EISX8M Series Industrial Ethernet 10/100 Mbps Compact Managed

EISX8M Se
eries
Industrial Ethernet 10/100
0 Mbps Compact Managed Swittching Hubs
Installation Guide
EISX8M extended-temperature managed switches provide ccapabilities
beyond both Plug and Play (PnP) and configurable switchess. Besides
conventional PnP features (auto-negotiation, 10/100 Mbpss data rate, halfor full-duplex operation, flow
w control), the EISX8M adds advvanced features
such as RapidRing™, VLAN
N, Trunking, Quality of Service (Q
QoS), Port
Mirroring, Simple Network Management
M
Protocol (SNMP), a
and a
programmable fault relay.
Each switch provides pream
mble regeneration with symmetryy and amplitude
compensation — retiming signals
s
to eliminate jitter. Digital p
pre-emphasis
compensates for inherent signal strength roll-off. Link integrrity is monitored,
verifying that a working ada
apter or hub is on the distant end of a segment.
Configuration can be done in two ways: a) via a web browse
er from a PC set
me LAN as the EISX default IP ad
ddress of
to communicate on the sam
192.168.92.68, or b) via a console
c
port connected to a Wind
dows-based
terminal emulation program
m (for console settings, see page 3).
All ports support PAUSE flo
ow control for full-duplex links and
d backpressure
for half-duplex. All RJ-45 ports feature Auto-MDIX for ease of cabling.
The switches are powered from
f
wide-range, low-voltage AC
C or DC sources
and redundant power conne
ections are provided for backup cconsiderations.
They come with the hardwa
are for either DIN-rail or panel mo
ounting. The
front panels feature a powe
er LED, a management status LED and bi-colour
LEDs for the link status, acttivity, and data rate of each port.
Designed for Industrial Ethe
ernet applications, each switch
complies with EMC immunitty and emissions compatibility
standards for industrial environments.
Specifications
Electrical
INPUT
Voltage:
Power
Non-fibre Units:
Fibre Units:
Frequency:
Functional
DC
AC
10–36 V
8–24 V
6W
10 W
N/A
6 VA
10 VA
47–63 Hz
Environmental
Operating Temperature:
Storage Temperature:
Humidity, non-cond.:
Protection:
– 40°C to +75°C
– 40°C to +85°C
10% to 95%
IP 30
DIN-rail Mounting
TS-35
Shipping Weight
1 lb (0.45 kg)
Regulatory Compliance
CE Mark; EN55022; EN55024
CFR 47 Part 15, Class A
UL508 — Industrial Control Equipment
For use in Class 2 circuits
Mechanical
Compliance:
Data Rates:
Signalling:
Connectors:
Segment
Length (max):
ANSI/IEEE 802.3
Copper
Fibre
10/100 Mbps
10BASE-T
100BASE-TX
RJ-45 (shielded)
100 m
100 Mbps
100BASE-FX
SC or ST
2 km*
15 km**
* multimode, ** single mode,
full-duplex
full-duplex
LED Indicators
Power
Status
Port Activity
Port Data Rate/Link
green
green
flashing
green (100 Mbps)
yellow (10 Mbps)
RJ-45 Connector Pin Assignments
Pin
Function
1
TD+
2
TD–
3
RD+
6
RD–
(All other pins are unused.)
Power Options
Power Considerations
The EISX8M can be
powered in various
ways as illustrated
below :
Voltage in the range of 10–36 VDC or 8–24 VAC
must deliver current commensurate with power
consumption. Power conductors can be stranded
(16–18 AWG) or solid (16–22 AWG). Zero volts
and the chassis are isolated from each other. Input
connections are reverse-polarity protected. Primary
power backup for a substitute DC supply or backup
battery is possible by way of built-in redundant
diode-isolated inputs, but separate provisions are
required for charging any backup battery.
LED Indicators
To aid troubleshooting, each port LED glows solid
if a link exists, flashes to show activity and shows
data rate by colour: green for 100 Mbps and yellow
for 10 Mbps. A power LED is provided. A status
LED glows green by default and its operation is
detailed in the Software Manual (enclosed CD).
Fault Relay
This relay is disabled by default. Its operation is
detailed in the Software Manual. Its contact is
normally closed and rated at 500 mA, 24 V (max).
Console Port
The Console Port uses the
standard RS-232 protocol
for configuring the switch.
For proper communication :
Set the Baud rate to 9600.
Set the Data bits to 8.
Set the Parity to None.
Set the Stop bits to 1.
Set the Flow control to None.
Need more help installing this product?
More information can be found at our website at www.ccontrols.com. If contacting our
office, ask for Technical Support.
Warranty
Contemporary Controls (CC) warrants this product to the original purchaser for two
years from the shipping date. If it fails to operate in compliance with its specification
during this period, CC will, at its option, repair or replace the product at no charge.
Product returned to CC for repair is warranted for one year from the date that the
repaired product is shipped back to the purchaser or for the remainder of the original
warranty period, whichever is longer. The customer is responsible for shipping product;
CC assumes no responsibility for product until received. This limited warranty covers
products only as delivered. User modification may void the warranty. Damage from
abuse, accident, disaster, misuse, or incorrect installation are not covered. This
warranty in no way warrants suitability of the product for any specific application. More
warranty information can be found at www.ccontrols.com.
Warning: This is a Class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.
Returning Products for Repair
Return the product to the location where it was purchased by following the instructions
at the URL below:
www.ccontrols.com/rma.htm
Declaration of Conformity
Information about the regulatory compliance of this product can be found at:
www.ccontrols.com/compliance.htm
December 2011
TD020810-0IF