LIEBERT® PSPTM
Quick Installation Guide
IMPORTANT SAFETY
INSTRUCTIONS
Liebert® PSPTM UPS
• Do not connect equipment that
may overload the UPS or
demand half-wave rectification,
such as a laser printer.
• Connect the UPS only to an
earthed / grounded socket that
meets electrical safety
guidelines.
• Locate the UPS near a wall
socket. Do not use an extension
cord between the UPS and the
socket.
• Use CE-marked cables only for
connections between mains,
the UPS and equipment.
• The Liebert PSP has been
designed for small office/home
office use only; it is NOT
recommended for use in lifesupport applications.
• In the event of an emergency,
press the On/Off button and
disconnect the power cord
from the AC mains to properly
disable the UPS.
• Do not attach power strips or
surge suppressors to the UPS.
• Do not attempt to service any
parts inside the UPS except
when replacing the batteries.
Failure to adhere to this could
cause personal injury or
equipment malfunction and
void the warranty.
• This unit uses components that
are dangerous for the
environment, such as electronic
cards and other electronic
components. Any component
that is removed must be taken
to specialized collection and
disposal centers. If this unit
must be dismantled, this must
be done by specialized
personnel who are properly
trained and qualified. The unit
must be taken to a center
specialized in collection and
disposal of dangerous
substances.
For technical support: visit
www.vertivco.com
SETUP
1. Inspecting the package
Inspect the package and the
UPS upon receipt.
Notify the carrier and dealer of
visible damage.
The package includes:
• Liebert PSP
• USB cable
• Quick-start guide
• 2 IEC output cables
The Liebert MultiLink™
software may be downloaded
from the Liebert Web site at:
multilink.liebert.com
See Step 7 for installation
instructions.
2. Decide Where to Place the
UPS
The UPS must be placed
indoors, protected from water,
direct sunlight and excessive
heat.
Provide at least 100mm (4”) of
clearance on all sides of the
unit for proper ventilation.
3. Charging the UPS Battery
before use
The UPS battery is not charged
before shipping. It MUST be
charged before use.
• Use the input power cord
from computer equipment as
the input power cord of UPS
Connect a user-supplied
power cord from the UPS to a
wall socket and charge for at
least eight hours. Unit can be
charged in the on or off state.
590-1631-501A\SLI-23285_REV1_11-17 1
LIEBERT® PSPTM
Quick Installation Guide
NOTE: If battery is placed in
storage, charge the battery every
six months if kept at -15°C to +29°C
(5°F to 85°F)—or every three
months if kept at 30°C (86°F) or
higher.
4. Starting the UPS
After the battery is fully
charged:
• Turn on the UPS by pressing
the On/Off button (see
Figure 1 below). LED 1 should
be illuminated (green),
indicating the UPS is
operating in Normal Mode.
• Plug the loads into the
battery backup sockets on
the rear of the UPS.
CAUTION: Do not connect a
laser printer to the UPS.
7. Setting up Liebert
MultiLink software
To start using the Liebert
MultiLink software:
• Install the software.
6. Connecting the network
surge protection
5. Connecting the loads
The UPS has three battery
backup sockets that provide
power when the UPS operates
on battery.
There is also one surge-only
socket (see Figure 2 below).
The UPS has two network cable
jacks for network line (see
Figure 2 below).
• Connect a single-line
network cable into the
network surge protection IN
jack on the rear of the UPS.
• Connect a network cable
from the OUT jack on the
rear of the UPS to a port on a
PC or network device such
as a router.
UPS CONTROLS AND CONNECTIONS
See the Liebert MultiLink
quick-start guide or user
manual for installation
instructions.
• Connect one end of the USB
cable (supplied) to the USB
port on the rear of the UPS.
Connect the other end to a
USB port on the computer.
See the Liebert MultiLink
user manual for operating
instructions.
NOTE: Vertiv recommends
connecting the USB cable directly
to the computer WITHOUT using a
USB hub.
Figure 2 - Rear Panel
Figure 1 - Front Panel LEDs
Overload symbol
LED 1 (green)
LED 2 (red= fault;
amber = overload)
Mains symbol
RJ-45 jacks (2)
network protection
USB interface
Fault symbol
On/Off button
Mains breaker
AC mains inlet
Battery backup
sockets (3)
IEC 320 C13
Surge socket (1)
IEC 320 C13
UPS STATUS, ALARM CONDITIONS AND ALERTS
CONDITION
LED1
COLOR
Normal Mode
LED1
Green
Solid (steady glow)
(None)
Battery Mode
LED1
Green
Flashes every 3 seconds
Every 3 seconds
Battery Low
LED1
Green
Flashes every 1 second till end of discharge (EOD)
Every 1 seconds
Overload
LED1
Amber
Solid (steady glow) until load drops or breaker trips
Continuous
Battery Replacement
LED1
Red
Flashes every 1 second for 5 seconds only
Every 1 second for 5
seconds only
Fault
LED1
Red
Solid (steady glow) until UPS shuts down after 5
seconds
Continuous until UPS shuts
down
2 590-1631-501A\SLI-23285_REV1_11-17
SOLID/FLASHING
AUDIBLE ALARM
LIEBERT® PSPTM
Quick Installation Guide
REPLACING THE BATTERY
Servicing of batteries should be
performed or supervised by
personnel knowledgeable about
batteries and required precautions.
When replacing batteries, replace
with the same type and size battery.
CAUTION: Do not dispose of
batteries in a fire. The batteries may
explode.
CAUTION: Do not open or mutilate
batteries. Released electrolyte is
harmful to the skin and eyes. It is
toxic.
screws from the right-side cover,
then pull up the right-side cover
and remove it.
2. Removing the old battery
CAUTION: Risk of electric
shock.
Remove the black wire from the
negative (-) terminal and the red
wire from the positive (+)
terminal.
Gently remove the battery from
the UPS.
This product is designed for IT
power systems with 230V.
3. Connecting the
replacement battery
Verify that the replacement
battery matches the dimensions
and battery specifications.
Connect the PSP battery leads to
the new battery. Be sure to
reconnect the red wire to the
positive (+) terminal and the black
wire to the negative (-)terminal.
NOTE: Small sparks may occur
at the battery connectors during
reconnection. Take care not to
short-circuit the positive and
negative battery terminals while
replacing the battery.
Place the battery in the UPS.
4. Reassembling the PSP
outer case
1. Opening the PSP outer
case
Ensure correct alignment of
front panel, then reattach the
right-side cover.
Evenly tighten the four screws
from Step 1. (DO NOT
overtighten the screws.)
Dispose of the old battery
properly at an appropriate
recycling facility.
Turn off all connected loads, then
turn off the UPS and unplug the
input power cord. (Batteries are
NOT hot-swappable.)
Carefully lay the UPS on its left
side, as shown in the illustration
to the right.
Use a #1 Phillips head
screwdriver to remove the four
TROUBLESHOOTING
If the UPS detects a fault, consult the table below for possible causes and solutions. For further assistance, please
contact your local Vertiv representative.
FAULT
Mains is normal, but LED 1 is not
illuminated.
POSSIBLE CAUSES
The UPS may not be turned on.
The power cord may not be connected
properly.
The upstream mains circuit breaker may be
tripped.
SOLUTIONS
• Press the On/Off button to turn on
the UPS.
• Connect the power cord securely into
a wall socket.
• Reset the circuit breaker.
LED 1 flashes (green) every 3 seconds, Battery voltage may be too low.
but there is no output power.
• Recharge the UPS for 8 hours.
Alarm buzzer beeps continuously
although mains is normal.
The UPS may be overloaded (check LED 2).
• Disconnect some equipment from
the UPS.
UPS does not provide expected
backup time.
The UPS battery reached end of life.
• Replace the internal battery.
The UPS is on and connected to
mains, but fails to operate properly.
Mains power may be outside the unit’s
operating range.
• If mains is normal, try reconnecting
mains and restarting the UPS.
590-1631-501A\SLI-23285_REV1_11-17 3
LIEBERT® PSPTM
Quick Installation Guide
SPECIFICATIONS
MODEL NUMBER
Capacity (VA/W)
PSP500MT3-230U
PSP650MT3-230U
500/300
650/390
Net Weight, kg (lb.)
3.9 (8.6)
Shipping Weight, kg (lb.)
4.8 (10.6)
Dimensions - W x D x H, mm (in.)
87 x 215 x 251 (3.4 x 8.5 x 9.9)
Mains Voltage
160-287VAC
Frequency
50/60Hz ±5Hz
Output Voltage (Mains Normal)
Typical 160-287VAC
Output Voltage (Battery Operation)
230VAC ±5%
On-Battery Wave Form
Stepped sine-wave
VRLA Battery Type - VDC x Ah x Quantity
12V x 7.2Ah x 1
12V x 7.2Ah x 1
Typical Recharge Time
6-8 hours to 90%
Battery Run Time
See Load Autonomy table below
Audible and Visual
Audible alarm / LED
Backup Sockets
IEC 320 C13 (3)
Surge Sockets
IEC 320 C13 (1)
Operating Temperature, °C (°F)
0 to 40 (32 to 104)
Storage Temperature, °C (°F)
-15 to 40 (5 to 104)
Storage Temperature, °C (°F)
-15 to 40 (5 to 104)
Operating / Storage Relative Humidity
0%-90%, non-condensing
EMI Classification
Class B
LOAD AUTONOMY
AGENCY
Liebert PSP 230V 500VA-650VA
Safety
EMC
IEC/EN/AS 62040-1-1
LOAD (WATTS)
500VA
650VA
EN 62040-2:2005 Class B
50
55
56
IEC 61000-4-2 Electrostatic discharge
100
18
19
150
12
12
200
8
8
250
5
5
300
N/A
4
350
N/A
3
IEC 61000-4-3 Radiated E-RFI fields
IEC 61000-4-4 Fast E transients
IEC 61000-4-5 Surges/Lightning
IEC 61000-4-6 Conducted RFI
Transportation
ISTA Procedure 1A Certification
NOTE: The Liebert PSP is compliant with the Restriction
of Hazardous Substances Directive (ROHS), prohibiting
use of six hazardous materials manufacturing
of electronics, including lead-free solder.
NOTE: : All run times are in minutes, assume fully
charged batteries and are typical at 25°C (77°F) with
resistive loads.
To contact Vertiv Technical Support: visit www.VertivCo.com