HPE G2 Metered Power Distribution Units
QuickSpecs
HPE G2 Metered Power Distribution Units
Overview
Setting new standards for reliable power distribution and metering
HPE Advanced Series G2 Metered PDUs are designed to work precisely with HPE Infrastructure and Compute solutions, providing
a highly accurate (billing grade accuracy) power distribution and metering solution for your racks. Designed for use with HPE
Standard, Advanced, and Enterprise racks (and compatible with other industry-standard server racks), HPE G2 Metered PDUs
guarantee a compatible fit and reliable operation backed by a 3 year warranty. HPE G2 Metered PDUs are also rated for operating
temperatures up to 60°C, adding an increased level of operational reliability for power distribution in IT racks.
A major concern for IT administrators and facility managers is their ability to quickly diagnose and service power related problems
in their IT racks. The HPE G2 PDU portfolio addresses this problem by, first, offering a wide range of models and mounting options
that promote flexible power configuration in IT racks. Vertical, Horizontal, and True 0U mounting, give you the flexibility to
efficiently utilize rack space while placing access to power where you need it most in the rack. Serviceability is further enhanced
with features such as color-coded outlets and low-profile form factors, allowing for simple and quick access to IT equipment and
power cables in the rear of the rack.
HPE G2 Metered PDU features are also directly focused on other pain points in the data center. 1Gb Ethernet alleviates the need
to maintain older switch solutions that have been traditionally required for PDU network connectivity. High-density outlet
configurations that provide up to 48 power outlets in a full-height vertical form factor allow for simple access to power in the rack
while minimizing physical cable requirements. Support for up to eight sensors per PDU provides a cost-effective and exhaustive
solution for monitoring the environmental elements (temperature, humidity, and leakage) in both the front and rear of the rack.
HPE IEC Locking Power Cords are a new supported option available for most HPE G2 PDUs. The IEC Locking Power Cords provide
secure cable retention to both the PDU and target device, protecting against vibration during shipping and ensuring that cables
are not dislodged during a service event. HPE’s IEC Locking Power Cords provide a safe and secure solution against the common
issues that lead to power-related downtime.
Why HPE Metered PDUs?
•
•
•
HPE Foundation Care services purchased for server and storage products, such as extended warranties and premium
support services, extend to our PDU products free of charge when purchased together.
HPE guarantees 100% compatibility between its Rack and Power Infrastructure products and its industry-standard
compute, storage, and networking solutions, backed with a 3-year warranty for all G2 Metered PDU models.
HPE offers multiple Metered PDU form factors that promote efficient use of space in the rack and provide flexibility in how
each PDU can be mounted and configured with cables.
Page 1
QuickSpecs
HPE G2 Metered Power Distribution Units
Models
100-120V Input, Single Phase, North America/Japan
HPE G2 Metered 1.9 kVA/IEC C20 Detachable 16A/120V Outlets (8) 5-20R/1U Horizontal NA/JP PDU
HPE G2 Metered 1.9kVA/IEC C20 Detachable 16A/120V Outlets (16) 5-20R/Vertical NA/JP PDU
HPE G2 Metered 2.8kVA/L5-30P 24A/120V Outlets (24) 5-20R/Vertical NA/JP PDU
HPE G2 Metered 2.8kVA/L5-30P 24A/120V Outlets (16) 5-20R/2U Horizontal NA/JP PDU
NOTE: Models P9R45A and P9R46A include a C19 to NEMA 5-15 detachable input power cord.
100-240V Input, Single Phase, Worldwide
HPE G2 Metered 3.6kVA/IEC C20 Detachable 16A/100-240V Outlets (12) C13/1U Horizontal WW PDU
NOTE: Worldwide models do not include an input power cord. Please go to the Related Options section and select the
appropriate input power cord for your geographic location.
200-208V Input, Single Phase, North America/Japan
HPE G2 Metered Modular 4.9kVA/L6-30P 24A/208V Outlets (6) IEC C19/1U Horizontal NA/JP PDU
HPE G2 Metered 4.9kVA/L6-30P 24A/208V Outlets (12) C13, (4) C19/2U Horizontal NA/JP PDU
HPE G2 Metered 4.9kVA/L6-30P 24A/208V Outlets (32) C13, (6) C19/Vertical NA/JP PDU
HPE G2 Metered 8.3kVA/CS8265C 40A/208V Outlets (30) C13, (6) C19/Vertical NA/JP PDU
HPE G2 Metered Modular 8.3kVA/CS8265C 40A/208V Outlets (6) C19/1U Horizontal NA/JP PDU
200-208V Input, Three Phase, North America/Japan
HPE G2 Metered 3Ph 8.6kVA/L15-30P 24A/208V Outlets (18) C13, (6) C19/Vertical NA/JP PDU
HPE G2 Metered 3Ph 8.6kVA/L21-30P 24A/208V Outlets (30) C13, (6) C19, (2) 5-20R/Vertical NA/JP PDU
HPE G2 Metered Modular 3Ph 8.6kVA/L15-30P 24A/208V Outlets (6) C19/1U Horizontal NA/JP PDU
HPE G2 Metered 3Ph 10kVA/CS8365C 35A/208V Outlets (30) C13, (6) C19/Vertical NA/JP PDU
HPE G2 Metered Modular 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (6) C19/1U Horizontal NA/JP PDU
HPE G2 Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (18) C13, (6) C19/Vertical NA/JP PDU
HPE G2 Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (36) C13, (12) C19/Vertical NA/JP PDU
HPE G2 Metered 3Ph 17.3kVA/60309 60A 4-wire 48A/208V Outlets (12) C13 (12) C19/Vertical NA/JP PDU
NOTE: Models P9R82A and P9R83A are high density models that have circuit breakers on the back side of the unit.
220-240V Input, Single Phase, International
HPE G2 Metered Modular 7.3kVA/60309 3-Wire 32A/230V Outlets (6) C19/1U Horizontal INTL PDU
HPE G2 Metered 7.3kVA/60309 3-Wire 32A/230V Outlets (12) C13, (4) C19/2U Horizontal INTL PDU
HPE G2 Metered 7.3kVA/60309 3-Wire 32A/230V Outlets (32) C13, (6) C19/Vertical INTL PDU
220-240V Input, Three Phase, International
HPE G2 Metered 3Ph 11kVA/60309 5-Wire 16A/230V Outlets (36) C13, (6) C19/Vertical INTL PDU
HPE G2 Metered Modular 3Ph 11kVA/60309 5-Wire 16A/230V Outlets (6) C19/1U Horizontal INTL PDU
HPE G2 Metered Modular 3Ph 22kVA/60309 5-Wire 32A/230V Outlets (6) C19/1U Horizontal INTL PDU
HPE G2 Metered 3Ph 22kVA/60309 5-Wire 32A/230V Outlets (18) C13, (6) C19/Vertical INTL PDU
HPE G2 Metered 3Ph 22kVA/60309 5-Wire 32A/230V Outlets (36) C13, (12) C19/Vertical INTL PDU
HPE G2 Metered 3Ph 22kVA/60309 5-Wire 32A/230V Outlets (12) C13 (12) C19/Vertical INTL PDU
NOTE: Models P9R84A and P9R85A are high density models that have circuit breakers on the back side of the unit.
P9R45A
P9R46A
P9R48A
P9R49A
P9R50A
P9R51A
P9R52A
P9R53A
P9R57A
P9R77A
P9R58A
P9R59A
P9R78A
P9R60A
P9R80A
P9R82A
P9R83A
P9R86A
P9R54A
P9R55A
P9R56A
P9R61A
P9R79A
P9R81A
P9R84A
P9R85A
P9R87A
Page 2
QuickSpecs
HPE G2 Metered Power Distribution Units
Models
Horizontal Form Factors
1U Horizontal WW Model (P9R50A)
1U Horizontal 120V Model (P9R45A)
Page 3
QuickSpecs
HPE G2 Metered Power Distribution Units
Models
1U Three-Phase Horizontal Model (P9R80A)
Vertical Form Factors
Vertical 120V Model (P9R46A)
Vertical Single Phase Model with 100-240V Output (P9R59A)
Page 4
QuickSpecs
HPE G2 Metered Power Distribution Units
Key Features
Power Metering •
and Management
•
•
All G2 HPE Metered PDUs meet IEC 62053-21, Class 1 standards for ±1% or better accuracy in power
metering of:
o Amperage
o Voltage
o Wattage
o Kilowatts per hour
An OLED display provides local monitoring and alert indications
Remote PDU management and power monitoring supported through integrated web-based user interface,
CLI, and third-party software applications supporting SNMP
Compatibility
•
•
Designed specifically for use with HPE rack enclosures, but compatible with most 3rd party IT racks
Integrated web-based user interface compatible with IPv4/IPv6 and SNMPv1/SNMPv3
Usability
•
•
•
•
•
Wide range of mounting options including vertical, 1U/2U horizontal, and True 0U (between the RETMA
rails) configurations
Low-profile PDU form factors ensure integrity of rear-rack keep-out zone for IT maintenance
Color-coded receptacles to easily distinguish between the different load segments/phases
Integrated cord retention on all IEC C19 and C13 receptacles (does not require any additional brackets)
Local and remote firmware updates
•
•
•
•
Local and LDAP security with multiple access levels
Support for HTTP, HTTPS, SSH protocols
Configurable alarm thresholds for both power and environmental monitoring
Optional dual-locking power cords securing both power connections
Security
HPE G2 Metered PDUs support multiple features that are unique to HPE and help to provide the best user experience. Information
on these features is summarized below with additional information found online in HPE G2 Metered PDU User’s Guide.
Rated for High
Operating
Temperatures
Increasing IT densities and escalating operating costs have created a need for rack infrastructure that can
operate reliably at higher operating temperatures. HPE G2 PDUs have been designed with high temperaturerated premium components and construction that support increased reliability levels at elevated temperatures.
HPE G2 PDUs are rated for operation in temperatures up to 60°C (or 140°F) in the rear of the rack.
IEC Locking
Power Cords
HPE G2 PDU models support optional IEC Locking Power Cords with an integrated locking technology on both
ends of the cable. HPE Locking Power Cord are available for both C13/14 and C19/20 power receptacles in
multiple cable length options, and can be purchased in single or six-pack kits. One IEC Locking Power Cord has
been included with each PDU model that supports either a C13 and/or C19 outlet.
High-Density
Vertical
PDU Models
High-density Vertical PDU models provide 24 outlets in a half-height (22U) form factor and 48 outlets in a fullheight (42U) form factor. This density is achieved by placing the power receptacles on one side of the PDU and
access to the circuit breakers on the opposite side without significantly impacting the height (profile) of the
PDU. See the Model Matrix section for more information on high-density Vertical PDU models.
Color-Coded
Outlets
All HPE G2 PDU models now include color-coded outlets which are highly visible from the rear of the rack. The
color-coding helps to easily and clearly identify outlets to simplify cabling and power phase balancing when
configuring your IT equipment.
1Gb Ethernet
Support
HPE is the first IT solutions company to standardize on 1Gb Ethernet for PDU network connectivity. This
eliminates the need to maintain older switching solutions needed for the 10/100 connectivity provided by most
other PDU manufacturers.
Page 5
QuickSpecs
HPE G2 Metered Power Distribution Units
Key Features
Environmental
Sensors
HPE G2 Metered PDU models include two environmental sensor ports (can be upgraded to six ports with the
addition of up to two G2 PDU Sensor Port Hubs) that can monitor and record up to eight sensor measurements.
Multiple senor options are available providing the ability to monitor temperature, humidity, water leakage, and
intrusion for each rack. Please review the Related Options section for a list of the options available.
Flexible
Mounting
Most vertical HPE G2 PDU models support mounting on the back and both sides of the PDU using a button and
keyhole mounting system for easy drop-in installation. This provides a flexible mounting capability that allows
power cables to be configured toward the front, middle, or rear of the rack, allowing users to customize their
cable management strategy specifically for each rack.
True 0U
Mounting
HPE Horizontal PDUs have a unique design specifically for data center customers who want to maximize space
efficiencies in the rack. All HPE 1U Horizontal PDUs can be installed in any U position in your rack or can be
installed in the 0U space between the RETMA rails on HPE Advanced and Enterprise Series racks (see figure
below).
HPE PDU
Extension Bar
Options
HPE PDU extension bar options help expand the availability of power in the rear of the rack. Each extension bar
includes a locking input power cord that connects to the PDU and supports HPE’s new IEC Locking Power Cords
for C13/C14 and C19/C20 outlets. HPE PDU extension bars can be added to Horizontal and Vertical PDU
models, with available C19 outlets, to add additional power outlets and expand access to power in the back of
the rack when needed. Extension Bars mount directly to the frame of the rack in multiple locations allowing you
the flexibility of placing access to power where it is needed most (see figure above). Multiple extension bar
options are available to help you customize the outlet configurations you require extension bars are also
compatible with previous generation PDU models that offer C20 outlets (locking feature only supported on new
G2 PDU models). See the Related Options section for more information on G2 Extension Bar models.
3-Year Warranty HPE G2 Metered PDU models are supported with a 3-year warranty. Additionally, the HPE Foundation Care
Extension program provides additional support and services for your PDU models when purchased with HPE
servers, storage, and networking solutions at no additional charge.
Additional information regarding worldwide limited warranty and technical support is available at:
http://h17007.www1.hpe.com/us/en/enterprise/servers/warranty/index.aspx#.V-10xE3rvbq
Page 6
QuickSpecs
HPE G2 Metered Power Distribution Units
Related Options
Related Options
Extension Bars
HPE G2 IEC C20 Input/(8) C13 Expansion Outlets/PDU Extension Bar Kit
HPE G2 IEC C20 Input/(4) C13 (2) C19 Expansion Outlets/PDU Extension Bar Kit
HPE G2 IEC C20 Input/(7) 5-20R Expansion Outlets/PDU Extension Bar Kit
NOTE: All kits include 2 extension bars with a locking C19 input power cord (1.8m).
P9Q66A
P9Q67A
P9Q68A
IEC Locking
Power Cords
HPE C13 - C14 WW 250V 10Amp 0.7m Black Locking Power Cord
HPE C13 - C14 WW 250V 10Amp 0.7m Black 6-pack Locking Power Cord
HPE C13 - C14 WW 250V 10Amp 1.4m Black Locking Power Cord
HPE C13 - C14 WW 250V 10Amp 1.4m Black 6-pack Locking Power Cord
HPE C13 - C14 WW 250V 10Amp 2m Black Locking Power Cord
HPE C13 - C14 WW 250V 10Amp 2m Black 6-pack Locking Power Cord
HPE C13 - C14 WW 250V 10Amp 3m Black Locking Power Cord
HPE C13 - C14 WW 250V 10Amp 3m Black 6-pack Locking Power Cord
HPE C19 - C20 WW 250V 16Amp 0.7m Black Locking Power Cord
HPE C19 - C20 WW 250V 16Amp 0.7m 6-pack Black Locking Power Cord
HPE C19 - C20 WW 250V 16Amp 1.2m Black Locking Power Cord
HPE C19 - C20 WW 250V 16Amp 1.2m 6-pack Black Locking Power Cord
HPE C19 - C20 WW 250V 16Amp 2m Black Locking Power Cord
HPE C19 - C20 WW 250V 16Amp 2m 6-pack Black Locking Power Cord
HPE C19 - C20 WW 250V 16Amp 2.5m Black Locking Power Cord
HPE C19 - C20 WW 250V 16Amp 2.5m 6-pack Black Locking Power Cord
NOTE: HPE Locking Power Cords are only supported on either C13/14 or C19/20 power
receptacles using HPE G2 PDUs.
Q0P67A
Q0Q02A
Q0P68A
Q0Q03A
Q0P69A
Q0Q04A
Q0P70A
Q0Q05A
Q0R19A
Q0R15A
Q0P71A
Q0R16A
Q0P72A
Q0R17A
Q0P73A
Q0R18A
IEC Standard Power HP C13 - C14 WW 250V 10A Gray 0.7m Jumper Cord
Cords
HP C13 - C14 WW 250V 10Amp 0.7m Jumper Cord
HP C13 - C14 WW 250V 10Amp 1.4m Jumper Cord
HP C13 - C14 WW 250V 10A Gray 1.37m Jumper Cord
HP C13 - C14 WW 250V 10Amp 1.4m 15 pc Jumper Cord
HP C13 - C14 WW 250V 10Amp 2.0m Jumper Cord
HP C13 - C14 WW 250V 10Amp Flint Gray 2.0m Jumper Cord
HP C13 - C14 WW 250V 10Amp 2.5m Jumper Cord
HP C13 - C14 WW 250V 10Amp 3.0m Jumper Cord
HP C13 - C14 WW 250V 10A Gray 3.0m Jumper Cord
HP C20 - C13 WW 250V 15Amp 2.0m Jumper Cord
HP C19 - C20 WW 250V 16Amp Flint Gray 1.20m Jumper Cord
HP C19 - C20 WW 250V 16Amp Flint Gray 2.0m Jumper Cord
HP C19 - C20 WW 250V 16Amp 2.5m Jumper Cord
HP 200-250V 10A C15 to C14 .76m Jumper Cable
Country-Specific
Power Cords
HP C13 - NEMA 5-15P US/CA 110V 10Amp 1.83m Power Cord
HP C19 - NEMA L6-20P NA/JP 250V 20Amp High Voltage 3.6m Power Cord
HP C19 - NBR-14136 BR 250V 16Amp 2.5m Power Cord
HP C19 - GB-1002 CN 250V 16Amp 2.5m Power Cord
HP C19 - IS-1293 IN/PK/BD 250V 16Amp 2.5m Power Cord
HP C19 - ISI-32 IL 250V 16Amp 2.5m Power Cord
HP C19 - AS3112-3 AU/NZ 250V 15Amp 3.6m Power Cord
A0K03A
142257-B28
142257-006
A0K04A
142257-007
A0K02A
AF573A
142257-002
142257-003
A0K06A
AF590A
AF575A
AF574A
295633-B22
E7807A
AF556A
AF593A
AF592A
AF584A
AF582A
AF583A
AF577A
Page 7
QuickSpecs
HPE G2 Metered Power Distribution Units
Related Options
HP C19 - IEC-309 DK/SE/AR 250V 16Amp 3.6m Power Cord
HP C19 - CEE-VII EU 250V 16Amp 3.6m Power Cord
HP C19 - CEI-23-50 IT/CL 250V 16Amp 3.6m Power Cord
HP C19 - SABS-164 ZA 250V 16Amp 3.6m Power Cord
HP C19 - BS-1363/A UK/HK/SG 250V 13Amp 3.6m Power Cord
HP 240 VAC 4.5M Unterminated End NA Power Cord
AF581A
AF576A
AF580A
AF579A
359615-031
E7806A
HPE Mounting
Brackets
HPE Vertical PDU 10K G2 Mounting Kit
H6L32A
NOTE: This kit allows for vertical HPE G2 PDU models to be mounted in HPE 10000 G2 series racks and
in the HPE Standard Series rack.
Environmental
Sensors
HPE G2 Metered PDUs include 2 physical sensor ports and can monitor and record up to eight sensor
measurements. Data collected by each sensor can be viewed and managed through the integrated graphical
user interface (GUI), or by third-party applications that communicate through SNMP or through a Redfish
supported API. Consult the HPE G2 Metered PDU User Guide for more information on use with third-party
software applications.
HPE G2 PDU Environmental Temperature Sensor
P9T00A
NOTE: Requires one input port and monitor/records one sensor measurement.
HPE G2 PDU Environmental Temperature and Humidity Sensor
P9T01A
NOTE: Requires one input port and monitors/records two sensor measurements.
HPE G2 PDU Environmental 3-Temperature and 1-Humidty Sensor
P9T02A
NOTE: Requires one input port and monitors/records four sensor measurements.
HPE G2 PDU Open/Close Door Sensor
P9T03A
NOTE: Requires two input ports and monitors/records two sensor measurements.
HPE G2 PDU Leak Detection Sensor
P9T04A
NOTE: Requires one input port and monitors/records one sensor measurement. Kit
covers up to six linear meters and can be expanded to cover up to thirty linear meters
with the addition of up to four HPE G2 PDU Leak Detection Sensor Extension Kits
(P9T08A).
HPE G2 PDU Sensor Port Hub
P9T07A
NOTE: This is an adapter that expands a single physical sensor port into three physical
sensor ports.
HPE G2 PDU Leak Detection Sensor Extension Kit
P9T08A
NOTE: Leak Detection Sensor (P9T04A) must be purchased separately to use in
conjunction with this kit. Up to four Extension Kits can be added to a single Leak
Detection Sensor to cover up to a maximum of thirty linear meters.
Page 8
QuickSpecs
HPE G2 Metered Power Distribution Units
Model Matrix – Input Power
Mounting options for Horizontal 1U and 2U PDU models
WxHxD
Unit Weight
Model
(inches)
(lbs.)
P9R45A
8.4
17.461 x 1.713 x 10.62
P9R49A
14.2
17.461 x 3.425 x 10.62
P9R50A
8.6
17.461 x 1.713 x 10.62
P9R51A
15.5
17.461 x 1.713 x 10.62
P9R52A
14.5
17.461 x 3.425 x 10.62
P9R54A
12.3
17.461 x 1.713 x 10.62
P9R55A
13.8
17.461 x 3.425 x 10.62
P9R77A
16.5
17.461 x 1.713 x 10.62
P9R78A
16.0
17.461 x 1.713 x 10.62
P9R79A
12.0
17.461 x 1.713 x 10.62
P9R80A
22.9
17.461 x 1.713 x 10.62
P9R81A
15.5
17.461 x 1.713 x 10.62
U Height
1U
2U
1U
1U
2U
1U
2U
1U
1U
1U
1U
1U
Horizontal
Mounting












True 0U Mounting









Mounting options for Vertical PDU models in HPE Advanced and Enterprise racks (1075mm depth)
Maximum PDUs per Side of Rack
WxHxD
Unit Weight
Model
Vertical Height
(inches)
(lbs.)
22U
36U
42U
48U
P9R46A
2.047 x 32.165 x 2.087
8.3
Half-Height
2
2
4
4
P9R48A
2.047 x 58.661 x 2.087
14.1
Mid-Height
2
2
2
P9R53A
2.047 x 68.898 x 2.087
16.0
Full-Height
2
2
P9R56A
2.047 x 68.898 x 2.087
14.4
Full-Height
2
2
P9R57A
2.047 x 68.898 x 2.953
17.6
Full-Height
2
2
P9R58A
2.047 x 58.661 x 2.953
14.5
Mid-Height
2
2
2
P9R59A
2.047 x 68.898 x 2.953
17.2
Full-Height
2
2
P9R60A
2.047 x 68.898 x 2.953
18.0
Full-Height
2
2
P9R61A
2.047 x 68.898 x 2.087
12.5
Full-Height
2
2
P9R82A*
2.047 x 36.024 x 4.409
23.8
Half-Height
1
1
2
2
P9R83A*
2.047 x 71.654 x 4.409
31.0
Full-Height
1
1
P9R84A*
2.047 x 36.024 x 4.409
14.2
Half-Height
1
1
2
2
P9R85A*
2.047 x 71.654 x 4.409
23.6
Full-Height
1
1
P9R86A
2.047 x 68.898 x 2.953
24.8
Full-Height
2
2
P9R87A
2.047 x 68.898 x 2.953
16.2
Full-Height
2
2
*HPE high density model mounts on its side with outlets facing the back of the rack
NOTE: HPE G2 Advanced and Enterprise 1200mm deep racks include an extra set (2) of PDU trays in the rear of the rack
enabling support of up to 2x the number of PDUs listed above for 1075mm deep racks.
Page 9
QuickSpecs
HPE G2 Metered Power Distribution Units
Model Matrix – Input Power
Model
Region
P9R45A
P9R46A
P9R48A
P9R49A
P9R50A
P9R51A
P9R52A
P9R53A
P9R54A
P9R55A
P9R56A
P9R57A
P9R58A
P9R59A
P9R60A
P9R61A
P9R77A
P9R78A
P9R79A
P9R80A
P9R81A
P9R82A
P9R83A
P9R84A
P9R85A
P9R86A
P9R87A
NA/JP
NA/JP
NA/JP
NA/JP
WW
NA/JP
NA/JP
NA/JP
INTL
INTL
INTL
NA/JP
NA/JP
NA/JP
NA/JP
INTL
NA/JP
NA/JP
INTL
NA/JP
INTL
NA/JP
NA/JP
INTL
INTL
NA/JP
INTL
Phase & Input
Voltage
1-ph, 120V
1-ph, 120V
1-ph, 120V
1-ph, 120V
1-ph, 100-240V
1-ph, 208V
1-ph, 208V
1-ph, 208V
1-ph, 230V
1-ph, 230V
1-ph, 230V
1-ph, 208V
3-ph, 208V
3-ph, 208V
3-ph, 208V
3-ph, 400V
1-ph, 208V
3-ph, 208V
3-ph, 400V
3-ph, 208V
3-ph, 400V
3-ph, 208V
3-ph, 208V
3-ph, 400V
3-ph, 400V
3-ph, 208V
3-ph, 400V
Input
Circuit
16A
16A
24A
24A
16A
24A
24A
24A
32A
32A
32A
40A
24A
24A
35A
16A
40A
24A
16A
48A
32A
48A
48A
32A
32A
48A
32A
Circuit
Breakers
none
none
(2) 1-pole, 20A
(2) 1-pole, 20A
none
(2) 2-pole 20A
(2) 2-pole 20A
(2) 2-pole 20A
(2) 1-pole, 16A
(2) 1-pole, 16A
(2) 1-pole, 16A
(3) 2-pole 20A
(3) 2-pole 20A
(3) 2-pole 20A
(3) 2-pole 20A
none
(3) 2-pole 20A
(3) 2-pole 20A
none
(6) 2-pole 20A
(6) 1-pole, 16A
(6) 2-pole 20A
(6) 2-pole 20A
(6) 1-pole, 16A
(6) 1-pole, 16A
(6) 2-pole 20A
(6) 1-pole, 16A
Input Plug
Type
C20 Inlet
C20 Inlet
L5-30P
L5-30P
C20 Inlet
L6-30P
L6-30P
L6-30P
IEC 32A, 1ph
IEC 32A, 1ph
IEC 32A, 1ph
CS8265C
L15-30P
L21-30P
CS8365C
IEC 16A, 3ph
CS8265C
L15-30P
IEC 16A, 3ph
IEC 60A, 3ph
IEC 32A, 3ph
IEC 60A, 3ph
IEC 60A, 3ph
IEC 32A, 3ph
IEC 32A, 3ph
IEC 60A, 3ph
IEC 32A, 3ph
Input Cord
Length
12' (detachable)
12' (detachable)
10'
12'
Cord Not Included
12'
12'
10'
12'
12'
10'
10'
10'
10'
10'
10'
12'
12'
12'
12'
12'
10'
10'
10'
10'
10'
10'
NOTE: All Input Circuit Ratings for NA/JP models have been de-rated according to NEC requirements.
Nominal Input Voltage Ratings used for calculating output power are as follows:
• 100 – 120V: 120V
• 200 – 208V: 208V
• 100 – 240V: 230V
• 220 – 240V: 230V
• 200 – 240V/346 – 415V: 230V
Page 10
QuickSpecs
HPE G2 Metered Power Distribution Units
Model Matrix – Output Power
Model
Region
Nominal
Power (kVA)
P9R45A
P9R46A
P9R48A
P9R49A
P9R50A
P9R51A
P9R52A
P9R53A
P9R54A
P9R55A
P9R56A
P9R57A
P9R58A
P9R59A
P9R60A
P9R61A
P9R77A
P9R78A
P9R79A
P9R80A
P9R81A
P9R82A
P9R83A
P9R84A
P9R85A
P9R86A
P9R87A
NA/JP
NA/JP
NA/JP
NA/JP
WW
NA/JP
NA/JP
NA/JP
INTL
INTL
INTL
NA/JP
NA/JP
NA/JP
NA/JP
INTL
NA/JP
NA/JP
INTL
NA/JP
INTL
NA/JP
NA/JP
INTL
INTL
NA/JP
INTL
1.9
1.9
2.8
2.8
3.6
4.9
4.9
4.9
7.3
7.3
7.3
8.3
8.6
8.6
10
11
8.3
8.6
11
17.3
22
17.3
17.3
22
22
17.3
22
Output
Voltage
Range
100-125V
100-125V
100-125V
100-125V
100-240V
200-240V
200-240V
200-240V
220-240V
220-240V
220-240V
200-240V
200-240V
100-240V
200-240V
220-240V
200-240V
200-240V
220-240V
200-240V
220-240V
200-240V
200-240V
220-240V
220-240V
200-240V
220-240V
Output
Receptacles
(8)5-20R
(16)5-20R
(24)5-20R
(16)5-20R
(12)C13
(6)C19
(12)C13, (4)C19
(32)C13, (6)C19
(6)C19
(12)C13, (4)C19
(32)C13, (6)C19
(30)C13, (6)C19
(18)C13, (6)C19
(30)C13, (6)C19, (2)5-20R
(30)C13, (6)C19
(36)C13, (6)C19
(6)C19
(6)C19
(6)C19
(6)C19
(6)C19
(18)C13, (6)C19
(36)C13, (12)C19
(18)C13, (6)C19
(36)C13, (12)C19
(12)C13, (12)C19
(12)C13, (12)C19
Support Extension Support Locking Power
Bar Options
Cord Options













































NOTE: For more information on Extension Bar and Power Cord options, please see the Related Options section.
Page 11
QuickSpecs
HPE G2 Metered Power Distribution Units
PDU Plugs
Voltage
100-125 V
Single Phase
200-240 V
Single Phase
200 - 208 V
NA/JPN
Three Phase
200 – 240 V
400 – 415 V
INTL
Three Phase
Amps
# Wires
Plug Name
15 A
3
NEMA 5-15
20 A
3
NEMA 5-20
30 A
3
NEMA L5-30
20 A
3
IEC C20
30 A
3
NEMA L6-30
32 A
3
IEC 309 32A
50 A
3
CS8265C
63 A
3
IEC 309 63A
30 A
5
NEMA L15-30
30 A
5
NEMA L21-30
50 A
4
CS8365C
60 A
4
IEC 309 60A
16 A
5
IEC 309 16 A
32 A
5
IEC 309 32 A
Sample Plug Image
(color may vary by manufacturer)
Receptacle (R)
Plug (P)
Page 12
QuickSpecs
HPE G2 Metered Power Distribution Units
Technical Specifications
Operating Temperature
Operating Relative
Humidity (%)
Operating Elevation
Storage Temperature
Storage Relative
Humidity (%)
Storage Elevation
Conformance Standards
Kit Contents
50° to 140° F (10° to 60° C)
10% to 90%
0 to 10,000 ft. (0 to 3000 m)
-4° to 140° F (-20° to 60° C)
5% to 95%
0 to 30,000 ft. (0 to 9144 m)
UL or CSA, CB Test+ FCC, ICES, VCCI - NA/JPN models
CE, DEMKO, EAC, KC, KCC, ACMA - INTL models
UL or CSA, CB Test+ CE, DEMKO, EAC, FCC, ICES, KCC KC - WW models
All G2 Metered PDU models ship with:
• Mounting brackets/hardware
• Tie wraps
• Locking Power Cord Sample
(for models with either C13 and/or C19 outlets)
• Read me first card
Environment-friendly
End-of-life Management Hewlett Packard Enterprise offers end-of-life product return, trade-in, and
recycling programs, in many geographic areas, for our products. Products
Products and Approach and Recycling
returned to Hewlett Packard Enterprise will be recycled, recovered or
disposed of in a responsible manner.
http://www.hpe.com/recycle
The EU WEEE directive (2002/95/EC) requires manufacturers to provide
treatment information for each product type for use by treatment facilities.
This information (product disassembly instructions) is posted on the
Hewlett Packard Enterprise web site. These instructions may be used by
recyclers and other WEEE treatment facilities as well as Hewlett Packard
Enterprise OEM customers who integrate and re-sell Hewlett Packard
Enterprise equipment.
http://www.hpe.com/recycle
Page 13
QuickSpecs
HPE G2 Metered Power Distribution Units
Summary of Changes
Date
27-Mar-2017
Version History
Version 1
Action
Added
Description of Change
New QuickSpecs.
Sign up for updates
© Copyright 2017 Hewlett Packard Enterprise Development Company, L.P.
The information contained herein is subject to change without notice.
The only warranties for Hewlett Packard Enterprise products and services are set forth in the express
warranty statements accompanying such products and services. Nothing herein should be construed as
constituting an additional warranty. Hewlett Packard Enterprise shall not be liable for technical or editorial
errors or omissions contained herein.
a00002908 - 15863 - Worldwide - V1 - 27-March-2017