Intrusion Alarm Systems | D8129 Octo‑relay Module
D8129 Octo‑relay Module
www.boschsecurity.com
The D8129 Octo-relay Module is suitable for
applications requiring Form C relays to operate
auxiliary systems or to display fire system status at
remote annunciators. Building components such as
HVAC, door lock releases, and stairwell pressurization
can interface with the D8129 for complete system
control and monitoring.
Industrial, commercial, and institutional facilities are
typical installations for the D8129 module. The eight
on-board relays can be programmed to activate on
system alarm, system trouble, individual zone or point
faults, and through remote control by authorized
users.
System overview
The D8129 Octo-relay Module provides eight
programmable Form C relays. Each relay provides dry
contact switching rated for 1.0 A at 30 VDC. The relays
are accessed through on-board screw terminal
connections.
The D8129 uses information from the control panel
serial data output to activate the relays. On-board
switches are used to configure the D8129 for different
operating modes, or to specify relay output numbers.
These switches, along with control panel programming
options, determine the D8129’s response to the serial
u
Programmable relay functions
u
Provides eight Form C relays
u
1 A at 30 VDC relay contact rating
u
Slide switch configuration
u
Allows remote control of relays
data. Programming within the control panel can
activate specific relays or sets of relays in response to
system conditions.
For the G Series control panels, slide switches are
configured for specific relay output numbers, which
are activated according to their programming. The
D8129 uses five slide switches with multiple setting
options to configure its mode of operation. The D8129
receives serial data from the control panel and
activates relays in response to control panel
conditions and slide switch settings. Relays can be
programmed for remote control from a panel keypad.
Functions
Output Relays
Each relay output provides a normally-open and a
normally-closed output.
Modes of Operation
A slide switch with multiple switch settings can be
used to configure the module for a specific mode of
operation for D8112 Series systems, or programming
can be used to determine relay operation for G Series
systems.
Certifications and approvals
Australia
C-Tick
2 | D8129 Octo‑relay Module
Region
Certification
Parts included
USA
UL
Quantity
Component
1
Octo-relay module
1
Hardware pack
1
Literature pack
AMCX: Central Station Alarm Units
(UL1610, UL1635), AMCX7: Central
Station Alarm Units Certified for Canada
(cULus), AOTX: Local Alarm Units
(UL464, UL609), AOTX7: Local Alarm
Units Certified for Canada (cULus),
APAW: Police Station Alarm Units
(UL365, UL464), APAW7: Police Station Alarm Units Certified for Canada
(cULus), APOU7: Proprietary Alarm
Units Certified for Canada (cULus),
NBSX: Household Burglar Alarm System
Units (UL1023), NBSX7: Household
Burglar Alarm System Units Certified for
Canada (cULus), UOJZ: Control Units,
System (UL864, 9th edition),UTOU:
Control Units and Accessories - Household System Type (UL985), UTOU7:
Control Units and Accessories - Household System Type Certified for Canada
(cULus)
Technical specifications
Properties
Board Dimensions:
12 cm x 7.6 cm x 1.9 cm
(5.0 in. x 3.0 in. x 0.75 in.)
Power Requirements
Current:
130 mA maximum
Voltage:
12 VDC nominal
NYCMEA
12-92-E, Vol. 12 12-92-E, Vol. 12
NYCMEA
12-92-E, Vol. 15 12-92-E, Vol. 15
Contact Rating:
1.0 A at 30 VDC for resistive load
FDNYCoA
6059
Timing:
During pulsed output, relay maintains closure for
1 sec
CSFM
7167-1615:0100 CONTROL UNIT
(HOUSEHOLD)
Type:
Form C dry contact
CSFM
7167-1615:0243
Ordering information
CSFM
7165-1615:0242
D8129 Octo‑relay Module
CSFM
7165-1615:0238
CSFM
7165-1615:0119
CSFM
7167-1615:0239
Relays
Provides 8 programmable relays.
Order number D8129
D137 Mounting Bracket
Used to mount accessory modules in D8103, D8108A,
and D8109 enclosures.
Installation/configuration notes
Order number D137
Compatibility Information
D138 Mounting Bracket, Right Angle
Control Panels
Used to mount accessory modules in D8103, D8108A,
and D8109 enclosures.
All G Series control panels
Order number D138
Notice
The D7212GV3, D7212GV2, and D7212G are not
listed for commercial fire applications.
Mounting Considerations
Up to four D8129 Octo-relay Modules can be mounted
in a control panel enclosure. For additional modules,
use the D137 Mounting Bracket.
Wiring Considerations
The D8129 connects to a control panel using the
12 VDC Auxiliary output, Serial Data Output, and
common terminals. Use 1.5 mm to 0.6 mm (16 AWG to
22 AWG) wires from the module to the control panel.
3 | D8129 Octo‑relay Module
Represented by:
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2013 | Data subject to change without notice
2538106379 | en, V2, 02. Jan 2013
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
China:
America Latina:
Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division
201 Building, No. 333 Fuquan Road
Via Anhanguera, Km 98
North IBP
CEP 13065-900
Changning District, Shanghai
Campinas, Sao Paulo, Brazil
200335 China
Phone: +55 19 2103 2860
Phone +86 21 22181111
Fax: +55 19 2103 2862
Fax: +86 21 22182398
al.securitysystems@bosch.com
www.boschsecurity.com.cn
www.boschsecurity.com