9V Battery POWERED Communication Capability

9V Battery POWERED
Communication Capability
Model Ei 605C Optical
High sensitivity – responds to all standard fires
Aesthetically pleasing, compact design
Innovative and robust optical chamber design
Low battery warning
Large Easy to use Test/Hush button
Hush Feature allows false alarm control
Interconnect up to 12 battery powered alarms
Easy to fit twist-on base
Optional upgrade to enable RadioLink interconnect
VdS approved to BS EN 14604:2005
Manufactured in Ireland to ISO 9001:2000
5 year Guarantee
Product Description
Operation
The Ei605C is an Optical Smoke Alarm using the light
scatter principle, giving a quick response to all standard
fires. It runs on a 9V replaceable alkaline battery
(supplied with the alarm)
The smoke detector will activate the built in sounder
upon sensing smoke particles. It will automatically
reset and silence the alarm when the smoke
particles are no longer present in the chamber.
The Ei605C has an innovative high performance optical
chamber with integral fixed insect screen reducing the
possibility of false alarms.
The red indicating LED will flash once every 40
seconds to show that the alarm is powered and it
has performed an automatic self-test.
The Ei605C is easily installed and comes supplied with
all necessary screw fixings.
The built in sounder will provide a minimum sound
output of 85dB at 3m.
The Ei605C has a large, easy to use, combined
Test/Hush button enables full testing of the alarm and
the ability to silence false alarms.
Pressing and holding the “Test/Hush” button will
perform a self test and sound the horn – checking
the chamber, electronics and horn.
The Ei605C maybe hardwire interconnected to twelve
battery powered alarms enabling all alarms to sound if
just one of the interconnected alarms should be
triggered.
Momentarily pressing the “Test/Hush” button when
an alarm is sounding will set the alarm into “HUSH”
mode. This reduces the sensitivity for a period of 10
minutes, after which the alarm automatically resets –
providing control over false alarms.
The Ei605C modular design allows it to be upgraded for
RadioLink functionality with the addition of the Ei605MRF
Radio frequency module. The optional RadioLINK
module simply plugs into the back of the Ei605C allowing
wireless interconnection of up to 12 RadioLink ready
alarms.
The smoke detector will emit a beep every 40
seconds to indicate that the battery is near depletion
and needs replacing.
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Email. eielectronics@eiltd.ie
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice.
Ei605C DataSht RevC
Model Ei605C Optical
Technical Specification
Sensor:
Optical, uses light scatter from
smoke particles
Alarm:
Piezoelectric-horn (built-in)
Alarm Sound Output: 85dB (minimum) at 3m
Sensitivity:
Airspeed:
Button Test:
Hush:
Complies with the requirements of
BS EN 14604: 2005
Essentially immune to the effect
of airspeed.
Temperature Range: 0 to 40°C
Humidity Range:
0% to 90% Relative Humidity
Interconnect:
Hardwire interconnect up to 12
battery powered alarms.
Simulates the effect of smoke to
check the chamber, electronics
and horn.
Silences nuisance alarm.
Automatically resets after
approximately 10 minutes.
Supply Voltage:
9V battery
Power-On Indicator:
Red LED flashes through cover
every 40 seconds
Installation & Placement
A combination of up to 12 battery
and Mains powered alarms maybe
RadioLINK interconnected.
Fixing:
Screw fixings supplied
Plastic material:
UL94HB flame retardant
Dimensions:
115mm (diameter) x 45mm
(height)
Weight:
200 grams
Warranty:
5 year (limited) warranty
Approvals:
VdS approved to
BS EN14604:2005, CE approved,
Manufactured to ISO 9001:2000
quality standards.
Specifications are subject to change
Alarms should be placed in accordance with the general guidelines shown in
the diagram above. These recommendations are based on the problem of
areas of “dead air” close to corners of rooms and apexes of ceilings, which
could result in the prevention of smoke reaching the smoke detector
Please consult the Instruction Leaflet supplied with the Ei605C for detailed
instructions as to how to correctly install and position the smoke detector
Important Precaution:
Do not install the actual smoke/heat
alarm itself in new or renovated
buildings until all work is completed
(including floor coverings) and the
building has been fully cleaned.
(Excessive dust and debris from
building work can contaminate the
smoke chamber and cause problems,
and it will also invalidate the guarantee).
If it must be installed, cover it
completely, particularly around the
edges, with a dust cover (eg. a plastic
bag), until all cleaning is finished..
Specifications are subject to change
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.+353 61 471277 Fx.+353 61 471053
Email. eielectronics@eiltd.ie
Web: www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice.
Ei605C DataSht RevC