATURES: aluminum XHHW-2 conductors cabled with a bare or insulated 8000 series
aluminum grounding conductor. A binder identification baring tape is wrapped
over the cabled assembly. Aluminum armor is interlocked over the conductor
assembly. All insulated conductors are phase identified.
STANDARDS: KINGWIRE Type MC Cable with Type XHHW-2 conductors meets or exceeds
UL standard 44, UL standard 1569, Federal Specification JC-30B, ICEA S-66524 and requirements of the National Electrical Code.
KINGWIRE MC Cable
Cond. Size
AWG or
MCM
Sub Assembly
(O.D.)
Overall
Diameter
(in)
6-6-6-6
0.57
0.78
237
50
4-4-4-6
0.66
0.88
298
65
2-2-2-6
0.78
1
411
90
1-1-1-4
0.89
1.11
496
100
1/0-1/0-1/0-4
0.97
1.19
578
120
Weight per 1000 ft.
(lbs)
Ampacity
(amps)
75° C
THREE CONDUCTOR WITH GROUND
2/0-2/0-2/0-4
1.06
1.27
678
135
3/0-3/0-3/0-4
1.16
1.38
833
155
4/0-4/0-4/0-2
1.27
1.59
1089
180
250-250-250-2
1.42
1.73
1275
205
300-300-300-2
1.51
1.79
1361
230
350-350-350-2
1.62
1.94
1653
250
400-400-400-1
1.72
2.04
1830
270
500-500-500-1
1.88
2.2
2177
310
600-600-600-1
2.1
2.4
2608
340
750-750-750-1/0
2.3
2.5
3118
385
KINGWIRE MC Cable
Cond. Size
AWG or
MCM
Sub Assembly
(O.D.)
Overall
Diameter
(in)
Weight per 1000 ft.
(lbs)
Ampacity
(amps)
75° C
FOUR CONDUCTOR WITH GROUND
6-6-6-6-6
0.70
0.92
278
50
4-4-4-4-6
0.77
1.04
360
65
2-2-2-2-6
0.89
1.10
482
72
1-1-1-1-4
0.99
1.21
619
80
1/0-1/0-1/0-1/0-4
1.08
1.3
727
92
2/0-2/0-2/0-2/0-4
1.18
1.4
858
108
3/0-3/0-3/0-3/0-4
1.3
1.61
1138
124
4/0-4/0-4/0-4/0-2
1.42
1.74
1374
144
250-250-250-250-1
1.58
1.9
1634
184
300-300-300-300-1
1.70
1.99
1722
230
350-350-350-350-1/0
1.82
2.13
1969
250
400-400-400-400-1/0
1.91
2.20
2189
300
500-500-500-500-2/0
2.11
2.35
2653
310
600-600-600-600/2/0
2.35
2.67
3177
340
750-750-750-750-3/0
2.60
2.86
3858
385
Notes:
1. Ampacities shown are for general use as specified by the National Electrical Code, Section 310.15
Under normal conditions four conductor ampacities are not derated as shown above. If NEC Section 310.15 (b) (4)
(a) does not consider the neutral as current carrying conductor, use ampacities listed for the three conductor cable.
2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%
3. Other conductor sizes available upon request. Other ground sizes are available upon request.
Download PDF