Rosemount™ 705 Wireless Totalizing Transmitter

Reference Manual
00809-0200-4705, Rev AB
May 2017
Rosemount™ 705 Wireless Totalizing
Transmitter
Reference Manual
Contents
00809-0200-4705, Rev AB
May 2017
Contents
1Section 1: Introduction
1.1 Using this manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Product recycling/disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2Section 2: Configuration
2.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Connecting the turbine meter or pulse output device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Configuring the transmitter on the bench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Supported engineering unit codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5 Joining the device to a network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3Section 3: Mounting
3.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Installing the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.1 Installing the transmitter in a direct mount configuration . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.2 Installing the transmitter in a remote mount configuration . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Wireless considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3.1 Selected an installation location and position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3.2 Electrical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3.3 Verifying operating atmosphere . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4 Remote antenna (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.4.1 WN remote antenna option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.5 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.6 Grounding the transmitter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4Section 4: Commissioning
4.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2 Configuring the transmitter to communicate with the wireless network. . . . . . . . . . . . . . . . . 22
4.3 Using AMS Device Manager to configure the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.4 Using a Field Communicator to change parameters within the device . . . . . . . . . . . . . . . . . . . 23
4.5 K-factor consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.6 Verifying operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
4.6.1 AMS Device Manager. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Contents
iii
Reference Manual
Contents
00809-0200-4705, Rev AB
May 2017
5Section 5: Operation and Maintenance
5.1 Basic operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.1.1 Rollover information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.1.2 Enabling the LCD continuous operation feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.2 Determining device health. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3 Interpreting LCD screen messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3.1 Startup screen sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3.2 Diagnostic button screen sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.3.3 Network connection status screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.3.4 Device diagnostic screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.4 Replacing the power module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
5.5 Modbus®, EtherNet/IP™ and OPC mapping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
5.6 Reset/restore device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.7 Suspend (pause) the totalization in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.8 Average flow rate filtering period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.9 Low-Flow cut-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.10 Input sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.11 How to reset the totalized volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.12 Service support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
AAppendix A: Specifications and Reference Data
A.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
A.1.1 Functional specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
A.1.2 Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
A.1.3 Frequency input specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
A.1.4 Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
A.2 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
A.3 Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
BAppendix B: Product Certifications
B.1 European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.2 Telecommunication Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.3 FCC and IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.4 Ordinary Location Certification from CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.5 Installing in North America. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.6 USA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
B.7 Canada . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
B.8 Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
iv
Contents
Reference Manual
Contents
00809-0200-4705, Rev AB
May 2017
B.9 International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
B.10 Brazil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
B.11 EAC - Belarus, Kazakhstan, Russia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
B.12 Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
CAppendix C: High Gain Remote Antenna Option
C.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
C.2 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.1 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.2 Coaxial length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.3 Coaxial material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.4 Antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.5 Physical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.6 RF lightning arrestor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.7 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.2.8 Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
C.3 Installation considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.1 Antenna mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.2 Antenna height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.3 Coaxial cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.4 Installing coaxial drip loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.3.5 Applying coaxial sealant moisture protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.4 Transient/lightning considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.4.1 Gateway transient protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.4.2 RF lightning arrestor ground connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
C.5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
C.6 Installing the high gain remote antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
DAppendix D: Mapping of Alert Messages in the HART® Command 48
Additional Status
Contents
v
Contents
May 2017
vi
Reference Manual
00809-0200-4705, Rev AB
Contents
Reference Manual
Title Page
00809-0200-4705, Rev AB
May 2017
Rosemount™ 705 Wireless Totalizing
Transmitter
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum
product performance, make sure to thoroughly understand the contents before installing, using, or
maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1 800 999 9307 (7:00 a.m. to 7:00 p.m. CST)
National Response Center
1 800 654 7768 (24 hours a day)
Equipment service needs
International
1 952 906 8888
The Rosemount 705 Transmitter and all other wireless devices should be installed only after the Smart
Wireless Gateway has been installed and is functioning properly. Wireless devices should also be
powered up in order of proximity from the Gateway, beginning with the closest. This will result in a
simpler and faster network installation.
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware or
products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact an Emerson™ Sales Representative.
Title Page
vii
Reference Manual
Title Page
00809-0200-4705, Rev AB
May 2017
Failure to follow these installation guidelines could result in death or serious injury.
 Only qualified personnel should perform the installation.
Explosions could result in death or serious injury.
 Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are
installed in accordance with intrinsically safe or non-incendive field wiring practices.

Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This
device may not cause harmful interference. This device must accept any interference received, including
interference that may cause undesired operation.

This device must be installed to ensure a minimum antenna separation distance of 20 cm from all
persons.
NOTICE
Shipping considerations for wireless products:
The unit was shipped to you without the power module installed. Remove the power module prior to
shipping.
Each power module contains two “C” size primary lithium batteries. Primary lithium batteries are
regulated in transportation by the U. S. Department of Transportation, and are also covered by IATA
(International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD
(European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure
compliance with these or any other local requirements. Consult current regulations and requirements
before shipping.
Power module considerations:
The power module with the wireless unit contains two “C” size primary lithium/thionyl chloride
batteries. Each battery contains approximately 2.5 grams of lithium, for a total of 5 grams in each pack.
Under normal conditions, the battery materials are self-contained and are not reactive as long as the
batteries and the pack integrity are maintained. Care should be taken to prevent thermal, electrical, or
mechanical damage. Contacts should be protected to prevent premature discharge.
Battery hazards remain when cells are discharged.
Power modules should be stored in a clean and dry area. For maximum battery life, storage
temperature should not exceed 30 °C.
The power module has surface resistivity greater than one gigaohm and must be properly installed in
the wireless device enclosure. Care must be taken during transportation to and from the point of
installation to prevent electrostatic charge build-up.
viii
Title Page
Reference Manual
Introduction
00809-0200-4705, Rev AB
Section 1
1.1
May 2017
Introduction
Using this manual
The sections in this manual provide information on installing, operating, and maintaining the
Rosemount™ 705 Wireless Totalizing Transmitter. The sections are organized as follows:
 Section 2: Configuration provides instruction on commissioning and operating Rosemount 705
Transmitter. Information on software functions, configuration parameters, and online variables is also
included.
1.2

Section 3: Mounting contains mechanical and electrical installation instructions.

Section 4: Commissioning contains techniques for properly commissioning the device.

Section 5: Operation and Maintenance contains operation and maintenance techniques.

Appendix A: Specifications and Reference Data supplies reference and specification data, as well as
ordering information.

Appendix B: Product Certifications contains approval information.

Appendix C: High Gain Remote Antenna Option contains specification data and installation of high
gain antenna.

Appendix D: Mapping of Alert Messages in the HART® Command 48 Additional Status contains
important alerts in the HART command 48 additional status field for the Rosemount 705 Transmitter.
Product recycling/disposal
Recycling of equipment and packaging should be taken into consideration. The product and packaging
should be disposed of in accordance with local and national legislation.
Introduction
1
Introduction
May 2017
2
Reference Manual
00809-0200-4705, Rev AB
Introduction
Reference Manual
Configuration
May 2017
00809-0200-4705, Rev AB
Section 2
Configuration
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Connecting the turbine meter or pulse output device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
Configuring the transmitter on the bench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 8
Supported engineering unit codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
Joining the device to a network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 10
2.1
Safety messages
Instructions and procedures in this section may require special precautions to ensure the safety of the
personnel performing the operations. Information that potentially raises safety issues is indicated by a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded
by this symbol.
Failure to follow these installation guidelines could result in death or serious injury.
 Only qualified personnel should perform the installation.
Explosions could result in death or serious injury.
 Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are
installed in accordance with intrinsically safe or non-incendive field wiring practices.

Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Electrical shock could cause death or serious injury.
 Use extreme caution when making contact with the leads and terminals.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This
device may not cause harmful interference. This device must accept any interference received, including
interference that may cause undesired operation.
 This device must be installed to ensure a minimum antenna separation distance of 20 cm from all
persons.
2.2
Connecting the turbine meter or pulse output device
The Rosemount™ 705 Wireless Totalizing Transmitter is compatible with a number of simple turbine
meters or pulse output devices. When ordered in the optional configuration for direct connection,
option code D1, the Rosemount 705 Transmitter is compatible with one inch turbine meter direct
connections. Figure 2-1 on page 8 shows the correct input connections to the pulse terminals on the
transmitter. To ensure a proper turbine meter connection, anchor the turbine meter lead wires into the
appropriate compression terminals and tighten the screws. In noisy environments, be sure to properly
ground the transmitter using the ground terminal.
Configuration
7
Reference Manual
Configuration
00809-0200-4705, Rev AB
May 2017
Wiring the transmitter
For the R1 option (remote mount), if the turbine meter or pulse output device is installed in a
high-voltage environment and a fault condition or installation error occurs, the sensor leads and
transmitter terminals could carry lethal voltage. Use extreme caution when making contact with the
leads and terminals.
Use the following steps to wire the sensor and power supply to the transmitter:
1. Remove the transmitter enclosure cover.
2. Attach the turbine meter leads according to the diagram Figure 2-1 on page 8.
Note
For noisy electrical environments, it is best practice to ground the loop accordingly.
3. Connect the black power module.
4. Verify the connection and power by viewing the LCD display and seeing the power up sequence.
5. Replace the cover and tighten.
Figure 2-1. Rosemount 705 Transmitter Terminal Block
C
A
B
A. Pulse input connection
B. HART® terminal connection
C. Terminal block ground connection
Note
Connections are not polarity sensitive.
2.3
Configuring the transmitter on the bench
When using a Field Communicator, any configuration changes must be sent to the transmitter using the
Send key (F2). AMS™ Device Manager configuration changes are implemented when the Apply button is
clicked.
8
Configuration
Reference Manual
Configuration
May 2017
00809-0200-4705, Rev AB
Configuring on the bench with AMS Device Manager
AMS Device Manager is capable of connecting to devices directly, using a HART modem, or with the
Gateway. When configuring on the bench with a HART modem, double click the device icon, then select
the Configure/Setup tab (or right click and select Configure/Setup). Configure the device settings
using the Direct Connection menu. When configuring with the Gateway, double click the device icon then
select the Configure/Setup tab (or right click and select Configure/Setup). Configure the device
settings using the Wireless Connection menu. To check or change sensor configuration using a Field
Communicator, enter the following Fast Key sequence: 2, 1, 2.
2.4
Supported engineering unit codes
The following engineering units are supported by the Rosemount 705 Transmitter.
Total volume
Volumetric flow rate
US gallons per second
US gallons
US gallons per minute
US gallons per hour
US gallons per day
Liters per second
Liters
Liters per minute
Liters per hour
Imperial gallons per second
Imperial gallons
Imperial gallons per minute
Imperial gallons per hour
Imperial gallons per day
Cubic meters per second
Cubic meters
Cubic meters per minute
Cubic meters per hour
Cubic meters per day
Cubic yards per second
Cubic yards
Cubic yards per minute
Cubic yards per hour
Cubic yards per day
Cubic inches per second
Cubic inches
Cubic inches per minute
Cubic inches per hour
Cubic inches per day
Pulses
Configuration
Hertz
9
Reference Manual
Configuration
00809-0200-4705, Rev AB
May 2017
If a custom volume unit is desired, the Rosemount 705 Transmitter can be configured to report the
totalized pulses, and a custom conversion can be done on the host system side. Similarly, if a custom flow
rate unit is desired, the transmitter can be configured to report pulses per second (Hertz), and a custom
conversion can be done on the host system side. When reporting pulses or hertz, the configured K-factor
has no affect on the reported values.
2.5
Units
Fast key
Volume
2, 1, 2
Flow
2, 2, 1
Joining the device to a network
To communicate with the Gateway, and ultimately the Host System, the transmitter must be configured
to communicate with the wireless network.
Using a Field Communicator or AMS Device Manager, enter the Network ID and Join Key so they match
the Network ID and Join Key of the Gateway and the other devices in the network. If the Network ID and
Join Key are not identical, the transmitter will not communicate with the network. The Network ID and
Join Key may be obtained from the Gateway on the Network>Settings page on the web server or by
clicking network information in the upper right hand corner. Using a Field Communicator, the Network
ID and Join Key can be configured using a Field Communicator with the Fast Key Sequence: 2, 1, 3.
The final device network configuration piece is the update rate which, by default, is one minute. It can be
changed at commissioning, or at any time, by using AMS Device Manager or the Gateway’s web server.
The update rate should be between one second and 60 minutes. To change the update rate with a Field
Communicator, use the Fast Key sequence: 2, 1, 4.
If doing a bench top initial configuration, after completion remove the power module until installation.
When the device is installed, insert the power module and close the housing cover securely. Always
ensure a proper seal so metal touches metal, but do not over tighten.
10
Configuration
Mounting
Reference Manual
May 2017
00809-0200-4705, Rev AB
Section 3
Mounting
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11
Installing the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
Wireless considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 15
Remote antenna (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18
LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
Grounding the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 19
3.1
Safety messages
Instructions and procedures in this section may require special precautions to ensure the safety of the
personnel performing the operations. Information that potentially raises safety issues is indicated by a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded
by this symbol.
Failure to follow these installation guidelines could result in death or serious injury.
 Only qualified personnel should perform the installation.
Explosions could result in death or serious injury.
 Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are
installed in accordance with intrinsically safe or non-incendive field wiring practices.

Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.

This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This
device may not cause harmful interference. This device must accept any interference received, including
interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 20 cm from all
persons.
Mounting
11
Reference Manual
Mounting
00809-0200-4705, Rev AB
May 2017
3.2
Installing the transmitter
The Rosemount™ 705 Wireless Totalizing Transmitter can be installed in one of two configurations:
Direct mount (D1): The turbine meter is connected directly to the Rosemount 705 Transmitter housing’s
conduit entry. For installation instructions, see “Installing the transmitter in a direct mount
configuration” on page 12.
Remote mount (R1): The turbine meter or pulse output device is mounted separate from the Rosemount
705 Transmitter housing, then connected to the transmitter via conduit. For installation instructions, see
“Installing the transmitter in a remote mount configuration” on page 14.
3.2.1
Installing the transmitter in a direct mount configuration
Figure 3-1. Direct Mount
B
C
A
A. Turbine meter
B. Rosemount 705 Transmitter
C. 1-in. NPT connection to flow meter and two piece pipe union
Note
Direct mount installation should not be employed when using tubing and connectors such as Swagelok®
fittings.
1. Install the turbine meter according to standard installation practices making sure to use thread
sealant on all of the connections.
2. Attach the turbine meter wiring to the terminals as indicated on the wiring diagram (Figure 3-2). This
procedure is already included for the D1 (direct mount) option.
12
Mounting
Reference Manual
Mounting
00809-0200-4705, Rev AB
May 2017
Figure 3-2. Rosemount 705 Terminal Block
C
A
B
A. Pulse input connection
B. HART® terminal connection
C. Terminal block ground connection
3. Attach the transmitter housing to the turbine meter using the threaded conduit entry.
4. Seal threads on 1-in. NPT turbine meter connection. Take union apart and turn on bottom
fitting to turbine meter.
5. Attach mill spec connector to turbine meter pickup.
6. Screw on the remaining union part.
Note
Sealant should already be applied to threads on the D1 (direct mount) option.
Note
Wireless devices should only be powered up after the Smart Wireless Gateway, in order of
proximity from the Smart Wireless Gateway beginning with the closest device. This results in a
simpler and faster network installation.
7. Connect the black power module
Figure 3-3. Power Module Installation
8. Close the housing cover and tighten to safety specification. Always ensure a proper seal so
metal touches metal, but do not over tighten.
9. Position the antenna so it is vertical, either straight up or straight down.
a. The antenna should be approximately 3 ft. (0.91 m) from any large structures or
buildings, to allow clear communication to other devices.
Mounting
13
Reference Manual
Mounting
00809-0200-4705, Rev AB
May 2017
Figure 3-4. Antenna Positioning
Possible antenna rotation shown.
Antenna rotation allows for best
installation practices in any
configuration.
3.2.2
Installing the transmitter in a remote mount configuration
Figure 3-5. Remote Mount Installation
C
A
B
A. Turbine meter
B. Rosemount 705 Transmitter
C. 1-in. supplied cable gland adapter for turbine meter.
Included:
(1) Cable gland
(1) Cable gland adapter for turbine meter
10 ft.. of cable connection wiring
1. Install the turbine meter or pulse output device according to standard installation practices being
sure to use thread sealant on all of the connections.
2. Pull the cable connection wiring through the supplied cable gland adapter for the turbine meter.
Then pull the cable wiring through the transmitter cable gland.
Note
Pay attention to the orientation of the cable gland to ensure proper connection to transmitter.
3. Attach the turbine meter or pulse output device wiring to the terminals as shown in the wiring
diagrams beginning on page 8.
Note
Wireless devices should only be powered up after the Smart Wireless Gateway, in order of proximity from
the Gateway beginning with the closest device. This results in a simpler and faster network installation.
14
Mounting
Reference Manual
00809-0200-4705, Rev AB
Mounting
May 2017
4. If commissioning the Rosemount 705 Transmitter, connect the power module as shown in Figure 3-3
on page 13.
5. Close the housing cover and tighten to safety specifications. Always ensure a proper seal by installing
the electronic housing covers so metal touches metal, but do not over tighten.
6. Position the antenna vertically, either straight up or straight down, as shown in Figure 3-4 on page 14.

3.3
The antenna should be approximately 3 ft. (1 m) from any large structures or buildings, to allow clear
communication to other devices.
Wireless considerations
Power up sequence
The Smart Wireless Gateway should be installed and functioning properly before any wireless field
devices are powered. Install the Black Power Module, SmartPower™ Solutions model number 701PBKKF
into the Rosemount 705 Transmitter to power the device. Wireless devices should also be powered up in
order of proximity from the Gateway, beginning with the closest. This will result in a simpler and faster
network installation. Enable Active Advertising on the Gateway to ensure that new devices join the
network faster. For more information see the Smart Wireless Gateway Reference Manual.
Antenna position
The antenna should be positioned vertically, either straight up or straight down, and it should be
approximately 3 ft. (1 m) from any large structure, building, or conductive surface to allow for clear
communication to other devices.
Figure 3-6. Antenna Position
Preparing (or sealing) the conduit entries
Due to possible damage from moisture after installation, ensure that each conduit entry is either sealed
with a conduit plug with appropriate thread sealant, or has an installed conduit fitting or cable gland
with appropriate thread sealant.
Mounting
15
Reference Manual
Mounting
00809-0200-4705, Rev AB
May 2017
Figure 3-7. Locating Conduit Entries
A
A
A. Conduit entry
Connecting the Field Communicator to the transmitter
The power module needs to be connected for the Field Communicator to interface with the Rosemount
705 Transmitter.
Figure 3-8. Field Communicator Connections
1
2
P/N 00753-9200-0020
3
4
3.3.1
COMM
Selected an installation location and position
When choosing an installation location and position, take into account access to the transmitter. For
best performance, the antenna should be vertical with space between objects in a parallel metal plane,
such as a pipe or metal framework, as the pipes or framework may adversely affect the antenna’s
performance.
16
Mounting
Reference Manual
Mounting
00809-0200-4705, Rev AB
3.3.2
May 2017
Electrical
Caring for the power module
The Rosemount 705 Transmitter is self-powered. The included Black Power Module contains two “C” size
primary lithium/thionyl chloride batteries. Each battery contains approximately 2.5 grams of lithium, for
a total of 5 grams in each pack. Under normal conditions, the battery materials are self-contained and
are not reactive as long as the batteries and the power module are maintained. Care should be taken to
prevent thermal, electrical, or mechanical damage. Contacts should be protected to prevent premature
discharge.
Making turbine meter connections
Make turbine meter connections through the cable entry in the side of the connection head. Be sure to
provide adequate clearance for cover removal and lead attachments (remote option).
3.3.3
Verifying operating atmosphere
Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Isolating the transmitter from sources of heat
The transmitter will operate within specifications for ambient temperatures between –40 and 185 °F
(–40 and 85 °C). Heat from the process is transferred from the switch to the transmitter housing. If the
expected process temperature is near or beyond specification limits, consider using an extension, or
remote mount the transmitter to thermally isolate it from the process.
Temperature limits
Options
Mounting
Operating limit
Storage limit
With LCD display
–4 to 175 °F
–20 to 80 °C
–40 to 185 °F
–40 to 85 °C
Without LCD display
–40 to 185 °F
–40 to 85 °C
–40 to 185 °F
–40 to 85 °C
17
Reference Manual
Mounting
00809-0200-4705, Rev AB
May 2017
3.4
Remote antenna (optional)
The remote antenna option provides flexibility for mounting the Rosemount 705 Totalizer based on
wireless connectivity, lightning protection, and current work practices.
When installing remote mount antennas for the transmitter, always use established safety procedures
to avoid falling or contact with high-power electrical lines.
Install remote antenna components for the transmitter in compliance with local and national electrical
codes and use best practices for lightning protection.
Before installing, consult with the local area electrical inspector, electrical officer, and work area
supervisor.
The transmitter remote antenna option is specifically engineered to provide installation flexibility while
optimizing wireless performance and local spectrum approvals.
To maintain wireless performance and avoid non-compliance with spectrum regulations, do not change
the length of cable or the antenna type.
If the supplied remote mount antenna kit is not installed per these instructions, Emerson is not
responsible for wireless performance or non-compliance with spectrum regulations.
The remote mount antenna kit includes coaxial sealant that is for the cable connections, lightning
arrestor, and antenna.Find a location where the remote antenna has optimal wireless performance.
Ideally this will be 15–25 ft. (4.6–7.6 m) above the ground or 6 ft. (2 m) above obstructions or major
infrastructure. To install the remote antenna, use one of the following procedures. The WN option is
25 ft. (7.6 m).
3.4.1
WN remote antenna option
1. Mount the antenna on a 1.5- to 2-in. pipe mast using the supplied mounting equipment.
2. Connect the lightning arrestor directly to the top of the Rosemount 705 Totalizer.
3. Install the grounding lug, lock washer, and nut on top of lightning arrestor.
4. Connect the antenna to the lightning arrestor using the supplied LMR-400 coaxial cable ensuring the
drip loop is not closer than 1 ft. (0.3 m) from the lightning arrestor.
5. Use the coaxial sealant to seal each connection between the wireless field device, lightning arrestor,
cable, and antenna.
6. Ensure the mounting mast and lightning arrestor are grounded according to local/national electrical
code.
Note
Any spare lengths of coaxial cable should be placed in 12-in. (0.3 m) coils.
18
Mounting
Reference Manual
Mounting
00809-0200-4705, Rev AB
3.5
May 2017
LCD display
If an LCD display is ordered, it will be shipped attached to the transmitter.
The optional LCD display can be rotated in 90° increments by squeezing the two tabs, pulling out,
rotating and snapping back into place.
If the LCD diplay pins are inadvertently removed from the interface board, carefully re-insert the pins
before snapping the LCD display back into place.
Installing the LCD display
To install the LCD display, use Figure 3-9 on page 19 and the following instructions:
1. Remove the LCD display cover. Do not remove the instrument cover in explosive environments when
the circuit is live.
2. Put the four-pin connector into the LCD display, rotate to the desired position and snap into place.
Note the following LCD display temperature limits:

Operating: –4 to 175 °F (–20 to 80 °C)

Storage:
–40 to 185 °F (–40 to 85 °C)
3. Replace the transmitter cover.
Note
Only use Rosemount Wireless LCD display part number: 00753-9004-0002. The transmitted data may
not match data displayed on LCD display due to differences in update rate and screen refresh rate.
Figure 3-9. Optional LCD Display
A
B
C
A. LCD pins
B. LCD display
C. LCD cover
3.6
Grounding the transmitter
The Rosemount 705 Transmitter operates best with the housing grounded. Floating systems, however,
can cause extra noise that may affect the accuracy of the transmitter. If the signal appears noisy or
erratic, grounding at a single point may solve the problem. Grounding of the electronics enclosure
should be done in accordance with local and national installation codes. Grounding is accomplished
through the process connection using the internal or external case grounding terminal.
Mounting
19
Reference Manual
Mounting
00809-0200-4705, Rev AB
May 2017
Determining grounding requirements
Each process installation has different grounding requirements. Use the options recommended by the
facility for the specific turbine meter or pulse output device.
1. Connect turbine meter wiring shield to the grounded transmitter housing.
2. Ensure the transmitter housing is electrically isolated from the turbine meter or pulse output device
wiring.
B
A
C
A. Turbine meter
B. Transmitter ground point
C. Rosemount 705 Transmitter
20
Mounting
Commissioning
Reference Manual
May 2017
00809-0200-4705, Rev AB
Section 4
Commissioning
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
Configuring the transmitter to communicate with the wireless network . . . . . . . . . . . . . . . . . page 22
Using AMS Device Manager to configure the transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Using a Field Communicator to change parameters within the device . . . . . . . . . . . . . . . . . . . page 23
K-factor consideration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Verifying operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 25
4.1
Safety messages
Instructions and procedures in this section may require special precautions to ensure the safety of the
personnel performing the operations. Information that potentially raises safety issues is indicated by a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded
by this symbol.
Failure to follow these installation guidelines could result in death or serious injury.
 Only qualified personnel should perform the installation.
Explosions could result in death or serious injury.
Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are
installed in accordance with intrinsically safe or non-incendive field wiring practices.


Verify the operating atmosphere of the transmitter is consistent with the appropriate hazardous
locations certifications.
Electrical shock could cause death or serious injury.
 Use extreme caution when making contact with the leads and terminals.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This
device may not cause harmful interference. This device must accept any interference received, including
interference that may cause undesired operation.
 This device must be installed to ensure a minimum antenna separation distance of 20 cm from all
persons.
Note
The Rosemount™ 705 Wireless Totalizing Transmitter and all other wireless devices should be installed
only after the Smart Wireless Gateway has been installed and is functioning properly.
Wireless devices should be powered up in order of proximity from the Gateway, beginning with the
device closest to the Gateway. This will result in a simpler and faster network installation.
Commissioning
21
Commissioning
00809-0200-4705, Rev AB
May 2017
4.2
Reference Manual
Configuring the transmitter to communicate with the
wireless network
In order to communicate with the Smart Wireless Gateway, and ultimately the Host System, the
transmitter must be configured to communicate with the wireless network. This step is the wireless
equivalent of connecting wires from a transmitter to the Host System. Using a Field Communicator or
AMS™ Device Manager, enter the Network ID and Join Key so they match the Network ID and Join Key of
the gateway and other devices in the network. If the Network ID and Join Key are not identical, the
Rosemount 705 Transmitter will not communicate with the network. The Network ID and Join Key may
be obtained from the Smart Wireless Gateway on the Setup>Network>Settings page on the web server,
shown in Figure 4-1.
Figure 4-1. Gateway Network Settings
22
Commissioning
Reference Manual
Commissioning
00809-0200-4705, Rev AB
4.3
May 2017
Using AMS Device Manager to configure the
transmitter
1. Right click on the Rosemount 705 Transmitter and select Configure.
2. When the menu opens, select Join Device to Network and follow the method to enter the Network
ID and Join Key.
4.4
Using a Field Communicator to change parameters
within the device
The most common parameters changed are the Network ID and Join Key. The Network ID and Join Key
may be changed in the wireless device by using the following Fast Key sequence. Set both Network ID
and Join Key.
Function
Wireless setup
4.5
Fast Key sequence
Menu items
2, 1, 1
Network ID, Set Join Key
K-factor consideration
The K-factor value is used to tell the Rosemount 705 Transmitter how much volume corresponds to an
input pulse. The K-factor is entered in units of “Pulses per Gallon”. It is important to configure the
transmitter with the proper K-factor that corresponds to the turbine meter that it is attached to. If the
K-factor is not configured properly, the accuracy of the reported totalized volume and flow rate may be
adversely affected. Any time the attached turbine meter is replaced, the K-factor setting should be
verified and/or modified accordingly to maintain a proper match.
If the K-factor is not specified to be pre-configured when ordering the Rosemount 705 Transmitter, it will
be shipped without any K-factor configured. In this case, the K-factor must be configured before any
valid values can be obtained for the totalized volume or the average flow rate. The transmitter will report
a value of NaN (Not a Number) when the K-factor has not been configured.
When changing the K-factor, the Rosemount 705 Transmitter will recalculate a new totalized volume
assuming that all captured input pulses correspond to the new K-factor value. This means the current
value of the totalized volume held in the transmitter may change as a result of changing the K-factor. If
this is not desired, the value of totalized volume can be noted, and reset the volume to the original value
after the new K-factor has been configured. To avoid any loss of volume accumulation, this procedure
should only be done when the flow through the attached turbine meter has been stopped.
Commissioning
23
Reference Manual
Commissioning
00809-0200-4705, Rev AB
May 2017
Figure 4-2. Handheld Tree
1 Dev Status: Good
2 Comm: Connected
3 Totalized Volume
4 Status
5 Average Flow Rate
6 Status
7 Update Rate
8 Join Device to N/W
9 Device Information
1 Refresh Alerts
2 No Actuve Alerts
3 History
4 F:
5 A:
6 M:
1 Identification
2 Revisions
3 Radio
4 Security
1 Basic Setup
2 Configure Totalizing Option
3 Join Device to N/W
4 Configure Update Rate
5 Configure Device Display
6 Configure Process Alerts
1 Over view
2 Configure
3 Service Tools
1 Guided Setup
2 Manual Setup
3 Alert Setup
1 Alert Description
2 Alert Image
1 Long Tag
2 Tag
3 Model
4 Transmitter S. N.
5 Date
6 Description
7 Message
8 Model Numbers
9 Device Image
1 Model Number 1
2 Model Number 2
3 Model Number 3
1 Universal
2 Field Device
3 Software
4 Hardware
5 DD Revision
1 MAC Address
2 Manufacturer
3 Device Tyoe
4 Device Revision
5 Software Revision
6 Hardware Revision
7 Xmit Power Level
8 Min Brdcst Rate
1 Write Protect Status: Disabled
2 Lock Status: Unlocked
3 Over the Air Upgrade: Unlocked
1 Wireless
2 Totalizing Option
3 Display
4 HART
5 Security
6 Device Information
7 Power
1 Network ID
2 Join Device to N/W
3 Broadcast Info
1 Turbine Configuration
2 Flow Configuration
1 Display Mode
2 Config Data History
1 Meas and Status Log
2 Config Data History
3 Variable Mapping
4 Percent Range
1 Write Protect Status: Disabled
2 Lock Stat: Unlocked
3 Lock/Unlock
4 Over the Air Upgrade
1 Long Tag
2 Tag
3 Transmitter S. N.
4 Date
5 Descrption
6 Message
1 K-factor
2 Volume Unites
3 Roll Over Point
4 Input Sensitivity
1 Flow Units
2 Low Flow Cutoff
3 Filter Period
1
2
3
4
5
Totalized Volume
Average Flow Rate
Electronic Temp
Supply Voltage
Percent of Range
1 Primary Variable
2 Secondary Variable
3 Third Variable
4 Fourth Variable
1 Upper Range Value
2 Lower Range Value
3 Upper Sensor Limit
4 Lower Sensor Limit
1 Power Mode
2 Power Source
1 Totalized Volume
2 Average Flow Rate
3 Alert Options
1 Totalized Volume/Avg Flow Rate
2 Status
3 HI-HI Alarm
4 HI Alarm
5 LO-LO Alarm
6 LO Alarm
1 Mode
2 Units
3 Alert Limit
4 Dead Band
1 Roll Over Point
2 Roll Over Exceeded
3 Roll Over Warning
4 Lifetime Warning
5 Roll Over Warn Thres
6 Lifetime Warn Thres
1 Alerts
2 Variables
3 Trends
4 Communication
5 Maintenance
6 Simulate
1 Refresh Alerts
2 No Active Alerts
3 History
1
2
3
4
Variable Summary
Mapped Variables
All Variables
Last Update Time
1 Totalized Volume
2 Average Flow Rate
3 Data History
1
2
3
4
5
Comm: Connected
Join Mode
Available Nghbrs
Advertisements
Join Attempts
1 Routine Maintenance
2 Reset/Restore
1 Clear Alert History
2 List of Previous alerts
1
2
3
4
PV
SV
TV
QV
1 PV / SV / TV / QV
2 PV / SV/ TV / QV Status
3 Gauge
1
2
3
4
5
Totalized Volume
Average Flow Rate
Electronics Temp
Supply Voltage
Percent of Range
1 Totalized Volume
Average Flow Rate
Electronics Temp
Supply Voltage
Percent of Range
2 Status
3 Gauge
1
2
3
4
5
6
7
Device Variable
Variable Units
Sample Interval
Date of Newest Val
Time of Newest Val
View Data History
Refresh
1 Measurement History
2 Locate Device
3 Install New Power Module
4 Set Total Volume
5 Sensor Life
1 Lifetime Counts
2 Reset Lifetime Cnts
1 Device Reset
2 Restore to Default Settings
1 Simulate
24
1 Totalized Volume
2 Average Flow Rate
3 Electronics Temperature
4S
l V lt
Commissioning
Reference Manual
Commissioning
00809-0200-4705, Rev AB
4.6
May 2017
Verifying operation
There are four ways to verify operation: using the optional local display (LCD), using the Field
Communicator, using the Smart Wireless Gateway's integrated web interface, or by using AMS Suite. If
the Rosemount 705 Transmitter was configured with the Network ID and Join Key, and sufficient time has
passed, the transmitter will be connected to the network.
Troubleshooting
If the device is not joined to the network after power up, verify the correct configuration of the Network
ID and Join Key, and verify that Active Advertising has been enabled on the Gateway. The Network ID and
Join Key in the device must match the Network ID and Join Key of the Gateway.
Operating the local display
The LCD displays the configured values at the update rate, or can optionally be enabled for continuous
display. See Enabling the LCD continuous operation feature .
Diagnostic button display sequence
More detailed diagnostic information can be obtained by removing the display cover of the Rosemount
705 Transmitter, and momentarily depressing the DIAG button. The LCD will display the diagnostic
screens as shown in Figure 4-4.
Press the Diagnostic button to display the TAG, Device ID, Software Revision, Network ID, Network Join
Status and Device Status screens.
Figure 4-3. Diagnostic Screen Sequence
Tag
Device ID
Abcde
id - 12
fgh
345678
Network ID
Network join
status
Device status
netwk
netwk
Suply
OK
volts
13 0 5
ID
7. 2 1
Network join status
The chevron-shaped status bar at the top of the screen indicates the progress of the network join
process. When the status bar is filled, the device is successfully connected to the wireless network. This is
shown, in Figure 4-4 on page 26.
Commissioning
25
Reference Manual
Commissioning
00809-0200-4705, Rev AB
May 2017
Figure 4-4. Network Join Status Screens
Searching for
network
Joining network
Connected with
limited bandwidth
Connected
NETwK
netwk
netwk
netwk
SRCHNG
NEGOT
LIM-OP
OK
Connecting with a Field Communicator
A Rosemount 705 DD is required for HART® Communication.
Function
Communications
Fast Key sequence
Menu items
2, 1, 3
Join Status, Communication Status, Join Mode, Number of
Available Neighbors, Number of Advertisements Heard,
Number of Join Attempts
Checking for communication using the Smart Wireless Gateway
In the integrated web interface from the Gateway, navigate to the devices page. This page shows
whether the device has joined the network and if it is communicating properly.
Note
The time to join the new device(s) to the network is dependent upon the number of devices being joined
and the number of devices in the current network. For one device joining an existing network with
multiple devices, it may take up to five minutes. It may take up to 60 minutes for multiple new devices to
join the existing network.
4.6.1
AMS Device Manager
When the device has joined the network, it will appear in the AMS Device Manager as illustrated below.
26
Commissioning
Reference Manual
Commissioning
00809-0200-4705, Rev AB
May 2017
Troubleshooting
If the device is not joined to the network after power up, verify the correct configuration of the Network
ID and Join Key, and verify that Active Advertising has been enabled on the Gateway. The Network ID and
Join Key in the device must match the Network ID and Join Key of the Gateway.
The Network ID and Join Key may be obtained from the Gateway in the upper right hand corner labeled
network information. The Network ID and Join Key may be changed in the wireless device by using the
following Fast Key sequence.
Function
Wireless
Commissioning
Fast Key sequence
Menu items
2,1,3
Join Device to Network
27
Commissioning
May 2017
28
Reference Manual
00809-0200-4705, Rev AB
Commissioning
Reference Manual
Operation and Maintenance
00809-0200-4705, Rev AB
May 2017
Section 5
Operation and Maintenance
Basic operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 29
Determining device health . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 30
Interpreting LCD screen messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 30
Replacing the power module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 37
Modbus®, EtherNet/IP™ and OPC mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 38
Reset/restore device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 39
Suspend (pause) the totalization in the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 39
Average flow rate filtering period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 39
Low-Flow cut-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
Input sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
How to reset the totalized volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
Service support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 40
5.1
Basic operation
5.1.1
Rollover information
The totalized volume will automatically restart at a volume of zero when the configured rollover point
has been reached. The table below describes some estimates to how long a rollover will take at max
values of 10 million. Best practices are to reset the total before the device rollover occurs. The totalized
volume will accumulate in the transmitter up to a configurable rollover point. Once the totalized volume
reaches the rollover point, the totalized value will automatically continue totalizing the volume starting
from zero. The rollover point defaults to 100 million, but can be configured to any value between one
and two billion. Note the resolution of the totalized volume is reduced as the value gets larger. Refer to
the table below or see the menu tree:
Configured units code
Earliest rollover
Typical longest LCD wait
Typical longest value wait
Cu.M
75 years
137 days
39 minutes
L
27 days
3 hours
2 seconds
UK Gal
125 days
15 hours
10 seconds
US Gal
104 days
12 hours
9 seconds
Barrel
11 years
21 days
6 minutes
Cu.F
2 years
3 days
1 minute
Cu.Y
57 years
105 days
30 minutes
Cu.I
0 day
3 minutes
0 seconds
Pulses
1 day
50 seconds
0 seconds
Note
The rollover value itself is not affected by the volume engineering units. For example, if the rollover value
is configured to 100 million with engineering units of gallons, a change to volume units of cubic meters
will cause the rollover value to still be 100 million, but will rollover at 100 million cubic meters rather than
100 million gallons.
Operation and Maintenance
29
Reference Manual
Operation and Maintenance
00809-0100-4248, Rev CA
May 2017
5.1.2
Enabling the LCD continuous operation feature
The Rosemount™ 705 Wireless Totalizing Transmitter has the ability to keep the LCD always on for local
indication of the total volume and average flow for the attached output device. Power module life will be
reduced when operating in this mode. For example, at a one minute update rates the power module life
would be reduced from a 10 year life to an estimated eight year life. More information on the power
module life impact for various update rates can be found at
Emerson.com/Rosemount/Power-Module-Life-Estimator
Enabling continuous LCD updates
AMS™ Device Manager
1. Connect the Rosemount 705 Transmitter to the HART® Communicator and access the Rosemount
705 DD.
2. Double click on the Rosemount 705 icon and select Configure>Guided Setup> Configure Device Display
Through the handheld
1. Connect the Rosemount 705 Transmitter to the HART Handheld device.
2. Fast keys 2, 1, 5 (Configure>Manual Setup> Display> Display Mode)
5.2
Determining device health
In addition, system considerations must be observed to ensure the device is still connected to the
wireless network and reporting values. On an Emerson Smart Wireless Gateway, this can be done by
referring to the parameter: PV_HEALTHY. The PV_HEALTHY has a “True” state when the device is on the
network and its updates are current, not late or stale, and the PV value is functioning properly. A “False”
state of PV_HEALTHY means the device is either off of the network, the data updates are not current, or
there is an issue measuring PV. In the case of a “False” state of PV_HEALTHY, it is recommended to
assume the device is not connected to the network and to take appropriate action.
5.3
Interpreting LCD screen messages
The transmitted data may not match data displayed on LCD display due to differences in update rate and
screen refresh rate.
5.3.1
Startup screen sequence
The following screens will display when the power module is first connected to the Rosemount 705
Transmitter.
XXXXX
XXXXxxx
All segments On: used to visually determine if there are any bad
segments on the LCD display
xxxxxx
30
Operation and Maintenance
Reference Manual
Operation and Maintenance
00809-0200-4705, Rev AB
May 2017
Device identification: used to determine Device Type
Abcde
Device information - Tag: user entered tag which is eight
characters long - will not display if all characters are blank
fgh
Totalized volume screen: accumulated total volume over time
Average rate screen: average rate value
Electronics screen: feature board temperature value, can be
modified to a specific variable in the DD
Operation and Maintenance
31
Reference Manual
Operation and Maintenance
00809-0100-4248, Rev CA
May 2017
Suply
7. 2 1
Supply voltage screen: voltage reading at the power module
terminals, can be modified to a specific variable in the DD
volts
alert
Alert screen: at least one alert is present - this screen will not
display if no alerts are present
presnt
5.3.2
Diagnostic button screen sequence
The following five screens will display when the device is operating properly and the Diagnostic Button
has been pressed:
Abcde
Device information - Tag: User entered tag which is 8
characters long - will not display if all characters are blank
fgh
id - XX
Device identification: Used to determine Device ID
XXXXXX
Software revision: Indication of the software revision of the
device
32
Operation and Maintenance
Reference Manual
Operation and Maintenance
00809-0200-4705, Rev AB
May 2017
netwk
13 0 5
Network ID: Assuming the device has the correct join key, this
ID tells the user what network the device can connect with
ID
netwk
Network connection status: The device has joined a network
and has been fully configured and has multiple parents
OK
Suply
7. 2 1
Supply voltage: Voltage reading at the power module terminals
volts
5.3.3
Network connection status screens
These screens display the network status of the device. Only one will be shown in the fourth position of
the diagnostic button screen sequence.
netwk
Diagnostic button screen 4.1: The device is attempting to start
the radio
unknwn
netwk
Diagnostic button screen 4.2: The device has just restarted
INIT
Operation and Maintenance
33
Operation and Maintenance
Reference Manual
00809-0100-4248, Rev CA
May 2017
netwk
Diagnostic button screen 4.3: The device is starting to join the
process
idle
netwk
Diagnostic button screen 4.4: the device is in a disconnected
state and requires a “Force Join” command to join the network
DISCNT
NETwK
Diagnostic button screen 4.5: The device is searching for the
Network
SRCHNG
netwk
Diagnostic button screen 4.6: The device is attempting to join
a network
NEGOT
netwk
Diagnostic button screen 4.7: The device is connected to the
Network, but is in a “Quarantined” state
conect
34
Operation and Maintenance
Reference Manual
Operation and Maintenance
00809-0200-4705, Rev AB
May 2017
netwk
LIM-OP
netwk
Diagnostic button screen 4.8: The device is joined and
operational, but is running with limited bandwidth for sending
periodic data
Diagnostic button screen 4.9: the device has joined a network
and has been fully configured and has multiple parents
OK
5.3.4
Device diagnostic screens
The following screens will show the device diagnostics depending on the state of the device, continuing
after Diagnostic Button Screen 5.
Diagnostic button screen 6.1: There is a critical error which
may prevent the electronics board from operating correctly
Diagnostic button screen 6.2: There is a warning which should
be addressed, but should not affect the device output
suply
failur
Operation and Maintenance
Diagnostic button screen 7.1: Terminal voltage has dropped
below level of operating limit. Replace the Black Power Module
model number 701PBKKF (part number: 00753-9220-0001)
35
Reference Manual
Operation and Maintenance
00809-0100-4248, Rev CA
May 2017
suply
low
radio
failur
confg
failur
snsr
failur
bdWTh
limitd
Diagnostic button screen 7.2: Terminal voltage is below the
recommended operating range - if this is a self-operated device,
the power module should be replaced - for line powered devices,
the supply voltage should be increased
Diagnostic button screen 8: device cannot retrieve information
from the radio in the device - the device may still be operational
and publishing HART data
Diagnostic button screen 9: Configuration of the transmitter is
invalid such that critical operation of the device may be affected
- check the extended configuration status to identify which
configuration item(s) need to be corrected
Diagnostic button screen 10: Switch attached to the
transmitter has failed, and valid readings from that switch are no
longer possible - check the switch and switch wiring
connections - check additional status for more detailed
information of the failure source
Diagnostic button screen 11: Device has not yet received all of
the requested wireless bandwidth needed to operate as
configured
Note
Use Rosemount Wireless LCD display part number: 00753-9004-0002.
36
Operation and Maintenance
Reference Manual
00809-0200-4705, Rev AB
5.4
Operation and Maintenance
May 2017
Replacing the power module
When the power module needs to be replaced, remove the power module cover and the depleted power
module. Replace the power module with a new Black Power Module, SmartPower™ Solutions model
number 701PBKKF (part number: 00753-9220-0001). Then replace the cover and tighten it to
specification. Always ensure a proper seal so metal touches metal, but do not over-tighten. After the
power module has been replaced, navigate to AMS Device Manager to reset the power module function.
This also can be done via the handheld 3, 5, 1, 3.
When replacing the power module, the device will stop totalizing data. The device will resume from
where the last total was periodically recorded (within a five minute window). Example: The best practice
when replacing the power module is to make note of the totalized volume before removing the power
module. After installing a new power module, the totalized volume can be set to the previous recorded
value.
Handling the power module
The black power module with the wireless unit contains two “C” size primary lithium/thionyl chloride
batteries. Each battery contains approximately 2.5 grams of lithium, for a total of 5 grams in each pack.
Under normal conditions, the battery materials are self-contained and are not reactive as long as the
batteries and the battery pack integrity are maintained. Care should be taken to prevent thermal,
electrical or mechanical damage. Contacts should be protected to prevent premature discharge.
Use caution when handling the power module, it may be damaged if dropped from heights in excess of
20 ft.
Battery hazards remain when cells are discharged.
Environmental considerations
As with any battery, local environmental rules and regulations should be consulted for proper
management of spent batteries. If no specific requirements exist, recycling through a qualified recycler is
encouraged. Consult the materials safety data sheet for battery specific information.
Shipping considerations
The unit was shipped to you without the power module installed. Remove the power module prior to
shipping.
Each power module contains two “C” size primary lithium batteries. Primary lithium batteries are
regulated in transportation by the U.S. Department of Transportation, and are also covered by
International Air Transport Association (IATA), International Civil Aviation Organization (ICAO), and
European Ground Transportation of Dangerous Goods (ARD). It is the responsibility of the shipper to
ensure compliance with these or any other local requirements. Consult current regulations and
requirements before shipping.
Operation and Maintenance
37
Reference Manual
Operation and Maintenance
00809-0100-4248, Rev CA
May 2017
5.5
Modbus®, EtherNet/IP™ and OPC mapping
Following is a table of parameters that can be used for Modbus, EtherNet/IP and OPC mapping. These
parameters are used by the Smart Wireless Gateway and can be found in the web interface of the
Gateway. Some of these parameters are analog values and some are discrete, and this is noted in the
description. The Setpoint parameters are used to drive the output channel and for the readback of the
state of the output channel.
Table 5-1. Parameters for Modbus, EtherNet/IP, and OPC Mapping
Parameter name
Description
Read/Write
SUPPLY_VOLTAGE
Maps the supply voltage of the device. For
monitoring the health of your power module use
SUPPLY_VOLTAGE_HEALTHY
Read
ELECTRONICS_TEMPERATURE
Maps the electronics temperature
Read
TOTALIZED_VOLUME
Maps the totalized volume the device has measured
Read
AVERAGE_FLOW_RATE
Maps the instantaneous flow rate over that period
of time set by the DD
Read
ACCUMULATOR_RESET
Use this parameter to reset the number of total
counts on the device
Write
ACCUMULATOR_STATE
What is the current totalized value of the device
Read
Mapping the Rosemount 705 Transmitter parameters
Below is the Gateway screen where the accumulator reset, accumulator state, totalized_volume,
average_flow variables and parameter can be mapped. This is important to understand how to reset the
totalized volume of the device via Modbus, OPC, or EtherNet/IP.
Figure 5-1. Smart Wireless Gateway Modbus Register Map
38
Operation and Maintenance
Reference Manual
Operation and Maintenance
00809-0200-4705, Rev AB
May 2017
To reset the total of the Rosemount 705 Transmitter via Modbus, follow the steps below.
1. Navigate to Modbus connection.
2. Map 705.Accumulaor_Reset.
3. Submit.
To reset the total of the Rosemount 705 Transmitter via OPC, follow the steps below.
1. Navigate to OPC connection.
2. Map 705.Accumulaor_Reset.
3. Submit.
To reset the total of the Rosemount 705 Transmitter via EtherNet/IP, follow the steps below.
1. Navigate to EtherNet/IP connection.
2. Map 705.Accumulaor_Reset.
3. Submit.
5.6
Reset/restore device
The Rosemount 705 Transmitter can be reset remotely over the wireless network, or locally via the wired
maintenance port. Resetting the device will cause the device to temporarily drop offline and rejoin to the
configured wireless network. When resetting the device, you can choose to reset the device with the
same configuration as it already has, or to revert the configuration settings to the original values that
were present when the device left the manufacturer. When reverting the configuration settings to
original values, not the turbine meter K-factor will also be reverted, so the turbine meter should be
verified to ensure the correct K-factor is being used.
Fast Keys
5.7
3, 5, 2
Suspend (pause) the totalization in the device
The Rosemount 705 Transmitter allows the totalization to be stopped, which will hold the current
totalized volume value and ignore any new input pulses. This can be done through a host connection to
the wireless gateway.
5.8
Average flow rate filtering period
The average flow rate filtering period controls how heavily the average flow rate is filtered. The default
setting of one second will cause the Rosemount 705 Transmitter to report the average flow rate over a
time interval of one second. Setting the period to a larger value will reduce noisy flow rate
measurements, but will increase the time constant of the reported value.
Fast Keys
Operation and Maintenance
2, 2, 2, 2, 3
39
Reference Manual
Operation and Maintenance
00809-0100-4248, Rev CA
May 2017
5.9
Low-Flow cut-off
The low flow cutoff value can be configured to cause the Rosemount 705 Transmitter to report zero flow
for any rates below the configured threshold. Totalized volume will be unaffected by the low flow cutoff
setting. The transmitter will continue to totalize any detectable volume - even for very small flow rates.
Fast Keys
5.10
2, 2, 2, 2, 2
Input sensitivity
The input sensitivity setting is used to adjust the minimum input voltage required for the Rosemount
705 Transmitter to count pulses. There are two settings “Normal” and “Reduced”. Under most
circumstances, the “Normal” setting will provide the most accurate flow readings. The “Reduced”
setting should be used in environments where outside interference is causing a degradation of
transmitter performance, such as picking up extra counts/showing a flow rate when the turbine meter is
not rotating. If the “Reduced” setting is selected, care should be taken to verify the device is properly
reporting flow, particularly at low frequencies.
Fast Keys
5.11
2, 2, 2,1, 4
How to reset the totalized volume
The totalized volume can be reset via the wireless network, through the wireless gateway, using a button
located behind the electronics/LCD display side housing cover, or by connecting to the local wired
maintenance port. To avoid any loss of volume accumulation, the totalizer should only be reset when the
flow through the attached turbine meter has been stopped.
Fast Keys
5.12
3, 5, 1, 4
Service support
To expedite the return process outside of the United States, contact the nearest Emerson representative.
Within the United States, call the Emerson Instrument and Valves Response Center using the
1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any
needed information or materials.
The center will ask for the following information:
40

Product model

Serial numbers

The last process material to which the product was exposed
Operation and Maintenance
Reference Manual
00809-0200-4705, Rev AB
Operation and Maintenance
May 2017
The center will provide:

A Return Material Authorization (RMA) number

Instructions and procedures that are necessary to return goods that were exposed tohazardous
substances.
Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed
of and understand the hazard. If the product being returned was exposed to a hazardous substance as
defined by OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous
substance identified must be included with the returned goods.
Operation and Maintenance
41
Operation and Maintenance
May 2017
42
Reference Manual
00809-0100-4248, Rev CA
Operation and Maintenance
Specifications and Reference Data
Reference Manual
May 2017
00809-0200-4705, Rev AB
Appendix A
Specifications and Reference Data
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 43
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 45
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 47
Spare parts and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 48
A.1 Specifications
A.1.1 Functional specifications
Field Communicator connections
Communication terminals
Terminal tabs are permanently fixed to terminal block
Wireless output
IEC 62591 (WirelessHART®) 2.4 GHz DSSS
Radio frequency power output from antenna
External (WK option) antenna: Maximum of 10 mW
(10 dBm) EIRP
Extended Range, External (WM option) antenna: Maximum of 18
mW (12.5 dBm) EIRP
High Gain, Remote (WN option) antenna: Maximum of 40 mW (16
dBm) EIRP
Local display
The optional integral LCD display can display discrete state and
diagnostic information. Display updates at each wireless update or
constantly when the device has the optional LCD display always on
option.
Materials of construction
Enclosure
Housing - Low-copper aluminum, or stainless steel
Paint - Polyurethane
Cover O-ring - Buna-N
Terminal block and power module pack
PBT
Antenna
PBT/PC integrated omni-directional antenna
Conduit entries
/ –14 NPT
1 2
Weight
Humidity limits
Low - copper aluminum
0–99 percent relative humidity
User selectable, one second to 60 minutes.
Rosemount™ 705 Wireless Totalizing Transmitter without LCD
display - 4.6 lb (2.0 kg)
Rosemount 705 Transmitter with M5 LCD display 4.7 lb (2.1 kg)
A.1.2 Physical specifications
Stainless steel
Wireless update rate
Electrical connections
Wireless power module
Replaceable, Intrinsically Safe Lithium-Thionyl Chloride power
module with PBT polymer enclosure. Ten year life at one
minute update rate.(1)
Rosemount 705 Transmitter without LCD display 8.0 lb (3.6 kg)
Rosemount 705 Transmitter with M5 LCD display 8.1 lb (3.7 kg)
Enclosure ratings (705)
NEMA 4X, and IP66/67
Note
Continuous exposure to ambient temperature limits (–40 °F
or 185 °F) (–40 °C or 85 °C) may reduce specified power
module life by less than 20 percent.
1.
Mounting
Transmitters may be attached directly to switch, brackets also
permit remote mounting. See “Dimensional drawings” on
page 45.
Reference conditions are 70 °F (21 °C), and routing data for three
additional network devices.
Specifications and Reference Data
43
Specifications and Reference Data
Reference Manual
May 2017
00809-0200-4705, Rev AB
A.1.3 Frequency input specifications
Temperature limits
Operating limit Storage limit
0 to 10 kHz
Description
A.1.4 Performance specifications
Without LCD display
–40 to 185 °F
–40 to 85 °C
–40 to 185 °F
–40 to 85 °C
With LCD display
–4 to 175 °F
–20 to 80 °C
–40 to 185 °F
–40 to 85 °C
Electromagnetic Compatibility (EMC)
All models
Meets all industrial environment requirements of EN61326 and
NAMUR NE-21. Maximum deviation <1% span during EMC
disturbance.(1)
Vibration effect
Wireless output unaffected when tested per the requirements of
IEC60770-1 field or pipeline with high vibration level (10–60 Hz
0.21mm displacement peak amplitude/60-2000 Hz 3g).
Wireless output unaffected when tested per the requirements of
IEC60770-1 field with general application or pipeline with low
vibration level(10–60 Hz 0.15 mm displacement peak
amplitude/60–500 Hz 2 g).
1.
44
During surge event device may exceed maximum EMC deviation limit or reset;
however, device will self-recover and return to normal operation with specified
start-up time.
Specifications and Reference Data
Specifications and Reference Data
Reference Manual
May 2017
00809-0200-4705, Rev AB
A.2 Dimensional drawings
Figure A-1. Rosemount 705 Transmitter
Shown with 2.4 GHz/WirelessHART extended range antenna
A
11.16 [284]
7.81 [198]
2.49 [63]
4.20 [107]
1.50 [38]
D
C
B
Shown with optional digital display
and 2.4 GHz/WirelessHART Antenna
Shown without optional digital display
6.05 [154]
7.88 [200]
E
A. 2.4 GHz/WirelessHART extended range antenna
B. 1-in. NPT connection to flow meter
C. Ground screw assembly
Dimensions are in inches (millimeters).
Specifications and Reference Data
0.42 [11]
F
D. Possible antenna rotation
E. Digital display cover
F. Transmitter electronics
45
Specifications and Reference Data
Reference Manual
May 2017
00809-0200-4705, Rev AB
Figure A-2. Rosemount 705 Transmitter Mounting Configurations with Optional Pipe Mounting Bracket
A
B
1.03 [26]
4.03 [102]
C
1.38[35]
D
A. 2-in. U-bolt for pipe mounting
B. Ground screw assembly
C.1-in. NPT connection to flow meter
D. Turbine meter connection
Dimensions are in inches (millimeters).
46
Specifications and Reference Data
Specifications and Reference Data
May 2017
Reference Manual
00809-0200-4705, Rev AB
A.3 Ordering information
Table A-1. Rosemount 705 Wireless Totalizing Transmitter Ordering Information
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
The Expanded offering is subject to additional delivery lead time.
Product description
705
Totalizing Transmitter (with connector mil-c-5015)
★
Transmitter output
X
Wireless
★
Transmitter type
D1
Direct mount
★
R1
Remote mount (10 ft. leads included)
★
D
Dual compartment housing - aluminum
★
E
Dual compartment housing - SST
★
Housing
Conduit threads
1
/ –14 NPT
1 2
★
Certifications
NA
No Hazardous Location Approval
I5
U.S.A Intrinsically Safe
★
I6
Canada Intrinsically Safe
★
N5
U.S.A. Division 2, Non-incendive
★
N6
Canada Division 2, Non-incendive
★
I1
ATEX Intrinsic Safety
★
IU
ATEX Intrinsic Safety for Zone 2
★
I7
IECEx Intrinsic Safety
★
IY
IECEx Intrinsic Safety for Zone 2
★
Wireless options
Wireless update rate, operating frequency and protocol
WA3
User configurable update rate, 2.4 GHz DSSS, IEC 62591 (WirelessHART)
★
Omni directional wireless antenna and SmartPower solutions(1)
WK1
External antenna, adapter for black power module (I.S. power module sold separately)
★
WM1
Extended range, external antenna, adapter for black power module (I.S. power module sold separately)
★
WJ1
Remote antenna, adapter for black power module (I.S.power module sold separately)
WN1(2)
High-gain, remote antenna, adapter for black power module (I.S. power module sold separately)
Other options
Display
M5
LCD display
Specifications and Reference Data
★
47
Specifications and Reference Data
Reference Manual
May 2017
00809-0200-4705, Rev AB
Table A-1. Rosemount 705 Wireless Totalizing Transmitter Ordering Information
★ The Standard offering represents the most common options. The starred options (★) should be selected for best delivery.
The Expanded offering is subject to additional delivery lead time.
Mounting bracket
B4
★
Universal L mounting bracket for 2-in. pipe mounting - SST bracket and bolts
Configuration
Calibration Factor (k-factor) Configuration. Factory configure date, descriptor, message fields, and wireless
parameters
C1
★
Typical model number: 705 X D1 D 1 I6 WA3 M5 B4 C1
1.
2.
Black Power Module must be shipped separately, order model 701PBKKF or part number: 00753-9220-000.
Limited availability, consult factory for details.
Spare parts and accessories
Spare parts and accessories
00705-9000-0001
Cable assembly, 1 ft. long for direct mount option
00705-9000-0002
Cable Assembly, 10 ft. long for remote mount option
03151-9270-0003
Remote housing bracket kit
701PBKKF
Black power module
48
Specifications and Reference Data
Product Certifications
Reference Manual
May 2017
00809-0200-4705, Rev AB
Appendix B
Product Certifications
Rev 1.1
European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
Telecommunication Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
FCC and IC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
Ordinary Location Certification from CSA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
Installing in North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
USA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 49
Canada . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 50
Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 50
International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 50
Brazil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 51
EAC - Belarus, Kazakhstan, Russia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 51
Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 52
B.1 European Directive Information
B.5 Installing in North America
A copy of the EC Declaration of Conformity can be found at the end
of the Quick Start Guide. The most recent revision of the EC
Declaration of Conformity can be found at
Emerson.com/Rosemount.
The US National Electrical Code® (NEC) and the Canadian Electrical
Code (CEC) permit the use of Division marked equipment in Zones
and Zone marked equipment in Divisions. The markings must be
suitable for the area classification, gas, and temperature class. This
information is clearly defined in the respective codes.
B.2 Telecommunication Compliance
All wireless devices require certification to ensure that they adhere
to regulations regarding the use of the RF spectrum. Nearly every
country requires this type of product certification. Emerson™ is
working with governmental agencies around the world to supply
fully compliant products and remove the risk of violating country
directives or laws governing wireless device usage.
B.3 FCC and IC
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following conditions: This device may not cause
harmful interference. This device must accept any interference
received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum
antenna separation distance of 20 cm from all persons.
B.4 Ordinary Location Certification
from CSA
The transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire
protection requirements by CSA, a nationally recognized test
laboratory (NRTL) as accredited by the Federal Occupational Safety
and Health Administration (OSHA).
Product Certifications
B.6 USA
I5
U.S.A. Intrinsically Safe (IS)
Certificate: CSA 70011131
Standards: FM 3600 – 2011, FM 3610 – 2010,
UL Standard 50 – Eleventh Edition,
UL 61010-1 – 3rd Edition,
ANSI/ISA-60079-0 (12.00.01) – 2013,
ANSI/ISA-60079-11 (12.02.01) – 2013,
ANSI/IEC 60529 – 2004
Markings: IS CL I, DIV 1, GP A, B, C, D T4; Class 1, Zone 0, AEx
ia IIC T4 Ga; T4 (-50 °C ≤ Ta ≤ +70 °C) when
installed per Rosemount™ drawing 00705-1020;
Type 4X; IP66
See the table at the end of this section for entity parameters
N5 U.S.A. Division 2, Nonincendive
Certificate: CSA 70011131
Standards: FM 3600 – 2011, FM 3611 – 2004,
UL Standard 50 – Eleventh Edition,
UL 61010-1 (3rd Edition),
ANSI/IEC 60529 – 2004
Markings: NI CL I, DIV 2, GP A, B, C, D T4;
T4 (-50 °C ≤ Ta ≤ +70 °C); Type 4X; IP66
49
Product Certifications
Reference Manual
May 2017
00809-0200-4705, Rev AB
Special Conditions for Safe Use (X):
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1GΩ. To
avoid electrostatic charge build-up, it must not be rubbed or
cleaned with solvents or a dry cloth.
1. For use only with the Model 701P or Rosemount P/N
753-9220-XXXX Smart Power Battery Module.
2. The surface resistivity of the antenna is greater than 1GΩ. To
avoid electrostatic charge build-up, it must not be rubbed or
cleaned with solvents or a dry cloth.
B.7 Canada
I6
Canada Intrinsically Safe (IS)
Certificate: CSA 70011131
Standards: CAN/CSA C22.2 No. 0-10,
CAN/CSA C22.2 No. 94-M91,
CSA Std C22.2 No.142-M1987,
CAN/CSA-60079-0 - 2011,
CAN/CSA-60079-11 - 2014,
CSA Std C22.2 No. 60529 - 2005,
CAN/CSA-C22.2 No. 61010-1 - 2012
Markings: IS CL I, DIV 1, GP A, B, C, D T4;
Ex ia IIC T4 Ga, T4; T4 (–50 °C ≤ Ta ≤ +70 °C)
when installed per Rosemount drawing
00705-1020; Type 4X; IP66
See the table at the end of this section for entity parameters.
2. The Rosemount 705 Transmitter enclosure may be made of
aluminum alloy and given a protective polyurethane paint
finish; however, care should be taken to protect it from
impact or abrasion if located in a Zone 0 area.
IU
For use with Rosemount SmartPower Power Module part
number 753-9220-0001, or for use with Emerson
SmartPower option 701PBKKF.
See the table at the end of this section for entity parameters.
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than 1GΩ. To
avoid electrostatic charge build-up, it must not be rubbed or
cleaned with solvents or a dry cloth.
2. The Model 701PBKKF Power Module may be replaced in a
hazardous area. The Power Modules have a surface resistivity
greater than 1GΩ and must be properly installed I the
wireless device enclosure. Care must be taken during
transportation to and from the point of installation to
prevent electrostatic charge build-up.
N6 Canada Division 2, Nonincendive
Certificate: CSA 70011131
Standards: CAN/CSA C22.2 No. 0-10,
CAN/CSA C22.2 No. 94-M91,
CSA Std C22.2 No. 213-M1987 (R2013),
CAN/CSA-60079-0 - 2011,
CAN/CSA Std C22.2 No. 60529 - 2005,
CAN/CSA-C22.2 No. 61010-1 - 2012
Markings: Suitable for Class 1, Division 2,
Groups A, B, C, D T4; T4 (–50 °C ≤ Ta ≤ +70 °C);
Type 4X; IP66
Special Conditions for Safe Use (X):
1. For use only with the Model 701P or Rosemount P/N
753-9220-XXXX Smart Power Battery Module.
2. The surface resistivity of the antenna is greater than 1GΩ. To
avoid electrostatic charge build-up, it must not be rubbed or
cleaned with solvents or a dry cloth.
B.8 Europe
I1
ATEX Intrinsic Safety
Certificate: Baseefa14ATEX0375X
Standards: EN 60079-0: 2012, EN 60079-11: 2012
Markings:
II 1 G Ex ia IIC T4 Ga, T4(–60 °C ≤ Ta ≤ +70 °C)
For use with Rosemount SmartPower™ power module part
number 753-9220-0001, or for use with Emerson
SmartPower option 701PBKKF.
See the table at the end of this section for entity parameters.
50
ATEX Intrinsic Safety for Zone 2
Certificate: Baseefa14ATEX0375X
Standards: EN 60079-0: 2012, EN 60079-11: 2012
Markings:
II 3 G Ex ic IIC T4 Gc, T4(–60 °C ≤ Ta ≤
+70 °C)
3. The Rosemount 705 Transmitter enclosure may be made of
aluminum alloy and given a protective polyurethane paint
finish; however, care should be taken to protect it from
impact or abrasion if located in a Zone 0 area.
B.9 International
I7
IECEx Intrinsic Safety
Certificate: IECEx BAS 14.0173X
Standards: IEC 60079-0: 2011, IEC 60079-11: 2011
Markings: Ex ia IIC T4 Ga, T4 (-60 °C ≤ Ta ≤ +70 °C)
For use with Rosemount SmartPower power module part
number 753-9220-0001, or for use with Emerson
SmartPower option 701PBKKF.
See the table at the end of this section for entity parameters.
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than
1 GΩ. To avoid electrostatic charge build-up, it must not be
rubbed or cleaned with solvents or a dry cloth.
2. The Rosemount 705 Transmitter enclosure may be made of
aluminum alloy and given a protective polyurethane paint
finish; however, care should be taken to protect it from
impact or abrasion if located in a Zone 0 area.
Product Certifications
Product Certifications
Reference Manual
May 2017
IY
IECEx Intrinsic Safety for Zone 2
Certificate: IECEx BAS 14.0173X
Standards: IEC 60079-0: 2011, IEC 60079-11: 2011
Markings: Ex ic IIC T4 Gc, T4 (-60 °C ≤ Ta ≤ +70 °C)
For use with Rosemount SmartPower power module part
number 753-9220-0001, or for use with Emerson
SmartPower option 701PBKKF.
See the table at the end of this section for entity parameters
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than
1 GΩ. To avoid electrostatic charge build-up, it must not be
rubbed or cleaned with solvents or a dry cloth.
2. The Rosemount 705 Transmitter enclosure may be made of
aluminum alloy and given a protective polyurethane paint
finish; however, care should be taken to protect it from
impact or abrasion if located in a Zone 0 area.
B.10 Brazil
I2
00809-0200-4705, Rev AB
B.11 EAC - Belarus, Kazakhstan, Russia
IM
Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate: TC RU C-US.MIO62.B.03122
Markings: 0Ex ia IIC T4 Ga X, T4 (–60 °C ≤ Ta ≤ +70 °C)
See the table at the end of this section for entity para.meters
Special Conditions for Safe Use (X):
1. See certificate for special conditions.
Turbine meter terminal
output parameters
Turbine meter terminal
input parameters
Voc/Uo = 2.5 V
Vmax/Ui = 10 V
Isc/Io = 253 μA
Imax/Ii = 1 mA
Pmax/Po = 640 μW
Pmax/Pi = 1 mW
Ca/Co = 2.9 μF
Ci = 2.2 nF
La/Lo= 500 mH
Li = 4.7 mH
INMETRO Intrinsic Safety
Certificate: UL-BR 17.0019X
Standards: ABNT NBR IEC 60079-0:2008 + Errata 1:2011,
ABNT NBR IEC 60079-11:2009
Markings: Ex ia IIC T4 Ga, T4 (–60 °C ≤ Ta ≤ +70 °C)
See the table at the end of this section for entity parameters
Special Condition for Safe Use (X):
1. See certificate for special conditions.
Product Certifications
51
Reference Manual
00809-0200-4705, Rev AB
Product Certifications
May 2017
B.12 Installation drawings
Figure B-1. Rosemount 705 Wireless Totalizing Transmitter
52
Product Certifications
Product Certifications
May 2017
Product Certifications
Reference Manual
00809-0200-4705, Rev AB
53
Reference Manual
00809-0200-4705, Rev AB
54
Product Certifications
May 2017
Product Certifications
High Gain Remote Antenna Option
May 2017
Reference Manual
00809-0200-4705, Rev AB
Appendix C
High Gain Remote Antenna Option
Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 55
Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 56
Installation considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57
Transient/lightning considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 57
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 58
Installing the high gain remote antenna . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 59
C.1
Safety messages
Procedures and instructions in this section may require special precautions to ensure the safety of the
personnel performing the operations. Information that raises potential safety issues is indicated by a
warning symbol ( ). Refer to the following safety messages before performing an operation preceded
by this symbol.
When installing remote mount antennas for the wireless field device, always use established safety
procedures to avoid falling or contact with high-power electrical lines.
Install remote antenna components for the wireless field device in compliance with local and national
electrical codes and use best practices for lightning protection.
Before installing consult with the local area electrical inspector, electrical officer, and work area
supervisor.
The wireless field device remote antenna option is specifically engineered to provide installation
flexibility while optimizing wireless performance and local spectrum approvals. To maintain wireless
performance and avoid non-compliance with spectrum regulations, do not change the length of cable
or the antenna type.
If the supplied remote mount antenna kit is not installed per these instructions, Emerson™ is not
responsible for wireless performance or non-compliance with spectrum regulations.
Be aware of overhead electrical power lines.
High Gain Remote Antenna Option
55
Reference Manual
High Gain Remote Antenna Option
00809-0200-4705, Rev AB
C.2
Functional specifications
C.2.1
Output
May 2017
WirelessHART® 2.4 GHz DSSs (direct sequence spread spectrum)
Radio Frequency Power Output from Antenna:
C.2.2

High gain remote (WN option) antenna:
Maximum of 40 mW (16 dBm) EIRP (Equivalent Isotropically Radiated Power)

High gain remote antenna (WJ1 option):
Maximum of 40 mW (16 dBm) EIRP 25 ft. of cable.
Coaxial length
25 ft. (7.6 m) with Type N Connections
C.2.3
C.2.4
C.2.5
Coaxial material

Heavy duty, low loss LMR400 cable

Minimum coaxial bend diameter: 1.0 ft. (0.3 m)
Antenna

Remote mount omni directional antenna

Fiberglass and aluminum construction

8 Db Gain WJ1 - 6dBi

Meets MIL-STD-810G (Method 510.5, Procedure I and II)
Physical specifications
Weight: 1.0 lb. (0.4 kg)
C.2.6
RF lightning arrestor
In-line lightning arrestor
Electrical connection: Lightning arrestor MUST be grounded per local electrical codes and regulations.
Mounting bracket
C.2.7

Horizontal or vertical mast accommodation

Supported mast diameter: 1.0 to 2.5-in. (2.5 to 6.4 cm)

Aluminum bracket

Nickel/zinc plated mounting U-bolts
Ratings
NEMA® 4X, and IP66/67
C.2.8
Vibration
3 g Max vibration
56
High Gain Remote Antenna Option
High Gain Remote Antenna Option
May 2017
Reference Manual
00809-0200-4705, Rev AB
C.3
Installation considerations
C.3.1
Antenna mounting
Mount antenna vertically (±5°)
C.3.2
Antenna height
Mount antenna 14 ft. (4.3 m) above infrastructure with clear line of sight.
C.3.3
Coaxial cable
Ensure that coaxial cable is securely affixed to the mast to avoid excessive cable movement.
C.3.4
Installing coaxial drip loop
Ensure a drip loop is installed not closer than 1.0 ft. (0.3 m) from the transmitter. It may also be
convenient to affix the drip loop to the lower portion of the mast ensuring condensation or rainwater will
flow away from the coaxial connections.
Figure C-1. Drip Loop Location
A
A. Coaxial drip loop
C.3.5
Applying coaxial sealant moisture protection
Utilize the coaxial sealant that is included in the high gain remote mounting kit package. Follow included
instructions for application on the coaxial connection.
C.4
Transient/lightning considerations
C.4.1
Gateway transient protection
When installing, consider including transient/lightning protection on interface connections (Ethernet,
Modbus®, and coaxial connections) to other equipment.
C.4.2
RF lightning arrestor ground connection
Ensure grounding connection is made on the RF lightning arrestor ground connection point.
High Gain Remote Antenna Option
57
Reference Manual
High Gain Remote Antenna Option
00809-0200-4705, Rev AB
C.5
May 2017
Dimensional drawings
Figure C-2. Device Connection and RF Lightning Arrestor
.53
n
[X] 2.75
4 PLS
`
A
n
n
E
D
C
B
A. Antenna
B. Min drip loop ∅ 12-in. (0.3 m)
C. 25 ft. (7.6 m) Cable
58
D. Lightning arrestor
E. Mounting bracket
High Gain Remote Antenna Option
High Gain Remote Antenna Option
May 2017
C.6
Reference Manual
00809-0200-4705, Rev AB
Installing the high gain remote antenna
1. Mount the transmitter following best practice mounting procedures as outlined in the Quick
Installation Guide and this manual.
2. Connect the RF Lightning protector to the device and tighten.
A
A. RF lightning protector
3. Connect antenna to mounting bracket and tighten nut carefully.
High Gain Remote Antenna Option
59
Reference Manual
00809-0200-4705, Rev AB
High Gain Remote Antenna Option
May 2017
4. Unwind coaxial cable and connect the cable to both the antenna and the lightning protector
connected to the transmitter, leaving one loop minimum for a drip loop. Ensure the drip loop is lower
than the device, allowing water to flow away from the device.
5. Apply the coaxial sealant around each of the coaxial connections and at the lightning arrestor, making
sure the RF connections are completely sealed.
60
High Gain Remote Antenna Option
High Gain Remote Antenna Option
May 2017
Reference Manual
00809-0200-4705, Rev AB
6. Attach U-bolts to mounting bracket in correct orientation ensuring antenna will be positioned in a
vertical position.
7. Tighten U-bolts to mast and ensure antenna is pointed in a vertical direction.
High Gain Remote Antenna Option
61
Reference Manual
00809-0200-4705, Rev AB
62
High Gain Remote Antenna Option
May 2017
High Gain Remote Antenna Option
Mapping of Alert Messages in the HART®
Command 48 Additional Status
Reference Manual
00809-0200-4705, Rev AB
May 2017
Appendix D
Mapping of Alert Messages in the
HART® Command 48 Additional
Status
This appendix outlines the most important alerts in the HART command 48 Additional Status Field for
the Rosemount™ 705 Wireless Totalizing Transmitter. The information in this section can be used by
DeltaV™ for alert monitoring, and in the Smart Wireless Gateway for Additional Status mapping in
Modbus®, OPC, etc.
A complete list of Additional Status bits is available in the Smart Wireless Gateway.
Table D-1 to Table D-2 displays the device variable and variable mapping indexes for the Rosemount 705
Transmitter.
Table D-3 to Table D-5 shows a list of the most important alert messages that may be displayed in the
AMS™ Device Manager and Field Communication together with the location of the Alert in the HART
command 48 Additional Status field.
To view Active Alerts, from the Home screen, go to Service Tools>Active Alerts.
Table D-1. Device Variable Index
Device variable
Index
0
Supply voltage
1
Electronics temperature
2
Totalized volume
3
Average flow rate
Table D-2. Default Variable Mapping Index (can be modified)
Variables
Index
PV
Totalized volume
SV
Average flow rate
TV
Electronics temperature
QV
Supply voltage
Table D-3. Failure Alerts (F:)
Message
Additional status(1)
Description
Electronics Failure
Byte 8 :: Bit 6
A failure has been detected in the device memory
and/or electronics
Configuration Error
Byte 2 :: Bit 6
The device has detected a configuration error based
on a change to the device
Radio Failure
Byte 1 :: Bit 6
The wireless radio has detected a failure or stopped
communicating
Supply Voltage Failure
Byte 6 :: Bit 2
The supply voltage is too low for the device to
broadcast
1.
Location of the Alert in the HART command 48 Status field.
Mapping of Alert Messages in the HART® Command 48 Additional Status
63
Mapping of Alert Messages in the HART®
Command 48 Additional Status
Reference Manual
00809-0200-4705, Rev AB
May 2017
Table D-4. Maintenance Alerts (M:)
Message
Additional status(1)
Description
Totalized Volume Rollover
Byte 3 :: Bit 2
The totalized volume has exceeded the maximum
value and automatically reset to zero
Average Flow Rate Saturated
Byte 3 :: Bit 0
The average flow rate is beyond the operating
limits of the device and the reported value is
saturated
Electronics Temperature
Beyond Limits
Byte 8 :: Bit 5
The terminal temperature has exceeded the
transmitter’s maximum range
Supply Voltage Low
Byte 8 :: Bit 4
The supply voltage is low and may soon affect
broadcast updates
1.
Location of the Alert in the HART command 48 Status field.
Table D-5. Advisory Alerts (A:)
Message
Additional status(1)
Description
Database Memory Warning
Byte 0 :: Bit 2
The device has failed to write to the
database memory. Any data written
during this time may have been lost
Totalized Volume Warning
Byte 3 :: Bit 1
The totalized volume has exceeded the
warning threshold value
Totalized Volume Stopped
Byte 3 :: Bit 5
The totalized volume accumulation has
been suspended by user
Sensor Input Life Alert
Byte 3 :: Bit 3
The lifetime pulse count value has
exceeded the configured warning
threshold
HI HI Volume Alert
Byte 5 :: Bit 4
A process value has surpassed the user
defined limit
HI Volume Alert
Byte 5 :: Bit 5
A process value has surpassed the user
defined limit
LO Volume Alert
Byte 5 :: Bit 6
A process value has surpassed the user
defined limit
LO LO Volume Alert
Byte 5 :: Bit 7
A process value has surpassed the user
defined limit
HI HI Flow Alert
Byte 5 :: Bit 0
A process value has surpassed the user
defined limit
HI Flow Alert
Byte 5 :: Bit 1
A process value has surpassed the user
defined limit
LO Flow Alert
Byte 5 :: Bit 2
A process value has surpassed the user
defined limit
LO LO Flow Alert
Byte 5 :: Bit 3
A process value has surpassed the user
defined limit
Button Stuck
Byte 1 :: Bit 5
A button on the Electronics Board is
detected as stuck in the active position
Non-Critical User Data Warning
Byte 2 :: Bit 1
A user written parameter does not match
expected value
Simulation Active
Byte 8 :: Bit 0
The device is in simulation mode and
may not be reporting actual information
1.
64
Location of the Alert in the HART command 48 Status field.
Mapping of Alert Messages in the HART® Command 48 Additional Status
Reference Manual
00813-0100-4021, Rev RB
May 2017
Global Headquarters
Emerson Automation Solutions
6021 Innovation Blvd.
Shakopee, MN 55379, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
RFQ.RMD-RCC@Emerson.com
North America Regional Office
Emerson Automation Solutions
8200 Market Blvd.
Chanhassen, MN 55317, USA
+1 800 999 9307 or +1 952 906 8888
+1 952 949 7001
RMT-NA.RCCRFQ@Emerson.com
Latin America Regional Office
Emerson Automation Solutions
1300 Concord Terrace, Suite 400
Sunrise, FL 33323, USA
+1 954 846 5030
+1 954 846 5121
RFQ.RMD-RCC@Emerson.com
Europe Regional Office
Emerson Automation Solutions Europe GmbH
Neuhofstrasse 19a P.O. Box 1046
CH 6340 Baar
Switzerland
+41 (0) 41 768 6111
+41 (0) 41 768 6300
RFQ.RMD-RCC@Emerson.com
Linkedin.com/company/Emerson-Automation-Solutions
Twitter.com/Rosemount_News
Facebook.com/Rosemount
Asia Pacific Regional Office
Emerson Automation Solutions Asia Pacific Pte Ltd
1 Pandan Crescent
Singapore 128461
+65 6777 8211
+65 6777 0947
Enquiries@AP.Emerson.com
Middle East and Africa Regional Office
Emerson Automation Solutions
Emerson FZE P.O. Box 17033
Jebel Ali Free Zone - South 2
Dubai, United Arab Emirates
+971 4 8118100
+971 4 8865465
RFQ.RMTMEA@Emerson.com
Youtube.com/user/RosemountMeasurement
Google.com/+RosemountMeasurement
Standard Terms and Conditions of Sale can be found on the Terms and Conditions of
Sale page.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
SmartPower, DeltaV, AMS, Rosemount, and Rosemount logotype are trademarks of
Emerson.
HART and WirelessHART are registered trademarks of the FieldComm Group.
Swagelok is a registered trademark of Swagelok Company.
EtherNet/IP is a trademark of ControlNet International under license by ODVA.
Modbus is registered trademark of Gould Inc.
National Electrical Code is a registered trademark of National Fire Protection
Association, Inc.
All other marks are the property of their respective owners.
© 2017 Emerson. All rights reserved.